Page 1729 Mar 2008 Siemens ITS
CPU 412
Function
Block protection:A password concept also protects the user program from unauthorized access
Integrated HMI services:The user only has to specify the source and destination of the data with HMI devices. The data arethen transported cyclically and automatically by the system.
Integrated communication functions: PG/OP communication Global data communication S7 standard communication S7 communication
Programmable properties
The STEP 7 tool "Hardware configuration" can be used to parameterize the properties and response of theS7-400 including the CPUs, e.g.
Page 1730 Mar 2008 Siemens ITS
Multipoint interface MPI: Definition of node addresses Startup/cycle behavior Stipulation of the maximum cycle time and communication load
Address allocation:Addressing of I/O modules
Retentive area:Definition of the number of retentive bit memories, counters, timers, data blocks, and clock memories
Size of the process image, local data Length of the diagnostics buffer Protection level:
Definition of access authorizations to program and data System diagnostics:
Definition of the handling and scope of diagnostics messages Timed interrupts:
Setting of periodicityDisplay and information functionsStatus and fault indicators:LEDs indicate internal and external faults and operating modes such RUN, STOP, restart,. test function, etc. Test functions:
The PG can be used to display signal states in program execution, modify process tags irrespective of the userprogram, read out the contents of stack memories, run separate program steps and inhibit program components.
Information functions:The PG can be used to provide the user with information about the memory capacity and operating mode of theCPU, and the current utilization of the working and load memories
Technical specifications
Page 1731 Mar 2008 Siemens ITS
6ES7 412-1XJ05-0AB0
6ES7 412-2XJ05-0AB0
6ES7 412-2EK06-0AB0
CPU 412-1 CPU 412-2 CPU 412-2 PNProduct versionHardware product version 03 03 01Firmware version V5.3 V5.3 V6.0General informationassociated programmingpackage
STEP7 V 5.3 SP2or higher with HWupdate
STEP7 V 5.3 SP2or higher with HWupdate
STEP7 V5.5 orhigher/iMap V3.0 +iMap STEP7 Add-on V3.0 SP5 orhigher
Technical specifications
Page 1732 Mar 2008 Siemens ITS
CiR - Configuration inRUNCiR synchronization time,basic load
100 ms 100 ms 100 ms
CiR synchronization time,time per I/O slave
30 µs; Time per I/Obyte
30 µs; Time per I/Obyte
30 µs; Time per I/Obyte
Supply voltage24 V DC No; Power supply
via system powersupply
No; Power supplyvia system powersupply
No; Power supplyvia system powersupply
Input currentfrom backplane bus 5 VDC, max.
0.6 A 1.1 A 1.3 A
from interface 5 V DC,max.
90 mA 90 mA; At each DPinterface
90 mA; At the DPinterface
Power lossesPower loss, typ. 2.5 W 4.5 W 5.5 WPower loss, max. 3 W 5 W 6.5 WMemoryWork memory•integrated 288 Kibyte 512 Kibyte 1 Mbyte•integrated (for program) 144 Kibyte 256 Kibyte 0.5 Mbyte•integrated (for data) 144 Kibyte 256 Kibyte 0.5 Mbyte•expandable No No No
Page 1733 Mar 2008 Siemens ITS
Load memory•expandable FEPROM Yes; with Memory
Card (FLASH)Yes; with MemoryCard (FLASH)
Yes; with MemoryCard (FLASH)
•expandable FEPROM,max.
