Cooling Water Problems
& Pretreatment Monitoring And
Control
![Page 2: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/2.jpg)
2
Why do cooling water problems exist?
If left untreated, cooling water systems provide an
environment where the four main cooling
problems will exist.
![Page 3: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/3.jpg)
3
Corrosion- Water tends to convert metals (such as mild steel) to their oxide states.
Scale- Water impurities, such as calcium and magnesium hardness can precipitate
and deposit depending on their concentrations, water temperature, pH,
alkalinity, and other water characteristics.
Microbiological Contamination -Cooling water systems offer a favorable
environment for micro organisms to grow and cause problems.
Fouling-Suspended solids from either external or internal sources can cause
deposits
![Page 4: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/4.jpg)
4
If left uncontrolled, these problems, either alone or
together, can cause: Increased maintenance cost Reduced heat transfer efficiency
and therefore greater energy losses
Possible production cutbacks or shutdowns
![Page 5: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/5.jpg)
5
It is an electrochemical process by which a metal returns to its natural state. For
example, mild steel is a commonly used metal in cooling water systems and is very susceptible to corrosion. It will return to its
iron oxide state.
Corrosion
![Page 6: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/6.jpg)
6
For corrosion to occur, a corrosion cell, consisting of an anode, a cathode, and an electrolyte, must exist. Metal ions dissolve
into the electrolyte (water) at the anode. Electrically charged particles (electrons)
are left behind.
These electrons flow through the metal to other points (cathodes) where electron-
consuming reactions occur. The result of this activity is the loss of metal and often
the formation of a deposit.
How does corrosion take place ?
![Page 7: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/7.jpg)
7
![Page 8: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/8.jpg)
8
General attack exists when the corrosion is uniformly distributed over the metal surface.
The iron oxide produced contributes to fouling problems.
Localized (or pitting) attack exists when only small areas of the metal corrode. Pitting is
the most serious form of corrosion. Because the action is concentrated in a small area.
Galvanic attack can occur when two different metals are in contact. The more active metal corrodes rapidly. Common examples in water
systems are steel and brass, aluminum and steel, zinc and steel, and zinc and brass.
What are the different types of corrosive attack ?
![Page 9: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/9.jpg)
9
The most important factors are:
Oxygen and other dissolved gasesDissolved or suspended solids Alkalinity or acidity (pH)VelocityTemperatureMicrobial activity
![Page 10: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/10.jpg)
10
Dissolved solids can affect the corrosion reaction by increasing the electrical
conductivity of the water. The higher the dissolved solids concentration, the greater
the conductivity and the more likelihood of corrosion .
Dissolved chlorides and sulfates are particularly corrosive. Suspended solids
can influence corrosion by erosive or abrasive action, and they can settle on
metal surfaces to set up localized corrosion cells .
How do dissolved or suspended solids affect corrosion?
![Page 11: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/11.jpg)
11
Acidic and slightly alkaline water can dissolve metal and the protective oxide film
on metal surfaces. More alkaline water favors the formation of the protective oxide
layer .
How does alkalinity or acidity affect corrosion?
![Page 12: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/12.jpg)
12
High-velocity water increases corrosion by transporting oxygen to the metal and by
carrying away corrosion products at a faster rate. High velocity can also cause erosion of metal surfaces, protective films, and oxides .
When water velocity is low, deposition of suspended solids can establish localized
corrosion cells, thereby increasing corrosion rates .
How does water velocity affect corrosion?
![Page 13: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/13.jpg)
13
Microbial growths promote the formation of corrosion cells. In
addition, the byproducts of some organisms, such as hydrogen
sulfide from anaerobic corrosive bacteria, are corrosive.
How does microbial growth affect corrosion?
![Page 14: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/14.jpg)
14
Below 160°F, every 25-50°F increase in temperature causes corrosion rates to
double. Above 160°F, additional temperature increases have relatively little
effect on corrosion rates in cooling water systems.
How does temperature affect corrosion?
