David J. Peterson Mechanical Option “Thesis Report” · 2004-05-12 · Lighting: · Fluorescent...
Transcript of David J. Peterson Mechanical Option “Thesis Report” · 2004-05-12 · Lighting: · Fluorescent...
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
1
David J. Peterson Mechanical Option “Thesis Report” The INOVA HEART INSTITUTE AT INOVA Fairfax Hospital, Falls Church, VA.
Thesis Report
“Exploring New Technologies to Optimize Design ”
Instructor: Dr. Srebric
May 5, 2004
Thesis Building Sponsor’s:
INOVA Fairfax Hospital www.inova.com
& Turner Construction
3300 Gallows Road, Falls Church, VA 22042
www.turnerconstruction.com
David J. Peterson MECHANICAL OPTION www.arche.psu.edu/thesis/2004/djp196
INOVA Fairfax Hospital’s INOVA Heart Institute Falls Church, VA
The INOVA Heart Institute project consists of a 156 beds, 6 operating rooms, five-story structure, 440,000 sq. ft., located on the west side of the INOVA Fairfax Hospital and adjacent to the existing outpatient surgery building. The current facility and new addition are owned by the INOVA Health System. The overall cost is approximately $80 million and it is currently under construction and is due to open in the Summer of 2004. Design and Construction Team: General Contractor: Turner Construction Architects: Wilmot/Sanz, Inc. Landscape Architects: Lewis Scully Gionet MEP Engineer: RMF Engineering, Inc. Civil Engineer: Dewberry & Davis Structural Engineer: Cagley & Associates
Architectural Features: · Upon opening the INOVA Heart Institute will offer unique features designed to create a soothing and peaceful healing environment aimed at enhancing the recovery process for heart patients. · The use of soft lighting, wood accents, gardens, water and quiet/meditation areas will be woven throughout the Institute, contrasting with the stark clinical setting of traditional hospitals. · A three story front entrance Atrium will greet its visitors and patients. · The perimeter walls are a combination of insulated glass and either brick façade for the main levels, precast concrete curtain walls for the lower sub- level/garage, an aluminum panel wall system for the upper penthouse.
Electrical System: · Normal power will be derived from Virginia Power. · Emergency power will come from separate backup generating system. · Isolation Power will be provided to labs and Eps. · Grounding system using grounding grid to include each room along with lighting protection system which will rely on separate down leads other than structural steel. · Telephone and Data system will be provided via raceway system and allow for a means to wire outlets throughout the building. · Sound and paging system located throughout corridors and staff areas.
Structural System · Poured concrete column and concrete beam system · Floors are steel framed with poured cast in place concrete slab · The roofing system will include a primary cast in place concrete slab.
Mechanical System Features: · Constant Volume System for the operating, intensive care, patient, and clean work areas with 95-99% efficiency final filters · Variable Volume System for the Atrium and open waiting areas · Secondary low temperature cooling system loop for the Cardio Vascular Operating Rooms (CVOR) · Medical gas piping to each patient, operating, holding and prepping space · 13 AHU (3 on stand-bye) with total building SA of approx: 330,000 CFM
Lighting: · Fluorescent lighting will be provided throughout the entire project to provide energy efficiency in Mechancial/Electrical, corridor, and storage Spaces. · Dimming of fluorescents troffers will be used in special applications throughout to achieve appropriate lighting conditions in labs, patient, and operation rooms. · Incandesencents and other specialty lighting will be used in selected areas to achieve specific lighting effects along with task lighting, where necessary.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
3
Table of Contents: Search by Topic: 1.0 Executive Summary:......................................................................................... 5 2.0 Background: ...................................................................................................... 7
2.1 Building Information .................................................................................................................................8 2.2 Systems Design .........................................................................................................................................9 2.3 Design Requirements...............................................................................................................................10 2.4 Systems Information................................................................................................................................10 2.5 Indoor Design Conditions........................................................................................................................10 2.6 Outdoor Design Conditions .....................................................................................................................10 2.7 Utility Rates and cost factors...................................................................................................................11 2.8 Air Systems .............................................................................................................................................11 2.9 Steam Systems.........................................................................................................................................12 2.10 Hydronic systems ..................................................................................................................................12 2.11 Systems Costs........................................................................................................................................13
3.0 Air Distribution Analysis (Depth Study): ..................................................... 14 3.1 Background .............................................................................................................................................15 3.2 Problem ...................................................................................................................................................15 3.3 Proposed Solution....................................................................................................................................15 3.4 Plan of Attack..........................................................................................................................................16 3.5 Contaminates ...........................................................................................................................................17
3.5.1 Contaminates; Pathogens .......................................................................................................17 3.5.2 Contaminates; Types ..............................................................................................................17 3.5.3 Contaminates; Classifications ................................................................................................17 3.5.4 Contaminates; Droplet Production .........................................................................................18 3.5.5 Contaminates; Droplet Detection ...........................................................................................18 3.5.6 Contaminates; Droplet Evaporation .......................................................................................18 3.5.7 Contaminates; Transmission ..................................................................................................19 3.5.8 Contaminates; Routes of Infection .........................................................................................20 3.5.9 Contaminates; Dose................................................................................................................20 3.5.10 Contaminates; Viability........................................................................................................21 3.5.11 Contaminates; Nosocomial...................................................................................................21 3.5.12 Contaminates; Mechanical System.......................................................................................22
3.6 Controlling Contaminates: General .........................................................................................................22 3.6.1 Controlling Contaminates; Dilution Ventilation ....................................................................23 3.6.2 Controlling Contaminates; Displacement Ventilation............................................................24 3.6.3 Controlling Contaminates; Pressure: Difference....................................................................24 3.6.4 Controlling Contaminates; Room Air Cleaning Devices .......................................................24
3.7 Respiratory System..................................................................................................................................25 3.8 Air Quality Indicators..............................................................................................................................27 3.9 Introducing spaces ...................................................................................................................................29 3.10 Simulation Conditions ...........................................................................................................................30
3.10.1 Simulation Conditions “Family Waiting Room” .................................................................31 3.10.2 Simulation Conditions “Post Anesthesia Care Unit” .........................................................32 3.10.3 Simulation Conditions “Transplant Waiting Room” ...........................................................33 3.10.4 Simulation Conditions Validating Case: “CCC Hospital’s Surgical Waiting Room”.........34
3.11 Normalized Age of Air Simulation........................................................................................................35 3.11.1 Normalized Age of Air Simulation “Family Waiting Room” .............................................36 3.11.2a Normalized Age of Air Simulation “Post Anesthesia Care Unit” ....................................37 3.11.2b Normalized Age of Air Simulation “Post Anesthesia Care Unit” ....................................38 3.11.3 Normalized Age of Air Simulation “Transplant Waiting Room” .......................................39 3.11.4 Normalized Age of Air Simulation, Validating Case: “CCC Hospital’s
Surgical Waiting Room” ..................................................................................................40 3.11.5 Normalized Age of Air Simulation, Regions of Most Concern ...........................................41 3.11.6 Normalized Age of Air Simulation, Closer look at Transplant Waiting
Room.................................................................................................................................41
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
4
3.12 Contaminate Removal Effectiveness, 100% Contamination Simulation...............................................43 3.12.1 CRE , 100% Contamination” Family Waiting Room” .......................................................44 3.12.2a CRE , Non-Patient Contamination “Post Anesthesia Care Unit”.....................................45 3.12.2b CRE , Patient Contamination “Post Anesthesia Care Unit” ............................................46 3.12.3 CRE , 100% Contamination “Transplant Waiting Room” ..............................................47 3.12.4 CRE, 100% Contamination, Validating Case ......................................................................48 3.12.5 CRE, 100% Contamination Simulation, Regions of Most Concern.....................................49 3.12.6 CRE, 100% Contamination Simulation, Closer look at Transplant Waiting Room.............51 3.12.7CRE, 1 Person Contamination Simulation, Closer look at Transplant Waiting Room .........51 3.12.8 Determining the Duration of time for Steady State Conditions to Occur.............................52
3.13 1st Proposed Solution.............................................................................................................................53 3.13.1 1st Proposed Solution, CRE, 100% Contamination ............................................................................54
3.13.2 1st Proposed Solution, Normalized Age of Air.....................................................................55 3.13.3 1st Proposed Solution, CRE, One person Contamination .....................................................56
3.14 2nd Proposed Solution ............................................................................................................................57 3.14.1 2nd Proposed Solution, CRE, 100% Contamination .............................................................58 3.14.2 2nd Proposed Solution, Normalized Age of Air ....................................................................59 3.14.3 2nd Proposed Solution, CRE, One person Contamination ...................................................60
3.15 Proposed Solutions, Cost Estimate ........................................................................................................60 3.16 Summary ...............................................................................................................................................61
4.0 Constructability Analysis (Breadth Study): ................................................. 63 4.1 Background .............................................................................................................................................64 4.2 Introducing the Space ..............................................................................................................................64 4.3 Problem ...................................................................................................................................................64 4.4 Plan of Attack .........................................................................................................................................65 4.5 Investigation of Upper Plenum Space .....................................................................................................65 4.6 3D Coordination Section Before Redesign..............................................................................................66 4.7 Schedule, Sequencing of Trades..............................................................................................................67 4.8 3D Coordination Section After Redesign ................................................................................................67 4.9 Impact of Redesign..................................................................................................................................68 4.10 Summary ...............................................................................................................................................68
5.0 Daylighting Analysis (Breadth Study) .......................................................... 69 5.1 Background .............................................................................................................................................70 5.2 Introducing the Space ..............................................................................................................................70 5.3 Problem ...................................................................................................................................................70 5.4 Plan of Attack..........................................................................................................................................71 5.5 Determination of Optimal glazing...........................................................................................................71 5.6 Daylight Simulations ...............................................................................................................................72
5.6.1 Daylight Simulations, Daylight Factor...................................................................................72 5.6.2 Daylight Simulations, AGI.....................................................................................................73
5.7 Building Loads and Operating Cost ........................................................................................................79 5.8 Impact on Exterior Façade .............................................................................................................80 5.9 Cost Analysis .....................................................................................................................................81 5.10 Feasibility of Results .............................................................................................................................82 5.11 Summary ...............................................................................................................................................82
6.0 Conclusions: ..................................................................................................... 84 7.0 Credits and Acknowledgements: ................................................................... 86 8.0 References:....................................................................................................... 88 9.0 Appendix:......................................................................................................... 91
9.1 Appendix A.1 ..........................................................................................................................................92 9.2 Appendix B.1.........................................................................................................................................105
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
5
1.0 Executive Summary:
The purpose of this report is to investigate the problematic distribution of
contaminates with in existing spaces(Depth), constructability of proposed solutions to the air
distribution systems(Breadth), and the optimization of natural daylighting(Breadth) for the
INOVA Heart Institute. The new INOVA Heart Institute is an addition to the INOVA
Fairfax Hospital (existing) in Falls Church, VA, The overall size of the new addition to the
original hospital is approximated at 410,000ft^2 of which 300,000ft^2 is conditioned.
In the depth study by using computational fluid dynamics it was determined that there
were regions of concern in multi-occupied spaces where high concentrations of contaminates
could collect and pose a threat to the inhabitants within those spaces. The types of spaces
investigated include waiting rooms and recovery rooms. Proposed solutions suggested that
changing the current air distribution system at minimal cost to the owner could drastically
reduce concentration levels.
In the first breath study on constructability, proposed solutions to the depth study
were investigated for feasibility of implementation. When changing air distribution systems
other problems may arise when actual renovation take place. Because of this the upper
plenum space above the room must be investigated for possible obstructions and hazards
posed by the redesign. The results of this investigation suggested that if the redesign was
implemented either before or after the actual design that there would be no major issues and
that constructability was possible.
The second breadth study investigated the optimization of natural daylight with the
mechanical system. It was determined that INOVA Heart Institute has a very large quantity
of glazing on its exterior surfaces of which exposure to natural light was rather large. By
investigating passive solar architecture design, along with recommended natural daylight
illuminace values it was determined that exterior glazing area could be reduced which would
have a positive impact on annual mechanical operating costs. With the change in window
area on the exterior walls associated impacts on the non-load bearing curtain wall were also
investigated. Cost of implementation was also included in this study.
The INOVA Heart Institute final rendering is shown in the photo on the following
page below courtesy of Turner Construction and is due to open in the summer of 2004.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
6
INOVA Rendering 1: “Final Rendering”
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
7
2.0 Background
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
8
2.0 Background: 2.1 Building Information
The INOVA Heart Institute is an addition to the existing INOVA Fairfax Hospital. It
is located in Northern Virginia just outside of the 495 Beltway in Falls Church, Virginia. As
stated in its name the new addition will serve as a Cardio-Vascular Institute and provide
Operating, Care, Rehabilitation and lab spaces for all issues dealing with the heart. The
demand for such facilities is ever increasing with the explosion in population in the Northern
Virginia Area. The overall size of the new hospital is approximated at 410,000 sq.ft. with 6
floors, 360,000 sqft of condition floor space, 6 cardio vascular operating rooms, over 150
patient rooms, outdoor gardens, along with a garage (located in the basement).. The hospital
is broken down into 3 wings and are divided into sections A, B and C. Sections A and B
serve the majority of the hospital and serve as recovery, patient, lab, general hospital office,
atrium and recreation spaces. The third wing or CVOR (Cardio-Vascular-Operating-Rooms)
serves as the critical care and operation wing.
The new addition will be located and attached to the rear of the existing facility on the
west end of the property.
INOVA Photo 1: “Existing Hospital”
The new addition receives all its chilled water and high pressure steam from this
remote central plant which is fed into the building’s sub-basement via existing tunnels
adjacent to the existing hospital. The west end of the property was the only appropriate
direction in which to expand. The north end contains overflow parking a water tower and the
central plant. The existing hospital extends all the way to the property limits on the east end
next to Gallows Road, a major thoroughfare.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
9
INOVA Photo 2: “Aerial shot of Existing Hospital”
The INOVA Heart Institute is currently being constructed between the new parking
deck and the existing hospital.
INOVA Photo 3: “Existing Central Plant”
2.2 Systems Design The design for the mechanical systems for the new INOVA Heart Institute include:
1. Provide round the clock sufficient conditions for patients, workers and visitors
with the use of terminal duct reheats, steam humidification and critical sensors
throughout. (CO2, Temperature, and Pressure)
2. A variable volume system for variable occupancy in the open areas and atrium
space
3. A constant volume system for the typical hospital area
4. A system that ingrates with the existing facilities district chilled water, steam
and condensate
5. Provide backup AHU’s to each system in order to maintain sufficient conditions
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
10
2.3 Design Requirements
The primary objective is to maintain sufficient condition for 24 hours of operation.
This requires proper filtration for indoor air quality issues, sufficient temperature, pressure,
and C02 levels. These requirements serve to protect the health and well being of the
inhabitants of the facility.