64 Mbyte 64 Mbyte 64 Mbyte
•integrated RAM, max. 512 Kibyte 512 Kibyte 512 Kibyte•expandable RAM Yes; with Memory
Card (RAM)Yes; with MemoryCard (RAM)
Yes; with MemoryCard (RAM)
•expandable RAM, max. 64 Mbyte 64 Mbyte 64 MbyteBackup•present Yes Yes Yes•with battery Yes; all data Yes; all data Yes; all data•without battery No No NoCPU-blocksDB•Number, max. 1 500; Number
range: 1 to 160003 000; Numberrange: 1 to 16000
3 000; Numberrange: 1 to 16000
•Size, max. 64 Kibyte 64 Kibyte 64 KibyteFB•Number, max. 750; Number range:
0 to 79991 500; Numberrange: 0 to 7999
1 500; Numberrange: 0 to 7999
•Size, max. 64 Kibyte 64 Kibyte 64 KibyteFC•Number, max. 750; Number range: 1 500; Number 1 500; Number
Page 1734 Mar 2008 Siemens ITS
range: 0 to 7999 range: 0 to 7999 range: 0 to 7999•Size, max. 64 Kibyte 64 Kibyte 64 KibyteOB•Size, max. 64 Kibyte 64 Kibyte 64 KibyteNesting depth•per priority class 24 24 24•additional within an errorOB
1 1 1
CPU processing timesfor bit operations, min. 75 ns 75 ns 75 nsfor word operations, min. 75 ns 75 ns 75 nsfor fixed point arithmetic,min.
75 ns 75 ns 75 ns
for floating pointarithmetic, min.
225 ns 225 ns 225 ns
Counters, timers andtheir retentivityS7 counter•Number 2 048 2 048 2 048•Retentivity
• adjustableYes Yes Yes
• lower limit0 0 0
Page 1735 Mar 2008 Siemens ITS
• upper limit2 047 2 047 2 047
• presetZ 0 to Z 7 Z 0 to Z 7 Z 0 to Z 7
•Counting range
• lower limit0 0 0
• upper limit999 999 999
IEC counter•present Yes Yes Yes•Type SFB SFB SFB•Number Unlimited (limited
only by RAMcapacity)
Unlimited (limitedonly by RAMcapacity)
Unlimited (limitedonly by RAMcapacity)
S7 times•Number 2 048 2 048 2 048•Retentivity
• adjustableYes Yes Yes
• lower limit0 0 0
• upper limit2 047 2 047 2 047
Page 1736 Mar 2008 Siemens ITS
• presetNo times retentive No times retentive No times retentive
•Time range
• lower limit10 ms 10 ms 10 ms
• upper limit9 990 s 9 990 s 9 990 s
IEC timer•present Yes Yes Yes•Type SFB SFB SFB•Number Unlimited (limited
only by RAMcapacity)
Unlimited (limitedonly by RAMcapacity)
Unlimited (limitedonly by RAMcapacity)
Data areas and theirretentivityretentive data area, total Total working and
load memory (withbackup battery)
Total working andload memory (withbackup battery)
Total working andload memory (withbackup battery)
Flag•Number, max. 4 Kibyte; Size of
bit memoryaddress area
4 Kibyte; Size of bitmemory address area
4 Kibyte; Size of bitmemory address area
•Retentivity available Yes Yes Yes•Retentivity preset MB 0 to MB 15 MB 0 to MB 15 MB 0 to MB 15
Page 1737 Mar 2008 Siemens ITS
•Number of clockmemories
8; (in 1 memorybyte)
8; (in 1 memorybyte)
8; (in 1 memorybyte)
Local data•adjustable, max. 8 Kibyte 8 Kibyte 8 Kibyte•preset 4 Kibyte 4 Kibyte 4 KibyteAddress areaI/O address area•Inputs 4 Kibyte 4 Kibyte 4 Kibyte•Outputs 4 Kibyte 4 Kibyte 4 Kibyte•of which, distributed
• MPI/DP interface,inputs
2 Kibyte 2 Kibyte 2 Kibyte
• MPI/DP interface,outputs
2 Kibyte 2 Kibyte 2 Kibyte
• DP interface,inputs
4 Kibyte
• DP interface,outputs
4 Kibyte
• PN interface,4 Kibyte
Page 1738 Mar 2008 Siemens ITS
inputs
• PN interface,outputs
4 Kibyte
Process image•Inputs, adjustable 4 Kibyte 4 Kibyte 4 Kibyte•Outputs, adjustable 4 Kibyte 4 Kibyte 4 Kibyte•Inputs, default 128 byte 128 byte 128 kbyte•Outputs, default 128 byte 128 byte 128 Kibyte•consistent data, max. 244 byte 244 byte 244 byte•Access to consistent datain process image
Yes Yes Yes
Subprocess images•Number of subprocessimages, max.
