C:UsersTonyLDocumentsRoom Control Design Guide
Transcript of C:UsersTonyLDocumentsRoom Control Design Guide
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOTNEUTRAL
NEUTRAL
NEUTRALLighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 4Dim 3
Occupancy Sensor(up to 4)
Daylight Sensor
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
Teachers Station
Entry Station Entry Station
KIT#1
Kit Ordering Numbers:DRC01PS-1S11-12-NDRC01PS-1X11-12-NDRC01PS-1S31-12-NDRC01PS-1X31-12-N
Primary Daylight Zone Secondary Daylight Zone
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Whiteboard Light(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station
Dialog Room Controller
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
ORANGE
ORANGE
GREY
GREY
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
ORANGEORANGE
GREYGREY
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOTNEUTRAL
(EM) LIGHTING LOAD 5(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6(EM) LIGHTING HOT
NEUTRAL
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
Classroom Front(Relay 1)
N
N
Classroom Rear(Relay 2)N
N
Front EM Light(Relay 5)N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Classroom Front(Relay 1)
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 1
Dim 4
Occupancy Sensor(up to 4)
Daylight Sensor
Teachers Station
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Entry Station
KIT#2
Kit Ordering Numbers:DRC01PS-1S11-12-EDRC01PS-1X11-12-EDRC01PS-1S31-12-EDRC01PS-1X31-12-E
Entry Station
Classroom Rear(Relay 2)
Dim 1 Dim 2
Dim 4Dim 3
Primary Daylight Zone Secondary Daylight Zone
Rear EM Light(Relay 6)
Whiteboard Light(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom with Emergency Lighting• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station• During power failure UL924 listed relays are
automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.
Dialog Room Controller
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOTNEUTRAL
NEUTRAL
NEUTRALLighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
Whiteboard LightRelay 3N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 2
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 1Dim 1
Occupancy Sensor(up to 4)
Daylight Sensor
RoomController(WRC-3160)
Building Controlvia
BACnet IP or Dialog Network
Teachers Station
Entry Station Entry Station
KIT#3
Kit Ordering Numbers:DRC01OS-1S11-12-NDRC01OS-1X11-12-NDRC01OS-1S31-12-NDRC01OS-1X31-12-N
Primary Daylight Zone Secondary Daylight Zone
Classroom Front(Relay 1)
Classroom RearRelay 2
Classroom Front(Relay 1)
Classroom RearRelay 2
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom• Windows Opposite to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station.
Dialog Room Controller
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
ORANGE
ORANGE
GREY
GREY
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
ORANGEORANGE
GREYGREY
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOTNEUTRAL
(EM) LIGHTING LOAD 5(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6(EM) LIGHTING HOT
NEUTRAL
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 2
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 1Dim 1
Dim 2
Dim 1
Occupancy Sensor(up to 4)
Daylight Sensor
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Teachers Station
Entry Station Entry Station
KIT#4
Kit Ordering Numbers:DRC01OS-1S11-12-EDRC01OS-1X11-12-EDRC01OS-1S31-12-EDRC01OS-1X31-12-E
Primary Daylight Zone Secondary Daylight Zone
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Front EM Light(Relay 5)
Rear EM Light(Relay 6)
Whiteboard Light(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom with Emergency Lighting• Windows Opposite to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control zones (3 zones)• Receptacle Control• Dimming Control (3 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station• During power failure UL924 listed relays are
automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.
Dialog Room Controller
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOTNEUTRAL
NEUTRAL
NEUTRALLighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 4Dim 3
Daylight SensorZone 2
RoomController(WRC-3160)
Occupancy Sensor(up to 4)
Daylight SensorZone 1
Building Controlvia
BACnet IP or Dialog Network
Teachers Station
Entry Station Entry Station
KIT#5
Kit Ordering Numbers:DRC01PM-1S12-12-NDRC01PM-1X12-12-NDRC01PM-1S32-12-NDRC01PM-1X32-12-N
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Window Daylight Zone Skylight Daylight Zone
Whiteboard Light(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom• Windows Perpendicular to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station
Dialog Room Controller
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
ORANGE
ORANGE
GREY
GREY
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
ORANGEORANGE
GREYGREY
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOTNEUTRAL
(EM) LIGHTING LOAD 5(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6(EM) LIGHTING HOT
NEUTRAL
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 4Dim 3
Dim 1
Dim 4
Daylight SensorZone 2
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Occupancy Sensor(up to 4)
Daylight SensorZone 1
Teachers Station
Entry Station Entry Station
KIT#6
Kit Ordering Numbers:DRC01PM-1S12-12-EDRC01PM-1X12-12-EDRC01PM-1S32-12-EDRC01PM-1X32-12-E
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Front EM Light(Relay 5)
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Window Daylight Zone Skylight Daylight Zone
Rear EM Light(Relay 6)
Whiteboard Light(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom with Emergency Power• Windows Perpendicular to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station• During power failure UL924 listed relays are
automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.
