    As a wholly British owned company Craig & Derricott have been designing, manufacturing and supplying low voltage electrical control and switchgear for over 70 years. Today our customers extend around the world and operate in a wide variety of markets and sectors including Railway, Construction, Ventilation (Fire rated), Explosion proof, Medical, Military, Panel builders and Power & Distribution.

    Based in the UK and certified to ISO 9001 we offer a wide range of assembled Electrical isolation and Control station products in the UAE region which are detailed in this catalogue. These are supported by a bespoke and special product service known as Mi switch, enabling customers to specify exact requirements which can be made to order.

    Simply contact your local Area Sales Manager to discuss your requirements.

    IndexThis catalogue covers our Building Services products.

    Simply contact our sales team to discuss your requirements and take advantage of our bespoke mi-switch service for made to order products at competitive prices.

    Range Description Page

    Enclosed Isolators

    Plastic Enclosed 3

    Die-Cast Aluminium Enclosed 5

    Sheet Steel Enclosed - Mild Steel 7

    Sheet Steel Enclosed - with Defeatable Door Interlock Handle 8

    Stainless Steel Enclosed 9

    Sloping Roof Stainless Steel Enclosed 10

    Flush Mounting Stainless Steel 11

    Technical Data 12

    Hinged Lid Sheet Steel 13

    Fire Rated - F300 / F400 15

    LUL Section 12 Equipment 17

    Dimensions and Fixings 19

    Ex IECEx / ATEX Zone 1 & 2 Isolators 23

    Ex IECEx / ATEX Zone 1 & 2 Dimensions 25

    Ex ATEX Zone 1/21 & 2/22 26

    Fire Rated - F200 28

    Panel Isolators

    Compact Panel Isolators 25A - 200A 29

    Standard Panel Isolators 100A - 1000A 31

    Panel Isolator Technical Data 33

    Compact Panel Isolator Dimensions 34

    Standard Panel Isolator Dimensions 35

    Changeover Isolators 32A - 630A 36

    Changeover Isolators Dimensions 37

    Bespoke Assemblies 38switchm

    switch

    switch

    Introduction & Index

  • www.craigandderricott.comPage

    2

    Product GuideProduct definitions and Utilisation categories to IEC 60947-3

    Definition Technical Description

    Switch-Disconnector

    Sym.

    A Disconnector is a mechanical switch which in the Open position, complies with requirements specified for the isolating function. A Disconnector or Isolator is an off-load device and marked Isolate elsewhere before opening they have an AC20/DC20 utilisation category.

    A Switch is a mechanical switching device capable of making, carrying and breaking current under normal circuit conditions, which may include specified operating overload conditions. They also carry, for a specified time, currents under specified abnormal circuit conditions, such as those of short circuit (i.e. Utilisation category AC23A duty).

    A Switch-Disconnector meets both of these criteria and with a Red/Yellow padlockable handle may also be called a Safety Isolator.

    Ingress ProtectionWhen choosing an isolating device, apart from the electrical performance, consideration must be given to the environmental conditions in which the device will be placed. The item may be subjected to dust or dirt or it may come in contact with degrees of moisture. Indoor conditions will vary considerably but items may well be placed outdoors where the full influence of rain, ice & snow will be present. Protecting items to varying degrees is detailed in BS EN 60529:1992.

    Employing a two digit code the standard defines protection against solid objects and separately protection against moisture i.e.

    IP66(protection against water)

    (protection against solid objects)

    Please refer to BS EN 60529:1992 for full details.

    The following extract defines the IP categories used within this document.

    1st Digit Protection against solid objects 2nd Digit Protection against water

    0 Not Protected 0 Not Protected

    2 Protected against solid objects greater than 12.5 1Protected against drip-

    ping water.

    4 Protected against solid objects greater than 1.0 4Protected against

    splashed water from any direction.

    5

    Protected against dust - allowing a degree of

    ingress that isnt harmful to the assembly.

    5 Protected against water jets from any direction.

    6 No ingress of dust. 6Protected against strong

    water jets from any direction.

    12.5

    1.0

    Utilisation Category

    Description

    AC20 Connecting & disconnecting under no-load conditions.

    AC21 Switching of resistive loads including moderate overloads.

    AC22 Switching of mixed resistive/inductive loads including moderate overloads.

    AC23 Switching of highly inductive loads(Capable of safely isolating a motor even under stalled conditions e.g. chiller unit)

    Frequent and Infrequent Use.The categories above can be suffixed to indicate a frequency of use:-Frequent Use (A) Up to 5 times a day for small devices (typically up to 100A), once a week for larger items. Infrequent Use (B) Once a week for smaller devices, once a month for the larger items.

    Product Guide & IP Data

  • Page

    3

    PadlockingAll items allow for the insertion of up to three padlocks in the Off position thus preventing the isolator being switched to the On position.

    Standard shackle diameter 6.4

    Safety Interlock

    Screwed lid enclosures have always been open to abuse by having the lid removable when the isolator is Off and padlocked. This would allow the switch shaft to be turned manually to the On position, thus defeating the safety padlocking feature.

    The i-switch range now incorporates a mechanical interlock which when a padlock is inserted prevents the enclosure lid from being removed.

    N = Switched neutral (Early make, late break)NL = Unswitched neutralEB = Early break auxiliary contacts

    Rating Format Interior Switch product range Cat. No.Enclosure

    Size

    20A6P GX20 SDP206 A

    (IP66)6P+2EB Aux GX20 SDP206EB

    25A

    2P CS25 SDP252

    A(IP66)

    3P CS25 SDP2533P+NL CS25 SDP253NL3P+N CS25 SDP253N

    3P+2EB Aux CS25 SDP253EB

    32A

    2P CS32 SDP322

    A(IP66)

    3P CS32 SDP3233P+NL CS32 SDP323NL3P+N CS32 SDP323N

    3P+2EB Aux CS32 SDP323EB

    40A

    2P CS40R SDP402

    B(IP66)

    3P CS40R SDP4033P+NL CS40R SDP403NL3P+N CS40R SDP403N

    3P+2EB Aux CS40R SDP403EB6P GX40 SDP406

    6P+2EB Aux GX40 SDP406EB

    63A

    2P CS63 SDP632

    B(IP66)

    3P CS63 SDP6333P+NL CS63 SDP633NL3P+N CS63 SDP633N

    3P+2EB Aux CS63 SDP633EB

    80A

    2P CS80 SDP802

    C(IP65)

    3P CS80 SDP8033P+NL CS80 SDP803NL3P+N CS80 SDP803N

    3P+2EB Aux CS80 SDP803EB

    100A

    2P CS100 SDP1002

    D(IP65)

    3P CS100 SDP10033P+NL CS100 SDP1003NL3P+N CS100 SDP1003N

    3P+2EB Aux CS100 SDP1003EB

    Catalogue Numbers

    Switch-Disconnectors (O-I)

    Rating Format Interior Switch product range Cat. No.Enclosure

    Size

    20A2P GX20 SCODP202

    A(IP66)3P GX20 SCODP203

    4P GX20 SCODP204

    40A2P GX40 SCODP402

    B(IP66)3P GX40 SCODP403

    4P GX40 SCODP404

    Changeover Switch-Disconnectors (I-O-II)

    General DescriptionSwitch-disconnectors housed in moulded plastic enclosures provide the basis for most industrial applications and the added benefits offered by the i-switch range provide the user with a wealth of opportunities when selecting the correct item for a specific application. Sealing up to IP66 is a standard feature as is the ability to add a selection of auxiliary blocks providing additional contacts and a choice of Neutral assemblies.

    With the i-switch range comes an important safety feature which prevents the enclosure cover being removed when the device has been padlocked in the Off position. When combined with the excellent on-load breaking capacity of the i-switch family this feature ensures that the term Safety Switch is fully satisfied.

    Watch a 3 minute video explaining the various safety features built-in to the design of the i-switch screwed lid product family.Technical

    DataPg 12

    DimensionsPg 19

    Encl

    osed

    Isol

    ator

    s

    If you require padlocking in both the Off & On positions then add a /10 to the catalogue number i.e. SDP633EB/10

    Catalogue Numbers

    Plastic Enclosed

    Safety Features

  • www.craigandderricott.comPage

    4

    Neutral Link 2 Early Break Neutral Link (Unswitched) Auxiliary (Switched)

    Description Cat. No.

    Auxiliary Contact - 2 Early Break SAUX2EB

    Auxiliary Contact - 1 N/O + 1 N/C SAUXCO

    25A Neutral (Unswitched) SNL25

    32A & 40A Neutral (Unswitched) SNL40

    63A Neutral (Unswitched) SNL63

    80A Neutral (Unswitched) SNL80

    100A Neutral (Unswitched) SNL100

    25A Neutral (Switched) SSP25

    32A & 40A Neutral (Switched) SSP40

    63A Neutral (Switched) SSP63

    80A Neutral (Switched) SSP80

    100A Neutral (Switched) SSP100

    Applicable to type CS interiors only

    Design Features

    Plastic Enclosed

    Enclosure

    Material 20A-63A PC/ABS 80A-100A PC

    Colour Enclosure - Grey RAL 7035

    Entries Size A Enclosure - 2 x M20 knock-outs on top & bottom faces. Size B Enclosure - 2 x M20/25 knock-outs on top & bottom faces. Back face - 2 x M20 knock-outs. Size C & D Enclosures - Blank sides.

    Cover Screws Stainless Steel (Captive)

    Fixings Outside sealed cavity.

    Switch-Disconnectors

    KEMA certified

    2 & 3 Pole Type CS - base mounted. (Accepts add-on Aux. blocks & Neutrals)

    6 Pole Type GX - base mounted. (also available with 2 E/B Aux.)

    Changeover Switch-Disconnectors

    KEMA certified

    2, 3 & 4 Pole Type GX - base mounted.

    Earthing

    KEMA certified

    Earth terminals are provided in the base of the enclosures.

    Encl

    osed

    Isol

    ator

    s

    Catalogue Numbers

    Technical DataPg 12

    DimensionsPg 19

    All switched neutral blocks have Early make, late break contacts.

    Accessories

  • Page

    5

    General DescriptionThe i-switch die-cast range provides the user with a product that will withstand a good deal of rough treatment. With sealing up to IP66 these assemblies can be placed in environments where resistance to impacts, moisture and dust/dirt are a concern.

    The i-switch range now incorporates a mechanical interlock which when a padlock is inserted prevents the enclosure lid from being removed.

    All safety features are identical to the plastic moulded range - see page 3 for details.

