DATE: October 6, 2009 TO: All Prospective Bidders FROM: Sharon Quinn RE: UMBC TRC Duct Work-PRF # 07-132 Bid # BC-20633-Q - ADDENDUM # 1 The following amends the above referenced Bid documents. Receipt of this addendum must be acknowledged by completing the enclosed "Acknowledgement of Receipt of Addenda" form and submitting it along with the Bid Price Sheet you return to the University. The due date and time for the Bid to be submitted to the University remains as FRIDAY, OCTOBER 9, 2009 by 2:00 p.m. to the issuing office. A. The following drawings are a part of this Addendum: 1. M-01-TRC.pdf 2. M-02-TRC.pdf 3. M-03-TRCl.pdf 4. M-05-TRC.pdf 5. M-07-TRCl.pdf B. The following questions have been submitted to the University for a response: 1. Note 3 on Drawing E-101 calls for us to run the new power from the humidifiers to the motor control center in the penthouse. The route of this conduit is not shown. It was discussed at the pre-bid meeting to run this conduit in the existing mechanical shaft. 1.1 QUESTION: Do you have a cost estimate available for the Technology Research Center Duct Work project, RFB No. BC-20633-Q.? ANSWER: No. 1.2 QUESTION: Is there an outside design firm that did drawings for this project, or was everything done in house? ? If there was an outside firm, which one was it? ANSWER: No outside design was done for this project.

Transcript of DATE: October 6, 2009 TO: All Prospective Bidders RE: UMBC TRC … · 2009-10-06 · PROJ. NO. DWN...

Page 1: DATE: October 6, 2009 TO: All Prospective Bidders RE: UMBC TRC … · 2009-10-06 · PROJ. NO. DWN BY: APPS BY: BALTIMORE COUNTY BALTIMORE, MARYLAND Gipe Associates Inc. Co n sult

DATE: October 6, 2009 TO: All Prospective Bidders FROM: Sharon Quinn RE: UMBC TRC Duct Work-PRF # 07-132

Bid # BC-20633-Q - ADDENDUM # 1

The following amends the above referenced Bid documents. Receipt of this addendum must be acknowledged by completing the enclosed "Acknowledgement of Receipt of Addenda" form and submitting it along with the Bid Price Sheet you return to the University.

The due date and time for the Bid to be submitted to the University remains as FRIDAY, OCTOBER 9, 2009 by 2:00 p.m. to the issuing office. A. The following drawings are a part of this Addendum:

1. M-01-TRC.pdf 2. M-02-TRC.pdf 3. M-03-TRCl.pdf 4. M-05-TRC.pdf 5. M-07-TRCl.pdf

B. The following questions have been submitted to the University for a response:

1. Note 3 on Drawing E-101 calls for us to run the new power from the humidifiers to the motor control center in the penthouse. The route of this conduit is not shown. It was discussed at the pre-bid meeting to run this conduit in the existing mechanical shaft.

1.1 QUESTION: Do you have a cost estimate available for the Technology Research

Center Duct Work project, RFB No. BC-20633-Q.? ANSWER: No. 1.2 QUESTION: Is there an outside design firm that did drawings for this project, or

was everything done in house? ? If there was an outside firm, which one was it?

ANSWER: No outside design was done for this project.

Page 2: DATE: October 6, 2009 TO: All Prospective Bidders RE: UMBC TRC … · 2009-10-06 · PROJ. NO. DWN BY: APPS BY: BALTIMORE COUNTY BALTIMORE, MARYLAND Gipe Associates Inc. Co n sult

Enclosure: Acknowledgement of Receipt of Addenda Form Cc: Procurement File

END OF ADDENDUM #1 DATED 10/06/09

This addendum was post on e-Maryland Market and

UMBC’s eBid Board on 10/06/09. (Original with enclosures were not mailed)

Page 3: DATE: October 6, 2009 TO: All Prospective Bidders RE: UMBC TRC … · 2009-10-06 · PROJ. NO. DWN BY: APPS BY: BALTIMORE COUNTY BALTIMORE, MARYLAND Gipe Associates Inc. Co n sult

BID NO.: BC-20633-Q BID DUE DATE: FRIDAY, OCTOBER 9, 2009 AT 2:00 P.M.

BID FOR: UMBC TRC DUCT WORK – (PRF #07-132) NAME OF BIDDER:___________________________________________

ACKNOWLEDGEMENT OF RECEIPT OF ADDENDA The undersigned, hereby acknowledges the receipt of the following addenda:

Addendum No. 1 dated 10/05/09

Addendum No. dated _________

Addendum No. dated _________

Addendum No. dated _________

Addendum No. dated _________ As stated in this Addendum, this form is to be returned with your Bid Price Sheet.

Signature Printed Name Title Date

END OF FORM

Page 4: DATE: October 6, 2009 TO: All Prospective Bidders RE: UMBC TRC … · 2009-10-06 · PROJ. NO. DWN BY: APPS BY: BALTIMORE COUNTY BALTIMORE, MARYLAND Gipe Associates Inc. Co n sult

KEY PLAN

NOT TO SCALE

NOT IN SCOPE

LAB

LAB MAIN PREP RM

LAB

LAB

STAIRWAY

ELEC CLST

RR

STORAGE

LAB

STORAGE

STORAGE

OFFICE

STORAGE

OFFICE OFFICE OFFICE

FD

LAB

STAIRWAY

PHONE

NETWORK

ROOM

OFFICE

OFFICELOBBY

OFFICEOFFICEOFFICE

OFFICE

OFFICE

OFFICE

OFFICEOFFICE

LOBBY

CONFERENCE ROOM

RESTROOM/STORAGE

OFFICE

OFFICE

R.R.

OFFICEOFFICE

OFFICEOFFICE

COMPUTER LABSTORAGECOMPUTER LAB

OFFICE

OFFICE

COPY RM

STO

.

STAIRWAY

STORAGE

OFFICE

OFFICE

OFFICEOFFICE

OFFICEOFFICE OFFICE

RR

OFFICE

FD

FD

FDFDFD

RESTROOM

OFFICE

OFFICE

OFFICE

OFFICEOFFICE

COMPUTER LAB

UTILITY

ROOM

FD

EQUIPMENT

ROOMOFFICE

OFFICEOFFICEOFFICE

OFFICE

OFFICEOFFICE

OFFICE

RRELEC CLST

RR

STAIRWAY

LAB

SECOND FLOOR - PLAN

SCALE: 1/8" = 1'-0"

MATCH L

INE

N

SECOND FLOOR - PART PLAN

SCALE: 1/8" = 1'-0"

N

8

SCALE: 1/8" = 1'-0"

0 8 16

M-2

SECOND FLOOR - PLAN

UNIVERSITY OF MARYLAND

SCALE:

PROJ. NO.

