CPM-41 DIGITAL MICRO-PROCESS METER <<Operating Manual>> Features Input: Universal input programmed by the front keys
DC Voltage: 0 ~ 10V DC Current: 0 ~ 20mA Thermocouple: K J E T R B S N C Type RTD: Pt100Ω or JPt100Ω Strain Gauge: 0 ~ 100mV
Sampling Time: 50mS Accuracy:
DC Voltage: 0.04% F.S ±1 digit DC Current: 0.04% F.S ±1 digit Thermocouple: 0.2% F.S ±1 digit RTD: 0.2% F.S ±1 digit Strain Gauge: 0.04% F.S ±1 digit
Display: Screens:
Measuring Screen: 5 digits 0.56” high brightness 7 segment LED
Index Screen: 5 digits 0.28” high brightness 7 segment LED
Alarm Indicators: 4 high brightess red squares LED
External Control Indicators: 3 high brightness green squares LED
Communicating Indicators: 1 high brightness red square LED
Display Range: -19999~19999 Red Settung Range: -19999~19999 Green MAX. / MIN. saving Reading may correspond with:
PV MAX. HOLD MIN. HOLD Reading by COMM port of RS485
Easily programmed from the front panel Control Functions: Control Output:
Output Types: Standard RELAY Contacts: SPDT; 3A /
115V, 2A / 230V Optional Open Collector output:
4 alarm relays Start Delay, Run Delay, Off Delay Time&
Hysteresis Used to be Differential Alarm Output with HI or
LOW setpoint Used to be DO, output tripped by RS485 directly
Analog Output: DC Voltage 0~10V & DC Current 0~20mA
selection Programmable 15BIT D/A convertor (Response
time: 100mS 0~90% step wave) Auto / Manual Output selection Setting Analog Output by Ccommunication Supply DC 24V Exciting Power for 2-wire sensors
Communicating Output: Communication: RS 485 Protocol: Modbus RTU Mode Baud Rate: 2400 / 4800 / 9600 / 19200 / 38400
bps Communication Address: 1~255 Master-Slave function by communication
External Control Input: CON1 / CON2 / CON3 programming:
BANK1~BANK3 selection Tare Zero Data Hold MAX. HOLD / MIN. HOLD / RESET Used to be DI, External Control Input may
read by RS485 Other Functions: Decimal Point selection Password Protection Memorize by EEPROM over 10 years
Optional Functions: Math functions: Square / Root / Absolutely / Reverse 16 segment for non-linearization Banks for preset:
Bank functions: BANK1 ~ BANK3 Parameters for preset:
DB,SDT,ALM-1~ALM-4,MD1~MD4,HY1~HY4,RD1~RD4,FD1~FD4
ORDERING INFORMATION:
CPM - Optional function — Input Type — 4 — Analogue
output RS 485
port — Excitation supply — Aux. Power
CODE OPTIONAL FUNCTION CODE INPUT
RANGE CODE INPUT RANGE CODE RELAY
OUTPUT CODE CODE EXCITATION SUPPLY CODE AUX. POWER
41 Standard A2 0 ~ 10 mA S1 1.0 mV/V 4 HH/Hi/Lo/LL N N None N None A AC 115/230 V A3 0 ~ 20 mA S2 1.25 mV/V B 0 ~ 10 mA E1 DC 10 V A3 AC 380 V A4 4 ~ 20 mA S3 1.5 mV/V C 0 ~ 20 mA E2 DC 12 V A4 AC 415 V
42 Math functions: reverse/square/ square root/ absolutely V4 0 ~ 5 V S4 2.0 mV/V D 4 ~ 20 mA E3 DC 24 V A24 AC 24 V
43 3 Banks V5 0 ~ 10 V S5 3.0 mV/V 2 0 ~ 5 V EO Specify D24 DC 24 V V6 1 ~ 5 V S6 4.0 mV/V 3 0 ~ 10 V D48 DC 48 V 44 16 segments for
non-linear V7 -10 ~ 0 ~ +10V S7 5.0 mV/V 4 1 ~ 5 V D11 DC 110 V TC Thermocouple S8 10.0 mV/V 5 -10 ~ 0 +10 V AO Specify AC 45 Full function above
including Pt Pt100Ω S9 20.0 mV/V 8 RS 485 DO Specify DC UI Universal input RP 50 ~ 50KΩ
CSEC -1- CPM41-2003/05
EXTERROR DESCRIPTION: INSTALLATION
96.0
48.0
92.0+0.8
44.0+0.8PANEL CUTOUT
FRONT VIEW
Unit: mm
7.0 20 98.0
DIMENSIONS
PANEL CUTOUT: 92+0.8(W) x 44+0.8(H) mm 1.0~8.0 mm
FIXED HOLDER: 120 mm (L) / W M4
Kg/cm2
FUN ENT
CON1CON2CON3
COM HHHILOLL
FRONT PANEL Kg/cm2
FUNENT
CON1 CON2 CON3
COM HH H I
LOL L
Measuring Screen
Control StatusIndications
Operating Keys
Index Screen
Engineer Unit
WIRING DIAGRAM
Analogue O utput
21 22 24 25 23 27 28 26 29 30 31 33 32 34
R 2(HI) R S-485
R x Tx
a c b a c b
R 3(LO )