    Catalogue Numbers

    C/O Switch-Disconnectors (I-O-II)

    Switch-Disconnectors (O-I)

    If you require padlocking in both the Off & On positions then add a /10 to the catalogue number i.e. SDDG403NX/10

    Rating Format

    Interior Switch product range

    Catalogue Nos. (Grey)Enclosure

    SizeBottom cable entries only (X)

    Top & Bottom cable entries (Y)

    20A 6P GX20 SDDG206X SDDG206Y A(IP66)6P+2EB Aux GX20 SDDG206EBX SDDG206EBY

    25A

    2P CS25 SDDG252X SDDG252Y

    A(IP66)

    3P CS25 SDDG253X SDDG253Y3P+N CS25 SDDG253NX SDDG253NY3P+NL CS25 SDDG253NLX SDDG253NLY

    3P+2EB Aux CS25 SDDG253EBX SDDG253EBY

    32A

    2P CS32 SDDG322X SDDG322Y

    A(IP66)

    3P CS32 SDDG323X SDDG323Y3P+N CS32 SDDG323NX SDDG323NY3P+NL CS32 SDDG323NLX SDDG323NLY

    3P+2EB Aux CS32 SDDG323EBX SDDG323EBY

    40A

    2P CS40R SDDG402X SDDG402Y

    A (IP66)

    3P CS40R SDDG403X SDDG403Y3P+N CS40R SDDG403NX SDDG403NY3P+NL CS40R SDDG403NLX SDDG403NLY

    3P+2EB Aux CS40R SDDG403EBX SDDG403EBY6P GX40 SDDG406X SDDG406Y

    B (IP66)

    6P+2EB Aux GX40 SDDG406EBX SDDG406EBY2P CS40 SDDG402TX SDDG402TY3P CS40 SDDG403TX SDDG403TY

    3P+NL CS40 SDDG403NLTX SDDG403NLTY3P+N CS40 SDDG403NTX SDDG403NTY

    3P+2EB Aux CS40 SDDG403EBTX SDDG403EBTY

    63A

    2P CS63 SDDG632X SDDG632Y

    B(IP66)

    3P CS63 SDDG633X SDDG633Y3P+N CS63 SDDG633NX SDDG633NY3P+NL CS63 SDDG633NLX SDDG633NLY

    3P+2EB Aux CS63 SDDG633EBX SDDG633EBY6P CS63 SDDG636X SDDG636Y

    6P+2EB Aux CS63 SDDG636EBX SDDG636EBY

    80A3P CS80 SDDG803X SDDG803Y

    B (IP66)3P+NL CS80

    SDDG803NLX SDDG803NLY

    3P+N CS80 SDDG803NX SDDG803NY

    Rating Format

    Interior Switch product range

    Cat. Nos. Cat. Nos.Enclosure

    Size(Bottom cable entries only)

    (Top & bottom cable entries)

    20A2P GX20 SCODDG202X SCODDG202Y

    A(IP66)3P GX20 SCODDG203X SCODDG203Y

    4P GX20 SCODDG204X SCODDG204Y

    40A2P GX40 SCODDG402X SCODDG402Y

    B(IP66)3P GX40 SCODDG403X SCODDG403Y

    4P GX40 SCODDG404X SCODDG404Y

    Encl

    osed

    Isol

    ator

    s

    Size A

    Size B

    Catalogue Numbers

    N = Switched neutral (Early make, late break)NL = Unswitched neutralEB = Early break auxiliary contactsX = Bottom cable entries onlyY = Top and bottom cable entriesT = Increased terminal capacity

    Die-Cast Aluminium Enclosed

    Technical DataPg 12

    DimensionsPg 20

  • www.craigandderricott.comPage

    6

    Description Cat. No.Auxiliary Contact - 2 Early Break SAUX2EBAuxiliary Contact - 1 N/O + 1 N/C SAUXCO25A Neutral (Unswitched) SNL2532A & 40A Neutral (Unswitched) SNL4063A Neutral (Unswitched) SNL6380A Neutral (Unswitched) SNL8025A Neutral (Switched) SSP2532A & 40A Neutral (Switched) SSP4063A Neutral (Switched) SSP6380A Neutral (Switched) SSP80

    Die-Cast Aluminium Enclosed

    Enclosure

    Material Die-cast aluminium alloy LM24 (BS1490) AL - Si8Cu3Fe

    Paint finish Grey - RAL 7035 Chromate pre-treatment and smooth power coat finish.

    Entries Included with std. catalogue No:-

    Style X - Bottom entries only Style Y - Bottom/top

    Cover Screws Stainless Steel (Captive)

    Earthing Terminals are provided on both lid and base to allow full earth continuity to be maintained

    Mounting All fixings are internal but outside of the IP66 sealed area. Guide channels are provided to assist with the fixing screw location.

    Switch-Disconnectors

    KEMA Certified

    2, 3 & 6 Pole Type CS - base mounted. (Accepts add-on Aux. blocks & Neutrals)

    6 Pole Type GX - base mounted. (also available with 2 E/B Aux.)

    Changeover Switch-Disconnectors

    KEMA Certified

    2, 3 & 4 Pole Type GX - base mounted.

    Assembly

    Sealing to IP66

    Encl

    osed

    Isol

    ator

    s

    All switched neutral blocks have Early make, late break contacts.

    Style Y has been designed and manufactured specifically to give the installer the flexibility to have cable entry top and bottom.

    The X version offers the installer cable entry at bottom only but has the advantage of guaranteeing IP rating is not compromised due to an installation fault or abuse.

    Style XStyle Y

    Catalogue Numbers

    Technical DataPg 12

    DimensionsPg 20

    Applicable to type CS interiors only

    Accessories

    Design Features

    Exploded view of a die cast assembly showing the type CS isolator interior.

  • Page

    7

    Rating Format

    Interior Switch product range

    Cat. No.Enclosure

    SizeStd Handle (IP66)

    20A6P GX20 SDMG206

    A 6P+2EB GX20 SDMG206EB

    25A

    2P CS25 SDMG252

    A3P CS25 SDMG253

    3P+NL CS25 SDMG253NL3P+N CS25 SDMG253N

    3P+2EB CS25 SDMG253EB

    32A

    2P CS32 SDMG322

    A3P CS32 SDMG323

    3P+NL CS32 SDMG323NL3P+N CS32 SDMG323N

    3P+2EB CS32 SDMG323EB

    40A

    2P CS40R SDMG402

    B

    3P CS40R SDMG4033P+NL CS40R SDMG403NL3P+N CS40R SDMG403N

    3P+2EB CS40R SDMG403EB6P GX40 SDMG406

    6P+2EB GX40 SDMG406EB

    63A

    2P CS63 SDMG632

    B3P CS63 SDMG633

    3P+NL CS63 SDMG633NL3P+N CS63 SDMG633N

    3P+2EB CS63 SDMG633EB

    Catalogue NumbersSwitch-Disconnectors (O-I)

    (If you require padlocking in both the Off & On positions then add a /10 to the catalogue number i.e. SDMG323NL/10.

    General DescriptionSwitch-disconnectors housed in mild steel enclosures provides the user with a robust and cost effective assembly along with the added features offered by the i-switch range. Sealing to IP66 is a standard feature as is the ability to add a selection of auxiliary blocks and a choice of Neutral assemblies. All safety features are identical to the plastic moulded range - see page 3 for details.

    Rating Format

    Interior Switch product range

    Cat. No. Enclosure Size

    20A2P GX20 SCODMG202

    A3P GX20 SCODMG2034P GX20 SCODMG204

    40A2P GX40 SCODMG402

    B3P GX40 SCODMG4034P GX40 SCODMG404

    Changeover Switch-Disconnectors (I-O-II)

    Design FeaturesEnclosure

    Material Sheet steel, thickness 1.2mmPaint finish Epoxy Powder Coated.Colour Enclosure - Grey RAL 7035Fitting 20A-32A Size A, 40A-63A Size BEntries Size A Enclosure - 2 x M20 Size B Enclosure - 2 x M20 + 2 x M25Cover Screws Stainless Steel (Captive)External Feet Size A enclosure - Cat. No. EFA Size B enclosure - Cat. No. EFB (See over for dimensions)

    Switch-Disconnectors

    KEMA Certified

    2 & 3 Pole Type CS - base mounted. (Accepts add-on Aux. blocks & Neutrals)

    6 Pole Type GX - base mounted. (also available with 2 E/B Aux.)

    Changeover Switch-Disconnectors

    KEMA Certified

    2, 3 & 4 Pole Type GX - base mounted.

    Earthing

    Earth continuity terminals are provided in the base and lid of each enclosure.

    Encl

    osed

    Isol

    ator

    s

    Mild Steel

    Catalogue Numbers

    N = Switched neutral (Early make, late break)NL = Unswitched neutralEB = Early break auxiliary contacts

    Sheet Steel Enclosed

    Technical DataPg 12

    DimensionsPg 19

  • www.craigandderricott.comPage

    8

    General DescriptionThis version of the sheet steel enclosure range includes a Defeatable Door Interlock Handle with all of the safety features found on the standard range but adds an override facility which allows the screwed lid to be removed in the On position for testing purposes. Sealing to IP65.

    Design FeaturesEnclosure

    Material Sheet steel, thickness 1.2mmPaint finish Iron phosphate pre-treatment & epoxy powder coat smooth finish.Colour Enclosure - Grey RAL 7035Entries Size A Enclosure - 2 x M20 Size B Enclosure - 2 x M20 + 2 x M25Cover Screws Stainless Steel (Captive)External Feet Size A enclosure - Cat. No. EFA Size B enclosure - Cat. No. EFB

    Switch-Disconnectors

    KEMA Certified

    2 & 3 Pole Type CS - base mounted. (Accepts add-on Aux. blocks & Neutrals)

    6 Pole Type GX - base mounted. (also available with 2 E/B Aux.)

    Changeover Switch-Disconnectors

    KEMA Certified

    2, 3 & 4 Pole Type GX - base mounted.

    Earthing

    Earth continuity terminals are provided in the base and lid of each enclosure.

    Encl

    osed

    Isol

    ator

    s

    Rating Format Interior Switch product rangeCat. No. Encl.

    Size

    20A6P GX20 SDMG206/H2

    A6P+2EB Aux GX20 SDMG206EB/H2

    25A

    2P CS25 SDMG252/H2

    A3P CS25 SDMG253/H2

    3P+NL CS25 SDMG253NL/H23P+N CS25 SDMG253N/H2

    3P+2EB Aux CS25 SDMG253EB/H2

    32A

    2P CS32 SDMG322/H2

    A3P CS32 SDMG323/H2

    3P+NL CS32 SDMG323NL/H23P+N CS32 SDMG323N/H2

    3P+2EB Aux CS32 SDMG323EB/H2

    40A

    2P CS40R SDMG402/H2

    B

    3P CS40R SDMG403/H23P+NL CS40R SDMG403NL/H23P+N CS40R SDMG403N/H2

    3P+2EB Aux CS40R SDMG403EB/H26P GX40 SDMG406/H2

    6P+2EB Aux GX40 SDMG406EB/H2

    63A

    2P CS63 SDMG632/H2

    B3P CS63 SDMG633/H2

    3P+NL CS63 SDMG633NL/H23P+N CS63 SDMG633N/H2

    3P+2EB Aux CS63 SDMG633EB/H2

    Catalogue Numbers

    Switch-Disconnectors (O-I)

    Insert a small diameter tool, such as a screwdriver to override the lid interlock.

    Sheet Steel Enclosed

    Description Cat. No.Auxiliary Contact - 2 Early Break SAUX2EBAuxiliary Contact - 1 N/O + 1 N/C SAUXCO25A Neutral (Unswitched) SNL2532A & 40A Neutral (Unswitched) SNL4063A Neutral (Unswitched) SNL6325A Neutral (Switched) SSP2532A & 40A Neutral (Switched) SSP4063A Neutral (Switched) SSP63

    (If you require padlocking in both the Off & On positions then add a /10 to the catalogue number i.e. SDMG323NL/10.

    With Defeatable Door Interlock Handle

    Catalogue Numbers

    N = Switched neutral (Early make, late break)NL = Unswitched neutralEB = Early break auxiliary contacts

    Technical DataPg 12

    DimensionsPg 19

    All switched neutral blocks have Early make, late break contacts.

    Applicable to type CS interiors only

    Accessories

  • Page

    9

    General DescriptionSwitch-disconnectors housed in stainless steel enclosures provides the user with an assembly that can be installed in the harshest of environments. Outdoor in unprotected positions or indoor and subject to severe environmental conditions, the standard stainless steel i-switch range with a flush back surface offers the ideal solution. Sealing to IP66 is a standard feature as is the ability to add a selection of auxiliary blocks providing additional contacts and a choice of Neutral assemblies. External mounting feet in stainless steel are offered as an accessory sized to match each enclosure. All safety features are identical to the plastic moulded range - see page 3 for details.

    The defeatable door interlock handle option provides an override facilty which allows the lid to be removed in the On position for testing purposes.

