DATE: October 6, 2009 TO: All Prospective Bidders FROM: Sharon Quinn RE: UMBC TRC Duct Work-PRF # 07-132
Bid # BC-20633-Q - ADDENDUM # 1
The following amends the above referenced Bid documents. Receipt of this addendum must be acknowledged by completing the enclosed "Acknowledgement of Receipt of Addenda" form and submitting it along with the Bid Price Sheet you return to the University.
The due date and time for the Bid to be submitted to the University remains as FRIDAY, OCTOBER 9, 2009 by 2:00 p.m. to the issuing office. A. The following drawings are a part of this Addendum:
1. M-01-TRC.pdf 2. M-02-TRC.pdf 3. M-03-TRCl.pdf 4. M-05-TRC.pdf 5. M-07-TRCl.pdf
B. The following questions have been submitted to the University for a response:
1. Note 3 on Drawing E-101 calls for us to run the new power from the humidifiers to the motor control center in the penthouse. The route of this conduit is not shown. It was discussed at the pre-bid meeting to run this conduit in the existing mechanical shaft.
1.1 QUESTION: Do you have a cost estimate available for the Technology Research
Center Duct Work project, RFB No. BC-20633-Q.? ANSWER: No. 1.2 QUESTION: Is there an outside design firm that did drawings for this project, or
was everything done in house? ? If there was an outside firm, which one was it?
ANSWER: No outside design was done for this project.
Enclosure: Acknowledgement of Receipt of Addenda Form Cc: Procurement File
END OF ADDENDUM #1 DATED 10/06/09
This addendum was post on e-Maryland Market and
UMBC’s eBid Board on 10/06/09. (Original with enclosures were not mailed)
BID NO.: BC-20633-Q BID DUE DATE: FRIDAY, OCTOBER 9, 2009 AT 2:00 P.M.
BID FOR: UMBC TRC DUCT WORK – (PRF #07-132) NAME OF BIDDER:___________________________________________
ACKNOWLEDGEMENT OF RECEIPT OF ADDENDA The undersigned, hereby acknowledges the receipt of the following addenda:
Addendum No. 1 dated 10/05/09
Addendum No. dated _________
Addendum No. dated _________
Addendum No. dated _________
Addendum No. dated _________ As stated in this Addendum, this form is to be returned with your Bid Price Sheet.
Signature Printed Name Title Date
END OF FORM
KEY PLAN
NOT TO SCALE
NOT IN SCOPE
LAB
LAB MAIN PREP RM
LAB
LAB
STAIRWAY
ELEC CLST
RR
STORAGE
LAB
STORAGE
STORAGE
OFFICE
STORAGE
OFFICE OFFICE OFFICE
FD
LAB
STAIRWAY
PHONE
NETWORK
ROOM
OFFICE
OFFICELOBBY
OFFICEOFFICEOFFICE
OFFICE
OFFICE
OFFICE
OFFICEOFFICE
LOBBY
CONFERENCE ROOM
RESTROOM/STORAGE
OFFICE
OFFICE
R.R.
OFFICEOFFICE
OFFICEOFFICE
COMPUTER LABSTORAGECOMPUTER LAB
OFFICE
OFFICE
COPY RM
STO
.
STAIRWAY
STORAGE
OFFICE
OFFICE
OFFICEOFFICE
OFFICEOFFICE OFFICE
RR
OFFICE
FD
FD
FDFDFD
RESTROOM
OFFICE
OFFICE
OFFICE
OFFICEOFFICE
COMPUTER LAB
UTILITY
ROOM
FD
EQUIPMENT
ROOMOFFICE
OFFICEOFFICEOFFICE
OFFICE
OFFICEOFFICE
OFFICE
RRELEC CLST
RR
STAIRWAY
LAB
SECOND FLOOR - PLAN
SCALE: 1/8" = 1'-0"
MATCH L
INE
N
SECOND FLOOR - PART PLAN
SCALE: 1/8" = 1'-0"
N
8
SCALE: 1/8" = 1'-0"
0 8 16
M-2
SECOND FLOOR - PLAN
UNIVERSITY OF MARYLAND
SCALE:
PROJ. NO.
DWN BY:
APP BY:
BALTIMORE COUNTY
BALTIMORE, MARYLAND
Gipe Associates Inc.Consulting EngineersBaltimore, Maryland
Easton, Maryland
HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER
PROJECT TITLE:REVISION No. DATE EXPLANTION
SEAL
AS NOTED
SHEET OF
DRAWING TITLE:
206
207
208
209
210
200
281
286 284 282
280
275277279
273 271
271A
278276
274
270270A
CORRIDOR
250D
260
263
265
264
262
257
266
267
CORRIDOR
CORRIDOR
255
252
253
252A
252B
250
251220
222
221
223
225227
229
224226
228230232
230B
230A
231
233
234
238240
242
201A
201B201
205A
200
205
204
202C
202B202A
202
CORRIDOR 201
12x12 UP/DN.
12x10
14x8
16x10 UP
10x10
T
T
12x6 UP
8"∅
18x16 UP
12x10
16x14
18x10 UP
16x8
12X6
UP
12x10
12x12 UP
12x1010x88x8
16x12 UP
8"∅
12"∅
14"∅
10x8 UP
T
12x12
14x14
12x8T
8x6
14x12
T
12x1010x8
12x10 UP
8x4
14x10
12x6
T
18x12 UP
10x1014x1010x10
14x12 UP
10x6
10x10
16x10
16x14 UP18x10 UP
14x8
T
T
6x12 UP
6x86x8
T
T
16x12 UP
12x10
18x10 UP
12x10
14x10
T
10x8
14x8
10x6
16x14
16x10
12x6
12x10
T
12x10
12x6
12x10 UP
12x8
18x12 UP12x1010x8
10x8
12x10 UP
8x8
16x8
T
8x8
18x10
12x10
8x14 UP & DN.
14x8
12x12
12x10 UP
T
16x8
10x10
12x10
16x10 UP & DN.
12x12 UP & DN.
12x12 UP & DN.
12x12 UP & DN.