A+ B - a c a c
R 1(HH ) R 4(LL)
13 11 12 CJ 2 4 5 3 7 8 6 9 1
C O N 3 C O N 1 C O M C O N 2
Excit. Supply External C ontrol
AC 230VAC 115V D C Power
AUX. PO W ER S IG NAL IN PUT
m A
V / TC P t100Ω A B b
RELAY FUNCTIONS
Start Delay: Run Delay / Off Delay Time & Hysteresis:
Start Delay (SD)
Deadband (DB)
HI Setpoint
Alarm Relay ON
Inhibit Inhibit
HI Setpoint
Alarm Relay ON
Hystereis
OFF D
ELAY
RUN
DELA
Y
Differential output with Hi or Low setpoint
HH Relay Mode: Differential mode HH Setpoint = -X HH Relay trip level = Hi setpoint - X
Hi Setpoint
Hi Relay ON
Lo Setpoint
HH Relay ON
- X
Lo Relay
LL Relay Mode: Differential mode LL Setpoint = Y LL Relay trip level = Lo setpoint + Y
Hi Setpoint
Lo Relay ON
Lo Setpoint
LL Relay
Y
Hi Relay ON
ON
KEY FUNCTIONS:
KEY NAME DESCRIPTION ENT ENTER 1. In the MEASURING PAGE, it allows users to switch the ALARM REMINDING (ALM-1, ALM-2…rESEt )
2. In the setting parameters, it allows users to save the data and enter to next parameter
UP 1. In the MEASURING PAGE, it allows usersto return the last ALARM REMINDING (ALM-1, ALM-2…rESEt ) 2. In the setting parameters, it allows users to increase the digits or switch the parameters
DOWN 1. In the setting parameters, it allows users to decrease the digits or switch the parameters 2. In the LEVEL PAGES, it allows users to return the last LEVEL PAGE 3. In the PARAMETER PAGES, it allowsusers to return the last PARAMETER PAGE
SHIFT 1. In the programming parameters, it allows users to move the cursor 2. In the LEVEL PAGES, it allows you to enter this page to select the level functions for setting
ENT + COMPOUND-1 In the LEVEL PAGES & PARAMETER PAGES, press ENT + can return to the MEASURING PAGE, and thedata will not be saved if users do not press ENT to save the revised data
+ COMPOUND-2 In the setting parameters, press + can return to the LEVEL page
NO KEYS In the LEVEL PAGES & PARAMETER PAGES, it will return to MEASURING PAGE automatically when users donot press any keys about 2 minutes
CSEC -2- CPM-41- 2003/05
POWER ON
“INPUT TYPE REMINDING"
“HI & LOW SCALE REMINDING"
"ALM-1 REMINDING"
"ALM-1 SETPOINT"
"ALM-2 REMINDING"
"ALM-2 SETPOINT"
"ALM-3 REMIND"
"ALM-3 SETPOINT"
"ALM-4 REMINDING"
"ALM-4 SETPOINT"
“SELF-DIAGNOSIS”
“MEASURING PAGE"
"ALARM-1 SETPOINT SETTING"
"ALARM-2 SETPOINT SETTING"
"ALARM-3 SETPOINT SETTING"
"ALARM-4 SETPOINT SETTING"
“MIN. SAVING"
“RESET SETTING"
“PASSWORD SETTING"
ENT ENT ENT ENT ENT
ENT ENT ENT
“USER LEVER PAGE"
“INPUT LEVER SETTING"
“OUTPUT LEVER SETTING"
“INPUT TYPE SETTING"
“INPUT SIGNAL SETTING"
“DECIMAL POINT SETTING"
“UNIT SETTING"
“DISPLAY HI SCALE PAGE"
“DISPLAY LOW SCALE PAGE"
“INPUT SIGNAL SPAN SETTING"
“INPUT SIGNAL ZERO SETTING"
“DISPLAY FUNCTION SETTING"
“MOVING AVG. SETTING"
“DISPLAY AVG. SETTING"
“ALARM LEVER SETTING"
“ALARM START DELAY SETTING"
“A/D CONVERTER ERROR ALARM
SETTING"
“ALM_1 MODE SETTING"
“ALM_1 HYSETERESIS
SETTING"
“ALM_1 RUN DELAY SETTING"
“ALM_1 OFF DELAY SETTING"
“ALM_2 MODE SETTING"
“ALM_2 HYSETERESIS
SETTING"
“ALM_2 RUN DELAY SETTING"
“ALM_2 OFF DELAY SETTING"
“ALM_3 MODE SETTING"
" ALM_3 OFF DELAY SETTING "
" ALM_4 MODE SETTING "
" ALM_4 HYSETERESIS
SETTING "
" ALM_4 RUN DELAY SETTING "
" ALM_4 OFF DELAY SETTING "
" ALM_3 HYSETERESIS
SETTING "
" ALM_3 RUN DELAY SETTING "
“ALARM DEAD BAND SETTING"
"CON-1 SETTING"
"CON-2 SETTING"
"CON-3 SETTING"
“ANALOG OUTPUT TYPE
SETTING"
“ANALOG OUTPUT SIGNAL
SETTING"
“ANALOG OUTPUT HI
SCALE SETTING"
“ANALOG OUTPUT LOW
SCALE SETTING"
“ANALOG OUTPUT SPAN ADJUSTMENT"
“ANALOG OUTPUT ZERO ADJUSTMENT"
“ADDRESS SETTING"
“BAUD RATE
SETTING"
“PARITY SETTING"
“CODE SETTING
ENT ENT ENT ENT ENT ENT ENT
ENT ENT ENT ENT
ENT ENT ENT ENT ENT ENT ENT ENT
