D5.1-Part 1_List of components impacting the future ETN performance
Transcript of D5.1-Part 1_List of components impacting the future ETN performance
Deliverable D5.1
Modeling requirements for the ETN
Part 1: List of components impacting the future ETN performance
Proprietary Rights Statement
This document contains information, which is proprietary to the "PEGASE" Consortium. Neither this
document nor the information contained herein shall be used, duplicated or communicated by any
means to any third party, in whole or in parts, except with prior written consent of the "PEGASE"
Consortium.
Grant Agreement Number: 211407 implemented as Large-scale Integrating Project
Coordinator: Tractebel Engineering S.A.
Project Website: http://www.fp7-pegase.eu
Date: 11/01/2010 Page: 2
Document Name: D5.1: Modeling requirements for the ETN – Part 1: List of components
impacting the future ETN performance
ID: DEL_WP5 1_D5.1-Part_1-Modeling_requirements_for_the_ETN–
List_of_components_impacting_the_future_ETN_performance_v0
WP: 5
Task: 5.1
Revision: v0
Revision Date: 11/01/2010
Author: FGH
Diffusion list
STB, SSB and Coordinator
Approvals
Name Company Date Visa
Author
Vadims Strelkovs
Vladimir Chuvychin
Antans Sauhats
Dmitrij Lubarskyi
Alexander Rubtsov
Oliver Scheufeld
Fekadu Shewarega
RTU
RTU
RTU
ESP
ESP
FGH
UDE
Task Leader Hendrik Vennegeerts
Oliver Scheufeld FGH
WP Leader István Erlich
Fekadu Shewarega UDE
Documents history
Revision Date Modification Author
01
02
03
04
05
Date: 11/01/2010 Page: 3
Executive Summary
The prevalence of new power electronic converter based devices and systems in their multifaceted
applications are steadily increasing in the European power systems. Additionally, protection and control
systems are becoming more and more complex and their impact and geographic reach is continuously
increasing.
As the first part of the deliverable 5.1 within the context of a multi-layered approach to tackle the issue,
this report provides the list of devices and systems slated for detailed analysis, which can broadly be
categorised into two: primary power equipment and protection and automation devices.
With regard to the former category, the report, by and large, deals with equipment containing voltage
source converters as key ingredients, such as the newer types of HVDC transmission systems, FACTS
devices, and wind farm aggregate models. Newer versions of phase shifting transformers are also
included in the list. The list is augmented by a brief review of the mode of operation and functionality
description of these devices and systems. This is followed by an analysis of the existing models used in
various simulation software packages with regard to their adequacy for steady state, quasi-steady state
and transient simulations.
The modelling of power system protection and automation systems is also in the focus of this deliverable.
This part of the assignment is broader in scope, with the ultimate objective being providing some suitable
models for protection and automation systems to be incorporated into simulation packages. The models
can serve as key ingredient in providing a tool to TSO that would enable the synchronous display of the
state of the ETN close to real time. They can also be used in OPF programs to determine realistic system
operating points, in preventive security assessment, in real-time congestion management or in dispatcher
training. In a broader context, suitable models can also improve on the existing practice in time
simulation of very large systems and open up the possibility of a realistic study of the ETN including
interactions with neighbouring systems.
The present report starts with the categorisation of protection and automation systems. The category
protection system includes the survey of all well-established protective schemes together with the current
difficulty in modelling using widely used simulation platforms. The list of automation systems has been
drawn down to under frequency load shedding, automatic re-closing, automatic synchronizing and over-
voltage/under-voltage limitation automation.
In general, protective relaying models describe a sequence of scenarios depicting connection and
disconnection of units for pre-determined model of the power system reflecting isolation/restoration of
service by means of protection system activation. The validity of the models can only be ascertained only
after a proper validation process. This process generally assumes a set of testing procedures, and
appropriate external signals are needed for testing. The form of the test signal for model validation is
contingent on the degree of simplification acceptable for the model under consideration.
Date: 11/01/2010 Page: 4
Table of content
Executive Summary ............................................................................................................ 3
1. Introduction ................................................................................................................ 6
2. List of new devices, concepts and systems to have an impact on the future ETN performance ............................................................................................. 7
2.1. List of primary power equipment to be considered and the description of their functionality ................. 7
2.1.1. Voltage source converter based HVDC transmission systems ..................................... 8
2.1.1.1. Fundamentals ............................................................................................ 8
2.1.1.2. Voltage source converter based HVDC versus classical HVDC ............... 8
2.1.1.3. Control of voltage source converter based HVDC ..................................... 9
2.1.2. The static synchronous shunt compensator (STATCOM) .......................................... 11
2.1.2.1. STATCOM basics .................................................................................... 11
2.1.2.2. STATCOM control .................................................................................... 11
2.1.3. Static Synchronous Series Compensator (SSSC) ...................................................... 12
2.1.3.1 SSSC basics ............................................................................................ 13
2.1.3.2 SSSC control ............................................................................................ 13
2.1.4. Wind farm aggregate model ........................................................................................ 14
2.1.5. Thyristor controlled series compensator (TCSC) ........................................................ 16
2.1.6. Hexagonal phase shifting transformers ....................................................................... 20
2.1.7. Asynchronized Synchronous Machine (ASM) ............................................................. 21
2.1.8. Magnetically controlled reactor (MCR) ........................................................................ 23
2.1.8.1. Detailed model ......................................................................................... 23
2.1.8.2. Simplified model for dynamic simulation .................................................. 27
2.2. List of relay protection and automation devices and system to be considered and the description of their functionality ............................................................................................................................... 27
2.2.1. Classification of protection and control systems ......................................................... 27
2.2.2. Classification of automation systems 1 ....................................................................... 43
2.2.3. Classification of automation systems 2 ....................................................................... 46
2.2.4. Current state of the technology and level of diffusion ................................................. 48
2.2.4.1. Classification of protection systems ......................................................... 48
2.2.4.2. Special protection schemes ..................................................................... 49
2.2.4.3. Example of a special protection scheme in Baltic interconnection .......... 51
2.2.5. Existing different software describing models of protective relaying and power system automation devices ......................................................................................... 54
2.2.5.1. PSCAD (Relay & Instrument Transformer Library) .................................. 54
2.2.5.2. CAPE (Relay catalog) .............................................................................. 55
2.2.5.3. EUROSTAG ............................................................................................. 55
Date: 11/01/2010 Page: 5
2.2.5.4. MATLAB / SIMULINK ............................................................................... 56
2.2.5.5. Conclusions .............................................................................................. 57
3. Conclusions.............................................................................................................. 58
4. References ............................................................................................................... 59
Date: 11/01/2010 Page: 6
1. Introduction
The objective of this work package within the context of the much broader set of tasks identified by
PEGASE is to set up a general methodology for modelling active system components, including
controllers and protection systems, to build a reliable system for validating models and data and to
specify or develop methods and tools for identifying model parameters. This will form the basis for the
process of standardization of models and achieving a better quality of simulation results.
Limitations on the further expansion of transmission facilities as a result of environmental concerns
means that the need for increased transmission capacity is more and more often achieved through the
implementation of fast acting higher-level protection and control structures that coordinate the operation
of several devices. This represents a shift from passive to active network security management. Such
protection systems and schemes are often difficult to model realistically with existing tools.
An accurate simulation of the behaviour of a power system taking these new developments into
consideration presupposes an accurate modelling of its individual elements. In the discussions leading
up to the launching of this project, the assumption was that many models of power system components
in use today are deemed to be inaccurate or computationally inefficient. When it comes to power system
dynamic modelling, even an agreed standard for control structures that are able to model equipment
behaviour with adequate accuracy are not available. Sometimes - as currently experienced with wind
generation systems - manufacturers are reluctant to divulge details of the control algorithms of their
equipment due to product protections reasons. On top of these permanent concerns, it is far from
obvious how the models of the new power technologies (electronic interfaces, FACTS, digital
controllers and protections, active distribution networks) should be introduced into the full time-scale
model of the power system.
The increasingly tight integration of the European power systems requires that the individual systems
exchange information so that each can assess the influence that the other systems might have on its own.
As long as these power systems consisted only of conventional components, this could be achieved
through an exchange of parameter/data. As the number of complex devices and control systems
increases, mere exchange of data is no longer sufficient because these organizations are likely to use
different simulation tools.
Thus it was found necessary to include the development of common formats for the exchange of power
system data in this work package. The common format would ensure that all TSOs have a common
understanding of how a particular device or control system operates. Thanks to this common
understanding, TSOs would be able to simulate accurately, using their own tools, the effect that their
neighbours’ system will have on the security of their own system.
Date: 11/01/2010 Page: 7
2. List of new devices, concepts and systems to have an impact
on the future ETN performance
2.1. List of primary power equipment to be considered and the description of
their functionality
Table 1 provides an overview of the primary power equipment which has to be considered for this task.
The first column of the table is assigned for the name of the respective device, system or scheme. The
second column contains of short description of the functionality whereas the third and last column
provides information about the issues of the device, system or scheme in terms of modelling.
Device/System/Scheme Description of functionality Issues in modelling
Voltage source conver-
ter based HVDC trans-
mission systems
Connection of two or more
AC terminals through voltage
source converter and DC
links.
Response to electrically close short-
circuits / inter-area power swings is
questionable. Furthermore the reac-
tion to significant frequency devia-
tions (>1 Hz) is not accurate.
Voltage source conver-
ter connecting wind
turbine generators to
the AC grid
AC/DC – DC/AC conversion
by voltage source converter
based on PWM technology.
Response to electrically close short-
circuits / inter-area power swings is
questionable. Furthermore the reac-
tion to significant frequency devia-
tions (>1 Hz) is not accurate.
Doubly-fed induction
generator (DFIG)
Electric machine equipped
with three phase rotor.
Response to electrically close short-
circuits / inter-area power swings is
questionable. Furthermore the reac-
tion to significant frequency devia-
tions (>1 Hz) is not accurate.
Wind farm aggregate
model
Dynamic equivalence repre-
senting wind farms with
respect to grid connection
point.
Response to electrically close short-
circuits / inter-area power swings is
questionable. Furthermore the reac-
tion to significant frequency devia-
tions (>1 Hz) is not accurate.
Interaction with harmonics is usu-
ally not considered.
STATCOM Device for reactive power
generation using converters
based on PWM technology.
Response to electrically close short-
circuits / inter-area power swings is
questionable. Furthermore the reac-
tion to significant frequency devia-
tions (>1 Hz) is not accurate.
Thyristor controlled se-
ries compensator
(TCSC)
Usually applied with long
transmission lines for compen-
sation of series line reactance.
Response to electrically close short-
circuits / inter-area power swings is
questionable. Furthermore the reac-
tion to significant frequency devia-
tions (>1 Hz) is not accurate.
Static Var Compensa-
tor (SVC)
Device for reactive power
generation using converters
based on Thyristor
technology.
Response to electrically close short-
circuits / inter-area power swings is
questionable. Furthermore the reac-
tion to significant frequency
deviations (>1 Hz) is not accurate.
Date: 11/01/2010 Page: 8
Phase shifting
transformers
Device for power flow control Model for short-circuit studies not
fully established, especially for
newer technologies.
Table 1: List of primary power equipment
The following section provides based on the table above some background details, which include:
a closer description of each device’s functionality
the reasons that gave rise to the perceived modeling deficits and where these deficits are
the scope of applicability of the corresponding models (timeframe and phenomena)
2.1.1. Voltage source converter based HVDC transmission systems
2.1.1.1. Fundamentals
HVDC Light is a DC transmission technology consisting of voltage source converter (VSC) stations and
a pair of cables. The DC transmission system comprises of extruded polymer cables both for land
transmission (underground) and across water (submarine cables). HVDC Light is by nature bipolar.
The converters use a set of six valves, two for each phase, which are equipped with high-power
Insulated Gate Bipolar Transistors (IGBT). The valves are controlled by a control system using pulse-
width modulation (PWM). Currently HVDC Light comes in unit sizes ranging from a few tens of MW.
In the upper range, the technology now reaches 1,200 MW and ±320 kV. Figure 1 provides a general
schematic of the circuit diagram of a VSC based HVDC Light
system.
Since IGBTs can be switched on or off as desired, output voltages and currents on the AC side can be
controlled precisely, and the control system thus enables the control of voltage, frequency, and flow of
active and reactive power according to the needs of the network. Additionally, HVDC Light has the
capability to rapidly control active and reactive power independent of one another.