DWN BY:

APP BY:

BALTIMORE COUNTY

BALTIMORE, MARYLAND

Gipe Associates Inc.Consulting EngineersBaltimore, Maryland

Easton, Maryland

HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER

PROJECT TITLE:REVISION No. DATE EXPLANTION

SEAL

AS NOTED

SHEET OF

DRAWING TITLE:

206

207

208

209

210

200

281

286 284 282

280

275277279

273 271

271A

278276

274

270270A

CORRIDOR

250D

260

263

265

264

262

257

266

267

CORRIDOR

CORRIDOR

255

252

253

252A

252B

250

251220

222

221

223

225227

229

224226

228230232

230B

230A

231

233

234

238240

242

201A

201B201

205A

200

205

204

202C

202B202A

202

CORRIDOR 201

12x12 UP/DN.

12x10

14x8

16x10 UP

10x10

T

T

12x6 UP

8"∅

18x16 UP

12x10

16x14

18x10 UP

16x8

12X6

UP

12x10

12x12 UP

12x1010x88x8

16x12 UP

8"∅

12"∅

14"∅

10x8 UP

T

12x12

14x14

12x8T

8x6

14x12

T

12x1010x8

12x10 UP

8x4

14x10

12x6

T

18x12 UP

10x1014x1010x10

14x12 UP

10x6

10x10

16x10

16x14 UP18x10 UP

14x8

T

T

6x12 UP

6x86x8

T

T

16x12 UP

12x10

18x10 UP

12x10

14x10

T

10x8

14x8

10x6

16x14

16x10

12x6

12x10

T

12x10

12x6

12x10 UP

12x8

18x12 UP12x1010x8

10x8

12x10 UP

8x8

16x8

T

8x8

18x10

12x10

8x14 UP & DN.

14x8

12x12

12x10 UP

T

16x8

10x10

12x10

16x10 UP & DN.

12x12 UP & DN.

12x12 UP & DN.

12x12 UP & DN.

16x12 UP

16x14 UP

16x10

18x12

FD

10x8

19 19

19 19

19 19

222222

9

1411

7 7

25

26

17

17

11 11

11

T

1111

17 21

17

25

3

20

20

T

77

17

14

1411 11

1414141414

1111

2323

23 23

77

2828

27

27

27

11

8

11

17

14

24

11

17

16

16

20

1414OFFICE

257A

4

T

15

10

12

19

19

1719

6

7

9

T

T

17

17

17

17

17 1721

18 18 18 18

FD

1815

FD

9

FD

12x10 6x4

T

18x10

8x6

16x14

10x8

16x6

14x12

16x14 DUCT CONTINUES DOWN TO SERVE

FIRST FLOOR ALSO.

252C

R.R.R.R.

T

T

T

12x10

10x8 UP & DN.

12x10 UP & DN.

UP

UP

29

1

DRAWING NOTES:

6x6 EXHAUST GRILLE, 6x6 DUCT UP TO ATTIC SPACE.1

30 30

8x6

8x612x6 UP

33

12x10

UP

14x14 UP

36 36

12x10

14x14 UP

12X10 UP

& DN.

12x6 UP & DN.

31

2

10x6 EXHAUST GRILLE, 8x6 DUCT UP TO ATTIC SPACE.2

14x8 UP

10x10 UP

16x8 UP/DN.

6x6 UP AND

DN.

29

1

3

14x8 R.A. UP & DN3

4

18x14 R.A. UP, 14x14 R.A. DN.4

5

16x14 R.A. UP, 10x8 R.A. DN.5

20x14 R.A. UP, 16x8 R.A. DN.6

6

MATCH L

INE

T

T

T

T

20x14

16x10 8"∅

14x10

41

18x12 R.A. UP, 12x12 R.A. DN.7

7

10x8

8

16x14 R.A. UP, 12x10 R.A. DN.8

10x12 UP

& DN.

16x8 UP

& DN.

18x12 R.A. UP, 12x8 R.A. DN.9

16x14 R.A. UP & DN.10

10

14x6

39

20x14 R.A. UP, 12x10 R.A. DN.11

20x16 R.A. UP, 18x10 R.A. DN.12

12

12x10

16x14

UP

42

39

12x6

12x8

41 8x6

39

10x8

8x8

41

39

8x6

12x8 UP

& DN.

18x14 R.A. UP, 14x10 R.A. DN.13

13

41

12x10

8x6

14

14x12 R.A. UP, 10x8 R.A. DN.14

20x12 R.A. UP, 10x6 R.A. DN.15

15

39 39

10x1010x8

20x14 R.A. UP, 16x10 R.A. DN.16

16x1016

8x6

41

16x12 R.A. UP, 8x6 R.A. DN.17

17

14x1439

8x6

A

A

A

A18x12 UP

UP

12x1012x10

14x8

28

14x8

28

14x8

14x8

16x10

14x8

14x8

8x8

12x6

8x8

12x6

14x8 12x612x6 10x8

11

10x8 10x8

12x6 12x6

14x8

12x6 14x610x610x6

8x8

12x6

10x6

12x6

8x8

12x6

10x610x66x10

12x612x612x6

8x8

12x6

8x8

12x610x4 10x410x4

10x6

8x812x6

12x6 12x6 10x6

12x8

10x6

12

10x6

12

10x6

12x6 12x6

19

10x8

12x6

12x612x6

12x6

1919

12x6

14x6

10x8

12x612x6

10x8

12x6 12x6 12x6 12x6

10x8

12x6 12x6

12x6 12x6

12x6 12x6

10x6 12x6

8x8

10x6

12x6

10x8

10x6

12x6

10x8

OFFICE

236

UP/DN10x8

8x6 UP

OFFICE

201C

11

10x8

9

18

14x6

42

14x12

20x12 UP

42

42

14x6

14x10 R.A. UP, 12x6 R.A. DN.18

& DN.

16x8 UP

& DN.

12x10 UP

UP & DN.

10x8

UP/DN.UP

10x8 UP & DN.

12x8 UP & DN.

& DN.

& DN.

11

30x20 UP/DN

48x36 UP/DN

30x30 UP/DN

40x30 UP/DN

40x20 UP/DN

40x30 UP/DN

30x30 UP/DN

3" HS/HR UP/DN

DN

DUCT SPACING SHOWN FOR CLARITY ONLY. DUCT SHALL BE

SPACED NO MORE THAN 1" APART FOR CEILING OPENINGS WITH

TWO DUCTS PENTRATING THE AREA.

19

19

14x14

19

19

19

19

UP

UP

19

UP/DN.

UP/DN.