ENTENTENTENTENT
ENT
“Password Correction" “Default=1000"
“No"
“Yes"
ENT ENT ENT ENT ENT ENT ENT
ENT ENT ENT ENT
ENT ENT ENT ENT ENT
ENT
ENT
ENT
ENT
ENT ENT
ENT
“Pres s + to a llow you re turn the USER LEVEL PAGE“
“MAX. SAVING"
“Press to select the LEVEL”
“Pres s + to a llow you re turn the USER LEVEL PAGE“
“Pres s + to a llow you re turn the USER LEVEL PAGE“
OPERATING DIAGRAM:
CSEC -3- CPM-41- 2003/05
OPERATING SETPS: ALARM REMINDING PAGES: STEP DISPLAY DESCRIPTION OTHER
1 POWER ON
Confrim the wiring and specification, turn on the power. The decription of ERROR CODE, please refer to the Appendant.
2
"SELF-DIAGNOSIS”
Enter to SELF-DIAGNOSIS
3
"INPUT TYPE REMINDING"
Enter to INPUT TYPE REMINDING
4
"HI & LOW SCALE
REMINDING"
Enter to HI & LOW SCALE REMINDING The upper screen is HI SCALE The lower screen is LOW SCALE
5
"ALM-1 REMINDING"
If the SELF-DIAGNOSIS is OK, it will enter to MEASURING PAGE Roll to ALM-1 REMINDING
6
"ALM-1 SETPOINT"
Roll to ALM-1 SETPOINT
7
"ALM-2 REMINDING"
Roll to ALM-2 REMINDING
8
"ALM-2 SETPOINT "
Roll to ALM-2 SETPOINT
9
"ALM-3 REMINDING "
Roll to ALM-3 REMINDING
10
"ALM-3 SETPOINT"
Roll to ALM-3 SETPOINT
11
"ALM-4 REMINDING"
Roll to ALM-4 REMINDING
12
"ALM-4 SETPOIN"
Roll to ALM-4 SETPOINT
1
"ALM-1 REMINDING "
Reture to ALM-1 REMINDING
CSEC -4- CPM-41- 2003/05
ALARM SETTING OPERATING: Press ENT + to allow you return the MEASURING PAGE *STEP U-0* In the parameter setting status, press to allow you return the last page
STEP DISPLAY DESCRIPTION SWITCH OTHERS In the MEASURING PAGE, press ENT to enter the ALARM SETTING
1. Press ENT to enter the ALARM-1 SETPOINT SETTING U-0
"MEASURING PAGE"
ENT
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the value 3. Press ENT to confirm and save the parameter
U-1
"ALARM-1 SETPOINT
SETTING" ENT 4. Press ENT to enter the ALARM-2 SETPOINT SETTING
Default: 0 Range: 0 ~ HI.SC
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the value 3. Press ENT to confirm and save the parameter
U-2
"ALARM-2 SETPOINT
SETTING" ENT 4. Press ENT to enter the ALARM-3 SETPOINT SETTING
Default: 0 Range: 0 ~ HI.SC
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the value 3. Press ENT to confirm and save the parameter
U-3
"ALARM-3 SETPOINT
SETTING" ENT 4. Press ENT to enter the ALARM-4 SETPOINT SETTING
Default: 0 Range: 0 ~ HI.SC
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the value 3. Press ENT to confirm and save the parameter
U-4
"ALARM-4 SETPOINT
SETTING" ENT 4. Press ENT to enter the MAX. SAVING PAGE
Default: 0 Range: 0 ~ HI.SC
1. Press ENT to enter the MIN. SAVING PAGE
U-5
"MAX. SAVING PAGE"
ENT
1. Press ENT to enter the RESET SETTING
U-6
"MIN. SAVING PAGE"
ENT
1. Press and the LED will be flashed and can be set
2. Press to move the cursor, press or to change the
parameters
3. Press ENT to confirm and save the parameter U-7
"RESET SETTING"
ENT 4. Press ENT to enter the PASSWORD SETTING
Default: NONE Range: NONE / RESET / A.SAVE NONE: Max & Min don’t reset RESET: Reset Max. & Min. to 0 A.SAVE: Save the values per 10 minutes; when users return to the power on, the records will not dispear
1. Press , and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the value 3. Press ENT to confirm and save the parameter (Password error will
return the MEASUREMENT PAGE. Password correct will enter to the USER LEVEL PAGE)
U-8
"PASSWORD
SETTING" ENT
Default: 1000 Range: 00000 ~ 20000 Change the password please refer to STEP B-13, and don’t forget the new password
L-0
"USER LEVEL PAGE"
Please refer to USER LEVEL OPERATING
CSEC -5- CPM-41- 2003/05
