DATASHEET - FIST-GPS2 - FIST generic splice/patch shelf · intra-facility cable - Splicing loose...

2
FIST is a Fiber Infrastructure System Technology. The Generic Splice/Patch Shelf, FIST-GPS2 is a mechanical shelf assembly for the FIST fiber management system in a rack environment. FIST-GPS2 is typically used in conjunction with FIST splice and patch trays (FIST-GPST-12). The unit has the following functions and features - Patching only, using patchcords, connectorized break-out or intra-facility cable - Splicing loose tube cable, non connectorized intra-facility or break-out cable to pigtails and patching these pigtails to patchcords - Ribbon splicing is possible - Splitters can be integrated - Can be installed in FIST racks and other 19” or metric (ETSI) racks FIST-GPS2 FIST generic splice/patch shelf - Available in 4 different heights (44, 88, 125 and 167 mm) - Kits to attach cables at the side or the back of the shelf are available - Optional jumper overlength storage facility - Full patching capability on the tray and between the trays of one shelf - Wraparound side panel and pigtail guide for easy repatching (only for 125 and 167 mm version). Patching trays are used instead of front patch panels - Patchcords are better managed in a horizontal plane - Full access at both sides of the connection - Reconnection to other positions in the same tray or shelf does not result in uncontrolled overlengths - Various connector adapters possible - Bend controls guide and protect the pigtail cable and ensure controlled cable bending

Transcript of DATASHEET - FIST-GPS2 - FIST generic splice/patch shelf · intra-facility cable - Splicing loose...

Page 1: DATASHEET - FIST-GPS2 - FIST generic splice/patch shelf · intra-facility cable - Splicing loose tube cable, ... FIST generic splice/patch shelf - Available in 4 different ... - Full

FIST is a Fiber Infrastructure System

Technology.

The Generic Splice/Patch Shelf, FIST-GPS2

is a mechanical shelf assembly for the FIST

fiber management system in a rack

environment.

FIST-GPS2 is typically used in conjunction

with FIST splice and patch trays

(FIST-GPST-12).

The unit has the following functions and

features

- Patching only, using patchcords,

connectorized break-out or

intra-facility cable

- Splicing loose tube cable, non

connectorized intra-facility or

break-out cable to pigtails and

patching these pigtails to patchcords

- Ribbon splicing is possible

- Splitters can be integrated

- Can be installed in FIST racks and

other 19” or metric (ETSI) racks

FIST-GPS2FIST generic splice/patch shelf

- Available in 4 different heights

(44, 88, 125 and 167 mm)

- Kits to attach cables at the side or

the back of the shelf are available

- Optional jumper overlength storage

facility

- Full patching capability on the tray

and between the trays of one shelf

- Wraparound side panel and pigtail

guide for easy repatching (only for

125 and 167 mm version).

Patching trays are used instead of front

patch panels

- Patchcords are better managed in a

horizontal plane

- Full access at both sides of the

connection

- Reconnection to other positions in

the same tray or shelf does not

result in uncontrolled overlengths

- Various connector adapters

possible

- Bend controls guide and protect the

pigtail cable and ensure controlled

cable bending

Page 2: DATASHEET - FIST-GPS2 - FIST generic splice/patch shelf · intra-facility cable - Splicing loose tube cable, ... FIST generic splice/patch shelf - Available in 4 different ... - Full

Tyco Electronics Raychem NV

Diestsesteenweg 692

3010 Kessel-Lo, Belgium

Tel 32-16 351 011 (USA)1-919-557-8900

Fax 32-16 351 697 (USA)1-919-557-8498

www.tycoelectronics.com

www.telecomosp.comTC 527/DS/12 06/07

Tyco Electronics, TE logo, FIST, SMOUV and RECORDsplice are trademarks

The information given herein, including drawings, illustrations and schematics which are intended for illustration purposes only, is believed to be reliable. However, Tyco Electronics

makes no warranties as to its accuracy or completeness and disclaims any liability in connection with its use. Tyco Electronics’ obligations shall only be as set forth in Tyco Electronics’

Standard Terms and Conditions of Sale for this product and in no case will Tyco Electronics be liable for any incidental, indirect or consequential damages arising out of the sale,

resale, use or misuse of the product. Users of Tyco Electronics products should make their own evaluation to determine the suitability of each such product for the specific application.

