Conventional System

download Conventional System

of 27

Transcript of Conventional System

  • 8/11/2019 Conventional System

    1/27

    Conventional System

    Conventional treatment consists of the following unit processes: coagulation, flocculation,

    clarification, and filtration, and is typically followed by disinfection at full-scale. Figure 1

    describes conventional treatment. Conventional treatment is often preceded by pre-

    sedimentation, may be accompanied by powdered activated carbon (PAC) addition, utilize

    granular activated carbon (GAC) as a filter media, and in some cases be followed by GAC

    adsorption. Conventional treatment is often preceded by pre-oxidation, or oxidation takes

    place concurrently. Oxidants common to conventional treatment are chlorine, chloramine,

    chlorine dioxide or permanganate. Occasionally membrane processes, either membrane

    filtration or ultrafiltration, accompany conventional treatment.

    In coagulation, a positively charged coagulant (usually an aluminum or iron salt) is added to

    raw water and mixed in the rapid mix chamber. The coagulant alters or destabilizes

    negatively charged particulate, dissolved, and colloidal contaminants. Coagulant aid

    polymers and/or acid may also be added to enhance the coagulation process. Turbidity and

    total organic carbon (TOC) are measures of particulates and dissolved organics impacting

    coagulation.

  • 8/11/2019 Conventional System

    2/27

    During flocculation, gentle mixing accelerates the rate of particle collision, and the

    destabilized particles are further aggregated and enmeshed into larger precipitates.

    Flocculation is affected by several parameters, including the mixing speed, mixing intensity

    (G), and mixing time. The product of the mixing intensity and mixing time (Gt) is frequently

    used to describe the flocculation process.

    There are two primary destabilization mechanisms in drinking water treatment: charge

    neutralization and sweep flocculation. The mechanism is dependent upon the coagulant

    dose. Most drinking water treatment plants operate using sweep flocculation, which

    requires a higher coagulant dose, rather than charge neutralization. In charge neutralization,

    the positively charged metal coagulant is attracted to the negatively charged colloids via

    electrostatic interaction. Flocs start to form during the neutralization step as particle

    collisions occur. Adding excess coagulant beyond charge-neutralization results in the

    formation of metal coagulant precipitates. These metal hydroxide compounds (e.g., Al(OH)3

    or Fe(OH)3) are heavy, sticky and larger in particle size. Sweep flocculation occurs when

    colloidal contaminants are entrained or swept down by the precipitates as they settle in the

    suspension.

    The optimal pH range for coagulation is 6 to 7 when using alum and 5.5 to 6.5 when using

    iron. For high alkalinity water, excessive amounts of coagulant may be needed to lower the

    pH to the optimal pH range. In these cases, it may be beneficial to use acid in addition to the

    coagulant to reduce the amount of coagulant needed and effectively lower chemical costs.

    Enhanced coagulation is now widely practiced for removing disinfection byproduct (DBP)

    precursors, and it also removes inorganics, particulates, and color causing compounds.

    Removing these contaminants using coagulation depends on the amount of coagulant

    added. It is important to determine the optimal dose for coagulation; insufficient doses will

    not effectively destabilize the particles and adding excessive doses can cause detrimental

    effects such as re-stabilization, excessive sludge production, or corrosion.

  • 8/11/2019 Conventional System

    3/27

    Water quality parameters such as pH, temperature, and alkalinity may dictate effectiveness

    of the coagulation-filtration process. The pH during coagulation has a profound influence on

    the effectiveness during the destabilization process. The pH controls both the speciation of

    the coagulant as well as its solubility, and it also affects the speciation of the contaminants.

    For high alkalinity water, an excessive amount of coagulant may be required to lower the pH

    to the optimal pH ranges (alum pH 6 to 7, iron 5.5 to 6.5). Temperature also impacts the

    coagulation process because it affects the viscosity of the water. Thus lower temperature

    waters can decrease the hydrolysis and precipitation kinetics. For some treatment

    objectives, other parameters like iron, manganese or sulfate impact coagulation. Some of

    the alternative coagulants such as polyaluminum chloride (PACl) can be advantageous over

    the traditional coagulants in low temperature conditions as these coagulants are already

    hydrolyzed, and therefore temperature tends to have less effect on the coagulation process.

    Following flocculation, agglomerated particles enter the clarification unit where they are

    removed by sedimentation by gravity or are floated and skimmed from the surface of the

    clarification unit. In the sedimentation processes, the majority of the solids are removed by

    gravitational settling; particles that do not settle and are still suspended are removed during

    the filtration process. Sedimentation is generally accomplished in rectangular or circular

    basins and is often enhanced by the addition of inclined plates or tubes which increase

  • 8/11/2019 Conventional System

    4/27

    effectiveness of the process by effectively increasing the surface area of the sedimentation

    basin. Dissolved air flotation (DAF) is another clarification process in which air is diffused as

    fine bubbles and suspended particles are floated to the surface and removed by skimming.

    Generally, DAF is most effective for small, fine, low-density particles like algae and may not

    be effective is all instances. Like conventional sedimentation, solids not removed by DAF are

    removed during filtration.

    Two parameters frequently used to describe the clarification process are the overflow rate

    and the detention time. The overflow rate is the process loading rate and is usually

    expressed in gpm/sf or gpd/sf. Overflow rates for conventional sedimentation generally

    range from 0.3 to 1 gpm/sf (500 to 1500 gpd/sf). Overflow rates for other processes can

    vary significantly. There are proprietary sand-ballasted clarification systems that have been

    demonstrated to operate effectively at overflow rates as high as 20 gpm/sf. Typical

    detention times range from 1 to 2 hours, although many states require up to 4 hours for

    full-scale surface water treatment.

