3M Electrical Markets Division AABBCC91845 29.02.2012Carl-Schurz-Strae 1 Issue: 02D-41453 NeussGermany
Page 2 of 4
Product Features
Superior track- and erosion resistance
Hydrophobic silicone material
One-piece termination
Built-in refractive stress controlling tube
Extended base for bottom sealing Fast and easy installation
Meets European standard specifications
Non flammable
Self Extinguishing
Application temperature range: -50 up to 130C.
Shelf life not limited
Product Selection
12 kV
Application Cross section
(mm)Insulation diameter
(mm)
Installed length
(mm)
Kit name
Indoor 25 120 12.8 21.6 255 92-EU 61-1
Indoor 150 300 20.9 32.3 275 92-EU 62-1
Indoor 400 - 630 30.8 44.8 335 92-EU 63-1
Outdoor 70 240 16.5 27.0 320 93-EU 61-1
Outdoor 150 300 20.9 32.3 325 93-EU 62-1
Outdoor 400 - 630 30.8 44.8 385 93-EU 63-1
24 kV
Application Cross section
(mm)Insulation diameter
(mm)
Installed length
(mm)
Kit name
Indoor 25 150 16.5 27.0 305 93-EU 61-1
Indoor 70 240 20.9 32.3 320 93-EU 62-1
Indoor 300 - 630 30.8 44.8 385 93-EU 63-1
Outdoor 25 150 16.5 27.0 335 94-EU 61-1
Outdoor 70 240 20.9 32.3 355 94-EU 62-1
Outdoor 300 - 630 30.8 44.8 415 94-EU 63-1
-
8/12/2019 Datasheet QT1 Kits AABBCC91845_02
3/4
3M Electrical Markets Division AABBCC91845 29.02.2012Carl-Schurz-Strae 1 Issue: 02D-41453 NeussGermany
Page 3 of 4
36 kV
Application Cross section
(mm)Insulation diameter
(mm)
Installed length
(mm)
Kit name
Indoor 25 70 16.5 27.0 315 94-EU 61-1
Indoor 50 150 20.9 32.3 335 94-EU 62-1
Indoor 185 - 500 30.8 44.8 370 94-EU 63-2
Outdoor 25 70 16.5 27.0 400 94-EU 61-2
Outdoor 50 150 20.9 32.3 415 94-EU 62-2
Outdoor 185 - 500 30.8 44.8 450 94-EU 63-2
Testing
The QT I Kit Series 9x-EU 6x were tested according
HD 629.1 02/2006 S2
Product Identification3M QT I termination kits are marked with supplier name, cable cross section ranges,voltage class and cable type, storage conditions and manufacturing codes for producttraceability.
Type of Test according to HD 629.1 S2 Table 3 & 4 Results
DC Voltage Withstand Test 6 x Uo ; t=15 min Passed
AC Voltage Withstand Test 4,5 x Uo ; t=5 min Passed
Particle Discharge Test 2 x Uo ; PD 10 pC Passed
Impulse Voltage Withstand Test 10 positive and negative impulses Passed
Heat Cycle in air 2.5x Uo 126 cycles Passed
Immersion 10 cycles Passed
Particle Discharge Test 2 x Uo ; PD 10 pC Passed
Thermal short circuit (screen) Passed
Thermal short circuit (conductor) Passed
Dynamic short circuit Passed
Impulse Voltage Withstand Test 10 x 125kV positive and negative impulses Passed
AC Voltage Withstand Test 2,5 x Uo ; t=15 min Passed
Salt Fog or 1000 h
Humidity 300 h Passed
-
8/12/2019 Datasheet QT1 Kits AABBCC91845_02
4/4
3M Electrical Markets Division AABBCC91845 29.02.2012Carl-Schurz-Strae 1 Issue: 02D-41453 NeussGermany
Page 4 of 4
Storage:
The shelf life of the silicone terminations are not limited.Temperature: - 40C to +50C.
Product Stewardship:3M has a fundamental concern for all who make, distribute and use its products, and forthe environment in which we live. This concern is the basis of our philosophy andpolicies by which we assess the health and environmental information on our productsand then take the appropriate steps to protect employee, the public health and theenvironment.
Customer Notice:
3M encourages its customers and potential users of 3M products to review theirapplications for such products from the standpoint of human health and environmental
quality. To help ensure that 3M products are not used in ways for which they were notintended or tested. 3M personnel are available to assist customers in dealing withecological and product safety considerations. Your 3M sales representative can arrangefor the proper contacts.
Regulatory Status:
3M QTI termination kits are not subject of the European WEEE and RoHS Directivesbut meet their requirements.
3M and Cold Shrink are trademarks of 3M Company
Important Notice
All statements, technical information and recommendations related to the Sellers products arebased on information believed to be reliable, but the accuracy or completeness thereof is notguaranteed. Before utilizing the product, the user should determine the suitability of the productfor its intended use. The user assumes all risks and liability whatsoever in connection with suchuse.
Any statements or recommendations of the Seller which are not contained in the Sellers currentpublications shall have no force or effect unless contained in an agreement signed by anauthorized office of the Seller.
The statements contained herein are made in lieu of all warranties, expressed or implied,including but not limited to the implied warranties of merchantability and fitness for a particularpurpose which warranties are hereby expressly disclaimed.
SELLER SHALL NOT BE LIABLE TO THE USER OR ANY OTHER PERSON UNDER ANYLEGAL THEORY; INCLUDING BUT NOT LIMITED TO NEGLIGENCEOR STRICT LIABILITY;FOR ANY INJURY OR FOR ANY DIRECT; INDIRECT; INCIDENTAL OR CONSEQUENTIALDAMAGES SUSTAINED OR INCURRED BY REASON OF THE USE OF ANY OF THESELLERS PRODUCTS.