16x12 UP
16x14 UP
16x10
18x12
FD
10x8
19 19
19 19
19 19
222222
9
1411
7 7
25
26
17
17
11 11
11
T
1111
17 21
17
25
3
20
20
T
77
17
14
1411 11
1414141414
1111
2323
23 23
77
2828
27
27
27
11
8
11
17
14
24
11
17
16
16
20
1414OFFICE
257A
4
T
15
10
12
19
19
1719
6
7
9
T
T
17
17
17
17
17 1721
18 18 18 18
FD
1815
FD
9
FD
12x10 6x4
T
18x10
8x6
16x14
10x8
16x6
14x12
16x14 DUCT CONTINUES DOWN TO SERVE
FIRST FLOOR ALSO.
252C
R.R.R.R.
T
T
T
12x10
10x8 UP & DN.
12x10 UP & DN.
UP
UP
29
1
DRAWING NOTES:
6x6 EXHAUST GRILLE, 6x6 DUCT UP TO ATTIC SPACE.1
30 30
8x6
8x612x6 UP
33
12x10
UP
14x14 UP
36 36
12x10
14x14 UP
12X10 UP
& DN.
12x6 UP & DN.
31
2
10x6 EXHAUST GRILLE, 8x6 DUCT UP TO ATTIC SPACE.2
14x8 UP
10x10 UP
16x8 UP/DN.
6x6 UP AND
DN.
29
1
3
14x8 R.A. UP & DN3
4
18x14 R.A. UP, 14x14 R.A. DN.4
5
16x14 R.A. UP, 10x8 R.A. DN.5
20x14 R.A. UP, 16x8 R.A. DN.6
6
MATCH L
INE
T
T
T
T
20x14
16x10 8"∅
14x10
41
18x12 R.A. UP, 12x12 R.A. DN.7
7
10x8
8
16x14 R.A. UP, 12x10 R.A. DN.8
10x12 UP
& DN.
16x8 UP
& DN.
18x12 R.A. UP, 12x8 R.A. DN.9
16x14 R.A. UP & DN.10
10
14x6
39
20x14 R.A. UP, 12x10 R.A. DN.11
20x16 R.A. UP, 18x10 R.A. DN.12
12
12x10
16x14
UP
42
39
12x6
12x8
41 8x6
39
10x8
8x8
41
39
8x6
12x8 UP
& DN.
18x14 R.A. UP, 14x10 R.A. DN.13
13
41
12x10
8x6
14
14x12 R.A. UP, 10x8 R.A. DN.14
20x12 R.A. UP, 10x6 R.A. DN.15
15
39 39
10x1010x8
20x14 R.A. UP, 16x10 R.A. DN.16
16x1016
8x6
41
16x12 R.A. UP, 8x6 R.A. DN.17
17
14x1439
8x6
A
A
A
A18x12 UP
UP
12x1012x10
14x8
28
14x8
28
14x8
14x8
16x10
14x8
14x8
8x8
12x6
8x8
12x6
14x8 12x612x6 10x8
11
10x8 10x8
12x6 12x6
14x8
12x6 14x610x610x6
8x8
12x6
10x6
12x6
8x8
12x6
10x610x66x10
12x612x612x6
8x8
12x6
8x8
12x610x4 10x410x4
10x6
8x812x6
12x6 12x6 10x6
12x8
10x6
12
10x6
12
10x6
12x6 12x6
19
10x8
12x6
12x612x6
12x6
1919
12x6
14x6
10x8
12x612x6
10x8
12x6 12x6 12x6 12x6
10x8
12x6 12x6
12x6 12x6
12x6 12x6
10x6 12x6
8x8
10x6
12x6
10x8
10x6
12x6
10x8
OFFICE
236
UP/DN10x8
8x6 UP
OFFICE
201C
11
10x8
9
18
14x6
42
14x12
20x12 UP
42
42
14x6
14x10 R.A. UP, 12x6 R.A. DN.18
& DN.
16x8 UP
& DN.
12x10 UP
UP & DN.
10x8
UP/DN.UP
10x8 UP & DN.
12x8 UP & DN.
& DN.
& DN.
11
30x20 UP/DN
48x36 UP/DN
30x30 UP/DN
40x30 UP/DN
40x20 UP/DN
40x30 UP/DN
30x30 UP/DN
3" HS/HR UP/DN
DN
DUCT SPACING SHOWN FOR CLARITY ONLY. DUCT SHALL BE
SPACED NO MORE THAN 1" APART FOR CEILING OPENINGS WITH
TWO DUCTS PENTRATING THE AREA.
19
19
14x14
19
19
19
19
UP
UP
19
UP/DN.
UP/DN.
UP UP
ROCKVILLE, MD 20852
TEL: 301-770-0802
FAX: 301-770-0832
11820 PARKLAWN DRIVE
SUITE 316
20 EXISTING CONVECTOR. 1/2" HS AND HR TO/FROM CONVECTOR.
20
20 20
20
20
20
KEY PLAN
NOT TO SCALE
NOT IN SCOPE
UNIVERSITY OF MARYLAND
SCALE:
PROJ. NO.
DWN BY:
APP BY:
BALTIMORE COUNTY
BALTIMORE, MARYLAND
Gipe Associates Inc.Consulting EngineersBaltimore, Maryland
Easton, Maryland
HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER
PROJECT TITLE:REVISION No. DATE EXPLANTION
SEAL
AS NOTED
SHEET OF
DRAWING TITLE:
ROCKVILLE, MD 20852
TEL: 301-770-0802
FAX: 301-770-0832
11820 PARKLAWN DRIVE
SUITE 316 23 FEB 2000 CONSTRUCTION DOCUMENTS
20
MJP
SAM
4
1
1
1
1
1
1
1
20x12 OED
1
14x10 OED
40x10
OED
24x8
TRANSFER
DUCT
24x8
TRANSFER
DUCT
24x24 PERFORATED
GRILLE (TYPICAL)
16x8 TRANSFER
DUCT (TYPICAL)
24x12
OED
1
32x8 TRANSFER
DUCT
12x8
20x12 OED
20x12 OED
114x8 OED14x8
1
24x12 OED
1
24x12 OED
3924x12 OED24x24 PERFORATED
GRILLE (TYPICAL)16x8 TRANSFER
DUCT (TYPICAL)
24x8 TRANSFER
DUCT (TYPICAL)1
14x8
OED
124x8 TRANSFER
DUCT
24x12
OED
1
24x12
OED
20x16 UP42x12
OED
24x24 PERFORATED
GRILLE (TYPICAL)
24x12 OED
24x8 TRANSFER
DUCT
1
FD
2
FD
2
FD
2FDFD
2
FD
2
FD
2
FD 2
T
11
16x10
14
12x6
18x10
UP
14x8
25
OED
ATTIC
HATCH
12x12 UP/DN
T
24x8 RA
GRILLE
T
8x6 DN
T
14x8
14x8 DNUP
T
T
16x14 UP
& DN.