![Page 15: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/15.jpg)
15
When designing a new system, choose corrosion-resistant materials to minimize the effect of an aggressive environment.
Adjust pH.Apply protective coatings such as paints,
metal plating, tar, or plastids.Protect cathodically, using sacrificial
metals.Add protective film-forming chemical
inhibitors that the water can distribute to all wetted parts of the system .
What methods are used to prevent corrosion ?
![Page 16: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/16.jpg)
16
Anodic corrosion inhibitors establish a protective film on the anode. These inhibitors
are effective, but dangerous: if insufficient anodic inhibitor is present, the entire corrosion
potential occurs at the unprotected anode sites. This causes severe localized (or pitting) attack.
Cathodic corrosion inhibitors form a protective film on the cathode. These inhibitors reduce the corrosion rate in direct proportion to
the reduction of cathodic area.
General corrosion inhibitors protect by filming all metal surfaces whether anodic or
cathodic .
How do chemical corrosion inhibitors work?
![Page 17: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/17.jpg)
17
Mainly anodicChromates NitritesOrthophosphatesSilicates
What inhibitors are commonly used for cooling water systems ?
Mainly cathodic• Bicarbonates• Metal cations• Polyphosphates
General• Soluble oils• Other organics
![Page 18: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/18.jpg)
18
Yes. The choice of treatment is basically a matter of economics.
In a once-through system, a very large volume of water passes through the
system only once.In an open recirculating system, more
chemical must be present because the water composition changes significantly
through the evaporation process.In a closed recirculating system, water
composition remains fairly constant. There is very little loss of either water or
treatment chemical
Does the type of cooling system affect treatment application principles?
![Page 19: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/19.jpg)
19
Consistent control of both the corrosion inhibitor chemicals and the key water
characteristics.
No program will work without proper control .
What is the most important factor in an effective corrosion inhibitor program?
![Page 20: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/20.jpg)
20
Scale is a dense coating of predominantly inorganic material formed from the
precipitation of water-soluble constituents. Some common scales are:
Calcium carbonate Calcium phosphate Magnesium salts Silica
Scale
![Page 21: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/21.jpg)
21
Temperature.Alkalinity or acidity (pH) .Amount of scale-forming
material present.Influence of other dissolved
materials, which may or may not be scale-forming.
Why does scale form?
![Page 22: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/22.jpg)
22
Calcium carbonate scale
![Page 23: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/23.jpg)
23
Limit the concentration of scale forming minerals by controlling cycles of concentration or by removing the minerals before they enter
the system.
Feed acid to keep the common scale-forming minerals (such as calcium carbonate) dissolved.
Make mechanical changes in the system to reduce the chances for scale formation.
Increased water flow and exchangers with larger surface areas are examples.
Treat with chemicals designed to prevent scale.
How can scale formation be controlled ?
![Page 24: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/24.jpg)
24
Some salts such as calcium carbonate become less soluble as temperature increase.
A change in PH or alkalinity can greatly affect scale formation, the solubility of calcium carbonate decreases with increasing PH.
When the amount of scale forming material dissolved exceeds its saturation point.
The higher the level of scale forming dissolved solids, the greater the chance of
scale forming .
How do these factors increase the amount of scaling?
![Page 25: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/25.jpg)
25
Calcium carbonate crystals modified by treatment with a polyacrylate into light, fluffy shapes that are easily dispersed from cooling system surface (magnified 2000X)
"Normal" calcium carbonate Calcium (calcite) crystals (magnified 2000X)
![Page 26: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/26.jpg)
26
Threshold inhibition chemicals prevent scale formation by keeping
the scale-forming minerals in solution and not allowing a deposit to form: Scale conditioners modify
the crystal structure of scale, creating a bulky, transportable
sludge instead of a hard deposit.
How do chemical scale inhibitors work?
![Page 27: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/27.jpg)
27
Threshold inhibition: Organic phosphates, polyphosphates, polymeric
compounds
Scale conditioning: Lignins, tannins, polymeric compounds
What are some common scale-control chemicals ?