UP UP

ROCKVILLE, MD 20852

TEL: 301-770-0802

FAX: 301-770-0832

11820 PARKLAWN DRIVE

SUITE 316

20 EXISTING CONVECTOR. 1/2" HS AND HR TO/FROM CONVECTOR.

20

20 20

20

20

20

KEY PLAN

NOT TO SCALE

NOT IN SCOPE

UNIVERSITY OF MARYLAND

SCALE:

PROJ. NO.

DWN BY:

APP BY:

BALTIMORE COUNTY

BALTIMORE, MARYLAND

Gipe Associates Inc.Consulting EngineersBaltimore, Maryland

Easton, Maryland

HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER

PROJECT TITLE:REVISION No. DATE EXPLANTION

SEAL

AS NOTED

SHEET OF

DRAWING TITLE:

ROCKVILLE, MD 20852

TEL: 301-770-0802

FAX: 301-770-0832

11820 PARKLAWN DRIVE

SUITE 316 23 FEB 2000 CONSTRUCTION DOCUMENTS

20

MJP

SAM

4

1

1

1

1

1

1

1

20x12 OED

1

14x10 OED

40x10

OED

24x8

TRANSFER

DUCT

24x8

TRANSFER

DUCT

24x24 PERFORATED

GRILLE (TYPICAL)

16x8 TRANSFER

DUCT (TYPICAL)

24x12

OED

1

32x8 TRANSFER

DUCT

12x8

20x12 OED

20x12 OED

114x8 OED14x8

1

24x12 OED

1

24x12 OED

3924x12 OED24x24 PERFORATED

GRILLE (TYPICAL)16x8 TRANSFER

DUCT (TYPICAL)

24x8 TRANSFER

DUCT (TYPICAL)1

14x8

OED

124x8 TRANSFER

DUCT

24x12

OED

1

24x12

OED

20x16 UP42x12

OED

24x24 PERFORATED

GRILLE (TYPICAL)

24x12 OED

24x8 TRANSFER

DUCT

1

FD

2

FD

2

FD

2FDFD

2

FD

2

FD

2

FD 2

T

11

16x10

14

12x6

18x10

UP

14x8

25

OED

ATTIC

HATCH

12x12 UP/DN

T

24x8 RA

GRILLE

T

8x6 DN

T

14x8

14x8 DNUP

T

T

16x14 UP

& DN.

24x14

OED

HATCH

ATTIC

HATCH

ATTIC

HATCH

ATTIC

HATCH

ATTIC

16x10 RA

GRILLE

12x1012x10 RA

GRILLE

15 MAR 2001 EMJAY AS-BUILT MOD'S

10 MAY 2000 VALUE ENGINEERING

23 FEB 2000 CONSTRUTION DOCUMENTS

1

20

Page 5: DATE: October 6, 2009 TO: All Prospective Bidders RE: UMBC TRC … · 2009-10-06 · PROJ. NO. DWN BY: APPS BY: BALTIMORE COUNTY BALTIMORE, MARYLAND Gipe Associates Inc. Co n sult

KEY PLAN

NOT TO SCALE

NOT IN SCOPE

FIRST FLOOR - PLAN

SCALE: 1/8" = 1'-0"

N

8

SCALE: 1/8" = 1'-0"

0 8 16

M-1

FIRST FLOOR - PLAN

UNIVERSITY OF MARYLAND

SCALE:

PROJ. NO.

DWN BY:

APP BY:

BALTIMORE COUNTY

BALTIMORE, MARYLAND

Gipe Associates Inc.Consulting EngineersBaltimore, Maryland

Easton, Maryland

HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER

PROJECT TITLE:REVISION No. DATE EXPLANTION

SEAL

AS NOTED

SHEET OF

DRAWING TITLE:

STAIRWAY

OFFICE

RR

STORAGE

STORAGE

OFFICE

RR

SHOWERS

ELEC RM

OFFICE

OFFICE

OFFICE

OFFICE

COMPUTER LABLAB

STORAGE Q

STORAGE

(GAS CANISTERS

FOR

LABS)

OFFICE

OFFICEOFFICE

DOWN

FD

STORAGE

FD

OFFICE

STAIRWAY

STORAGE

CLASSROOM

RESTROOM

NOT IN SCOPE

STORAGE

CONFERENCE

STAIRWAY

OFFICEOFFICEOFFICEOFFICEOFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICEOFFICE

OFFICE

OFFICEOFFICE

OFFICEOFFICE

MED

ICAL RM

LAB

OFFICEOFFICEOFFICE

OFFICE

RESTROOM

LAB

LAB

OFFICE

OFFICE

STORAGE

NOT IN SCOPE

MOD MOD

AHU No.2

180 CORRIDOR

180G

180H

180F

180E

180D

180I

180J

180K

180C 180B

180A

180

180L

CORRIDOR

CORRIDOR

132

130

128 126

124

122

120

STORAGE

STORAGE

STORAGE

STORAGE

VENDING

150

STORAGE Q/A148

151

157

159

STAIR

STORAGE

105B

105A

JANITOR

103

WOMENS MENS

JAN.

105

CORRIDOR

104

STORAGE

187

188

185183

181

186

184182

180

179177 175

173

171

178 176 174172

170

MAIN

180

160

162

161163

165

167

169

164166 168

CORRIDOR #3CORRIDOR

CORRIDOR

CORRIDOR

CORR

IDOR

CORRIDOR

AHU No.1

12x10

12x12 UP

T

T

16x8 UP

12x8

T

12x6

12x10 UP

FD

FD

6x4

FD

6x4

12x8

FD

FD

10x8

8"∅

6"∅

T

6x4

FDT

14x8

T

16x8 UP

T

T

12x12 UP

12x10 6x6

12x8T

10x8

10x8

16x8

6"∅6x612x8

12x6

T

10x8

T

T

10x6

10x10

10x10

16x14

10x10

14x12

12x10

12x8

10x6

10"∅

T

8"∅

T

12x10

12x10

T

16x10 UP

12x8 12x10

T

10x8

12x12UP

T

10x8

12X12 UP

12x810x8

8x610x8

12x8

16x12 UP

T

10x10

10x8

16x14 UP

T

14x12

12x1010x88x6

T

2

9 9

11

2

11

9

11 11

11

15

3

17

17

21

21

FD

4

4

11 2 8

8

10 10

15 15

12

12

12

6

21

4 4 4

21

2

1

8 11 11

2

9

9

11

21

10

4

17

14 14

2

7

7

T

13 13 13

5

5

T

T

2

FD

15

15

FD

FD

4

FD

9

FD

9

FD

9

FD

9

9FD

FD

9

FD

9

FD

9FD

9FD

9

FD

9

FD FD

9 9FD

9

FD

9

22FD

2

15

12x10

10x810x6

10x8

8x6

10x612x6

6"∅

10x6

10x10

10x8

6x8

8x6

10x812x12

16x14 UP

8x6 16x8

12x8 10x6

40x30

50x50VD

40x30

6x6

6x6

UP

8x6

2929

3332

12x10 UP

29

12x10 UP

14x8 UP

10x8

CHSCHR

CHS

CHR

DRAWING NOTES:

1

1

1 REFER TO DRAWING M-6, BOILER ROOM NEW WORKPARTIAL PLAN FOR CONTINUATION OF PIPING.

40x30

29

8x6 UP

14x14

UP

10X8

12x12

8x6

8x6

10x8 UP

10x8

16x8 UP

41

43

4112x8

12x10 UP

9

12x10 UP

12x8 UP

10x810x6

8x6

39

40 40

16x14

UP

RM

18x10

12x6

155

14x10 UP

10x6

10x8 UP

8x8

39

8x6

10x6 UP

10 10

16x10 UP

39

40

8x6 UP

12x8 UP

8x6

39

42

39

8x612x6

30x20 UP

16x8

UP

16x8 TRANSFER

12x10

10x8

UP

29 29 31

8x6

12x10 UP

2

UP

39

8x6

40

12x6

UP8x6

8x6

41

UP

2

2 12x12 EXHAUST GRILLE, 10x8 DUCT UP TOATTIC SPACE.

3 8x6 EXHAUST GRILLE, 12x6 DUCT UP TO ATTIC SPACE.

3

8x6

10

8x6

12x10

8x6

8x6

8x6

8x6

8x6

39

UP

8x6

8x6

39

39

8x6

10x6

6x6

21

17

11

11

17

UP

8x612x12

12x10

UP

48x36

48x36

UP

4

5

4 40x30 RETURN AIR DUCT.

5 40x20 RETURN AIR DUCT UP.

6

6 40x30 SUPPLY AIR DUCT UP.

7

7 30x30 RETURN AIR DUCT UP.

30x30 UP

8

8 40x40 RETURN AIR DUCT

EXISTING CONCRETE PAD TO BE REMOVED

REMOVE CONCRETE PATIO IN

THIS AREA TO POINT INDICATED.

REMOVE THE ENTIRE ROOF AND

ALL APPURTENANCES BACK TO

EXTERIOR BUILDING WALL.

REMOVE CONCRETE TO THIS POINT

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

A.

B.

C.

D.

E.

F.

G.

17.

GENERAL NOTES: (APPLIES TO MECHANICAL DRAWINGS):

THE LOCATION OF EXISTING UNDERGROUND UTILITIES IS SHOWN IN AN APPROXIMATE WAY ONLY.

DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. REPAIR ALL

DAMAGES OCCASIONED BY FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UNDERGROUND

UTILITIES.

MAINTAIN MINIMUM OF 3'-0" COVER OVER UNDERGROUND CHILLED WATER MAINS.

PROVIDE AN AIR VENT AT THE HIGH POINT OF EACH DROP IN THE HEATING AND CHILLED WATER SYSTEMS.

UNLESS OTHERWISE NOTED, ALL PIPING AND DUCTWORK IS OVERHEAD.

INSTALL PIPING AND DUCTWORK SO THAT ALL VALVES AND DAMPERS ARE ACCESSIBLE.

COORDINATE ALL MECHANICAL WORK WITH ELECTRICAL WORK, ETC., SHOWN ON OTHER DRAWINGS.

EXCEPT AS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS 4'-0" (CENTERLINE) ABOVE FINISHED FLOOR ADJACENT TO THE ROOM LIGHT SWITCH. NOTIFY THE ENGINEER OF ANY ROOMS

WHERE THE ABOVE LOCATION CANNOT BE MAINTAINED OR WHERE THERE IS A QUESTION ON LOCATION.

MAINTAIN MINIMUM 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUIT, SUSPENDED EQUIPMENT,

ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL AND ELECTRICAL ROOMS.

CERTAIN ITEMS SUCH AS CLEANOUTS, ACCESS DOORS, RISE AND DROPS IN DUCTWORK, ETC., ARE INDICATED

ON THE DRAWINGS FOR CLARITY OR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED

AS THE EXTENT OF THE REQUIREMENTS FOR THOSE ITEMS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR

THESE ITEMS AS REQUIRED ELSEWHERE IN THE CONTRACT DOCUMENTS.

EQUIPMENT CONNECTION SIZES MAY DIFFER FROM INDICATED DUCT OR PIPE SIZES. PROVIDE APPROPRIATE

TRANSITIONS WHERE REQUIRED.

THESE DRAWINGS ARE DIAGRAMMATIC AND ALL OFFSETS, FITTINGS, TRANSITIONS AND ACCESSORIES ARE

NOT NECESSARILY SHOWN. COORDINATE THE INSTALLATION OF ALL PIPING, DUCTWORK, EQUIPMENT AND

OTHER WORK WITH ALL OTHER TRADES.

IT IS THE INTENT THAT ALL WORK SHALL BE COMPLETE IN EVERY RESPECT AND THAT MATERIAL OR WORK

SPECIFICALLY NOT INDICATED ON DRAWINGS, BUT NECESSARY TO COMPLETE THE WORK, SHALL BE

FURNISHED.

EXACT LOCATION OF DIFFUSERS, REGISTERS AND GRILLES PROVIDED IN CEILING SHALL BE COORDINATED

WITH EXISTING CEILING.

REFER TO AIR DEVICE SCHEDULES FOR SIZE OF DUCT FROM BRANCH DUCT TO NECK OF AIR DEVICE.

ALL BRANCH DUCT RUNOUTS TO AIR DEVICES SHALL BE PROVIDED WITH

VOLUME DAMPERS.

MATERIAL, EQUIPMENT, INSTALLATION AND PROCEDURES SHALL BE IN STRICT ACCORDANCE WITH THE

APPLICABLE REQUIREMENTS OF THE LATEST CURRENT EDITION OF THE REFERENCED DOCUMENTATION.

REGULATIONS OF LOCAL AUTHORITIES HAVING JURISDICTION.

NFPA-NATIONAL FIRE PROTECTION ASSOCIATION.

SMACNA - SHEET METAL AND AIR CONDITIONING NATIONAL ASSOCIATION.

ASME - AMERICAN SOCIETY OF MECHANICAL ENGINEERS.

ASTM - AMERICAN SOCIETY OF TESTING AND MATERIALS.

ASHRAE - AMERICAN SOCIETY OF HEATING, REFRIGERATION AND AIR CONDITIONING ENGINEERS, INC.

BOCA, NATIONAL PLUMBING CODE, LATEST ADOPTED EDITION.

ALL AUTOMATIC TEMPERATURE CONTROL SETPOINTS SHALL BE ADJUSTABLE.