24x14
OED
HATCH
ATTIC
HATCH
ATTIC
HATCH
ATTIC
HATCH
ATTIC
16x10 RA
GRILLE
12x1012x10 RA
GRILLE
15 MAR 2001 EMJAY AS-BUILT MOD'S
10 MAY 2000 VALUE ENGINEERING
23 FEB 2000 CONSTRUTION DOCUMENTS
1
20
KEY PLAN
NOT TO SCALE
NOT IN SCOPE
FIRST FLOOR - PLAN
SCALE: 1/8" = 1'-0"
N
8
SCALE: 1/8" = 1'-0"
0 8 16
M-1
FIRST FLOOR - PLAN
UNIVERSITY OF MARYLAND
SCALE:
PROJ. NO.
DWN BY:
APP BY:
BALTIMORE COUNTY
BALTIMORE, MARYLAND
Gipe Associates Inc.Consulting EngineersBaltimore, Maryland
Easton, Maryland
HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER
PROJECT TITLE:REVISION No. DATE EXPLANTION
SEAL
AS NOTED
SHEET OF
DRAWING TITLE:
STAIRWAY
OFFICE
RR
STORAGE
STORAGE
OFFICE
RR
SHOWERS
ELEC RM
OFFICE
OFFICE
OFFICE
OFFICE
COMPUTER LABLAB
STORAGE Q
STORAGE
(GAS CANISTERS
FOR
LABS)
OFFICE
OFFICEOFFICE
DOWN
FD
STORAGE
FD
OFFICE
STAIRWAY
STORAGE
CLASSROOM
RESTROOM
NOT IN SCOPE
STORAGE
CONFERENCE
STAIRWAY
OFFICEOFFICEOFFICEOFFICEOFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICEOFFICE
OFFICE
OFFICEOFFICE
OFFICEOFFICE
MED
ICAL RM
LAB
OFFICEOFFICEOFFICE
OFFICE
RESTROOM
LAB
LAB
OFFICE
OFFICE
STORAGE
NOT IN SCOPE
MOD MOD
AHU No.2
180 CORRIDOR
180G
180H
180F
180E
180D
180I
180J
180K
180C 180B
180A
180
180L
CORRIDOR
CORRIDOR
132
130
128 126
124
122
120
STORAGE
STORAGE
STORAGE
STORAGE
VENDING
150
STORAGE Q/A148
151
157
159
STAIR
STORAGE
105B
105A
JANITOR
103
WOMENS MENS
JAN.
105
CORRIDOR
104
STORAGE
187
188
185183
181
186
184182
180
179177 175
173
171
178 176 174172
170
MAIN
180
160
162
161163
165
167
169
164166 168
CORRIDOR #3CORRIDOR
CORRIDOR
CORRIDOR
CORR
IDOR
CORRIDOR
AHU No.1
12x10
12x12 UP
T
T
16x8 UP
12x8
T
12x6
12x10 UP
FD
FD
6x4
FD
6x4
12x8
FD
FD
10x8
8"∅
6"∅
T
6x4
FDT
14x8
T
16x8 UP
T
T
12x12 UP
12x10 6x6
12x8T
10x8
10x8
16x8
6"∅6x612x8
12x6
T
10x8
T
T
10x6
10x10
10x10
16x14
10x10
14x12
12x10
12x8
10x6
10"∅
T
8"∅
T
12x10
12x10
T
16x10 UP
12x8 12x10
T
10x8
12x12UP
T
10x8
12X12 UP
12x810x8
8x610x8
12x8
16x12 UP
T
10x10
10x8
16x14 UP
T
14x12
12x1010x88x6
T
2
9 9
11
2
11
9
11 11
11
15
3
17
17
21
21
FD
4
4
11 2 8
8
10 10
15 15
12
12
12
6
21
4 4 4
21
2
1
8 11 11
2
9
9
11
21
10
4
17
14 14
2
7
7
T
13 13 13
5
5
T
T
2
FD
15
15
FD
FD
4
FD
9
FD
9
FD
9
FD
9
9FD
FD
9
FD
9
FD
9FD
9FD
9
FD
9
FD FD
9 9FD
9
FD
9
22FD
2
15
12x10
10x810x6
10x8
8x6
10x612x6
6"∅
10x6
10x10
10x8
6x8
8x6
10x812x12
16x14 UP
8x6 16x8
12x8 10x6
40x30
50x50VD
40x30
6x6
6x6
UP
8x6
2929
3332
12x10 UP
29
12x10 UP
14x8 UP
10x8
CHSCHR
CHS
CHR
DRAWING NOTES:
1
1
1 REFER TO DRAWING M-6, BOILER ROOM NEW WORKPARTIAL PLAN FOR CONTINUATION OF PIPING.
40x30
29
8x6 UP
14x14
UP
10X8
12x12
8x6
8x6
10x8 UP
10x8
16x8 UP
41
43
4112x8
12x10 UP
9
12x10 UP
12x8 UP
10x810x6
8x6
39
40 40
16x14
UP
RM
18x10
12x6
155
14x10 UP
10x6
10x8 UP
8x8
39
8x6
10x6 UP
10 10
16x10 UP
39
40
8x6 UP
12x8 UP
8x6
39
42
39
8x612x6
30x20 UP
16x8
UP
16x8 TRANSFER
12x10
10x8
UP
29 29 31
8x6
12x10 UP
2
UP
39
8x6
40
12x6
UP8x6
8x6
41
UP
2
2 12x12 EXHAUST GRILLE, 10x8 DUCT UP TOATTIC SPACE.
3 8x6 EXHAUST GRILLE, 12x6 DUCT UP TO ATTIC SPACE.
3
8x6
10
8x6
12x10
8x6
8x6
8x6
8x6
8x6
39
UP
8x6
8x6
39
39
8x6
10x6
6x6
21
17
11
11
17
UP
8x612x12
12x10
UP
48x36
48x36
UP
4
5
4 40x30 RETURN AIR DUCT.