![Page 28: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/28.jpg)
28
Fouling is the accumulation of solid material other than scale in a way that hampers the
operation of plant equipment or contributes to its deterioration.
Fouling
![Page 29: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/29.jpg)
29
Dirt and silt.Sand.Corrosion products .Natural organics.Microbial masses.Aluminum phosphates.Iron phosphate .
Examples of common foulants are :
![Page 30: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/30.jpg)
30
Water characteristics.Temperature.Flow velocity.Microbial growths.Corrosion.Contamination .
What influences fouling in a cooling system ?
![Page 31: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/31.jpg)
31
How do water characteristics affect fouling?
Distilled water will not foul. However, most waters contain the dissolved and suspended materials that can cause a significant fouling
problem under certain conditions.
How does temperature affect fouling?
Increasing temperature increases the fouling tendency. Because heat-transfer surfaces
are hotter, than the cooling water, they accelerate fouling .
![Page 32: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/32.jpg)
32
How does flow rate affect fouling?At low flow rates (one foot per second or
less), fouling occurs due to natural settling of sus pended material. At higher flow rates
(three feet per second or more), fouling can still occur, but usually is less severe.
How do microbial growths affect fouling?
Microorganisms can form deposits on any surface. In addition, corrosive or iron
depositing bacteria cause or utilize corrosion products, which subsequently deposit as
voluminous foulants. All microbial colonies act as a collection site for silt and dirt, causing a deposit of different foulants .
![Page 33: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/33.jpg)
33
Fouling of a heat exchanger tube bundle
![Page 34: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/34.jpg)
34
Corrosion can form insoluble corrosion products that migrate and mix with debris,
process contamination, or microbial masses to aggravate fouling .
How does corrosion affect fouling?
![Page 35: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/35.jpg)
35
Material that leaks from the process side of heat exchange equipment can cause serious
fouling problems in several ways:
Depositing as insoluble products. Providing nutrient for micro organisms and
causing severe microbial growths. Reacting with scale or corrosion inhibitors to
form insoluble foulants.
How does process contamination affect
fouling ?
![Page 36: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/36.jpg)
36
Fouling can be controlled mechanically or by the use of chemical treatments. The best method of control depends upon the type of
fouling.
Control of fouling in the cooling system involves three major tactics :
How can fouling be controlled?
![Page 37: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/37.jpg)
37
Prevention: Whatever can be done to prevent foulants from entering the cooling
system; this may require mechanical changes or addition of chemicals to clarify
make-up water.
Reduction: Steps taken to remove or reduce the volume of foulants that
unavoidably enter the system. This may involve side stream filtering periodic tower
basin cleaning.
Ongoing Control: Taking regular action to minimize deposition of the foulants in
the system. This can include adding chemical dispersants and air rumbling or
back-flushing exchangers .
![Page 38: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/38.jpg)
38
Charge-reinforcement and wetting-agent, dispersants act to Keep foulants in suspension,
preventing them from settling on metal surfaces or helping to remove fouling deposits
that have already formed. The charge reinforcement dispersants cause
the foulants to repel one another by increasing the electrical charges they carry.
The wetting agents reduce surface tension, inhibiting new deposit formation and possibly removing existing deposits. This action keeps
the particles in the bulk water flow, where they are more likely to be removed from the system.
How do chemical inhibitors work?
![Page 39: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/39.jpg)
39
Charge reinforcers Anionic polymers
Wetting agents Surfactants
What kinds of chemicals are normally used ?
![Page 40: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/40.jpg)
40
What is microbiological contamination?
The uncontrolled growth of microorganisms can lead to
deposit formations which contribute to fouling, corrosion
and scale.
Microbio Problems
![Page 41: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/41.jpg)
41
Microbial slimes are masses of microscopic organisms and their waste products. These
slimes are usually characterized by their gooey feeling and can be plant or animal.