UP

9

9 DUCT SPACING SHOWN FOR CLARITY ONLY. DUCT SHALL BE

SPACED NO MORE THAN 1" APART FOR CEILING OPENINGS WITH

TWO DUCTS PENTRATING THE AREA.

9

9

9

9

9

9

ROCKVILLE, MD 20852

TEL: 301-770-0802

FAX: 301-770-0832

11820 PARKLAWN DRIVE

SUITE 316

8x68x6

PROVIDE FLOW METERS NEXT TO ALL BALANCING VALVES SERVING 2 OR MORE PIECES OF EQUIPMENT

AND WHERE INDICATED ON PLANS.

PROVIDE DRAIN VALVES AT ALL LOW POINTS FOR DRAINAGE OF PIPING SYSTEMS.

18.

19.

REMOVE EXISTING EXHAUST FAN, DUCTWORK AND ALL APPURTENANCES ON THIS WALL TO ALLOW INSTALLATION OF

PROPOSED DUCTWORK AS INDICATED.

10

10

11 EXISTING CONVECTOR. 1/2" HS AND HR TO/FROM CONVECTOR.

11

12 EXISTING UNIT HEATER. 1/2" HS AND HR TO/FROM UNIT HEATER.

12

11

11

EX HEAT PUMP

EX AHU

EX 24x12 SUPPLY

13 PROVIDE HOT WATER HEATING COIL IN EXISTING 24x12 DUCT.

21,600 BTUH, 2000 CFM, 2.2 GPM, 1-ROW, .05 APD MAX, 80 EAT.

13

14 3/4" HS AND HR TO/FROM HEATING COIL.

14

G

NEW GAS

SERVICE BY

BGE

KEY PLAN

NOT TO SCALE

NOT IN SCOPE

UNIVERSITY OF MARYLAND

SCALE:

PROJ. NO.

DWN BY:

APP BY:

BALTIMORE COUNTY

BALTIMORE, MARYLAND

Gipe Associates Inc.Consulting EngineersBaltimore, Maryland

Easton, Maryland

HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER

PROJECT TITLE:REVISION No. DATE EXPLANTION

SEAL

AS NOTED

SHEET OF

DRAWING TITLE:

ROCKVILLE, MD 20852

TEL: 301-770-0802

FAX: 301-770-0832

11820 PARKLAWN DRIVE

SUITE 316 23 FEB 2000 CONSTRUCTION DOCUMENTS

20

MJP

SAM

3

NOTE:

REFER TO ELECTRICAL SITE PLAN

E-2 FOR CHILLER LOCATION AND

CHILLED WATER PIPE ROUTING

1

1

1

1

OPENING

24x24 PERF. GRILLE

(TYP.) 22x8 OED.

16x8 TRANSFER

OPENING

22x8 OED.

16x8 TRANSFER

OPENING

24x24 PERF. GRILLE

(TYP.)

1

1

24x8 OED.16x8 OED.

16x8 TRANSFER

OPENING (TYP)

24x24 PERF. GRILLE

(TYP.)

1

24x8 OED.

24x24 PERF. GRILLE

(TYP.)

1

24x10 OED.

24x24 PERF. GRILLE

(TYP.)

1

8x6 OED.

24x24 PERF. GRILLE

(TYP.)

1

32x8 TRANSFER

GRILLE

22x14 OED.

24x8 TRANSFER

OPENING

24x24 PERF. GRILLE (TYP)

16x8 TRANSFER

OPENING

16x8 TRANSFER

OPENING22x8 OED.

1

22x8 OED.

10x8 OED.16x8 TRANSFER

OPENING

16x8 TRANSFER

OPENING

16x8 OED.12x8 OED.

24x24 PERF. GRILLE (TYP)

16x8 TRANSFER (TYP)

1

ALL AIR TRANSFER OPENINGS SHALL BE SLEEVED.

ALL OPEN END DUCTS TO HAVE BIRD SCREEN AND VOLUME DAMPERS.

24x24 PERFORATED GRILLES TO BE FIELD LOCATED.

FIELD VERIFY NEED FOR FIRE DAMPERS IN EXISTING WALLS.

20.

21.

22.

23.

1

FD

FD

2

2

FD

2

FD

2

FD

2

FD2

FD

2

FD 2

FD

2

FD

FD

2

2

FD2

2

2

2

2

2

FD

FD

FD

14x8

16x8 TRANSFER

OPENING

G

G

10x10

10x10 OED.

56x34

SD

SD

SD

SD

G

4"

24x8

OED

16x6

OED

20x4

FD

3

3

3

3

3

3

22x8

OED

T

14x14

UP

16x8

OED

12x12

UP

12x12

12x10

12

12

14x8

UP

24x8

OED

16x8

OED

16x8

OED

FD

9

FD FD FD FD99

FDFD

20

23 FEB 2000 CONSTRUCTION DOCUMENTS

10 MAY 2000 VALUE ENGINEERING1

15 MAR 2001 EMJAY AS-BUILT MOD'S

Page 6: DATE: October 6, 2009 TO: All Prospective Bidders RE: UMBC TRC … · 2009-10-06 · PROJ. NO. DWN BY: APPS BY: BALTIMORE COUNTY BALTIMORE, MARYLAND Gipe Associates Inc. Co n sult

8

SCALE: 1/8" = 1'-0"

0 8 16

ATTIC - PLAN

SCALE: 1/8" = 1'-0"

MATCH L

INE

N

ATTIC - PART

SCALE: 1/8" = 1'-0"

N

M-3ATTIC - PLAN

EF

EF

EF

EF

HATCH

EF

EF

HATCH

EF

12x10

12x12 DN.

12x12

16x8 DN.

12x10

18x10

16x10 DN.

12x6 DN.

18x16

18x10

DN.12x12 DN.

16x12

10x8

10x10

12x12

14x12

12x10 DN.

18x12 DN.

14x12 DN.

16x10 16x10

16x14 DN.

18x10

12x16 DN.

18x10 DN.

16x14 DN.

12x10 DN.

18x12 DN.

12x10 DN.16x8 DN.

18x10 DN.

14x8 DN.

12x12

12x10

DN.

10x8 DN.

16x8 DN.

12x10 DN.

10x10 DN.

14x16

12x10

12x10 DN.

16x10 DN.

12x12 DN.

12x12 DN.

12x12 DN.16x14 DN.

18x12

40

23

41

39

42

54

22 21

55

53

52

20

19

15

45

46

16

47

49

48

17

18

51

50

44

32 11

34

3331

36

35

12

37

14

13

38

10

30

9

87

29

6

4

5

27

26

3

25

24

2

1

28

56

12x6 DN.

48x36

43

40x30

10x8 DN.

57

16x14 DN.

9'-0"

1

M-3

1

M-3

SECTION

SCALE: 1/8" = 1'-0"

1

M-3

STUD (TYP.)