15 15 15
Digital channels•Inputs 32 768 32 768 32 768•Outputs 32 768 32 768 32 768•Inputs, of which central 32 768 32 768 32 768•Outputs, of which central 32 768 32 768 32 768Analog channels•Inputs 2 048 2 048 2 048•Outputs 2 048 2 048 2 048•Inputs, of which central 2 048 2 048 2 048
Page 1739 Mar 2008 Siemens ITS
•Outputs, of which central 2 048 2 048 2 048Hardware configurationExpansion devices, max. 21 21 21Multicomputing Yes; 4 CPUs max.
(with UR1 orUR2)
Yes; 4 CPUs max.(with UR1 or UR2)
Yes; 4 CPUs max.(with UR1 or UR2)
Interface modules•Number of connectableIMs (total), max.
6 6 6
•Number of connectableIM 460s, max.
6 6 6
•Number of connectableIM 463s, max.
4; IM 463-2 4; IM 463-2 4; IM 463-2
Number of DP masters•integrated 1 2 1•via IM 467 4 4 4•via CP 10; CP 443-5
Extended10; CP 443-5Extended
10; CP 443-5Extended
•Mixed mode IM + CPpermitted
No; IM 467 notsuitable for usewith CP 443-5Ext. and CP443-1EX4x, EX20,GX20 (in PNIO
No; IM 467 notsuitable for use withCP 443-5 Ext. andCP443-1 EX4x,EX20, GX20 (inPNIO mode)
No; IM 467 notsuitable for use withCP 443-5 Ext. andCP443-1 EX4x,EX20, GX20 (inPNIO mode)
Page 1740 Mar 2008 Siemens ITS
mode)•via interface module 0 0 0•Number of pluggable S5modules (via adaptercapsule in central device),max.
6 6 6
Number of IO Controllers•integrated 0 0 1•via CP 4; No mixed
operation ofCP443-1 EX40and CP443-1 EX41/EX20/GX20,max. 4 in centralcontroller
4; No mixedoperation of CP443-1EX40 and CP443-1EX 41/EX20/GX20,max. 4 in centralcontroller
4; No mixedoperation of CP443-1 EX40 and CP443-1 EX41/EX20/GX20, max.4 in centralcontroller
Number of operable FMsand CPs (recommended)•FM Limited by
number of slotsand number ofconnections
Limited by numberof slots and numberof connections
Limited by numberof slots and numberof connections
•CP, point-to-point CP 440: Limitedby number ofslots; CP 441:
CP 440: Limited bynumber of slots; CP441: Limited by
CP 440: Limited bynumber of slots; CP441: Limited by
Page 1741 Mar 2008 Siemens ITS
•CP, point-to-point Limited bynumber of slotsand number ofconnections
number of slots andnumber ofconnections
number of slots andnumber ofconnections
•PROFIBUS and EthernetCPs
14; Of which 10CPs max. or IMsas DP master, 4PN controllermaximum
14; Of which 10 CPsmax. or IMs as DPmaster, 4 PNcontroller maximum
14; In total max. 10CPs as DP masterand PN controller,of which up to 10IMs or CPs as DPmaster and up to 4CPs as PN controller
Time of dayClock•Hardware clock (real-timeclock)
Yes Yes Yes
•battery-backed andsynchronizable
Yes Yes Yes
•Resolution 1 ms 1 ms 1 ms•Deviation per day(buffered), max.
1.7 s; Power off 1.7 s; Power off 1.7 s; Power off
•Deviation per day(unbuffered) max.