5 40x20 RETURN AIR DUCT UP.
6
6 40x30 SUPPLY AIR DUCT UP.
7
7 30x30 RETURN AIR DUCT UP.
30x30 UP
8
8 40x40 RETURN AIR DUCT
EXISTING CONCRETE PAD TO BE REMOVED
REMOVE CONCRETE PATIO IN
THIS AREA TO POINT INDICATED.
REMOVE THE ENTIRE ROOF AND
ALL APPURTENANCES BACK TO
EXTERIOR BUILDING WALL.
REMOVE CONCRETE TO THIS POINT
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
A.
B.
C.
D.
E.
F.
G.
17.
GENERAL NOTES: (APPLIES TO MECHANICAL DRAWINGS):
THE LOCATION OF EXISTING UNDERGROUND UTILITIES IS SHOWN IN AN APPROXIMATE WAY ONLY.
DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. REPAIR ALL
DAMAGES OCCASIONED BY FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UNDERGROUND
UTILITIES.
MAINTAIN MINIMUM OF 3'-0" COVER OVER UNDERGROUND CHILLED WATER MAINS.
PROVIDE AN AIR VENT AT THE HIGH POINT OF EACH DROP IN THE HEATING AND CHILLED WATER SYSTEMS.
UNLESS OTHERWISE NOTED, ALL PIPING AND DUCTWORK IS OVERHEAD.
INSTALL PIPING AND DUCTWORK SO THAT ALL VALVES AND DAMPERS ARE ACCESSIBLE.
COORDINATE ALL MECHANICAL WORK WITH ELECTRICAL WORK, ETC., SHOWN ON OTHER DRAWINGS.
EXCEPT AS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS 4'-0" (CENTERLINE) ABOVE FINISHED FLOOR ADJACENT TO THE ROOM LIGHT SWITCH. NOTIFY THE ENGINEER OF ANY ROOMS
WHERE THE ABOVE LOCATION CANNOT BE MAINTAINED OR WHERE THERE IS A QUESTION ON LOCATION.
MAINTAIN MINIMUM 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUIT, SUSPENDED EQUIPMENT,
ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL AND ELECTRICAL ROOMS.
CERTAIN ITEMS SUCH AS CLEANOUTS, ACCESS DOORS, RISE AND DROPS IN DUCTWORK, ETC., ARE INDICATED
ON THE DRAWINGS FOR CLARITY OR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED
AS THE EXTENT OF THE REQUIREMENTS FOR THOSE ITEMS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
THESE ITEMS AS REQUIRED ELSEWHERE IN THE CONTRACT DOCUMENTS.
EQUIPMENT CONNECTION SIZES MAY DIFFER FROM INDICATED DUCT OR PIPE SIZES. PROVIDE APPROPRIATE
TRANSITIONS WHERE REQUIRED.
THESE DRAWINGS ARE DIAGRAMMATIC AND ALL OFFSETS, FITTINGS, TRANSITIONS AND ACCESSORIES ARE
NOT NECESSARILY SHOWN. COORDINATE THE INSTALLATION OF ALL PIPING, DUCTWORK, EQUIPMENT AND
OTHER WORK WITH ALL OTHER TRADES.
IT IS THE INTENT THAT ALL WORK SHALL BE COMPLETE IN EVERY RESPECT AND THAT MATERIAL OR WORK
SPECIFICALLY NOT INDICATED ON DRAWINGS, BUT NECESSARY TO COMPLETE THE WORK, SHALL BE
FURNISHED.
EXACT LOCATION OF DIFFUSERS, REGISTERS AND GRILLES PROVIDED IN CEILING SHALL BE COORDINATED
WITH EXISTING CEILING.
REFER TO AIR DEVICE SCHEDULES FOR SIZE OF DUCT FROM BRANCH DUCT TO NECK OF AIR DEVICE.
ALL BRANCH DUCT RUNOUTS TO AIR DEVICES SHALL BE PROVIDED WITH
VOLUME DAMPERS.
MATERIAL, EQUIPMENT, INSTALLATION AND PROCEDURES SHALL BE IN STRICT ACCORDANCE WITH THE
APPLICABLE REQUIREMENTS OF THE LATEST CURRENT EDITION OF THE REFERENCED DOCUMENTATION.
REGULATIONS OF LOCAL AUTHORITIES HAVING JURISDICTION.
NFPA-NATIONAL FIRE PROTECTION ASSOCIATION.
SMACNA - SHEET METAL AND AIR CONDITIONING NATIONAL ASSOCIATION.
ASME - AMERICAN SOCIETY OF MECHANICAL ENGINEERS.
ASTM - AMERICAN SOCIETY OF TESTING AND MATERIALS.
ASHRAE - AMERICAN SOCIETY OF HEATING, REFRIGERATION AND AIR CONDITIONING ENGINEERS, INC.
BOCA, NATIONAL PLUMBING CODE, LATEST ADOPTED EDITION.
ALL AUTOMATIC TEMPERATURE CONTROL SETPOINTS SHALL BE ADJUSTABLE.
UP
9
9 DUCT SPACING SHOWN FOR CLARITY ONLY. DUCT SHALL BE
SPACED NO MORE THAN 1" APART FOR CEILING OPENINGS WITH
TWO DUCTS PENTRATING THE AREA.
9
9
9
9
9
9
ROCKVILLE, MD 20852
TEL: 301-770-0802
FAX: 301-770-0832
11820 PARKLAWN DRIVE
SUITE 316
8x68x6
PROVIDE FLOW METERS NEXT TO ALL BALANCING VALVES SERVING 2 OR MORE PIECES OF EQUIPMENT
AND WHERE INDICATED ON PLANS.
PROVIDE DRAIN VALVES AT ALL LOW POINTS FOR DRAINAGE OF PIPING SYSTEMS.
18.
19.
REMOVE EXISTING EXHAUST FAN, DUCTWORK AND ALL APPURTENANCES ON THIS WALL TO ALLOW INSTALLATION OF
PROPOSED DUCTWORK AS INDICATED.