2.1.1.2. Voltage source converter based HVDC versus classical HVDC
The superiority of HVDC Light from the classical HVDC stems from the fact that the outputs of the
VSC are determined solely by the control system and not by the AC network’s ability to keep the
voltage and frequency constant. This gives total flexibility regarding the location of the converters in the
AC system since the requirements on the AC network in terms of short-circuit capacity (SCR) is low
(SCR can even be as low as zero). In other words, HVDC Light can feed power even into a passive
network.
Classic HVDC terminals can provide limited control of reactive power by means of switching of filters
and shunt banks and to some degree through firing angle control.
But the HVDC Light control makes it possible to create any voltage phase angle or amplitude, which
can be accomplished almost instantly. Unlike conventional HVDC converters that normally have a 5%
minimum current, the HVDC Light converter can operate at very low power or even at zero power. As
the active and reactive power are controlled independently, at zero active power the full rating can be
Sending end converter (SEC) Receiving end converter (REC)
Figure 1: Circuit diagram of a VSC based HVDC (HVDC Light)
Date: 11/01/2010 Page: 9
utilized to transmit reactive power. If and when the need arises, the same converter can even be used as
a SVC and it is then called SVC Light.
Active power transfer can be quickly reversed by HVDC Light without any change of control mode, and
without any filter switching or converter blocking. The power reversal is obtained by changing the
direction of the DC current and not by changing the DC voltage as for conventional HVDC. The table
below (Table 1) shows a comparison of the characteristics of a classical HVDC and the HVDC Light.
Function Classical HVDC HVDC Light
Converter valves Thyristor IGBT
Connection
valve - AC grid
Converter transformer Series reactor (+ transformer)
Filtering and reactive
compensation
50% -filters and shunt capacitors Only small filter
DC current smoothing Smoothing reactor + DC filter DC capacitor
Communication between
converter station controls
Needed Not needed
Table 2: Summary of the key differences between classical HVDC and HVDC Light
After the analysis of the differences between classical HVDC and HVDC Light, the subsequent section
deals with the control of HVDC which is based on voltage source converters.
2.1.1.3. Control of voltage source converter based HVDC
The function of the receiving end converter (REC) is to transfer the active power transmitted by the
sending end converter (SEC) to the AC grid by maintaining the DC voltage at the desired level. The
reactive power channel is used to support the grid voltage during faults and also in steady-state. The
control structure for the REC is shown in Figure 2.
Figure 2: Simplified model of the DC and AC voltage control of receiving end VSC
Date: 11/01/2010 Page: 10
The PI-controller maintains DC voltage through active converter current under consideration of a feed-
forward term representing the power transfer through the DC link. AC voltage control is performed by
two controllers. The PI controller in the upper branch is slow and only responsible for set-point tracing
in steady-state operation. The controller in the lower branch is a fast-acting proportional controller with
dead band. It is activated when the voltage error is larger than 0.1 p.u. and it is responsible for grid
voltage support during faults. The magnitude of the current outputs is limited. In steady-state operation
the DC voltage control and by implication the d-component of the REC current has higher priority. In
case of a grid fault the priority is switched to reactive current to provide voltage support. The decoupled
control of active and reactive current is achieved by a feed-forward current control with a very good
dynamic response. This control is based on a vector control approach with its rotating reference frame
aligned to the grid voltage. Due to the voltage orientation of the reference frame, active power can be
controlled through d- and reactive power through q- component of the converter current. The current
control structure makes use of standard PI controllers (Figure 3). The magnitude of the output voltages
is limited by the maximum modulation index and the DC voltage.
Figure 3: Feed-forward Decoupled Current Control
The SEC is responsible for transmitting the active power injected into the sending end of the
transmission system, while maintaining the AC voltage set point. HVDC Light will increasingly play an
important role to transmit power from offshore wind farms to the respective distribution or transmission
grid onshore (high or extra-high voltage). The frequency control capability can be used to control the
slip of the doubly-fed induction machines (DFIM) feeding into SEC. This may be used to reduce the
active power flow through the converter of the DFIM into its rotor circuit (thus the converter rating) still
further without reducing the total power.
As the power control is performed by the wind turbines, a simple voltage magnitude controller for the
SEC will suffice to fulfil the aforementioned requirements. The frequency can be directly regulated
without the need for a closed loop structure. Figure 4 shows the control structure of the SEC.
Figure 4: Simplified model of sending end VSC control
Date: 11/01/2010 Page: 11
Since no current control is used, a current limitation can only be achieved indirectly by blocking the
IGBTs during a severe fault in the (internal) wind farm grid. The voltage control capability of the SEC
can be used to initiate a controlled voltage drop to reduce the wind farm power during fault ride-through
in the high voltage grid.
2.1.2. The static synchronous shunt compensator (STATCOM)
2.1.2.1. STATCOM basics
The STATCOM is a shunt-connected, controlled reactive power source. Its capacitive or inductive
output current can be controlled independently of the AC system voltage, and thus provides voltage
support by generating or absorbing reactive power at the point of common coupling without the need for
external reactors or capacitor banks.
The basic scheme is shown in Figure 5 below.
Figure 5: Basic structure of the STATCOM
The basic components of a STATCOM are an inverter with a capacitor on the DC side, coupling
transformer, and the control system. The equipment action results from the continuous and quick control
of capacitive or inductive reactive power.
2.1.2.2. STATCOM control
The interaction between the AC system voltage at the point of connection determined by the system
load flow configuration and the voltage produced by the inverter enables the control of the STATCOM
var output. When these two voltages are synchronized and have the same amplitude, the active and
reactive power exchange is zero. However, if the amplitude of the STATCOM voltage is smaller than
that of the system voltage, it produces a current lagging behind the voltage by 90 degrees, and the
compensator behaves as an inductive load, whose value depends on the voltage amplitude difference.
Making the STATCOM voltage higher than the AC system voltage will cause the current to lead the
voltage by 90 degrees, thus injects reactive power into the bus connecting the STATCOM to the system.
I
Ut
Ut <Uac
Ut >Uac
Q generation
Q consumption
Filters
Udc
Ut
Voltage source
converter
Network bus
DC capacitor
Uac
Date: 11/01/2010 Page: 12
2.1.3. Static Synchronous Series Compensator (SSSC)
Figure 7 shows the basic structure of a SSSC.
U1 U2
Useries
Uconv
Udc
DC capacitor
The main characteristics and basic functions are described in the following two sections.
Figure 7: Basic scheme of the SSSC
Figure 6: Simplified control scheme for the STATCOM
Date: 11/01/2010 Page: 13
2.1.3.1 SSSC basics
The Static Synchronous Series Compensator (SSSC) is a series FACTS device used to control the power
flow and to improve power oscillation damping on power grids. The SSSC injects a voltage Useries in
series with the transmission line to which it is connected.
As the SSSC does not use any active power source, the injected voltage must stay in quadrature with the
line current. By varying the magnitude Useries = Uq of the injected voltage (which is in quadrature with
the current), the SSSC performs the function of a variable reactance compensator, either capacitive or
inductive.
The variation of an injected voltage is performed by means of a Voltage-Source Converter (VSC)
connected on the secondary side of a coupling transformer. The VSC uses forced-commutated power
electronic devices (GTOs, IGBTs or IGCTs) to synthesize a voltage Uconv from a DC voltage source.
A capacitor connected on the DC side of the VSC acts as a DC voltage source. A small active power is
drawn from the line to keep the capacitor charged and to cover the transformer and VSC losses, so that
the injected voltage Us is practically 90 degrees out of phase with the current I.
2.1.3.2 SSSC control
The control system of a SSSC consists of the following elements:
A phase-locked loop (PLL) which synchronizes on the positive-sequence component of the
current I. The output of the PLL (angle Θ=t) is used to compute the direct-axis and
quadrature-axis components of the AC three-phase voltages and currents (labeled as Ud, Uq or
Id, Iq on the diagram).
Measurement systems measuring the AC positive-sequence of voltages U1 and U2 (U1q and
U2q) as well as the DC voltage UDC.
AC and DC voltage controllers which compute the two components of the converter voltage
(Ud_conv and Uq_conv) are required to obtain the desired DC voltage (UDC-ref) and the injected
voltage (Uq-ref). The Uq voltage regulator is assisted by a feed forward type regulator which
predicts the Uconv voltage from the Id current measurement.
Figure 8: Simplified control structure of the SSSC
Date: 11/01/2010 Page: 14
2.1.4. Wind farm aggregate model
The most commonly used generator type in modern wind turbines is the DFIG. A typical layout of a
DFIG system is shown in Figure 9. The back-to-back frequency converter in combination with pitch
control of the rotor blades enables variable speed operation, leading to higher energy yields compared to
fixed speed wind turbines.
Since the IGBT-converter is located in the rotor circuit, it only has to be rated to a small portion of the
total generator power (typically 20-30%, depending on the desired speed range). A rotor crowbar is used
to protect the rotor side converter against over-currents and the DC capacitors against over-voltages
during grid faults. But a crowbar ignition means the loss of the generator controllability through the
machine side converter (MSC), since the machine rotor is short-circuited through the crowbar resistors
and the MSC is blocked. During this time slot the generator acts as a common induction generator and
consumes reactive power, which is not desirable for low voltage ride-through (LVRT). To avoid a
crowbar ignition for most fault scenarios, a DC chopper is used to limit the DC voltage by short-
circuiting the DC circuit through the chopper resistors. A line inductor and an AC filter are used at the
grid side converter to improve the power quality.
Operating Control
Pitch Control
Gearbox
Measurements
Generator
ASG
3-
Line
Crowbar
MSC PWM LSC PWM
Back-to-Back PWM Converter
Converter Control
L
Chopper
Figure 9: DFIG based wind energy conversion system
The combination of mechanical pitch control and speed control through the electromechanical generator
torque is standard in modern multi-MW wind turbines. The speed control acts to maximize the power
output of the wind turbine across a wide range of wind speeds by adjusting the turbine rotational speed
according to the rotor blade characteristics by adjusting the generator torque. The pitch control tries to
maintain the generator speed constant for operation above nominal wind speed and during wind gusts by
pitching the rotor blades out of the wind, thereby reducing the mechanical stress on the wind turbine and
the drive train at high wind speeds and limits the output power of the WT.
Figure 9 also shows the distribution of the control tasks in a DFIG based wind turbine. The operating
control is responsible for the coordination of pitch and converter control and also assumes some
supervisory control tasks to guarantee safe and automatic operation of the wind turbine.
The commonly used control approach for the speed is based on standard PI controllers and the speed
using a fixed relationship between measured power and reference speed, which is stored in a lookup
table. The control approach is based on power measurement, because wind speed measurement is
inaccurate due to the wind sensor location behind the turbine. The control structure is shown in Figure
10. The upper part shows the speed control, which uses the measured electrical power to determine the
speed set-point with a lookup table. The PI controller adjusts the generator speed by changing the
reference value of the electromagnetic torque. With this value and the measured generator speed the
Date: 11/01/2010 Page: 15
reference electrical power is calculated and passed to the converter control, which controls the active
power to the desired value. The lower part of the control structure describes the pitch control, which is
also based on a PI controller. This controller is only active, if the generator speed exceeds its nominal
value. The controller output is the set-point for the pitch angle, which is adjusted by the pitch actuator
with a certain delay. The pitch actuator can easily be modelled by a PT1 element with rate and output
limitation. The structure shown also includes a wind turbine model based on the cp-curves of the WT
and the basic equation of wind power conversion. The wind speed used in this power conversion model
is filter by a PT1 element to consider the smoothing effect across the area swept by the rotor blades.
Figure 10: Speed and pitch control
Figure 11shows the circuit diagram of the LSC. In a DFIG system the function of the LSC is to maintain
the DC voltage and provide reactive current support for optimization of the reactive power sharing of
MSC and LSC in steady-state. During grid faults additional short-time reactive power can be fed to
support the grid. Especially when the machine rotor is short circuited through the crowbar resistors, the
generator consumes reactive power. This reactive power has to be compensated by the LSC.