FIN. FL.

40x30

12x10

18x10

30x24

30x20

12x6

16x8

10x8

10x6

8x620x14

20x8

12x6

40x30

10x8

40x20

40x18

10x8

12x10

30x18

30x18 20x14 16x14

12x6

12x8

16x8

8x4

12x8

20x10

30x20

10x6

14x10 DN.

30x20

8x8

12x10

14x8

24x1820x16

8x6

20x16

8x6

10x6

10x8

10x6

14x14 DN.

12x10

30x20

12x12

16x12

14x10 DN. 16x12 DN.

12x6

10x10

12x8

30x18

16x8

12x6

8x6

30x14

8x6

18x18

10x10

10x8

VDVDVD

18x12

VD

14x10

14x10

VD

12x6

40x24

40x30

18x16 8x8

18x14

VD8x6

VD

12x6

16x10

10x8

VD

20x16

16x8

14x14

VD

10x810x10

VD

12x10

40x14

40x14

12x12

30x14

VD

10x10

18x12

10x812x10

30x20 S.A.

9'-4"

STUD (TYP.)

FIN. FL.

2

M-3

2

M-3

2

M-3

SECTION

SCALE: 1/8" = 1'-0"

16x812x8

14x14 DN. & UP

14x14 DN. & UP

THRU ROOF

THRU ROOF

10x8

12x10 DN. & UP THRU ROOF

6x6 DN. & UP

THRU ROOF

10x10 UP

THRU ROOF

8x6 DN.

8x6 UP

12x6 DN. & UP THRU ROOF

16x14 DN.

16x14 UP

THRU

ROOF

8x6 DN. & UP

THRU ROOF

14x8 DN.

6x6 DN.

6x6 UP

6x6 DN.

6x6 UP TO

THRU ROOF

18x14

DN.

8x8

16x14 DN.

14x20 DN.

MATCH L

INE

2700

20x16

12x18

20x20

20x20 R.A.

16x14

DN.

12x10

DN.

500

18x12 DN.

16x14 DN.

14x20 DN.

16x20

DN.

16x14

DN.

12x8 DN.

14x18 DN.

14x12 DN.

20x12 DN.

1500

20x14 DN.

16x12 DN.B

B

B

B

12x10

12x6

DN.

DN.

18x16

DN.

DN.

DN.

DN.

18x10

DN.

DN.

DN.

20x16

18x12

18x12

12x8

20x18

20x16

30x18

20x18

30x20

16x8 DN.

14x10 DN.

750

20x12 DN.

18x10 DN.

10x8 DN.

12x8

DN.

DN.

S.A. DN. R.D. DN.

30x30 R.D. DN.

20x14

30x1830x1420x1420x14

40x30 S.A. DN.

30x20 DN.

30x20

40x20 R.A. DN.

30x20

30x20

20x1820x16

14x8

20x16 R.A.

40x20 R.A.

DRAWING NOTES:

1 EXHAUST FAN IN VERTICAL POSITION.

1

1 1

1

1

1

12x6 DN. & UP

THRU ROOF

1

1

DN.

20x14 S.A.

E.F. No.15

E.F. No.18

E.F. No.14

E.F. No.3

E.F. No.17

E.F. No.7

E.F. No.9

E.F. No.16

E.F. No. 10

1

1

E.F. No.13

E.F. No.12

E.F. No.19

E.F. No.20

E.F. No.21

UNIVERSITY OF MARYLAND

SCALE:

PROJ. NO.

DWN BY:

APP BY:

BALTIMORE COUNTY

BALTIMORE, MARYLAND

Gipe Associates Inc.Consulting EngineersBaltimore, Maryland

Easton, Maryland

HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER

PROJECT TITLE:REVISION No. DATE EXPLANTION

SEAL

AS NOTED

SHEET OF

DRAWING TITLE:

SP

SP

SP

SP

SP

STATIC PRESSURE

SENSOR (TYP.)

FIN. FLOOR

CEILING

18x12 R.A.

30x14 S.A.

40x20 S.A.

30x20 R.A.

9'-4"STUD (TYP.)

SECTION

SCALE: 1/8" = 1'-0"

3

M-3

3

M-3

3

M-3

48x36 S.A.

30x20 R.A.

6x12 S.A.

GOOSE NECK

(TYP.)EXHAUST FAN IN

VERTICAL POSITION

VAV BOX12x10 EXH.

FIN. FLOOR

40x14 S.A.

30x18 R.A.40x30 S.A.

30x30 R.A.

FIN. FLOOR

8'-4"

14x10 R.A.

40x30 30x30

SECTION

SCALE: 1/8" = 1'-0"

4

M-3

4

M-3

4

M-3

12x6 S.A.

CEILING

EXISTING ROOF RIDGE

16" O.C. (TYP.)

ATTIC FLOOR

53 1/2" MIN.

EXISTING RAFTER

(TYP.)

DUCT PENETRATION - DETAIL

SCALE: 1/4" = 1'-0"

9'-0"

36x48

ATTIC FLOOR

48x36

EXISTING ROOF RIDGE

STUD (TYP.)

SECTIONELEVATION

ROOF SLOPES

8x16

DN.

DUCT SPACING SHOWN FOR CLARITY ONLY. DUCT SHALL BE

SPACED NO MORE THAN 1" APART FOR CEILING OPENINGS WITH

TWO DUCTS PENTRATING THE AREA.

2

2

2

2

14x14

ROCKVILLE, MD 20852

TEL: 301-770-0802

FAX: 301-770-0832

11820 PARKLAWN DRIVE

SUITE 316

GENERAL NOTES:

CONTRACTOR SHALL REFER TO PRECAST PLANK DETAIL ON

STRUCTURAL DRAWING S-1 FOR CRITERIA OF DUCT

PENTRATIONS TO ATTIC FLOOR.

1.

2

2

2

2

2

48x36 S.A. DN.

40x20

CONTRACTOR TO PROVIDE A MEANS TO WALKOVER ANY

LOW LYING DUCTS CROSSING ATTIC CORRIDORS.

2.

PROVIDE FIRE DAMPERS AT ALL FLOOR AND ATTIC

PENETRATIONS.

3.

KEY PLAN

NOT TO SCALE

NOT IN SCOPE

UNIVERSITY OF MARYLAND

SCALE:

PROJ. NO.

DWN BY:

APP BY:

BALTIMORE COUNTY

BALTIMORE, MARYLAND

Gipe Associates Inc.Consulting EngineersBaltimore, Maryland

Easton, Maryland

HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER

PROJECT TITLE:REVISION No. DATE EXPLANTION

SEAL

AS NOTED

SHEET OF

DRAWING TITLE:

ROCKVILLE, MD 20852

TEL: 301-770-0802

FAX: 301-770-0832

11820 PARKLAWN DRIVE

SUITE 316 23 FEB 2000 CONSTRUCTION DOCUMENTS

20

MJP

SAM

5

12x10

16x12

1

1

1

1

1

1

1

1

HATCH

ATTIC

12x12

DN.