    Rating Format Interior Switch product range Cat. No.Enclosure

    Size

    20A2P GX20 SCODS202

    A(IP66)3P GX20 SCODS203

    4P GX20 SCODS204

    40A2P GX40 SCODS402

    B(IP66)3P GX40 SCODS403

    4P GX40 SCODS404

    Changeover Switch-Disconnectors (I-O-II)

    Design FeaturesEnclosure (Flush rear surface)

    Material Stainless steel, Grade 304, thickness 1.2mm (Grade 316 to special order)Finish Brushed - Satin (150 grit)Entries Size A Enclosure - 2 x M20 Size B Enclosure - 2 x M20 + 2 x M25Cover Screws Stainless Steel (Captive)External Feet Size A enclosure - Cat. No. EFA Size B enclosure - Cat. No. EFB

    Switch-Disconnectors

    KEMA Certified

    2 & 3 Pole Type CS - base mounted. (Accepts add-on Aux. blocks & Neutrals)

    6 Pole Type GX - base mounted. (also available with 2 E/B Aux.)

    Changeover Switch-Disconnectors

    KEMA Certified

    2, 3 & 4 Pole Type GX - base mounted.

    Earthing

    Earth continuity terminals are provided in the base and lid of each enclosure.

    Rat-ing Format

    Interior Switch product range

    Catalogue No.Enclosure

    SizeStd. Handle (IP66)

    H2 Handle (IP65)

    20A6P GX20 SDS206 -

    A6P+2EB Aux GX20 SDS206EB -

    25A

    2P CS25 SDS252 SDS252/H2

    A3P CS25 SDS253 SDS253/H2

    3P+NL CS25 SDS253NL SDS253NL/H23P+N CS25 SDS253N SDS253N/H2

    3P+2EB Aux CS25 SDS253EB SDS253EB/H2

    32A

    2P CS32 SDS322 SDS322/H2

    A3P CS32 SDS323 SDS323/H2

    3P+NL CS32 SDS323NL SDS323NL/H23P+N CS32 SDS323N SDS323N/H2

    3P+2EB Aux CS32 SDS323EB SDS323EB/H2

    40A

    2P CS40R SDS402 SDS402/H2

    B

    3P CS40R SDS403 SDS403/H23P+NL CS40R SDS403NL SDS403NL/H23P+N CS40R SDS403N SDS403N/H2

    3P+2EB Aux CS40R SDS403EB SDS403EB/H26P GX40 SDS406 SDS406/H2

    6P+2EB Aux GX40 SDS406EB SDS406EB/H2

    63A

    2P CS63 SDS632 SDS632/H2

    B3P CS63 SDS633 SDS633/H2

    3P+NL CS63 SDS633NL SDS633NL/H23P+N CS63 SDS633N SDS633N/H2

    3P+2EB Aux CS63 SDS633EB SDS633EB/H2

    Catalogue Numbers

    Standard Switch-Disconnectors (O-I)

    (If you require padlocking in both the Off & On positions then add a /10 to the catalogue number i.e. SDS323NL/10.

    Encl

    osed

    Isol

    ator

    s

    Catalogue Numbers

    N = Switched neutral (Early make, late break)NL = Unswitched neutralEB = Early break auxiliary contacts

    Stainless Steel Enclosed

    Technical DataPg 12

    DimensionsPg 19

  • www.craigandderricott.comPage

    10

    Rating Format Interior Switch product range Cat. No.Encl. Size

    20A6P GX20 SDSSR206 A

    (IP66)6P+2EB AUX GX20 SDSSR206EB

    25A

    2P CS25 SDSSR252A

    (IP66)3P CS25 SDSSR253

    3P+2EB AUX CS25 SDSSR253EB3P+N CS25 SDSSR253N

    32A

    2P CS32 SDSSR322A

    (IP66)3P CS32 SDSSR323

    3P+2EB AUX CS32 SDSSR323EB3P+N CS32 SDSSR323N

    40A

    2P CS40R SDSSR402

    B(IP66)

    3P CS40R SDSSR4033P+2EB AUX CS40R SDSSR403EB

    3P+N CS40R SDSSR403N6P GX40 SDSSR406

    6P+2EB AUX GX40 SDSSR406EB

    63A

    2P CS63 SDSSR632B

    (IP66)3P CS63 SDSSR633

    3P+2EB AUX CS63 SDSSR633EB3P+N CS63 SDSSR633N

    Catalogue Numbers

    Sloping Roof Switch-Disconnectors (O-I)

    General DescriptionBased upon Craig & Derricotts i-switch range of isolation equipment, the specially designed stainless steel sloping roof enclosure is ideally suited for hygienic environments with their associated severe cleaning routines. The design has been created to minimise areas where dirt can accumulate and incorporates a flush rear surface and universal fixing that include IP66 sealings. All safety features are identical to the plastic moulded range - see page 3 for details.

    Design FeaturesEnclosure (Flush rear surface)

    Material Stainless steel, Grade 316, thickness 1.2mm body, 1.5mm lid. (15 Slope)Finish Brushed - Satin 150 gritEntries The enclosures are supplied as standard without entries. Optional pre-drilled bottom entries can be supplied as follows:- Size A - 2xM20 (add M20 to cat No.) Size B - 2xM25 (add M25 to cat No.) e.g. SDSSR322/M20, SDSSR403N/M25Cover Screws Stainless Steel (Captive)

    Safety Features

    Switch-Disconnectors

    KEMA Certified

    2 & 3 Pole Type CS - base mounted. (Accepts add-on Aux. blocks & Neutrals)

    6 Pole Type GX - base mounted. (also available with 2 E/B Aux.)

    Earthing

    Earth continuity terminals are provided in the base and lid of each enclosure.

    Fixings

    Universal fixings across the range.

    Sloping Roof Stainless Steel Enclosed

    (If you require padlocking in both the Off & Onpositions then adda /10 to the catalogue number i.e. SDSSR323NL/10)

    Encl

    osed

    Isol

    ator

    sDescription Cat. No.

    Auxiliary Contact - 2 Early Break SAUX2EBAuxiliary Contact - 1 N/O + 1 N/C SAUXCO25A Neutral (Unswitched) SNL2532A & 40A Neutral (Unswitched) SNL4063A Neutral (Unswitched) SNL6380A Neutral (Unswitched) SNL8025A Neutral (Switched) SSP2532A & 40A Neutral (Switched) SSP4063A Neutral (Switched) SSP6380A Neutral (Switched) SSP80

    Catalogue Numbers

    N = Switched neutral (Early make, late break)EB = Early break auxiliary contacts

    Technical DataPg 12

    DimensionsPg 19

    All switched neutral blocks have Early make, late break contacts.

    Applicable to type CS interiors only

    Accessories

  • Page

    11

    Encl

    osed

    Isol

    ator

    sFlush Mounting Stainless Steel

    General DescriptionCraig & Derricott have been manufacturing flush mounting isolators for more than 70 years and in that time the design has been carefully modified to give features that installers and end users really need.

    The assembly consists of a zinc plated back box (complete with knock-outs) and a stainless steel fascia plate which carries the isolating switch and lockable handle. The fascia plate now comes in an attractive brushed finish which resists the fingerprint effect associated with highly polished surfaces.

    Equally at home in kitchens, laboratories, food processing areas, hospitals and many other areas where an elegant, low projection isolation device is required.

    Rating Format Interior Switch product range Cat. No.Enclosure

    Size

    20A2P

    GXSDFL202

    A3P SDFL2034P SDFL204

    32A2P

    GXSDFL322

    B3P SDFL3234P SDFL324

    40A2P

    GXSDFL402

    B3P SDFL4034P SDFL404

    63A2P

    GNSDFL632

    C3P SDFL6334P SDFL634

    Catalogue NumbersSwitch-Disconnectors (O-I)

    Earthing

    Separate earthing points on fascia plate and back box.

    Sealing

    Isolating switch to stainless steel fascia plate - IP66.

    Fascia plate securing screws

    Stainless steel (M5 x 25 with Allen Key head).

    InstallationWhilst the joint between the isolating switch and the stainless steel fascia plate is factory sealed to IP66 min, when installed, the fascia to mounting surface seal is the responsibility of the installer.

    To maintain the sealing overall, an efficient bond must be made using some form of gasketing material. This is particularly vital on tiled surfaces where grout lines can channel moisture down the wall.

    A continuous bead of moisture resistant mastic is a simple way of providing a seal, and can improve the appearance of the final assembly on an uneven surface.

    Typical Installation(D max = 20mm with standard length

    mounting screws

    Enclosure

    Fascia plate Stainless steel 304, thickness 1.2mm Finish Brushed.

    Back box Sheet steel, thickness 1.4mm Finish Galvanised

    Entries

    Knockouts in back box.

    Design Features

    Technical DataPg 12

    DimensionsPg 19

  • www.craigandderricott.comPage

    12

    Application Category Sym. Unit Rating

    Rated insulation voltage - Ui V 690

    Rated thermal current - Ith A 10

    Rated operational current (AC15)

    110V

    Ie A

    8

    220-240V 8

    380-400V 3

    660-690V 1

    Max. conductor size - - mm2 1.5

    Tightening torque - - Nm 0.6

    Auxiliary Contacts

    Data supplied against tests to IEC/BS EN 60947-5-1

    Terminal Markings

    2 & 3 Pole

    O-I (900 indexing)

    1(L1) 3(L2) 5(L3)

    2(T1) 4(T2) 6(T3)

    6 Pole

    O-I (900 indexing)

    1 4 5 8 9 12

    2 3 6 7 10 11

    C/O (4 pole shown)

    I-O-II (900 indexing)

    Pol

    e 1

    Pol

    e 2

    Pol

    e 3

    Pol

    e 4

    1 4 5 8 9 12 13 16

    2 6 10 14

    ...products for the real world

    Encl

    osed

    Isol

    ator

    sTechnical Data for pages 3-11Technical Data

    Data supplied against tests to IEC/BS EN 60947-3 Rating

    Application Sym. Unit Category 20A 25A 32A 40A 63A 80A 100ASwitch product range - - GX20 CS25 CS32 GX40 CS40 CS40R CS63 CS80 CS100

    Rated thermal current Ithe A 20 25 32 40 40 40 63 80 100

    Rated insulation voltage Ui V 690 690 690 690 690 690 690 690 1000

    Rated impulse voltage Uimp kV 6 6 6 6 6 6 6 6 8.0

    Rated operational power (3 phase AC) Pe kW

    380/440 - AC23 7.5 11 15 18.5 18.5 15 25 30 59

    500V - AC23 7.5 15 15 15 22 15 30 37 63

    690V - AC23 7.5 15 15 15 22 15 30 30 51

    Rated short time withstand current (1 sec)

    Icw A 250 500 600 800 1100 600 1300 1400 2600

    Max. fuse size for short circuit protection (gG Characteristic)

    kA

    10kA 20 35 35 40 80 40 80 80 160

    25kA 16 32 32 35 80 32 63 63 160

    50kA - 32 32 - 80 32 63 63 160

    Recommended connecting capacity

    - Terminal type

    mm2 Flexible cable 2.5 x 2 6 6 6 x 2 16 6 16 16 50

    mm2 Rigid cable 2.5 x 2 10 10 10 x 2 25 10 25 25 70

    Nm Tightening torque 1.0 1.2 1.2 1.0 1.2 1.2 1.2 1.2 2

  • Page

    13

    Encl

    osed

    Isol

    ator

    s General DescriptionSupplied in hinged lid powder coated sheet steel and stainless steel enclosures these IP65 sealed assemblies are eminently suitable for most industrial indoor or outdoor applications.

    Supplied as Switch-Disconnectors, all items are supplied in generously sized enclosures which helps to avoid the need for extension boxes.

    The design offers a choice of accessories and options to match a variety of real world applications.

    Design Features Safety handle - when padlocked in the Off position, the

    enclosure door cannot be opened. Capable of accepting up to three padlocks in the Off position. (On position on request).

    Door interlock handle can be defeated to enable emergency opening or for testing purposes.

    Removable gland plates on top & bottom of all enclosures.

    Enclosure size 2 and above isolating switches are mounted on a removable galvanised chassis plate.

    IP65 Sheet steel, iron phosphate pre treatment with a powder coat RAL7035 (Grey) textured finish.

    IP65 Stainless steel enclosures, grade 304 with a brushed finish, for severe environments are available to order, please contact our Sales team for details.

    Removable gland plates are fitted to the top & bottom faces andemploy blind fixings that will maintain the IP sealing even if a gland plate fixing screw should be missed.

    Rating Format Sheet steel (Grey) Sheet steel (Red) Encl. Size

    63A3P+N SDG00633N SDR00633N 13P+NL SDG00633NL SDR00633NL 1

    6P+2E/B SDG00636EB SDR00636EB 2

    80A3P+N SDGC00803N SDRC00803N 13P+NL SDGC00803NL SDRC00803NL 1

    100A3P+N SDGC01003N SDRC01003N 3A3P+NL SDGC01003NL SDRC01003NL 3A

    125A3P+N SDGC01253N SDRC01253N 4A3P+NL SDGC01253NL SDRC01253NL 4A

    6P+2E/B SDGC01256EB SDRC01256EB 5A

    160A3P+N SDGC01603N SDRC01603N 4A3P+NL SDGC01603NL SDRC01603NL 4A

    200A3P+N SDGC02003N SDRC02003N 5A3P+NL SDGC02003NL SDRC02003NL 5A

    250A3P+N SDG02503N SDR02503N 53P+NL SDG02503NL SDR02503NL 5

    400A3P+N SDG04003N SDR04003N 63P+NL SDG04003NL SDR04003NL 6

    630A3P+N SDG06303N SDR06303N 83P+NL SDG06303NL SDR0603NL 8

    800A3P+N SDG08003N SDR08003N 83P+NL SDG08003NL SDR08003NL 8

    1000A3P+N SDG10003N SDR10003N 103P+NL SDG10003NL SDR10003NL 10

    Switch-Disconnectors* (O-I)

    Catalogue Numbers

    N = switched neutral (Early make, late break) NL = Unswitched neutral (50% rated, 100% on request)EB = Early break auxiliary contactsAdd /PE to include a multiple earth bar (i.e. SDR08003NL/PE)Add /10 to allow padlocking in both the Off & On positions (i.e. SDG02003N/10)

    Stainless steel enclosures are readily available based upon customer requirements. Please contact your Local Sales Manager for further details.

    Multi-padlock capacity available on all handles.

    Hinged Lid Sheet Steel

    DimensionsPg 20

  • www.craigandderricott.comPage

    14

    Data supplied against tests to BS EN 60947-3Rating (A)

    3P 3P 6P 3P 3P 3P 6P 3P 3P 3P 3P 3P 3P 3P

    Application Sym Unit Category 32 63 63 80 100 125 125 160 200 250 400 630 800 1000

    Rated thermal current Ithe A 32 63 63 80 100 125 125 160 200 270 500 630 720 1000

    Rated insulation voltage Ui V 690 690 690 690 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

    Rated impulse voltage Uimp kV 6 6 6 6 8 8 8 8 8 12 12 12 12 8

    Rated operational current (AC) Ie A

    Up to 415V - AC21A 32 63 63 80 100 125 125 160 200 250* 400* 630* 800* 1000*

    690V - AC21A 32 63 - 80 100 125 125 160 200 250 400 630 800 1000

    Up to 415V - AC22A 32 63 - 80 100 125 125 160 200 250* 400* 630* 800* 1000*

    690V - AC22A 32 63 - 80 100 125 125 160 160 250 400 630 800 -

    Up to 415V - AC23A 32 54 - 63 105 111 111 132 200* 250* 400* 630* 720* -

    690V - AC23A 17 33 - 33 53 57 57 57 57 250 350 350 350 -

    Rated operational current (DC) ( /poles in series)

    Ie A

    Up to 48V - DC21A 32/1 63/1 - 80/1 - - - - - 250/2 400/2 630/1 800/1 1000/1

    220V - DC21A 32/3 63/4 - 80/4 - - - - - 250/2 400/2 630/2 800/2 1000/3

    Up to 48V - DC22A - - - - - - - - - 250/2 400/1 630/1 800/1 -

    220V - DC22A - - - - - - - - - 250/2 400/2 630/2 800/2 -

    Up to 48V - DC23A - - - - - - - - - 250/2 400/1 630/1 800/1 -

    220V - DC23A - - - - - - - - - 250/2 400/2 630/2 630/2 -

    Rated operational power Pe kW

    400/415V - AC23A 15 25 25 30 59 63 63 75 75 132 200 315 355 400

    690V - AC23A 15 30 30 30 51 55 55 55 55 200 315 355 355 -

    Short circuit making capacity Icm kA Peak value 1.4 2.9 - 3.0 3.7 4.0 4.0 5.0 5.0 35 65 80 80 105

    Short circuit with-stand (1sec) Icw kA rms value 0.6 1.3 1.3 1.4 2.6 2.8 2.8 3.0 3.0 8 17 17 17 50

    Min. mechanical endurance - Operations (10

    3) 250 250 - 250 50 50 50 50 50 16 10 10 10 6

    Min. electrical endurance - 415V - at 0.65 pf - - - - - - - - - 1,000 1,000 500 500 500

    Connecting capacity

    - Terminal type

    mm2 Min/Max 2.5/10 2.5/25 2.5/25 -/25 -/70 -/70 -/70 -/70 -/95

    mm Stud/Cu palm width - - - - - - - - 8x25 10x30 10x30 12x40 12x40 12x60

    Nm Tightening torque 1.2 1.3 1.3 2 2 2 2 2 12 25 25 40 40 40

    Add-on auxiliary blocks are available for all IP65 products. All auxiliaries are supplied as 1 N/O+1 N/C pair.N/O contacts are early make, late break.

    Catalogue Numbers

    Rating (A) 63-200 250 400-800 1000

    Cat No SAUXCO SAUXKITB SAUXKITC SAUXKITD

    TYPE A C C B

    For Switch-Disconnectors

    Encl

    osed

    Isol

    ator

    s

    Hinged Lid Sheet Steel

    DimensionsPg 20

    Technical Specification - Switch-Disconnectors

    Spares / Accessories - Auxiliary Contacts

  • Page

    15

    Encl

    osed

    Isol

    ator

    s General Description Craig and Derricott have been supplying isolation equipment for the Ventilation Industry for more than 15 years. The F400 Fire Rated product is designed specifically for installations where the supply must be maintained for 2 hours at 400C.

    * Enclosure sizes from the Standard Hinged Lid range - see page 20.

    Fire Rated

    DimensionsPg 21

    The use of this switchgear range is to maintain power to vital equipment such as smoke extraction / ventilation fans allowing the safe evacuation of businesses, carparks and public areas.

    These switch-disconnectors are installed near to the extraction fan for isolation purposes, and has been tested in conjunction with the fan equipment to meet the stringent thermal requirements of BSEN 12101-3. All enclosures come standard with padlocking in both Off and On.

    The F300 Fire Rated product is designed for installations where the supply must be maintained for 1 hour at 300C.

    Rating Format Assembly Form (IP65)Catalogue No.(Finished Red)

    Temp. Class.

    Encl. size

    (IP65)

    20A

    2PLid mounted

    in sheet steel

    enclosure

    FSDMR0202

    F400 A

    3P FSDMR02033P+2EB Aux FSDMR0203EB

    3P+N FSDMR0203N4P FSDMR02046P FSDMR0206

    20A

    2PLid mounted in die-cast aluminiumenclosure

    FSDDR0202

    F400E

    3P FSDDR02033P+2EB Aux FSDDR0203EB

    3P+N FSDDR0203N4P FSDDR02046P FSDDR0206 B

    32A

    2P

    Lid mounted in die-cast aluminium enclosure

    FSDDR0322

    F400 B

    3P FSDDR03233P+2EB Aux FSDDR0323EB

    3P+N FSDDR0323N4P FSDDR03246P FSDDR0326

    6P+2EB Aux FSDDR0326EB8P FSDDR0328

    63A

    2P

    Base mounted in hinged lid sheet steel enclosure

    FSDMR0632

    F400 C

    3P FSDMR06333P+2EB Aux FSDMR0633EB

    3P+N FSDMR0633N4P FSDMR06346P FSDMR0636

    6P+2EB Aux FSDMR0636EB

    125A

    2P RS1BD11/HPHT

    F400 D

    3P RS1BT21/HPHT3P+2EB Aux RS1BT31/2EB/HPHT

    3P+N RS1BT21/HPHT/NL4P RS1BQ21HPHT6P RS1BY31/HPHT

    6P+2EB Aux RS1BY41/2EB/HPHT

    160A

    3P FSDMR1603

    F3004*

    4P FSDMR1604

    6P FSDMR1606 5*6P+2EB Aux FSDMR1606EB

    200A

    3P FSDMR2003

    F3005*3P+2EB Aux FSDMR2003EB

    4P FSDMR20046P FSDMR2006 7*6P+2EB Aux FSDMR2006EB

    250A

    3P FSDMR2503

    F3005*3P+2EB Aux FSDMR2503EB

    4P FSDMR25046P FSDMR2506 7*6P+2EB Aux FSDMR2506EB

    400A

    3P FSDMR4003

    F3006*3P+2EB Aux FSDMR4003EB

    4P FSDMR40046P FSDMR4006 9*6P+2EB Aux FSDMR4006EB

    630A

    3P FSDMR6303

    F3008*3P+2EB Aux FSDMR6303EB

    4P FSDMR63046P FSDMR6306 9*6P+2EB Aux FSMDR6306EB

    Catalogue Numbers

    N = Switched neutral (Early make, late break)EB = Early break auxiliary contacts

  • www.craigandderricott.comPage

    16

    Fire Rated

    Encl

    osed

    Isol

    ator

    sSpecificationWithin BS EN 12101-3: 2003 (Smoke and heat controls) there are different classes of duty which define a specific temperature gradient, upper temperature limit and time period.

    F300 300oC for 60 min.

    F400 400oC for 120 min.

    Data supplied against tests to IEC/BS EN 60947-3Application Sym. Unit Category 20A 32A 63A 125A 160A 200A 250A 400A 630A

    Rated thermal current Ithe A 20 32 63 125 160 200 250 400 630

    Rated insulation voltage Ui V 690 690 690 690 750 1000 1000 1000 1000

    Rated impulse voltage Uimp kV 6.0 6.0 6.0 6.0 12.0 12.0 12.0 12.0 12.0

    Rated operational power (3 phase AC)

    Ie / PeA/kW

    415V - AC23A 20/9.5 32/15 40/18.5 100/55 100/45 200/110 250/132 400/200 630/315

    690V - AC23B 20/9.5 20/9.5 20/9.5 - 63/45 200/170 250/200 350/315 350/355

    660V - AC23B - - - 30/22 - - - - -

    Short circuit withstand (1 sec) Icw kA RMS value

    - - - 1.5 5.0 8.0 8.0 17.0 17.0

    Conditional Short Circuit Current

    FusegG kA/

    Fuse(A)415V 50/32 50/32 50/63 50/200 50/160 50/200 50/250 -

    690V 40/32 40/32 40/63 50/63 50/63 50/200 50/250 50/400 100/630

    Recommended connect-ing capacity

    - Terminal type

    mm2 Flexible cable 4.0 6 16 50 95 95 120 2/150 2/185

    mm2 Rigid cable 4.0 10 25 50 95 95 120 2/150 2/185

    Nm Tightening torque 1.2 1.2 3.0 12.0 8.0 8.0 8.0 17.0 21.0

    DimensionsPg 21

    Technical Specification

  • Page

    17

    Background London Underground Limited (LUL) Section 12 Equipment

    Following the London Kings Cross fire of 1987, the resulting Fennell enquiry prompted the introduction of additional fire precautions for Sub-surface Railway Stations. These additional requirements were introduced under section 12 of the Fire Precautions Act 1971, and since then have been known simply as Section 12 regs.

    The forensic report on the fire sited several instances of a flash over effect caused by materials and paint finishes being ignitable. Exacerbating the conditions underground were toxic fumes given off by certain materials being excessively heated.

    Although the new regulations dealt with all aspects of fire prevention such as the removal of wooden escalators, the installation of heat detectors, improved staff training etc, as far as actual equipment supplied for underground use, the overriding emphasis was on materials and paint finishes.

    With this isolation range, the overall consideration has been to meet, and where possible exceed, the Section 12 requirements. This has been achieved by the careful selection of individual component materials and the use of only recognised and approved paint finishes.

    Rating Format

    Interior Switch product range

    Catalogue Nos.Enclosure

    SizeGrey Red

    25A

    2P GN25 DCG252LUL10 DCR252LUL10

    A(IP65)

    3P GN25 DCG253LUL10 DCR253LUL103P+2EB Aux GN25 DCG253EBLUL10 DCR253EBLUL10

    4P GN25 DCG254LUL10 DCR254LUL106P GN25 DCG256LUL10 DCR256LUL10

    6P+2EB Aux GN25 DCG256EBLUL10 DCR256EBLUL10

    40A

    2P R32 DCG402LUL10 DCR402LUL10

    B(IP65)

    3P R32 DCG403LUL10 DCR403LUL103P+2EB Aux R32 DCG403EBLUL10 DCR403EBLUL10

    4P R32 DCG404LUL10 DCR404LUL106P R32 DCG406LUL10 DCR406LUL10

    6P+2EB Aux R32 DCG406EBLUL10 DCR406EBLUL10

    To order a neutral link please include in the catalogue ref. as follows:-Example - 3 Pole + Neutral Link - DCG403NLLUL10

    Switch-Disconnectors (O-I)

    Electrical ratings to BS EN 60947-3

    Application Sym Unit Category Rating

    Rated thermal current Ithe A - 25A 40A

    Rated operational power (3 phase AC) - kW

    380/440VAC23A 11.0 15.0

    Die-Cast Enclosures

    Encl

    osed

    Isol

    ator

    s

    Catalogue Numbers

    EB = Early break auxiliary contacts

    LUL Section 12 Equipment

    DimensionsPg 22

    Design Features

    Technical Specification

    * Replaced by the current regulations:- The Fire Precautions (Sub-surface Railway Stations (England) Regulations 2009.

    Paint Finishes:- LU1-085 Compliant Paint Finish Colour - Light Grey (RAL7035) Traffic Red (RAL3020) Captive lid fixing screws with a security head. Enclosure material - Aluminium (LM6) Sealing to IP65. Supplied with pre-finished steel mounting brackets. Padlocking cast lever handle. Positive break contacts. Earthing points on both lid and base plus external earth stud. Padlocking in both Off & On. Second product label supplied loose for fitting by the contractor where the original label may be obscured. Labels - Engraved traffolyte labels in various colours can be supplied attached to the side of the enclosure or supplied loose for fitting adjacent to the isolator.

    LUL Product Registration Certificate Nos. 638 & 639 Status - Authorised for use.

  • www.craigandderricott.comPage

    18

    Stainless Steel Enclosures

    Lid mounted switch interiors. Captive lid fixing screws with a security head. Enclosure material - 18 gauge stainless steel grade 304. Finish - Natural - Brushed (Non glare) Sealing to IP65. Supplied with stainless steel mounting brackets. Padlocking cast lever handle. Positive break contacts. Earthing points on both lid & base plus external earth stud. Padlocking in both Off & On. Second product label supplied loose for fitting by the contractor where the original label may be obscured. Labels - Engraved traffolyte labels in various colours can be supplied attached to the side of the enclosure or supplied loose for fitting adjacent to the isolator.

    LUL Product Registration Certificate Nos. 638 & 639 Status - Authorised for use.

    To order a neutral link please include in the catalogue ref. as follows:- Example - 3 Pole + Neutral Link - DS253NLLUL10

    Rating Format

    Interior Switch product range

    Catalogue Nos.Enclosure

    SizeStainless steel

    25A

    2P GN25 DS252LUL10

    C(IP65)

    3P GN25 DS253LUL103P+2EB Aux GN25 DS253EBLUL10

    4P GN25 DS254LUL106P GN25 DS256LUL10

    6P+2EB Aux GN25 DS256EBLUL10

    40A

    2P GN40 DS402LUL10

    D(IP65)

    3P GN40 DS403LUL103P+2EB Aux GN40 DS403EBLUL10

    4P GN40 DS404LUL106P GN40 DS406LUL10

    6P+2EB Aux GN40 DS406EBLUL10

    Switch-Disconnectors (O-I)

    Encl

    osed

    Isol

    ator

    s

    Electrical ratings to BS EN 60947-3

    Application Sym Unit Category Rating

    Rated thermal current Ithe A - 25A 40A

    Rated operational power(3 phase AC) - kW

    380/440VAC23A 11.0 18.5

    Hinged Lid Enclosures

    RatingCatalogue Nos. Enclosure

    SizeGrey Red

    40A DCG0403LUL DCR0403LUL 1

    63A DCG0633LUL DCR0633LUL 1

    80A DCG0803LUL DCR0803LUL 2

    100A DCG1003LUL DCR1003LUL 2

    125A DCG1253LUL DCR1253LUL 2A

    160A DCG1603LUL DCR1603LUL 2A

    200A DCG2003LUL DCR2003LUL 3

    250A DCG2503LUL DCR2503LUL 3

    315A DCG3153LUL DCR3153LUL 4

    400A DCG4003LUL DCR4003LUL 4

    Switch-Disconnectors (O-I)

    Catalogue Numbers

    Catalogue Numbers

    EB = Early break auxiliary contacts

    Rating Rated Thermal Current Ith

    Rated operational Power PekW (400V - AC23A)

    40A 40A 18.563A 63A 2580A 80A 40100A 100A 40125A 125A 63160A 160A 80200A 200A 100250A 250A 132315A 315A 160400A 400A 220

    Electrical ratings to BS EN 60947-3

    LUL Section 12 Equipment

    DimensionsPg 22

    Design Features

    Design Features

    Technical Specification

    Technical Specification

    Ratings 40A - 400A (3P + switched N). Grey or Traffic Red LU1-085 Compliant Paint Finish. All metal padlocking handle. Can be supplied lockable in both Off & On. Removable top & bottom gland plates. Sealing to IP65.LUL Product Registration Certificate No. 3062 Status - Authorised for use.

  • Page

    19

    Overall Dims. Fixing detailsH W D F1 F2

    Size A 135 100 95 85 98.5 5.5Size B 175 130 115 115 135 5.5Size C 255 180 125 163.5 238.5 4.5Size D 255 180 175 163.5 238.5 4.5

    W D

    H

    F1

    F2

    40

    4 x Fixings ()

    Sizes C & D

    W D

    H

    30F1

    F2

    4 x

    Fixi

    ngs

    ()

    SizesA & B

    1

    Dimensions & Fixings

    Overall Dims. Internal Fixings External Fixings

    H W D F1 F2 F3 F4 F5

    Size A 135 100 80 51 86 5.5 126 140 16 6.35

    Size B 175 130 100 81 126 5.5 155 178 16 6.35

    Stainless steel enclosures are supplied without raised dimples to allow flush mounting.

    Employing external mounting straps EFA or EFB.

    * 62 when using Defeatable Door Interlock Handle

    4 x

    Inte

    rnal

    Fixi

    ngs

    ()

    4 x

    Exte

    rnal

    Fixi

    ngs

    (

    )

    *

    Encl

    osed

    Isol

    ator

    s

    Size A Size B

    Overall Dims.

    H1 200 240

    H2 165 200

    W 135 185

    D 80 100

    D2 127 147

    Internal Fixings

    FCH 70 90

    FCV 110 130

    5.5 5.5

    125 sq100 sq

    75 40175 sq150 sq 40*

    Size B

    Size C

    = 75*

    = 100*

    Size A

    Plastic Enclosed

    Mild Steel & Stainless Steel Enclosed

    Sloping Roof Stainless Steel Enclosed

    Flush Mounting Stainless Steel

  • www.craigandderricott.comPage

    20

    4 off internal mounting holes

    D BW

    A H

    Gland plate thickness (K)

    Han

    dle

    proj

    ectio

    n

    C

    J (C

    RS

    )

    F G (CRS)

    E

    Size A

    Entries style X

    Entries style YEntries as shown repeatedon top face of enclosure.

    2 Holes M25 x 1.5 Through

    Size B

    Entries style X

    Entries style YEntries on top and bottom of enclosure as shown.

    Three entries on bottom face of enclosure only.

    Dimensions & Fixings

    Encl

    osed

    Isol

    ator

    sMaterialIP65 Sheet steel, iron phosphate pre treatment with a powder coat textured finishIP65 Stainless Steel, grade 304 with a brushed finished

    Hinges Metal with quick release pins.

    Door Locks All metal locks supplied with one key per enclosure.Enclosures 1 & 2 IP65 - 1 lockEnclosures 3 - 9 IP65 - 2 locksEnclosures 10 IP65 - 3 locks

    Gland plates All enclosures are supplied with a removable gland plate on top & bottom faces finished to match the enclosure.

    Chassis plate Above enclosure size 1, all assemblies have the switching element mounted on a removable chassis plate. Matl. - 2mm zinc plated steel.

    Dim 1 2 3 3A 4 4A 5 5A 6 7 8 10

    H 250 250 400 350 500 400 550 550 750 750 900 1000

    W 250 300 350 300 350 300 450 400 450 600 600 750

    D 100 200 200 175 200 175 250 175 275 300 300 300

    A 170 170 320 270 420 320 470 470 670 670 820 920

    B 170 220 270 220 270 220 370 320 370 520 520 670

    C 40 67 67 67 67 67 67 67 67 67 67 67

    K 1.5 1.5 1.5 2.0 1.5 2.0 2.0 2.0 2.0 2.5 2.5 2.5

    6.5 6.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 10.5 10.5

    E 35 35 35 35 35 35 35 35 35 35 35 35

    F 53 58 58 58 58 58 58 58 58 58 58 58

    G 18 18 13 13 13 13 13 13 13 13 13 13

    J 58 58 58 58 58 58 58 58 58 58 58 58

    6.5 6.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 10.5 10.5

    Enclosure Sizes

    External Feet

    External Mounting Feet (Four per set)Case Sizes 1 & 2 Cat No. SEFL1/KITCase Sizes 3 - 7 Cat No. SEFL2/KITCase Sizes 8 - 10 Cat No. SEFL3/KIT

    Die-Cast Enclosed

    Hinged Lid Sheet Steel

  • Page

    21

    Size C

    Size D

    Size B

    Dimensions & FixingsEn

    clos

    ed Is

    olat

    ors

    Size E

    Size A

    Fire Rated (High Temperature)

  • www.craigandderricott.comPage

    22

    CASTELL LOCKPOSITION

    Enclosure finished with an approved paint system and sealed to IP65

    Overall Depth 140

    40A Die cast Aluminium Enclosure (B)

    40A Stainless Steel Enclosure (D)

    4 x M6 fixings

    25A Die cast Aluminium Enclosure (A)

    148 CRS

    110 SQ

    90 C

    RS

    25A Stainless Steel Enclosure (C)

    4 x M6 fixings

    3M ScotchKote EA9WB painted handle

    Dimensions & Fixings

    Encl

    osed

    Isol

    ator

    s

    LUL Section 12 Equipment

    Hinged Lid

  • Page

    23

    General DescriptionCraig & Derricott has been associated with the design and manufacture of Ex products for more than 30 years.

    The EXZ1 range of enclosed switch-disconnectors are supplied in EX e enclosures manufactured from glass reinforced polyester sealing to IP65 ensuring the product will withstand being installed in the harshest of industrial environments.

    The operating handles are available in Red/Yellow or Black and can be padlocked in the Off position. All lids are mechanically interlocked with the isolating switch and are removable in the On position only.

    Available in ratings from 20A - 150A the isolating switch interiors are supplied in either 3 or 4 pole formats complete with 1 N/O (Early break) & 1 N/C (Late make) auxiliary contacts.

    Rating Format Handle Colour Cat. No. Enclosure Size

    20A3P+Aux

    Red/Yellow EXZ1SDR0203

    ABlack EXZ1SDB0203

    4P+AuxRed/Yellow EXZ1SDR0204

    Black EXZ1SDB0204

    32A3P+Aux

    Red/Yellow EXZ1SDR0323

    BBlack EXZ1SDB0323

    4P+AuxRed/Yellow EXZ1SDR0324

    Black EXZ1SDB0324

    63A3P+Aux

    Red/Yellow EXZ1SDR0633

    CBlack EXZ1SDB0633

    4P+AuxRed/Yellow EXZ1SDR0634

    Black EXZ1SDB0634

    150A 3P+AuxRed/Yellow EXZ1SDR1503

    DBlack EXZ1SDB1503

    Aux - 1 N/O (Early break) & 1 N/C (Late make)

    Encl

    osed

    Isol

    ator

    s

    CertificationAll items have been approved with ATEX (Sira 13ATEX3205X) and IECEx (IECEx SIR 13.0076X) certicates for use in Zones 1 & 2.

    The equipment is designed and tested to comply with the following:-

    EN 60079-0 Electrical Atmospheres, Part 0 : Equipment - General requirements. EN 60079-1 Electrical Atmospheres, Part 1 : Equipment protection by flameproof enclosures d. EN 60079-7 Electrical Atmospheres, Part 7 : Equipment protection by increased safety e. EN 60947-1 Low-Voltage switch gear and controlgear - Part 1:general rules. EN 60947-3 Low-Voltage switch gear and controlgear -Part 3:switches, disconnectors, switch-disconnectors and fuse combination units. EN 60529 Degrees of protection provided by enclosures. (IP Code)

    Natural brass Earthing Plate shown with glands fitted (Glands not supplied)

    Catalogue Numbers

    Ex IECEx/ATEX Zone 1 & 2 Isolators

    DimensionsPg 25

  • www.craigandderricott.comPage

    24

    Equipment Marking

    20A II 2 G Ex e d IIC T4 Gb - (-40oC Ta +40oC)

    32A II 2 G Ex e d IIC T6 Gb - (-40oC Ta +40oC)

    63A II 2 G Ex e d IIC T6 Gb - (-40oC Ta +40oC)

    150A II 2 G Ex e d IIC T5 Gb - (-40oC Ta +30oC)

    Ex e d IIC T6 Gb

    Equipment protection level Temperature class Gas group Protection method - Increased safety e Flameproof d Explosion protection

    Key to MarkingSpecific marking for Explosion protection

    Equipment groupEquipment categoryEnvironment e.g. Gas

    II2G

    Encl

    osed

    Isol

    ator

    s

    Application Sym. Unit CategoryMain Contacts Aux. Contacts

    20A 32A 63A 150A Category Aux.

    Rated thermal current Ithe A 20 32 63 150 10

    Rated insulation voltage Ui V 690 690 690 690 690

    Rated current - A

    AC3 (230V) 20 32 63 150 AC15 (250V) 10

    AC3 (400V) 20 32 63 150 AC15 (400V) 8

    AC3 (500V) 20 32 63 150 DC13 (24V) 8

    AC3 (690V) 16 32 63 125 DC13 250V) 1

    Terminal Capacity - 2x6mm2 2x16mm2 2x35mm2 2x95mm2 2x6

    Tightening Torque (Nm) - 1.2 2.5 3 6 1.2

    Terminal Type -

    Enclosure Size

    A B C D

    Brass (Natural) EXZ1EPA1 EXZ1EPB1 EXZ1EPC1 EXZ1EPD1

    Brass (Electroless Nickel Plated EXZ1EPA2 EXZ1EPB2 EXZ1EPC2 EXZ1EPD2

    Connection Terminal M4 M5 M6 M8

    Earthing PlatesTo enable armoured cables to be eartyh bonded within the insulated enclosure a selection of pre-drilled earthing plates are available for each enclosure size.

    Supplied in either natural or electroless Nickel plated brass.

    Ex IECEx/ATEX Zone 1 & 2 Isolators

    DimensionsPg 25

    Technical Specification - Switch-Disconnector Main Contacts

  • Page

    25

    Enclosure C Enclosure D

    Encl

    osed

    Isol

    ator

    s

    Enclosure A Enclosure B

    Ex IECEx/ATEX Zone 1 & 2 Dimensions

  • www.craigandderricott.comPage

    26

    General DescriptionA range of Switch-Disconnectors housed in heavy duty cast enclosures - ATEX certified for use in Cat II, Zones 1, 2, 21 & 22 environments.

    Certifications and Approvals

    Certification Code Ex d II 2 GD IIB T6 Certification No. ITS 09 ATEX 16433X, ITS 09 ATEX 16436U Certification standard EN 60079-0, EN 60079-1, EN 61241-0 & EN 61241-1 Operating temperature -20oC to +40oC Ingress Protection IP65

    High quality heavy duty cast enclosures are used throughout the range. (Cast Iron 16A - 63A, Cast Aluminium 80A - 250A).

    The enclosures are supplied with large cable entries which can be fitted with approved reducers to suit individual cable requirements. All load switching interiors are supplied as either 3P+N (switched neutral) or 6P and have AC23A ratings to BS EN 60947-3. Auxiliary contacts are available for applications such as SCADA packages.

    Operating handles are capable of accepting up to three padlocks in the Off position. Finish - RAL 7035 Two pack grey epoxy coating over etching primer.

    Encl

    osed

    Isol

    ator

    s

    Ex ATEX Zone 1/21 & 2/22 Isolators

    DimensionsPg 27

    Rating (A)

    16A 20A 25A 40A 63A 80A 100A 125A 250A

    Application Sym. Unit Category 3P 6P 3P 6P 3P 3P 3P 3P 3P 3P

    Enclosure - - - G21 G21 G21 G22 G22 G22 G24 G25 G25 G28

    Rated thermal current Ithe A - 16 20 25 40 40 63 80 100 125 250

    Rated insulation voltage Ui V - 690 690 690 690 690 690 690 750 750 1000

    Rated impulse voltage Uimp kV - 6.0 6.0 6.0 6.0 6.0 6.0 6.0 8.0 8.0 12.0

    Rated opertaional power (3 phase AC) Pe kW

    380/440V - AC23 7.5 7.5 11.0 18.5 18.5 25.0 30.0 37.0 45.0 132.0

    500V - AC23 9.0 7.5 15.0 15.0 22.0 30.0 37.0 - - -

    690V - AC23 9.0 7.5 15.0 15.0 22.0 30.0 30.0 37.0 45.0 200.0

    Rated short time withstand current (1 sec) Icw A 400 250 500 800 1100 1300 1400 2500 2500 8000

    Max. fuse size for short circuit protection (gG characteristic) In A

    10kA 32 20 35 40 80 80 80 - - -

    25kA 31 16 32 35 63 63 63 - - -

    50kA 32 - 32 - 63 63 63 - - -

    Connecting capacity

    - Terminal type

    mm2 Flexible cable 6.0 2x2.5 6.0 2x6.0 16.0 16.0 16.0 - - -

    mm2 Rigid cable 10.0 2x2.5 10.0 2x10 25.0 25.0 25.0 - - -

    mm Stud Cu palm width - - - - - - - 8x20 8x20 10x30

    Nm Tightening torque 1.2 1.2 1.2 1.2 1.2 1.2 1.2 6.0 8.0 30-44

    Technical Specification

  • Page

    27

    DimensionsEnclosure Material A B C D E F G Weight (Kg)

    G21 Fe 180 155 145 130 195 7.0 100 9

    G22 Fe 205 220 156 160 230 9.0 117 19

    G24 Al 321 361 228 291 320 11.0 179 21

    G25 Al 366 406 218 250 370 11.0 177 25

    G28 Al 586 690 294 480 580 14.0 216 96

    A Enclosure Width D Fixing Centre Height B Enclosure Height E Fixing Centre WidthC Enclosure Depth F Fixing Hole Diameter G Internal Depth from Base Plate

    N.B. Enclosures can be close coupled at either end (To special order)

    Encl

    osed

    Isol

    ator

    s

    Current Rating (A) Format Catalogue No.

    Enclosure Ref. Supplied Entries*

    External Earth

    16 3P+N+2E/B DGC0164EBZ1 G21 3 x M20 M625 3P+N+2E/B DGC0254EBZ1 G21 4 x M20 M620 6P + 2E/B DGC0206EBZ1 G21 2 x M25 + 1 x M20 M640 3P+N+2E/B DGC0404EBZ1 G22 2 x M25 + 1 x M20 M840 6P + 2E/B DGC0406EBZ1 G22 2 x M25 + 1 x M20 M863 3P+N+2E/B DGC0634EBZ1 G22 2 x M25 + 1 x M20 M880 3P+N+2E/B DGC0804EBZ1 G24 3 x M32 + 1 x M20 M8

    100 3P+N+2E/B DGC1004EBZ1 G25 3 x M32 + 1 x M20 M8125 3P+N+2E/B DGC1254EBZ1 G25 3 x M40 + 1 x M20 M8160 3P+N+2E/B DGC1604EBZ1 G25 2 x M32 + 1 x M20 M8200 3P+N+2E/B DGC2004EBZ1 G28 3 x M50 + 1 x M20 M10250 3P+N+2E/B DGC2504EBZ1 G28 3 x M50 + 1 x M20 M10

    * Other entry configurations available on request.

    Catalogue Numbers

    N = Switched neutral (Early make, late break)EB = Early break auxiliary contacts

    Ex ATEX Zone 1/21 & 2/22 Isolators

    Dimensions

  • www.craigandderricott.comPage

    28

    Encl

    osed

    Isol

    ator

    sGeneral Description To complement the F300 / F400 fire rated switch-disconnector range described on page 15-16, Craig and Derricott have introduced the F200 Fire Rated isolator for installations where the supply must be maintained for 2 hours at 200C.The use of this product is to maintain power to vital equipment such as smoke extraction / ventilation fans allowing the safe evacuation of businesses, carparks and public areas.

    These switch-disconnectors are installed near to the extraction fan for isolation purposes, and has been tested in conjunction with the fan equipment to meet the stringent thermal requirements of BSEN 12101-3. These base mounted enclosures come standard in a red (RAL 3020) colour finish, with padlocking in both Off and On position.

    Die-cast aluminium enclosures - Sealing to IP66 Hinged lid enclosures - Sealing to IP65

    Rating FormatInterior Switch Product Range

    Catalogue No.(Finished Red)

    Temp. Class.

    Encl. size

    20A6P

    GX20F2SDDR206X

    F200 A6P+2EB Aux F2SDDR206EBX

    25A

    2P

    CS25

    F2SDDR252X

    F200 A3P F2SDDR253X

    3P+2EB Aux F2SDDR253EBX3P+N F2SDDR253NX3P+NL F2SDDR253NLX

    32A

    2P

    CS32

    F2SDDR322X

    F200 A3P F2SDDR323X

    3P+2EB Aux F2SDDR323EBX3P+N F2SDDR323NX3P+NL F2SDDR323NLX

    40A

    2P

    CS40R

    F2SDDR402X

    F200 A

    3P F2SDDR403X3P+2EB Aux F2SDDR403EBX

    3P+N F2SDDR403NX3P+NL F2SDDR403NLX

    6PGX40

    F2SDDR406X6P+2EB Aux F2SDDR406EBX

    2P

    CS40

    F2SDDR402TX

    F200 B3P F2SDDR403TX

    3P+2EB Aux F2SDDR403EBTX3P+N F2SDDR403NTX3P+NL F2SDDR403NLTX

    63A

    2P

    CS63

    F2SDDR632X

    F200 B3P F2SDDR633X

    3P+2EB Aux F2SDDR633EBX3P+N F2SDDR633NX3P+NL F2SDDR633NLX

    80A3P

    CS80

    F2SDDR803X

    F200 B3P+N F2SDDR803NX3P+NL F2SDDR803NLX

    Catalogue Numbers

    Rating FormatInterior Switch Product Range

    Catalogue No.(Finished Red)

    Temp. Class.

    Encl. size

    63A3P+N

    CS63F2SDRC00633N

    F200 13P+NL F2SDRC00633NL

    80A3P+N

    CS80F2SDRC00803N

    F200 13P+NL F2SDRC00803NL

    100A3P+N

    CS100F2SDRC01003N

    F200 3A3P+NL F2SDRC01003NL

    125A3P+N

    CS125F2SDRC01253N

    F200 4A3P+NL F2SDRC01253NL

    160A3P+N

    CS160F2SDRC01603N

    F200 4A3P+NL F2SDRC01603NL

    200A3P+N

    CS200F2SDRC02003N

    F200 5A3P+NL F2SDRC02003NL

    Catalogue Numbers

    Fire Rated

    TechnicalData

    Pg 12+14

    DimensionsPg 20

    For top and bottom cable entires, please replace X with Y in the catalogue number i.e. F2SDDR206Y

    N = Switched neutral (Early make, late break)NL = Unswitched neutralEB = Early break auxiliary contactsT = Increased terminal capacityX = Bottom cable entries only

  • Page

    29

    General Description Craig & Derricott has ranges of compact control panel isolation equipment for panel mounting ranging from 25A to 200A. All come supplied with operating handle and a standard length shaft.

    A compact range of switch-disconnectors with the capacity to add auxiliary and neutral block options to the basic load break switch block.

    Features IP2X terminal protection. Door interlock handles with override facility. DIN rail or base mounting. Add-on auxiliary/neutral blocks.

    The catalogue numbers below include:- On-load AC23A switch-disconnector. 100mm standard length shaft assembly. IP65 minimum door interlock handle.(Black) Terminal covers (A2 frame size only).

    Extended shaftsBoth the standard 100mm shaft and the longer version as shown below can easily be adjusted to suit specific panel depths. The correct dimension to be removed (X) can easily be determined using the dimensions shown on page 34-35.

    63A 3P assembly complete with standard shaft and handle assembly.

    The standard 100mm option shown.

    Handle assembly supplied with the A0 & A1 frame sizes (SDH1/BLK).

    Handle assembly supplied with the A2 & A3 frame sizes (SDH3/BLK).

    Includes emergency override facility.

    Pane

    l Iso

    lato

    rs

    Shaft length L Frame size Shaft (mm2) Catalogue No.200mm AO & A1 6 SSH2200mm A2 & A3 8 SSH17

    Catalogue Numbers

    Compact Panel Isolators 25A - 200A

    Technical DataPg 33

    DimensionsPg 34

    Catalogue NumbersCurrent

    Rating (A) Format Catalogue NumberFrame Size

    25A

    2P SD00252B

    A03P SD00253B

    3P+N SD00253NB3P+NL SD00253NLB

    6P SD00256B

    32A

    3P SD00323B

    A03P+N SD00323NB3P+NL SD00323NLB

    6P SD00326B

    40A

    3P SD00403B

    A03P+N SD00403NB3P+NL SD00403NLB

    6P SD00406B

    63A

    3P SD00633B

    A13P+N SD00633NB3P+NL SD00633NLB

    6P SD00636B

    80A

    3P SD00803B

    A13P+N SD00803NB3P+NL SD00803NLB

    6P SD00806B

    100A

    3P SDC01003B

    A23P+N SDC01003NB3P+NL SDC01003NLB

    6P SDC01006B

    125A

    3P SDC01253B

    A23P+N SDC01253NB3P+NL SDC01253NLB

    6P SDC01256B6P+2EB Aux SDC01256EB

    160A

    3P SDC01603B

    A23P+N SDC01603NB3P+NL SDC01603NLB

    6P SDC01606B6P+2EB Aux SDC01606EB

    200A3P SDC02003B/ETC

    A36P SDC02006B/ETC

    B = Black Handle. For Red Handle, replace B with R in the catalogue number. i.e. SD00253RNB = Switched neutral (Early make, late break) with Black HandleNLB = Unswitched neutral with Black HandleETC = Excluding Terminal Covers

  • www.craigandderricott.comPage

    30

    Assembly of SDH1/BLK handle and SSH1/2 shaft assembly

    Neutral Link 2 Early Break Neutral Link (Unswitched) Auxiliary (Switched)

    Description Cat. No.

    Auxiliary Contact - 2 Early Break SAUX2EB

    Auxiliary Contact - 1 N/O + 1 N/C SAUXCO

    25A Neutral (Unswitched) SNL25

    40A Neutral (Unswitched) SNL40

    63A Neutral (Unswitched) SNL63

    80A Neutral (Unswitched) SNL80

    100A Neutral (Unswitched) SNL100

    125A Neutral (Unswitched) SNL125

    160A Neutral (Unswitched) SNL160

    200A Neutral (Unswitched) SNL200

    25A Neutral (Switched) SSP25

    40A Neutral (Switched) SSP40

    63A Neutral (Switched) SSP63

    80A Neutral (Switched) SSP80

    100A Neutral (Switched) SSP100

    125A Neutral (Switched) SSP125

    160A Neutral (Switched) SSP160

    200A Neutral (Switched) SSP200

    Auxiliary BlocksAll of the accessories listed below can be retro-fitted. One block can be fitted either side of the main assembly on all of the 3 pole switch-disconnector interiors.

    SAUXCO

    SSP63

    63A Switch-Disconnector fitted with Aux blocks

    Typical 40A 6 pole assembly

    Pane

    l Iso

    lato

    rs

    Catalogue Numbers

    Compact Panel Isolators 25A - 200A

    Technical DataPg 33

    DimensionsPg 34

    Accessories

  • Page

    31

    General Description A robust range of load break switches to ensure simple installation in applications such as power distribution boards. The compact design also suits OEMs and stand alone enclosure installations. A range of accessories extends the versatility.

    Alternative shafts As an alternative to the standard 200mm shaft a 400mm option is available as indicated below. The shafts are manufactured from square section steel and zinc plated. The height setting is adjusted by passing the shaft through a bush in the switch mechanism and locking it in position using two cup point grub screw.

    Catalogue Numbers Load break switch current RatingShaft length L 100A - 160A 200A - 250A 400 - 1000A

    400mm SSH13 SSH14 SSH15Drive Shaft Section 6mm2 8mm2 12mm2

    Max. possible enclosure depth

    200mm 250 270 285

    400mm 450 470 485

    L

    Handle assembly supplied with the B2 frame size(SDH3BLK).

    Handle assembly supplied with the B3 (SDH4/BLK) & B4 (SDH7/BLK) frame sizes

    Pane

    l Iso

    lato

    rs

    Features:- On-load AC23A ratings. Four frame sizes covering 100A - 1000A. Direct lug connections onto plated Copper palms. Windows for contact inspection Supplied as either 3 or 4 pole versions. IP65 sealing door interlocking handles. Internal locking feature.

    The catalogue numbers below include:- On-load AC23A switch-disconnector. 200mm standard length shaft assembly. IP65 door interlock handle.(Black).

    Standard Panel Isolators 100A - 1000A

    Technical DataPg 33

    DimensionsPg 35

    Catalogue NumbersCurrent

    Rating (A) Format Catalogue NumberFrame Size

    100A3P SD01003B/ETC

    B13P+NL SD01003NLB/ETC4P SD01004B/ETC

    125A3P SD01253B/ETC

    B13P+NL SD01253NLB/ETC4P SD01254B/ETC

    160A3P SD01603B/ETC

    B13P+NL SD01603NLB/ETC4P SD01604B/ETC

    200A

    3P SD02003B/ETC

    B23P+NL SD02003NLB/ETC

    4P SD02004B/ETC6P SD020006B/ETC

    250A

    3P SD02503B/ETC

    B23P+NL SD02503NLB/ETC

    4P SD02504B/ETC6P SD02506B/ETC

    315A3P SD03153B/ETC

    B36P SD03156B/ETC

    400A

    3P SD04003B/ETC

    B33P+NL SD04003NLB/ETC

    4P SD04004B/ETC6P SD04006B/ETC

    630A3P SD06303B/ETC

    B33P+NL SD06303NLB/ETC4P SD06304B/ETC

    800A3P SD08003B/ETC

    B33P+NL SD08003NLB/ETC4P SD08004B/ETC

    1000A3P SD10003B/ETC

    B44P SD10004B/ETC

    B = Black Handle. For Red Handle, replace B with R in the catalogue number. i.e. SD00253RNB = Switched neutral (Early make, late break) with Black HandleNLB = Unswitched neutral with Black HandleETC = Excluding Terminal Covers

  • www.craigandderricott.comPage

    32

    Auxiliary Contacts Add-on auxiliary contacts are available for the 100A - 1000A range and can be selected from the table below. All auxiliary kits contain the necessary fixings and attachments to install the contact blocks which are supplied in 1 N/O + 1 N/C format. All N/O contacts are early break with respect to the main poles when switching from On to Off.

    Load break switch ratingRating (A) 100 - 160A 250A 400 - 800A 1000A

    Catalogue No. SAUXKITA SAUXKITB SAUXKITC SAUXKITDBlock type B C C B

    Contact block types

    SDH1 Handle (A0 & A1)

    Panel drilling

    SDH3/4/7 Handles Panel drilling

    Handle Shaft sectionDimension

    YIsolator Frame

    Sizes

    SDH3 8mm2 80mm A2, A3, B1 & B2

    SDH4 12mm2 146mm B3

    SDH7 12mm2 220mm B4

    Aux. contact block

    Sym. Category Auxiliary blocks type B Auxiliary blocks type CThermal current Ithe 10A 10ARated insulation voltage Ui 660V a.c. or d.c. 690V a.c.Utilisation Category - AC15 6.0A at 120V, 4.0A at 250V, 2.0A at 660V 4.0A at 240V

    DC13 1.0A at 120V, 0.5A at 240V, 0.1A at 660V 1.0A at 120VPure Resistive 10A -

    Auxiliary Contacts Type A - Data supplied against tests to BS EN 60947-1

    B C Pane

    l Iso

    lato

    rs

    Standard Panel Isolators 100A - 1000A

    Technical DataPg 33

    DimensionsPg 35

    Accessories

    Dimensions

  • Page

    33

    * All

    AC

    21, A

    C22

    & A

    C23

    test

    s ca

    rrie

    d ou

    t at 4

    15V

    Pane

    l Iso

    lato

    rsPanel Isolators Technical Data

    Technical Specification - Switch-DisconnectorsD

    ata

    supp

    lied

    agai

    nst t

    ests

    to B

    S E

    N 6

    0947

    -3

    Com

    pact

    Pan

    el Iso

    lator

    s 25A

    - 20

    0ASt

    anda

    rd P

    anel

    Isolat

    ors 1

    00A

    - 100

    0A

    App

    licat

    ion

    Sym

    Uni

    tC

    ateg

    ory

    2532

    4063

    8010

    012

    516

    020

    010

    012

    516

    020

    025

    040

    063

    080

    010

    00

    Rated

    ther

    mal c

    urre

    ntI th

    A25

    3240

    6380

    100

    125

    160

    200

    115

    125

    160

    200

    270

    500

    630

    720

    1000

    Rated

    insu

    lation

    vo

    ltage

    U iV

    690

    690

    690

    690

    690

    1000

    1000

    1000

    1000

    750

    750

    750

    1000

    1000

    1000

    1000

    1000

    1000

    Rated

    impu

    lse vo

    ltage

    U imp

    kV6

    66

    66

    88

    88

    88

    812

    1212

    1212

    8

    Rated

    oper

    ation

    al cu

    rrent

    (AC)

