CTO CSLS CHARM Cabinets - · PDF fileDeltaV SIS Process Safety System Product Data Sheet...
-
Upload
vuongtuyen -
Category
Documents
-
view
227 -
download
1
Transcript of CTO CSLS CHARM Cabinets - · PDF fileDeltaV SIS Process Safety System Product Data Sheet...
DeltaV SIS Process Safety System Product Data SheetNovember 2017
CTO CSLS CHARM Cabinets
Delivers Electronic Marshalling enabled by CHARMs technology
Reduce system footprint
Eliminate I/O home run cables
Significantly reduce cabinet design engineering
Fully documented package
Introduction
The DeltaV SIS Configure-To-Order (CTO) CHARMs Smart Logic Solver (CSLS) Cabinets provide an off-the-shelf solution for faster project execution and reduced installation costs. CTO CSLS Cabinets are factory tested and ready for installation in technical rooms. Electronic Marshalling eliminates traditional I/O design tasks and allows field wiring to start long before safety strategies are finalized.
CTO CSLS CHARM Cabinet.
Front View Rear View
www.emerson.com/deltavsis 2
CTO CSLS CHARM Cabinets November 2017
Benefits
Delivers Electronic Marshalling enabled by CHARMs technology: The CTO CSLS Cabinets offer the full benefits of Electronic Marshalling. The individual channels can be defined for any combination of field signal type, as required by the safety equipment. This allows for 100 % utilization of channels, regardless of the I/O signal mix. Late changes are easily accommodated with minimal re-engineering and no rewiring.
Reduced system footprint: Equipment room footprint is reduced by eliminating the traditional marshalling cabinets with cross wiring to traditional I/O cards.
Significantly reduce cabinet design engineering: The CTO CSLS cabinets are pre-engineered and factory tested. The I/O flexibility allows the same design to serve a wide variety of I/O signals, conditioned individually by the CHARM. Field wiring design is complete at the terminal block.
Fully documented package: Each cabinet is supplied with full documentation and engineering drawings showing internal lay- out, bill of materials and internal wiring. They are designed to meet local building code and industry best practices in order to deliver proven functionality with minimal costs.
Product Description
The CTO CSLS Cabinets offering comprises a range of pre- engineered solutions based on industry standard, preinstalled with CHARM I/O and related equipment, ready to be installed in an equipment room and connected to safety instrumentation or equipment.
The cabinets are typical, free standing enclosures intended for floor mounting in equipment room areas, where temperature and humidity are controlled within the requirements for computer/electronic equipment. They come ready to receive incoming plant AC power. All internal wiring to power distribution components and grounding conductors has been tested at the factory.
Before delivery, each cabinet undergoes a full in-house inspection, to assure that it is fully operational before shipping directly to site. Electronic Marshalling eliminates the need for any internal cross wiring and I/O rationalization there is typically no need for FAT at a staging facility.
These cabinets can be ordered and delivered directly together with the DeltaV SIS electronic marshalling equipment and LS CHARM I/O to site to begin field wiring (FAT may be optional).
The CTO CSLS Cabinets are configured by selecting a base enclosure model and required options to meet specific project needs.
Base enclosure models are available:
For different cabinet sizes / entry (Front Access or Front and Rear access).
For different power distribution needs: DC powered or AC powered.
For different world area design standards and regulations: EUR (Europe) and NA (US/Canada).
Configurable options examples: the type of LS CHARMS (I.S. or non I.S.), side panels, cabinet light, nameplate engraving and injected power.
All CTO CSLS cabinets come with following equipment installed.
Primary and secondary 24VDC power distribution for LS CHARM I/O Cards and field instrumentation.
Wire ducts or wire basket.
Grounding bars.
Wiring plan pocket.
Emerson Name Plate Holder and blank name plate insert.
DeltaV LS CHARM I/O equipment based on your configuration (and priced seperately): including CSLS carriers, CHARM base plates, standard terminal blocks, address plugs and terminals.
The CSLS cards and LS CHARMs are not included and are to be ordered separately.
The required number of (redundant) LS CHARM I/O cards and CSLS cards depends on the actual number and types of I/O that will be wired into the cabinet.
The following sections provide a more detailed specification for the CTO CSLS Cabinets and available options.
www.emerson.com/deltavsis 3
CTO CSLS CHARM Cabinets November 2017
Base Model number Description # LS CHARM IO
Power Requirements (Pri and Sec)
Permitted Location
/ World Area
EU-CAB-800F-192-AC-CSLS
AC Powered SIS Electronic Marshalling cabinet for 192 LS CHARM I/O; 800mm W x600mm D; Front Access SafeArea Locations.
192 230 VACSafe
Area EUR
EU-CAB-800FR-480-AC-CSLS
AC Powered SIS Electronic Marshalling cabinet for 480 LS CHARM I/O; 800mm Wx 800mm D; Front and RearAccess; Safe Area Locations.
