Set No.
Project Location Maps
73513-16001ATetra Tech Engineers, Architects & Landscape Architects, P.C.
ArchitectureEngineeringPlanningHighPerformanceFacilitiesfo
r
County of Oswego Window Replacements:Public Safety Center - 39 Churchill Road, Oswego, NYHealth Complex - 74 Bunner Street, Oswego, NYLegislative Office Building - 46 East Bridge Street, Oswego, NY
County Of OswegoOswego, NY 13126
N
5 DRAWING REVISION NUMBER
CENTER LINE
CUT LINE
NORTH ARROW
PHOTO
DETAIL
WALL SECTION
STANDARD REFERENCE BUBBLE
DRAWING NUMBER
DETAIL NUMBER
DRAWING TITLE & SCALE
METAL, STEEL
CONCRETE
BRICK
CONCRETE MASONRY UNITS
PLYWOOD
ROUGH WOOD
INSULATION (LOOSE OR BATT)
RIGID INSULATION
Floor Plan1/8"=1'-0"
N
NOTE: REFER TO FINISH PLANS FOR ROOM FINISH KEYAND ADDITIONAL ABBREVIATIONS
AAC ASBESTOS ABATEMENT CONTRACTORAAD AUTOMATIC AIR DAMPERAB ANCHOR BOLT, AIR BARRIERAC AIR CONDITIONING, ALTERNATING CURRENTACCMP ASPHALT COATED CORR METAL PIPEACM ASBESTOS CONTAINING MATERIALACT ACOUSTICAL CEILING TILEACU AIR CONDITIONING UNITAD AREA DRAINADA AMERICAN DISABILITIES ACTADD ADDENDUMADDL ADDITIONALADDN ADDITIONADH ADHESIVEADJ ADJACENTADR ACCESS DOORAESS ARCH EXPOSED STRUCTURAL STEELAFF ABOVE FINISH FLOORAH ACCESS HATCHAHU AIR HANDLING UNITAIB AIR INFILTRATION BARRIERALT ALTERNATEALTB ACOUSTICALLY LINED TRANSFER BOXALTN ALTERATION ALUM ALUMINUMAMP AMPEREANOD ANODIZEDANT ACID NEUTRALIZATION TANKAP ACCESS PANELAPPROX APPROXIMATE (LY)APC ARCHITECTURAL PRECAST CONCRETEARCH ARCHITECT (URAL)A/S AIR SEPARATORASB ASBESTOSASPH ASPHALTATV ATMOSPHERIC VENTAUD AUDITORIUMAUTO AUTOMATICAV ACID VENTAVE AVERAGEAVTR ACID VENT THRU ROOFAW ACID WASTE
B BOILER, BRICK, BOTTOMBB BASKETBALLBBD BOILER BLOWDOWNBC BOTTOM OF CURBBCU BLOWER COIL UNITBCX BOTTOM CHORD EXTENSIONBD BOARDBDD BACKDRAFT DAMPERBFP BACK FLOW PREVENTERBG BOTTOM GRILLEBIT BITUMINOUSBLDG BUILDING BLOCKBLK BLOCKING BLKGBM BEAMBO BY OTHERSBOD BOTTOM OF DUCTBOF BOTTOM OF FOOTINGBOS BOTTOM OF STEELBOT BOTTOMBPL BEARING PLATEBR BOTTOM REGISTERBRDG BRIDGINGBRG BEARINGBRK BRICK
BRSH BRICKSHELFBRZ BRONZEBS BOTH SIDES, BOTTOM OF STAIRBSMT BASEMENTBSPL BACKSPLASHBT BENTBTU BRITISH THERMAL UNITSBTUH BRITISH THERMAL UNITS PER HOURBUR BUILT-UP ROOFINGBW BOTTOM OF WALLBWC BACK WATER CHECK VALVE
C1 CARPET TYPE 1C CONDUIT, CONVECTOR, CONDENSOR,
COMMONCA COMPRESSED AIRCAB CABINETCATV CABLE TELEVISIONCB CATCH BASIN, CIRCUIT BREAKER, CHALKBOARDCCTV CLOSED CIRCUIT TELEVISIONCD CEILING DIFFUSER, CONDENSATE DRAINCEM CEMENTCER CERAMIC CF CUBIC FEET, CEILING FANCFM CUBIC FEET PER MINUTECFMF COLD FORMED METAL FRAMINGCFT1 CERAMIC FLOOR TILE TYPE 1CG CEILING GRILLECHAN CHANNELCHUV CEILING HUNG UNIT VENTILATORCI CAST IRONCIP CAST IN PLACECIRC CIRCUMFERENCECJ CONTROL JOINTCL CENTER LINECLG CEILINGCLKG CAULKINGCLL CONTRACT LIMIT LINECLR CLEAR (ING) (ENCE)CLRM CLASSROOMCMP CORRUGATED METAL PANELCMT CERAMIC MOSAIC TILECMU CONCRETE MASONRY UNITCO CLEAN OUTCODP CLEAN OUT DECK PLATECOL COLUMNCOMB COMBINATIONCOMP COMPRESS (ED) (ION) (IBLE), COMPOSITECONC CONCRETECOND CONDENSATECONN CONNECTIONCONST CONSTRUCTIONCONT CONTINOUSCONTR CONTRACT (OR)COORD COORDINATECORR CORRUGATED, CORRIDORCOWP CLEAN OUT WALL PLATECPVC CHLORINATED POLY VINYL CHLORIDECR CEILING REGISTERCRS COURSE (S)CSK COUNTERSINKCSMT CASEMENTCT COMPUTER TERMINAL, CERAMIC BASE TILECTD COATEDCTOP COUNTER TOPCTR CENTERCU CUBICCUH CABINET UNIT HEATERCV CONVECTOR, CURB VALVECW COLD WATER
CWR CHILLED WATER RETURNCWS CHILLED WATER SUPPLYCWT1 CERAMIC WALL TILE TYPE 1
D1 DANCE FLOORING TYPE 1D DIESEL FUEL, DEPTHDB DRY BULBDC DIRECT CURRENTDDC DIRECT DIGITAL CONTROLDE DELONIZED WATERDEG DEGREESDEMO DEMOLISHDEP DEPRESS (ED) (ION)DET DETAIL (ED)DF DRINKING FOUNTAINDH DOUBLE HUNGDHU DEHUMIDIFICATION UNITDI DROP INLET, DUCTILE IRON, DISTILLED WATERDIA DIAMETERDIAG DIAGONALDIM DIMENSIONDISP DISPENSERDIST DISTANCEDIV DIVISIONDL DEAD LOADDN DOWNDO DITTODP DAMPPROOF (ING)DPR DAMPERDR DOOR, DEEP RIBDWG DRAWINGDS DOWNSPOUT, DRAINAGE STRUCTUREDT DRAIN TILEDTA DOVETAIL ANCHORDTL DETAILDW DUMBWAITER, DISHWASHERDWL DOWELDWR DRAWER
E EASTEA EXHAUST AIR, EACHEAT ENTERING AIR TEMPERATUREEB EXPANSION BOLTEC ELECTRICAL CONTRACTORECF ENHANCED CONCRETE FLOORINGEIFS EXTERIOR INSULATION FINISH SYSTEMEF EACH FACE, EXHAUST FANEJ EXPANSION JOINTELEC ELECTRIC (AL)ELEM ELEMENTELEV ELEVATION, ELEVATOREM EMERGENCYEMT ELECTRICAL METALLIC TUBINGENC ENCLOSUREEOD EDGE OF DECKEOS EDGE OF SLABEQ EQUAL, EQUIVALENTEQC EQUIPMENT CONTRACTOREQUIP EQUIPMENTES EXPOSED SURFACE, EXPOSED STRUCTUREESF ELASTIC SHEET FLASHINGESM ELASTIC SHEET MEMBRANEEW EACH WAYEWC ELECTRIC WATER COOLEREWT ENTERING WATER TEMPERATUREEXH EXHAUSTEXG EXISTINGEXP EXPANSIONEXT EXTERIOR, EXTERNAL
F FAHRENHEITFA FIRE ALARMFAI FRESH AIR INTAKEFCU FAN COOLING UNITFD FLOOR DRAIN, FIRE DAMPERFDC FIRE DEPARTMENT CONNECTIONFE FIRE EXTINGUISHERFEC FIRE EXTINGUISHER CABINETFF FINISH FLOOR, FACTORY FINISHFFE FINISH FLOOR ELEVATIONFFL FINISH FLOOR LINEFG FLOOR GRILLEFH FIRE HYDRANTFHC FIRE HOSE CABINETFIN FINISH (ED)FIXT FIXTUREFL FLUSHFLD FLOOR DUCTFLEX FLEXIBLEFLG FLASHINGFLR FLOOR (ING)FLUOR FLUORESCENTFM FLOOR MOUNTEDFMC FLEXIBLE METAL CONDUITFND FOUNDATIONFOB FREIGHT ON BOARD, FLAT ON BOTTOMFOG FUEL OIL GAUGEFOR FUEL OIL RETURNFOS FUEL OIL SUPPLYFOT FLAT ON TOPFP FIREPROOF (ING)FPM FEET PER MINUTEFR FRAME, FLOOR REGISTERFRA FRESH AIRFRC FIRE RESISTANT COATINGFRP FIBERGLASS REINFORCED PANELFRT FIRE RETARDANTFS FLOOR SINKFSD FIRE AND SMOKE DAMPERFT FEET, FLOOR TREATMENTFTG FOOTINGFTR FIN TUBE RADIATIONFV FLUSH VALVE
G GAS, GLYCOLGA GAUGEGAL GALLONGALV GALVANIZEDGASK GASKET (ED)GC GENERAL CONTRACT (OR)GCMU GLAZED CONCRETE MASONRY UNITGCO GRADE CLEANOUT GF GROUND FACEGL GLASS, GLAZINGGND GROUNDGPM GALLONS PER MINUTEGR GRADE (ING), GLYCOL RETURNGS GLYCOL SUPPLYGVL GRAVELGWB GYPSUM WALL BOARDGYP GYPSUM
H HEIGHTHB HOSE BIBHBD HARD BOARDHC HEATING CONTRACT (OR), HANDICAPHCR HOT/CHILLED RETURNHCS HOT/CHILLED SUPPLYHD HEAVY DUTY
HDPE HIGH DENSITY POLYETHYLENEHDR HEADERHDW HARDWAREHG HOT GLYCOLHIP HIGH IMPACT PANELHM HOLLOW METALHORZ HORIZONTALHP HORSEPOWER, HIGH PRESSURE, HEAT PUMPHPC HIGH PERFORMANCE COATINGHPL HIGH PRESSURE LAMINATEHR HANDRAIL, HOURHT HEIGHTHTG HEATINGHV HIGH VOLTAGEHVAC HEATING/VENTILATING/AIR CONDITIONINGHVU HEATING AND VENTILATING UNITHW HOT WATERHWH HOT WATER HEATERHWP HOT WATER PUMPHWR HOT WATER RETURNHWS HOT WATER SUPPLY
ID INSIDE DIAMETERIE INVERT ELEVATIONIN INCHESINCL INCLUDE (D) (ING)INS INSULATE (D) (ION)INT INTERIORINV INVERTIP IRON PIPEIPS IRON PIPE SIZEIW INDIRECT WASTE
J JANITORS CLOSETJAN JANITORS CLOSETJB JUNCTION BOXJC JANITORS CLOSETJCT JUNCTIONJT JOINT
KW KILOWATTKWH KILOWATT PER HOURKV KILOVOLTKVA KILOVOLT AMPERE
L LENGTH, LONGLAB LABORATORYLAD LADDERLAM LAMINATE (D)LAT LEAVING AIR TEMPERATURELAV LAVATORYLB POUNDLBL LABELLBP LEAD BASED PAINTLC LANDSCAPE CONTRACTOR (SITE)LCC LEAD COATED COPPERLDR LEADERLEV LEVELLF LINEAR FOOTLFMC LIQUID-TIGHT FLEXIBLE METAL CONDUITLFNC LIQUID-TIGHT FLEXIBLE NONMETALLIC CONDUITLG LENGTH, LONGLGI LARGE GROUP INSTRUCTIONLH LEFT HANDLIN LINEARLKR LOCKERLL LIVE LOADLP LOW PRESSURELPC LOW PRESSURE CONDENSATE
LPS LOW PRESSURE STEAMLPT LOW POINTLS LINOLEUM SHEET TYPE 1LT LIGHTLT1 LINOLEUM TILE TYPE 1LTL LINTELLV LOW VOLTAGELVR LOUVERLWT LEAVING WATER TEMPERATURE
MAN MANUALMAS MASONRYMAT MATERIALMAU MAKE UP AIR UNITMAX MAXIMUMMB MARKER BOARDMBH THOUSAND BTUHMBR MEMBERMD MOTORIZED DAMPERME MECHANICAL EQUIPMENTMECH MECHANICAL (LY)MED MEDIUMMEMB MEMBRANEMEZZ MEZZANINEMF MIXING FAUCETMFR MANUFACTURE (R)MH MAN HOLEMIN MINIMUMMIR MIRRORMISC MISCELLANEOUSMO MASONRY OPENINGMOD MODULE (OR), MODELMR MOP RECEPTORMP MULTICOLOR WALL COATINGMT MOUNTMTD MOUNTEDMTG MOUNTINGMTL METALMTH MARBLE THRESHOLDMTR METERMULL MULLIONMVEJ MASONRY VENEER EXPANSION JOINT
N NORTH, NO WORK REQUIREDNAT NATURALNC NORMALLY CLOSEDNEC NATIONAL ELECTRIC CODENEG NEGATIVENEUT NEUTRALIZATIONNIC NOT IN CONTRACTNO NUMBER, NORMALLY OPENNOM NOMINALNRC NOISE REDUCTION COEFFICIENTNTS NOT TO SCALE
OA OVERALL, OUTSIDE AIROC ON CENTEROD OUTSIDE DIAMETEROH OVERHEADOPNG OPENINGOPP OPPOSITEOPP HD OPPOSITE HAND
P PAINT SURFACE(S) INCLUDING SOFFITSPAR PARALLELPART PARTITIONPC PLUMBING CONTRACT (OR),
PIGMENTED CONCRETEPCC PRECAST CONCRETE
PE PORCELAIN ENAMELPERF PERFORATE (ION) (ED)PERI PERIMETERPERP PERPENDICULARPL PLATE, PROPERTY LINEPLAM PLASTIC LAMINATEPLAS PLASTER, PLASTICPLF POUNDS PER LINEAR FOOTPLYWD PLYWOODPM PLUGMOLDPNL PANELPOC POINT OF CURVATURE, POINT OF CONNECTIONPOL POLISHEDPOS POSITIVEPOT POINT OF TANGENCYPR PAIRPRE POWER ROOF EXHAUSTERPREP PREPARE (ATION)PRF PREFORMEDPROJ PROJECTPS PAINT EXPOSED STRUCTURE/DECKPSF POUNDS PER SQUARE FOOTPSI POUNDS PER SQUARE INCHPT POINTPT1 PORCELAIN TILE TYPE 1PTD PAINTEDPTFR PRESSURE TREATED FIRE RETARDANTPTP PRESSURE TREATED PRESERVATIVEPVC POLYVINYL CHLORIDEPVMT PAVEMENTPWE POWER WALL EXHAUSTER
QF QUARTZ FLOORINGQT QUARRY TILE
R RADIUS, RETURN, REFRIGERANTRA RETURN AIRRAD RADIATIONRAF RETURN AIR FAN, RESILIENT ATHLETIC FLOORINGRB RESILIENT BASERC ROOFING CONTRACT (OR)RCA RECYCLED CONCRETE AGGREGATERCP REINFORCED CONCRETE PIPE,
REFLECTED CEILING PLANRCU REMOTE CONDENSING UNITRD ROOF DRAINRECEPT RECEPTACLEREF REFERENCEREFL REFLECT (ED) (IVE) (OR)REFR REFRIGERATORREG REGISTERREINF REINFORCE (D) (ING)REM REMOVEDREQD REQUIREDRESIL RESILIENTRET RETAINING, RETURNREV REVISION, REVISED, REVEALRF RUBBER FLOORING TYPE 1RFG ROOFINGRFH ROOF HATCHRFM RECESSED FLOOR MATRG RETURN GRILLERGS RIGID GALVANIZED STEELRH RIGHT HANDRHC REHEAT COILRI ROUGH-INRL RAIN LEADERRLG RAIL (ING)RM ROOM
RMC RIGID METAL CONDUITRNC RIGID NONMETALLIC CONDUITRNT RUNNING TRAPRO ROUGH OPENINGROW RIGHT OF WAYRPM REVOLUTIONS PER MINUTERR REMOVE EXISTING AND REPLACE WITH NEWRS RUBBER STAIR TREAD/RISERRTH ROOF TOP HOODRTU ROOF TOP UNITRW RAW WATER
S SOUTH, SUPPLY, SURGE PROTECTEDSA SUPPLY AIRSAN SANITARYSAS SMOOTH ALL SIDESSC SOLID CORE, SILL COCK, SEALED CONCRETESCHED SCHEDULESCT STRUCTURAL CLAY TILESD STORM DRAIN, SPLITTER DAMPER,
SMOKE DAMPERSEC SECTIONSF SQUARE FEETSGI SMALL GROUP INSTRUCTIONSGT STRUCTURAL GLAZED TILESH SHELF, SHELVING, SMOKE HATCHSHR SHOWER, SHEAR WALLSHT SHEETSHTHG SHEATHINGSIM SIMILARSK SINKSL SOUND LINED, SKYLIGHTSLC SILLCOCKSLV SLEEVESLVR STORM LOUVERSMH SANITARY MANHOLESOG SLAB ON GRADESP STATIC PRESSURE, STANDPIPE,
SPACE (ING) (ES)SPEC SPECIFICATION (S)SPKR SPRINKLERSPL SPECIALSQ SQUARESS STAINLESS STEELSST STRUCTURAL STEEL TUBINGST STORM, STORAGESTA STATIONSTC SHOWER TEMPERATURE CONTROLLER,
STAINED CONCRETESTD STANDARDSTG SEATINGSTL STEELSTN STAIN (ED)STOR STORAGESTRU STRUCTURALSURF SURFACESUSP SUSPENDEDSV SHEET VINYL, STEAM VENTSW SWITCH, SOFTENED WATERSWCI SERVICE WEIGHT CAST IRONSYM SYMMETRICALSYN SYNTHETICSYS SYSTEM
T TREAD, TOP, TOILET ROOM, TONST1 TERRAZZO TYPE 1TB TOP AND BOTTOM, TACK BOARD,
TERRAZZO BASE
TBD TO BE DETERMINEDTC TEMPERATURE CONTROL, TEMPERED CLEAR,
TELECOMMUNICATIONS CONTRACTOR,TOP OF CURB
TCX TOP CHORD EXTENTIONTDV TRIPLE DUTY VALVETEL TELEPHONETEMP TEMPERATURETG TOP GRILLE, TONGUE AND GROOVETHK THICKNESSTHR THRESHOLDTME TO MATCH EXISTINGTMV THERMOSTATIC MIXING VALVETOD TOP OF DUCTTOF TOP OF FASCIA, TOP OF FOOTINGTOL TOLERANCETOM TOP OF MASONRYTOP TOP OF PIPE, TOP OF PIERTOS TOP OF STEEL, TOP OF STAIRTPART TOILET PARTITIONTR TOP REGISTERTRN TRANSOMTS TOP OF STAIRTV TELEVISIONTW TEMPERED WATER, TOP OF WALLTYP TYPICAL
UC UNDERCUTUD UNDERDRAINUE UNDERGROUND ELECTRICUG UNDERGROUNDUH UNIT HEATERUNF UNFINISHEDUNIF UNIFORMUNO UNLESS NOTED OTHERWISEUR URINALUT UNDERGROUND TELEPHONEUV UNIT VENTILATOR
V VENT, VOLTVAR VARIES, VARIABLEVARN VARNISHVAT VINYL ASBESTOS TILEVAV VARIABLE AIR VOLUMEVB VACUUM BREAKER, VAPOR RETARDER BARRIER,
VOLLEYBALLVCB VENTED COVE BASEVCT1 VINYL COMPOSITE TILE TYPE 1VD VOLUME DAMPERVERM VERMICULITEVERT VERTICALVEST VESTIBULEVIF VERIFY IN FIELDVIN VINYLVIT VITREOUS TILEVNR VENEERVOL VOLUMEVTR VENT THROUGH ROOFVWC VINYL WALL COVERING
W WEST, WIDTH, WIDE, WASTE, WATTWB WET BULBWC WATER CLOSET, WALL COVERINGWD WOODWD1 WOOD FLOORING - GYMWD2 WOOD FLOORING - STAGEWDW WINDOWWDWC WINDOW CONTRACTORWF WASH FOUNTAIN
WG WALL GRILLE, WATER GAUGEWH WALL HUNG, WALL HYDRANTWI WROUGHT IRONWM WIREMOLDWP WATER PROOFING, WORKING POINTWR WATER REPELLENT, WIDE RIB, WALL REGISTERWS WATER STOPWSCT WAINSCOTWT WEIGHTWWHP WATER TO WATER HEAT PUMPWWM WELDED WIRE MESHW/ WITHW/O WITHOUT
XHCI EXTRA HEAVY CAST IRON
YD YARD DRAIN, YARD
Drawing List:
Title Sheet, Symbols & Abbreviations
Architectural Drawings:A100 Public Safety Center First Floor PlanA101 Public Safety Center Second and
Third Floor PlansA200 Health Complex First Floor PlanA201 Health Complex Second Floor PlanA300 Legislative Office Building Floor PlansA400 Window And Curtain Wall TypesA401 Window And Curtain Wall Details
November 28, 2016
Oswego Map
Oswego Health Complex
Oswego Public Safety Center
STAGING AREA MAP - PUBLIC SAFETY STAGING AREA MAP - HEALTH COMPLEX
STAGING AREASTAGINGAREA
S
M
DUMPSTERLOCATIONS
DUMPSTERLOCATIONS
EXG CONCRETEBARRIERS
Legislative Office Building
STAGING AREA MAP - LEGISLATIVE OFFICE BUILDING
DUMPSTERLOCATIONS
STAGINGAREA
11B 1C
1B 1B
1B
1D
1B
1B1B1B1B1B1D
1B
1D 1D
1B 1B 1B 1B 1B
3
5 1K3
Drawn by: Drawing No.:
Description:Rev. No.: Date:
Tetra Tech Engineers, Architects& Landscape Architects, P.C.
1
A
2 43 5 6 7 8
BC
D
9 10 11 12 13 14 15 16 17
EF
GH
IN N
ML
JI
HG
FE
DC
BA
ML
KJ
K
Public Safety CenterFirst Floor Plan
TLE
A1001 Public Safety Center First Floor Plan1/16" = 1'-0"
N
Project No.:
Date:
73513-16001A
Key PlanNTS
County of OswegoWindow Replacements
AB
C D
OPEN
OPEN
County of OswegoOswego, NY 13126
November 28, 2016
General Notes
General Demolition Notes:
APPLIES TO ALL DRAWINGS
Legend
xxxINDICATES WINDOW TYPE
INDICATES OPERABLE AWNING SASH
INDICATES METAL SKIN INSULATED SPANDREL PANEL
INDICATES 2" GLAZED SKIN INSULATED SPANDREL PANEL
INDICATES 1" GLAZED SKIN INSULATED SPANDREL PANEL
Keyed Notes:EXISTING CURTAIN WALL TO BE RE-GLAZED1
PUBLIC SAFETY CENTER
PROVIDE FIXED GLAZING AND NO BLIND AND THIRD GLAZING PANELREQUIRED WHERE VIEW IS OBSTRUCTED BY CHASE WALLCONSTRUCTION
2
BLIND AND REMOVABLE INTERIOR GLAZING PANEL NOT REQUIRED3
MODIFY AND SEAL EXISTING WALL TO WINDOW MULLION, REFER TODETAIL 18/A401
4
WINDOW OR CURTAIN WALL TYPE EXTENDS TO UPPER OR LOWERFLOOR
5
1B
1B
1B
1D 1B 1B1D
1B1A1B
1D 1D 1B1B 1D
1A 1A 1D 1B 1D1A1D
1A
1B
1D
1B
1B
1B1B
1B1B1B1B
1B1B1B1B1B1B
1B
1B
1D
1B1A1B 1B 1B 1B 1B1A1B 1B1A1B 1B1A1B 1B1A1B
1B 1B 1B
1B1A1B 1B1A1B 1B1B1A1B
1D1D1D
3 3 3 3 3
13 1K5
1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G 1G1H 1I 1F 1F 1E 1B 1F1B 1F 1H 1I
1G
1G
1G
1G
1G1G1G1G1G1G1G1G1G1A1A1J1J1J1J1J1J1J1J1J1J1J1J1J1J1J1G1G1G1G1G1G1G1G
1G1G1G1G1G
1G
1G
1G
1G
1G
1G
1E
1E1E3 3
3
1
424244
2 4 2 2 2 2
4 4 4 4 4
2
3
4 4
1K5
2
4
Drawn by: Drawing No.:
Description:Rev. No.: Date:
Tetra Tech Engineers, Architects& Landscape Architects, P.C.
1
A
2 43 5 6 7 8
BC
D
9 10 11 12 13 14 15 16 17
EF
GH
IN N
ML
JI
HG
FE
DC
BA
ML
KJ
K
Public Safety CenterSecond and Third Floor Plans
TLE
A101
1 Public Safety Center Third Floor Plan1/16" = 1'-0"
N
Project No.:
Date:
73513-16001A
Key PlanNTS
County of OswegoWindow Replacements
AB
C D
OPEN
OPEN
County of OswegoOswego, NY 13126
November 28, 20162 Public Safety Center Second Floor Plan1/16" = 1'-0"
General Notes
General Demolition Notes:
APPLIES TO ALL DRAWINGS
Legend
xxxINDICATES WINDOW TYPE
INDICATES OPERABLE AWNING SASH
INDICATES METAL SKIN INSULATED SPANDREL PANEL
INDICATES 2" GLAZED SKIN INSULATED SPANDREL PANEL
INDICATES 1" GLAZED SKIN INSULATED SPANDREL PANEL
Keyed Notes:EXISTING CURTAIN WALL TO BE RE-GLAZED1
PUBLIC SAFETY CENTER
PROVIDE FIXED GLAZING AND NO BLIND AND THIRD GLAZING PANELREQUIRED WHERE VIEW IS OBSTRUCTED BY CHASE WALLCONSTRUCTION
2
BLIND AND REMOVABLE INTERIOR GLAZING PANEL NOT REQUIRED3
MODIFY AND SEAL EXISTING WALL TO WINDOW MULLION, REFER TODETAIL 18/A401
4
WINDOW OR CURTAIN WALL TYPE EXTENDS TO UPPER OR LOWERFLOOR
5
2A 2A 2A 2A 2A
2J
2B
2A 2B
2A
2A
2B2A
2A
2A2A
2A
2A
2A
2B2A2A2A2B2B
2L 2M 2K
2V 2V 2V
2A
2V
2U
2G
2B2D 2D
2V
2A
2A
2A
2B 2B
2A2A
2A 2U
2V2V2V2V
2U
2U
2U
2B
2V
2V
2V
2U
2U
2U
2U
1 1 1
4
2A
2B
5
A
A
A A A
A A
A
A
A A A A A A
A
A
A
A
A
A A A A
A
A
AA
A
AA
A A A
A A A
A
A
A
A
AAAAA
B
B
B
B
B
A
A
A
A
A
AA
A A
AA
A
A
A
Drawn by: Drawing No.:
Description:Rev. No.: Date:
Tetra Tech Engineers, Architects& Landscape Architects, P.C.
1
A
2 43 5 6 7 8
BC
D
9 10 11 12 13 14 15 16 17
EF
GH
IN N
ML
JI
HG
FE
DC
BA
ML
KJ
K
Health Complex First Floor Plan
TLE
A2001 First Floor Plan
1/16" = 1'-0"
General Notes
General Demolition Notes:
APPLIES TO ALL DRAWINGS
Legend
xxxINDICATES WINDOW TYPE
INDICATES OPERABLE AWNING SASH
INDICATES METAL SKIN INSULATED SPANDREL PANEL
INDICATES 2" GLAZED SKIN INSULATED SPANDREL PANEL
INDICATES 1" GLAZED SKIN INSULATED SPANDREL PANEL
Keyed Notes:EXISTING LOUVERS BELOW WINDOWS TO REMAIN1
HEALTH COMPLEX
BLIND AND REMOVABLE INTERIOR GLAZING PANEL NOT REQUIRED2
SEAL EXISTING WALL TO WINDOW MULLION3
WINDOW OR CURTAIN WALL TYPE EXTENDS TO UPPER OR LOWERFLOOR
4
BLIND AND REMOVABLE INTERIOR GLAZING PANEL REQUIRED ATBOTTOM GLAZING ONLY
5
BLIND NOT REQUIRED PROVIDE INTERIOR GLAZING PANEL TYPEHCL.
6
PROVIDE INTERIOR GLAZING PANEL TYPE HCL.7
Project No.:
Date:
County of OswegoOswego, NY 13126
County of OswegoWindow Replacements
N
Key PlanNTS
A
BC
73513-16001A
November 28, 2016
1. WHERE REMOVAL OF WINDOW SYSTEM CONTAINING ASBESTOS ISSHOWN, REMOVE AND DISPOSE OF WINDOW SYSTEM AS ASBESTOSCONTAINING OR CONTAMINATED MATERIALS (SECTION 02 82 00).
2. WHERE REMOVAL OF WINDOW SYSTEM CONTAINING MERCURY ISSHOWN, REMOVE AND DISPOSE OF WINDOW SYSTEM AS HAZARDOUSMATERIAL (SECTION 02 84 00).
3. WINDOW SYSTEMS INCLUDE, WITHOUT LIMITATION, ANY AND ALL OFTHE FOLLOWING (INCLUDING COMBINATIONS OF TWO OR MORE):
a. WINDOWS j. CAULKINGb. DOORS k. GLAZING COMPOUNDSc. FLASHING l. GLASSd. WINDOW PANELS m. SEALANTSe. FRAMING n. SILLSf. SASHES o. SCREENSg. HARDWARE p. STOOLSh. INSULATION q. MULLIONSi. ALL FINISHES r. MUNTINS
4. REMOVE THE ENTIRE WINDOW SYSTEM BETWEEN THEMASONRY/CONCRETE/STRUCTURAL STEEL THAT SURROUNDS THEM,EXCEPT AS FOLLOWS:
a. LINTELSb. MASONRY OR STONE SILLSc. STRUCTURAL SUPPORTSd. ITEMS SCHEDULED FOR REUSE BY OTHER CONTRACTORS.
5. REMOVE CAULK FROM THE WINDOW OR DOOR ASSEMBLY FRAME ANDTHE SURROUNDING WALL SURFACES.
6. MULTIPLE LAYERS/APPLICATIONS OF CAULKING MAY BE PRESENT ONWINDOW SYSTEMS.
8. AFTER THE WINDOW OR DOOR SYSTEM HAS BEEN REMOVED ANDAFTER CLEARANCE AIR SAMPLES HAVE BEEN COLLECTED OR IF NO AIRSAMPLES ARE REQUIRED, ONCE SATISFACTORY CLEARANCE CRITERIAARE ACHIEVED, COORDINATE WITH CONTRACTOR RESPONSIBLE FORINSTALLATION OF NEW WINDOW AND PROVIDE HARD WALL BARRIERSTO THE INTERIOR OF THE BUILDING, AS SPECIFIED IN SECTION 01 50 00,IF NEW WINDOWS WILL NOT BE INSTALLED IMMEDIATELY FOLLOWINGREMOVALS.
Window System and Caulk Abatement NotesAbatement Legend:REMOVE WINDOW SYSTEM WITH ASBESTOS CONTAININGCAULKING
REMOVE WINDOW SYSTEM WITH MERCURY CONTAINING CAULKING
HEALTH COMPLEX
A
B
1. CONTRACTOR PERFORMING ANY AND ALL ASBESTOS ABATEMENTWORK SHALL BE A NYSDOL LICENSED ASBESTOS CONTRACTOR.
2. PERFORM ALL WORK IN ACCORDANCE WITH SECTION 02 82 00 -ASBESTOS ABATEMENT.
3. ASBESTOS CONTAINING MATERIALS SHALL BE ABATED INACCORDANCE WITH THE DRAWINGS AND SECTION 02 82 00 PRIOR TOANY GENERAL DEMOLITION WORK THAT COULD DISTURB THOSEMATERIALS.
4. DO NOT SCALE DRAWINGS.
5. COORDINATE ALL WORK WITH OTHER CONTRACTORS.
6. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ANY AND ALLVARIANCES FROM INDUSTRIAL CODE RULE 56, WHICH ARE DESIREDOR NECESSARY TO PERFORM THE WORK.
7. REMOVE ALL ABATED MATERIALS FROM THE WORK AREA AND /ORBUILDING IN SEALED BAGS, DRUMS OR PLASTIC SHEETING.
Asbestos Abatement General Notes
2I 2I 2I 2I 2I 2I
2L 2M 2K
2M
2R 2O 2R
2T
2Q
2Q
2T
2T
2Q 2Q
2T
2T
2Q
2T
2O
2N
2S
2N
2N
2S
2N
2O
2R
2N
2R
2N
2R
2N
2R
2N
2R2O
2O
2R
2R
2S2N
2R
2O
2S
2N
2N
2R2P
2N
2W
2W
2H
2BB
2BB
2BB
2AA
2W
2H
2W
2C
2W2D
2W
2BB
2BB
2BB
2AA
2BB
2BB
2BB
2AA
2BB
2BB
2BB
2AA
2B
2W
1
1 2
4
3
222222
2F
6
6
6
66
66
66
6666
6
6
6
A
A
A
A
A
A A A A A A
A A A
A A A
A
A
A
A
A
A
A A
A
B
B
B
B
B
B
B
B
BBBBBBB
B B B B B B
A
A
A
A
A
A
A
A
A
A
AA
A
A
A
A
AAAA
A
A
A
A
A
A
A
A
A
AAAAA
A
AA
6 6
77
6
6
66
7
Drawn by: Drawing No.:
Description:Rev. No.: Date:
Tetra Tech Engineers, Architects& Landscape Architects, P.C.
1
A
2 43 5 6 7 8
BC
D
9 10 11 12 13 14 15 16 17
EF
GH
IN N
ML
JI
HG
FE
DC
BA
ML
KJ
K
Health Complex Second Floor Plan
TLE
A2011 Second Floor Plan
1/16" = 1'-0"
General Notes
General Demolition Notes:
APPLIES TO ALL DRAWINGS
Legend
xxxINDICATES WINDOW TYPE
INDICATES OPERABLE AWNING SASH
INDICATES METAL SKIN INSULATED SPANDREL PANEL
INDICATES 2" GLAZED SKIN INSULATED SPANDREL PANEL
INDICATES 1" GLAZED SKIN INSULATED SPANDREL PANEL
Keyed Notes:EXISTING LOUVERS BELOW WINDOWS TO REMAIN1
HEALTH COMPLEX
BLIND AND REMOVABLE INTERIOR GLAZING PANEL NOT REQUIRED2
SEAL EXISTING WALL TO WINDOW MULLION3
WINDOW OR CURTAIN WALL TYPE EXTENDS TO UPPER OR LOWERFLOOR
4
BLIND AND REMOVABLE INTERIOR GLAZING PANEL REQUIRED ATBOTTOM GLAZING ONLY
5
BLIND NOT REQUIRED PROVIDE INTERIOR GLAZING PANEL TYPEHCL.
6
PROVIDE INTERIOR GLAZING PANEL TYPE HCL.7
Project No.:
Date:
County of OswegoOswego, NY 13126
County of OswegoWindow Replacements
N
Key PlanNTS
A
BC
73513-16001A
November 28, 2016
1. WHERE REMOVAL OF WINDOW SYSTEM CONTAINING ASBESTOS ISSHOWN, REMOVE AND DISPOSE OF WINDOW SYSTEM AS ASBESTOSCONTAINING OR CONTAMINATED MATERIALS (SECTION 02 82 00).
2. WHERE REMOVAL OF WINDOW SYSTEM CONTAINING MERCURY ISSHOWN, REMOVE AND DISPOSE OF WINDOW SYSTEM AS HAZARDOUSMATERIAL (SECTION 02 84 00).
3. WINDOW SYSTEMS INCLUDE, WITHOUT LIMITATION, ANY AND ALL OFTHE FOLLOWING (INCLUDING COMBINATIONS OF TWO OR MORE):
a. WINDOWS j. CAULKINGb. DOORS k. GLAZING COMPOUNDSc. FLASHING l. GLASSd. WINDOW PANELS m. SEALANTSe. FRAMING n. SILLSf. SASHES o. SCREENSg. HARDWARE p. STOOLSh. INSULATION q. MULLIONSi. ALL FINISHES r. MUNTINS
4. REMOVE THE ENTIRE WINDOW SYSTEM BETWEEN THEMASONRY/CONCRETE/STRUCTURAL STEEL THAT SURROUNDS THEM,EXCEPT AS FOLLOWS:
a. LINTELSb. MASONRY OR STONE SILLSc. STRUCTURAL SUPPORTSd. ITEMS SCHEDULED FOR REUSE BY OTHER CONTRACTORS.
5. REMOVE CAULK FROM THE WINDOW OR DOOR ASSEMBLY FRAME ANDTHE SURROUNDING WALL SURFACES.
6. MULTIPLE LAYERS/APPLICATIONS OF CAULKING MAY BE PRESENT ONWINDOW SYSTEMS.
8. AFTER THE WINDOW OR DOOR SYSTEM HAS BEEN REMOVED ANDAFTER CLEARANCE AIR SAMPLES HAVE BEEN COLLECTED OR IF NO AIRSAMPLES ARE REQUIRED, ONCE SATISFACTORY CLEARANCE CRITERIAARE ACHIEVED, COORDINATE WITH CONTRACTOR RESPONSIBLE FORINSTALLATION OF NEW WINDOW AND PROVIDE HARD WALL BARRIERSTO THE INTERIOR OF THE BUILDING, AS SPECIFIED IN SECTION 01 50 00,IF NEW WINDOWS WILL NOT BE INSTALLED IMMEDIATELY FOLLOWINGREMOVALS.
Window System and Caulk Abatement NotesAbatement Legend:REMOVE WINDOW SYSTEM WITH ASBESTOS CONTAININGCAULKING
REMOVE WINDOW SYSTEM WITH MERCURY CONTAINING CAULKING
HEALTH COMPLEX
A
B
1. CONTRACTOR PERFORMING ANY AND ALL ASBESTOS ABATEMENTWORK SHALL BE A NYSDOL LICENSED ASBESTOS CONTRACTOR.
2. PERFORM ALL WORK IN ACCORDANCE WITH SECTION 02 82 00 -ASBESTOS ABATEMENT.
3. ASBESTOS CONTAINING MATERIALS SHALL BE ABATED INACCORDANCE WITH THE DRAWINGS AND SECTION 02 82 00 PRIOR TOANY GENERAL DEMOLITION WORK THAT COULD DISTURB THOSEMATERIALS.
4. DO NOT SCALE DRAWINGS.
5. COORDINATE ALL WORK WITH OTHER CONTRACTORS.
6. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ANY AND ALLVARIANCES FROM INDUSTRIAL CODE RULE 56, WHICH ARE DESIREDOR NECESSARY TO PERFORM THE WORK.
7. REMOVE ALL ABATED MATERIALS FROM THE WORK AREA AND /ORBUILDING IN SEALED BAGS, DRUMS OR PLASTIC SHEETING.
Asbestos Abatement General Notes
3M3S
3M 3N 3N 3M 3M3S
5555A
AAAAA
B B B
3MA
A
A
A
A
AB B B B B3M
3M
3M
3M
3M
3S 3S
3S 3S 3S 3S
6 6
3O
3C 3BB3O
3G
3B
3A
3O 3P 3P3L 3I
3O
1 1
1
1
A A A A A
B B B B B B B
A
A
A
A
A
A
A A AB B B B B B
3I 3I 3I 3I 3I
3I 3I 3I 3I 3I 3I
3O 3O
3O
3O
3O
3O
3O 3O
3H
7
3R3F
3E 3E
3A
3D
3F 3BB
3B
1
1
1
1
3K3R
3R
3R3K
2
2
2
22
A A A A
B B B B B B
A
A
A
A
A
A
A A AB B B B B B
3K3K3K3K3K
3K3K3K3K3K3R3R3R
3R
3R
3R
3R
3R3R
3Q
3A
3Q
3D
3C 3BB
3B
1 1
1
1
1
3Q
3
3Q
3J
2
A A A A
B B B B B B B
A
A
A
A
A
A
A A AB B B B B B
3J
3J3J3J3J3J3J
3J3J3J3J3J
3Q 3Q 3Q
3Q
3Q
3Q
3Q
3Q3Q
Drawn by: Drawing No.:
Description:Rev. No.: Date:
Tetra Tech Engineers, Architects& Landscape Architects, P.C.
1
A
2 43 5 6 7 8
BC
D
9 10 11 12 13 14 15 16 17
EF
GH
IN N
ML
JI
HG
FE
DC
BA
ML
KJ
K
Legislative Office Building Floor Plans
TLE
A300
1 First Floor Plan1/16" = 1'-0"
2 Second Floor Plan1/16" = 1'-0"
3 Third Floor Plan1/16" = 1'-0"
4 Fourth Floor Plan1/16" = 1'-0"
Key PlanNTS
N
Project No.:
Date:
73513-16001A
County of OswegoWindow Replacements
County of OswegoOswego, NY 13126
November 28, 2016
General Notes
General Demolition Notes:
APPLIES TO ALL DRAWINGS
Legend
xxxINDICATES WINDOW TYPE
INDICATES OPERABLE AWNING SASH
INDICATES METAL SKIN INSULATED SPANDREL PANEL
INDICATES 2" GLAZED SKIN INSULATED SPANDREL PANEL
INDICATES 1" GLAZED SKIN INSULATED SPANDREL PANEL
Keyed Notes:WINDOW OR CURTAIN WALL TYPE EXTENDS TO UPPPER OR LOWERFLOOR
1
LEGISLATIVE OFFICE BUILDING
2
DISCONNECT, REMOVE, REINSTALL AND RECONNECT EXISTINGVENT HOOD TO DUCT ABOVE CEILING. PROVIDE CUT-OUT ININSULATED SPANDREL PANEL.
3
REMOVE, MODIFY AND REINSTALL EXISTING SUSPENDED CEILINGSYSTEM AS REQUIRED TO PERFORM WORK. PROVIDE BRAKEFORMED METAL TRIM TO MATCH CEILING GRID WHERE CLOSURE ISREQUIRED BETWEEN CEILING AND WINDOW, TYPICAL WHEREREQUIRED, VIF.
4
REMOVE AND REINSTALL EXISTING EXTERIOR GRATING PANEL5
BLIND AND REMOVABLE INTERIOR GLAZING PANEL NOT REQUIREDAT RADIUS GLAZING PANEL
REMOVE EXISTING METAL HEADER PANEL AND PROVIDE .060"FORMED ALUMINUM HEADER PANEL TO MATCH WINDOW ANDEXISTING HEADER (APPROX. 18" HIGH X 6'-8" LONG) WITH FORMEDDRIP EDGE HEM AND PERIMETER RETURNS SEALED INTO EXISTINGMORTAR JOINTS.
6
GENERAL DEMOLITION NOTE A (SIMILAR) REMOVE EXISTING DOOR,FRAME, SIDELIGHT, TRANSOM, HARDWARE & THRESHOLD.
7
1. WHERE REMOVAL OF WINDOW SYSTEM CONTAINING BOTH ASBESTOSAND RCRA METALS ARE SHOWN, REMOVE AND DISPOSE OF WINDOWSYSTEM AS HAZARDOUS MATERIAL (SECTION 02 84 00) AND ASBESTOSCONTAINING OR CONTAMINATED MATERIALS (SECTION 02 82 00).
2. WHERE REMOVAL OF WINDOW SYSTEM CONTAINING ONLY RCRAMETALS ARE SHOWN, REMOVE AND DISPOSE OF WINDOW SYSTEM ASHAZARDOUS MATERIAL (SECTION 02 84 00).
3. WINDOW SYSTEMS INCLUDE, WITHOUT LIMITATION, ANY AND ALL OFTHE FOLLOWING (INCLUDING COMBINATIONS OF TWO OR MORE):
a. WINDOWS j. CAULKINGb. DOORS k. GLAZING COMPOUNDSc. FLASHING l. GLASSd. WINDOW PANELS m. SEALANTSe. FRAMING n. SILLSf. SASHES o. SCREENSg. HARDWARE p. STOOLSh. INSULATION q. MULLIONSi. ALL FINISHES r. MUNTINS
4. REMOVE THE ENTIRE WINDOW SYSTEM BETWEEN THEMASONRY/CONCRETE/STRUCTURAL STEEL THAT SURROUNDS THEM,EXCEPT AS FOLLOWS:
a. LINTELSb. MASONRY OR STONE SILLSc. STRUCTURAL SUPPORTSd. ITEMS SCHEDULED FOR REUSE BY OTHER CONTRACTORS.
5. REMOVE CAULK FROM THE WINDOW OR DOOR ASSEMBLY FRAME ANDTHE SURROUNDING WALL SURFACES.
6. MULTIPLE LAYERS/APPLICATIONS OF CAULKING MAY BE PRESENT ONWINDOW SYSTEMS.
7. AT LOCATIONS WHERE A SECONDARY WINDOW SYSTEM IS LOCATEDBEHIND THE EXTERIOR WINDOW SYSTEM SCHEDULED FOR REMOVAL,AND THE SECONDARY WINDOW SYSTEM IS SCHEDULED TO REMAIN -REMOVE ALL CAULKING FROM THE SECONDARY SYSTEM TO THEEXTENT ACCESSIBLE. IF ALL CAULKING LOCATED ON THE SECONDARYSYSTEM IS NOT ABLE TO BE REMOVED, ENCAPSULATE REMAININGCAULKING COMPOUND WITH 2 INDEPENDENT COATS OF BRIDGINGENCAPSULANT. EACH COAT SHALL BE OF A DIFFERENT COLOR.
8. AFTER THE WINDOW OR DOOR SYSTEM HAS BEEN REMOVED ANDAFTER CLEARANCE AIR SAMPLES HAVE BEEN COLLECTED OR IF NO AIRSAMPLES ARE REQUIRED, ONCE SATISFACTORY CLEARANCE CRITERIAARE ACHIEVED, COORDINATE WITH CONTRACTOR RESPONSIBLE FORINSTALLATION OF NEW WINDOW AND PROVIDE HARD WALL BARRIERSTO THE INTERIOR OF THE BUILDING, AS SPECIFIED IN SECTION 01 50 00,IF NEW WINDOWS WILL NOT BE INSTALLED IMMEDIATELY FOLLOWINGREMOVALS.