USER LEVEL OPERATING: 【*Please enter to the USER LEVEL when you use the new machine*】 Press ENT + to allow you return the MEASURING PAGE *STEP U-0* Press + to allow you return the USER LEVEL PAGE *STEP L-0* In the parameter setting status, press to allow you return the last page
STEP DISPLAY DESCRIPTION SWITCH OTHERS 1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the value 3. Press ENT to confirm and save the parameter and enter to the USER
LEVEL PAGE
U-8
" PASSWORD
SETTING " ENT
Default: 1000 Range: 00000 ~ 20000 Change the password please refer to STEP B-13, and don’t forget the new password
1. Press and the LED will be flashed and can be set
2. Press to select the LEVEL PAGES【LEVEL Input / Output / Alarm】
L-0
“USER LEVEL PAGE”
Range: LEvEL input:【INPUT LEVEL SETTING】 LEvEL oUPUt:【OUTPUT LEVEL SETTING】 LEvEL ALArM:【ALARM LEVEL SETTING】
1. Press to select the【INPUT LEVEL SETTING】
2. Press ENT to enter the INPUT LEVEL SETTING *STEP A-0*
L-1
【INPUT LEVEL
SETTING】
1. Press or to select the【OUTPUT LEVEL SETTING】
2. Press ENT to enter the OUTPUT LEVEL SETTING *STEP B-0*
L-2
【OUTPUT LEVEL
SETTING】
1. Press or to select the【ALARM LEVEL SETTING】
2. Press ENT to enter the ALARM LEVEL SETTING *STEP C-0*
L-3
【ALARM LEVEL
SETTING】
INPUT LEVEL OPERATING: Press ENT + to allow you return the MEASURING PAGE *STEP U-0* Press + to allow you return the USER LEVEL PAGE *STEP L-0* In the parameter setting status, press to allow you return the last page
STEP DISPLAY DESCRIPTION SWITCH OTHERS 1. In the LEvEL USEr, press the screen will be flashed and can be set
2. Press to select theLEvEL inPUT【INPUT LEVEL SETTING】
A-0
【INPUT LEVEL
SETTING】 ENT
3. Press ENT to enter the INPUT TYPE SETTING
1. Press + then press the screen will be flashed and can be set
2. Press or to select the INPUT TYPE 3. Press ENT to confirm and save the parameter
A-1
"INPUT TYPE
SETTING" ENT 4. Press ENT to enter the INPUT SIGNAL SETTING
Default: LINER Selecting Types: Liner / RTD / Thermocouple LinEr: Analog input rtd: RTD input tC: Thermocouple input
1. Press + then press the screen will be flashed and can be set
2. Press or to select the INPUT SIGNAL 3. Press ENT to confirm and save the parameter
A-2
"INPUT SIGNAL
SETTING" ENT 4. Press ENT to enter the DECIMAL POINT SETTING
Default: Liner: 20mA Range: Liner: 20mA /10V / 100mV /
1Kohm RTD: DIN Pt100 / JIS Pt100 TC: K / J / E / T / R / S / B / N / C
1. Press and the screen will be flashed and can be set
2. Press or to select the position of DECIMAL POINT 3. Press ENT to confirm and save the parameter
A-3
"DECIMAL POINT
SETTING" ENT 4. Press ENT to enter the UNIT SETTING
Default: 000.00 Range: 00000 / 0000.0 /
000.00 / 00.000 / 0.0000
CSEC -6- CPM-41- 2003/05
STEP DISPLAY DESCRIPTION SWITCH OTHERS
1. In the RTD or TC INPUT, press the screen will be flashed and can be set
2. Press or to select the °C or °F 3. Press ENT to confirm and save the parameter
A-4
"UNIT SETTING"
ENT 4. Press ENT to enter the DISPLAY HI SCALE PAGE
Default: Liner: mA RTD & TC: °C (or °F) Selection
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
A-5
"DISPLAY HI SCALE
PAGE" ENT 4. Press ENT to enter the DISPLAY LOW SCALE PAGE
Default: 20.00 Range: 0 ~ 19999
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
A-6
"DISPLAY LOW SCALE
PAGE" ENT 4. Press ENT to enter the INPUT SIGNAL SPAN SETTING
Default: 0.00 Range: -19999 ~ HI.SC
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
A-7
“INPUT SIGNAL SPAN
SETTING" ENT 4. Press ENT to enter the INPUT SIGNAL ZERO SETTING
Default: 20.00 Range: mA input: -20.00 ~ +20.00 V input: -10.00 ~ +10.00 EX: Input is set by 4~20mA, Span is 20.00
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
A-8
"INPUT SIGNAL ZERO
SETTING" ENT 4. Press ENT to enter the DISPLAY FUNCTION SETTING