    I eA

    400V

    - AC2

    1A25

    3240

    6380

    100

    125

    160

    200

    100*

    125*

    160*

    200*

    250*

    400*

    630*

    800*

    1000

    *

    690V

    - AC2

    1A25

    3240

    6380

    100

    125

    160

    200

    100

    125

    160

    200

    250

    400

    630

    800

    1000

    400V

    - AC2

    2A-

    --

    --

    100

    125

    160

    200

    100*

    125*

    160*

    200*

    250*

    400*

    630*

    800*

    1000

    *

    690V

    - AC2

    2A-

    --

    --

    100

    125

    160

    160

    100

    125

    160

    200

    250

    400

    630

    800

    -

    400V

    - AC2

    3A21

    2929

    4856

    100

    112

    128

    128

    100*

    125*

    135*

    200*

    250*

    400*

    630*

    720*

    -

    690V

    - AC2

    3A17

    1717

    3333

    53-

    --

    4050

    6320

    025

    035

    035

    035

    0-

    Rated

    oper

    ation

    al cu

    rrent

    (DC)

    ( /

    poles

    in se

    ries)

    I eA

    Up to

    48V

    - DC2

    1A25

    /132

    /140

    /163

    /180

    /1-

    --

    -10

    0/212

    5/216

    0/220

    0/225

    0/240

    0/263

    0/180

    0/110

    00/1

    220V

    - DC

    21A

    25/3

    32/3

    40/3

    63/4

    80/4

    --

    --

    100/3

    125/3

    160/3

    200/2

    250/2

    400/2

    630/2

    800/2

    1000

    /3

    Up to

    48V

    - DC2

    2A-

    --

    --

    --

    --

    100/2

    125/2

    160/2

    200/2

    250/2

    400/1

    630/1

    800/1

    -

    220V

    - DC

    22A

    --

    --

    --

    --

    -10

    0/312

    5/316

    0/320

    0/225

    0/240

    0/263

    0/280

    0/2-

    Up to

    48V

    - DC2

    3A-

    --

    --

    --

    --

    100/2

    125/2

    160/2

    200/2

    250/2

    400/1

    630/1

    800/1

    -

    220V

    - DC

    23A

    --

    --

    --

    --

    -10

    0/312

    5/316

    0/320

    0/225

    0/240

    0/263

    0/263

    0/2-

    Rated

    oper

    ation

    al po

    wer

    P ekW

    400/4

    15V

    - AC2

    3A11

    1515

    2530

    5963

    7575

    3745

    7511

    013

    220

    031

    535

    540

    0

    690V

    - AC2

    3A15

    1515

    3030

    5155

    5555

    3745

    7517

    020

    031

    535

    535

    5-

    Shor

    t circ

    uit m

    aking

    ca

    pacit

    yI cm

    kAPe

    ak va

    lue1.2

    1.41.4

    2.93.0

    3.74.0

    5.05.0

    77

    735

    3565

    8080

    105

    Shor

    t circ

    uit w

    ithsta

    nd

    (1se

    c)I cw

    kArm

    s valu

    e0.5

    0.60.6

    1.31.4

    2.62.8

    3.03.0

    55

    58

    817

    1717

    50

    Min.

    mech

    anica

    l en

    dura

    nce

    -Op

    erati

    ons

    250 x 10

    325

    0 x 103

    250 x 10

    325

    0 x 103

    250 x 10

    350

    x10

    350

    x10

    350

    x10

    350

    x10

    320

    x10

    320

    x10

    320

    x10

    316

    x10

    316

    x10

    310

    x10

    310

    x10

    310

    x10

    36 x 10

    3

    Min.

    electr

    ical

    endu

    ranc

    e-

    415V

    - at

    0.65 p

    f-

    --

    --

    --

    --

    5,000

    5,000

    1,000

    1,000

    1,000

    1,000

    500

    500

    500

    Conn

    ectin

    g cap

    acity

    -Te

    rmina

    l type

    mm2

    Min/M

    ax2.5

    /62.5

    /102.5

    /102.5

    /252.5

    /2510

    /7010

    /7010

    /70-

    --

    --

    --

    --

    -

    mmSt

    ud/C

    u palm

    widt

    h-

    --

    --

    --

    8/20

    8x25

    8x25

    8x25

    8x25

    10x3

    010

    x40

    12x4

    012

    x40

    12x6

    0

    NmTig

    htenin

    g tor

    que

    1.21.2

    1.21.2

    1.22

    22

    126

    88

    2025

    2540

    4040

  • www.craigandderricott.comPage

    34

    A1 Size (63A - 80A) A1-A1 Size (6 pole 63A-80A)

    A0-A0 Size (6 pole 25A & 40A)A0 Size (25A - 40A)

    A2 Size (100A - 160A)

    X1 Minimum depth.X2 Maximum depth with 100mm shaft extension.X3 Maximum depth with 200mm shaft extension.

    X1 - 80 X2 - 180 X3 - 280 X1 - 100 X2 - 195 X3 - 295

    X1 - 98 X2 - 195 X3 - 295 X1 - 145 X2 - 240 X3 - 340

    X1 - 196 X2 - 290 X3 - 390

    AU

    XA

    UX

    A3 Size (200A)

    X1 - 196 X2 - 290 X3 - 390

    A2-A2 Size (6 pole 100A-160A)

    Pane

    l Iso

    lato

    rs

    Compact Panel Isolators Dimensions

    Dimensions

    A3 Size (6 pole 200A)X1 - 196 X2 - 290 X3 - 390X1 - 196 X2 - 290 X3 - 390

  • Page

    35

    Pane

    l Iso

    lato

    rsStandard Panel Isolators Dimensions

    X1 Minimum depth.X3 Maximum depth with 200mm shaft extension.X4 Maximum depth with 400mm shaft extension.

    Rating A B L

    3P 4P 3P 4P

    400A 211 257 205 151 197

    600A 244 306 223 183 245

    800A 260 330 223 199 269

    B1 Size (100A - 160A)X1 - 130 X3 - 255 X4 - 455

    B2 Size (200A - 250A)X1 - 190 X3 - 270 X4 - 470

    B4 Size (400A - 800A)X1 - 220 X3 - 285 X4 - 485

    Rating P Q S T

    400A 46 25 4 11

    600A 62 40 5 13.5

    800A 70 40 5 13.5

    B4 Size (1000A)X1 - 240 X3 - 285 X4 - 485

    B2 Size (6P 200A)

    B2 Size (6P 250A)

    B4 Size (6P 315A)

    B4 Size (6P 400A)

  • www.craigandderricott.comPage

    36

    Data supplied against tests to BS EN 60947-3 Rating (A)

    Application Sym Unit Category 63 100 125 160 200 250 400 630

    Rated thermal current Ithe A 63 100 125 160 200 250 400 630

    Rated insulation voltage Ui V 750 750 1000 1000 1000 1000 1000 1000

    Rated impulse voltage Uimp kV 6 6 6 6 6 12 12 12

    Rated operational current Ie A415V - AC22A 63 100 125 160 200 250 400 630

    415V - AC23A 63 100 125 160 200 250 400 630

    Rated making capacity (AC23A) A 415V, 0.35 pf 630 630 1,250 1,600 2,000 2,500 4,000 6,300

    Rated breaking capacity (AC23A) A 415V, 0.35 pf 504 504 1,000 1,280 1,600 2,000 3,200 5,040

    Short circuit current kA rms (with fuses) 80 80 80 80 80 100 100 80

    Rated S/C making capacity kA Peak 15 15 20 20 20 30 40 50

    Min. mechanical endurance - Operations 20,000 20,000 10,000 10,000 10,000 10,000 10,000 10,000

    Min. electrical endurance - 415V - at 0.65 pf 2,500 1,500 1,000 1,000 1,000 1,000 1,000 500

    Connecting capacity

    - Terminal type

    mm2 Max 35 35 95 95 95 240 300 400

    mm Stud/Cu palm width 6x12 6x12 8x22 8x22 8x22 10x25 10x25 12x50

    Nm Tightening torque 3 3 10 10 10 30 45 50

    General Description A compact range of load break Changeover Switches suitable for a wide range of applications.

    Features Compact piggy-back design. On-load AC23A ratings. Supplied as four pole format. Windows for visual contact inspection.

    The catalogue numbers below include:- On-load AC23A changeover four pole switch. 200mm standard length shaft assembly. IP65 door interlocking handle.

    Alternative shafts As an alternative to the standard 200mm shaft a 400mm option is available as indicated below. The shafts are manufactured from square section steel and zinc plated. The height setting is adjusted by passing the shaft through a bush in the switch mechanism and locking it in position using two cup point grub screw.

    Load break switch current RatingShaft length L 63A - 100A 125A - 200A 250A - 630A

    400mm SSH14 SSH18 SSH15Drive Shaft Section 8mm2 8mm2 12mm2

    Max. possible enclosure depth

    200mm 270 285 330

    400mm 470 485 530

    L

    Typical C2/C3Arrangement

    Handle assembly supplied with the C2

    & C3 frame size (SDH6/BLK).

    Supplied Handles Designed to compliment the handles used on our enclosed equipment, the door interlocked versions are capable of being locked with up to three individual padlocks (6.4 max shackle dia). All handles are sealed to IP65 which will enable installations in a wide variety of environmental conditions.

    Changeover Isolators 32A - 630A

    Pane

    l Iso

    lato

    rs

    DimensionsPg 37

    Catalogue NumbersCurrent Rating

    Frame Size TP&N

    63A C1C SCOD00634B100A C1C SCOD01004B125A C2C SCOD01254B160A C2C SCOD01604B200A C2C SCOD02004B250A C2 SCOD02504B400A C3 SCOD04004B630A C3 SCOD06304B

    If the contacts should weld due to a fault or an excessive current situation, an override facility is provided for the use of a competent person which will allow the enclosure lid to be opened.

    Technical Specification - Changeover Switch-Disconnectors

  • Page

    37

    Pane

    l Iso

    lato

    rs

    Frame Size Rating a1 b1 c d e f g h j k m n p qC2 250A 309.5 252 61 25 124 138 163 65.5 81 4.0 242 255-355 145 18C3 400A 352 276 70 25 150 180 205 85 96 4.0 262 300-400 220 26C3 630A 352 276 70 40 150 185 223 84 98 5.0 262 300-400 220 26

    Frame Size C1C - 63A & 100A Ratings Frame Size C2C - 125A, 160A & 200A Ratings

    80

    Changeover Isolators Dimensions

    Frame Sizes C2 / C3 - 250A, 400A, 630A Ratings

  • www.craigandderricott.comPage

    38

    Bespoke AssembliesTake advantage of our bespoke mi-switch service.

    Made to order products at competitive prices.

    Made to order A

    ssemblies

  • Page

    39

    Projects within the GCCCraig & Derricott has been supplying equipment for prestigious projects across the GCC for many years. Some of the more recent are shown below:-

    Projects within the G

    CC

  • www.craigandderricott.comPage

    40

    Notes

    Your local Area Sales Manager ..................................................

    Mob. Telephone No. ..................................................email address ..................................................

    Your local Sales Promoter ..................................................

    Mob.Telephone No. ..................................................email address ..................................................

    Your Internal Sales Contact ..................................................

    Direct.Telephone No. ..................................................email address .................................................. N

    otes

    Pag

    e

  • Page

    41

    Craig & Derricott Ltd.Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP U.K.t: +44(0)1543 375541 e: [email protected]

    C&D

    Web

    site

    Craig & Derricott Ltd.Hall Lane, Walsall Wood, Walsall, West Midlands WS9 9DP U.K.t: +44(0)1543 375541 e: [email protected] C&

    D W

    ebsi

    te

    C&

    D E

    xpor

    t Cat

    alog

    ue I

    ssue

    3 C

    DPD

    11

    Head Office:-Craig & Derricott FZCDubai United Arab Emirates.t: 00971(0)50 3554080 00971(0)52 9909555e: [email protected]

    Middle East Office:-