10
10
11 EXISTING CONVECTOR. 1/2" HS AND HR TO/FROM CONVECTOR.
11
12 EXISTING UNIT HEATER. 1/2" HS AND HR TO/FROM UNIT HEATER.
12
11
11
EX HEAT PUMP
EX AHU
EX 24x12 SUPPLY
13 PROVIDE HOT WATER HEATING COIL IN EXISTING 24x12 DUCT.
21,600 BTUH, 2000 CFM, 2.2 GPM, 1-ROW, .05 APD MAX, 80 EAT.
13
14 3/4" HS AND HR TO/FROM HEATING COIL.
14
G
NEW GAS
SERVICE BY
BGE
KEY PLAN
NOT TO SCALE
NOT IN SCOPE
UNIVERSITY OF MARYLAND
SCALE:
PROJ. NO.
DWN BY:
APP BY:
BALTIMORE COUNTY
BALTIMORE, MARYLAND
Gipe Associates Inc.Consulting EngineersBaltimore, Maryland
Easton, Maryland
HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER
PROJECT TITLE:REVISION No. DATE EXPLANTION
SEAL
AS NOTED
SHEET OF
DRAWING TITLE:
ROCKVILLE, MD 20852
TEL: 301-770-0802
FAX: 301-770-0832
11820 PARKLAWN DRIVE
SUITE 316 23 FEB 2000 CONSTRUCTION DOCUMENTS
20
MJP
SAM
3
NOTE:
REFER TO ELECTRICAL SITE PLAN
E-2 FOR CHILLER LOCATION AND
CHILLED WATER PIPE ROUTING
1
1
1
1
OPENING
24x24 PERF. GRILLE
(TYP.) 22x8 OED.
16x8 TRANSFER
OPENING
22x8 OED.
16x8 TRANSFER
OPENING
24x24 PERF. GRILLE
(TYP.)
1
1
24x8 OED.16x8 OED.
16x8 TRANSFER
OPENING (TYP)
24x24 PERF. GRILLE
(TYP.)
1
24x8 OED.
24x24 PERF. GRILLE
(TYP.)
1
24x10 OED.
24x24 PERF. GRILLE
(TYP.)
1
8x6 OED.
24x24 PERF. GRILLE
(TYP.)
1
32x8 TRANSFER
GRILLE
22x14 OED.
24x8 TRANSFER
OPENING
24x24 PERF. GRILLE (TYP)
16x8 TRANSFER
OPENING
16x8 TRANSFER
OPENING22x8 OED.
1
22x8 OED.
10x8 OED.16x8 TRANSFER
OPENING
16x8 TRANSFER
OPENING
16x8 OED.12x8 OED.
24x24 PERF. GRILLE (TYP)
16x8 TRANSFER (TYP)
1
ALL AIR TRANSFER OPENINGS SHALL BE SLEEVED.
ALL OPEN END DUCTS TO HAVE BIRD SCREEN AND VOLUME DAMPERS.
24x24 PERFORATED GRILLES TO BE FIELD LOCATED.
FIELD VERIFY NEED FOR FIRE DAMPERS IN EXISTING WALLS.
20.
21.
22.
23.
1
FD
FD
2
2
FD
2
FD
2
FD
2
FD2
FD
2
FD 2
FD
2
FD
FD
2
2
FD2
2
2
2
2
2
FD
FD
FD
14x8
16x8 TRANSFER
OPENING
G
G
10x10
10x10 OED.
56x34
SD
SD
SD
SD
G
4"
24x8
OED
16x6
OED
20x4
FD
3
3
3
3
3
3
22x8
OED
T
14x14
UP
16x8
OED
12x12
UP
12x12
12x10
12
12
14x8
UP
24x8
OED
16x8
OED
16x8
OED
FD
9
FD FD FD FD99
FDFD
20
23 FEB 2000 CONSTRUCTION DOCUMENTS
10 MAY 2000 VALUE ENGINEERING1
15 MAR 2001 EMJAY AS-BUILT MOD'S
8
SCALE: 1/8" = 1'-0"
0 8 16
ATTIC - PLAN
SCALE: 1/8" = 1'-0"
MATCH L
INE
N
ATTIC - PART
SCALE: 1/8" = 1'-0"
N
M-3ATTIC - PLAN
EF
EF
EF
EF
HATCH
EF
EF
HATCH
EF
12x10
12x12 DN.
12x12
16x8 DN.
12x10
18x10
16x10 DN.
12x6 DN.
18x16
18x10
DN.12x12 DN.
16x12
10x8
10x10
12x12
14x12
12x10 DN.
18x12 DN.
14x12 DN.
16x10 16x10
16x14 DN.
18x10
12x16 DN.
18x10 DN.
16x14 DN.
12x10 DN.
18x12 DN.
12x10 DN.16x8 DN.
18x10 DN.
14x8 DN.
12x12
12x10
DN.
10x8 DN.
16x8 DN.
12x10 DN.
10x10 DN.
14x16
12x10
12x10 DN.
16x10 DN.
12x12 DN.
12x12 DN.
12x12 DN.16x14 DN.
18x12
40
23
41
39
42
54
22 21
55
53
52
20
19
15
45
46
16
47
49
48
17
18
51
50
44
32 11
34
3331
36
35
12
37
14
13
38
10
30
9
87
29
6
4
5
27
26
3
25
24
2
1
28
56
12x6 DN.
48x36
43
40x30
10x8 DN.
57
16x14 DN.
9'-0"
1
M-3
1
M-3
SECTION
SCALE: 1/8" = 1'-0"
1
M-3
STUD (TYP.)
FIN. FL.
40x30
12x10
18x10
30x24
30x20
12x6
16x8
10x8
10x6
8x620x14
20x8
12x6
40x30
10x8
40x20
40x18
10x8
12x10
30x18
30x18 20x14 16x14
12x6
12x8
16x8
8x4
12x8
20x10
30x20
10x6
14x10 DN.
30x20
8x8
12x10
14x8
24x1820x16
8x6
20x16
8x6
10x6
10x8
10x6
14x14 DN.
12x10
30x20
12x12
16x12
14x10 DN. 16x12 DN.
12x6
10x10
12x8
30x18
16x8
12x6
8x6
30x14
8x6
18x18
10x10
10x8
VDVDVD
18x12
VD
14x10
14x10
VD
12x6
40x24
40x30
18x16 8x8
18x14
VD8x6
VD
12x6
16x10
10x8
VD
20x16
16x8
14x14
VD
10x810x10
VD
12x10
40x14
40x14
12x12
30x14
VD
10x10
18x12
10x812x10
30x20 S.A.