Default: 0.00 Range: mA input: -20.00 ~ +20.00 V input: -10.00 ~ +10.00 EX: Input is set by 4~20mA, Zero is 4.00
1. Press and the right side LED will be flashed and can be set
2. Press or to select the DISPLAY FUNCTION 3. Press ENT to confirm and save the parameter
A-9
" DISPLAY FUNCTION
SETTING " ENT 4. Press ENT to enter the MOVING AVG. SETTING
Default: PV Range:PV / MAX / MIN / COMM When the setting is MAX( or Min), it means the display is MaxHold( or Min. Hold); if the setting is COMM, it means the display is reading by RS485 PORT
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
A-10
" MOVING AVG.
SETTING " ENT 4. Press ENT to enter the DISPLAY AVG. SETTING
Default: 50 Range: 0 ~ 1000
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
A-11
" DISPLAY AVG.
SETTING " ENT 4. Press ENT to return the INPUT type SETTING
Default: 10 Range: 0 ~ 1000 When the DISPLAY AVG. is higher, the display is more stable; but the response time will be slow
A-1
" INPUT TYPE
SETTING "
OUTPUT LEVEL OPERATING: Press ENT + to allow you return the MEASURING PAGE *STEP U-0* Press + to allow you return the USER LEVEL PAGE *STEP L-0* In the parameter setting status, press to allow you return the last page
STEP DISPLAY DESCRIPTION SWITCH OTHERS 1. In the LEvEL USEr, press the screen will be flashed and can be set
2. Press to select the LEvEL oUPUT【OUTPUT LEVEL SETTING】
B-0
【OUTPUT LEVEL
SETTING】 ENT
3. Press ENT to enter the CON-1 SETTING
CSEC -7- CPM-41- 2003/05
STEP DISPLAY DESCRIPTION SWITCH OTHERS
1. Press and the screen will be flashed and can be set
2. Press or to select the parameters 3. Press ENT to confirm and save the parameter
B-1
" CON-1 SETTING "
ENT 4. Press ENT to enter the CON-2 SETTING 1. Press and the screen will be flashed and can be set
2. Press or to select the parameters 3. Press ENT to confirm and save the parameter
B-2
" CON-2 SETTING "
ENT 4. Press ENT to enter the CON-3 SETTING 1. Press and the screen will be flashed and can be set
2. Press or to select the parameters 3. Press ENT to confirm and save the parameter
B-3
" CON-3 SETTING "
ENT 4. Press ENT to enter the ANALOG OUTPUT TYPE SETTING
Default: NONE Range: NONE / A-M / TARE /
Data HOLD / RESET / DI NONE: No functions A-M: Auto or Manual Analog output selection TARE: Compel to reset to 0 D.HOLD: Data Hold function RESET: MAX. & MIN. reset to 0 DI: External Control Input may read by RS485
1. Press and the screen will be flashed and can be set
2. Press or to select the ANALOG OUTPUT TYPE 3. Press ENT to confirm and save the parameter
B-4
" ANALOG OUTPUT
TYPE SETTING" ENT 4. Press ENT to enter the ANALOG OUTPUT SIGNAL SETTING
Default: AUTO Range: AUTO / MENU AUTO: Correspond with Full Scale Ratio for output MANU: According to Manual Output Setting Ratio for output
1. Press + then press , the screen will be flashed and can be set
2. Press or to select the ANALOG OUTPUT SIGNAL 3. Press ENT to confirm and save the parameter
B-5
"ANALOG OUTPUT SIGNAL SETTING"
ENT 4. Press ENT to enter the ANALOG OUTPUT HI SCALE SETTING
Default: 4-20mA Range: 4-20mA / 0-20mA/ 0-10V /
0-5V / 1-5V
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
B-6
"ANALOG OUTPUT HI
SCALE SETTING" ENT 4. Press ENT to enter the ANALOG OUTPUT LOW SCALE SETTING
Default: 0.00% Range: 0 ~ 100.00% EX: The Output is set by4~20mA, and the display is set by 0~1000.0; if Ao.Hi.C is set by 50.00%, then the display is 500.0, the Output is 20mA
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
B-7
"ANALOG OUTPUT
LOW SCALE SETTING"
ENT 4. Press ENT to enter the ANALOG OUTPUT SPAN SETTING
Default: 0.00% Range: 0 ~ 100.00% EX: The Output is set by4~20mA, and the display is set by 0~1000.0; if Ao.Lo.C is set by 0.00%, then the display is 0.0, the Output is 4mA