2.4 Systems Information
The mechanical systems for this hospital are a combination of constant volume and
variable volume with thirteen separate air handlers. Eight of these air handlers feed into four
main shafts that supply patient rooms and clinical areas for the entire building, two of which
are stand-bye. Three of these air handlers feed the Cardio Vascular Operating Rooms
(CVOR) on the 2nd and the area directly above on the 3rd floor, one of these is a stand-bye.
The last two of these feed the atrium and waiting areas.
2.5 Indoor Design Conditions The indoor air conditions are taken from the mechanical specifications and are
represented below. Indoor Air Conditions
Indoor design conditions for all areas excluding CVOR’s Dry Bulb: 72 F Relative Humidity: 50% Indoor design conditions for all areas including CVOR’s (Cardio-Vascular Operating Rooms): Wet Bulb: 65 F Relative Humidity: 50%
INOVA Table 1: Indoor Air Conditions
2.6 Outdoor Design Conditions The outdoor air conditions for design match that of the design conditions given in
ASHRAE’s Fundamentals for Washington, DC (at 0.4%) and are listed in the table to follow.
Outdoor Air Conditions Design Cooling Temperatures: (Summer) Dry Bulb: 95 F Mean Wet Bulb: 76 F Design Cooling Temperatures: (Winter) Dry Bulb: 15 F Evaporating Temperatures: Wet Bulb: 79 F Mean Dry Bulb: 89 F
INOVA Table 2: Outdoor Air Conditions
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
11
2.7 Utility Rates and cost factors The following utility charges apply to the INOVA Heart Institute. The energy
sources for the new addition are electric power from Virginia Electric and Power Company
and gas from the Washington Gas and Light Company.
Virginia Electric and Power Company Schedule GS-3U Distribution Service Charges Basic monthly: $119.80 or $1437.60 annual Distribution Demand on all KW: $2.12 per KW Competitive Trans. On Peak Demand: $2.897 per KW Competitive Trans. On Peak KWH: $0.00568 per KWH
INOVA Table 3: Electric Rate Summary Under this rate schedule there is always a distribution demand on all KW but there
are no excess off-peak demand charges like there is for on-peak. Keeping this new facility on
the premises of the existing facility takes advantage of the no off- peak demand charge.
Washington Gas Commercial and Industrial Service Rate Schedule NO. 2 System Charge: $196.2 /(annual) Distribution Charge: (Per Therm) First: 125 Therms 0.3083/(mos.) Next: 875 Therms 0.2483/(mos.) Over: 1,000 Therms 0.1831/(mos.)
INOVA Table 4: Gas Rates Summary
On-peak hours are as follows: 1. For the period of June 1 through September
30, 10 a.m. to 10 p.m., Mondays through Fridays.
2. For the period of October 1 through May 31, 7 a.m. to 10 p.m., Mondays through Fridays.
Information for the gas boilers located in the central plant is not accessible. Savings
is obtained by the use of a central plant, which purchases this utility presumably in large
quantities to support the needs of the existing as well as the new facilities on the property.
2.8 Air Systems AHUs 1,2,3,4 and 7,8,9,10 serve patient rooms and general hospital Area (Constant
Volume System). For design conditions three air handlers are used to supply air into a
common duct, which then splits into two major shafts that run down the entire length of the
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
12
building. The fourth unit (AHU-4) is connect to the same system and is for back up purposes
only.
AHUs 5 and 6 serve the atrium and lobby areas (Variable Volume System). For
design conditions the two air handlers are used to supply air into a common duct and supply
air to the front entrance atrium.
AHUs 11,12,13 serve Cardio Vascular Operating Room (CVORs) spaces and areas
directly above (Constant Volume System with Isolation Dampers). For design conditions two
air handlers are used to supply air into a common duct which only drops down two floors.
The third unit (AHU-13) is connect to the same system and is for back up purposes only.
AHUs Section System Type
Room SA (F):
CFM (each):
Outdoor Air (%):
Back-Up
Unit (AHU):
Cooling (Tons - each):
Cooling (Total Tons):
1,2,3,4 A CAV 55 40000 30 4 184 552
5,6 Atrium VAV 55 32000 30 - 144 288
7,8,9,10 B CAV 55 40000 30 10 184 552
11,12,13 C CAV 55 40000 30 13 184 368 INOVA Table 5: AHU Characteristics
AHUs Section System Type
Pre-Filter (%)
Post-Filter (%)
Final-Filter (%)
Post Final Filter (%)
AHU Location
1,2,3,4 A CAV 30 60 95 99.95 5th FL Penthouse5,6 Atrium VAV 30 60 - - 5th FL Penthouse7,8,9,10 B CAV 30 60 95 99.95 5th FL Penthouse11,12,13 C CAV 30 60 95 99.95 4th FL Penthouse
INOVA Table 6: AHU Filtration
2.9 Steam Systems The system brings in High Pressure Steam (HPS) from the central plant. The system
converts HPS into Medium pressure steam (MPS) and Low Pressure Steam (LPS) through a
network of Pressure Reducing Valves (PRV) that accommodates the various mechanical
equipment throughout the new facility.
2.10 Hydronic systems Hot water is provided to the building through a self-contained loop, which
uses steam/heating-water-converters or heat exchangers to produce hot water to re-circulate
through the building. The purpose of the hot water loop is to provide reheat to CAV and
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
13
VAV terminal units and preheat to the AHUs and radiant panels. The facility has seven
major hot water pumps to perform this task.
Chilled water is provided to the building by the remote central plant, also the location
of the primary/secondary pumping. The purpose of the chilled water is to provide cooling for
coils located within the air handlers and fan coil units.
There is a secondary chilled water loop that serves the CVOR wing of the building.
Secondary chilled water supplied by two air-cooled chillers (50 tons each). The cooling coils
here are used to supply an air dry bulb temp of 42.3 F at an entering water temperature of 38
F to the operating spaces.
2.11 Systems Costs:
The following mechanical system costs, supply actual values for the all three wings of
the new hospital combined and they are further broken down into three main costs
Mechanical/ Plumbing/Medical Gas (combined), Sprinklers and Electrical. The system cost
represented show that the Mechanical overall cost is the most expensive per square foot of
the building.
System's Cost Type Cost ($) Cost/sq.ft. ($)Sprinkler 836,000 2.04*Mechanical 17,200,000 42.02Electrical 9,200,000 22.33
Total: 27,236,000 66.39
*(Includes all Mech., Plumbing, and Med. Gas )
INOVA Table 7: System’s Cost
The Overall cost for the building was $80 million per square foot the mechanical systems
make up approximately 21% of the overall cost of the entire building.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
14
3.0 Air Distribution Analysis (Depth Study)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
15
3.0 Air Distribution Analysis (Depth Study) 3.1 Background
Like most building applications, in health care facilities the most desirable manner of
introducing supply air to its spaces is to maximize overall distribution throughout theses
spaces. This is most important with critical environments such as hospitals because the
threat of disease and infection is more prevalent. Proper distribution and mixing of air
maximizes the effectiveness of ventilation and ensures that clean air is available everywhere
it is needed and eliminates stagnant air pockets.
Most often in building system design a simulated analysis of what actually occurs is
omitted. In the case of air distribution many negative effects can occur once the building is
completed and operating. In such buildings as hospitals these negative effects can attribute
to infection, sickness and even death.
Large multi-occupied spaces such as waiting rooms, intensive care units, and post
operating recovery rooms are suspect areas for airborne contamination. The primary method
of air borne contamination in these multi-occupied spaces is coughing and sneezing (person
expelling contaminants into open air). The primary reason for secondary contamination and
ultimate infection from patient to patient is due to improper placement of supply air
distribution diffusers and return air vents.
3.2 Problem Good air mixing is achieved by careful selection of diffuser location and
performance, with proper attention to room construction and/or perimeter exposures that can
affect distribution performance. The goal for this proposed solution would be to minimize
the spreading of secondary contaminates by reducing the overall concentrations, keeping
them localized, and ventilating them efficiently and properly. Proper design, placement, and
location of supply and return side diffuser/ventilation equipment can maximize air quality
while accruing no additional operating expenses or having any adverse effects on its
occupants. The impacts of this topic would require a study of systems equipment with
amount overall supply and return air quantities required to be distributed to each space as
well as studies of how supply and return air are supplied to each space. 3.3 Proposed Solution
The solution method for properly mixing and distributing air in multi-occupied spaces
within a hospital begins with the selection of suspect areas, which include intensive care
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
16
units, recovery, and waiting rooms. Supply and return air quantities must be accurately
accounted for and defined for each space. Then all parameters effecting airflow in the space
must be defined these include location, orientation, and general obstructions. Once all the
space-defining characteristics have been determined Computational Fluid Dynamic (CFD)
simulation analyses will be preformed on each space to model flow patterns and assess each
rooms’ performance. Once simulations have been done and room performance has been
assessed decisions must be made on how much and where supply and return air distribution
equipment must be distributed/ventilate and where it will be located. Affects on the
relocation of diffusers and vents types with in the space must also be looked at. Simulations
will represent typical setting of people and their location in the room of interest. Developing
regions of most concern will be the focus for the simulations. The worst case scenario will be
simulated in order to see where low velocities, low flow and stagnant pockets exist.
The scale at which the simulations will be done and the density of the mesh of which
the simulations will calculate associated properties cannot fully show the effects of person-
to-person contamination, but can give insight on what may occur in the space. Inspiring and
expiring of air is a very difficult concept to model due to the relative nature of people and the
differences in each individual. Only speculation of effects from person to person
contamination within the space can be ascertained. The simulations do show the
development of concentrations at steady state in low velocity areas and low flow areas
produced by improper and or inadequate air distribution.
For the purpose of this study pockets and regions that are adjacent to doors (entrances
and exits) will not be considered. The reason for this is that people are not likely to remain
in these areas for durations of time which contaminate levels can develop in these areas flow
patterns will change regularly and steady state conditions will mostly like never be achieved
in these areas. Also open areas free of furniture and people or areas where people will most
likely not congregate will not be considered.
Regions will be considered threatening if air flow patterns yielded high age of air and
concentrations where air flow patterns were maintained for a period of time or long enough
to have a sustain concentrations levels greater then exhaust concentration.
3.4 Plan of Attack
1. Define Space Conditions through the design documents
2. Simulate models to meet initial thermal design conditions.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
17
3. Simulate and evaluate Indoor Air Quality Indicators
4. Determine regions of most concern
5. Propose solutions to rectify any problems
6. Re-simulate with proposed solutions.
7. Evaluate the solutions (cost, feasibility, and effectiveness)
3.5 Contaminates: In the field of Indoor Air quality very little research is available on the microbiology
aspect of this science. The lack of information on the transmission of pathogenic particles is
due to the fact that the “aerobiology” is misunderstood and that the “threat posed by such
airborne microbes is greatly underestimated.”(9) 3.5.1 Contaminates; Pathogens:
The pathogen term refers to any microorganism or agent that may cause disease or
irritation in the respiratory system. There are three types of respiratory pathogens: viruses,
bacteria and fungi. Less than two dozen pathogens account for the majority of contagious
infections. 3.5.2 Contaminates; Types:
Viruses are very small cell based parasites. The major viruses of concern include the
rhinovirus and influenza (approximate range of size is 0.03 to 0.2 um in diameter). Bacteria
are single celled microorganisms. The most common are TB, Legionella Pneumophila, and
Anthrax (approximate range of size is 0.2 to 3 um in diameter). Fungi can cause infection for
low immune systems can develop in HVAC systems and are a major concern in hospitals
(approximate range of size is 0.8 to 20 um in diameter). A chart showing Relative Size is
located in Appendix A.1. 3.5.3 Contaminates; Classifications:
There are three classifications that define all airborne pathogens communicable, non–
communicable, and nosocomial. When classifying respiratory pathogens the term
communicable is interchangeable with the term contagious. Communicable diseases are
disease mainly coming from humans. Non-communicable diseases are diseases derived from
the environment. Microbes that cause infection for people with low immune systems and or
people recovering in hospitals are known as nosocomial or hospital acquired infections.
These usually only occur when a person’s health is compromised. Appendix A.2 and A.3 has
a list of major respiratory pathogens classified into these three categories.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
18
3.5.4 Contaminates; Droplet Production: Respiratory pathogens can be transmitted through the exchange of infectious moisture
droplets or particles called droplet nuclei, which can easily spread, throughout the space. It is
said that a person in the infectious stage of a “cold may produce 6200 droplet nuclei per hour
of viable disease containing viruses that remain airborne longer than 10 minutes.”
A droplet nuclei is the remnants of an evaporated droplet expelled by a person
through the actions of coughing or sneezing, which can introduce pathogenic microbes into a
space. One microbe is equivalent to one colony forming unit or CFU. Sizes of a droplet
nuclei range from approximately 0.02 microns to 10 microns in size. Normal pathogenic
viruses range from 0.02 to 1 micron. One Micron has the density of approximately 1g/m^3.
A profile of particle sizes that an infections person can produce can be found in Appendix
A.4.
A single sneeze can generate a hundred thousand floating bioaerosol particles
containing viable microorganisms. A single cough typically produces about 1% of this
amount, but “coughs occur about ten times more frequently than sneezes.” Negligible
production occurs when talking. When a person sneezes or coughs many thousands of
droplets are vigorously expelled into the atmosphere. In the case of sneezing initial
velocities can be as high as 100 m/s. If droplet nuclei are produced by an infectious patient,
then they will contain pathogenic microorganisms which will be dispersed into the
atmosphere.
3.5.5 Contaminates; Droplet Detection: It is said that detection of viruses and bacteria is normally a time consuming
laboratory process, and is not always guaranteed to be successful unless one knows exactly
what one is looking for. Detection of airborne pathogens in an air stream is nearly
impossible, new technologies offer some promise but for now only can speculate on
simulated results. Knowing room and particle characteristics can simulate approximate
location. 3.5.6 Contaminates; Droplet Evaporation:
During sneezing most of the droplets are approximately 10 to 100 µm in diameter.
The larger droplets fall to the ground, while evaporation of the smaller droplets take place
and they rapidly decrease in size to become droplet nuclei.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
19
The precise rate of evaporation is dependent on the vapor pressure in the air which is
governed by its temperature and humidity. Because of this most of the droplets produced
by a sneeze quickly evaporate to form droplet nuclei and or single microbes. Droplet
nuclei are so small that they settle slowly and remain suspended in air for a
considerable period of time.
Diameter of Droplet (µm)
Evaporation Time (Seconds)
Distance that droplet will fall Before evaporation (m)
200 5.2 6.51 100 1.3 0.42 50 0.31 0.0255 25 0.08 0.00159 12 0.02 0.00008.5
INOVA Table 8: Water droplet Evaporation Time(9)
The previous table shows the evaporation times of water droplets and falling distance
before evaporation in air at 22C and 50 % relative humidity. Under calm conditions a 2um
particle would take approximately 4.4 hours to fall a distance of 2 m. Given this long
suspension time particles will be carried long distances by natural convection currents.