9'-4"
STUD (TYP.)
FIN. FL.
2
M-3
2
M-3
2
M-3
SECTION
SCALE: 1/8" = 1'-0"
16x812x8
14x14 DN. & UP
14x14 DN. & UP
THRU ROOF
THRU ROOF
10x8
12x10 DN. & UP THRU ROOF
6x6 DN. & UP
THRU ROOF
10x10 UP
THRU ROOF
8x6 DN.
8x6 UP
12x6 DN. & UP THRU ROOF
16x14 DN.
16x14 UP
THRU
ROOF
8x6 DN. & UP
THRU ROOF
14x8 DN.
6x6 DN.
6x6 UP
6x6 DN.
6x6 UP TO
THRU ROOF
18x14
DN.
8x8
16x14 DN.
14x20 DN.
MATCH L
INE
2700
20x16
12x18
20x20
20x20 R.A.
16x14
DN.
12x10
DN.
500
18x12 DN.
16x14 DN.
14x20 DN.
16x20
DN.
16x14
DN.
12x8 DN.
14x18 DN.
14x12 DN.
20x12 DN.
1500
20x14 DN.
16x12 DN.B
B
B
B
12x10
12x6
DN.
DN.
18x16
DN.
DN.
DN.
DN.
18x10
DN.
DN.
DN.
20x16
18x12
18x12
12x8
20x18
20x16
30x18
20x18
30x20
16x8 DN.
14x10 DN.
750
20x12 DN.
18x10 DN.
10x8 DN.
12x8
DN.
DN.
S.A. DN. R.D. DN.
30x30 R.D. DN.
20x14
30x1830x1420x1420x14
40x30 S.A. DN.
30x20 DN.
30x20
40x20 R.A. DN.
30x20
30x20
20x1820x16
14x8
20x16 R.A.
40x20 R.A.
DRAWING NOTES:
1 EXHAUST FAN IN VERTICAL POSITION.
1
1 1
1
1
1
12x6 DN. & UP
THRU ROOF
1
1
DN.
20x14 S.A.
E.F. No.15
E.F. No.18
E.F. No.14
E.F. No.3
E.F. No.17
E.F. No.7
E.F. No.9
E.F. No.16
E.F. No. 10
1
1
E.F. No.13
E.F. No.12
E.F. No.19
E.F. No.20
E.F. No.21
UNIVERSITY OF MARYLAND
SCALE:
PROJ. NO.
DWN BY:
APP BY:
BALTIMORE COUNTY
BALTIMORE, MARYLAND
Gipe Associates Inc.Consulting EngineersBaltimore, Maryland
Easton, Maryland
HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER
PROJECT TITLE:REVISION No. DATE EXPLANTION
SEAL
AS NOTED
SHEET OF
DRAWING TITLE:
SP
SP
SP
SP
SP
STATIC PRESSURE
SENSOR (TYP.)
FIN. FLOOR
CEILING
18x12 R.A.
30x14 S.A.
40x20 S.A.
30x20 R.A.
9'-4"STUD (TYP.)
SECTION
SCALE: 1/8" = 1'-0"
3
M-3
3
M-3
3
M-3
48x36 S.A.
30x20 R.A.
6x12 S.A.
GOOSE NECK
(TYP.)EXHAUST FAN IN
VERTICAL POSITION
VAV BOX12x10 EXH.
FIN. FLOOR
40x14 S.A.
30x18 R.A.40x30 S.A.
30x30 R.A.
FIN. FLOOR
8'-4"
14x10 R.A.
40x30 30x30
SECTION
SCALE: 1/8" = 1'-0"
4
M-3
4
M-3
4
M-3
12x6 S.A.
CEILING
EXISTING ROOF RIDGE
16" O.C. (TYP.)
ATTIC FLOOR
53 1/2" MIN.
EXISTING RAFTER
(TYP.)
DUCT PENETRATION - DETAIL
SCALE: 1/4" = 1'-0"
9'-0"
36x48
ATTIC FLOOR
48x36
EXISTING ROOF RIDGE
STUD (TYP.)
SECTIONELEVATION
ROOF SLOPES
8x16
DN.
DUCT SPACING SHOWN FOR CLARITY ONLY. DUCT SHALL BE
SPACED NO MORE THAN 1" APART FOR CEILING OPENINGS WITH
TWO DUCTS PENTRATING THE AREA.
2
2
2
2
14x14
ROCKVILLE, MD 20852
TEL: 301-770-0802
FAX: 301-770-0832
11820 PARKLAWN DRIVE
SUITE 316
GENERAL NOTES:
CONTRACTOR SHALL REFER TO PRECAST PLANK DETAIL ON
STRUCTURAL DRAWING S-1 FOR CRITERIA OF DUCT
PENTRATIONS TO ATTIC FLOOR.
1.
2
2
2
2
2
48x36 S.A. DN.
40x20
CONTRACTOR TO PROVIDE A MEANS TO WALKOVER ANY
LOW LYING DUCTS CROSSING ATTIC CORRIDORS.
2.
PROVIDE FIRE DAMPERS AT ALL FLOOR AND ATTIC
PENETRATIONS.
3.
KEY PLAN
NOT TO SCALE
NOT IN SCOPE
UNIVERSITY OF MARYLAND
SCALE:
PROJ. NO.
DWN BY:
APP BY:
BALTIMORE COUNTY
BALTIMORE, MARYLAND
Gipe Associates Inc.Consulting EngineersBaltimore, Maryland
Easton, Maryland
HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER
PROJECT TITLE:REVISION No. DATE EXPLANTION
SEAL
AS NOTED
SHEET OF
DRAWING TITLE:
ROCKVILLE, MD 20852
TEL: 301-770-0802
FAX: 301-770-0832
11820 PARKLAWN DRIVE
SUITE 316 23 FEB 2000 CONSTRUCTION DOCUMENTS
20
MJP
SAM
5
12x10
16x12
1
1
1
1
1
1
1
1
HATCH
ATTIC
12x12
DN.
