Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

24
EFICIENŢA ENERGETICĂ INOVAŢII IN INFRASTRUCTURA CENTRELOR DE DATE Flavius PORUMB AdNet Telecom, CTO [email protected] www.adnettelecom.ro IDG Conference, 31 Mai 2011 Cloud Computing + Virtualization + The New Data Center = less energy bills through GREEN IT

description

Speaking on Datacenter Innovation and best-practices:Flavius PorumbCTO, AdNet Telecom

Transcript of Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

Page 1: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

EFICIENŢA ENERGETICĂINOVAŢII IN INFRASTRUCTURA CENTRELOR DE DATE

Flavius PORUMBAdNet Telecom, CTO

[email protected]

www.adnettelecom.ro

IDG Conference, 31 Mai 2011Cloud Computing + Virtualization + The New Data Center = less energy bills through GREEN IT

Page 2: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.ro

Sumar1. Eficienţa energetică2. Optimizarea distribuţiei de putere3. Optimizări mecanice (răcire)4. Optimizări servere5. Concluzii, best-practices

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Optimizare holistică

Page 3: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.roEficienţă energetică (1)

2%

10%

5%

83%

TerenConstructieProject MgmtEnergie, Răcire

Costuri Constructie

Sursa: J.Hamilton@Amazon

57%

8%

18%

13%4%

Servere

Echipamente telco

Distribuție energie & Răcire

Energie

alte costuri

Costuri Lunare

Amortizare - 3 ani server & 10 ani infrastructura, PUE 1.45

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 4: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.ro

Business best-practice • ECONOMIC: reducere de costuri• SOCIAL: impact mai mic asupa

mediului (amprenta de carbon)

Eficienţă energetică (2)De ce?

Ritmul de inovare este alert datorita jucătorilor globali

1

2

Adoptare best-practices

Mutare DC in Cloud

Nu există decât 2 soluţii

pentru eficientizare

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 5: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.roEficienţă energetică (3)PUE

PUE = (Putere Totală Facilitate)/(Sarcină echipamente IT&C)Power Usage Effectiveness

(vezi si DCIE, http://www.thegreengrid.org/)

DatacenterAlimentare reţea

Putere (transformator, tablou, UPS, baterii, etc)

Răcire (chillere, CR)

Sarcina IT&C

Consum servere, storage, telco eq. etc.

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 6: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.ro

PUE DCiE Nivel Eficiență

3.0 33% Total Ineficient

2.5 40% Ineficient

2.0 50% Mediu

1.5 67% Eficient

1.2 83% Foarte Eficient

PUE = Total Facility Power / IT Equipment PowerDCiE = IT Equipment Power / Total Facility Power

• Nu puteți controla şi îmbunătăți ceea ce nu măsurați!• Primar - Măsurători lunare/săptămânale• Mediu – Măsurători zilnice• Avansat – Măsurători orare (BMS)

Eficienţă energetică (4)

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 7: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.ro

Sumar1. Eficienţa energetică2. Optimizarea distribuţiei de putere3. Optimizări mecanice (răcire)4. Optimizări servere5. Concluzii, best-practices

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 8: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.roDistribuţia Puterii

Pierderi 0.3% 6%2-4%

1%

11% pierderi în distribuție

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 9: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.ro

Optimizarea Distribuţiei Puterii Best Practices

• Evitaţi conversiile • Creşteţi eficienţa conversiilor cu transformatoare si PDU-uri de bune calitate• Tensiunea înaltă cât mai aproape de servere pentru a evita pierderile pe linii• Folosiţi echipamente IT eficiente dpdv consum (Energy Star - economii de 20-30%)• Inovaţii -> OCP; fără UPS central, baterie în rack/server

-> DC în rack• OVERSELL ?

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 10: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.ro

Sumar1. Eficienţa energetică2. Optimizarea distribuţiei de putere3. Optimizări mecanice (răcire)4. Optimizări servere5. Concluzii, best-practices

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 11: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.roOptimizări mecanice (1)Concept

Aerrece

Aercald

(Computer Room Air Handler

/Conditioner)

Mix diluat aer cald-rece

min.1.2m

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

CRAC / CRAH

Page 12: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.roOptimizări mecanice (2)Concept

33% din total consum energie

Cu cel mai mare impact asupra PUE, dupa gradul de utilizare al serverelor

si in multe cazuri ieftin si usor de adresat!

Din nou “Nu puteţi controla şi îmbunătăţi ceea ce nu măsuraţi!”