480 230 VACSafe
Area EUR
NA-CAB-800F-192-AC-CSLS
AC Powered SIS Electronic Marshalling cabinet for 192 LS CHARM I/O; 800mm W x600mm D; Front Access SafeArea Locations.
192 120 VACSafe Area
US/CANADA
NA-CAB-800F-252-AC-CSLS
AC Powered SIS Electronic Marshalling cabinet for 252 LS CHARM I/O; 800mm W x600mm D; Front Access SafeArea Locations.
252 120 VACSafe Area
US/CANADA
NA-CAB-800FR-480-AC-CSLS
AC Powered SIS Electronic Marshalling cabinet for 480 LS CHARM I/O; 800mm Wx 800mm D; Front and RearAccess; Safe Area Locations.
480 120 VACSafe Area
US/CANADA
NA-CAB-800FR-504-AC-CSLS
AC Powered SIS Electronic Marshalling cabinet for 504 LS CHARM I/O; 800mm Wx 800mm D; Front and RearAccess; Safe Area Locations.
504 120 VACSafe Area
US/CANADA
Overview of CTO CSLS Cabinets Base Models
The CTO base model reference for cabinets uses the following naming convention:EUR or NA-CAB-XXXYY-ZZZIO-IP-DDDD, where
EUR : Europe Design Standards and Regulations / NA : US/Canada Design Standards and Regulations.
XXX = cabinet width (mm), e.g. 800, 1200.
YY = F for Front only access (600 mm deep), FR for Front and Rear access (800 mm deep).
ZZZ= maximum I/Os count in this CTO.
IP= Incoming Power, DC=24V DC or AC=120/230V AC.
DDDD= short description of content and purpose.
www.emerson.com/deltavsis 4
CTO CSLS CHARM Cabinets November 2017
Base Model
NA
-CA
B-8
00F-
252-
AC-
CSL
S
NA
-CA
B-8
00FR
-504
-AC-
CSL
S
NA
-CA
B-8
00F-
192-
AC-
CSL
S
NA
-CA
B-8
00FR
-480
-AC-
CSL
S
EU-C
AB
-800
F-19
2-A
C-C
SLS
EU-C
AB
-800
FR-4
80-A
C-C
SLS
World Area US/CAN US/CAN US/CAN US/CAN EUR EUR
Power Input (DC: 24VDC, AC:120/230VAC) AC AC AC AC AC AC
Enclosure Access (F: Front, FR: Front-Rear) F F/R F F/R F F/R
# CHARMI/O 252 504 192 480 192 480
Enclosure Options
Nameplate Engraving G0 No
1 Yes
Type of CHARMS(to be specified for each row of
CHARMS)C
1 Non I.S.
2 I.S.
Cabinet Light L1 No
2 LED light with motion sensor
Temperature Monitoring T0 No
1 Thermostat
Door Fans F1 Continuous Run
2 Thermostat Controlled
Plinth D1 100mm
N/A
2 200mm
Side Panels S0 No
1 Yes
Door Hing H1 Left Hinged
N/A
2 Right Hinged
Cable Routing B1 Cable Duct
N/A
2 Wire Basket
Baying Kit B0 No
1 Yes
Cable Clamps Rail R0 No
1 Yes
Utility Socket Selection U0 No
N/A
1 Yes
24VDC for Injected Power V
1 Front side No
2 Front side Yes
3 Rear side NoN/A
N/A
N/A
4 Rear side Yes
Certification Z
0 No
1 CE N/A 2 CSA N/A
Following more detailed options can be specified upon order (if applicable) :
Disconnect switches for DC power feeds can be configured separately for CSLS power and for injected power inputs
Type of utility socket : German-Russia / France-Poland / Switzerland / UK-Ireland / USA-Canada / Italy
Power supply configuration : Power for CSLS and/or injected power (with diode), Front and Rear position in cabinet
24VDC for injected power : optionally prewired (according specification to be provided)
Wiring color scheme different from default : US (L- Black, N- White) / EUR (L- Brown, N- Blue)
Input Voltage different from default : US (120VAC) / EUR (230VAC)
Overview of CTO CSLS Cabinets models and Options
: Default option settingo : Configure To Order option setting,
different from default blank : option setting not possible for the base enclosure
: Intentionally left blank to fill in your configuration choices
www.emerson.com/deltavsis 5
CTO CSLS CHARM Cabinets November 2017
NA-CAB-800F-252-AC-CSLS
Dimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm Plinth
Access Front Access single door, right hand hinged, latch type lock and 2 sets of keys (key N3524E)
Protection Category IP54 NEMA 12
Approximate Weight ~200 kg
Color Cabinet RAL7035, Plinth RAL7022
Door Fans Configurable: