DURING THIS COURSE WE WILL TRY TO COVER THE FOLLOWING TOPICS: GENERAL OVERVIEW OF DELTA-V SYSTEM HARDWARE INSTALLATION SOFTWARE CONFIGURATION OPERATOR BASICS AND GRAPHICS CONFIGURATION SYSTEM ADMINISTRATION & MAINTENANCE DATABASE ADMINISTRATOR

GENERAL OVERVIEW

THE DELTA-V SYSTEMDELTA-V SYSTEM CONSISTS OF THE FOLLOWING COMPONENTS: I/O SUBSYSTEM CONTROLLER POWER SUPPLIES WORKSTATION CONTROL NETWORK

SYSTEM ARCHITECTURE

SYSTEM ARCHITECTURE (MULTIPLE NODES)

SYSTEM ARCHITECTURE (MULTIPLE NODES)THE ABOVE FIGURE ILLUSTRATES A DELTA-V CONTROL NETWORK WITH EIGHT NODES MAXIMUMS: 120 --- NODES 100 --- CONTROLLERS / SIMPLEX OR REDUNDANT PAIRS 60 --- WORKSTATIONS

I/O SUBSYSTEM (CARRIER SPECIFICATIONS)DELTA-V SYSTEM CONTAINS FOLLOWING TYPES OF CARRIERS: HORIZONTAL CARRIER 2-Wide Horizontal Power/Controller Carrier 2-Wide Horizontal Power Carrier 8-Wide Horizontal I/O Interface Carrier 1-Wide Horizontal Carrier Extenders and VERTICALPLUS CARRIERS 4-Wide VerticalPLUS Power/Controller Carrier 4-Wide VerticalPLUS Power Carrier 8-Wide VerticalPLUS I/O Interface Carriers 1-Wide VerticalPLUS Carrier Extenders

I/O SUBSYSTEM (I/O CARDS)A VARIETY OF I/O CARDS ARE AVAILABLE IN SERIES 2 e.g. AI, 8-CHANNEL, 4-20 MA (SERIES 2 SIMPLEX) AI, 4-20 MA, HART (SERIES 2 SIMPLEX AND REDUNDANT; 2 AND 4 WIRE) AI, 16, CHANNEL, 4-20 MA, HART (SERIES 2 SIMPLEX) AO, 8-CHANNEL, 4-20 MA, HART (SERIES 2 SIMPLEX AND REDUNDANT) DI, 8-CHANNEL, 24 VDC, DRY CONTACT (SERIES 2 SIMPLEX AND REDUNDANT) DI, 8-CHANNEL, 24 VDC, ISOLATED (SERIES 2 SIMPLEX)

I/O SUBSYSTEM (MASS TERMINATION BLOCKS)THE DELTA-V SYSTEM CAN USE FOLLOWING TYPES OF MASS TERMINATION BLOCKS: 10-Pin Mass Termination Block 16-Pin Mass Termination Block 24-Pin Mass Termination Block 40-Pin Mass Termination Block

I/O SUBSYSTEM (I/O INTERFACE KEYING)THERE ARE TWO KEYS ON I/O CARD & TWO KEYS ON THE I/O TERMINAL BLOCK

THE KEYS ON THE I/O CARD ARE SET AT THE FACTORY, BUT KEYS ON THE I/O TERMINAL BLOCK CAN BE CHANGED

CONTROLLER SPECIFICATIONSITEMPower requirement (supplied by system power supply through 2widepower/controller carrier)Fuse protection Power dissipation Mounting

MD/MD PLUS+5 VDC at 1.4 A maximum3.0 A, non-replaceable fuses 5.0 W typical 7.0 W maximum On right slot of power/controller Carrier

MX+5 VDC at 1.4 A maximum3.0 A, nonreplaceable fuses 5.0 W typical 7.0 W maximum On right slot of power/controller carrier

SYSTEM POWER SUPPLY SPECIFICATIONSIN DELTA-V SYSTEM THERE ARE FOLLOWING THREE POWER SUPPLIES: SYSTEM POWER SUPPLY (AC/DC) SYSTEM POWER SUPPLY (DUAL DC/DC) INTRINSICALLY SAFE SYSTEM POWER SUPPLY

WORKSTATIONEMERSON HAVE CLASSIFIED DIFFERENT WORKSTATIONS IN TERMS OF THEIR FUNCTIONALITY: PROFESSIONAL PLUS PROFESSIONAL PLUS AS REMOTE CLIENT SERVER LOCAL PROFESSIONAL OPERATOR BASE MAINTENANCE OPERATOR STATION AS REMOTE CLIENT SERVER LOCAL APPLICATION STATION REMOTE PROFESSIONAL OPERATOR BASE REMOTE APPLIOCATION STATION (SATELLITE CONNECTION ONLY) SIMULATE FOR STAND ALONE WORKSTATION