Date: 11/01/2010 Page: 16
Figure 11: Line side converter control
The MSC controls active and reactive power of the DFIG and follows a tracking characteristic to adjust
the generator speed for optimal power generation depending on wind speed. Optionally a fast local
voltage controller can be implemented. The cascaded control structure of the MSC is shown in Figure
12. The outer power control loop of the MSC adjusts the rotor current set values of the inner rotor
current loop.
Figure 12: Machine side converter control
The control structures described above adequately reflect the behavior of a single machine. However,
modern wind turbines are rarely used as standalone systems. More significant is the study of the number
of machines operating together as a wind farm. How the currently established control structures need to
be modified for the aggregate model is the focus of the next phase of the study.
2.1.5. Thyristor controlled series compensator (TCSC)
A Thyristor Controlled Series Capacitor (TCSC) is a series-controlled capacitive reactance that can
provide continuous control of power on the AC line over a wide range. From the system viewpoint, the
principle of variable-series compensation is simply to increase the fundamental-frequency voltage
across the fixed capacitor (FC) in a series compensated line through appropriate variation of the firing
angle, . This enhanced voltage changes the effective value of the series-capacitive reactance.
Date: 11/01/2010 Page: 17
The basic module of a TCSC has a series capacitor in parallel with a thyristor-controlled reactor, L as
shown in Figure 13. An actual TCSC system usually comprises a cascaded combination of a number of
these TCSC modules, together with a fixed series capacitor, CF. This fixed series capacitor is provided
primarily to minimise costs. The capacitors C1, C2,...,Cn; in different TCSC modules may have different
values to provide a wider range of reactance control. The inductor in series with the anti-parallel
thyristor is split into two parts to protect the thyristor valves in case of an inductor short circuit. A
practical TCSC module also includes protective equipment normally installed with series capacitor.
A simple understanding of TCSC functioning can be obtained by analyzing the behavior of a variable
inductor connected in parallel with an FC. The equivalent impedance, Ze, of this combination is
expressed as:
CjZe
1
LC
LjLj
21
Uc
IL
Figure 13: Basic TCSC scheme
tcosIi ll ω
For a more detailed insight into the functioning of the TCSC, the differential equations governing the
behaviour of the TCSC can be written as follows:
Basic differential equations:
CL u
dt
diL
βωβ t
LlC itcosÎ
dt
duC ω
0dt
diL L
βπωβ t
tcosIdt
duC l
C ω
Date: 11/01/2010 Page: 18
The solution of the above differential equations:
)tcos()cos(
costcos
I)t(i l
L
ωλ
βλ
βω
λ
λ
12
2
βωβ t
)tsin()tsin(
)cos(
cosLI)t(u Rl
C ωωλβλ
βλ
λ
ωλ
12
0)t(iL
βπωβ t
βλβλ
λ
βλωωλ tan(tan
cos)tsin(LI)t(u RlC
12
Definitions:
: firing angle
: control angle (=180°-)
R: resonant angle (=C.L
R
1ω )
: ratio between resonant and supply frequencies, i.e. π
ω
ω
ωλ
100
RR
Boost factor
The peak value of thyristor current occurs at t=0. Thus,
1
12
2
)cos(
cosIi l
maxLλβ
β
λ
λ
The peak value of the voltage across the capacitor
The ratio of the fundamental frequency component of the thyristor current to the peak value of the line
current is given by the relationship:
βλβλ
λ
βββ
λ
λ
πtantan
cossin
I
i
l
maxL
1
2
21
22
2
2
2
The ratio of the fundamental frequency component of the capacitor current to the peak value of the line
current is given by the relationship:
21
2
1
21
2
2
2
2 βββλβλ
λ
β
λ
λ
π
sintantan
cos
I
iI
I
i
l
maxCl
l
maxC
The capacitor voltage can then be obtained by multiplying the maximum current with
Date: 11/01/2010 Page: 19
0
1XjLj
CjR λλω
ω . Thus,
21
2
1
21
2
2
2
2
0
βββλβλ
λ
β
λ
λ
πλ
sintantan
cosXj
I
iI
I
u
l
maxCl
l
maxC
The ratio between the fundamental frequency component of the capacitor voltage with and without
thyristor action is defined as boost factor. Thus boost factor kB is defined as:
21
2
1
21
2
2
2
2
0
βββλβλ
λ
β
λ
λ
πλ
sintantan
cos
I
iI
XjI
uk
l
maxCl
l
maxCB
0 10 20 30 40 50 60 70 80 90-20
-15
-10
-5
0
5
10
15
20
25
control angle
boost
facto
r
Boost factor as a function of control angle
capacitive mode
inductive mode
Figure 14: Boost factor for lambda = 2.77
Date: 11/01/2010 Page: 20
Xc
Controller
Voltage
Detection
Uc
Xc
Measurement
Power
Oscillation
Damper
IL
Power
Measurement
Figure 15: Control structure for TCSC
2.1.6. Hexagonal phase shifting transformers
Phase shifting transformers (PST) are used to control power flows by inserting a series voltage into the
line. The procedure essentially involves two windings, the series winding and the excitation winding. To
obtain a phase shift between the incoming and outgoing voltages, the excitation voltage must be
supplied by a phase different from the one into which the series winding inducing voltage. Different
regulating transformer technologies employ different methods of creating the shifted voltage. A
common method of deriving the extra voltage is to couple the series winding of a PST with the
quadrature voltage—the phase-to-phase voltage of the two other phases. Such a traditional PST design
works with the excitation winding connected either in delta or wye. This simple approach, however,
results in an asymmetrical transformer design: the magnitudes of the incoming and outgoing voltages
differ depending on the applied regulating angle. This causes changes in the flow of the reactive power,
leading to undesired coupling of the active and reactive power control actions. More sophisticated
designs are used to make the solution symmetrical in order to maintain the same voltage magnitudes at
the load and source sides of a PST. Symmetrical PSTs shift the voltages while keeping their magnitudes
identical 0. Hexagonal PSTs are of a symmetrical design. Six windings are placed on a three-legged
core. These windings are interconnected in such a way that both the series and excitation windings
virtually intersect each other with the effect that no delta or wye winding can be isolated in the structure
of a hexagonal PST as shown in Figure 16.
Date: 11/01/2010 Page: 21
IcIbIa
I’cI’bI’a
V2a V2c
I2b I2bI2a
ΔVa
Va Vb Vc
Figure 16: Winding connection for a single core hexagonal phase shifter
2.1.7. Asynchronized Synchronous Machine (ASM)
ASM (as compared to conventional a synchronous machine) has two field windings shifted for some
angle (often 90º). An additional winding may have a power rating equal or less than main winding. Each
of the field windings is controlled independently. This can be used to improve the transient stability of a
generator especially in reactive power consumption mode. When both windings have the same power
rating, ASM becomes a variant of a DFIG with a two-phase rotor.
An ASM can operate in three general modes, depending on the number of field windings excited:
1. Asynchronized synchronous generator (both windings are controlled by Automatic Voltage
Regulation (AVR))
2. Synchronous generator (only one winding is controlled by AVR)
3. Induction generator (both windings are shorted)
Figure 19 below provides a static power diagram for an ASM with a rated power of 160 MW.
Date: 11/01/2010 Page: 22
Figure 17: Static power diagram for an ASM (rated power 160MW)
The different areas shown in Figure 17 are:
1 Field current limit
2 Stator current limit
3 Induction generator mode curve
4 Minimal excitation limit (overcame in asynchronized mode)
5 Minimal excitation limit (overcame in asynchronized mode)
The differential equations for an asynchronized synchronous machine (in d-q frame) [83] are:
With the following constraints:
Date: 11/01/2010 Page: 23
Where
j – time constant of the machine,
s - slip,
MM – mechanical torque,
– rotor angle,
ufd, ufd – excitation voltages,
ud, uq – machine terminal voltages,
id, iq – machine terminal currents,
ifd, ifq – field winding currents,
i1d, i1q – damper winding currents,
xd, xq, xffd, xffq, x11d, x11q – leakage inductances of machine stator, field windings and damper
windings,
xafd, xa1d, xf1d, xafq, xa1q, xf1q – mutual inductances of machine stator, field windings and damper
windings.
As seen from the equations the main difference of an ASM compared to a synchronous machine is in the
additional equation for the second field winding magnetic flux derivative pfq. Therefore these
equations may be further simplified similar to ordinary synchronous machine equations if required.
AVR generates control signals in frame xy that corresponds to the terminal voltage. Then these signals
are transformed to the machine frame qd.
Simplified AVR equations may be represented as follows (details are not disclosed by manufacturers):
where ut, u0 – terminal voltage and its reference, , 0 - rotor angle and its reference, P, P0 – generator
active power and its reference, s – slip, ku1, ku2, ku3, kd, ks, kp - coefficients, Ue - signal produced by
special block to equalize currents in both windings in steady state.
Ue signal may be calculated with equation
where kfu – coefficient that defines main and additional winding currents ratio in steady state.
2.1.8. Magnetically controlled reactor (MCR)
A MCR is a device for local voltage regulation. The main winding that is connected to the power system
is placed on the core and its saturation is regulated by the current in the control winding. As an effect
the device reactance can be adjusted to keep the voltage at a defined set point.
The advantage of MCR against SVC is that it does not require thyristor valves rated to full power of the
device, but only for the control winding power. Also filters are not required for MCR as well as step-up
transformer.
2.1.8.1. Detailed model
MCR may have various designs and detailed model depending on the particular design used. An
example of a MCR scheme is shown in Figure 18 below [84]:
Date: 11/01/2010 Page: 24
Figure 18: Example of a MCR scheme
Figure 19: Equivalent electrical circuit diagram for the main windings of a MCR
Date: 11/01/2010 Page: 25
Figure 20: Equivalent electrical circuit diagram for the control windings of a MCR
Figure 21: Equivalent magnetic circuit diagram of a MCR
For this MCR design the model may be formulated as a matrix differential equation:
where
Date: 11/01/2010 Page: 26
111111
111
22
22
32310000
32220000
22210000
12110000
21110000
011
010
09
08
07
06
05
04
03
02
01
012
LLWWWW
LLWWWW
LLWWWW
LLWWWW
LLWWWW
LLWWWWWWWWWW
LLWWWWWWWWWW
WWWR
WWR
WWR
WWWR
WWWR
WWR
WWR
WWWR
WWWR
WWR
WWR
WWWR
A
CBMBBMMBBMMM
BAMMMBBMMBBM
MM
B
B
MM
MM
B
B
MM
MM
B
B
MM
32
31
22
21
12
11
1
1
1
11
10
9
8
7
6
5
4
3
2
1
12
i
i
i
i
i
i
i
i
i
x
C
B
A
0
0
)()(
)()(
0
0
0
0
0
0
0
0
0
0
0
0
)(
32323131
32322222
22222121
12121111
21211111
11
11
RiRi
RiRi
RiRi
RiRi
RiRi
RRiRRi
RRiRRi
xc
CmCCBmBB
BmBBAmAA
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
U
U
U
U
U
b
BC
AB
Ri = Ri + Rci,
Ri – linear reluctances,
Rci(Bci) – differential reluctances,
RAm, RBm, RCm – resistances that reflect core losses,
Rij – resistances of control winding branches,
WM, WB, W0 – winding turns,
Date: 11/01/2010 Page: 27
LA, LB, LC – leakage inductances of main windings,
Lij – leakage inductances of control winding branches,
i – magnetic fluxes,
iij – control winding currents,
iA, iB, iC - phase currents,
UAB, UBC – phase-to-phase voltages,
U0 – control winding voltage.
This detailed model allows an accurate simulating of the core saturation processes and therefore
sinusoidal components production.
2.1.8.2. Simplified model for dynamic simulation
In dynamic simulation MCR may be accounted as a variable susceptance. Then the following equation
may be used:
where BR – reactor susceptance, BAVR – reference susceptance as calculated by automatic voltage
regulator, TR – equivalent time constant of the MCR.
A typical value for TR constant is 0.3 s. This model is valid for normal operational conditions and does
not account effects of close short circuit faults, because in case of a voltage drop the MCR is unloaded
instantly because of the decrease of saturation.
2.2. List of relay protection and automation devices and system to be considered
and the description of their functionality
This chapter provides a list of the most common protection systems for main power system units. The
first section of this chapter classifies protection systems for power systems, whereas the second section
describes the current state of technology and level of diffusion regarding protection systems.