Window System and Caulk Abatement NotesAbatement Legend:REMOVE WINDOW SYSTEM WITH ASBESTOS, BARIUM, CHROMIUM,AND LEAD CONTAINING CAULKING
REMOVE WINDOW SYSTEM WITH BARIUM, CHROMIUM, AND LEADCONTAINING CAULKING
A
B
LEGISLATIVE OFFICE BUILDING
1. CONTRACTOR PERFORMING ANY AND ALL ASBESTOS ABATEMENTWORK SHALL BE A NYSDOL LICENSED ASBESTOS CONTRACTOR.
2. PERFORM ALL WORK IN ACCORDANCE WITH SECTION 02 82 00 -ASBESTOS ABATEMENT.
3. ASBESTOS CONTAINING MATERIALS SHALL BE ABATED INACCORDANCE WITH THE DRAWINGS AND SECTION 02 82 00 PRIOR TOANY GENERAL DEMOLITION WORK THAT COULD DISTURB THOSEMATERIALS.
4. DO NOT SCALE DRAWINGS.
5. COORDINATE ALL WORK WITH OTHER CONTRACTORS.
6. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ANY AND ALLVARIANCES FROM INDUSTRIAL CODE RULE 56, WHICH ARE DESIREDOR NECESSARY TO PERFORM THE WORK.
7. REMOVE ALL ABATED MATERIALS FROM THE WORK AREA AND /ORBUILDING IN SEALED BAGS, DRUMS OR PLASTIC SHEETING.
Asbestos Abatement General Notes
3A 3B 3C 3D
3F 3G 3I 3J 3K 3L
3M 3N 3O 3P 3Q 3R 3S3E
(CURTAIN WALL SYSTEM)MATCH EXISTING MULLION DIMENSIONS
VERIFY IN FIELD
3BB
(CURTAIN WALL SYSTEM)TYPE FC SINGLE GLAZING
AT THIS WINDOW
PATTERNED GLAZINGTYPE FY/FCP
PATTERNED GLAZINGTYPE FY/FCP
FIXED GLASS, TYP
22
22
22 22 22 22
21 2121
21
20 20
20
2020
2020
20
20
20
19
19
19 19
19
19 19
19
19
FIXED GLASS, TYP
PROVIDE ADDITIONALJAMB WIDTH TO MATCHEXISTING PROFILE,BOTH SIDES
21
26
20
20
20
202025
19191919
23
19
24
REFER TO A401FOR DETAILS, TYP.
27
27 27 SIM. 27 SIM.
27 SIM. 27 SIM. 27 SIM.
27 SIM.
21 21
21
21
21
20
19
21
20
19
SIM.
19
21
20
19
SIM.
SIM.
3H
ALIGN, V.I.F.EXISTING STEELFRAME, TO REMAIN
28
29
30
31
1A 1B 1C 1D 1E 1F 1G 1H 1J1I
1K
(EXISTING CURTAIN WALL SYSTEM TO REMAIN)
REMOVE ALL EXISTING GLAZING AND PROVIDE GLAZINGTYPES AS INDICATED. NO WORK AT EXISTING DOOR.
FIXED GLAZING, TYP.2
3
1
5
6
4
2
1
3
2
3
1
5
4
6
5
4
6
5
6
4 4
5
6
4
5
6
4
5
6
1
2
3
REFER TO A401FOR DETAILS, TYP.
2A 2B 2D 2F 2G 2H 2I 2J
2K
2L
2M 2N 2O 2P 2Q 2R 2S 2T 2U 2V
(CURTAIN WALL SYSTEM)
2C
2W
(CURTAIN WALL SYSTEM) (CURTAIN WALL SYSTEM)
2AA 2BB
FIXED GLAZING, TYP
11
13
1011
108
9
7
11
16
10
11
16
10
11
16
10
17
15
16
10
14
15
16
14
15
16
15
16
15
16
14
15
16
14
15
16 16
12
13
10
11
13
10
10
11
13
11
13
10
11
13
10
11
11
1613
11
10
11
11
11
10
16
11
10
1613
11
10 1010
10 1010
10
10
10
11
11
11
13
SIM.
SIM.2ENOT USED
REFER TO A401FOR DETAILS, TYP.
Drawn by: Drawing No.:
Description:Rev. No.: Date:
Tetra Tech Engineers, Architects& Landscape Architects, P.C.
1
A
2 43 5 6 7 8
BC
D
9 10 11 12 13 14 15 16 17
EF
GH
IN N
ML
JI
HG
FE
DC
BA
ML
KJ
K
Window and Curtain Wall Types
TLE
A400Project No.:
Date:
County of OswegoWindow Replacements
County of OswegoOswego, NY 13126
73513-16001A
November 28, 2016
3 Legislative Office Building - Window and Curtain Wall Types1/4" = 1'-0"
2 Health Complex - Window Types1/4" = 1'-0"
1 Public Safety Center - Window Types1/4" = 1'-0"
General Notes
General Demolition Notes:
APPLIES TO ALL DRAWINGS
Legend
xxxINDICATES WINDOW TYPE
INDICATES OPERABLE AWNING SASH
INDICATES METAL SKIN INSULATED SPANDREL PANEL
INDICATES 2" GLAZED SKIN INSULATED SPANDREL PANEL
INDICATES 1" GLAZED SKIN INSULATED SPANDREL PANEL
Drawn by: Drawing No.:
Description:Rev. No.: Date:
Tetra Tech Engineers, Architects& Landscape Architects, P.C.
1
A
2 43 5 6 7 8
BC
D
9 10 11 12 13 14 15 16 17
EF
GH
IN N
ML
JI
HG
FE
DC
BA
ML
KJ
K
Window And Curtain Wall Details
TLE
A401
19Head Detail
21Sill Detail
22Sill Detail
23Top of Curtain Wall Detail
24Curtain Wall Head Detail
20Jamb Detail
8Jamb Detail
7Head Detail
9Sill Detail
1Head Detail
2Jamb Detail
3Sill Detail
Project No.:
Date:
County of OswegoWindow Replacements
County of OswegoOswego, NY 13126
73513-16001A
November 28, 2016
10Head Detail
11Jamb Detail
14Jamb Detail
15Jamb Detail
17Sill Detail
16Sill Detail
13Sill Detail
4Head Detail
5Jamb Detail
6Sill Detail
12Jamb Detail
18Mullion Detail at Partition
26Curtain Wall Sill Detail
25Curtain Wall Jamb Detail
27Floor Section/Spandrel
28Head Detail
29Horizontal Mullion Detail
30Jamb Detail
31Sill Detail