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
B-8
"ANALOG OUTPUT SPAN
FINE ADJUSTMENT" ENT 4. Press ENT to enter the ANALOG OUTPUT ZERO SETTING
Default: 0 Range: -4000 ~ 4000 ANALOG OUTPUT HI SCALE has errors, it allows user to get fine adjustment the SPAN
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
B-9
"ANALOG OUTPUT ZERO
FINE ADJUSTMENT" ENT 4. Press ENT to enter the ADDRESS SETTING
Default: 0 Range: -4000 ~ 4000 ANALOG OUTPUT LOW SCALE has errors, it allows user to get fine adjustment adjust the ZERO
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
B-10
"ADDRESS SETTING"
ENT 4. Press ENT to enter the BAUD RATE SETTING
Default: 1 Range: 1 ~ 255
CSEC -8- CPM-41- 2003/05
STEP DISPLAY DESCRIPTION SWITCH OTHERS
1. Press and the screen will be flashed and can be set
2. Press or to select the BAUD RATE 3. Press ENT to confirm and save the parameter
B-11
"BAUD RATE
SETTING" ENT 4. Press ENT to enter the PARITY SETTING
Default: 9600 Range: 2400 / 4800 / 9600 / 19200
/ 38400
1. Press and the screen will be flashed and can be set
2. Press or to select the PARITY 3. Press ENT to confirm and save the parameter
B-12
"PARITY SETTING"
ENT 4. Press ENT to enter the CODE SETTING
Default: NONE Range: NONE / EVEN / ODD
1. Press and the screen will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
B-13
"CODE SETTING"
ENT 4. Press ENT to return the CON-1 SETTING
Default: 1000 Range: 0 ~ 20000 Please remember the new CODE in case for next time to using
B-1
"CON-1 SETTING"
ENT
ALARM LEVEL OPERATING: Press ENT + to allow you return the MEASURING PAGE *STEP U-0* Press + to allow you return the USER LEVEL PAGE *STEP L-0* In the parameter setting status, press to allow you return the last page
STEP DISPLAY DESCRIPTION SWITCH OTHERS 1. In the LEvEL USEr, press , the screen will be flashed and can be set
2. Press to select the LEvEL ALArM【ALARM LEVEL SETTING】
C-0
【ALARM LEVEL
SETTING】 ENT
3. Press ENT to enter the ALARM DEAD BAND SETTING
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
C-1
"ALARM DEAD BAND
SETTING" ENT 4. Press ENT to enter the ALARM START DELAY SETTING
Default: 0.00% Range: -50.00 ~ +50.00
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter C-2
"ALARM START
DELAY SETTING" ENT
4. Press ENT to enter the A/D SYSTEM ERROR ALARM SETTING
Default: 0.00.0 Range: 99’59”,9 (min.sec.0)
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, different places mean different relays for
output (Refer to the diagram of right side) , press to change the values to 1
3. Press ENT to confirm and save the parameter
C-3
"A/D CONVERTER
ERROR ALARM SETTING"
ENT 4. Press ENT to enter the ALM_1 MODE SETTING
Default: 00000 Range: 01111(BINARY)
1. Press and the screen will be flashed and can be set
2. Press or to select the ALM_1 MODE 3. Press ENT to confirm and save the parameter C-4
"ALM_1 MODE
SETTING" ENT
4. Press ENT to enter the ALM_1 HYSTERESIS SETTING
Default: HI Range: HI/LO/DIF.HI/DIF.LO/DO/NONE HI: Over the setpoint, the relay trips LO: Under the setpoint, the relay trips DIF.HI: Compare with ALM_2, if it over the setpoint, the relay trips DIF.LO: Compare with ALM_2, if it under the setpoint, the relay trips DO: Output tripped by communication
Alarm Dead Band
Start Delay Time
Dead Band(db)
Hi Setting
Alarm Relay ON
Inhibit Inhibit
Start Delay Time
Start Delay Time
Dead Band(db)
Hi Setting
Alarm Relay ON
Inhibit Inhibit
AL-1: AL-2: AL-3: AL-4:
The setting is 00001, the ALM-1 (Relay1) output The setting is 00010, the ALM-2 (Relay2) output The setting is 00100, the ALM-3 (Relay3) output The setting is 01000, the ALM-4 (Relay4) output