The authors divided the description into two parts:
protective relaying and
power system automation
The reason is that they fall into different categories:
a) A protective relay is the device, which gives instruction to disconnect a faulty part of the
system. This action ensures that the remaining system is still fed with power, and protects the
system from further damage due to the fault.
b) Power system automation is the application of automatic devices to the electric transmission
or distribution systems. Automation is primarily used to monitor the state of the system,
operate switching and control devices remotely, and protect the system from disturbances.
2.2.1. Classification of protection and control systems
The list of protection system used for power systems is arranged in table form. This table consists of 6
columns:
Type of the protected object and /or physical quantity monitored. The first column provides information
about the object or apparatus (e.g. transformers etc.) which is protected or the physical quantity (current,
voltage etc.) which is monitored in order to protect the equipment in case the physical quantity exceeds
certain (predefined) limit.
Type of protection. The column contains the type of protection according to (ANSI/IEC)
definitions.
Date: 11/01/2010 Page: 28
Input analog and digital signals. The different input signals (analog or digital) that are required
by the protection system are described here.
Main settings. The typical/most common configuration or settings of the respective protection
system is specified in the fourth column.
Output digital signals. The type of (digital) output signals (e.g. warnings etc.) is named in this
column.
Additional information
TYPE OF
PROTECTED
OBJECT
TYPE OF
PROTECTION
INPUT ANALOG
AND DIGITAL
SIGNALS
MAIN
SETTINGS
OUTPUT
DIGITAL
SIGNALS
ADDITIONAL
INFORMATION
GENERAL
CURRENT
PROTECTIONS
Instantaneous
and definite
time over-
current
protection for
phase currents
ANSI 50/51
(non-
directional)
ANSI 67
(directional)
iA(t), iB(t), iC(t)
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Time delay
settings.
Direction
settings.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
Inverse time
over-current
protection for
phase currents
ANSI 51 (non-
directional)
ANSI 67
(directional)
iA(t), iB(t), iC(t)
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Settings for
IEC, ANSI
or user
defined
curves.
Direction
settings.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
Comments:
Phase over-current protection can be implemented as three-phase or as single-
phase protection.
RMS or instantaneous values of phase currents can be used.
For the phase directional element the fault current of the corresponding phase
and the un-faulted phase-to-phase voltage are used as reference voltage. With
three-phase short-line faults, stored voltage values are used to clearly determine
the direction if the measurement voltages are not sufficient.
Phase over-current protection can contain a number of supplementary functions
(switch on to fault function, harmonic restraint blocking function, dynamic
increase of pick-up values function).
Date: 11/01/2010 Page: 29
Instantaneous
and definite
time over-
current
protection for
residual
currents
ANSI 50N/51N
(non-
directional)
ANSI 67N
(directional)
iA(t), iB(t), iC(t),
3i0(t)
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Time delay
settings.
Direction
settings.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
Inverse time
over-current
protection for
residual
currents
ANSI 51N
(non-
directional)
ANSI 67N
(directional)
iA(t), iB(t), iC(t),
3i0(t)
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Settings for
IEC, ANSI
or user
defined
curves.
Direction
settings.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
Comments:
Residual over-current protection can be implemented as three-phase or as
single-phase protection.
The over-current protection for the ground current can either operate with
measured or calculated quantities of 3I0.
Residual over-current protection can contain a number of supplementary
functions (switch on to fault function, harmonic restraint blocking function,
dynamic increase of pick-up values function).
Instantaneous
and definite
time over-
current
protection for
negative
sequence
currents
(unbalanced
load
protection)
ANSI 46
iA(t), iB(t), iC(t)
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Time delay
settings.
Direction
settings.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
Inverse time
over-current
protection for
negative
sequence
currents
(unbalanced
load
protection)
ANSI 46
iA(t), iB(t), iC(t)
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Settings for
IEC, ANSI
or user
defined
curves.
Direction
settings.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
Date: 11/01/2010 Page: 30
Circuit
Breaker
Failure
Protection
ANSI 50BF
iA(t), iB(t), iC(t),
3i0(t)
Circuit breaker
position
Pick-up
settings.
Time delay
settings.
Tripping
signal
Blocking
signal
Necessary for
network
simulations
The circuit breaker failure function ensures fast back-up tripping of surrounding
breakers. A current check with extremely short reset time is used as check criteria to
achieve a high security against unnecessary operation.
The unit can be single or three-phase started to allow use with single phase tripping
applications. The current criteria can be set to two out of four e.g. two phases or one
phase plus the residual current to achieve a higher security.
The function can be programmed to give single or three phase re-trip of the own
breaker to avoid unnecessary tripping of surrounding breakers at an incorrect starting
due to mistakes during testing.
Pole
Discordance
Protection
ANSI 50PD
Might not be
necessary
Single pole operated circuit breakers can due to electrical or mechanical failures end
up with the different poles in different positions (close-open). This can cause negative
and zero sequence currents, which gives thermal stress on rotating machines and can
cause, unwanted operation of zero sequence current functions.
Normally the own breaker is tripped to correct the positions. If the situation consists
the remote end can be inter-tripped to clear the unsymmetrical load situation.
The pole discordance function operates based on information from auxiliary contacts
of the circuit breaker for the three phases with additional criteria from unsymmetrical
phase current when required.
Thermal
overload
protection
ANSI 49
iA(t), iB(t), iC(t)
Blocking signal
Coolant
temperature
Alarm, trip,
and reset
settings.
Temperatur
e settings.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
Three methods of overload detection can be used (depends on the type of the
protected object):
Overload calculation using a thermal replica according to IEC 60255-8, without
ambient temperature influence.
Overload calculation using a thermal replica according to IEC 60255-8, with
ambient temperature influence.
Calculation of the hot-spot temperature and determination of the ageing rate
according to IEC 60354.
Phase
undercurrent
protection
ANSI 37
Might not be
necessary
Date: 11/01/2010 Page: 31
This protection is used to protect pump un-priming or breaks in load coupling. The un-
priming of a suction pump can be due to the absence of liquid in the pump. Pump un-
priming or a break in a coupling leads to off-load operation of the motor and therefore a
drop in the current absorbed.
Protection
against neutral
earthing
impedance
overloads
ANSI 50N/51N
Might not be
necessary
This protection allows the limiting impedance to be protected against the thermal
effects of an overload. When a phase-to-earth fault occurs on the network, the fault
current is reclosed via the neutral earthing connection. If the fault is resistive, the fault
current may be lower than the earth fault protection thresholds and higher than the
permanent current that the resistor can withstand. A permanent current thus flows
through the limiting impedance and may damage it.
Instantaneous
high-current
switch-on-to-
fault protection
(SOTF)
Might not be
necessary
The instantaneous high-current switch-onto-fault protection function is provided to
disconnect immediately and without delay feeders that are switched onto a high-current
fault. It is primarily used as fast protection in the event of energizing the feeder while the
earth switch is closed, but can also be used every time the feeder is energized - in other
words also following automatic re-closure
GENERAL
VOLTAGE
PROTECTIONS
Over-voltage
protection
ANSI 59
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Time delay
settings.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
Inverse time
over-voltage
protection
ANSI 59
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Settings for
IEC, ANSI
or user
defined
curves.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
Residual over-
voltage
protection
ANSI 59N
uA(t), uB(t), uC(t),
3u0(t)
Blocking signal
Pick-up
settings.
Time delay
settings.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
Date: 11/01/2010 Page: 32
Under-voltage
protection
ANSI 27
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Time delay
settings.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
Inverse time
under-voltage
protection
ANSI 27
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Settings for
IEC, ANSI
or user
defined
curves.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
Remanent
under-voltage
protection
ANSI 27
Might not be
necessary
After the opening of a circuit during an automatic switchover (or a short cut in the
power supplied by the utility), the motors maintain a voltage for the time it takes for the
flux to be extinguished. If the voltage supply is restored while the motors are operating
as generators, this may lead to phase opposition coupling causing transient electrical and
mechanical phenomena that might be damaging for the motor.
The remanent under-voltage protection monitors the voltage of the busbar supplying
the motors and authorizes the power supply to be restored if this voltage is lower than
the threshold.
Over-
excitation
protection
ANSI 24
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Time delay
settings.
Settings for
preset or
user defined
curves.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
Comments:
The overexcitation protection measures the ration voltage/frequency, which is
proportional to the induction ―B‖ in the iron core.
The maximum of the three phase-to-phase voltages is decisive for the
calculation.
Synchrocheck
and voltage
check
ANSI 25
Refers to
automation
devices.
Date: 11/01/2010 Page: 33
The synchronism and voltage check function ensures, when switching a line onto a
busbar, that the stability of the network is not endangered. The voltage of the feeder to
be energized is compared to that of the busbar to check conformances in terms of
magnitude, phase angle and frequency within certain tolerances. Optionally, de-
energization of the feeder can be checked before it is connected to an energized busbar
(or vice versa).
The synchronism check can either be conducted only for automatic re-closure, only
for manual closure (this includes also closing via control command) or in both cases.
Different close permission (release) criteria can also be programmed for automatic and
manual closure.
GENERAL
FREQUENCY
PROTECTIONS
Over/under
frequency
protection
ANSI 81O/U
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Time delay
settings.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
Rate-of-change
of frequency
protection
ANSI 81R
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Time delay
settings.
Tripping
signal
Blocking
signal
Warning
signal
Necessary for
network
simulations
SPECIFIC
TRANSFORMER
AND
AUTOTRANSFORME
R
PROTECTIONS
Differential
protection
(current)
ANSI 87
iA(t), iB(t), iC(t),
3i0(t)
Blocking signal
Pick-up
settings.
Time delay
settings.
Tripping
signal
Blocking
signal
Necessary for
network
simulations
Comments:
Phase currents are taken from all ends of the protected transformer.
The simple current differential protection using time over-current relays is
considered here. It is seldom used in present day applications due to their
susceptibility to false operation from causes such as a) inrush magnetizing
current when energizing the transformer, and b) saturation errors or mismatch
errors of current transformers.
Differential
protection
(percentage)
ANSI 87T
iA(t), iB(t), iC(t),
3i0(t)
Blocking signal
Settings for
tripping
characteristi
c.
Settings for
2nd
and 5th
harmonic
restraint.
Tripping
signal
Blocking
signal
Necessary for
network
simulations
Comments:
Phase currents are taken from all ends of the protected transformer.
The biased (stabilized) differential protection is considered here. It is known
also as percentage differential protection.
Percentage differential protection contains a number of supplementary
functions (adaptation to transformation ratio and vector group, stabilization
against in-rush and over-excitation).
Date: 11/01/2010 Page: 34
Differential
protection
(high
impedance)
ANSI 87
iA(t), iB(t), iC(t),
3i0(t)
Blocking signal
Settings for
tripping
characterist
ic.
Tripping
signal
Blocking
signal
Necessary for
network
simulations
Comments:
Phase currents are taken from all ends of the protected transformer.
The high impedance differential protection is considered here. It can be used
when the involved CT cores have same turn ratio and similar magnetizing
characteristics. It utilizes an external summation of the phases and neutral
current and a series resistor and a voltage dependent resistor externally to the
relay.
Restricted
earth fault
protection
ANSI 87N
iA(t), iB(t), iC(t),
3i0(t)
Blocking signal
Settings for
tripping
characteristi
c.
Tripping
signal
Blocking
signal
Necessary for
network
simulations
The restricted earth fault function can provide higher sensitivity for earth fault
currents than differential protection and it do not need harmonics stabilization.
Restricted earth fault protection is usually configured to measure one neutral current and
one three-phase set of currents.
Tank earth
leakage
protection
ANSI 50/51
Might not be
necessary
This protection is designed to protect a transformer against internal faults
between a winding and the frame.
Protection by
gas, pressure
and
temperature
detection
(DGPT)
Might not be
necessary
The DGPT (detection of gas, pressure and temperature) is a protective device used
for liquid-insulated transformers. It detects anomalies inside the liquid dielectric such as
emission of gas, or a rise in pressure or temperature, and causes the transformer-
switching device (circuit-breaker or switch-fuse) to trip.
Date: 11/01/2010 Page: 35
SPECIFIC
TRANSMISSION
AND
DISTRIBUTION
LINE
PROTECTIONS
Distance
Protection
ANSI 21
iA(t), iB(t), iC(t),
3i0(t)
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Time delay
settings.
Direction
settings.
Settings for
tripping
characterist
ic.
Load
encroachm
ent settings.