8.6 s; For powerOn
8.6 s; For power On 8.6 s; For power On
Operating hours counter•Number 16 16 16
Page 1742 Mar 2008 Siemens ITS
•Number/Number range 0 to 15 0 to 15 0 to 15•Range of values SFCs 2, 3 and 4:
0 to 32767 hoursSFC 101: 0 to2^31 - 1 hours
SFCs 2, 3 and 4: 0to 32767 hours SFC101: 0 to 2^31 - 1hours
SFCs 2, 3 and 4: 0to 32767 hours SFC101: 0 to 2^31 - 1hours
•Granularity 1 hour 1 hour 1 hour•retentive Yes Yes YesClock synchronization•supported Yes Yes Yes•to MPI, master Yes Yes Yes•to MPI, slave Yes Yes Yes•to DP, master Yes Yes Yes•to DP, slave Yes Yes Yes•in AS, master Yes Yes Yes•in AS, slave Yes Yes Yes•on Ethernet via NTP No; via CP No; via CP Yes; as client•to IF 964 DP No NoInterfacesInterfaces 1 x
MPI/PROFIBUSDP
1 x MPI/PROFIBUSDP, 1 x PROFIBUSDP
1 x MPI/PROFIBUSDP, 1 x PROFINET(2 ports)
Number of USB interfaces 0 0 01st interface
Page 1743 Mar 2008 Siemens ITS
Type of interface integrated integrated integratedPhysics RS 485 /
PROFIBUS + MPIRS 485 / PROFIBUS+ MPI
RS 485 /PROFIBUS + MPI
Isolated Yes Yes YesPower supply to interface(15 to 30 V DC), max.
150 mA 150 mA 150 mA
Number of connectionresources
MPI: 32, DP: 16 MPI: 32, DP: 16 MPI: 32, DP: 16
Functionality•MPI Yes Yes Yes•DP master Yes Yes Yes•DP slave Yes Yes Yes
Type of interface integrated integrated integratedPhysics RS 485 /
PROFIBUS +MPI
RS 485 /PROFIBUS + MPI
RS 485 /PROFIBUS + MPI
Isolated Yes Yes YesPower supply tointerface (15 to 30 VDC), max.
150 mA 150 mA 150 mA
Number of connectionresources
MPI: 32, DP: 16 MPI: 32, DP: 16 MPI: 32, DP: 16
Functionality
Page 1744 Mar 2008 Siemens ITS
•MPI Yes Yes Yes•DP master Yes Yes Yes•DP slave Yes Yes YesMPI•Number of connections 32; If a
diagnosticsrepeater is usedon the line, thenumber ofconnectionresources on theline is reducedby 1
32; If a diagnosticsrepeater is used onthe line, thenumber ofconnectionresources on theline is reduced by1
32; If a diagnosticsrepeater is usedon the line, thenumber ofconnectionresources on theline is reduced by1
•Services
• PG/OPcommunication
Yes Yes Yes
• RoutingYes Yes Yes
• Global datacommunication
Yes Yes Yes
• S7 basicYes Yes Yes
Page 1745 Mar 2008 Siemens ITS
communication
• S7communication
Yes Yes Yes
• S7communication,as client
Yes Yes Yes
• S7communication,as server
Yes Yes Yes
•Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/sDP master•Number of connections,max.
16; If adiagnosticsrepeater is usedon the line, thenumber ofconnectionresources on theline is reducedby 1
16; If a diagnosticsrepeater is used onthe line, thenumber ofconnectionresources on theline is reduced by1
16; If a diagnosticsrepeater is usedon the line, thenumber ofconnectionresources on theline is reduced by1
•Services
Page 1746 Mar 2008 Siemens ITS
• PG/OPcommunication
Yes Yes Yes
• Global datacommunication
No No No
• S7 basiccommunication
Yes Yes Yes
• S7communication
Yes Yes Yes
• S7communication,as client
Yes Yes Yes
• S7communication,as server
Yes Yes Yes
• Equidistancemode support
Yes Yes Yes
Yes Yes Yes
Page 1747 Mar 2008 Siemens ITS
• Isochronousmode
• SYNC/FREEZEYes Yes Yes
• Activation/deactivation of DP slaves
Yes Yes Yes
• Direct dataexchange (slave-to-slavecommunication)
Yes Yes Yes
• DPV1Yes Yes Yes
•Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s•Number of DP slaves,max.
32 32 32
•Address area
• Inputs, max.2 Kibyte 2 Kibyte 2 Kibyte
• Outputs, max.2 Kibyte 2 Kibyte 2 Kibyte
•User data per DP slave
Page 1748 Mar 2008 Siemens ITS
• User data per DPslave, max.
244 byte 244 byte 244 byte
• Inputs, max.244 byte 244 byte 244 byte
• Outputs, max.244 byte 244 byte 244 byte
• Slots, max.244 244 244
• per slot, max.128 byte 128 byte 128 byte
DP slave•Number of connections 16 16 16•Services
• PG/OPcommunication
Yes; withinterface active
Yes; with interfaceactive
Yes; with interfaceactive
• S7 routingYes; withinterface active
Yes; with interfaceactive
Yes; with interfaceactive
• Global datacommunication
No No No
• S7 basicNo No No
Page 1749 Mar 2008 Siemens ITS
communication
• S7communication
Yes Yes Yes
• S7communication,as client
Yes Yes Yes
• S7communication,as server
Yes Yes Yes
• Direct dataexchange (slave-to-slavecommunication)
No No No
• DPV1No No No
•GSD file http://support.automation.siemens.com/WW/view/de/113652
http://support.automation.siemens.com/WW/view/de/113652
http://support.automation.siemens.com/WW/view/de/113652
•Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s
Page 1750 Mar 2008 Siemens ITS
•Automatic baud ratesearch
No No No
•Transfer memory
• Inputs244 byte 244 byte 244 byte
• Outputs244 byte 244 byte 244 byte
•Address area, max. 32; Virtual slots 32; Virtual slots 32; Virtual slots•User data per addressarea, max.
32 byte 32 byte 32 byte
•User data per addressarea, of whichconsistent, max.
32 byte 32 byte 32 byte
2nd interfaceType of interface integrated PROFINETPhysics RS 485 /
PROFIBUSEthernet RJ45
Isolated Yes YesIntegrated switch YesNumber of ports 2Power supply tointerface (15 to 30 VDC), max.
150 mA
Automatic detection of Yes; Autosensing
Page 1751 Mar 2008 Siemens ITS
transmission speedAutonegotiation YesAutocrossing YesMedia redundancy•supported Yes•Switchover time on linebreak, typically
200 ms
•Number of stations inthe ring, max.
50
Change of IP addressat runtime, supported
Yes; Assignmentby higher-level IO-Controller or bythe user programwith SFB104"IP_CONF"
Number of connectionresources
16 48
Functionality•DP master Yes No•DP slave Yes No•PROFINET IOController
Yes
•PROFINET IO Device Yes•PROFINET CBA Yes
Page 1752 Mar 2008 Siemens ITS
•Local OperatingNetwork
No
DP master•Number of connections,max.
16
•Services
• PG/OPcommunication
Yes
• Global datacommunication
No
• S7 basiccommunication
Yes
• S7communication
Yes
• S7communication,as client
Yes
• S7Yes
Page 1753 Mar 2008 Siemens ITS
communication, asserver
• Equidistancemode support
Yes
• Isochronousmode
Yes
• SYNC/FREEZEYes
• Activation/deactivation of DP slaves
Yes
• Direct dataexchange (slave-to-slavecommunication)
Yes
• DPV1Yes
•Transmission rate, max. 12 Mbit/s•Number of DP slaves,max.
64
•Address area
Page 1754 Mar 2008 Siemens ITS
• Inputs, max.4 Kibyte
• Outputs, max.4 Kibyte
•User data per DP slave
• User data per DPslave, max.
244 byte
• Inputs, max.244 byte
• Outputs, max.244 byte
• Slots, max.244
• per slot, max.128 byte
DP slave•Number of connections 16•GSD file http://support.automa
tion.siemens.com/WW/view/de/113652
•Transmission rate, max. 12 Mbit/s•Transfer memory
Page 1755 Mar 2008 Siemens ITS
• Inputs244 byte
• Outputs244 byte
•Address area, max. 32•User data per addressarea, max.
32 byte
•User data per addressarea, of whichconsistent, max.