Dialog Room Controller
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOTNEUTRAL
NEUTRAL
NEUTRALLighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 1
Dim 2Dim 2
RoomController(WRC-3160) Daylight Sensor
Zone 2
Occupancy Sensor(up to 4)
Daylight SensorZone 1
Building Controlvia
BACnet IP or Dialog Network
Teachers Station
Entry Station Entry Station
KIT#7
Kit Ordering Numbers:DRC01OM-1S12-12-NDRC01OM-1X12-12-NDRC01OM-1S32-12-NDRC01OM-1X32-12-N
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Whiteboard Light(Relay 3)
Window Daylight Zone Skylight Daylight Zone
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom• Windows Opposite to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station
Dialog Room Controller
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
ORANGE
ORANGE
GREY
GREY
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
ORANGEORANGE
GREYGREY
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOTNEUTRAL
(EM) LIGHTING LOAD 5(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6(EM) LIGHTING HOT
NEUTRAL
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 2
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 1Dim 1
Dim 2
Dim 1
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Daylight SensorZone 2
Occupancy Sensor(up to 4)
Daylight SensorZone 1
Teachers Station
Entry Station Entry Station
KIT#8
Kit Ordering Numbers:DRC01OM-1S12-12-EDRC01OM-1X12-12-EDRC01OM-1S32-12-EDRC01OM-1X32-12-E
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Classroom Front(Relay 1)
Classroom Rear(Relay 2)
Front EM Light(Relay 5)
Rear EM Light(Relay 6)
Whiteboard Light(Relay 3)
Window Daylight Zone Skylight Daylight Zone
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Classroom with Emergency Lighting• Windows Opposite to Teaching Wall• Skylight• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (4 zones)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station• During power failure UL924 listed relays are
automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.
Dialog Room Controller
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3LIGHTING LOAD 4
LIGHTING HOT LOAD 4
LIGHTING HOTNEUTRAL
NEUTRALLighting120/277/347Vac
DistributionCabinet
(by Others)
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 4Dim 3
Daylight SensorClassroom B
RoomController(WRC-3160)
Occupancy SensorClassroom A
Daylight SensorClassroom A
N
N
N
Occupancy SensorClassroom B
Building Controlvia
BACnet IP or Dialog Network
Entry Station(s)Classroom B
Teachers StationClassroom B
Entry Station(s)Classroom A
Teachers StationClassroom A
KIT#9
Kit Ordering Numbers:DRC02PS-2S12-22-NDRC02PS-2X12-22-NDRC02PS-2S32-22-NDRC02PS-2X32-22-N
Near Window(Relay 1)
Classroom B
Primary Daylight Zone Primary Daylight Zone
Near Window(Relay 2)
Secondary Daylight Zone Secondary Daylight Zone
Interior(Relay 1)
Interior(Relay 2)
Classroom A
Whiteboard Light(Relay 3)
Whiteboard Light((Relay 4))
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Double Classroom• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones per room)• Light Control (2 zones per room)• Dimming Control (2 zones per room)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station (ON/OFF) and Teacher Station
(GENERAL, TEACHING, A/V, ALL, DIMMING) providemanual control of lights
• Upon Exit and after Occupancy sensor times out,lights and receptacles switched OFF.
• Lights can be switched OFF manually at EntryStation and Teacher Station
Dialog Room Controller
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
ORANGE
ORANGE
GREY
GREY
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
ORANGEORANGE
GREYGREY
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3LIGHTING LOAD 4
LIGHTING HOT LOAD 4
LIGHTING HOTNEUTRAL
(EM) LIGHTING LOAD 5(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6(EM) LIGHTING HOT
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Near Window(Relay 1)N
Interior(Relay 5)N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2
Dim 4Dim 3
Daylight SensorClassroom B
Entry Station(s)Classroom B
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924) Teachers Station
Classroom B
Occupancy SensorClassroom A
Daylight SensorClassroom A
N
N
N
Classroom A Classroom B
Occupancy SensorClassroom B
Entry Station(s)Classroom A
Teachers StationClassroom A
KIT#10
Kit Ordering Numbers:DRC02PS-2S12-22-NDRC02PS-2X12-22-NDRC02PS-2S32-22-NDRC02PS-2X32-22-N
Primary Daylight Zone Primary Daylight Zone
Near Window(Relay 2)
Interior(Relay 6)
Secondary Daylight Zone Secondary Daylight Zone
Whiteboard Light(Relay 3)
Whiteboard Light((Relay 4))
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Double Classroom with Emergency Lighting• Windows Perpendicular to Teaching Wall• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones per room)• Light Control (3 zones per room)• Dimming Control (2 per room)• Entry Station (General ON/ALL OFF)• Teacher Station (Teaching, General ON, A/V, Quiet Mode)
• Emergency Lighting Control (2 zones Orange & Grey)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station• During power failure UL924 listed relays are
automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.
Dialog Room Controller
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
NEUTRAL
NEUTRALLighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 2
0-10V Dimming(18/2 per channel)
Dim 1
RoomController(WRC-3160)
Local Room Dataline (18/2)
Occupancy Sensor(up to 4)
Daylight Sensor
N
Dim 3
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOTNEUTRAL
Building Controlvia
BACnet IP or Dialog Network
Entry Station
KIT#11
Kit Ordering Numbers:DRC01NS-1S11-03-NDRC01NS-1X11-03-NDRC01NS-1S31-03-NDRC01NS-1X31-03-N
Interior(Relay 1)
Secondary Daylight Zone
Display / Track(Relay 3)
Near Window(Relay 2)
Primary Daylight Zone
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Office• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (General ON/ALL OFF)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Office Wall
Station
Dialog Room Controller
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
ORANGE
ORANGE
GREY
GREY
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
ORANGEORANGE
GREYGREY
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOTNEUTRAL
(EM) LIGHTING LOAD 5(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6(EM) LIGHTING HOT
NEUTRAL
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
0-10V Dimming(18/2 per channel)
Dim 1
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Local Room Dataline (18/2)
Occupancy Sensor(up to 4)
Daylight Sensor
N
Dim 3
Interior EM(Relay 5)N
Dim 2
Entry Station
KIT#12
Kit Ordering Numbers:DRC01NS-1S11-03-EDRC01NS-1X11-03-EDRC01NS-1S31-03-EDRC01NS-1X31-03-E
Near Window(Relay 2)
Primary Daylight Zone
Secondary Daylight Zone
Display / Track(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Office with Emergency Lighting• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (General ON/ALL OFF)
• Emergency Lighting Control (1 zones Orange)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Office Wall
Station• During power failure UL924 listed relays are
automatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright. Emergency lights remain ON withall controls disabled until primary power is restored.