HATCH

ATTIC

HATCH

ATTIC

WALKWAY

SP

WALKWAY

23 FEB 2000 CONSTRUCTION DOCUMENTS

10 MAY 2000 VALUE ENGINEERING1

15 MAR 2001 EMJAY AS-BUILT MOD'S

20

Page 7: DATE: October 6, 2009 TO: All Prospective Bidders RE: UMBC TRC … · 2009-10-06 · PROJ. NO. DWN BY: APPS BY: BALTIMORE COUNTY BALTIMORE, MARYLAND Gipe Associates Inc. Co n sult

8

SCALE: 1/8" = 1'-0"

0 8 16

ROOF - PLAN

SCALE: 1/8" = 1'-0"

MATCH L

INE

MATCH L

INE

N

ROOF - PART PLAN

SCALE: 1/8" = 1'-0"

N

M-5ROOF - PLAN

14x14 GOOSENECK

14x14 GOOSENECK

10x10 GOOSENECK

12x10 GOOSENECK

6x6 GOOSENECK

12x6 GOOSENECK

10x10 GOOSENECK

8x6 GOOSENECK

12x6 GOOSENECK

16x14 GOOSENECK

8x6 GOOSENECK

6x6 GOOSENECK

6x6 GOOSENECK

10x8 GOOSENECK

UNIVERSITY OF MARYLAND

SCALE:

PROJ. NO.

DWN BY:

APP BY:

BALTIMORE COUNTY

BALTIMORE, MARYLAND

Gipe Associates Inc.Consulting EngineersBaltimore, Maryland

Easton, Maryland

HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER

PROJECT TITLE:REVISION No. DATE EXPLANTION

SEAL

AS NOTED

SHEET OF

DRAWING TITLE:

30x3040x30

30x30

40x30

40x20

48x36

30x20

ROCKVILLE, MD 20852

TEL: 301-770-0802

FAX: 301-770-0832

11820 PARKLAWN DRIVE

SUITE 316

KEY PLAN

NOT TO SCALE

NOT IN SCOPE

UNIVERSITY OF MARYLAND

SCALE:

PROJ. NO.

DWN BY:

APP BY:

BALTIMORE COUNTY

BALTIMORE, MARYLAND

Gipe Associates Inc.Consulting EngineersBaltimore, Maryland

Easton, Maryland

HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER

PROJECT TITLE:REVISION No. DATE EXPLANTION

SEAL

AS NOTED

SHEET OF

DRAWING TITLE:

ROCKVILLE, MD 20852

TEL: 301-770-0802

FAX: 301-770-0832

11820 PARKLAWN DRIVE

SUITE 316 23 FEB 2000 CONSTRUCTION DOCUMENTS

20

MJP

SAM

EF-3

FOR EF-21

FOR EF-17

FOR EF-7

FOR EF-20

FOR EF-9

FOR EF-10

FOR EF-16

FOR EF-13

FOR EF-12

FOR EF-14

FOR EF-18

FOR EF-15

FOR EF-19

7

1 1

1

1 1

1

20

23 FEB 2000 CONSTRUCTION DOCUMENTS

10 MAY 2000 VALUE ENGINEERING1

15 MAR 2001 EMJAY AS-BUILT MOD'S

Page 8: DATE: October 6, 2009 TO: All Prospective Bidders RE: UMBC TRC … · 2009-10-06 · PROJ. NO. DWN BY: APPS BY: BALTIMORE COUNTY BALTIMORE, MARYLAND Gipe Associates Inc. Co n sult

M-7DETAILS

SCALE: NONE

FIRE DAMPER - DETAIL

EACH SIDE OF

DIAMETER BOLTS

COLLAR W/ 1/4"

BE SECURED TO

DAMPER SHALL

1/4" DIA. BOLTSCOLLAR ONLY W/

DAMPER

FASTENED TO

STEEL ANGLES

PROVIDE SLIP JOINT

NEGATOR CLOSURE

STAINLESS STEEL

UNLESS OTHER-

FOR 1-1/2 HR.

IN DUCTWORK ON

SPRING

WISE NOTED

U.L. LABELED

FIBERGLASS

LOW DENSITY

FLOOR CONSTRUCTION

CONCRETE OR STEEL

BLADE LOCK

PACKING

FUSIBLE LINK

DUCT

SHEET METAL

STEEL BLADES

ACCESS PANEL

COLLAR

COIL

W/ NEEDLE VALVE(TYP)

PRESSURE GAUGE

VENT (TYP)

MANUAL AIR

GATE VALVE (TYP)

END DRAIN VALVESTRAINER W/HOSE

HOSE END DRAIN

VALVE (TYP)

THERMOMETER (TYP)

UNION (TYP)

SCALE: NONE

CWS

BALANCING VALVE

THREE-WAY MODULATING

COMBINATION SHUT-OFF

CWR

VALVE (ATC)

SCHEDULE 40 GALVANIZED STEEL PIPE

PIPE AND INSULATION TO BE

PIPE SLEEVE THRU INTERIOR WALL

SMALLER, 20 GAUGE; 4" TO 6", 16 GAUGE; OVER 6", 14 GAUGE.

NOTE: FOR INTERIOR FRAME PARTITIONS-PIPE SLEEVES MAY BE FABRICATED FROM GALVANIZED

SHEET METAL; ROUND TUBE CLOSED WITH SNAPLOCK JOINT, WELDED SPIRAL SEAMS, OR

WELDED LONGITUDINAL JOINT. FABRICATE FROM THE FOLLOWING GAUGES: 3" AND

CONCEALED PIPING

NOT SUPPORT PIPE FROM

CENTERED IN SLEEVE - DO

SLEEVE COMPLETELY COVER OPENING

AGAINST WALL AND OF SIZE TO

FINISHED ESCUTCHEON PLATE FLUSH

FINISHED WALL SURFACE

PIPING EXPOSED TO VIEW

SCALE: NONE

SEAL SLEEVES THRU FIRE/SMOKEWALLS AND FLOOR IN A SMOKE

TIGHT MANNER WITH AN APPROVED

THROUGH RATED ASSEMBLIES

SEALED PER A LISTED ASSEMBLY

FIRE STOP CAULK. SLEEVES

SHALL BE CONSTRUCTED &SLEEVE OF SIZE TO PASS PIPE

FINISHED WALL SURFACES

TERMINATE SLEEVE FLUSH WITH

AND INSULATION; REMOVE BURRS

VARIABLE AIR VOLUME BOX

3'-0" MIN. BEFORE TAKE

MANUAL VOLUME DAMPER

(TYP. FOR EACH DIFFUSER)

LOW PRESSURE DUCT TO

PLAN VIEW

VARIABLE AIR VOLUME BOX

V.A.V. BOX

DUCT STRAP (TYP.)