Blocking
from power
swings
settings.
Tripping
signal
Blocking
signal
Necessary for
network
simulations
Comments:
Distance protection can contain a number of supplementary functions (power
swing detection, switch on to fault function, load encroachment function).
Tele-
protection
schemes for
distance
protection
Tripping signal
Blocking signal
Releasing
(unblocking)
signal
Type of
tele-
protection
scheme.
Distance
protection
zone for
tele-
protection
scheme.
Pick-up,
waiting,
prolongatio
n, and time
delay
settings.
Tripping
signal
Blocking
signal
Releasing
(unblocking)
signal
Necessary for
network
simulations
In under-reach schemes, the protection is set with a normal grading characteristic. If a
trip command occurs in the first zone, the other line end receives this information via a
transmission channel. There the received signal initiates a trip.
In overreach schemes, the protection works from the start with a fast overreaching
zone. This zone, however, can only cause a trip if the opposite end also detects a fault in
the overreaching zone. A release (unblock) signal or a block signal can be transmitted.
In cases where there is no or only weak in-feed present at one line end, the distance
protection does not pick up there during a short-circuit on the line. Likewise, on lines
where there is only a single sided in-feed or where the star-point is only earthed behind
one line end, the line end without zero sequence current cannot generate a permissive
signal, as fault detection does not take place there. In these cases special measures for
weak and zero in-feed are used.
Date: 11/01/2010 Page: 36
Tele-protection
schemes for
earth fault
protection
Tripping signal
Blocking signal
Releasing
(unblocking)
signal
Type of
tele-
protection
scheme.
Earth fault
protection
zone for
tele-
protection
scheme.
Pick-up,
waiting,
prolongatio
n, and time
delay
settings.
Tripping
signal
Blocking
signal
Releasing
(unblocking)
signal
Necessary for
network
simulations
Directional comparison scheme.
When the earth fault protection recognizes a fault in the forward direction, it
initially sends a permissive signal to the opposite line end. If a permissive
signal is also received from the opposite end, a trip signal is routed to the trip
logic.
Directional unblocking scheme.
The unblocking method is a permissive scheme. It differs from the directional
comparison scheme in that tripping is possible also when no release signal is
received from the opposite line end. It is therefore mainly used for long lines
when the signal must be transmitted across the protected feeder by means of
power line carrier (PLC) and the attenuation of the transmitted signal at the
fault location may be so severe that reception at the other line cannot
necessarily be guaranteed.
Directional blocking scheme.
In the case of the blocking scheme, the transmission channel is used to send a
block signal from one line end to the other. The signal may be sent directly after
fault inception (jump detector above dotted line) and stopped immediately, as
soon as the distance protection detects a fault in the forward direction,
alternatively the signal is only sent when the distance protection detects the
fault in the reverse direction. It is stopped immediately as soon as the earth fault
protection detects an earth fault in forward direction. Tripping is possible with
this scheme even if no signal is received from the opposite line end. It is
therefore mainly used for long lines when the signal must be transmitted across
the protected line by means of power line carrier (PLC) and the attenuation of
the transmitted signal at the fault location may be so severe that reception at the
other line cannot necessarily be guaranteed.
Date: 11/01/2010 Page: 37
Differential
protection
ANSI 87L
iA(t), iB(t), iC(t),
3i0(t)
Blocking signal
Settings for
tripping
characterist
ic.
Settings for
2nd
harmonic
restraint.
Settings for
charging
current
compensati
on.
Tripping
signal
Blocking
signal
Necessary for
network
simulations
Comments:
Phase currents are taken from all ends of the protected object.
For lines with three or more ends or for bus bars, the principle of differential
protection is extended in that the total sum of all currents flowing into the
protected object is zero in healthy operation, whereas in case of a fault the total
sum is equal to the fault current.
The measured quantities should be sent as digital telegrams via communication
channels. For this, each device should be equipped with at least one protection
data interface.
Broken
conductor
detection
Might not be
necessary
The relay can incorporate an element, which measures the ratio of negative to
positive phase sequence current (Ι2/Ι1) to detent broken conductor. This will be affected
to a lesser extent than the measurement of negative sequence current alone, since the
ratio is approximately constant with variations in load current. Hence, a more sensitive
setting may be achieved.
SPECIFIC
GENERATOR
AND
MOTOR
PROTECTIONS
Start-up
overcurrent
protection
ANSI 51
Might not be
necessary
Gas turbines can be started by means of a startup converter. A controlled converter
feeds a current into the generator creating a rotating field of gradually increasing
frequency. This causes the rotor to turn and thus drive the turbine. At approx. 70 % of
rated speed, the turbine is ignited and further accelerated until it attains rated speed. The
startup converter is thereby switched off.
Assuming that a short-circuit can occur in the generator during startup, a short-circuit
protection is necessary over the entire frequency range.
Excessive
start-up time
and locked
rotor
protection
ANSI 51LR
Might not be
necessary
Date: 11/01/2010 Page: 38
Excessive start-up time.
When a machine is switched on, protection is activated if the current of one of
the three phases is higher than the current threshold for a time T. This time T
must be above the maximum value of the normal start-up time.
Rotor locking.
The protection is locked during start-up. In steady-state operating conditions, the
protection is activated when the current of one of the three phases is higher than
the current threshold for a time exceeding the set time delay.
Protection
against too
many
successive
startups
ANSI code 66
Might not be
necessary
Too many successive start-ups may be due to the faulty operation of an automatic
control device, too many manual operations or a series of re-closings when a fault
occurs. The consequences are excessive rise in temperature and a succession of
mechanical shocks on the couplings.
These problems can be avoided using a protection device that counts the number of
start-ups carried out over a determined period of time.
Under-
excitation (loss
of field)
protection
ANSI 40
iA(t), iB(t), iC(t)
uA(t), uB(t), uC(t)
Blocking signal
Under-
excitation
characteri
stic.
Time
delay
settings.
Tripping
signal
Blocking
signal
Warning
signal
The under-excitation protection protects a synchronous machine from asynchronous
operation in the event of faulty excitation or regulation and from local overheating of the
rotor. Furthermore, it avoids endangering network stability by under-excitation of large
synchronous machines.
Protection
against
reversals in
active power
ANSI 32P
iA(t), iB(t), iC(t)
uA(t), uB(t),
uC(t)
Blocking signal
Pick-up
settings.
Time
delay
settings.
Direction
settings.
Tripping
signal
Blocking
signal
Warning
signal
This type of protection allows an inversion of the active power sign to be
detected in the absence of an electrical fault.
Protection
against
reversals in
reactive power
ANSI 32Q
iA(t), iB(t), iC(t)
uA(t), uB(t), uC(t)
Blocking signal
Pick-up
settings.
Time delay
settings.
Direction
settings.
Tripping
signal
Blocking
signal
Warning
signal
Date: 11/01/2010 Page: 39
This protection is used to detect a loss in excitation of the synchronous machines
connected to the network. Upon occurrence of a loss in excitation, the machine
compensates for the drop in magnetizing power by absorbing the reactive power on the
network. The reactive power of the machine is thus negative. The protection detects the
inversion of the sign of the machine’s reactive power.
Jump of
voltage vector
Might not be
necessary
Sometimes consumers with their own generating plant feed power directly into a
network. The incoming feeder is usually the ownership boundary between the network
utility and these consumers/producers. A failure of the input feeder line for example due
to a three-pole automatic re-closure, can result in a deviation of the voltage or frequency
at the feeding generator which is a function of the overall power balance. When the
incoming feeder line is switched on again after the dead time, it may meet with
asynchronous conditions, which cause damage to the generator or the gear train between
generator and drive.
One way to identify an interruption of the incoming feeder is to monitor the phase
angle in the voltage. If the incoming feeder fails, the abrupt current interruption causes a
phase angle jump in the voltage. This jump is detected by means of a delta process. As
soon as a preset threshold is exceeded, an opening command for the generator or bus-tie
coupler circuit breaker is issued.
This means that the vector jump function is mainly used for network decoupling.
90 % stator
earth fault
protection
ANSI 59N,
64G, 67G
Might not be
necessary
The stator earth fault protection detects earth faults in the stator windings of three-
phase machines. The machine can be operated in busbar connection (directly connected
to the network) or in unit connection (via unit transformer). The criterion for the
occurrence of an earth fault is mainly the emergence of a displacement voltage, or
additionally with busbar connection, of an earth current. This principle makes possible a
protected zone of 90 % to 95 % of the stator winding.
Sensitive earth
fault
protection
ANSI 51GN,
64R
Might not be
necessary
The highly sensitive earth fault protection detects earth faults in systems with
isolated or high-impedance earthed starpoint. This stage operates with the magnitude of
the earth current. It is intended for use where the earth current amplitude gives an
indication of the earth fault. As an example of this is with electrical machines in busbar
connection in an isolated power system, where during a machine earth fault of the stator
winding, the entire network capacity supplies the earth fault current, but with a network
earth fault, the earth fault current is negligible due to the low machine capacitance. The
current may be measured using toroidal CTs or CTs in Holmgreen connection.
100 % stator
earth fault
protection
with 3rd
harmonic
ANSI 27/59TN
Might not be
necessary
Date: 11/01/2010 Page: 40
The 3rd harmonic emerges in each machine in a more or less significant way. The
shape of the poles causes it. If an earth fault occurs in the generator stator winding, the
division ratio of the parasitic capacitances changes, since one of the capacitances is
short-circuited by the earth fault. During this procedure, the 3rd harmonic measured in
the starpoint decreases, whereas the 3rd harmonic measured at the generator terminals
increases (see the following figure). The 3rd harmonic forms a zero phase-sequence
system and can thus also be determined by means of the voltage transformer switched in
wye/delta or by calculating the zero phase-sequence system from the phase-earth-
voltages.
100 % stator
earth fault
protection with
20Hz voltage
injection
ANSI 64G
Might not be
necessary
An external low frequency alternating voltage source (20 Hz) injects into the
generator starpoint a voltage of max. 1% of the rated generator voltage. If an earth fault
occurs in the generator starpoint, the 20 Hz voltage drives a current through the fault
resistance. From the driving voltage and the fault current, the protective relay
determines the fault resistance.
Inter-turn
protection
ANSI 59N
Might not be
necessary
The inter-turn fault protection detects faults between turns within a generator winding
(phase). This situation may involve relatively high circulating currents that flow in the
short-circuited turns and damage the winding and the stator. The protective function is
characterized by a high sensitivity.
Given the way the generators are constructed, it is rather unlikely that an inter-turn
fault will occur.
Generators with a separate stator winding (e.g. large-sized hydro-electric generators)
are more likely to be affected. In this configuration, the transverse differential protection
or the zero sequence current protection are used instead between the connected star-
points.
Rotor earth
fault protection
ANSI 64R
Might not be
necessary
Rotor earth fault protection is used to detect earth faults in the excitation circuit of
synchronous machines. An earth fault in the rotor winding does not cause immediate
damage; however, if a second earth fault occurs it constitutes a winding short-circuit of
the excitation circuit. The resulting magnetic imbalances can cause extreme mechanical
forces, which may destroy the machine.
Sensitive rotor
earth fault
protection
with 1 to 3 Hz
square wave
voltage
injection
ANSI 64R
Might not be
necessary
Date: 11/01/2010 Page: 41
The rotor earth fault protection works with a direct voltage of approximately 50V, the
polarity of which is reversed between 1 and 4 times per second, depending on the
setting. This voltage is injected into the rotor circuit. The voltage passes through a
resistor unit and is symmetrically coupled to the excitation circuit via high-resistance
resistors, and at the same time connected to the earthing brush (potential to earth) via a
low-resistance measuring shunt. The voltage taken at the measuring shunt and the
control voltage are fed into the protection device via measuring transducers. The control
voltage is proportional to the injected 50V voltage in terms of amplitude and frequency.
The measurement voltage reflects the earth current flowing in the rotor.
Voltage
restrained
overcurrent
protection
Might not be
necessary
The generator terminal voltage will drop during fault conditions and so a voltage-
measuring element can be used to control the current setting of this element. On
detection of a fault the current setting is reduced by a set factor. This ensures faults are
cleared in spite of the presence of the generator decrement characteristic.