Depending on ventilation strategy and air distribution, droplet nuclei can travel even longer
distances and thus be widely distributed throughout the building space. A chart showing the
disappearance of airborne sneeze droplets after duration of time is located in Appendix A.7. 3.5.7 Contaminates; Transmission:
Microorganisms can enter the air by a variety of routes. The eyes and nasal passages
and mouth are vulnerable to microbial transmission. Contaminated skin cells, which are
continually shed by room occupants can also be a form of transmission. Most common
forms of transmission are touching contaminated surfaces or direct contact with person in
close range.
The approximate number of new infections can be calculated when knowing the room
ventilation rate. From this relationship it can be seen that with the increase in ventilation the
number of new infections will decrease.
Equation (1):
N =(S) x (1 – exp -((I) x (D) x (Qp) x (T) /(Qr)))
N = # of new infections S = # of susceptible I = # of infectors
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
20
D = # of infectious doses Qp = pulmonary vent rate T = duration exposed Qr = room ventilation rate
3.5.8 Contaminates; Routes of Infection: “The airborne route of transmission is important for a number of pathogenic
microorganisms in hospital buildings. The airborne link in the ‘chain of infection’ associated
with diseases such as TB is the weakest ‘link’, and the one which gives hospital engineers
and health care authorities the best opportunity to break the chain. Through the use of well-
designed engineering systems it is possible to control the spread of airborne pathogens in
hospital buildings. There is a need to raise the general awareness of available
engineering control measures and to carry out research into the optimization of these
measures in healthcare facilities.”(9)
Displayed in Appendix A.9 is a chart that shows the route of infection of colds at
various doses. The results displayed in this chart show that the nose and the eyes are the
most vulnerable routes of virus invasion. Displayed in Appendix A.10 is a chart that shows
the typical source of the cold virus. 3.5.9 Contaminates; Dose:
Dose is the total mass of toxin subjected to body it is a function of airborne
concentration, duration of exposure and uptake efficiency. In general high concentration for
short time has high efficiency effect while low concentration long time low efficiency effect.
Determining the mass body of burden can be a helpful way of determining concentrations the
body has contained over a duration of exposure it is a function of the mass of a contaminate
contained, mass inhaled, Efficiency of absorption, and efficiency of elimination. Because
results from CFD analysis or at best only rough estimates the mass body of burden will not
be calculated for occupants receiving a concentration dose.
The dose received from an airborne concentration of microbes depends on the local
air change rate and degree of mixing as well as the generation rate. The successful
transmission of an infection, however, depends on all of the following factors: susceptibility
of the individual; duration of exposure; concentration of infectious agent; virulence of
infectious agent; breathing rate; route of infection The health and degree of immunity can be
as important as the dose received from prolonged exposure. Rate of infection can be useful
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
21
in determining risk assessment. A chart showing communicable respiratory infections and
rate of infection characteristics can be found in Appendix A.5.
The mean infection or incapacitating dose (ID50) it the dose or number of
microorganisms that will cause infections in 50% of an exposed population. Applies only to
microorganisms and units are always in terms of microorganisms or CFU or colony forming
units. (cfu/m^3) In Appendix A.12 the infectious dose curve for influenza (typical
pathogen) along with general information about the pathogen are listed. The following
equation can be used to calculate dose.
Equation (2):
.
Dt = Dose over duration of time Q = Pulmanary ventilation rate c = Concentration over time t = Duration of time
3.5.10 Contaminates; Viability: Various elements in the environment can destroy most airborne microbes. These
elements include: direct sunlight, dehydration, high temperatures, freezing temperatures and
oxygen(oxidation) in the environment will destroy most pathogens. Airborne microbes also
may lose viability over time in the absence of sunlight. Decay rate is subject to change given
actual conditions experienced in the space. A chart showing the viability of airborne
particles indoors after duration of time is located in Appendix A.6. 3.5.11 Contaminates; Nosocomial:
“Nosocomial infection or hospital originating infection is a major problem in many
healthcare facilities, with approximately 1 in 10 patients acquiring an infection during a
hospital stay.” (9) The economic impact of nosocomial infections is considerable and many
have become drug resistant.
Most nosocomial infections are direct or from person to person contact but can still be
transmitted through the airborne route. “It has been calculated that the airborne route of
transmission accounts for 10% of all sporadic cases of nosocomial infection.”(1)
All respiratory pathogens are potentially nosocomial. In intensive-care units and high
occupancy areas in hospitals, almost a third of nosocomial infections are respiratory.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
22
Nosocomial infections can also be airborne but non-respiratory, such as when common
microbes settle in wounds typically resulting in post operating infections. Natural defenses
are usually compromised for individuals who succumb to nosocomial infections. All
respiratory pathogens are potentially nosocomial.
When concerning ventilation systems Humidity control is a very important issue in
hospitals because it prevents bacteria, mold and fungi growth and spreading throughout the
facility. Nosocomial infections can result in poor humidity control. 3.5.12 Contaminates; Mechanical System
Poorly designed or maintained mechanical ventilation systems can house and
distribute pathogenic contaminates. Elements in the ventilation system can be contaminated
with microorganisms that can spread fairly easily throughout the building
INOVA Rendering 2: Sources and pathways of microbial contamination
Cooling coils and humidifiers and low air velocities are all potentials for sponing
unwanted pathogenic contaminates such as Legionella Pneumophila. Even filters that are not
maintained and change regularly can become dirty, and they themselves can become
contaminated and can aid in the spread of airborne pathogens.
3.6 Controlling Contaminates: General: Ventilation systems in buildings are designed and operated to deliver fresh air to
occupants while removing internally generated contaminates to provide acceptable thermal
comfort levels in the vicinity of occupants. When designing ventilation systems the
emphasis is primarily on thermal comfort because quality perceived and judgment is much
larger and better defined by standards. On the other hand poor air quality response time is
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
23
much longer and not very well defined. The chain of infection is therefore very much
influenced by the ventilation conditions, which exist in any particular clinical setting.
When controlling airborne pathogens, good mechanical ventilation, or supply of clean
and or outdoor air, is probably the most effective along with efficient air movement
throughout space. Ventilation in hospitals is vital for contaminate control. Ventilation in
general is the supply of fresh air to a space to replace contaminated air that may dilute and or
displace contaminates. In large facilities such as the one explored in this study only about
30% outside air is introduced into the supply air. This means that high efficiency filters must
be used to prevent contaminate introduction through recirculated air, which is the case for
this building.
Air movement is crucial when trying to prevent contamination it is also a necessary
requirement for this type of facility in order to maintain spaces, with few or no stagnant air
pockets, increase thermal comfort, and achieve uniform humidity control.
In theory as clean ventilated air is introduced it will produces uniform concentration
of contaminants and it removes contaminated air at average concentration of the space or at
contaminate equilibrium. Contaminate equilibrium is a function of volume flow rate of clean
air, volume of the space and the rate at which contaminates are introduced into the space.
The following equations show this at well-mixed conditions.
Equation (3): Ceq = Cg/( AC) x (Vr) Ceq = Contaminate Equilibrium Cg = Rate of contaminate introduction in space AC = Number of air changes Vr =Room Volume
3.6.1 Controlling Contaminates; Dilution Ventilation:
contaminates effectively. Dilution ventilation is used most effectively in smaller spaces.
Dilution ventilation is the intentional mixing of large
quantities of clean/fresh air in a space. With good
conventional air distribution and properly designed
diffusers, dilution ventilation can achieve fairly well
mixed or ideal conditions for flushing out and removing
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
24
Hospitals such as the INOVA Heart Institute use a combination of dilution ventilation
and pressurization with high air change rates. 3.6.2 Controlling Contaminates; Displacement Ventilation:
Laminar and displacement ventilation carefully directs airflows to displace
contaminated air. This type of ventilation introduces fresh air a low velocity, causing a piston
type effect for air towards return inlets, and causes non-uniform concentration of
contaminates in the space. Displacement ventilation can remove contaminates (2) times that of well mixed space
but stratification issues may cause adverse temperature and humidity conditions at different
altitudes and locations within the space. These types of systems are somewhat specialized
and are often used in clean rooms and operating rooms but are starting to be used more
commercially. In hospitals especially they are ideal in isolation environments and aid in the
prevention of nosocomial infections. Supply and return air vents are often at opposite ends
of room (i.e. air can be supplied at low levels and exhausted at high levels or vice versa)
3.6.3 Controlling Contaminates; Pressure: Difference: Pressure differences are used throughout the new facility to prevent contaminated air
from one zone or space to spread to another via doors and other means of indoor infiltration.
By controlling the airflows within a building it is possible to create ‘high’ and ‘low’ pressure
regions. Primarily used in isolation rooms to prevent airborne pathogens from escaping. A
major problem associated with pressurization is that of maintaining designed pressure at all
times in critical areas. Unfortunately the process pressure
difference does not prevent contaminates already within a space
from spreading into potentially susceptible areas also within that
space.
3.6.4 Controlling Contaminates; Room Air
Cleaning Devices:
There are a variety of room air cleaning devices
currently available, incorporating technologies such as high efficiency particulate air
(HEPA) filters, ultraviolet germicidal irradiation (UVGI) lamps, along with many others.
These devices are intended to be mounted within a room and designed to reduce the overall
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
25
microbial level in the room air. Strategically placed they are fairly efficient in protecting
hospital staff and patrons.
The efficiency of such filtration devices as HEPA filters, although as much as 99% its
overall room effectiveness may be much lower because compared to the entire space very
little air passes through the device. Again, when dealing with filters they must be maintained
and regularly changed/cleaned to prevent contamination and reduction in discharge rate.
The benefits of Ultraviolet Germicidal Radiation (UVGI) have been known for
nearly a century and can be used in many ways to disinfect air in buildings. They can be
installed in the air system itself or in actual spaces UV radiation can damage the DNA of a
microorganism and render it no longer viable as a pathogenic viral agent. Unfortunately UV
light is mostly used in upper air levels outside of a normal breathing plain in a space, as it can
be irritating and uncomfortable if exposed to for duration of time.
There are many other approaches in which engineers have proposed to reduce overall
contaminate concentrations and viability in a space of which only a few have been listed here
in this report.
3.7 Respiratory System “Protection for one by mechanism is the unfortunate exposure to another” through
means of coughing and sneezing resulting in the production of bioareosols in a space. The
single most important physical characteristic by which to classify airborne pathogens is size,
deposition of particles varies within the respiratory system. In general smaller particles
(viruses) tend to be more hazardous, more easily deposited into the lungs, harder to capture
by respiratory defenses. Due to lack of mass tend to stay suspended in air for extended
periods of time. A virus such as pathogenic influenza is approximately 0.1 um diameter and
settling time can take as much as 10 days. Fortunately viruses tend to die rapidly in air. A
chart on associated particle settling times based on diameter of particle is located in
Appendix A.8.
As stated previously bioaerosol /aerosol sources are a direct result of coughing,
sneezing, in the mechanical system, cooling towers and humidifiers. For the purpose of this
study only contaminates introduced by occupants will be considered. In general large
particles tend to deposit in the nasopharyngeal region. Smaller particles deposit in
pulmonary region. Deposition is not perfect and some inhaled will be exhaled. Bioareosols
come in the form of solid particles and liquid droplets depending on evaporation times.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
26
Classifications of particles as they affect the respiratory system are defined as
inhalable, repairable, and ultrafine.
INOVA Renderings 3,4: Entire Respiratory System (to the Left) and the
Tracheo Bronchial region (to the right) Inhalable particles or particles with approximate diameter (Dp) less than 10um are capable
of depositing any where in the respiratory system. Repairable or fine particles with
approximate diameter (Dp) less than 2.5 um can penetrate gas exchange region of respiratory
system (Alveoli Sacs) and are more likely to be retained than larger inhalable particles. These
particles can pose greater threat to immune system. Ultrafine particles or particles with
approximate diameter (Dp) less than 0.02um are not well characterized and include such
substances as diesel exhaust and or a variety of indoor sources.
The major parts of the respiratory system include: Nasopharyngeal region or regions
including Nostrils to Larynx (throat); Tracheo bronchial region or regions including Trachea
(windpipe), bronchi, Bronchioles; and Pulmonary region or regions including the Lungs and
Alveoli. The normal adult breathing rate through the nose at seated rest condition is
approximately 12 breaths/min and the overall volumetric flow rate at this condition is
approximately 6L/min. The mouth dominates breathing at 34.5 L/min.
The respiratory system is one of the main points of entry for particle size
contaminants. Clearance mechanisms or respiratory protection mechanisms against
contaminates include: removal to digestive tract by cilia in Tracheo bronchia region;
phagocytosis or digestion by macrophages in the lungs; coughing is the rapid expulsion of air
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
27
from lungs; and sneezing, which is the rapid expulsion of air from nasal passages.
Susceptibility of respiratory system to air contaminates depends on size local air conditions
and velocity. As a result contaminate particles deposit non-uniformly through respiratory
system. Displayed in Appendix A.11 is a chart that shows the break down of respiratory
infections colds (Upper Respiratory Infections). Colds make up the largest single respiratory
infection, influenza will predominate colds during the flu season.
3.8 Air Quality Indicators
Recently indoor air quality (IAQ) has become an important issue and as a result
researchers have developed a number of different air quality indicators. Air quality Indicators
are represented values determined by the space and associated characteristics to show the
quality of air within that space. Two air quality indicators will be used for the purpose of this
study, normalized age of air (inverse to air exchange efficiency) and the contaminate removal
effectiveness.
Equation (4):
Tn = (T)/(Te)
Tn = Normalized age of air (Is the normalized age of air at point in the space.) T = Age of local air (Is the age of air at a point in the space.) Te = Age of air at exhaust (Is the shortest possible time needed for replacing the air in the room.)
Tn > 1 Represents less than ideal age of air. Tn = 1 Represents ideal age of air. Tn < 1 Represents better than ideal age of air
Equation (5): Te = 1 / (ACH) ACH = the number of air changes per hour in a room Equation (6): T = (Tn)/ (ACH) Equation (7): ε = (Ce – Cs ) / (Ca – Cs) ε = Contaminate Removal Effectiveness Ce = Concentration at the exhaust Cs = Concentration supplied to room
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
28
Ca = Concentration average in room
In the proposed steady the purpose of analyzing space concentration from contaminate by people nothing will be supplied into the space it is assumed that all contaminates introduced by the space leave space through exhausts. Therefore Contaminate Removal Effectiveness will be applied to specific points in space for analyzation of problematic regions: Equation (8): ε = (Ce) / (C) C = Concentration at a point in the room
ε > 1 Represents better than ideal conditions for contaminate removal conditions at a specific point.
ε = 1 Represents ideal contaminate removal conditions or perfect mixing at specific point. ε < 1 represents less than ideal contaminate removal condition at a
specific point Equation (9):
Ce = Σ (Md* Cd)/Σ (Md)
Md = Mass flowexhaust Cd = Concentrationexhaust
To obtain perceived indoor air quality indicators computational fluid dynamics CFD
will be used to calculate distributions of contaminate concentration and local age of air for
the four spaces proposed. The contaminant concentration distributions will be simulated for
secondary contaminants introduced into the space by occupants.
To do this several assumptions were introduced to obtain age of air and concentration
distributions. First, all results were obtained for steady state airflows, which is the case for
spaces where cooling /heating loads do not change rapidly. Influence of infiltration was
neglected, under assumption that the flow rate of the supplied fresh air through the inlets is
much larger than the flow rated cause by infiltration. This assumption of negligible
infiltration implies that there was no contamination inflow or out flow from adjacent spaces.
The final assumption is that contaminant distributions are not influence by different densities
of contaminants and no additional contaminates were introduced into the system through the
supply air terminals.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
29
3.9 Introducing spaces
A total of 4 multi-occupied spaces were simulated in Pheonic’s computational fluid
dynamic CFD program. Three of the spaces represent actual spaces in the INOVA Heart
Institute. These spaces are: the Ground Floor Transplant Waiting Room; the First Floor
Family Waiting Room; and the Second Floor Post Anesthesia Recovery Room. The fourth
space was simulation validating case, which was located at Centre County Community
Hospital and it was a Surgical Waiting Room.
INOVA Rendering 5: Simulated Spaces
INOVA Rendering 6: Simulated Spaces
First Floor Family Waiting
Second Floor Post Anesthesia Recovery Unit (PACU)
Ground Floor Transplant Waiting Room
CCC Hospital Surgical Waiting Room
Reflected Ceiling Plan Floor/Furniture Plan
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
30
3.10 Simulation Conditions In the following section is a rendering of a typical seen for each of the following
spaces originally created in 3D AutoCAD and then imported and simulated in Pheonic’s
CFD program. To follow each rendering is a list of important stats that were implemented
and observed for each space simulated. The point of the simulation was to achieve the
design thermal ambient conditions within the space.
Represented simulated values represent a snapshot in time at steady state condition
without transients, which may interrupt flow patterns. Steady state conditions mean flow
patterns have achieved their ultimate state (i.e. temperature, pressure, contamination, and age
of air) without transient interruption, such as movement by people. The reason for this is
because it is difficult to represent the unpredictability nature of people sitting and moving in
and out. This steady state assumption is applicable where people have tendency to be
stationary for duration of time (i.e. just sitting and waiting). The most likely areas for these
assumptions are away from doors and near corners.
The air quality in the occupant’s vicinity is the focus of ventilation design and
therefore, it is important to evaluate air quality in the occupied zone, which depends on the
ventilation strategy, contaminant source and room size.
In general it has been shown that displacement ventilation systems have overall better
performance in eliminating contaminates but are not the best in maintaining of uniform
thermal comfort overall or mixing of spaces and was not strategy simulated. The purpose of
this study is to maintain similar thermal condition while achieving better mixing of the space.
A dilution system with high ACH rate is what was originally designed for the spaces
analyzed. When it comes to temperature and humidity concerns the existing design strategies
that were implemented in these spaces were only modified in the way in which air was
discharged through the supply terminals or the relative location slightly modified.
For feasibility of cost and implementation this study will for the most part maintain
existing conditions and provide low impact solutions to minimize additional cost and
renovation.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
31
3.10.1 Simulation Conditions “Family Waiting Room”
INOVA Table and Rendering 9,7: Simulated Spaces Conditions
Space: Family Waiting Room
Room Numbers: 01PC29, 01PC28, 01PC27 Floor: 1 Simulated Cell Dimesions: Occupancy: 37 X Plain: 74 Floor Area (ft^2): 1296.73 Y Plain: 115 Volume (ft^3): 11672.2 Z Plain: 22 Volume of air (ft^3): 7669.3 Total: 187,220 Design SA TdB (F): 55 Simulated: Delta T (F) 14.36 Design RA TdB (F): 85 Simulated SA TdB (F) 62.4 Design Delta T (F): 30 Simulated RA TdB (F) 76.76 Design Ambient TdB (F): 72 Simulated Ambient TdB (F): 72 Simulation Iterations: 5000 Design CFM: 1200 Simulation Run Time (hours): 5 Design OA CFM: 360 Simulations Ran: 18 Req. OA CFM (Std. 62) 262.8 Simulated Loads: Air Changes Per Hour 9.4 People (Watts): 3700 Req. Air Changes Per Hour (Hospital): 6 Monitors (Watts): 80 Air Changes Per Hour OA: 2.8 Lights (Watts): 676 *Req. Air Changes Per Hour OA (Hospital): 2 Vending (Watts): 260 Floor Flux (Watts): 733.6 Total Design Load (Watts): 11384.40 Simulated Total Load (Watts): 5449.6 Total Design Load (BTUH): 38880 Simulated Total Load (BTUH): 18611.47
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
32
3.10.2 Simulation Conditions “Post Anesthesia Care Unit”
Space: Post Anesthesia Care Unit Room
Room Numbers: 02PD05,02PD06,02PD07,02PD10,02PD05 (A,B,C,D)Floor: 2 Simulated Cell Dimensions: Occupancy: 17 X Plain: 100 Floor Area (ft^2): 2043.04 Y Plain: 83 Volume (ft^3): 18387.7 Z Plain: 24 Volume of air (ft^3): 10320.7 Total: 199,200 Design SA TdB (F): 55 Simulated: Delta T (F) 10.93 Design RA TdB (F): 85 Simulated SA TdB (F) 66.2 Design Delta T (F): 30 Simulated RA TdB (F) 77.10 Design Ambient TdB (F): 72 Simulated Ambient TdB (F): 72 Simulation Iterations: 5000 Design CFM: 1585 Simulation Run Time (hours): 6 Design OA CFM: 475.5 Simulations Ran: 21 Req. OA CFM (Std. 62) 207.6 Simulated Loads: Air Changes Per Hour 9.2 People (Watts): 1700 Req. Air Changes Per Hour (Hospital): 6 Monitors (Watts): 490 Air Changes Per Hour OA: 2.76 Lights (Watts): 2288 *Req. Air Changes Per Hour OA (Hospital): 2 Floor Flux (Watts): 1000 Total Design Load (Watts): 15036.89 Simulated Total Load (Watts): 5478 Total Design Load (BTUH): 51354 Simulated Total Load (BTUH): 18708.466
INOVA Table and Rendering 10,8: Simulated Spaces Conditions
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
33
3.10.3 Simulation Conditions “Transplant Waiting Room”
Space: Transplant Waiting Room
Room Numbers: 00PB03,00PB05,00PB06 Floor: G Simulated Cell Dimensions: Occupancy: 52 X Plain: 111 Floor Area (ft^2): 1728.00 Y Plain: 72 Volume (ft^3): 16378.94 Z Plain: 20 Volume of air (ft^3): 11160.85 Total: 159,840 Design SA TdB (F): 55 Simulated: Delta T (F) 9.2 Design RA TdB (F): 85 Simulated SA TdB (F) 67.3 Design Delta T (F): 30 Simulated RA TdB (F) 77 Design Ambient TdB (F): 72 Simulated Ambient TdB (F): 72 Simulation Iterations: 5000 Design CFM: 3060 Simulation Run Time (hours): 6 Design OA CFM: 918 Simulations Ran: 25 Req. OA CFM (Std. 62) 363.7 Simulated Loads: Air Changes Per Hour 16.45 People (Watts): 4900 Req. Air Changes Per Hour (Hospital): 12 Monitors (Watts): 320 Air Changes Per Hour OA: 4.935 Lights (Watts): 2350 *Req. Air Changes Per Hour OA (Hospital): 2 Floor Flux (Watts): 1078 Kids (Watts): 225 Total Design Load (Watts): 29030.22 Simulated Total Load (Watts): 8873 Total Design Load (BTUH): 99144 Simulated Total Load (BTUH): 30303.07
INOVA Table and Rendering 11,9: Simulated Spaces Conditions
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
34
3.10.4 Simulation Conditions Validating Case: “CCC Hospital’s Surgical Waiting Room”
Space: CCC Hospital (Surgical Waiting Room)
Room Numbers: Surgical Wait
Date Surveyed: 3/10/2004 Floor: G Simulated Cell Dimensions: Occupancy: 22 X Plain: 86 Floor Area (ft^2): 294.85 Y Plain: 53 Volume (ft^3): 808.8433 Z Plain: 22 Volume of air (ft^3): 773.5377 Total: 100,276 Assumed Design SA TdB (F): 55 Simulated: Delta T (F) 13.2 Assumed Design RA TdB (F): 85 Simulated SA TdB (F) 62.6 Assumed Design Delta T (F): 30 Simulated RA TdB (F) 76 Design Ambient TdB (F): 75 Simulated Ambient TdB (F): 75 Design CFM: 698.1 Simulation Iterations: 5000 Design OA CFM: 210 Simulation Run Time (hours): 3 Req. OA CFM (Std. 62) 127.69 Simulations Ran: 16 Air Changes Per Hour 54.3 Simulated Loads: Req. Air Changes Per Hour (Hospital): 6 People (Watts): 2200 Air Changes Per Hour OA: 16.3 Lights (Watts): 620 *Req. Air Changes Per Hour OA (Hospital): 2 Floor Flux (Watts): 100 Total Design Load (Watts): 6622.87 Simulated Total Load (Watts): 2920 Total Design Load (BTUH): 22618.44 Simulated Total Load (BTUH): 9972.384
INOVA Table and Rendering 12,10: Simulated Spaces Conditions
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
35
CFD simulations were based on a constant flow and generation rates and performed
at steady state conditions. Accuracy of results will very greatly if performed at, non-steady
state, transient conditions. As a result many more simulations are necessary to provide more
accurate/real life solutions. Accuracy of results in the simulation are a function of size of
mesh created or the number of cells at which temperature, velocity, pressure, contamination,
and age of air are calculated over in a room. For simplicity walls and objects provided zero
diffusion or adsorption of contaminates (i.e. loss rate at which contaminate is re-emitted by
objects).
3.11 Normalized Age of Air Simulation Age of air is the time a particle of air travels from inlet to the point of interest and it is
a function of velocity and the path length followed. Normalized age of air is the age of air at
the point of interest divided by the time a particle travels from inlet to exhaust. If normalized
age of air in any region is greater than (1.0) then the point is less than perfectly well mixed
and stagnant regions can be visibly seen. Simulations were performed to compare the local
relative age of air at any point in the space with the ideal age of air, which is at the exhaust,
or return air. In general if flow increases along a path then stagnant regions or pockets will
decrease and the age of air goes will go down (flow velocities will increase in these areas).
For the purpose of these results normalized age of air will be considered only in the
horizontal breathing plane at a height of 1.3 meters or 4.26 feet unless other wised noted.
See Appendix A.11 for a reference diagram of the normal breathing plane.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
36
3.11.1 Normalized Age of Air Simulation “Family Waiting Room”
INOVA Rendering 11: Simulation of Normalized Age of Air & Scale
Scale: 0 represents 100 percent fresh air (occurs at inlets) < 1 represents better than perfect mixing 1 represents perfect mixing (occurs at outlets) > 1 represents less then perfect mixing (formation of stagnant pockets occurs) Breathing Plan at seated level or 1.3 m Color representation indicates that from a range of 1 to 1.5 that potential stagnant pockets occur in 3 areas within the space. Space without representative color contours represent normalized age of air better than perfect mixing ( < or = 1) or area of no concern.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
37
3.11.2a Normalized Age of Air Simulation “Post Anesthesia Care Unit”
INOVA Rendering 12: Simulation of Normalized Age of Air & Scale
Scale: 0 represents 100 percent fresh air (occurs at inlets) < 1 represents better than perfect mixing 1 represents perfect mixing (occurs at outlets) > 1 represents less then perfect mixing (formation of stagnant pockets occurs) Breathing Plan at seated level or 1.3 m Color representation indicates that from a range of 1 to 1.5 that potential stagnant pockets occur in 3 areas within the space. Space without representative color contours next to dark blue contours represent normalized age of air better than perfect mixing ( < or = 1) or area of no concern.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
38
3.11.2b Normalized Age of Air Simulation “Post Anesthesia Care Unit”
INOVA Rendering 13: Simulation of Normalized Age of Air & Scale
Scale: 0 represents 100 percent fresh air (occurs at inlets) < 1 represents better than perfect mixing 1 represents perfect mixing (occurs at outlets) > 1 represents less then perfect mixing (formation of stagnant pockets occurs) Breathing Plan at patient level or 1.1 m Color representation indicates that from a range of 1 to 1.5 that potential stagnant pockets occur in 1 area within the space. Space without representative color contours next to dark blue contours represent normalized age of air better than perfect mixing ( < or = 1)or area of no concern.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
39
3.11.3 Normalized Age of Air Simulation “Transplant Waiting Room”
INOVA Rendering 14: Simulation of Normalized Age of Air & Scale
Scale: 0 represents 100 percent fresh air (occurs at inlets) < 1 represents better than perfect mixing 1 represents perfect mixing (occurs at outlets) > 1 represents less then perfect mixing (formation of stagnant pockets occurs) Breathing Plan at seated level or 1.3 m Color representation indicates that from a range of 1 to 2 that potential stagnant pockets occur in 2 areas within the space. Space without representative color contours next to dark blue contours represent normalized age of air better than perfect mixing ( < or = 1)or area of no concern. Space without representative color contours next to bright red contours represent normalized age of air worse than perfect mixing ( > or = 2)or area of concern.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
40
3.11.4 Normalized Age of Air Simulation, Validating Case: “CCC Hospital’s Surgical Waiting Room”
INOVA Rendering 15: Simulation of Normalized Age of Air & Scale
Scale: 0 represents 100 percent fresh air (occurs at inlets) < 1 represents better than perfect mixing 1 represents perfect mixing (occurs at outlets) > 1 represents less then perfect mixing (formation of stagnant pockets occurs) Breathing Plan at seated level or 1.3 m Color representation indicates that from a range of 1 to 1.5 that potential regions of concern occur in 3 areas within the space Space without representative color contours next to dark blue contours represent normalized age of air better than perfect mixing ( < or = 1)or area of no concern.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
41
3.11.5 Normalized Age of Air Simulation, Regions of Most Concern
In the previous section simulated snap shots were provided for each of the four spaces
simulated at indicated breathing planes. Areas that were boxed out (red or green) were
considered areas of concern based on the normalized age of air. When determining the
regions of most concern for the normalized age of air analysis five points were considered:
quantity and location of people, location of breathing plane, location of entrances and exits,
overall function of space, and critical variations of the age of air within a space. If an area
within a space happens to have a dense population, away from major points of entrances and
exits, in a type of space where people may be situated for a duration of time, where
normalized age of air values exceed ideal values by a considerable percentage it was
considered a region of most concern of which a redesign may be required.
For the spaces excluding the validating case (Family Waiting and Post Anesthesia
Care Unit) the area’s of concern do not meet all the criteria for regions of most concern
established in this section for normalized age of air.