32 byte
PROFINET IO Controller•Services
• PG/OPcommunication
Yes
• S7 routingYes
• S7communication
Yes
• Isochronousmode
Yes; Only with IRTand the HighPerformance optionYes
Page 1756 Mar 2008 Siemens ITS
• Open IEcommunication
•Transmission rate, max. 100 Mbit/s•Number of connectableIO devices, max.
256
•Max. number ofconnectable IO devicesfor RT
256
• of which in line,max.
256
•Number of IO deviceswith IRT and the option"high flexibility"
256
• of which in line,max.
61
•Number of IO Deviceswith IRT and the option"high performance", max.
64
• of which in line,max.
64
•Shared device, Yes
Page 1757 Mar 2008 Siemens ITS
supported•Prioritized startupsupported
Yes
• Number of IODevices, max.
32
•Activation/deactivation ofIO Devices
Yes
• Number of IODevices that canbe simultaneouslyactivated/deactivated, max.
8
•IO Devices changingduring operation (partnerports), supported
Yes
• Max. number ofIO devices pertool
8; 8 parallel callsof the SFC 12"D_ACT_DP"possible per line.Max. 32 IODevices changingduring operation
Page 1758 Mar 2008 Siemens ITS
(partner ports) aresupported.
•Device replacementwithout swap medium
Yes
•Send cycles 250 μs, 500 μs, 1ms, 2 ms, 4 msadditionally withIRT with highperformance: 250µs to 4 ms in 125µs frame
•Updating time 250 µs to 512 ms;minimum valuedepends on presetcommunicationshare forPROFINET IO, onthe number of IODevices and onthe amount ofconfigured userdata, seePROFINET systemdescription
Page 1759 Mar 2008 Siemens ITS
•Address area
• Inputs, max.4 Kibyte
• Outputs, max.4 Kibyte
•User data per addressarea, max.
• User dataconsistency, max.
1 024 byte
PROFINET IO Device•Services
• PG/OPcommunication
Yes
• S7 routingYes
• S7communication
Yes
• Isochronousmode
No
Page 1760 Mar 2008 Siemens ITS
• Open IEcommunication
Yes
• IRT, supportedYes
• Prioritized startupsupported
Yes
• Shared device,supported
Yes
• Number of IOcontrollers with shareddevice, max.
2
•Transfer memory
• Inputs, max.1 440 byte; Per IOController withshared device
• Outputs, max.1 440 byte; Per IOController withshared device
•Submodules64
Page 1761 Mar 2008 Siemens ITS
• Number, max.
• User data persubmodule, max.
1 024 byte
Open IE communication•Open IE communication,supported
Yes
•Number of connections, max. 46•Local port numbers used atthe system end
0, 20, 21, 25, 80,102, 135, 161,34962, 34963, 34964,65532, 65533, 65534,65535
•Keep-alive function,supported
Yes
Communication functionsPG/OP communication Yes Yes Yes•Number of connectable OPswithout message processing
31 31 47
•Number of connectable OPswith message processing
31; When usingalarm_S andalarm_D
31; When usingalarm_S andalarm_D
47; When usingAlarm_S/SQ andAlarm_D/DQ
Data record routing Yes Yes YesGlobal data communication
Page 1762 Mar 2008 Siemens ITS
•supported Yes Yes Yes•Number of GD packets,transmitter, max.
8 8 8
•Number of GD packets,receiver, max.
16 16 16
•Size of GD packets, max. 54 byte 54 byte 54 byte•Size of GD packet (of whichconsistent), max.
1 variable 1 variable 1 variable
S7 basic communication•supported Yes Yes Yes•User data per job, max. 76 byte 76 byte 76 byte•User data per job (of whichconsistent), max.
1 variable 1 variable 1 variable
S7 communication•supported Yes Yes Yes•as server Yes Yes Yes•as client Yes Yes Yes•User data per job, max. 64 Kibyte 64 Kibyte 64 Kibyte•User data per job (of whichconsistent), max.
462 byte 462 byte; 1 variable462 byte; 1 variable
S5-compatible communication•supported Yes; Via FC
AG_SEND andAG_RECV, max.