Restart inhibit
for motors
ANSI 66/49
Might not be
necessary
The rotor temperature of a motor generally remains well below its maximum
admissible temperature during normal operation and also under increased load
conditions. However, with startups and resulting high startup currents caused by small
thermal time constants it may suffer more thermal damage than the stator. To avoid
multiple startup attempts causing tripping, a repeated startup of the motor must be
prevented, if it may be assumed that admissible rotor heating would be otherwise be
exceeded.
Inadvertent
energization
ANSI 50/27
Might not be
necessary
The inadvertent energizing protection serves to limit damage by accidental
connection of the stationary or already started, but not yet synchronized generator, by
fast actuation of the mains breaker. A connection to a stationary machine is equivalent
to connection to a low-ohmic resistor. Due to the nominal voltage impressed by the
power system, the generator starts up with a high slip as an asynchronous machine. In
this context, un-permissibly high currents are induced inside the rotor, which may
finally destroy it.
DC
voltage/current
protection
ANSI
59NDC/51ND
C
Might not be
necessary
To detect DC voltages, DC currents and small AC quantities, relay can be equipped
with a measuring transducer input that can be used either for voltages (±10V) or currents
(± 20mA). The DC voltage / DC current protection can be used, for example, for the
monitoring of the excitation voltage of synchronous machines or for the detection of
earth faults in the DC section of the start-up converter of a gas turbine set.
Shaft current
protection
Might not be
necessary
Date: 11/01/2010 Page: 42
Positive
sequence
under-voltage
and phase
rotation
direction
protection
Might not be
necessary
This type of protection is used to protect motors. It performs two protection
functions:
Protects against positive-sequence voltage drops. The positive-sequence voltage
accurately defines the motor torque value. It is therefore more accurate than the
voltage measurement.
Protects against an inversion in phase rotation direction. An inverse phase
rotation direction may be due to a cable connection error. This inversion leads to
the motors operating in the opposite direction, which may be prejudicial to the
mechanical load and, consequently, to the motor.
SPECIFIC
SHUNT REACTOR
AND
SHUNT
CAPACITOR
PROTECTIONS
Neutral to
neutral
unbalance
protection
ANSI 50N/51N
Might not be
necessary
This protection is designed to protect double star-connected capacitor banks.
Harmonic
current
overloading
protection
Might not be
necessary
Where excessive harmonic currents are anticipated, harmonic relaying may be
required for shunt capacitors.
Voltage
differential
protection
method for
grounded wye
banks
Might not be
necessary
Comparing capacitor bank tap voltage with the bus voltage derives a signal
responsive to the loss of individual capacitor elements or units. The capacitor bank tap
voltage is obtained by connecting a voltage-sensing device across the ground end
parallel group (or groups) of capacitors. This may be a midpoint tap, where the voltage is
measured between the midpoint of the phase and ground. Alternatively, the tap voltage
may be measured across low-voltage capacitors (that is, a capacitive shunt) at the neutral
end of the phase.
SPECIFIC
BUSBAR
PROTECTIONS
End Fault
Protection
(dead zone
protection)
Might not be
necessary
The function of the end fault protection is to protect the zone between the current
transformer and the circuit breaker when the circuit breaker is open.
Partial
Differential
Protection
Might not be
necessary
Date: 11/01/2010 Page: 43
This type of bus protection is also referred to as ―bus overload‖ or ―selective backup‖
protection. It is a variation of the differential principle in which currents in one or more
of the circuits are not included in the phasor summation of the currents to the relay. This
method may be used as a backup to a complete differential protection scheme, as
primary protection for a station with loads protected by fuses or to provide local breaker
failure protection for load breakers, or both.
OTHER
USEFUL
ELEMENTS
FOR
NETWORK
SIMULATION
MODELS
Tripping logic
A function block for protection tripping can be provided for circuit breakers
involved in the tripping of the fault. It can provide the pulse prolongation to
ensure a trip pulse of sufficient length, as well as all functionality necessary for
correct co-operation with autoreclosing functions.
The trip function block can include functionality for evolving faults and breaker
lockout.
It can enable single and two-pole tripping for those functions, which do not
have their own phase selection capability.
Fuses
Sequence
(harmonic)
analyzer
RMS
computation
block
ABC to DQ0
transformation
block
REMARKS:
a) Monitoring, measuring and signaling devices (such as fault locators) are not included in the
table as they would not influence the simulation processes.
b) The parameters and features of the protection functions are selected and shown in the table so
that the corresponding models would remain as simple as possible, yet detailed enough to
capture the underlying physical phenomena.
2.2.2. Classification of automation systems 1
Power system automation falls into a different category than protective relaying system do. Power
system automation is the application of automatic devices to the electric transmission or distribution
systems. Automation is primarily used to monitor the state of the system, operate switching and control
devices remotely, and protect the system from negative implications caused by disturbances.
Date: 11/01/2010 Page: 44
TYPE OF
PROTECTED
OBJECT
TYPE OF
PROTECTION
INPUT SIGNALS
NECESSARY
SETTINGS
OUTPUT
SIGNALS
Calculated
signals
Power
system,
island of
power
system
Underfrequency
load shedding uA(t), uB(t), uC(t),
1. Frequency
settings
2. Rate-of-
change of
frequency
settings
(optional)
3. Number of
load
shedding
steps
4. Maximum
anticipated
overload
5. Size of the
load shed at
each step
6. Time delay
Tripping
signal
Power
system
frequency f,
Rate-of-
change of
frequency
df/dt,
frequency
deviation
from rated
value Δf
Comments:
In large systems the load shedding devices should be spread throughout the system.
The reclosing of feeders that have been tripped for load shedding is left to system
operator. Frequency relays can be used to restore loads automatically
Normally input signal is one line-to-line voltage
Transmission
line
Automatic
reclosing
Protection tripping
signal,
Circuit breaker's
disconnection
signal,
Circuit breaker's
closing signal,
Blocking signals,
Transmission line's
voltages (optional)
1. Dead time
setting
2. Reset time
setting
3. Single or
multiple-shot
reclosing?
4. Operating
time of
circuit
breaker
5. Number of
reclose
attempts
Tripping
signal
Dead time
and reset
time settings
Comments:
Time settings are defined in IEEE Std. C37.100 – 1992
Synchronism check relays should be used on highly interconnected transmission
On single-tie circuit with dispersed generation, reclosing on the circuit must be
delayed long enough for the dispersed generation to be isolated from the utility
The protection on transmission lines that have tapped transformers without breakers
should be blocked from reclosing for faults within the transformer
For lines with capacitors voltage supervision may be required
Date: 11/01/2010 Page: 45
Transmission
line,
Generators
Out-of-step
protection
uA(t), uB(t), uC(t),
iA(t), iB(t), iC(t),
Rate-of-change
of impedance,
Double blinder
characteristics,
Tripping time
delay,
Negative
sequence of
current,
Direction of
power flow,
Voltage phases
differences
setting
Tripping
signal,
Blocking
signal
Positive-
sequence
impedance,
Rate-of-
change of
impedance,
Negative
sequence of
current,
Direction of
power flow,
Voltages
phases
differences
Comments:
Two methods can be used for out-of-step protection: impedance associated and phase
associated
Reclosing of
generator
and power
system,
Reclosing of
two power
systems
Automatic
synchronizing
Phase voltages at
synchronized ends
Δf,
Difference in
voltages,
Phase angle that
the breaker
contacts close
Reclosing
signal
Phase
voltages on
synchronized
ends,
Difference in
phase
voltages,
Frequencies
on
synchronized
ends f1 and f2,
Δf=f1- f2,
Difference in
phase angles
of voltages
on
synchronized
ends
Comments: Synchronizer compares the voltages on two sides of an open breaker
Generators
Turbine speed
governor
uA(t), uB(t), uC(t),
iA(t), iB(t), iC(t),
Speed droop,
Pref,
Governor's time
constants,
Limiters values
Control
signal
Generator's
output
power,
Frequency
Comments: standard models of specific governor systems should be used
Generators
Overfrequency
protection uA(t), uB(t), uC(t),
Frequency
setting,
Tripping time
delay
Tripping
signal
Generator's
frequency
Comments: overfrequency protection disconnects excessive generation
Date: 11/01/2010 Page: 46
2.2.3. Classification of automation systems 2
This chapter presents list of automation systems which are specific for applications used in UPS
countries.
TYPE OF
PROTECTED
OBJECT
TYPE OF
PROTECTION
INPUT SIGNALS
NECESSARY
SETTINGS
OUTPUT
SIGNALS
GENERAL
Overvoltage
limitation
automation
uA(t),uB(t),uC(t),3u0(t),
iA1(t),iB1(t),iC1(t),3i01(t)
iA2(t),iB2(t),iC2(t),3i02(t)
Signal of remote
switching on of reactors
Signal of remote
disconnection of reactors
Signal of remote
disconnection of line
Detection of
disconnection of phases
A, B and/or C of
transmission line
Voltage settings,
Current settings,
Reactive power setting,
Active power setting,
Active power's braking
coefficient,
Control time delay,
Reactor's connection
time delay,
Time delay of
transmission line
disconnection,
Breaking failure
automation time delay
Control signal,
Reactor switching
on,
Disconnection of
transmission line,
Remote switching
on of reactor at
the other side
transmission,
Remote
disconnection of
the end of
transmission line,
Signal of breaking
failure automation
Device for
detection of
transmission
line
disconnection
Position of line isolator,
State of phases A, B and
C of the circuit breaker 1,
State of phases A, B and
C of the circuit breaker 2,
Disconnection of line by
personnel
Single-phase
disconnection by
protective relaying,
Three-phase
disconnection by
protective relaying,
Three-phase
disconnection by
protective relaying
with blocking of
reclosing,
State of the 2 circuit
breaker
Autoreclosing
connection time delay
Disconnection
before auto
reclosing
operation,
Disconnection
after
autoreclosing
operation,
Connection of
line,
Disconnection for
maintenance
procedure
Date: 11/01/2010 Page: 47
TYPE OF
PROTECTED
OBJECT
TYPE OF
PROTECTION
INPUT SIGNALS
NECESSARY
SETTINGS
OUTPUT
SIGNALS
Overcurrent
detection
device
iA(t),iB(t),iC(t),
External blocking,
Temperature of
environment
Stage 1...n
Set of three time delay
settings for each stage:
Stage1:
Signal1, signal2,
signal 3
.
.
Stage n:
Signal1, signal2,
signal3
Undervoltage
limitation
automation
uA(t),uB(t),uC(t),
iA1(t),iA2(t),...iAN(t),
External start signal
Blocking signal
Umin setting
Time delay
Umax setting
Logic of feeders'
disconnection order
Tripping signal,
Closing signal,
Blocking of
reclosing
Same set for each
feeder
Device for
monitoring of
preceding
condition
uA(t),uB(t),uC(t),3 u0(t)
iA(t),iB(t),iC(t), 3i0(t)
Few active power
settings – n stages Stage 1 ... stage n
Overload
detection
device
uA(t),uB(t),uC(t),3 u0(t)
iA(t),iB(t),iC(t), 3i0(t)
Few active power
settings – n stages
Time delay settings
Stage 1 ... stage n
Date: 11/01/2010 Page: 48
2.2.4. Current state of the technology and level of diffusion
2.2.4.1. Classification of protection systems
Relays are compact networks that are connected throughout the power system to detect intolerable or
unwanted conditions within an assigned area. In theory relay system should be able to respond to the
infinity of abnormalities that can possible occur within the power system.
The Institute of Electrical and Electronic Engineers (IEEE) defines a relay as "an electric device that is
designed to respond to input conditions in prescribed manner and, after specified conditions are met, to
cause contact operation or similar abrupt change in associated electric control circuits".
The existing protective systems can be classified by design as:
a) Electromagnetic type relays.
b) Analog type solid-state relay.
c) Microprocessor based protective system.
The electromagnetic types of relays are still in service in the power systems and few manufacturing
companies produce electromagnetic relays at present.
Analog solid-state relays are devices of generation preceding microprocessor era. Some relays are in
service in the power systems but manufacturing process practically stopped.
Microprocessor-based protection systems are the new generation of protection and control equipment.
There are some advantages as well as disadvantages of microprocessor-based devices.
Advantages of Microprocessor-based protective systems:
1) Many microprocessor-based protective systems allow to record and then reply modes
preceding of functioning during breakdown, for analysis of emergency situation.
2) Microprocessor-based protective systems allow changing pick-up settings with the help of a
computer and turning from one characteristic to the other using only software tools.