SCALE: NONE

REMOVABLE ACCESS PANEL

(DO NOT OBSTRUCT)CONTROLLER

CONTROL BOX

SUPPLY AIR DUCT

SUPPLY AIR MAIN

MEDIUM PRESSURE

VARIABLE PRIMARY

3 DUCT DIAMETER MIN. STRAIGHT DUCT

CONICAL

TAP

AIRFLOW

MIN. CLEAR

HEAT COIL

FOR SERVICING

MAINTAIN 24"

6"

OFF OR ELBOW

DIFFUSER

12"

MIN.

GOOSENECK DETAIL

ANGLE IRON REINFORCING

WHERE REQUIRED

METAL SCREEN

ANGLE RIVETED OR

TRACK WELDED

AS REQUIRED

DUCT SIZE +25

48" MINIMUM

SCREEN

FRAME

BOLTS

36" MIN.

135 MIN.

R

R=W-

2

AND JOINTS

ROOF

WATERPROOF SEAMS

SCALE: NONE

UNIVERSITY OF MARYLAND

SCALE:

PROJ. NO.

DWN BY:

APP BY:

BALTIMORE COUNTY

BALTIMORE, MARYLAND

Gipe Associates Inc.Consulting EngineersBaltimore, Maryland

Easton, Maryland

HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER

PROJECT TITLE:REVISION No. DATE EXPLANTION

SEAL

AS NOTED

SHEET OF

DRAWING TITLE:

CURB

6" MIN.

EXHAUST

SCALE: NONE

AIRFLOW

3'-0" MIN. STRAIGHT

DUCT FULL SIZE OF

FAN CONNECTION

VIBRATION ISOLATOR (TYP.)

5/8" MIN. ALL THREAD ROD(TYP. OF 4 MIN.)

30 MAXIMUM

FLEXIBLE CONNECTION (TYP.)

CABINET FAN

COMBINATION SPRING

DOUBLE DEFLECTION

NEOPRENE VIBRATION

ISOLATOR

BY STRUCTURAL ENGINEER

STRUCTURE OR AS APPROVED

FROM TOP CHORD OF

VERTICAL IN-LINE CABINET

FAN DETAIL

ROOF

SCALE: NONE

AIRFLOW

3'-0" MIN. STRAIGHT

DUCT FULL SIZE OF

FAN CONNECTION

VIBRATION ISOLATOR (TYP.)

5/8" MIN. ALL THREAD ROD(TYP. OF 4 MIN.)

30 MAXIMUM

FLEXIBLE CONNECTION (TYP.)

CABINET FAN

COMBINATION SPRING

DOUBLE DEFLECTION

NEOPRENE VIBRATION

ISOLATOR

BY STRUCTURAL ENGINEER

STRUCTURE OR AS APPROVED

FROM TOP CHORD OF

HORIZONTIAL IN-LINE CABINET

FAN DETAIL

CEILING

ROOF

COOLING COIL PIPING

FLOW METER FITTING

PRE-HEAT COIL PIPING

THERMOMETER

GAUGE

COIL

MANUAL AIR VENT

PIPING SIMILAR

MULTIPLE COIL

DRAIN W/ HOSEAIR FLOW

END AND CAP (TYPICAL)

VALVE

MODULATING

BALANCING VALVE (TYP.)SHUT OFF/COMBINATIONSUPPLY

RETURN

FITTING

FLOW METER

3-WAY

SCALE: NONE

DUCT SIZE SHALL

BE INDICATED ON

PLANS

TRANSITION TO VAV

BOX INLET AS

REQUIRED

DRAIN SHALL BE ONE PIPE SIZE LARGER THAN

4" MIN.

THE SIZE OF THE NIPPLE ON THE DRAIN PAN

DRAIN (1/4" PER 10'-0" MIN.)

NOTE: INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

UNION

CLEAN OUT

CLEAN OUT

PITCHED DOWN TOWARD

ECCENTRIC

INCREASER

DRAIN PAN

4" MIN.

SPILL

CONDENSATE

ONTO SPLASH

BLOCK

CONDENSATE DRAIN PIPING

SCALE: NONE

DETAILA

M-7

BUILDING PAPER

ALL SIDES

7/16 OSBSHEATHING

4" VINYL SIDING

MATCH EXISTING ROOF

IN ALL RESPECTS

GENERAL NOTE:

FLASHING 16 oz COPPER

COORDINATE DUCT FLANGE

LOCATION WITH FLASHING

2x4

MATCH EXISTING ROOF SLOPE

GENERAL NOTE:

8"

ROCKVILLE, MD 20852

TEL: 301-770-0802

FAX: 301-770-0832

11820 PARKLAWN DRIVE

SUITE 316

GATE VALVE (TYP)

DRAIN VALVE

STAINER W/HOSE ENDDRAIN

VALVE (TYP)

P/T PORT (TYP.)

VALVE (ATC)MANUAL AIR VENT

(TYP.)

UNION

(TYP)

HOSE END

COIL

THREE-WAY MODUALTING

HS

HR

COMBINATION BALANCING

AND SHUT-OFF VALVE

NOTE: DETAIL TYPICAL FOR DUCT MOUNTED HEATING COILS SIMILAR.

SCALE: NONE

TERMINAL UNIT HEATING COIL PIPING

23 FEB 2000 CONSTRUCTION DOCUMENTSMJP

SAM

METAL DRIP EDGE

BAKED ENAMEL

ALUMINUM TRIM

PROVIDE WEEP HOLES IN FLASHING

HEAD & JAMB

SILL

OVER DUCT FLANGE (TYP)

9 20

DUCT

ASPHALT SHINGLES, ASTM D3018 TYPE 1, CLASS A

FIRE RESISTANCE, 30 YEAR WARRANTYROOF SHINGLE COLOR TO MATCH EXISTING ROOF

2x4

VINYL SIDING WITH DOUBLE 4" PATTERN

COLOR AS SELECTED BY OWNER

6"

B

M-7

B1

M-7

4"

2x4 TREATED WOOD

7/16 SHEATHING

10 MAY 2000 VALUE ENGINEERING1

1

1

1

DORMER FEATURE DELETED

ATTIC DUCT PENETRATION (TYP)NOT TO SCALE:

DUCTWORK COVERED WITH

FLASHING

SHINGLES

WELDED STEEL CURB

INSULATION AND REINFORCED

WEATHERPROOFING

15 MAR 2001 EMJAY AS-BUILT MOD'S