For the space which is the validating case (CCC Hospital, Surgical Waiting Room)
there is evidence that there are region of most concern based on the criteria established in this
section, but because it is not apart of the building which is the focus of this thesis and it will
not be closely looked at or considered for air distribution redesign
For the space, which is, the Transplant Waiting Room there is evidence that there are
regions of most concern based on the criteria established in this section and will be further
investigated closely looked at and considered for an air distribution redesign.
3.11.6 Normalized Age of Air Simulation, Closer look at Transplant Waiting
Room As shown in section 2.10.3 for the Transplant Waiting Room there are (2) areas of
concern that exist when performing the Normalized age of air simulations. After all
simulation were performed, through further investigation and verification with a contact from
the general contractors office it was determined that the area of concern boxed in green did
have an air supply not previously seen in the design documents. Subsequently, for the
purpose of the results previously simulated, it will be assumed that the normalized age of air
in this region is not an issue and will not be considered for redesign.
Closely looking at the remaining region it can be seen that the normalized age of air is
fairly diverse and is for the majority of the region greater than (1.0). This again means that
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
42
the region is not well mixed and stagnant area’s or pockets can visibly be seen. This may
pose an issue when contaminates are introduced by occupants situated in this region.
Contamination simulations will be done to prove the validity of this assumption.
INOVA Rendering 16: Simulation of Normalized Age of Air
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
43
3.12 Contaminate Removal Effectiveness, 100% Contamination Simulation
Contaminate Removal Effectiveness (CRE) is a ratio of the average exhausted
contaminates to the average number contaminates within the space. If the number of
contaminates in any region is greater than the average exhausted concentrations then that
region is less than perfectly well mixed and stagnant regions can be visibly seen. Areas
where CRE is less then or equal to (1) will be considered ideal conditions and no need to
modify. Simulations were performed to show the relative concentrations throughout the
breathing plan in order to compare with the average exhausted contaminates. The focus of
this analysis will only target secondary contaminates or contaminants introduced into the
space by its occupants. Therefore, for the purpose of this analysis it will be assumed that
supply air will be free from contaminates, this however is an idealized situation and is never
the case in actuality.
The reason for 100% contamination or contamination of all occupants in space at
capacity is to determine at worst case scenario the most problematic area in the space this
will enable one to address “ Regions of most concern” and alleviate problems or problem
areas as seen fit by the engineer. The rate of release of contaminates by an infected
individual will be 6200 droplet nuclei per hour or an equivalent 2.07 particles/m^3/second.
For the purpose of these results the Contaminate removal effectiveness ratio along with the
contaminate concentration will only be considered in the horizontal breathing plane at a
height of 1.3 meters or 4.26 feet unless other wised noted. See Appendix A.12 for a
reference diagram of the normal breathing plane. See Appendix A.13 for CRE calculations.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
44
3.12.1 CRE , 100% Contamination “Family Waiting Room”
INOVA Rendering 17: “CRE” & Scale
C(exhaust) = 106 particles/m^3 Concentration range set at 106 to 500 particles/m^3 Scale of concentrations: = 106 represents Contaminate Removal effectiveness of (perfect mixing) > 106 represents less than perfect mixing (formation of stagnant pockets occurs) < 106 represents better then perfect mixing Color representation indicates that from the given range of 106 (dark blue) to 500 (bright red) particles/m^3 that potential stagnant pockets occur in 1 major location of concern. Space without representative color contours next to dark blue contours represents normalized concentrations that are better than perfect mixing (< 106) or regions of no major concern. Space without representative color contours next to bright red contours represents normalized concentrations that are less than perfect mixing (> 500) or areas of major concern. Regions that are primarily greater than a concentration of 500 occur directly in front of infected and are to be expected and may be neglected.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
45
3.12.2a CRE , Non-Patient Contamination “Post Anesthesia Care Unit”
INOVA Rendering 18: “CRE” & Scale
C(exhaust) = 22 particles/m^3 Breathing Plan: 1.1 meters (for patient in bed ) Concentration range set at 22 to 500 particles/m^3 Scale of concentrations: = 22 represents Contaminate Removal effectiveness of (perfect mixing) > 22 represents less than perfect mixing (formation of stagnant pockets occurs) < 22 represents better then perfect mixing Color representation indicates that from the given range of 22 (dark blue) to 500 (bright red) particles/m^3 that potential stagnant pockets occur in 1 major location of concern. Space without representative color contours next to dark blue contours represents normalized concentrations that are better than perfect mixing (< 22) or regions of no major concern. Space without representative color contours next to bright red contours represents normalized concentrations that are less than perfect mixing (> 500) or areas of major concern. Regions that are primarily greater than a concentration of 500 occur directly in front of infected and are to be expected and may be neglected.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
46
3.12.2b CRE , Patient Contamination “Post Anesthesia Care Unit”
INOVA Rendering 19: “CRE” & Scale
C(exhaust) = 16 particles/m^3 Breathing Plan: 1.3 meters (for seated occupants) Concentration range set at 16 to 500 particles/m^3 Scale of concentrations: = 16 represents Contaminate Removal effectiveness of (perfect mixing) > 16 represents less than perfect mixing (formation of stagnant pockets occurs) < 16 represents better then perfect mixing Color representation indicates that from the given range of 16 (dark blue) to 500 (bright red) particles/m^3 that potential stagnant pockets occur in 1 major location of concern. Space without representative color contours next to dark blue contours represents normalized concentrations that are better than perfect mixing (< 16) or regions of no major concern. Space without representative color contours next to bright red contours represents normalized concentrations that are less than perfect mixing (> 500) or areas of major concern. Regions that are primarily greater than a concentration of 500 occur directly in front of infected and are to be expected and may be neglected.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
47
3.12.3 CRE , 100% Contamination “Transplant Waiting Room”
INOVA Rendering 20: “CRE” & Scale
C(exhaust) = 66 particles/m^3 Breathing Plan: 1.3 meters (for people sitting) Concentration range set at 66 to 500 particles/m^3 Scale of concentrations: = 66 represents Contaminate Removal effectiveness of (perfect mixing) > 66 represents less than perfect mixing (formation of stagnant pockets occurs) < 66 represents better then perfect mixing Color representation indicates that from the given range of 66 (dark blue) to 500 (bright red) particles/m^3 that potential stagnant pockets occur in 1 major location of concern. Space without representative color contours next to dark blue contours represents normalized concentrations that are better than perfect mixing (< 66) or regions of no major concern. Space without representative color contours next to bright red contours represents normalized concentrations that are less than perfect mixing (> 500) or areas of major concern. Regions that are primarily greater than a concentration of 500 occur directly in front of infected and are to be expected and may be neglected.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
48
3.12.4 CRE, 100% Contamination, Validating Case: “CCC Hospital’s Surgical Waiting Room”
INOVA Rendering 21: “CRE” & Scale
C(exhaust) = 107 particles/m^3 Concentration range set at 107 to 500 particles/m^3 Scale of concentrations: = 107 represents Contaminate Removal effectiveness of (perfect mixing) > 107 represents less than perfect mixing (formation of stagnant pockets occurs) < 107 represents better then perfect mixing Color representation indicates that from the given range of 107 (dark blue) to 500 (bright red) particles/m^3 that potential stagnant pockets occur in 1 possible location of concern. Space without representative color contours next to dark blue contours represents normalized concentrations that are better than perfect mixing (< 107) or regions of no major concern. Space without representative color contours next to bright red contours represents normalized concentrations that are less than perfect mixing (> 500) or areas of major concern. Regions that are primarily greater than a concentration of 500 occur directly in front of infected and are to be expected and may be neglected.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
49
3.12.5 CRE, 100% Contamination Simulation, Regions of Most Concern In the previous section simulated snap shots were provided for each of the four spaces
simulated at indicated breathing planes. Area’s that were boxed out (red) were considered
areas of concern based on the Contaminate Removal Effectiveness (CRE). When
determining the regions of most concern for the CRE of the space analysis five points must
be considered: quantity and location of people, location of breathing plane, location of
entrances and exits, overall function of space, and critical variations of the contaminate
concentration. If an area within had a dense population, away from major points of
entrances and exits, in a type of space where people may be situated for a duration of time,
where concentration values exceed ideal values removed by the exhaust by a considerable
percentage and where considerable concentration appear to engulf more than one person it
will be considered a region of most concern of which a redesign may be required.
By simulating the unlikely event of worst case scenario or a case where 100% of the
occupants is infected stagnant area’s become most evident and easy to see base on the
simulated pictures. In almost all simulations the highest contaminate concentration are
located around the infected individual or place of origin. This suggests that at these steady
state conditions that the highest concentrations will stay centralized around place of origin
and not inhibit others. By studying the presumed person’s breathing plane effects of
contamination from contaminated person next to a uninfected person it can be seen if for a
duration of time in area of low velocity or low flow quantity of air (i.e. stagnant pocket) that
one unhealthy individual may infect another healthy individual.
For the spaces excluding the validating case (Family Waiting and Post Anesthesia
Care Unit) the area’s of concern do not meet all the criteria for regions of most concern
established in this section for contaminate removal effectiveness at 100% contamination.
Simulations only give general idea of contaminate collection where flow patterns are not
varying with time further simulations must be done to prove it.
For the space which is the validating case (CCC Hospital, Surgical Waiting Room)
there is evidence that there is a region of most concern based on the criteria established in
this section, but because it is not apart of the building which is the focus of this thesis it will
not be closely looked at and considered for air distribution redesign
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
50
For the space, which is, the Transplant Waiting Room there is evidence that there are
regions of most concern based on the criteria established in this section and will be further
investigated closely looked at and considered for an air distribution redesign.
3.12.6 CRE, 100% Contamination Simulation, Closer look at Transplant Waiting Room
As shown in section 2.11.3 for the Transplant Waiting Room there is (1) area of
concern that exist when performing the Contaminate Removal Effectiveness simulation.
Closely looking at the region it can be seen that the contaminate concentration is fairly high
engulfing more than just one individual and is for the majority of the region greater than the
effective removal rate at which the return air ducts exhaust concentration levels This again
means that the region is not well mixed and stagnant area’s or pockets are present. This may
pose an issue when contaminates are introduced by occupants situated in this region.
INOVA Rendering 22: “CRE” Close Look
The results in this simulations show that due to improper air distribution that there is
a potential for concentrations to build up in hazardous areas or areas in which uninfected
people are at risk. A more likely verifying simulation must be done to show the affect of
what may actually occur if a single infected individual is to be located in this region. Areas
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
51
outside of the region of most concern have concentrations closer to the exhaust
concentrations as indicated by the dark blue contour (lower limit value of range is set to
equal exhaust concentrations). This suggests that concentration levels are adequate for
optimal removal from the space. Based on simulated alone results in area in which
normalized age of air and contaminate removal effectiveness simulations suggested not well
mixed regions do not necessarily mean that regions are concernable and should be
redesigned. Only through further investigation and simulation can results be truly validated
3.12.7 CRE, 1 Person Contamination Simulation, Closer look at Transplant
Waiting Room
INOVA Rendering 23: “CRE” Close Look
When simulating one infected individual in the region of most concern it can be see
that at the present steady state conditions. A considerable amount of contaminates collects in
front of another person’s face. The probe value indicates that at steady state an approximate
concentration of 120 particles per meter^3 are present in front of healthy individual.
Although this is a potentially considerable microbial concentration the likelihood of steady
state condition to occur in this corner region must be investigated (i.e. the time it takes to
occur). A dose as little as 20 microbes or CFU of influenza can cause infection in 50% or
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
52
more of the population. This concentration could yield a dose able to infect in 20 mins based
on the breathing rate of rested seated breathing rate (7.66L/min).
3.12.8 Determining the Duration of time for Steady State Conditions to Occur
For well-mixed models determining the steady state conditions is fairly simple and is
characterized by the following equation.
Equation (10):
(Ce – Ct)/( Ce – C0) = exp ( - Q/VxT) Where Q = (Surface area of entry) x (Average Velocity of air) Ce = is the steady state exhaust concentration Ct = the uniform concentration throughout the volume C0= is the concentration present at zero time Q = the total supply flow rate into the space V = is the Volume of the room T = the duration of time that steady state condition take to occur
Unfortunately as seen in the previous simulations well mixed conditions are not
present and in reality will never be present for any spaces. Therefore the above equation will
not apply to the entire space. For sake of simplicity a more approximate approach was taken
for determining the duration of time that steady state conditions take to occur. By taking an
approximate differential control volume, using measured values, directly in front of the
healthy individuals face in which contaminates appear to be present a rough estimate on
duration of time can be obtained for a 99% steady state condition of the approximate well
mixed volume Ce = 120 part/ m3 Ct= 120*0.99 = 118.8 part/m3 C0= 0 part/ m3 V = 2.0645E-4 m3 Surface Area of entry = 4.064 m2 Average Velocity of air= 0.08133 m/s
Duration of time at 99.99% Steady State = approximately 4 - 5 seconds These results suggest in the area of the two occupants, that at even semi steady state
conditions, that it would only take a matter of minutes before the healthy person is exposed
to high infecting concentrations less than or equal to the simulated 120 particles per meter ^3.
It must be remembered that the values that are obtained above are only a rough estimate and
are used to show that within such close proximity high concentrations may develop in the
region directly in front of a susceptible healthy individual, given steady state conditions. It
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
53
must be remembered though that this assumes that the sick individual is producing a constant
generation rate of contaminates. The following simulated picture shows the approximate
location of differential control volume along with flow arrows to show path of air in the
horizontal breathing plane.
INOVA Rendering 24: Duration Control Volume
3.13 1st Proposed Solution The first proposed solution will require the relocation of the two existing perimeter
four-way diffusers. The proposed solution would relocate the existing diffuser two feet over
and two feet up from their original position in the ceiling grid. This solution will require
increasing duct length and determining if any other equipment or piping in the upper plenum
space will be affected. Due to the complexity of upper ceiling plenum space, which may
contain piping for steam, medical gases (3 types), reheat, and preheat water for FCU and
CAV/VAV, telecom wiring, and general electric wiring, a constructability study will be
performed to deem that if relocation of diffusers are necessary is feasible. In the following
section, the original location of diffusers are marked in purple.