167 mm high 125 mm high 88 mm high 44 mm high

M Metric

L 19” I 19" J 19” K 19”

Dimensions, capacity

The shelf unit is painted (powder coated) in

light grey (RAL 7035).

*Standard Connector

**Small Form Factor Connector

FIST-GPS2- X - X X X - X

Trays only Storage & trays

0 No trays R Storage only

2 2 trays S Storage + 1 tray (K only)

4 4 trays T Storage + 2 trays (M, I, J, L only)

6 6 trays U Storage + 4 trays (M, I, L only)

8 8 trays V Storage + 6 trays (L only)

Consumables, accessories and toolsFor a list of accessories, please refer to the

FIST-GPS2/GPST-12 ordering guide.

Description Dimensions Max. capacity connectors

H W D Without storage basket With storage basket

mm mm mm Std*/SFF** Std/SFF

FIST-GPS2-L 167 481 280 96/192 72/144

FIST-GPS2-M 125 531 280 72/144 48/96

FIST-GPS2-I 125 481 280 72/144 48/96

FIST-GPS2-J 88 481 280 48/96 24/48

FIST-GPS2-K 44 481 280 24/48 12/24

Ordering information

Connector adapter with retainer

N No connectors/pigtails

Chassis type Number of trays and content

BOC: Break-out cable (diameter of individual pigtails

inside the BOC is max. 2.8 mm). IFC: Intra-facility cable

(1) Only for SMOUV-1120-02 (45 mm long heat-

shrinkable splice protector) which is supplied with

the kit.

(2) Contact your local sales engineer for shelves with

pre-fibered pre-connectorized IFC.

(3) Ribbon SMOUV included in the kit.

Min.return loss SC FC E2000 LC DIN ST MU

Single mode standard45 dB (PC) K Q

50 dB (UPC) A C L1 U1

60 dB (APC 8°) B D E9 L2

60 dB (APC 9°) S3

Single mode low loss50 dB (UPC) S6

60 dB (APC 8°) S7 F

60 dB (APC 9°) S8

Single mode consumer grade50 dB (UPC) SC FC LC

60 dB (APC 8°) SD FD LD

Multi mode50/900 µ S5D F5D E5D L5D T5D

62.5/900 µ S5E F5E E5E L5E T5E

Tray options

NN Without trays

Other options contain GPST-12 trays with following configuration:

Pre- Splice holder Patchcords leave shelf side

Cable type fibered holder or Left Right Left Right

micro-fan-out Std. SFF

connectors connectors

Patchcord or pre- No - AA AA AA AA

connectorized BOC

Loose tube cable or non Yes (2) SMOUV12 (1) IA AI MA AM

pre-connectorized IFC ANT JA AJ NA AN

RECORDsplice VA AV WA AW

No SMOUV12 (1) EA AE PA AP

ANT FA AF QA AQ

RECORDsplice BA AB ZA AZ

Pre-connectorized IFC No SMOUV12 (1) EA AE - -

ANT FA AF - -

RECORDsplice BA AB - -

Non pre-connectorized Yes SMOUV12 (1) KA AK - -

BOC ANT LA AL - -

RECORDsplice CA AC - -

No SMOUV12 (1) GA AG - -

ANT HA AH - -

RECORDsplice DA AD - -

R4 Yes micro fan-out R4A AR4 - -

Ribbon pigtail R8 Yes micro fan-out R8A AR8 - -

(patching only) R12 Yes micro fan-out R12A AR12 T12A AT12

R4 Yes SMOUV-R2-12 S4A AS4 - -

Ribbon pigtail R8 Yes (3) & S8A AS8 - -

(splicing & patching) R12 Yes micro fan-out S12A AS12 U12A AU12