Yes; Via FCAG_SEND andAG_RECV, max.
Yes; Via FCAG_SEND andAG_RECV, max. via
Page 1763 Mar 2008 Siemens ITS
•supported via 10 CP 443-1 or 443-5
via 10 CP 443-1or 443-5
10 CP 443-1 or 443-5
•User data per job, max. 8 Kibyte 8 Kibyte 8 Kibyte•User data per job (of whichconsistent), max.
240 byte 240 byte 240 byte
•Number of simultaneous AG-SEND/AG-RECV orders perCPU, max.
24/24 24/24 24/24
Standard communication(FMS)•supported Yes; Via CP
and loadable FBYes; Via CP andloadable FB
Yes; Via CP andloadable FB
Open IE communication•TCP/IP Yes; via integrated
PROFINET interfaceand loadable FBs
• Number ofconnections, max.
46
• Data length, max.32 Kibyte
• Several passiveconnections per port,
Yes
Page 1764 Mar 2008 Siemens ITS
supported•ISO-on-TCP (RFC1006) Via CP 443-1
Adv. andloadable FB
Via CP 443-1 andloadable FB
Yes; Via integratedPROFINET interfaceor CP 443-1 Adv.and loadable FBs
• Number ofconnections, max.
46
• Data length, max.1452 bytes viaCP 443-1 Adv.
1452 bytes via CP443-1 Adv.
32 Kibyte; 1452 bytesvia CP 443-1 Adv.
•UDP Yes; via integratedPROFINET interfaceand loadable FBs
• Number ofconnections, max.
46
• Data length, max.1 472 byte
Web server•supported No No Yes•Number of HTTP clients 5•User-defined websites YesPROFINET CBA (at setsetpoint communication load)
Page 1765 Mar 2008 Siemens ITS
•Setpoint for the CPUcommunication load
20 %
•Number of remoteinterconnection partners
32
•Number of functions,master/slave
150
•Total of all Master/Slaveconnections
4 500
•Data length of all incomingconnections master/slave, max.
45 000 byte
•Data length of all outgoingconnections master/slave, max.
45 000 byte
•Number of device-internaland PROFIBUSinterconnections
1 000
•Data length of device-internalund PROFIBUSinterconnections, max.
16 000 byte
•Data length per connection,max.
2 000 byte
•Remote interconnections withacyclic transmission
• Sampling frequency:200 ms; Dependingon preset
Page 1766 Mar 2008 Siemens ITS
Sampling time, min. communication load,number ofinterconnections anddata length used
• Number of incominginterconnections
250
• Number of outgoinginterconnections
250
• Data length of allincominginterconnections, max.
8 000 byte
• Data length of alloutgoinginterconnections, max.
8 000 byte
• Data length perconnection, max.
2 000 byte
•Remote interconnections withcyclic transmission
Page 1767 Mar 2008 Siemens ITS
• Transmission frequency:Transmission interval, min.
1 ms; Dependingon presetcommunicationload, number ofinterconnectionsand data lengthused
• Number of incominginterconnections
300
• Number of outgoinginterconnections
300
• Data length of allincoming interconnections,max.
4 800 byte
• Data length of all outgoinginterconnections, max.
4 800 byte
• Data length per connection,max.
450 byte
Page 1768 Mar 2008 Siemens ITS
•HMI variables via PROFINET(acyclic)
• Number of stations thatcan log on for HMIvariables (PN OPC/iMap)
2x PN OPC/1xiMap
• HMI variable updating500 ms
• Number of HMI variables1 000
• Data length of all HMIvariables, max.
32 000 byte
•PROFIBUS proxy functionality
• supportedYes; 32PROFIBUS slavesmax. connectable
• Data length per connection,max.
240 byte; Slave-dependent
Number of connections•overall 32 32 48S7 message functions
Page 1769 Mar 2008 Siemens ITS
Number of login stations formessage functions, max.