What are microbial slimes ?
![Page 42: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/42.jpg)
42
No. Some organisms do not create slime deposits and do not promote metal
corrosion.The presence of large numbers of these
harmless organisms, however, indicates that conditions are ideal for the growth of
harmful organisms
Are all organisms found in a cooling water system
harmful ?
![Page 43: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/43.jpg)
43
The make-up water supply, wind, and insects can all carry micro organisms into a
cooling water system.
How do microorganisms enter a cooling water
system ?
![Page 44: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/44.jpg)
44
Nutrients: For instance, hydrocarbons or other carbon sources can serve as food for
slime-forming organisms.Atmosphere: Organism growth depends
upon the availability of oxygen or carbon dioxide.
Location: Such factors as the amounts of light and moisture significantly affect
growth rates.Temperatures: Organisms that make up
slime tend to flourish between 40 and 150°F .
What factors contribute to microbial growth ?
![Page 45: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/45.jpg)
45
Can slime cause scale formation?Yes. Slime can cause or accelerate the rate
of scale formation. Slime can cause treatment chemicals for scale to be
ineffective. Reduces heat transfer, causing higher energy cost.
Can slime cause fouling?Slime masses themselves are foulants.
Other micro organisms and suspended solids can become part of the fouling deposit.
Although many organisms tend to die at high temperatures, the remaining debris still
fouls metal surfaces .
![Page 46: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/46.jpg)
46
Certain organisms, for example, the sulfate-reducing type, generate corrosive hydrogen
sulfide which causes severe pitting attack. In addition, slime can accelerate corrosion by depositing on the metal and preventing
protective film formation .
Can slime cause corrosion ?
![Page 47: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/47.jpg)
47
Generally, microbial organisms form colonies at points of low water velocity.
Heat exchangers are therefore subject to microbiological contamination. Similarly,
cooling towers are subject to fouling as well as surface and internal rot .
Do organisms affect specific areas in a cooling system?
![Page 48: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/48.jpg)
48
Types and quantities of microbial organisms.
Microbial trouble signs such as wood rot, slime deposits, and corrosion.
Operating characteristics of the system, such as temperature, flow rate, and water
composition.
What factors must be considered in planning an effective microbial
control program?
![Page 49: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/49.jpg)
49
Types of equipment employed, such as cooling towers, spray ponds,
open box condensers.
Sources of contamination, such as organisms and nutrients carried into
the system. These factors can influence the growth of troublesome
organisms and affect the microbial control treatments .
![Page 50: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/50.jpg)
50
Oxidizing biocidesNon-oxidizing biocides Biodispersants
What types of chemicals are used for microbial
control ?
![Page 51: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/51.jpg)
51
Chemicals called "oxidizing biocides" literally "burn up" any microbe they come in
direct contact with. Common oxidizers are chlorine, chlorine dioxide, bromine, ozone,
and organo chlorine slow-release compounds.
Chlorine is one of the most widely used, cost-effective biocides, and is available in
liquid, gaseous, or solid form. Its effectiveness is increased when used with
non oxidizing biocides and biological dispersants .
What are oxidizing biocides?
![Page 52: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/52.jpg)
52
Organic compounds utilized in killing microorganisms. They are
effective in areas or systems where chlorine may not be
adequate.
What are non-oxidizing biocides ?
![Page 53: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/53.jpg)
53
These chemicals do not kill organisms; they loosen microbial deposits, which can
the ىbe flushed away. They also expose new
layers-of-microbial slime or algae to the attack of oxidizing, biocides, Bio-
dispersants are an effective preventive measure, because they make it difficult for the microorganisms to attach to the metal
surfaces to form deposits .
What are bio-dispersants?
![Page 54: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/54.jpg)
54
Pretreatment is the preparation of the cooling water system to insure that the treatment program can work effectively
from startup .