In the following re-simulated picture with the new diffusers it can be seen that the
overall concentration levels have been reduced drastically in the normal breathing plane and
that high concentration levels have been, for the most part, isolated to the place of origin or
to the infected individual from which they were generated from. The normalized age of air
has been considerably reduced and the previous region of concern has been reduced moved
away from the normal breathing plane to behind the occupants. Boxed in green are the
previous regions of main concern. Boxed in red are the new areas of concern that may result.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
54
3.13.1 1st Proposed Solution, CRE, 100% Contamination
INOVA Rendering 25: “CRE” & Scale
C(exhaust) = 66 particles/m^3 Breathing Plan: 1.3 meters (for people sitting) Concentration range set at 66 to 500 particles/m^3 Scale of concentrations: = 66 represents a Contaminate Removal effectiveness of (perfect mixing) > 66 represents less than perfect mixing (formation of stagnant pockets occurs) < 66 represents a better then perfect mixing Color representation indicates that from the given range of 66 (dark blue) to 500 (bright red) particles/m^3 that potential stagnant pockets occur in no major areas of concern Space without representative color contours next to dark blue contours represents normalized concentrations that are better than perfect mixing (< 66) or regions of no major concern. Space without representative color contours next to bright red contours represents normalized concentrations that are less than perfect mixing (> 500) or areas of major concern. Regions that are primarily greater than a concentration of 500 occur directly in front of infected and are to be expected and may be neglected.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
55
3.13.2 1st Proposed Solution, Normalized Age of Air
INOVA Rendering 26: Normalized Age of Air & Scale
Scale: 0 represents 100 percent fresh air (occurs at inlets) < 1 represents better than perfect mixing 1 represents perfect mixing (occurs at outlets) > 1 represents less then perfect mixing (formation of stagnant pockets occurs) Breathing Plan at seated level or 1.3 m Color representation indicates that from a range of 1 to 2 that potential stagnant pockets occur in 1 area within the space, behind occupant’s breathing plane. Space without representative color contours next to dark blue contours represent normalized age of air better than perfect mixing ( < or = 1)or area of no concern. Space without representative color contours next to bright red contours represent normalized age of air worse than perfect mixing ( < or = 2)or area of concern.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
56
3.13.3 1st Proposed Solution, CRE, One person Contamination
INOVA Rendering 27: “CRE” Close Look
In this simulation for one contaminated person the overall concentration levels in
front of the uninfected occupant to the right has decreased drastically by nearly 5 times to
approximately 20 particles per meter^3 as shown by the new probe value. The solution is
therefore expectable in reducing contaminates.
Surprisingly there were no significant increases or decreases in stratification of air
due to this change in the air distributions. This may be an issue if such redesigns are
considered and may be the focus of future studies. Also ambient temperatures in the region
appear to be approximately the same or better (i.e. no increase in temperature) in this high
occupancy region. This was all due to the flow patterns and throw increase by the proposed
solution.
It is important to remember that simulations only give an approximate estimate of
what concentration levels may be achieved given the conditions represented in each
simulation. Simulations done here have a mesh quantity of 150,000 to 200,000 the
approximate mesh size ranges from one inch near inlets and mouths to six inches over the
majority of the space. A contaminate particle size is roughly 1x10-8 to 1x10-6 meters in
diameter. The simulations that were performed had mesh sizes of no more than 200,000
cells, any more usually caused extremely long iteration time or crashed.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
57
3.14 2nd Proposed Solution The second proposed solution will require somewhat less work to implement as it is
only to replace the existing (2) diffusers with a combination of both two-way and three-way
diffusers.
The proposed solution would require that the diffuser closest to the corner be replaced
with a two diffuser and the diffuser located towards the bottom of the designated region be
replaced with a three way. This solution is very low impact and would require minimal cost
and effort to implement.
In the following re-simulated picture with the new diffusers it can be seen that the
overall concentration levels have again been reduced considerably in the normal breathing
plane and that high concentration levels again have been isolated to the place of origin. The
normalized age of air has been significantly reduced and the previous region of concern has
been reduced and moved away from the normal breathing plane to behind the occupants like
the previous solution. Boxed in green are the previous regions of main concern. Boxed in red
are the new regions of main concern.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
58
3.14.1 2nd Proposed Solution, CRE, 100% Contamination
INOVA Rendering 28: “CRE” & Scale
C(exhaust) = 66 particles/m^3 Breathing Plan: 1.3 meters (for people sitting) Concentration range set at 66 to 500 particles/m^3 Scale of concentrations: = 66 represents Contaminate Removal effectiveness of (perfect mixing) > 66 represents less than perfect mixing (formation of stagnant pockets occurs) < 66 represents better then perfect mixing Color representation indicates that from the given range of 66 (dark blue) to 500 (bright red) particles/m^3 that potential stagnant pockets occur in no major areas of concern Space without representative color contours next to dark blue contours represents normalized concentrations that are better than perfect mixing (< 66) or regions of no major concern. Space without representative color contours next to bright red contours represents normalized concentrations that are less than perfect mixing (> 500) or areas of major concern. Regions that are primarily greater than a concentration of 500 occur directly in front of infected and are to be expected and may be neglected.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
59
3.14.2 2nd Proposed Solution, Normalized Age of Air
INOVA Rendering 29: Normalized Age of Air & Scale
Scale: 0 represents 100 percent fresh air (occurs at inlets) < 1 represents better than perfect mixing 1 represents perfect mixing (occurs at outlets) > 1 represents less then perfect mixing (formation of stagnant pockets occurs) Breathing Plan at seated level or 1.3 m Color representation indicates that from a range of 1 to 2 that potential stagnant pockets occur in 1 area within the space. Space without representative color contours next to dark blue contours represent normalized age of air better than perfect mixing ( < or = 1)or area of no concern. Space without representative color contours next to bright red contours represent normalized age of air worse than perfect mixing ( < or = 2)or area of concern.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
60
3.14.3 2nd Proposed Solution, CRE, One person Contamination
INOVA Rendering 30: “CRE” Close Look
In this simulation for one contaminated person the overall concentration levels in
front of the uninfected occupant to the right has decreased more than the first proposed
solution by nearly 12 times to approximately 10 particles per meter^3 as shown by the new
probe value. The solution is therefore expectable in reducing contaminates. Surprisingly
there were no significant increases or decreases in stratification of air due to this change in
the air distributions. This may be an issue if such redesigns are considered and may be the
focus of future studies. Also ambient temperatures in the region appear to be approximately
the same or better (i.e. no increase in temperature) in this high occupancy region. This was
all due to the flow patterns and throw increase by the proposed solution.
3.15 Proposed Solutions, Cost Estimate
A cost estimate was done to show which solution was better. For nearly Half the
Price you get twice the effectiveness when removing contaminates from the regions of most
concern by selecting proposed solution #2 Cost include installation and contractors overhead
and profit based on costs provided by RS MEANS. Detailed cut sheets where costs were
obtained can be found in Appendix A.14.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
61
Proposed Solution # 1: Duct work Cost estimate Solution: 1 Length Inc. (Lft): 4
Dimesion of Duct (in): 10 x 8 90 elbow increase (Lft): 3
Perimeter of Duct (in): 36 Weight/Lft (lb/Lft): 9
Type of duct: S.S. 304 Cost/lb ($): 9.3
# ducts: 2 Above Avg Ins. Increase (%): 25
O & P Total Cost with Insulation ($): 1464.75 INOVA Table 13: Proposed Solution 1, Costs
Proposed Solution # 2: Diffuser Cost Estimate
Type : Cost ($): 2 - way, 24 x 24 380 3 - way, 24 x 24 380
O & P Total Cost ($): 760 INOVA Table 14: Proposed Solution 2, Costs
3.16 Summary When evaluating a space, it must be asked will the case ever exist that is potentially
dangerous to others. Hospital environments are not a place to question indoor air quality
especially with people with comprised immune systems. Solutions that were resolved in this
study were only simulated and not tested, therefore may not be best for these situations or
applicable to other situations. It must be understood that individuals are not all susceptible to
the concentration of contaminates in stagnant pockets deemed unsuitable by this study. The
basis of this research, I have preformed is only at worst case scenario and with the placement
of a single infected individual in regions deemed unsuitable.
The focus of this study was contaminates produced by occupants within multi-
occupied regions, in the normal breathing plane, where most inspiring and expiring occurs.
Two proposed solutions were investigated, that significantly reduced contaminates. The
question that still remains is, “What is safe enough?” So little is known about the effects of
pathogenic contaminates. Most microbes do not live long enough in air and peoples’
immune systems are not the same. The most common forms of viral transmission are
through direct contact, extreme close range with the infected person, and touching surfaces in
which contaminates are deposited. Close range contamination is based on flow patterns,
overall contaminate risk, and dose received. Because contaminates can pose such threat in
hospital environments something must be done to alleviate the problems experienced by
occupied spaces. This report tried to achieve solutions which were effective, efficient and at
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
62
minimal cost to the owner. The simulated results show that nothing can be perfectly
achieved, but methods explored can offer so help in alleviating and rectifying problems.
Although solutions explored do not suggest perfect contaminate removal
effectiveness they do provide better flow patterns, which displace and reduce contaminate
from the designated breathing plane. From the solutions it was seen that moving diffusers is
a more costly endeavor than changing diffuser types and if anything is to be done it is my
recommendation that changing diffusers is easier to maintain, fix, operate, and implement. It
is the most appropriate solution for hospitals such as the INOVA Heart Institute, which
already uses a complex combination of dilution ventilation (high air change rate) and
pressurization. Other systems such as displacement ventilation although better for
contaminate removal were not best solution due to stratification issues as well as complexity
of design for such large diverse spaces.
These simulated results can only approximate dose received by individuals. Unlike
the subjects used in the simulations people expel and inhale contaminates at different rates
and times. The amount that it takes to actually infect varies from person to person as well as
the environment which spreading occurs. The simulations can indicate areas of concerned
with in a space and can suggest ways to improve. The manor of expelling contaminates may
be the focus of another study to determine additional related issues such as deposition of
particles along with re-emitting from surfaces. In general the tendency in design is toward the use of performance standards. The
ability to estimate risk is vital in design. Modeling is one option that can provide us with the
ability to estimate such risks.
In the case of the INOVA Heart Institute it is still a hospital and it is my feeling that
such issues discussed should be assess and at minimum the system should provide proper
distributed air and comfortable climate. Also, the comfort in knowing that situations, if ever
occurs, have been taken into account when the designing the air distribution system.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
63
4.0 Constructability Analysis (Breathe Study)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
64
4.0 Constructability Analysis (Breathe Study)
4.1 Background To reduce contaminates in regions deemed of most concern. The redesign of air
distribution system is necessary in this region. Effects of previously simulation require
diffusers to be move to new location in ceiling grid approximately a distance of 4 ft from
original location. Associated ductwork will have to be lengthened to accommodate the new
locations.
4.2 Introducing the Space The Transplant Waiting Room will be the focus of this analysis. Approximate
dimesions and volumes can be found in section 2.9.3 of this report. Below is an AutoCad 3D
rendered image of the space. Diffusers to be relocated are circled in purple.
INOVA Rendering 31: Transplant Diffuser Relocation
4.3 Problem The problem with moving diffusers may cause issues with other equipment and
piping located in the upper plenum space. These obstacles may cause a costly relocating and
displacing issue.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
65
4.4 Plan of Attack As stated previously the purpose of this investigation is to investigate the upper
plenum space above the Transplant Waiting Room in the INOVA Heart Institute. The
following steps will be done as a result to this investigation.
1. Locate location of equipment, piping, ducting, conduit, and structural features
within the upper plenum space using the design documents.
2. Create a 3D coordination section based on original design documents using
AutoCAD.
3. Develope schedule for approximate sequencing of trades for original design.
4. Create a 3D coordination section based on new design documents using
AutoCAD.
5. Determine how schedule of sequencing of trades is impacted and effected for
new design.
4.5 Investigation of Upper Plenum Space Through investigation of the design documents the following appears to be located in
the upper plenum space.
1. Piping a. Primary Heat Supply lines b. Re-Heat Supply lines for Terminal Reheat Units c. Domestic Water lines d. Fire lines
2. Ducts a. Primary Supply Air to Space b. Primary Return Air from Space
3. Conduit a. Electric to recessed lighting b. Electric to various room sensors c. Telecom to PA speakers
4. CAVs a. One Terminal Reheat Unit
5. Fire protection a. Sprinklers for space below
6. Lighting a. Recessed Lighting for space below
To follow is an actual photo of the installation phase of the Mechanical, Electrical,
and Plumbing MEP taken in the summer of 2003.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
66
INOVA Photo 4: MEP Coordination
4.6 3D Coordination Section Before Redesign The following is a rendering of the Transplant Waiting Space and associated original
design of the upper plenum space. Diffusers to be relocated are circled in purple. CAV is
hidden from view by airside ducting. Rendering only shows major MEP and Structural
concerns.
INOVA Rendering 32: Original Transplant Diffuser Location
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
67
4.7 Schedule, Sequencing of Trades The following is a schedule for the sequencing of trades based on the evaluation of
the design documents.
1. Main electrical wiring in conduit 2. Waterside piping (list types) 3. Mechanical Equipment (CAV)
a. Connections to reheat water b. Connections to electrical and building automation control system
4. Airside Ductwork a. Includes insulation and taping terminal units
5. Fire Sprinklers a. take offs from main fire line to sprinkler
6. Telecommunications a. sound and paging runs
7. Installation of drop ceiling and fixtures a. Recessed lighting installation and electrical connection b. Diffuser installation and connection to airside equipment c. Sprinkler head installation and connection to fire line take-offs
4.8 3D Coordination Section After Redesign The following is a rendering of the Transplant Waiting Space and associated redesign
of the upper plenum space. Relocated diffusers are circled in purple. Rendering only shows
major MEP and Structural concerns.
INOVA Rendering 33: Transplant Diffuser Relocation
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
68
4.9 Impact of Redesign As shown in the investigation and by detailed coordination sections it is assumed that
no major obstructions (MEP or Structural) were incurred when relocating the ductwork. The
redesign could have been implemented in the original design phase or as a later renovation.
4.10 Summary Through investigation it was determined that the minor redesign of the upper plenum
space was feasible. No major obstructions were to be found. The structural aspect of the
upper plenum space is free from concrete beams, which only appear to be above the middle
and opposite ends of the room near mechanical and elevator shafts. Drop panels (4 inches in
depth) exist above perimeter columns outside the space and pose no issue either. No major
penetration was necessary as no full height (floor to floor) walls were present above the
space. This led to no additional changes needed to be made for fire protection concerns.
The overall depth of the plenum space is approximately 4 feet and much clearance is
available in the region of concern.
If the proposed redesign is to be implemented after initial construction verification of
assumptions based off the design documents must be surveyed. Minor issues that may be of
concern only exist when talking about relocating sprinkler heads and associated take-offs
from the main line. As such locations could not be determined by the design documents.
The redesign of ductwork will be required to maintain existing heights and only lengthened
in the horizontal direction. This is to avoid any interference with existing piping or conduit
take-offs.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
69
5.0 Daylighting Analysis (Breathe Study)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
70
5.0 Daylighting Analysis (Breathe Study) 5.1 Background
The INOVA Heart Institute contains approximately 150 patient recovery rooms. Of
these 96 are located around the perimeter of the building and contain acess to windows.
Overall the 400,000ft^2 facility contains approximately 22,726 ft^2 of glazing that is
exposed to the outside.
5.2 Introducing the Space Below is a computer rendered image of a typical patient room along with the
associated floor plan. Each room contains one bed and has access to one shared bathroom.