Dialog Room Controller
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
NEUTRAL
NEUTRALLighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
General Lighting(Relay 1)
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Dim 2
RoomController(WRC-3160)
Local Room Dataline (18/2)
Occupancy Sensor(up to 4)
Daylight Sensor
Office Toggle Station
Preset Station(Optional)
N
Dim 3
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOTNEUTRAL
Building Controlvia
BACnet IP or Dialog Network
KIT#13
Kit Ordering Numbers:DRC01PS-1S11-30-NDRC01PS-1X11-30-NDRC01PS-1S31-30-NDRC01PS-1X31-30-N
Primary Daylight Zone
Display / Track(Relay 2)
Display / Track(Relay 3)
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Office• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (4-button toggle)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights and receptacle can be switched OFF
manually at Wall Station
Dialog Room Controller
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
ORANGE
ORANGE
GREY
GREY
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
ORANGEORANGE
GREYGREY
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3SWITCHED RECEPTACLE(S) LOAD 4
RECEPTACLE(S) HOT
LIGHTING HOTNEUTRAL
(EM) LIGHTING LOAD 5(EM) LIGHTING HOT
(EM) LIGHTING LOAD 6(EM) LIGHTING HOT
NEUTRAL
NEUTRAL
Emergency120/277/347Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Receptacle120Vac
DistributionCabinet
(by Others)
Receptacle(Relay 4)
N
N
N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Dim 1
0-10V Dimming(18/2 per channel)
Dim 2
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Local Room Dataline (18/2)
Occupancy Sensor(up to 4)
Daylight Sensor
Office Toggle Station
Preset Station(Optional)
N
Dim 3
Genreal Ltg EM(Relay 5)N
Dim 1
KIT#14
Kit Ordering Numbers:DRC01PS-1S11-30-EDRC01PS-1X11-30-EDRC01PS-1S31-30-EDRC01PS-1X31-30-E
General Lighting(Relay 1)
Primary Daylight Zone
Display / Track(Relay 2)
Display / Track(Relay 3)
Primary Daylight Zone
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Office with Emergency Lighting• Requires UL924 Relay Expansion Pack (orange)• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (2 zones)• Light Control (3 zones)• Receptacle Control• Dimming Control (3 zones)• Wall Station (4-button)
• Emergency Lighting Control (1 zones Orange)(Requires UL924 Relay Expansion Pack)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Office Wall Station provides manual control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights and receptacle can be switched OFF
manually at Wall Station
• During power failure UL924 listed relays areautomatically switched ON by back-up powersource switching designated emergency lights ONand to full-bright.
• Emergency lights remain ON with all controlsdisabled until primary power is restored.
Dialog Room Controller
Connection Schematic
Section 2 www.DouglasLightingControls.com
PURPLERED
YELLOWBLUE
BLUEWHITEBLACK
ORANGE
ORANGE
GREY
GREY
PURPLERED
YELLOWBLUE
BLUE
BLACKWHITE
ORANGEORANGE
GREYGREY
LIGHTING LOAD 1LIGHTING LOAD 2LIGHTING LOAD 3LIGHTING LOAD 4
LIGHTING HOT LOAD 4
LIGHTING HOTNEUTRAL
(EM) RECEPTACLE LOAD 5(EM) RECEPTACLE HOT
(EM) RECEPTACLE LOAD 6(EM) RECEPTACLE HOT
NEUTRAL
Receptacle120Vac
DistributionCabinet
(by Others)
NEUTRAL
Lighting120/277/347Vac
DistributionCabinet
(by Others)
Office A(Relay 3)N
DATALINE
DIM 1DIM 2
DIM 4DIM 3
Office B((Relay 4))
0-10V Dimming(18/2 per channel)
Local Room Dataline (18/2)
Dim 2Dim 1
Daylight SensorClassroom B
Entry Station(s)Office B
Building Controlvia
BACnet IP or Dialog Network
RoomController(WRC-3160)
EM Expansion(WUL-3924)
Occupancy SensorClassroom A
Daylight SensorClassroom A
N
Office A Office B
Occupancy SensorClassroom B
Entry Station(s)Office A
Receptacle(Relay 5)
N
Receptacle(Relay 6)
N
KIT#15
Kit Ordering Numbers:DRC02NS-2S12-04-NDRC02NS-2X12-04-NDRC02NS-2S32-04-NDRC02NS-2X32-04-N
Primary Daylight Zone Primary Daylight Zone
Options• Additional Occupancy Sensors (4 max.)• Vacancy Control (Manual ON / Auto OFF)• Extended Lens range: 54’ diameter (standard 28”)
Two Offices, One Dialog Room Controller• Occupancy Control (Auto ON /Auto OFF)• Daylight Control (1 zones per room)• Light Control (2 zones per room)• Receptacle Control• Dimming Control (1 zones per room)• Wall Station (ON/OFF)
• UL924 Relay Expansion for additional light load(2 zones Orange & Grey)
Operation• Upon Entry Occupancy sensor switches lights and
receptacles ON• Daylight Sensor maintains light level based on light
level pre-set• Entry Station and Teacher Station provide manual
control of lights• Upon Exit and after Occupancy sensor times out,
lights and receptacles switched OFF.• Lights can be switched OFF manually at Entry
Station and Teacher Station
Dialog Room Controller