31; Max. 31with alarm_S andalarm_D (OP's);max. 8 withalarm_8 andalarm_P (e.g.WinCC)
31; Max. 31with alarm_S andalarm_D (OP's);max. 8 withalarm_8 andalarm_P (e.g.WinCC)
47; Max. 47 withAlarm_S/SQ andAlarm_D/DQ(OPs); max. 8with Alarm,Alarm_8,Alarm_8P, Notifyand Notify_8 (e.g.WinCC)
Symbol-related messages Yes Yes YesSCAN procedure Yes Yes YesNumber of messages•overall, max. 256 256 256Block related messages Yes Yes YesProcess diagnostic messages Yes Yes Yessimultaneously active Alarm-Sblocks, max.
250;Simultaneouslyactivealarm_S/SQblocks oralarm_D/DQblocks
250;Simultaneouslyactivealarm_S/SQblocks oralarm_D/DQblocks
250;Simultaneouslyactive alarm_S/SQblocks oralarm_D/DQblocks
Alarm 8-blocks Yes Yes Yes•Number of instances for alarm 8 300 300 300
Page 1770 Mar 2008 Siemens ITS
and S7 communication blocks,max.•preset, max. 150 150 150Process control messages Yes Yes YesTest commissioning functionsStatus/control•Status/control variable Yes; Up to 16
variable tablesYes; Up to 16variable tables
Yes; Up to 16variable tables
•Variables Inputs/outputs,memory bits,DBs, distributedI/Os, timers,counters
Inputs/outputs,memory bits,DBs, distributedI/Os, timers,counters
Inputs/outputs,memory bits, DBs,distributed I/Os,timers, counters
•Number of variables, max. 70; Status/control 70; Status/control 70; Status/controlForcing•Forcing Yes Yes Yes•Force, variables Inputs/outputs, bit
memories,distributed I/Os
Inputs, outputs,bit memories,peripheral inputs,peripheral outputs
Inputs/outputs, bitmemories,distributed I/Os
•Number of variables, max. 64 64 64Status block Yes; Up to 2
simultaneouslyYes; Up to 2simultaneously
Yes; Up to 16simultaneously
Single step Yes Yes Yes
Page 1771 Mar 2008 Siemens ITS
Number of breakpoints 4 4 16Diagnostic buffer•present Yes Yes Yes•Number of entries, max. 200 400 400
• adjustableYes Yes Yes
• preset120 120 120
Isochronous modeIsochronous mode Yes; For
PROFIBUS onlyYes; ForPROFIBUS only
Yes; ViaPROFIBUS DP orPROFINETinterface
Number of DP masters withisochronous mode
1 2 1
User data per isochronous slave,max.
244 byte 244 byte 244 byte
equidistance Yes Yes Yesshortest clock pulse 1.5 ms; 0.5 ms
without use ofSFC 126, 127
1.5 ms; 0.5 mswithout use ofSFC 126, 127
1.5 ms; 0.5 mswithout use ofSFC 126, 127
max. cycle 32 ms 32 ms 32 msConfigurationConfiguration software
Page 1772 Mar 2008 Siemens ITS
•STEP 7 Yes Yes Yesprogramming•Programming language
• LADYes Yes Yes
• FBDYes Yes Yes
• STLYes Yes Yes
• SCLYes Yes Yes
• CFCYes Yes Yes
• GRAPHYes Yes Yes
• HiGraph®Yes Yes Yes
•Command set see instructionlist
see instructionlist
see instruction list
•Nesting levels 7 7 7Know-how protection•User program protection/passwordprotection
Yes Yes Yes
•Block encryption Yes; With S7block Privacy
Height 290 mm 290 mm 290 mmDepth 219 mm 219 mm 219 mmRequired slots 1 1 1WeightWeight, approx. 0.7 kg 0.7 kg
Page 1773 Mar 2008 Siemens ITS
•Block encryption Yes; With S7block Privacy
DimensionsWidth 25 mm 25 mm 25 mmHeight 290 mm 290 mm 290 mmDepth 219 mm 219 mm 219 mmRequired slots 1 1 1WeightWeight, approx. 0.7 kg 0.7 kg 750 g