The approximate area of the patient room is 294 ft^2. The exterior wall area is
approximately 84 ft^2 and the window glazing area is approximately 35 ft^2 for each room.
INOVA Rendering 34,35: Typical Perimeter Patient Room and Floor Plan
5.3 Problem/Solution As stated previously the total exterior glazing area is just under 23,000 ft^2. With
such high amounts of glass exposed to the outside an increase in mechanical loads can be
expected due to solar gain during the day as well as associated losses of heat during the night.
The overall impact on the mechanical system results in wasted energy due to building
envelope design especially for a facility that is operating 24 hours a day. The purpose of this
study will be to optimize the effects described above without decreasing recommended
values of natural daylight. This will be done in hopes of reducing the overall load on the
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
71
mechanical system which will translate to annual energy savings for the owner. The redesign
for the perimeter patient windows may require renovation of the existing curtain wall façade,
which will also be studied.
5.4 Plan of Attack The proposed solution for this study will be to optimize the glazing area of 96 typical
perimeter patient rooms which will reduce mechanical load and meet recommend natural
daylight illuminances for each space. The following steps will be performed as a result to
this investigation.
1. Determine optimal glazing area based on room characteristics and location of
Facility.
2. Simulate typical patient room to see if recommended natural daylight values
are met.
3. Determine building load and energy usage and estimated HVAC operating
cost.
4. Determine impacts of exterior curtain wall façade.
5. Provide cost analysis of redesign 6. Determine feasibility of implementing redesign.
5.5 Determination of Optimal glazing Much Research was done to determine glazing area that reduces loads while
maintains optimal area for daylight transmission into the space. In a study performed by the
National Renewable Energies Laboratory (NREL) on passive solar architecture the
recommended area of a passive solar feature such as azimuth facing windows is
approximately 10% of the floor area for the region of the country nearest to Washington DC.
This figure is suppose to account for the reduction solar gains in cooling months (March to
September) and increase solar gains in heating months (October to February).
The area of typical patient room is approximately 21’ x 14’ or 294 ft^2. The suggested
window glazing area is approximately 29 ft^2 for the patient room The idea of “ Effective Aperture” for estimates of the optimum glazing area was next
used. Effective Aperture is a relationship that is dependent upon both aperture (window
area) size and visible transmittance as an effective determinant to measure illumination
levels. When the effective aperture, the product of the window to wall ratio and the visible
transmittance of the glazing, is approximately 0.18, daylighting saturation will be achieved.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
72
Additional glazing area or light will be counterproductive because it will increase the cooling
loads more than it will reduce the lighting loads. In maximizing daylight benefits and
minimizing mechanical operating cost the following equation was obtained and used to
determine optimal window to wall ratio for window area in the typical patient rooms.
Equation (11):
EA = wwr * vt = 0.18
(vt) = visible transmittance (wwr) = window to wall ratio (EA) = effective aperture
The visible transmittance of the glazing is 55% (Given by Manufacturer, Appendix
B.1). This means that the optimal window to wall area is 0.323 or 32%. The current window
to wall area for a patient room is (35ft^2)/(84ft^2) or 42%. Multiplying this result by the
visible transmittance of 55% gives and effective aperture of 0.23, which is greater than the
recommended value of 0.18 and can be reduced. If the window to wall ratio is reduced to the
recommended value of 32% producing and effective aperture of 0.18 then the area of the
window would be 28ft^2. This attribute can be useful in evaluating the cost effectiveness and the daylighting
potential of a schematic building configuration. The location and height of the window will
determine the distribution of the light admitted as well as the depth and penetration. One rule
of thumb states that the depth of daylight penetration should be about 2.5 times the distance
between the top of a window and the windowsill or approximately ¾ the depth of the room.
5.6 Daylight Simulations From the results in the previous section, the new window area will be simulated into
AGI to see if the minimum recommended daylight factor is met for all perimeter /exterior
facing patient rooms. The window area that will be used for each patient room will be
approximately 28 ft^2 dimensions: 4’-8” x 6’-2 ¼”.
5.6.1 Daylight Simulations, Daylight Factor
The daylight factor at a point in an interior is the ratio of the illuminance produced at
that point by daylight (excluding sunlight) from a sky of known or assumed luminance
distribution to the illuminance on a horizontal plane due to an unobstructed hemisphere of
this sky. No actual information provided that indicates required daylighting for hospitals
environment (i.e. patient room). At the recommendation from the lighting advisor patient
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
73
rooms will liken to bedrooms of house. From the INESA Handbook the a chart
recommending daylight factors and sunlight exposures for a bedroom states: “A minimum
0.5% daylight factor should cover at least 5.6 square meters with the penetration of this zone
being not less than ¾ of the depth of the room facing the window.” In Appendix B.2 the
layout of a typical patient room is shown along with the recommended values indicated
above.
In a conducted study shown in Daylighting Performance and Design about, “25% of
window wall area was the minimum acceptable window size for 50% of the observers but
this had to be increased to about 32 % if 85 % of the people were to be satisfied.” In general
the study recommended that window sizes should be somewhere between 20% and 40% of
the window wall area. If below 20% dissatisfaction will arise. If above a 40% level
satisfaction with window area will be high but unless special measures are taken, such as a
solar control glass, the incidence of thermal and visual discomfort is likely to increase.
5.6.2 Daylight Simulations, AGI The purpose of simulating daylight exposure to each room is to determine if the
minimum 0.5% daylight factor is met in all of the 96 perimeter patient rooms. The following
table illustrates the internal and external reflectance and transmittance values used to perform
such simulations.
Room Type: Perimeter Patient Height above ground (ft): 20
Simulated Room Criteria Feature Reflectance (%): Transmittance
Wall: 0.6 - Floor: 0.3 - Ceiling: 0.8 - Furniture: 0.5 - Window: 0.3 0.55
Ground (outside ) : 0.23 -
INOVA Table 15: Space Design Characteristics
The simulated rendering shown below illustrates South East isometric view of (4)
patient rooms used to perform the simulations. The rooms will be facing: North, South, East,
and West at an elevation of 20 feet (First floor height).
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
74
INOVA Rendering 36: Typical Perimeter Patient Room
This rendering shows the simulation, which was performed on June 21st or the
Summer Solstice (Longest day of the year) at noon. The simulations will also be performed
on December 21st or Winter Solstice (Shortest day of the year) and on March 21st or Vernal
Equinox (Middle day of the year) also at noontime. For the purpose of this daylight analysis
only illuminance levels will be considered at the peak point in the day or noon. The
simulated values obtained for external illuminace and the associated internal illuminace
needed to meet the minimum daylight factor or shown in the table below. Simulations were
also performed at 8am and 4pm and results can be found in Appendix B.3. Location: Washington D.C. Conditions: Overcast Recommended Daylight Factor (%): 0.5
Time Performed: 12pm External Illumance (fc): Internal Illuminance needed (fc): March 21st
(*Vernal equinox) 6719 33.595June 21st
(Summer solstice) 8920 44.6December 21st
(Winter solstice) 3133 15.665
*Autumnal equinox will produce the same results as the Vernal equinox and will not be simulated.INOVA Table 16: Internal and External Illuminaces
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
75
These are a sample of simulated daylight views rendered in AGI for the typical patient room on June 21st at noon. INOVA Rendering 37: East view (Noon, June 21) INOVA Rendering 38: West view (Noon, June 21) INOVA Rendering 39: South view (Noon, June 21) INOVA Rendering 40: North view (Noon, June 21)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
76
These are illuminace daylight calculations experienced by the room which were performed in AGI for the typical patient room during 3 times of the year at noon. The green contour represents where the minimum internal illuminace values needed no longer meet the recommended values. The window location is locate on the left side of the layout. INOVA AGI Calcs. 1: East View (Noon, June. 21) INOVA AGI Calcs. 2: West View (Noon, June. 21) INOVA AGI Calcs. 3: South View (Noon, June. 21) INOVA AGI Calcs. 4: North View (Noon, June. 21)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
77
These are illuminace daylight calculations experienced by the room which were performed in AGI for the typical patient room during 3 times of the year at noon. The green contour represents where the minimum internal illuminace values needed no longer meet the recommended values. The window location is locate on the left side of the layout. INOVA AGI Calcs. 5: East view (Noon, Dec. 21) INOVA AGI Calcs. 6: West View (Noon, Dec. 21) The representative contour for south view is not present because the entire space meets the minimum requirements for daylight. INOVA AGI Calcs. 7: South View (Noon, Dec. 21) INOVA AGI Calcs. 8: North View (Noon, Dec. 21)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
78
These are illuminace daylight calculations experienced by the room which were performed in AGI for the typical patient room during 3 times of the year at noon. The green contour represents where the minimum internal illuminace values needed no longer meet the recommended values. The window location is locate on the left side of the layout. INOVA AGI Calcs. 9: East view (Noon, Mar. 21) INOVA AGI Calcs. 10: West View (Noon, Mar. 21) The representative contour for south view is not present because the entire space meets the minimum requirements for daylight. INOVA AGI Calcs. 11: South View (Noon, Mar. 21) INOVA AGI Calcs. 12: North View (Noon, Mar. 21)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
79
From the daylight simulation analysis it can be seen that minimum daylight factor
requirements are met determined in section 4.6.1 of this study and that the window
reduction is possible.
5.7 Building Loads and Operating Cost From the table shown below the windows that will be involved in the redesign
equate to approximately 15% of the the total glazing of the building. The total reduction
in actual window area (594ft^2) will be approximately 3%.
Window investigated: Direction Quantity West: 39 East: 15 North: 18 South: 24 Total windows: 96 Total window area (ft^2): 3360 Total Building window area (ft^2): 22,726 Percentage of Building (%): 14.78 Reduction in window area (%): 2.7
INOVA Table 17: Windows Investigated To determine the building loads, total energy consumed, operating cost by the
new facility and entire energy analysis was performed in Carrier’s Hourly analysis
program for the entire facility (301,967 ft^2).
Annual Site Energy Consumed after window
reduct Before Window
Reduction after window
reduct Before Window
Reduction Component (kBTU) (kBTU) (kBTU/ft²) (kBTU/ft²) Air System Fans 21,732,518 21,732,518 71.97 71.97Cooling 12,166,450 12,116,354 40.291 40.125Heating 40,509,900 41,592,020 134.153 137.737Pumps 3,698,295 3,698,203 12.247 12.247Cooling Tower Fans 3,487,921 3,482,731 11.551 11.534
HVAC Sub-Total 81,595,084 82,621,825 270.211 273.612
after window
reduct Before Window
Reduction after window
reduct Before Window
Reduction Component (kBTU) (kBTU) (kBTU/ft²) (kBTU/ft²) Cooling Coil Loads 81,472,616 81,077,472 269.806 268.497Heating Coil Loads 33,936,824 34,836,708 112.386 115.366Grand Total 115,409,440 115,914,180 382.191 383.863Conditioned Floor Area (ft²) 301967.7 kBTU/yr Savings with new system implemented: 1,026,741
INOVA Table 18: Annual Energy Consumed
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
80
From the table shown in the previous page it can be seen that the annual
mechanical load was reduced by approximately a million kBTU/yr. The total mechanical
load before window reduction was estimated at 82.6 million kBTU/yr and after
approximately 81.6 million kBTU/yr. The total reduction is approximately 2% of the
original design. In terms of annual operating cost ($) this translate to approximately
$2400 a year. The total mechanical operating cost before window reduction was
estimated at $430,100 and after approximately $432,500.
Annual Cost Summary To Operate
after window reduct
Before Window Reduction
after window reduct
Before Window
Reduction Component ($) ($) ($)/ft^2 ($)/ft^2 Air System Fans 189,978 190,311 0.629 0.63 Cooling 102,932 102,787 0.341 0.34 Heating 75,207 77,293 0.249 0.256 Pumps 32,329 32,384 0.107 0.107 Cooling Tower Fans 29,671 29,685 0.098 0.098
HVAC Sub-Total 430,116 432,460 1.425 1.432 Conditioned Floor Area (ft²) 301967.7 $/yr Cost Savings with new system implemented 2,344
INOVA Table 19: Annual Energy Consumed
5.8 Impact on Exterior Façade
Below is an elevation of the typical patient room looking at the window
exposed to the outside. Highlighted in red is the approximate window reduction from the
redesign.
INOVA Rendering 41: Interior Patient Room Elevation
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
81
The original dimensions and area of the window are 5’-8” x 6’-2 ¼” and 35 ft^2
Area highlighted in red represents the new window dimensions and area which are 4’-8”
x 6’-2 ¼” and 28ft^2. The change in total area per window per room is 6.2 ft^2. The
total reduction in window area for the 96 rooms is approximately 594 ft^2. Below is an
external view of the elevation for a typical patient room a spandrel glass curtain wall
façade surrounds the patient room window. A typical wall section can be found in
Appendix B.4.
INOVA Rendering 42: Exterior Patient Room Elevation
Structurally the loads for proposed new design do not change relatively much and
will not be analyzed at the suggestion of structural advisor. This is primarily due to the
fact that in the absence of existing window glass, similar curtain wall spandrel glass and
insulation will be replaced along with an extra vertical mullion separating existing
spandrel glass and new spandrel glass to secure the replacement. Replacement spandrel
glass will be used to reduce the cost of replacing a new oversized piece of spandrel glass.
5.9 Cost Analysis The following is a cost analysis on the components that will be changed as a result of
redesigning the window.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
82
In Appendix B.5 are the associated cost cut sheets provided by RS MEANs.
Window Renovation Cost
Feature $/ft^2 $/unit ft^2 replaced $/room # rooms Total cost
Interior wall: 4.66 - 6.2 28.892 96 2773.632
New window ( 4’-8” x 6’-2 ¼”): - 1735 - 1735 96 166560
Old window ( 5’-8” x 6’-2 ¼” ): - 2107 - 2107 96 202272
Mullion Framing (spandrel Glass): 8.6 - 6.2 53.32 96 5118.72 Painting Interior Walls: 0.84 - 6.2 5.208 96 499.968 Spandrel Glass replacement: 17 - 6.2 105.4 97 10223.8
Curtain wall/Ins. hardware (15% S. Glass): - - - - - 1533.57
Total Cost of Original window: 202272
Total Cost of new window and modifications: 186709.69
Cost Savings from Original Design: 15562.31INOVA Table 20: Window Renovation Cost
The new design would have savings on original design if implemented as the
original design. The annual savings in HVAC Operating cost would be a year $2344
approx. Based on information provided by local consulting firm based out of
Washington DC the typical assumed value for demolition and removal of existing
material such as curtain wall and window facades is approximately 25 % of initial cost.
This means that if the redesign was implemented after original construction that
additional $46,677 would be tacked on to the total cost of the new window and
modifications cost of $186,709 or a total cost of $233,387. This is obviously not a wise
choice if the annual mechanical operating cost savings is only 1% of the new renovation
cost $2344 per year.