3) Microprocessor-based protective systems allow the provision of all information regarding
their state to remote operational centers through special communication channels.
4) Microprocessor-based protective systems are less prone to dust, increased humidity,
aggressive gas than electromechanical relays.
5) A small microprocessor-based protective system can replace a whole set of standard
electromechanical relays.
6) Higher reliability of static microprocessor-based protective systems in comparison with
electromagnetic relays containing elements moving mechanically.
Disadvantages of Microprocessor-based protective systems:
1) Impact of electromagnetic disturbances from the power supply network to the operation of
the system.
2) There are essential differences in operation of electromechanical and microprocessor-based
relays caused by their different susceptibility to harmonics, saturation and other wave
distortion.
Date: 11/01/2010 Page: 49
3) Considerable complication of exploitation.
4) Information redundancy.
With electronic relays, the protection principles and fundamentals are essentially unchanged as are the
issues regarding protection reliability. Though regarding the modeling issue all types of relays should be
considered separately.
Basic components of a digital relay are:
a) A signal conditioning subsystem.
b) A conversion subsystem.
c) A digital processing relay subsystem.
Typical logic units that may be involved in a microprocessor-based protective system are shown in
Figure 22.
Figure 22: Basic components of a microprocessor-based system
2.2.4.2. Special protection schemes
Date: 11/01/2010 Page: 50
According to [80], special protection schemes are defined as: ―a protection scheme that is designed to
detect a particular system condition that is known to cause unusual stress to the power system and to
take some type of predetermined action to counteract the observed condition in a controlled manner. In
some cases, SPSs are designed to detect a system condition that is known to cause instability, overload,
or voltage collapse. The action prescribed may require the opening of one or more lines, tripping of
generators, ramping of HVDC power transfers, intentional shedding of load, or other measures that will
alleviate the problem of concern. Common types of line or apparatus protection are not included in the
scope of interest here [32].
According to [31], there are five states of operating conditions – Normal, Alert, Emergency, In Extremis
and Restorative. In case of highly reliable SPS with a good performance, a normal power system
operation could be shifted from the Normal state to Alert state (Figure 23). This confidence in SPS
would allow much better utilization of existing assets (transmission lines etc.).
Figure 23: Power system operating states (arrows express possible transitions among them)
In 1992, CIGRE and IEEE performed a survey about the installed SPSs among the utilities. The detailed
statistical results of the answers reporting 111 installed SPSs can be found in [80]. Very important and
interesting observations and information can be extracted from it, although they are not explicitly stated
there [32]:
The trend is quite obvious; the most SPSs have been commissioned in the nineties. The
degree of complexity is rapidly increasing and the solutions are more and more
sophisticated.
All installed SPSs are dedicated solutions for particular power systems. There is no scheme
that could be applied to another power system with minimal modifications.
All installed SPSs are either fully or in major part designed and installed by utilities. There is
no company that would offer a SPS to utilities as a complete solution ranging from data
acquisition to execution of control actions, except ABB. Only some parts of existing SPSs
have been supplied to utilities from an external environment, e.g. algorithm, software
package etc.
SPS should be armed (i.e. ready for operation) all the time, not only in the periods when the
power system is heavily stressed.
―…the cost of the false trips is generally much lower than the cost of failure of the SPS to
operate when required…‖ This implies, that even with the risk of malfunction, SPS
installation is economically beneficial / profitable.
Regardless of the third last bullet, some utilities look for assistance from the vendors’ side of two kinds:
Date: 11/01/2010 Page: 51
1) A complete ―turn-key‖ solution – they don’t specify the way in which the problems should
be resolved but only provide a description of the problems and critical scenarios.
2) Delivery of a part of the solution – they have their own ideas, algorithms or studies but they
need a help to set up the system / platform, build an infrastructure etc.
The four main design criteria, which should be used for SPS, are:
1) Dependability – The certainty that the SPS operates when required, that is, in all cases where
emergency controls are required to avoid a collapse.
2) Security – The certainty that the SPS will not operate when not required, does not apply
emergency controls unless they are necessary to avoid a collapse.
3) Selectivity – The ability to select the correct and minimum amount action to perform the
intended function, that is, to avoid using disruptive controls such as load shedding if they are
not necessary to avoid a collapse.
4) Robustness – The ability of the SPS to provide dependability, security and selectivity over
the full range of dynamic and steady state operating conditions that it will encounter.
Other very important relevant questions have been raised in [81]:
1) Reliability of SPS (the author means basically the availability of the system, i.e. inability of
the system to operate due to the failure of one or more of its components should be minimal,
similar to Dependability as defined by CIGRE).
2) Impact on daily operation of a grid (i.e. acceptance by the operators and required effort for
the training of the operators).
3) Documentation of SPS.
Conclusion:
Due to all installed SPSs are dedicated solutions for particular power systems and there is no scheme
that could be applied to another power system with minimal modifications. SPS systems are not
classifiable. So this report will not present modeling problems for SPS. Below is example of specific
SPS solution for the Baltic power system.
The Classification of SPS and further analysis is planned for the future report WP5.3. There is a need in
developing common methodology for the assessment of power system security during operation of SPS
systems. One of the approaches can by the application of Hybrid Dynamic Systems.
The example of the specific SPS solution for the Baltic power system is presented below.
2.2.4.3. Example of a special protection scheme in Baltic interconnection
High voltage power lines of 330 kV form the basic network of the Baltic interconnection. There are 58
high-voltage transmission lines of total length 4136.9 km and 32 substations equipped with 54
autotransformers of the 347/242kV and 330/115 kV voltages with the total capacity of 8665.0 MVA.
Regional transmission network of the Baltic interconnection consists primarily of 110 kV lines, with the
only exception of Estonian power system, where in addition, 220 kV voltage is used.
Date: 11/01/2010 Page: 52
Figure 24: The interconnection of the Baltic region
The simplified structure of the anti-emergency automation system, which is used in the Baltic
interconnection, is shown in Figure 24. The main part of this system is the so-called ―adaptive matrix‖
(4th block in Figure 25). It analyzes the information of region’s state (i.e. number of operating hydro
units, number of hydro units in the pumping or compensation state, power flow between Latvia and
Estonia etc.) and distributes the appropriate control action.
The algorithm of the described anti-emergency automation system was carefully simulated using
Mustang software developed by the Latvian TSO department. Investigations of the described SPS
system will be executed during the fulfillment of task 3 of WP5.
An adaptive matrix operates in the united power system as well as in islanded mode.
Date: 11/01/2010 Page: 53
Figure 25: Simplified structure of the system of anti-emergency in the Baltic interconnection
1) Anti-emergency system of Ignalinos NPP (see also Figure 24).
2) Anti-emergency system of Smolensk NPP.
3) Anti-emergency system of 750kV substation Belorusskaja.
4) Adaptive matrix, which distributes the amount of necessary control action among hydro
power plants. It can disconnect the load as well.
5) Block, which determines the necessity of the disconnection of load.
Blocks 4 and 5 are two similar blocks located in Plavinas HPP and Ignalinos NPP with
similar settings. Each block controls different power stations. Signals to Kruonio PSHPP
duplicate control to increase operation reliability.
6) Adaptive disconnection of load in Belorussia.
7) Adaptive disconnection of load in Latvia and Lithuania.
8) Disconnection of pumps in Kruonio PSHPP.
9) Start-up of all hydro units in Kruonio PSHPP.
10) Start-up of one hydro unit in Kruonio PSHPP.
11) Number of pumps in Kruonio PSHPP before the contingency.
12) Start-up of hydro units in Pļaviņu HPP: I - 100 %; II - 50 % amount.
13) Start-up of hydro units in Ķeguma HPP: I - 100 %; II - 50 % amount.
14) Start-up of hydro units in Rīgas HPP: I - 100 %; II - 50 % amount.
15) Control of active power flow between Latvia and Estonia before contingency.
Date: 11/01/2010 Page: 54
The main factors for operation of the special protection scheme are:
1) Under-frequency situation in the power system (f<49.4 Hz, t=1 sec).
2) Loss of one or two blocks at the Ignalinos NPP (750 MW or 1300 MW).
3) Loss of specific intersystem transmission lines.
Here we will consider the behavior of emergency automation only during the disturbances associated
with under-frequency situations.
An excerpt from the adaptive matrix of the Pļaviņu HPP is shown in Figure 26. In case of frequency
decline below 49.4 Hz, the control action depends on the situation in Kruonio pumped storage power
plant and on the situation in Pļaviņu HPP.
Figure 26: Excerpt from the adaptive matrix of the Latvian Pļaviņu HPP
The main shortcoming of the considered approach is linked with the pre-determined control actions of
the adaptive matrix. These control actions and settings are chosen in advance according to some
previously calculated possible emergency situations. However, it is not possible to foresee all the
possible power system failures and cascading events. Therefore the considered approach is most
effective when the emergency situation corresponds or is close to the foreseen one. In other cases it can
produce wrong control actions.
2.2.5. Existing different software describing models of protective relaying and power
system automation devices
2.2.5.1. PSCAD (Relay & Instrument Transformer Library)
PSCAD software contents few very simple models of protective relaying and power system automation.
For example, differential protection model provides verification if operational point is situated in
tripping zone? Other necessary models are possible to create using logical and mathematical basic
elements. It is also possible to create new models using Fortran software.
Date: 11/01/2010 Page: 55
Figure 27: Example of a PSCAD library
2.2.5.2. CAPE (Relay catalog)
Authors of CAPE software periodically update relay's data. Relay's models are created with high
resolution. Unfortunately it is not possible to transfer models to another software environment. Besides
CAPE software can simulate only steady state conditions.
Figure 28: Screenshot from the CAPE software
2.2.5.3. EUROSTAG
EUROSTAG software gives excess to different protection and automation devices. The list of devices is
limited. It is not possible to transfer models to another software environment. Mathematical descriptions
are internal type only. It is possible to create model using EUROSTAG blocks with transfer functions.
For users applying the EUROSTAG software, the included concept of macro-automation probably will
be convenient and sufficient for the analysis of the model.
Date: 11/01/2010 Page: 56
Figure 29: User interface of EUROSTAG
2.2.5.4. MATLAB / SIMULINK
MATLAB software with SIMULINK does not have a library of protective relaying and automation
elements. The advantage of the software is the availability of a wide range of basic elements to create
the required models. Below is one example of a model (Figure 30).
A package developed at Texas A&M University using MATLAB and SIMULINK provides such
capabilities through five standard component libraries. For example, Relay Element library contains:
Data Acquisition Board, Digital Filter, Digital Fourier Transform, Basic Measurement, Differential
Equation-Based Impedance Measurement, Universal Comparator, Zone Comparator, Triggering
Element, Symmetrical Components and Bias Characteristic. Using elements from Relay Library, one
can quickly model a given relay. Developed models can be made part of existing or new libraries.
Figure 30: Example of a model in MATLAB/SIMULINK
Date: 11/01/2010 Page: 57
2.2.5.5. Conclusions
a) Traditional electric power system's elements (transformers, transmission lines, generators and
so on), protective relaying and automation devices can be represented as models. Description
of their operational principles and mathematical models can be found in textbooks and
surveys of relays. Some specific operational algorithms companies use to provide speed of
relay response (for example distance protection should locate appearance of fault, type of
fault with high speed and accuracy) is not known. Using standard algorithms is not possible
to receive high accuracy. Unfortunately, companies usually do not describe all details of their
of their protection devices such as a full specification and description of control units.
In stable networks, as found e.g. in Europe, extremely short tripping times are not required. A total fault
clearance time (protection plus circuit-breaker) of approximately 5 cycles (100 ms in 50 Hz systems) is
generally sufficient.
The German utility board (VDEW) states the following requirement for the protection tripping time
during the critical three-phase close-in fault:
EHV-system 25 ms
HV-system 30 ms
MV-system 40 ms
Table 1: Example for protection tripping time (German Utility Board (VDEW))
b) In spite of the use of protective relaying devices in different software environments new
models should be developed for PEGASE project. In contrast to turbine governors, excitation
systems and synchronous generators for protective relaying and automation devices there are
no mathematical description or standard block diagrams in standards.
In case existing protective relaying model is planned to be used from any model library there should be
need in modification of the model.