HATCH
ATTIC
HATCH
ATTIC
WALKWAY
SP
WALKWAY
23 FEB 2000 CONSTRUCTION DOCUMENTS
10 MAY 2000 VALUE ENGINEERING1
15 MAR 2001 EMJAY AS-BUILT MOD'S
20
8
SCALE: 1/8" = 1'-0"
0 8 16
ROOF - PLAN
SCALE: 1/8" = 1'-0"
MATCH L
INE
MATCH L
INE
N
ROOF - PART PLAN
SCALE: 1/8" = 1'-0"
N
M-5ROOF - PLAN
14x14 GOOSENECK
14x14 GOOSENECK
10x10 GOOSENECK
12x10 GOOSENECK
6x6 GOOSENECK
12x6 GOOSENECK
10x10 GOOSENECK
8x6 GOOSENECK
12x6 GOOSENECK
16x14 GOOSENECK
8x6 GOOSENECK
6x6 GOOSENECK
6x6 GOOSENECK
10x8 GOOSENECK
UNIVERSITY OF MARYLAND
SCALE:
PROJ. NO.
DWN BY:
APP BY:
BALTIMORE COUNTY
BALTIMORE, MARYLAND
Gipe Associates Inc.Consulting EngineersBaltimore, Maryland
Easton, Maryland
HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER
PROJECT TITLE:REVISION No. DATE EXPLANTION
SEAL
AS NOTED
SHEET OF
DRAWING TITLE:
30x3040x30
30x30
40x30
40x20
48x36
30x20
ROCKVILLE, MD 20852
TEL: 301-770-0802
FAX: 301-770-0832
11820 PARKLAWN DRIVE
SUITE 316
KEY PLAN
NOT TO SCALE
NOT IN SCOPE
UNIVERSITY OF MARYLAND
SCALE:
PROJ. NO.
DWN BY:
APP BY:
BALTIMORE COUNTY
BALTIMORE, MARYLAND
Gipe Associates Inc.Consulting EngineersBaltimore, Maryland
Easton, Maryland
HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER
PROJECT TITLE:REVISION No. DATE EXPLANTION
SEAL
AS NOTED
SHEET OF
DRAWING TITLE:
ROCKVILLE, MD 20852
TEL: 301-770-0802
FAX: 301-770-0832
11820 PARKLAWN DRIVE
SUITE 316 23 FEB 2000 CONSTRUCTION DOCUMENTS
20
MJP
SAM
EF-3
FOR EF-21
FOR EF-17
FOR EF-7
FOR EF-20
FOR EF-9
FOR EF-10
FOR EF-16
FOR EF-13
FOR EF-12
FOR EF-14
FOR EF-18
FOR EF-15
FOR EF-19
7
1 1
1
1 1
1
20
23 FEB 2000 CONSTRUCTION DOCUMENTS
10 MAY 2000 VALUE ENGINEERING1
15 MAR 2001 EMJAY AS-BUILT MOD'S
M-7DETAILS
SCALE: NONE
FIRE DAMPER - DETAIL
EACH SIDE OF
DIAMETER BOLTS
COLLAR W/ 1/4"
BE SECURED TO
DAMPER SHALL
1/4" DIA. BOLTSCOLLAR ONLY W/
DAMPER
FASTENED TO
STEEL ANGLES
PROVIDE SLIP JOINT
NEGATOR CLOSURE
STAINLESS STEEL
UNLESS OTHER-
FOR 1-1/2 HR.
IN DUCTWORK ON
SPRING
WISE NOTED
U.L. LABELED
FIBERGLASS
LOW DENSITY
FLOOR CONSTRUCTION
CONCRETE OR STEEL
BLADE LOCK
PACKING
FUSIBLE LINK
DUCT
SHEET METAL
STEEL BLADES
ACCESS PANEL
COLLAR
COIL
W/ NEEDLE VALVE(TYP)
PRESSURE GAUGE
VENT (TYP)
MANUAL AIR
GATE VALVE (TYP)
END DRAIN VALVESTRAINER W/HOSE
HOSE END DRAIN
VALVE (TYP)
THERMOMETER (TYP)
UNION (TYP)
SCALE: NONE
CWS
BALANCING VALVE
THREE-WAY MODULATING
COMBINATION SHUT-OFF
CWR
VALVE (ATC)
SCHEDULE 40 GALVANIZED STEEL PIPE
PIPE AND INSULATION TO BE
PIPE SLEEVE THRU INTERIOR WALL
SMALLER, 20 GAUGE; 4" TO 6", 16 GAUGE; OVER 6", 14 GAUGE.
NOTE: FOR INTERIOR FRAME PARTITIONS-PIPE SLEEVES MAY BE FABRICATED FROM GALVANIZED
SHEET METAL; ROUND TUBE CLOSED WITH SNAPLOCK JOINT, WELDED SPIRAL SEAMS, OR
WELDED LONGITUDINAL JOINT. FABRICATE FROM THE FOLLOWING GAUGES: 3" AND
CONCEALED PIPING
NOT SUPPORT PIPE FROM
CENTERED IN SLEEVE - DO
SLEEVE COMPLETELY COVER OPENING
AGAINST WALL AND OF SIZE TO
FINISHED ESCUTCHEON PLATE FLUSH
FINISHED WALL SURFACE
PIPING EXPOSED TO VIEW
SCALE: NONE
SEAL SLEEVES THRU FIRE/SMOKEWALLS AND FLOOR IN A SMOKE
TIGHT MANNER WITH AN APPROVED
THROUGH RATED ASSEMBLIES
SEALED PER A LISTED ASSEMBLY
FIRE STOP CAULK. SLEEVES
SHALL BE CONSTRUCTED &SLEEVE OF SIZE TO PASS PIPE
FINISHED WALL SURFACES
TERMINATE SLEEVE FLUSH WITH
AND INSULATION; REMOVE BURRS
VARIABLE AIR VOLUME BOX
3'-0" MIN. BEFORE TAKE
MANUAL VOLUME DAMPER
(TYP. FOR EACH DIFFUSER)
LOW PRESSURE DUCT TO
PLAN VIEW
VARIABLE AIR VOLUME BOX
V.A.V. BOX
DUCT STRAP (TYP.)