CONTROL NETWORK THE CONTROL NETWORK IS AN ISOLATED ETHERNET LOCAL AREA NETWORK (LAN) THAT PROVIDES COMMUNICATION BETWEEN THE CONTROLLERS AND WORKSTATIONS THE CONTROL NETWORK IS DEDICATED TO THE DELTA-V SYSTEM. A SEPARATE ETHERNET INTERFACE IS PROVIDED VIA THE DELTA-V PROFESSIONAL PLUS AND APPLICATION STATION TO CONNECT THE DELTA-V SYSTEM TO A PLANTWIDE LAN

SYSTEM CAPACITYSYSTEM SIZING 30,000 DSTS UNLIMITED SCADA TAGS 15,000 ADVANCED UNIT MANAGEMENT DSTS 1 MAX. PROFESSIONAL PLUS STATION 10 MAX. PROFESSIONAL STATIONS 10 MAX. APPLICATION STATIONS 59 MAX. OPERATOR STATIONS 60 MAX. WORKSTATIONS OF ANY KIND 5 MAX. REMOTE DATA SERVERS 100 MAX. SIMPLEX CONTROLLERS

SYSTEM CAPACITY (CONT.)SYSTEM SIZING 100 MAX. REDUNDANT CONTROLLERS 120 MAX. NODES EXCLUDING REDUNDANT NODES 42 MAX. REMOTE WORKSTATIONS 250 MAX PLANT AREAS (INCLUDING REMOTE ZONE AREAS) 255 MODULES PER UNIT 250 ALARM TYPES (CAN BE ADDED IF DESIRED) 200 DELTA-V USER ACCOUNTS

DEVICE SIGNAL TAG (DST) LICENSINGDST licensing is based on the number of inputs and outputs as follows: Analog Output Analog Input Discrete Output Discrete Input Generally speaking each instrument wired into a set of screw terminals will require 1 DST. When identifying the required DST licensing start with the P&ID and count the number and type of instruments.

PROFESSIONAL PLUS SYSTEM SOFTWARE

PROFESSIONAL STATION SOFTWARE

MAINTENANCE STATION SOFTWARE

OPERATOR STATION SOFTWARE

BASE STATION SOFTWARE

APPLICATION STATION SOFTWARE

DELTA-V SIMULATE SUITEDelta-V Simulate lets you use all Delta-V software for training and development without purchasing duplicate system hardware. Allows you to configure the Delta-V software suite on a single PC or in a multi-node system. Allows you to test and execute your system configuration and OPC interfaces, execute batch and continuous control Allows you to easily coordinate and initialize control simulation and set control execution to be faster or slower than real time.

ASSET MANAGEMENT SOLUTION (AMS)The Delta-V / Asset Management Solution (AMS) provide the capability to configure, calibrate, monitor and troubleshoot intelligent field devices. The system provides the following capability: Complete capturing of all current device data Comparison/reconciliation Device alert monitoring Device template creation Device signal tag and device tag search capability Conventional I/O, HART and Fieldbus-based support On-line help Diagnostic add-on capability

ALARMS & EVENTSTHERE ARE FOUR ALARMS PRIORITIES AVAILABLE IN DELTA-V BUT NEW ALARM PRIORITY CAN BE ADDED. CRITICAL WARNING ADVISORY LOG

NOTE: ALARMS WITH LOG PRIORITY WILL GENERATE AN EVENT IN THE EVENT SUMMARY RATHER THAN ALARM.

HARDWARE INSTALLATION

BUSSED FIELD POWER CONNECTOR DELTA-V I/O CARRIER IS INSTALLED ON TYPE T-DIN RAIL USING THE LATCHING SWITCH ON 2-WIDE POWER / CONTROLLER CARRIER 4 TERMINALS ARE PROVIDED FOR INPUT POWER i.e. FOR 12VDC & 24VDC ON EACH 8-WIDE I/O CARRIER TWO BUSSED FIELD POWER CONNECTORS ARE PROVIDED FOR POWERING THE FIELD DEVICES

BEVELED KEYS BEVELED KEYS ARE SUPPLIED WITH THE TWO-PART CONNECTOR ON THE HORIZONTAL AND VERTICAL CARRIER TO PREVENT DAMAGE TO THE CARDS

BEVELED KEYS (CONT.) YOU CAN SETUP ANY STANDARD FOR THE KEYING SCHEME. A SAMPLE KEYING SCHEME IS SHOWN BELOW

DIN RAIL SPACINGSUGGESTED SPACING FOR DIN RAIL INSTALLATION ON MOUNTING SURFACE IS AS FOLLOWS: AN AREA 1.3 CM (0.5 IN.) WIDE, CENTERED 4.5 CM (1.75 IN.) FROM THE LEFT SIDE OF A 2 WIDE POWER/CONTROLLER CARRIER AN AREA 1.3 CM (0.5 IN.) WIDE, CENTERED 8.3 CM (3.25 IN.) FROM EITHER SIDE OF AN 8-WIDE I/O INTERFACE CARRIER