• Instalatí senzori de temperatura si umiditate• Atentie la contaminarea aerului rece -> container culoar cald/ culoar rece

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 13: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.roOptimizări mecanice (3)Container Culoar Cald (HACS - Hot Aisle Container System)

SFAT: Pentru a evita contaminarea,

folosiţi blanking panel pentru locurile

libere din rack.

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 14: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.roOptimizări mecanice (4)Container Culoar Rece (Cold Air Container System)

SFAT: Consultati preverile legale de stingere a incendiilor cand optati pentru HACS/CACS.

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Mai ineficient vs HACS

Page 15: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.roOptimizări mecanice (5)Free Cooling – “Deschideti Ferestrele!”

Economii de 30-50%

Economizerele (bazate pe AER / FLUIDE) sunt indicate in special in zone cu clima temperata/rece

SFAT: Acordati atentie sistemelor de control, in

special cele legate de filtrare si control al umiditatii

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 16: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.roOptimizări mecanice (6)“Măriţi temperatura din Datacenter!”

ASHRAERecomandări(înainte de 2008)Temperatură20-25 ᵒCUmiditate 40-55%Recomandări(după 2008)Temperatură18-27 ᵒCUmiditate 5.5-15 ᵒC

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 17: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.ro

Sumar1. Eficienţa energetică2. Optimizarea distribuţiei de putere3. Optimizări mecanice (răcire)4. Optimizări servere5. Concluzii, best-practices

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 18: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.roOptimizări servere (1)Virtualizare

Top 5 motive:

1. Consolidare - costuri mai mici pentru HW/SW/mentenanta

2. Scalabilitate, îmbunătăţire time-to-market3. Disponibilitate - migrare facilă4. Agilitate – noi servere uşor de provizionat5. Responsabilitate față de mediu

"Virtualization will continue as the highest-impact issue challenging infrastructure and operations through 2015, changing how you manage, how and what you buy, how you deploy, how you plan and how you charge" - Philip Dawson, Research VP, Gartner

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 19: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.roOptimizari servere (2)Dezvoltări Hardware

06 Aprilie – Cisco UCS C260 M2

26 Sep 2010SeaMicro - SM1000022 Mar 2011- Dell PowerEdge

C5125 (Microservers)

14 Feb 2011 – Dell PowerEdge C6145

5 Mai 2010 -Liquid BladeTilera (arhitectura iMesh™ )

Fabric computing

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 20: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.ro

- Răcire evaporativă- Design propriu (OCP) pentru sistemul de distributie al puterii (surse la 277V) , UPS în rack- Servere de 1.5RU (ventilatoare m.eficiente de 60mm) => 30 servere / rack- Serverele nu au carcasa- Acces la cabluri pe front- Prinderi componente

Optimizari servere (3)Facebook, OCP, Dezvoltări in-house

Studiu de caz – DC Pineville, Oregon

PUE 1.07

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 21: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.ro

Sumar1. Eficienţa energetică2. Optimizarea distribuţiei de putere3. Optimizări mecanice (răcire)4. Optimizări servere5. Concluzii, best-practices

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 22: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.ro

Best PracticesMăsuraţi PUE !

Optimizaţi distribuţia de putere

Îmbunătăţiţi circulaţia aerului.

Free cooling

Ridicaţi temperatura

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 23: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

www.adnettelecom.ro

Audit(măsuraţi PUE,

inventariere echipamente/consum

uri)

Informaţi-vă!Cautati

configuratii eficiente

Revizuiti strategia de

business

Revizuiti posibile puncte de blocaj

(schimbări tehnologice, CAPEX mare, curba de

învăţare a noilor tehnologii(

Puneti la punct un plan

de actiune

ACTIONATI!

Eficientizarea devine o prioritate pentru toata compania. Exemple:• DC Mgr – indicator de performanta bazat pe scaderea PUE• Software Eng. - cod optimizat pentru economie de resurse (scurt, putine accesari HDD, etc)• Bonificati clientii care folosesc echipamente eficiente• Alegere vendori echipamente cu cea mai buna performanta = Procesare/W*TCO

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011

Page 24: Datacenter Innovation - 2011 May31 - IDG Conference - Enterprise Auditorium

MULŢUMESC !

Flavius PORUMBAdNet Telecom, CTO

[email protected]

IDG Conference, 2011 May 31Cloud Computing + Virtualization + The New Data Center = less

energy bills through GREEN IT

www.adnettelecom.ro

INOVAŢII IN INFRASTRUCTURACENTRELOR DE DATE

31 Mai 2011