Pretreatment Monitoring And Control
![Page 55: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/55.jpg)
55
New systems or existing ones being returned to service can contain significant
amounts of contaminating material. Films of oil or grease, general coatings or spots of
rust, dirt and sand always remain in newly constructed systems. These materials do
not represent faulty construction; they result from conditions existing during
construction.
Why is cooling water system pretreatment
needed ?
![Page 56: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/56.jpg)
56
In systems taken off line, deposits can be present as the result of scale, corrosion,
fouling, or micro biological contamination. If these materials are not removed through
effective pretreatment, the subsequent chemical program will not be effective .
![Page 57: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/57.jpg)
57
System cleaning Application of special pretreat ment
chemicals Initial high dose application of corrosion
inhibitors Ongoing application of corrosion inhibitors
at maintenance levels
What are the steps in system preparation and
start-up ?
![Page 58: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/58.jpg)
58
Acid removes corrosion products and some mineral contaminants, but has little effect
upon organic materials. With improper application it may attack system metal and
cause severe metal attack. Improper flushing will leave metal surfaces in a highly reactive state, which makes them especially
vulnerable to corrosion attack.
What effect does acid cleaning have on a cooling system?
![Page 59: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/59.jpg)
59
Automation of systems has become increasingly important as the nature of
acceptable cooling water treatment programs has changed.
For every treatment program there are specific chemical concentration ranges where
it functions best and provides the intended protection. If not properly controlled, any
chemical program can fail, leading to possible lost production, increased mainten ance cost,
and increased energy usage .
What is meant by monitoring and control? Why is it important?
![Page 60: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/60.jpg)
60
An automatic system is an excellent addition to any treatment program where
pH control is important. However, for proper operation, these systems need periodic
maintenance and attention.
Are automatic systems available for pH control ?
![Page 61: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/61.jpg)
61
Corrosion Coupons-To establish relative corrosion rates of different metals in cooling systems, small metal strips called corrosion
coupons can be used. These preweighed coupons are placed in the system for at
least 30 days, then removed, cleaned, and weighed again. The difference in the
coupon's weight before and after exposure is used in calculat ing the corrosion rate .
What are some methods for determining conditions in a cooling system?
![Page 62: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/62.jpg)
62
Corrosion Test Rack: Evaluates the effectiveness of corrosion inhibition
programs on non-heat transfer surfaces. It is designed to be used with either
corrosion coupons or Corrater probes.
• The Corrater: An electronic instrument that measures the corrosion and pitting tendencies in a cooling system. It provides an instantaneous, direct reading of the system's corrosion rate in mils per year (mpy) when its probe is inserted
into the cooling water.
![Page 63: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/63.jpg)
63
Deposit Monitor: An aid in examining the performance of a cooling water program. A sample tube of proper
metallurgy is surrounded by a glass jacket to form a small heat exchanger. Cooling system water flows between the sample
tube and the glass jacket. The metal surface of the sample can be observed at any time during the testing period. Heat transfer rates can be sim ulated using a
cartridge heater and cooling water flows regulated with a control valve.
The Corrater gives instantaneous readouts of corrosion rates when its probe is inserted into an operating cooling water system.
![Page 64: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/64.jpg)
64
Microbiological Analysis:
Provides answers on the kinds and quantities of bacteria present in a cooling system.
Results of these analyses indicate the effectiveness of the microbiological control
program .
![Page 65: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/65.jpg)
65
The deposit monitor is a useful tool in determining the effectiveness of a chemical treatment program.
![Page 66: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/66.jpg)
66
Plant operating and supervisory personnel must know the impor tance of correct
system treatment and have the ability to monitor and control critical cooling water
variables on a day-to-day basis. Proper training of all cooling water personnel is a
prime method of achieving a successful treatment program .
What is the role of plant personnel in proper monitoring and control of the cooling water
system?
![Page 67: Cooling water problems](https://reader030.fdocuments.net/reader030/viewer/2022013111/547a1048b4af9fa0158b49f8/html5/thumbnails/67.jpg)
67
http://www.kimia-store.com/[email protected]