CSEC -9- CPM-41- 2003/05
CSEC -10- CPM-41- 2003/05
STEP DISPLAY DESCRIPTION SWITCH OTHERS1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
C-5
" ALM_1 HYSTERESIS
SETTING" ENT 4. Press ENT to enter the ALM_1 RUN DELAY SETTING
Default: 0.00% Range: -50.00 ~ +50.00 Run / Off Delay & Hysteresis
Hi Setting
Run D
elay T
ime
Alarm Relay ON
Hysteresis
Off D
elay T
ime
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
C-6
"ALM_1 RUN DELAY
SETTING" ENT 4. Press ENT to enter the ALM_1 OFF DELAY SETTING
Default: 0.00.0 Range: 99’59”,9 (min.sec.0) Run / Off Delay & Hysteresis
Hi Setting
Run D
elay T
ime
Alarm Relay ON
Hysteresis
Off D
elay T
ime
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
C-7
"ALM_1 OFF DELAY
SETTING" ENT 4. Press ENT enter to the ALM_2 MODE SETTING
Default: 0.00.0 Range: 99’59”,9 (min.sec.0) Run / Off Delay & Hysteresis
Hi Setting
Run D
elay T
ime
Alarm Relay ON
Hysteresis
Off D
elay T
ime
1. Press and the screen will be flashed and can be set
2. Press or to select the ALM_2 MODE 3. Press ENT to confirm and save the parameter
C-8
"ALM_2 MODE
SETTING" ENT 4. Press ENT to enter the ALM_2 HYSTERESIS SETTING
Default: HI Range: HI/LO/DO/NONE HI: Over the setpoint, the relay trips LO: Under the setpoint, the relay trips DO: Output tripped by communication
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
C-9
"ALM_2 HYSTERESIS
SETTING" ENT 4. Press ENT to enter the ALM_2 RUN DELAY SETTING
Default: 0.00% Range: -50.00~+50.00 Please refer to STEP C-5 (ALM_1 HYSTERESIS SETTING) the diagram of right side
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
C-10
"ALM_2 RUN DELAY
SETTING" ENT 4. Press ENT to enter the ALM_2 OFF DELAY SETTING
Default: 0.00.0 Range: 99’59”,9( . .0) Please refer to STEP C-6 (ALM_1 RUN DELAY SETTING) the diagram of right side
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
C-11
"ALM_2 OFF DELAY
SETTING" ENT 4. Press ENT enter to the ALM_3 MODE SETTING
Default: 0.00.0 Range: 99’59”,9(min.sec.0) Please refer to STEP C-7 (ALM_1 OFF DELAY SETTING) the diagram of right side
1. Press and the screen will be flashed and can be set
2. Press or to select the ALM_3 MODE 3. Press ENT to confirm and save the parameter
C-12
"ALM_3 MODE
SETTING" ENT 4. Press ENT to enter the ALM_3 HYSTERESIS SETTING
Default: LO Range: HI / LO / DO / NONE HI: Over the setpoint, the relay trips LO: Under the setpoint, the relay trips DO: Output tripped by communication
1. Press , and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
C-13
" ALM_3 HYSTERESIS
SETTING" ENT 4. Press ENT to enter the ALM_3 RUN DELAY SETTING
Default: 0.00% Range: -50.00 ~ +50.00 Please refer to STEP C-5 (ALM_1 HYSTERESIS SETTING) the diagram of right side
1. Press , and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values
3. Press ENT to confirm and save the parameter
C-14
"ALM_3 RUN DELAY
SETTING" ENT 4. Press ENT to enter the ALM_3 OFF DELAY SETTING
Default: 0.00.0 Range: 99’59”,9(min.sec.0) Please refer to STEP C-6 (ALM_1 RUN DELAY SETTING) the diagram of right side
CSEC -11- CPM-41- 2003/05
STEP DISPLAY DESCRIPTION SWITCH OTHERS
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and the parameter
C-15
"ALM_3 OFF DELAY
SETTING" ENT 4. Press ENT enter to the ALM_4 MODE SETTING
Default: 0.00.0 Range: 99’59”,9 (min.sec.0) Please refer to STEP C-7 (ALM_1 OFF DELAY SETTING) the diagram of right side
1. Press and the screen will be flashed and can be set
2. Press or to select the ALM_4 MODULE 3. Press ENT to confirm and the parameter
C-16
"ALM_4 MODE
SETTING" ENT 4. Press ENT to enter the ALM_4 HYSTERESIS SETTING