Date: 11/01/2010 Page: 58
3. Conclusions
This report represents the first part of deliverable D5.1 in the framework of the PEGASE project. It
provides an overview of the components which are considered to have an impact on the future ETN
performance.
The focus lies on primary power equipment which consists of electronic components and features a non-
linear behavior in general. Furthermore, protective relaying and automation systems are considered to
have an impact on the future ETN performance due to the fact that the system as such is operated closer
to its limits and future tasks will require e.g. special protection schemes.
The report starts-off with listing new concepts, devices and systems slated for detailed analysis,
description of their functionality and some initial thoughts spelling out performance and quality
requirements expected of the models. Based on the preliminary analysis of existing models with regard
to their adequacy for the different simulation purposes, possible modelling gaps have been suggested.
This is followed by a survey of the current approach in modelling protective relaying and automation
systems. Presently each producer of protective and automation systems proposes its own model tied to a
particular application, significantly reducing or precluding the portability of the models for use on other
platforms. The analysis of the current modelling practice and the fidelity of the models to reproduce the
physical reality will be the subject of further work in this Work Package.
Date: 11/01/2010 Page: 59
4. References
1 Bogdan Kasztenny and Eugeniusz Rosolowski: Modeling and Protection of Hexagonal Phase-
Shifting Transformers Part I: Short-Circuit Model, IEEE TRANSACTIONS ON POWER
DELIVERY, VOL. 23, NO. 3, JULY 2008
2 Michael P. Bahrmann and Brian K. Johnson: The ABC of HVDC Transmission technologies:
An overview of HVDC sytems and applications, IEEE Power & Energy Magazine March/April
2007 Vol. 5 No. 2
3 Stanley H. Horowitz, Arun G. Phadke, “Power System Relaying,” 3rd edition, John Wiley &
Sons Ltd., 2008, ISBN: 978-0-470-05712-4.
4 Q. H. Wu, Z. Lu, T. Y. Ji, “Protective Relaying of Power Systems Using Mathematical
Morphology,” Springer, 2009, ISBN 978-1-84882-498-0
5 Network Protection and Automation Guide, Alstom, 2002, ISBN 2-9518589-0-6
6 Bertil Lundqvist, “100 Years of Relay Protection, the Swedish ABB Relay History”
7 SIPROTEC Multi-Functional Protective Relay with Local Control 7SJ62/64 v4.7, Manual,
Siemens.
8 Pedro Nunes, Atef Morched, M. Teresa Correia de Barros, “Analysis of Generator Tripping
Incidents on Energizing nearby Transformers,” International Conference on Power Systems
Transients – IPST 2003 in New Orleans, USA.
9 Ziegler G.: Numerical Distance Protection, 2nd Edition, Publicis Corporate Publishing, 2006,
ISBN 3-89578-266-1.
10 Elmore W. A.: Protective Relaying Theory and Applications, 2nd Edition, Marcel Dekker Inc.,
2003, ISBN 0-82470-972-1
11 Héctor J. Altuve, Michael J. Thompson, Joe Mooney, “Advances in Breaker-Failure
Protection,” Schweitzer Engineering Laboratories, Inc., 2006.
12 S. Casoria, Patrice Brunelle, Gilbert Sybille, “Hysteresis Modeling in Matlab Power System
Blockset.”
13 SIPROTEC Distance Protection 7SA6 V4.61, Manual, Siemens.
14 Li-Cheng Wu, Chih-Wen Liu, Ching-Shan Chen, “Modeling and Testing of a Digital Distance
Relay Using MATLAB and SIMULINK.”
15 IEC 60255-24 Electrical Relays – Common Format for Transient Data Exchange
(COMTRADE) for Power Systems, 2001.
16 SIPROTEC Differential Protection 7UT613/63x V4.60, Manual, Siemens.
17 Leonard L. Grigsby, Power System Stability and Control, CRC Press, 2006.
18 Anderson, P. M., LeReverend, B. K., “Industry experience with special protection schemes,”
IEEE/CIGRE Committee Report, IEEE Transactions on Power Systems, PWRS, 11, 1166–
1179, August 1996.
Date: 11/01/2010 Page: 60
19 James D. McCalley, Weihui Fu, “Reliability of special protection schemes,” IEEE
Transactions on Power Systems, Vol. 14, No. 4, November 1999.
20 Fabio Saccomanno, “Electric Power Systems, Analysis and Control,” IEEE Press, 2003, ISBN
0-471-23439-7
21 P.M.Anderson, B.K.Lereverend: Industry Experience with Special Protection Schemes, IEEE
Transactions on Power Systems, Vol. 11, No. 3, August 1996.
22 E.K.Nielsen, M.E.Coultes, D.L.Gold, J.R.Taylor, P.J.Traynor: An Operations View of Special
Protection Systems, IEEE Transactions on Power Systems, Vol. 3, No. 3, August 1988.
23 Ziegler G.: Numerical Differential Protection, Publicis Corporate Publishing, 2005, ISBN 3-
89578-234-3.
24 Ziegler G.: Numerical Distance Protection, 2nd Edition, Publicis Corporate Publishing, 2006,
ISBN 3-89578-266-1.
25 Elmore W. A.: Protective Relaying Theory and Applications, 2nd Edition, Marcel Dekker Inc.,
2003, ISBN 0-82470-972-1.
26 Reimert D.: Protective Relaying for Power Generation Systems, Taylor & Francis, 2006, ISBN
0-8247-0700-1.
27 Horowitz S. H, Phadke A. G.: Power System Relaying, 3rd Edition, John Wiley & Sons, 2008,
ISBN 978-0-470-05712-4.
28 Hewitson L. G., Brown M., Balakrishnan R.: Practical Power System Protection, Elsevier,
2004, ISBN 0-7506-6397-9.
29 Gurevich V.: Protection Devices and Systems for High-Voltage Applications, Marcel Dekker,
2003, ISBN 0-8247-4056-4.
30 Preve C.: Protection of electrical networks, ISTE, 2006, ISBN 1-905209-06-1.
31 Phadke A.G., Thorp J. S.: Computer Relaying for Power Systems, John Wiley & Sons, 1993,
ISBN 0-471-92063-0.
32 Bernas S., Ciok Z.: Mathematical Modeling of Power System Elements, Warsaw, VNT, 1977.
33 Gers J. M., Holmes E. J.: Protection of Electricity Distribution Networks, 2nd Edition, The
Institution of Electrical Engineers, 2004, ISBN 0-86341-357-9.
34 Blackburn J.L, Domin T.J.: Protective relaying, Principles and Applications, 3rd Edition, CRC
Press, 2007, ISBN 1-57444-716-5.
35 Kundur P.: Power System Stability and Control, McGraw-Hill, Inc., 1994
36 Marek Zima: Special Protection Schemes in Electric Power Systems, Literature Survey, Swiss
Federal Institute of Technology, Zurich, 2002.
37 Generator Protection. Application Guide, ABB, 1986.
38 Transformer Protection IED RET670, Technical Reference Manual, ABB, 2006.
39 Transformer Protection IED RET670, Application Manual, ABB, 2006.
40 Line Distance Protection IED REL670, Technical Reference Manual, ABB, 2006.
Date: 11/01/2010 Page: 61
41 Line Distance Protection IED REL670, Application Manual, ABB, 2006.
42 Busbar Differential Protection IED REB670, Technical Reference Manual, ABB, 2006.
43 Busbar Differential Protection IED REB670, Application Manual, ABB, 2006.
44 Bay Control IED REC670, Technical Reference Manual, ABB, 2006.
45 Bay Control IED REC 670, Application Manual, ABB, 2006.
46 Line Differential Protection IED RED670, Technical Reference Manual, ABB, 2006.
47 Line Differential Protection IED RED670, Application Manual, ABB, 2006.
48 REF 542 Plus Switchbay Protection and Control Unit, Manual part 1: Operation and
Maintenance, ABB, 2001.
49 REU 523 Combined Overvoltage and Undervoltage Relay, Technical Reference Manual, ABB,
1999.
50 RXHB 411 and RAHB 411 Compact Breaker Failure Relay, Technical Reference Manual,
ABB, 2001.
51 Network Protection and Automation Guide, Alstom, 2002, ISBN 2-9518589-0-6.
52 MiCOM P631, P632, P633, P634 Transformer Differential Protection, Software Version: 610,
Technical Manual, Areva.
53 MiCOM P125, P126, P127 Directional/Non-directional Relay, Version 6D, Technical Guide,
Areva.
54 MiCOM P139 Feeder Management and Bay Control, Software Version: 605/611/612,
Technical Manual, Areva.
55 MiCOM P342, P343 Generator Protection Relays, Software Version: 0070C, Technical Guide,
Areva.
56 MiCOMho P443 and P445 Distance Relay, Software Version: 33, Technical Manual, Areva.
57 MiCOM P54x Series Current Differential Relays, Technical Guide, Alstom, 2002.
58 MiCOM P740 Numerical Busbar Protection, Technical Manual, Alstom.
59 MiCOM P921-P922-P923 Voltage and Frequency Relays, Technical Guide, Alstom.
60 PS 462, PS 482 Time-Overcurrent Protection Devices, Software Version: 610, Technical
Manual, Alstom.
61 SIPROTEC Differential Protection 7UT613/63x V4.60, Manual, Siemens.
62 SIPROTEC Distance Protection 7SA6 V4.61, Manual, Siemens.
63 SIPROTEC Numerical Voltage, Frequency, and Overflux Protection 7RW600 V3.0, Instruction
Manual, Siemens, 2001.
64 SIPROTEC Line Differential Protection with Distance Protection 7SD52/53 V 4.60, Manual,
Siemens.
Date: 11/01/2010 Page: 62
65 SIPROTEC Multi-Functional Protective Relay with Local Control 7SJ62/64 V4.7, Manual,
Siemens.
66 SIPROTEC Distributed Busbar/ Breaker Failure Protection 7SS522 V4.6, 7SS523 V3.3,
7SS525 V3.3, Manual, Siemens, 2007.
67 SIPROTEC Multifunctional Machine Protection 7UM62 V4.6, Manual, Siemens, 2005.
68 SIPROTEC Breaker Management Device 7VK61 V4.60, Manual, Siemens, 2008.
69 Mason C. R.: The Art & Science of Protective Relaying, GE. Available at
http://www.gedigitalenergy.com/multilin/notes/artsci/index.htm
70 T60 Transformer Management Relay, UR Series Instruction Manual, Revision 5.2x, GE
Multilin, 2007.
71 745 Transformer Management Relay, Instruction Manual, Firmware Revision: 280.000, GE
Multilin, 2004.
72 C60 Breaker Protection System,UR Series Instruction Manual, Revision: 5.4x, GE Multilin,
2007.
73 F650 Digital Bay Controller, User manual, Firmware version: 3.7X, GE Multilin, 2007.
74 G60 Generator Management Relay, UR Series Instruction Manual, Revision: 5.2x, GE
Multilin, 2006.
75 ANSI/IEEE Std. C37.91-2000 - IEEE Guide for Protective Relay Applications to Power
Transformers, 2000.
76 IEEE Std. PC37.119 D7 - IEEE Guide for Breaker Failure Protection, Draft, 05/16/2005.
77 IEEE Std. C37.113-1999 - IEEE Guide for Protective Relay Applications To Transmission
Lines, 1999.
78 IEEE Std. C37.2-1991 - IEEE Standard Electrical Power System Device Function Numbers,
1991.
79 IEEE Std. C37.96-2000 - IEEE Guide for Ac Motor Protection, 2000.
80 IEEE Std. C37.97-1979 - IEEE Guide for Protective Relay Applications To Power System
Buses, 1979.
81 IEEE Std. C37.99-2000 - IEEE Guide for the Protection of Shunt Capacitor Banks, 2000.
82 IEC 60255-13 Electrical Relays - Biased (Percentage) Differential Relays, First Edition, 1980.
83 IEC 60255-8 Electrical Relays - Thermal Electrical Relays, Second Edition, 1990.
84 L.G.Mamikonyanz, Aspects of transients and asynchronous mode of synchronous and induction
machines analysis (Л.Г. Мамиконянц, Анализ некоторых аспектов переходных и
асинхронных режимов синхронных и асинхронных машин), Moscow, 2006.
85 E. I. Zabutskiy, Combined controllable electromagnetic reactors (Е. И. Забудский,
Совмещенные регулируемые электромагнитные реакторы), Moscow, 2003.