CPAN-U 17÷51 - Clivetclivet.lt/wp-content/uploads/2012/03/CPAN-U-17-51.pdf · PACKAGED CPAN-U...

2
PACKAGED CPAN-U 17÷51 ELFOFRESH LARGE CPAN-U 17 FC R-410A AIR 4 ELFOFresh Large units are designed to guarantee ideal air exchange rates in shops and offices. Their main characteristics include: 4 cooling, heating and humidification of outdoor air with only minimal energy consumption thanks to Free-Cooling and an exclusive Active Thermodynamic Heat Recovery that recovers heat from extracted air and returns it to the incoming fresh air; 4 electronic filtration control for guaranteed purity of incoming fresh air and effective removal of airborne dust (optional). Make-up unit, full fresh air With return/exhaust and thermodynamic heat recovery Reversible heat pump Indoor installation Air flow rate from 330 to 920 l/s Heating-Cooling Air cooled Indoor inst. Horizontal inst. Refrig. R-410A Herm. Rotary (17÷31) Free-Cooling Active Thermodynamic Heat Recovery Herm. Scroll (41-51) functions and features available configurations HID-P1 room thermostat for remote wall mounting. Main functions: 4 manual or automatic summer/winter selection 4 temperature setting 4 ECO mode (automatic day/night heat regulation).

Transcript of CPAN-U 17÷51 - Clivetclivet.lt/wp-content/uploads/2012/03/CPAN-U-17-51.pdf · PACKAGED CPAN-U...

Page 1: CPAN-U 17÷51 - Clivetclivet.lt/wp-content/uploads/2012/03/CPAN-U-17-51.pdf · PACKAGED CPAN-U 17÷51 ELFO FRESH LARGE CPAN-U 17 AIR R-410A FC ELFOFresh Large units are designed to

PACK

AG

ED

CPAN-U 17÷51

ELFOFRESH LARGE

CPAN-U 17

FCR-410AAIR

4

ELFOFresh Large units are designed to guarantee ideal air exchange rates in shops and offices. Their main characteristics include:

4 cooling, heating and humidification of outdoor air with only minimal energy consumption thanks to Free-Cooling and an exclusive Active Thermodynamic Heat Recovery that recovers heat from extracted air and returns it to the incoming fresh air;

4 electronic filtration control for guaranteed purity of incoming fresh air and effective removal of airborne dust (optional).

Make-up unit, full fresh airWith return/exhaust and thermodynamic heat recoveryReversible heat pump

Indoor installationAir flow rate from 330 to 920 l/s

Heating-Cooling Air cooled Indoor inst. Horizontal inst. Refrig. R-410A Herm. Rotary(17÷31)

Free-Cooling Active Thermodynamic Heat Recovery

Herm. Scroll(41-51)

functions and features

available configurations

HID-P1 room thermostat for remote wall mounting. Main functions:4 manual or automatic summer/winter

selection4 temperature setting4 ECO mode (automatic day/night heat

regulation).

Guida_2011_v26.indd 152Guida_2011_v26.indd 152 21/03/11 16:5221/03/11 16:52

Page 2: CPAN-U 17÷51 - Clivetclivet.lt/wp-content/uploads/2012/03/CPAN-U-17-51.pdf · PACKAGED CPAN-U 17÷51 ELFO FRESH LARGE CPAN-U 17 AIR R-410A FC ELFOFresh Large units are designed to

17 21 25 31 41 511503 1503 1503 1503 1503 1503950 950 950 950 950 950443 443 518 518 668 668

4 900 900 900 900 900 900700 700 700 700 700 700135 145 175 185 215 225

17 21 25 31 41 514 kW 6,18 7,62 8,64 10,9 12,4 15,9

kW 2,50 3,00 3,30 3,80 5,40 7,20- 3,60 3,60 3,90 3,80 4,50 4,10

4 kW 6,75 8,26 9,19 11,9 13,2 16,9kW 2,50 3,00 3,30 3,80 5,40 7,20- 5,20 4,90 5,20 5,30 6,50 6,10l/s 330 390 470 610 690 920Pa 190 175 300 180 270 340l/s 300 360 440 550 640 860Pa 180 165 290 210 250 360- 1 ROT 1 SCROLLdB(A) 53 55 57 59 61 62V/Ph/Hz 230/1/50 400/3/50 + N

BA

A2

C

A1

■ Accessories supplied separately.

The above data refer to standard units.

CAUTION! For trouble-free operation of the unit it is essential to maintain the clearances in green.

(1) Coil inlet air temperature in discharge 27°C D.B. - 19°C W.B.; external air temperature 35°C D.B. - 24°C W.B.; external air temperature 35°C D.B. - 24°C W.B.; the EER refers to the compressors only

(2) Coil inlet air temperature in discharge: 20°C D.B. - 12°C W.B.; external air temperature 7°C D.B. - 6°C W.B.; the COP refers to the compressors only

(3) ROT = rotary compressor(4) Sound levels refer to units with full load under nominal test conditions. The sound pressure is measured at

1 m from the external surface of the unit in open field conditions.

Key to symbols:

Data referred to the following conditions:

Sizes Length (A) mmWidth (B) mmHeight (C) mm

(A1) mm(A2) mm

Weight in oper. kg

SizesCooling capacity (1)Total input (1)EER (1)Heating capacity (2)Total input (2)COP (2)

Supply air flow rateSupply working headDischarge air flow rateDischarge working headNumber and type of compressors (3)Sound pressure level (4)Power supply

4 Copper/copper condenser coils4 Copper/copper evaporator coils4 Additional water coil4 Modulating three-way valve4 2 kW pre-heating electric heaters4 3 kW pre-heating electric heaters4 4,5 kW pre-heating electric heaters4 Class G4 air filters in discharge4 Electronic filters4 3 kg/h immerse electrode steam humidifier

4 5 kg/h immerse electrode steam humidifier4 8 kg/h immerse electrode steam humidifier4 Air side dirty filters differential pressure switch4 RS485 remote communication serial port (MODBUS)

■ 4 Service handset for local control with 1,5-metre cable■ 4 Service hand-held keypad for local control with 20-metre cable■ 4 Remote control with remote microprocessor control

accessories

dimensions and clearances

technical data

Guida_2011_v26.indd 153Guida_2011_v26.indd 153 15/03/11 17:1515/03/11 17:15

REF

-DG

11C

001G

B-0

0

prosset
Casella di testo
Data contained in this document are not binding and may be changed by the Manufacturer without notice. No part of this publication may be reproduced
prosset
Casella di testo
www.clivet.com