SCALE: NONE
REMOVABLE ACCESS PANEL
(DO NOT OBSTRUCT)CONTROLLER
CONTROL BOX
SUPPLY AIR DUCT
SUPPLY AIR MAIN
MEDIUM PRESSURE
VARIABLE PRIMARY
3 DUCT DIAMETER MIN. STRAIGHT DUCT
CONICAL
TAP
AIRFLOW
MIN. CLEAR
HEAT COIL
FOR SERVICING
MAINTAIN 24"
6"
OFF OR ELBOW
DIFFUSER
12"
MIN.
GOOSENECK DETAIL
ANGLE IRON REINFORCING
WHERE REQUIRED
METAL SCREEN
ANGLE RIVETED OR
TRACK WELDED
AS REQUIRED
DUCT SIZE +25
48" MINIMUM
SCREEN
FRAME
BOLTS
36" MIN.
135 MIN.
R
R=W-
2
AND JOINTS
ROOF
WATERPROOF SEAMS
SCALE: NONE
UNIVERSITY OF MARYLAND
SCALE:
PROJ. NO.
DWN BY:
APP BY:
BALTIMORE COUNTY
BALTIMORE, MARYLAND
Gipe Associates Inc.Consulting EngineersBaltimore, Maryland
Easton, Maryland
HVAC RENOVATIONS - TECHNOLOGY RESEARCH CENTER
PROJECT TITLE:REVISION No. DATE EXPLANTION
SEAL
AS NOTED
SHEET OF
DRAWING TITLE:
CURB
6" MIN.
EXHAUST
SCALE: NONE
AIRFLOW
3'-0" MIN. STRAIGHT
DUCT FULL SIZE OF
FAN CONNECTION
VIBRATION ISOLATOR (TYP.)
5/8" MIN. ALL THREAD ROD(TYP. OF 4 MIN.)
30 MAXIMUM
FLEXIBLE CONNECTION (TYP.)
CABINET FAN
COMBINATION SPRING
DOUBLE DEFLECTION
NEOPRENE VIBRATION
ISOLATOR
BY STRUCTURAL ENGINEER
STRUCTURE OR AS APPROVED
FROM TOP CHORD OF
VERTICAL IN-LINE CABINET
FAN DETAIL
ROOF
SCALE: NONE
AIRFLOW
3'-0" MIN. STRAIGHT
DUCT FULL SIZE OF
FAN CONNECTION
VIBRATION ISOLATOR (TYP.)
5/8" MIN. ALL THREAD ROD(TYP. OF 4 MIN.)
30 MAXIMUM
FLEXIBLE CONNECTION (TYP.)
CABINET FAN
COMBINATION SPRING
DOUBLE DEFLECTION
NEOPRENE VIBRATION
ISOLATOR
BY STRUCTURAL ENGINEER
STRUCTURE OR AS APPROVED
FROM TOP CHORD OF
HORIZONTIAL IN-LINE CABINET
FAN DETAIL
CEILING
ROOF
COOLING COIL PIPING
FLOW METER FITTING
PRE-HEAT COIL PIPING
THERMOMETER
GAUGE
COIL
MANUAL AIR VENT
PIPING SIMILAR
MULTIPLE COIL
DRAIN W/ HOSEAIR FLOW
END AND CAP (TYPICAL)
VALVE
MODULATING
BALANCING VALVE (TYP.)SHUT OFF/COMBINATIONSUPPLY
RETURN
FITTING
FLOW METER
3-WAY
SCALE: NONE
DUCT SIZE SHALL
BE INDICATED ON
PLANS
TRANSITION TO VAV
BOX INLET AS
REQUIRED
DRAIN SHALL BE ONE PIPE SIZE LARGER THAN
4" MIN.
THE SIZE OF THE NIPPLE ON THE DRAIN PAN
DRAIN (1/4" PER 10'-0" MIN.)
NOTE: INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
UNION
CLEAN OUT
CLEAN OUT
PITCHED DOWN TOWARD
ECCENTRIC
INCREASER
DRAIN PAN
4" MIN.
SPILL
CONDENSATE
ONTO SPLASH
BLOCK
CONDENSATE DRAIN PIPING
SCALE: NONE
DETAILA
M-7
BUILDING PAPER
ALL SIDES
7/16 OSBSHEATHING
4" VINYL SIDING
MATCH EXISTING ROOF
IN ALL RESPECTS
GENERAL NOTE:
FLASHING 16 oz COPPER
COORDINATE DUCT FLANGE
LOCATION WITH FLASHING
2x4
MATCH EXISTING ROOF SLOPE
GENERAL NOTE:
8"
ROCKVILLE, MD 20852
TEL: 301-770-0802
FAX: 301-770-0832
11820 PARKLAWN DRIVE
SUITE 316
GATE VALVE (TYP)
DRAIN VALVE
STAINER W/HOSE ENDDRAIN
VALVE (TYP)
P/T PORT (TYP.)
VALVE (ATC)MANUAL AIR VENT
(TYP.)
UNION
(TYP)
HOSE END
COIL
THREE-WAY MODUALTING
HS
HR
COMBINATION BALANCING
AND SHUT-OFF VALVE
NOTE: DETAIL TYPICAL FOR DUCT MOUNTED HEATING COILS SIMILAR.
SCALE: NONE
TERMINAL UNIT HEATING COIL PIPING
23 FEB 2000 CONSTRUCTION DOCUMENTSMJP
SAM
METAL DRIP EDGE
BAKED ENAMEL
ALUMINUM TRIM
PROVIDE WEEP HOLES IN FLASHING
HEAD & JAMB
SILL
OVER DUCT FLANGE (TYP)
9 20
DUCT
ASPHALT SHINGLES, ASTM D3018 TYPE 1, CLASS A
FIRE RESISTANCE, 30 YEAR WARRANTYROOF SHINGLE COLOR TO MATCH EXISTING ROOF
2x4
VINYL SIDING WITH DOUBLE 4" PATTERN
COLOR AS SELECTED BY OWNER
6"
B
M-7
B1
M-7
4"
2x4 TREATED WOOD
7/16 SHEATHING
10 MAY 2000 VALUE ENGINEERING1
1
1
1
DORMER FEATURE DELETED
ATTIC DUCT PENETRATION (TYP)NOT TO SCALE:
DUCTWORK COVERED WITH
FLASHING
SHINGLES
WELDED STEEL CURB
INSULATION AND REINFORCED
WEATHERPROOFING
15 MAR 2001 EMJAY AS-BUILT MOD'S