SOFTWARE CONFIGURATION

WINDOWS VERSION REQUIREMENT FOR DELTA-VDELTA-V VERSIONV6 v7.1 v7.2 v7.3

OPERATING SYSTEMWindows NT Server 4.0 with SP6a Windows NT Workstation 4.0 with SP6a Windows NT Server 4.0 with SP6a Windows NT Workstation 4.0 with SP6a Windows Server 2003 Windows XP Professional SP1 Windows Server 2003 Windows XP Professional SP1

WINDOWS VERSION REQUIREMENT FOR DELTA-V (CONT.)DELTA-V VERSIONv7.4, v7.4.1 v7.4.2 v8.3 v8.4.x

OPERATING SYSTEMWindows Server 2003 Windows XP Professional SP1 Windows Server 2003 SP1 Windows XP Professional SP2 Windows Server 2003 Windows XP Professional SP2 Windows Server 2003 Windows XP Professional SP2

WINDOWS VERSION REQUIREMENT FOR DELTA-V (CONT.)DELTA-V VERSIONv9.3 v9.3.1 v10.3

OPERATING SYSTEMWindows Server 2003 SP1 Windows XP Professional SP2 Windows Server 2003 SP2 Windows XP Professional SP2 Windows Server 2003 Standard Edition with SP2 (32-bit) Windows XP Professional with SP3 (32bit) & Windows Vista Business Edition with SP1 (32-bit)

WINDOWS VERSION REQUIREMENT FOR DELTA-V (CONT.)DELTA-V VERSIONv10.3.1

OPERATING SYSTEMWindows Server 2003 Standard Edition with SP2 (32-bit) Windows XP Professional with SP3 (32bit) Windows Vista Business Edition with SP2 (32-bit) & Windows Vista Ultimate Edition with SP2 (32-bit)

V11.3

Windows Server 2008 Windows 7 (32-bit)

DELTA-V INSTALLATION INSERT THE DELTA-V SOFTWARE CD-ROM #1 IN TO THE CDROM DRIVE SELECT INSTALL DELTA-V V9.3 FROM THE SPLASH SCREEN OR OPEN WINDOWS EXPLORER, SELECT THE CD DRIVE AND BROWSE FOR SETUP.EXE ON THE ROOT DIRECTORY OF THE CD AND DOUBLE CLICK IT.

DELTA-V INSTALLATION (CONT.) SELECT OK WHEN PROMPTED TO INSTALL THE .NET FRAMEWORK 1.1. AFTER THE REBOOT LOG BACK ON AND CONTINUE WITH THE DELTA-V INSTALLATION

DELTA-V INSTALLATION (CONT.) SELECT NEXT FROM THE WELCOME BANNER SELECT YES FROM THE LICENSE AGREEMENT DIALOG BOX SELECT THE APPROPRIATE WORKSTATION TYPE FROM THE LIST

DELTA-V INSTALLATION (CONT.) VERSION CONTROL IS ONLY SUPPORTED ON SERVER 2003 OPERATING SYSTEM BECAUSE OF SQL REQUIREMENT. SELECT YES TO PROCEED WITH THE INSTALLATION

DELTA-V INSTALLATION (CONT.) SELECT THE DESIRED INSTALLATION TYPE:

DELTA-V INSTALLATION (CONT.) SELECT NEXT ON THE START COPYING FILES TO BEGIN INSTALLATION:

DELTA-V INSTALLATION (CONT.) WHEN PROMPTED INSERT THE DISC-2. SELECT OK.

DELTA-V INSTALLATION (CONT.) CLICK FINISH WHEN INSTALLATION PHASE IS COMPLETED

DELTA-V WORKSTATION CONFIGURATION ONCE THE WORKSTATION IS REBOOTED THE DELTA-V WORKSTATION CONFIGURATION WILL AUTOMATICALLY START

DELTA-V WORKSTATION CONFIGURATION (CONT.) AFTER REGALL/REGISTRY COMPLETES , DELTA-V WORKSTATION CONFIGURATION WILL START AUTOMATICALLY, SELECT NEXT TO BEGIN

DELTA-V WORKSTATION CONFIGURATION (CONT.) A MESSAGE BOX ALLOWING YOU TO CONFIGURE SYSTEM PREFERENCES AT THIS TIME WILL APPEAR. CLICK YES

DELTA-V WORKSTATION CONFIGURATION (CONT) IN THE SYSTEM PREFERENCE DIALOGUE SELECT THE