5.10 Feasibility of Results. The only way that the new design would be acceptable is if it was initial
implemented as an addendum to the original design before construction. Again, the new
design would have saved approximately $ 15,000 and saved on mechanical operating
costs which was estimated to be $2344 a year. It must be realized that this is all with
respect to loosing 20% of the original window area in the perimeter patient rooms.
Values are only estimated and simulated approximations of cost and may vary.
5.11 Summary The potential for savings through daylighting is affected by location, climate,
building use, and building form. Through the investigation of optimizing of natural
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
83
daylight it was determined that reducing overall glazing area to achieve mechanical
operating cost benefits was not effective. This is due to the small fraction of actual glass
area that was reduced and the cost of implementation to actually change the windows.
The facility in general is rather large is operational all the time, the cost benefits were
minimal compared to overall mechanical operating cost and sufficient savings were not
realized because of this. It must be noted that the building does have premium quality
glazing with Low-E glass which does perform a valid service when saving energy.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
84
6.0 Conclusions
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
85
6.0 Conclusions Integration and coordination of the proposed redesigns required analysis of many
different fields of design. Solutions for redesign were researched, consulted upon,
simulated, assessed and reviewed and not all proposed solutions had positive benefits.
The use of simulation programs gives a good indication of what problems or
benefits a system may encounter. Simulations are only as accurate as the programmer
can make them. They do not in any way perform 100% perfect results or simulate every
aspect or variable in real life situations. Yet simulation such as AGI(Lighting), Carrier’s
Hourly Analysis Program(Mechanical), and Pheonics (CFD) program may and do give,
an indication of what may occur and maybe of value to the engineer before actual
implementation of a system or building. These are an excellent resource in determining
risks and system feasibility, provided that they are correctly used and tested many times.
.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
86
7.0 Credits and Acknowlegements
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
87
7.0 Credits and Acknowlegements
1. I would like to thank the INOVA Health Care System for letting me use their facility.
2. I would like to thank Turner Construction:
John Almquist Quiton Cooper
3. I would like to thank Centre County Community Hospital: William Stranahan
4. I would like to thank the following MEP engineering consultants: Jim Hoffman Jim Stewart Ann Juran Chris Skoug
5. I would like to thank the Penn State Architectural Engineering Department:
Professor Srebric Professor Friehaut Professor Bahnfleth Professor Mumma Professor Moeck Professor Mistrick
6. I would like to thank the Penn State Architectural Engineering Graduate students:
Atila Novoselac Yazhuo Qian
7. I would like to thank some of the graduating Penn State Architectural Engineering Students (no specific order):
Ben Hagan Jackson Burham Jarod Stanton Joe Firrantello Adam Sontag Sara Lham Lincoln Harberger David Walenga David Clark Katie Trail Mike Carrol Nick Maffeo Craig Dubler Lindy Stowell……
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
88
8.0 References:
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
89
8.0 References: 1. “Aerobiological Engineering,” http://www.arche.psu.edu/iec/abe/,
March 2004 2. ASHRAE Standard 62-2001, Energy Standards for Buildings. 3. ASHRAE Special Project 1991, “HVAC Design Manual for Hospitals and Clinics,” Atlanta, GA, ASHRAE, 2003. 4. ASHRAE Handbook, “Fundamentals,” ASHRAE, 2001 5. Allen, Edward, “Fundamentals of Building Construction Materials and
Methods,” New York, NY, John Wiley & Sons, 1999.
6. Ander. D Gregg, “Daylighting Performance and Design,” Jon Wiley and Sons, Inc., 2nd Edition, Hoboken, NJ, 2003
7. Balboni, Barbara, “, Assemblies Cost Data,” Kingston, MA, RS MEANS, 28th Edition, 2003.
8. Beggs C.B., “Engineering the Control of AirBorne Pathogens,” http://www.efm.leeds.ac.uk/CIVE/MTB/CBB-paper1.pdf, January 2004 9. Beggs C.B., “The Use of Engineering Measures to Control AirBorne Pathogens in Hospital Buildings,”
http://www.efm.leeds.ac.uk/CIVE/MTB/CBB-Nov8.pdf, March 2004
10. Boyce, P.R., “Human Factors in Lighting,” London, UK, Taylor and Francis Publishing, 2003. 11. Ching, Francis D.K., “Building Construction Illustrated,” New York, NY, John Wiley & Sons, 1991. 12. Dunn, Charles E., Lumalier, “Meeting on UVGI,” Summer Intern, 2003. 13. Heinsohn, Robert., “Indoor Air Quality Engineering,” New York, NY, Marcel Dekker, 1999. 14. Kowalski, Wladyslaw J., “Immune Building Systems Technology,” New York, NY, McGraw Hill, 2003. 15. Kowalski, Wladyslaw J., “Airborne Respiratory Diseases and Mechanical Systems for Control of Microbes,” HPAC, July 2003.
16. Lindeburg, Micheal R., “Engineering Economic Analysis,” Belmont, CA,
Professional Publications, 2001.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
90
17. Linscomb, Mike., “Aids Clinic HVAC System Limits Spread of TB,”
HPAC, February 1994.
18. Mossman, Melville J., “, Mechanical Cost Data,” Kingston, MA, RS MEANS, 26th Edition, 2003.
19. Novoselac, Atila., “Comparison of Air Exchange Efficiency and Contaminant Removal Effectiveness as IAQ Indices,” ASHRAE, 2003 20. NREL “Renewable Energy; A Guide to the New World of Energy Choices,” http://www.nrel.gov , March 2004 21. Pederson, Curtis O., “Cooling and Heating Load Calculation Principles,” Atlanta, GA, ASHRAE, 1998. 22. Rea, Mark S., “The IESNA Lighting Handbook, Reference and Application,” New York, NY, IESNA Publications Department, 9th Edition, 2000. 23. THERMIE, ”Daylighting in Buildings” http://erg.ucd.ie/mb_daylighting_in_buildings.pdf, November 2003. 23. Turner Construction, Construction Drawings, Shop Drawings and Specifications.
24. Virginia Power,”Schedule GS-3U” http://www.dom.com /customer/pdf/va/vags3u.pdf
26. Washington Gas Light Company, ”Commercial and Industrial Service Schedule No. 2”
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
91
9.0 Appendix:
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
92
9.1 Appendix A.1:
Appendix Table A1: Relative Size of Airborne Pathogens(15)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
93
9.1 Appendix A.2:
Appendix Table A2: Classifications of Respiratory Pathogens and Sizes(15)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
94
9.1 Appendix A.3
Appendix Table A3: Classifications of Respiratory Pathogens and Sizes(15)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
95
9.1 Appendix A.4
Appendix Table A4: Profile of Particle Sizes Produced by an Infectious Person(15)
9.1 Appendix A.5
Appendix Table A5: Communicable Respiratory Infections Characteristic(15)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
96
9.1 Appendix A.6
Appendix Table A6: Viability of Airborne Microbes Indoors in Absence of Sunlight(15)
9.1 Appendix A.7
Appendix Table A7: Disappearance of airborne sneeze droplets from room air by size(15)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
97
9.1 Appendix A.8
Appendix Table A8: Approximate Particle Settling Times(PSU-AE.552)
9.1 Appendix A.9
Appendix Table A9: Routes of Infection of Colds(15)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
98
9.1 Appendix A.10
Appendix Table A10: Source of Cold Virus Dispersion(15)
9.1 Appendix A.11
Appendix Table A11: Breakdown of Respiratory Infections(15)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
99
9.1 Appendix A.12
Appendix Table A12: Breakdown of Respiratory Infections(14)
Appendix Table A12: Breakdown of Respiratory Infections(14)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
100
9.1 Appendix A.13
*Survey Temperature Surface Measurements At Centre County Community Hospital (Used Infrared Temperature Sensor Gun) Simulated CFD Results: Ceiling @ diffuser (Tdb): 62.59 Ceiling @ diffuser (Tdb): 62.59 Back Wall (Tdb): 77 Back Wall (Tdb): 76.038 Front Wall (Tdb): 76 Front Wall (Tdb): 75.2 Left Wall (Tdb): 76.8 Left Wall (Tdb): 76.69 Right Wall (Tdb): 77 Right Wall (Tdb): 76.5 Floor @ Center (Tdb): 76.2 Floor @ Center (Tdb): 74.2
Appendix Table A13a: Validating Surface Temperature Measurements
Appendix Table A13b: Validating Flow Measurements
Appendix Table A13c: Validating Ambient Temperature Measurements
* Measurements performed at the survey done on 3/10/04 along with the CFD simulated results. Variation from measure data and simulated data only vary at most by +/- 2 degrees Fahrenheit. Measured Flows were simulated in CFD.
*Surveyed Flow Measurements: Centre County Community Hospital (Used Flow Funnel over 20 minute period) Average Flow from solo diffuser CFM: 698.4(Notes: Very large flow rate for size of room – very loud)
*Surveyed Ambient Temperature Measurements: Centre County Community Hospital (Used Heat Stress Monitor)
Ambient Temperature (Tdb): 75.4
Ambient Temperature (Twb): 58.1
Ambient Temperature Simulated (Tdb): 75.1(Ambient Temperature taken over 15 minute period)
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
101
9.1 Appendix A.14
Appendix Table A14: Established Breathing Plane(19)
9.1 Appendix A.15
Contaminate Removal Effectiveness (100% infected):
Space: Family Waiting Room
X: 105Y: 104Z: 98.6
Concentration Avg in plans: (C)
Comb. Avg: 102.53
Concentration Avg at Exhaust: RA 1 106
Mass Flow Avg at Exhaust RA 1 0.7286
Total Concentration Avg at exhaust (CE): 106
Contam Remove Effectiveness: (CE/(C) = 1) 1.03
Values represent contaminates introduced by occupants only ( + or – 5% ok)
Appendix Table A15a: Contaminate Removal Effectiveness Simulated Values
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
102
Contaminate Removal Effectiveness (100% infected):
Space: Post Anesthesia Care Unit Room(Patient infected):
(Non-Patient infected):
X: 33.72 12.5 18 Y: 32.75 16.8 22 Z: 29 17.7 25
Concentration Avg in plans: (C)
Comb. Avg: 31.82 15.67 21.67 RA 1 34 6.25 17.5 RA 2 33 20.5 18.2 Concentration Avg at Exhaust: RA 3 32 18.75 32.2 RA 1 0.3254 0.3254 0.3254 RA 2 0.3529 0.3529 0.3529 Mass Flow Avg at Exhaust RA 3 0.2997 0.2997 0.2997
Total Concentration Avg at exhaust (CE): 33.03 15.22 22.26 Contam Remove Effectiveness: (CE/(C) = 1) 1.04 0.97 1.03
Values represent contaminates introduced by occupants only ( + or – 5% ok)
Appendix Table A15b: Contaminate Removal Effectiveness Simulated Values
Contaminate Removal Effectiveness (100% infected): Space: Transplant Waiting Room
(1 infected):
X: 58.7 1.5 Y: 62.33 2.2 Z: 77 2.5
Concentration Avg in plans: (C)
Comb. Avg: 66.01 2.07 RA 1 46 1.1 RA 2 74 2.1 Concentration Avg at Exhaust: RA 3 76 3.3 RA 1 0.684 0.684 RA 2 0.5814 0.5814 Mass Flow Avg at Exhaust RA 3 0.627 0.627
Total Concentration Avg at exhaust (CE): 107.40 2.14 Contam Remove Effectiveness: (CE/(C) = 1) 1.02 1.03
Values represent contaminates introduced by occupants only ( + or – 5% ok)
Appendix Table A15c: Contaminate Removal Effectiveness Simulated Values
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
103
Contaminate Removal Effectiveness (100% infected):
Space: CCC Hospital
X: 101
Y: 109
Z: 105Concentration Avg in plans: (C)
Comb. Avg: 105
Concentration Avg at Exhaust: RA 1 107.4
Mass Flow Avg at Exhaust RA 1 0.426
Total Concentration Avg at exhaust (CE): 107.4
Contam Remove Effectiveness: (CE/(C) = 1) 1.023
Values represent contaminates introduced by occupants only ( + or – 5% ok)
Appendix Table A15d: Contaminate Removal Effectiveness Simulated Values
9.1 Appendix A.16
Appendix Table A16a: RS MEANS Air Supply Duct Fitting Cut Sheets
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
104
Appendix Table A16b: RS MEANS Duct Insulation Cut Sheets
Appendix Table A16c: RS MEANS Air Supply Duct Cut Sheets
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
105
Appendix Table A16d: RS MEANS Air Diffuser Cut Sheets
9.1 Appendix A.17
Diffuser Schedule: 4-way, 2-way, 3-way Throw in Feet (x,y) Throw Direciton and CFM
Type Blow NC 150 fpm 100 fpm 50 fpm X Y TDC-A4 4-way 23 10 12 17 84 84TDC- G2 2-way 23 11 16 22 169 169TDC-A3 3-way 28 11 14 20 127
" " " 10 12 17 84Neck Size (in) 9 x 9 Org. Diffuser: (102/340) Face Size (in) 24 x 24 CFM 340
Appendix Table A17: Titus Diffuser Specifications 9.2 Appendix B.1 :
Type: Low-E Tinted Insulating Glass
Visible Light Transmission
U-Value Winter
U-Value Summer SHGC Shading
Coefficient Outdoor Visible Light Reflectance
55% 0.31 0.34 0.32 0.37 9%
Appendix Table B1: Glazing Attributes
Means Suggest that both 2 way and 3 way cost approx the same.
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
106
9.2 Appendix B.2:
Appendix Table B2: Titus Diffuser Specifications 9.2 Appendix B.3:
Location: Washington D.C. Conditions: Overcast Recommended Daylight Factor (%): 0.5
March 21st (*Vernal equinox) External Illumance (fc):
Internal Illuminance needed (fc):
8am 1910 9.5512pm 6719 33.5954pm 2711 13.555
June 21st (Summer solstice) External Illumance (fc):
Internal Illuminance needed (fc):
8am 4129 20.64512pm 8920 44.64pm 4723 23.615
December 21st (Winter solstice) External Illumance (fc):
Internal Illuminance needed (fc):
8am 459 2.29512pm 3133 15.6654pm 584 2.92
*Autumnal equinox will produce the same results as the Vernal equinox and will not be simulated.
Appendix Table B3: External/Internal Illuminace Values
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
107
9.2 Appendix B.4:
Appendix Table B4: Typical Exterior Wall Section
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
108
9.2 Appendix B.5:
Appendix Table B5a: RS MEANs Dry Wall Cut Sheet
Appendix Table B5b: RS MEANs Typical Window Cut Sheet
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
109
Appendix Table B5c: RS MEANs Mullion Cut Sheet
Appendix Table B5d: RS MEANs Interior Painting Cut Sheet
David Peterson INOVA Fairfax Hospital Penn State AE, Mechanical The INOVA Heart Institute
110
Appendix Table B5e: RS MEANs Spandrel glazing Cut Sheet