Default: HI Range: HI/LO/DIF.HI /DIF.LO/DO/NONE HI: Over the setpoint, the relay trips LO: Under the setpoint, the relay trips DIF.HI: Compare with ALM_3, if it over the setpoint, the relay trips DIF.LO: Compare with ALM_3, if it under the setpoint, the relay trips DO: Output tripped by communication
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
C-17
" ALM_4 HYSTERESIS
SETTING" ENT 4. Press ENT to enter the ALM_4 RUN DELAY SETTING
Default: 0.00% Range: -50.00~+50.00 Please refer to STEP C-5 (ALM_1 HYSTERESIS SETTING) the diagram of right side
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
C-18
"ALM_4 RUN DELAY
SETTING" ENT 4. Press ENT to enter the ALM_4 OFF DELAY SETTING
Default: 0.00.0 Range: 99’59”,9(min.sec.0) Please refer to STEP C-6 (ALM_1 RUN DELAY SETTING) the diagram of right side
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
C-19
"ALM_4 OFF DELAY
SETTING" ENT 4. Press ENT to return the ALARM DEAD BAND SETTING
Default: 0.00.0 Range: 99’59”,9(min.sec.0) Please refer to STEP C-7 (ALM_1 OFF DELAY SETTING) the diagram of right side
C-1
"ALARM DEAD BAND
SETTING" ENT
MEASURING COMPENSATION OPERATING STEPS: STEP DISPLAY DESCRIPTION SWITCH OTHERS
In the MEASURING PAGE, press ENT over 5 sec, it will enter the DISPLAY LOW SCALE COMPENSATION SETTING
P-0
"MEASURING PAGE"
ENT
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
P-1
"DISPLAY LOW SCALE
COMPENSATION SETTING"
ENT 4. Press ENT to enter the DISPLAY HI SCALE OFFSET SETTING
Default: 0.00% Range: - 50 ~ +50% F.S Display Low Scale Offset
Hi Scaling
Low Scaling
Low Offset
Standard
Input Low Input Hi
Hi Offse
1. Press and the right side LED will be flashed and can be set
2. Press to move the cursor, press or to change the values 3. Press ENT to confirm and save the parameter
P-2
"DISPLAY HI SCALE
COMPENSATION SETTING"
ENT 4. Press ENT to enter the DISPLAY SOFTWARE VERSION
Default: 0.00% Range: - 50 ~ +50% F.S Display Hi Scale Offset
Hi Scaling
Low Scaling
Low Offset
Standard
Input Low Input Hi
Hi Offse
Press ENT to enter the FUNCTIONS LOCK SETTING
P-3
"DISPLAY SOFTWARE
VERSION" ENT
STEP DISPLAY DESCRIPTION SWITCH OTHERS
Press ENT to enter the FUNCTIONS LOCK SETTING P-3
"DISPLAY SOFTWARE
VERSION" ENT
1. Press , and the right side LED will be flashed and can be set 2. Press to move the cursor, different places mean different functions
for skip (Refer to the diagram of right side) , press to change the values to 1(Lock) or 0(Unlock)
3. Press ENT to confirm and save the parameter
P-4
"FUNCTIONS LOCK
SETTING" ENT 4. Press ENT to return the MEASURING PAGE
Default: 01111 Range: 01111(BINARY)
P-0
"MEASURING PAGE"
ENT
Alarm Setting 1:Skip 0:Unskip Input Setting 1:Skip 0:Unskip Output Setting 1:Skip 0:Unskip Alarm Setting 1:Skip 0:Unskip None
ERROR CODE OF SELF-DIAGNOSIS: STEP DESCRIPTION DISPLAY SWITCH OTHERS
ERROR CODE OF SELF-DIAGNOSIS: : A/D circuits error (Please return to the Factory)
: Display postive overflow (Signals over the range) (Please check the Input Signals)
: Display negative overflow (Signals under the range) (Please check the Input Signals)
SOFTWARE OPTIONAL FUNCTIONS: (NEEDS TO EXTRA CHARGES) ITEM MODEL NO. DESCRIPTION OTHERS
Option 1 CPM-42 Math functions NON: None(Default), SQU: Square, ROOT: Root ABS: Absolutely, INVT: Reverse
Option 2 CPM-43 3 Banks for preset BANK1 ~ BANK3 Option 3 CPM-44 Non-Lineariztion 16 segment for non-linearization
Option 4 CPM-45 All functions included Option 1 + Option 2 + Option 3
HARDWARE OPTIONAL FUNCTIONS: (NEEDS TO EXTRA CHARGES) ITEM DESCRIPTION OTHERS
Option A Analogue Output 0~10Vdc / 0~20mAdc selection, 15 BIT DAC can be programmed
Option B Communication Output RS-485 / RS-232C, MODBUS RTU Mode
CSEC -12- CPM-41- 2003/05