    The most commonly used filter type in the conventional treatment process is a dual-media

    filter comprised of anthracite and sand; however, mono-media (sand), multi-media (garnet,

    anthracite, and sand), and other media configurations, including the use of granular

    activated carbon, are also used in drinking water treatment. During filtration, the majority

    of suspended particles are removed in the top portion of the filter media. Filters are

    backwashed to dislodge and remove particles trapped within the filter bed, to reduce head

    loss (pressure build up), and to keep the filter media clean.

    The filter loading rate is a measure of the filter production per unit area and is typically

    expressed in gpm/sf. Typical filter loading rates range from 2 to 4 gpm/sf; however, higher

    filter loading rates, 4 to 6 gpm/sf, are becoming more common at full-scale. This can be a

    critical parameter because it determines the water velocity through the filter bed and can

    impact the depth to which particles pass through the media. The filter run time describes

  • 8/11/2019 Conventional System

    5/27

    the length of time between filter backwashes during which a filter is in production mode.

    The filter run time is not only an indicator of the effectiveness of prior treatment (i.e., the

    ability of the coagulation and clarification steps to remove suspended solids), but also plays

    a role in the effectiveness of the filter itself. Filter performance, particularly with regard to

    particulate contaminants, is often poorest immediately following a backwash. As the filter

    run time increases and the concentration of solids in the media increases, the filtration

    process often performs better with regard to particulate contaminant removal.

    Residuals generated by the conventional treatment process include coagulation solids

    (sludge) and spent backwash. Spent backwash is often returned to the treatment process as

    a means to minimize water loss. Sludge may also be recycled to minimize coagulant and

    coagulant aid doses and improve process performance. Process solids (i.e., coagulation

    sludge and filtered solids) will contain elevated concentrations of contaminants removed

    during the treatment process. Depending on the source water concentration of a particular

    contaminant and any disposal limitations, it may be necessary evaluate the disposal of

    process solids with respect to state and local hazardous waste regulations.

  • 8/11/2019 Conventional System

    6/27

    Membrane Filtration

    Membranes have been used in water and wastewater applications since the 1960's.

    However, initially membrane processes were felt to be too expensive for this field, and were

    only applied in niche applications or special circumstances. This changed during the 1990's

    due to the emergence of several drivers, including legislation to achieve improved

    treatment standards, and resource scarcity, which created the need to use membranes on

    saline or wastewater sources. The rapid uptake of membranes since 2000 has led to a

    dramatic fall in costs, to the extent that membranes now often compete with conventional

    processes, while achieving much better quality standards.

    There are two classes of membrane process used in the water and wastewater field. The

    first category includes reverse osmosis (RO) and nanofiltration (NF). These membranes have

    a dense non porous separating layer cast onto a porous support, and are used for the

    removal of dissolved substances. The second category is membrane filtration, in which a

    micro-porous separating layer provides a barrier to the finest particles present in the feed

    source but allows dissolved components to pass through. Membrane filtration is often used

    as a treatment process in its own right, but may also be used as pre-treatment to an RO

    stage.

    An early application was in the use of RO and membrane filtration for industrial water

    treatment, either for general process water use or for ultrapure water production. This has

    now been surpassed in importance by the use of membrane filtration in drinking water

    treatment to remove turbidity and provide a disinfection barrier, particularly to parasitic

    microorganisms such as cryptosporidium and giardia.

    One of the longest established uses for membranes in water treatment is in the use of RO

    for desalinating seawater. Even in the Middle East where energy is cheap, RO has recently

    taken over from distillation processes as the preferred technology for most duties. A recent

    new application of membranes in desalination is in the use of membrane filtration as a pre-

    treatment to RO, and this area has grown at a dramatic rate since 2005.

  • 8/11/2019 Conventional System

    7/27

    Last but not least, membranes are now being used in the newly emerging application of

    wastewater reuse, the fastest growing and potentially most promising membrane

    application in the water industry. In fact, membranes have been an enabling technology for

    this application, since without membranes, wastewater treatment to a standard

    guaranteeing quality and security would be too difficult and costly.

    RO is required to ensure that dissolved organics, and sometimes salts, are removed to a

    sufficient extent. Membrane filtration is needed as a pre-treatment to the RO, and this

    application will form the subject this paper. Without membrane pre-treatment, stable

    operation of the RO has been found to be unachievable, so the advent of the membrane

    filtration boom for drinking water in the late 1990's enabled the commercial realization of

    this application.

    Technology

    There are two types of membrane filtration technology for water and wastewater

    treatment, namely ultrafiltration (UF) and microfiltration (MF). UF has pores of 0.010.02

    m, while MF for water treatment has pores of 0.04 0.10 m. In wastewater applications,

    coarser MF pore sizes of 0.2 and 0.4 m can be used, but the finer MF membranes for water

    duties are also suitable. The separation spectrum illustrated in Figure 1 shows the particle

    size that the different filtration technologies are designed to address, with some examples

    of common challenges.

  • 8/11/2019 Conventional System

    8/27

    The figure shows that membrane filtration is two to three orders of magnitude coarser than

    RO. MF removes common particles found in water including bacteria and other microbial

    organisms, while UF removes viruses in addition, thereby providing a physical disinfection

    barrier. For RO pre-treatment of wastewater, membrane filtration is normally used in

    combination with coagulation to control fouling, ensure operational stability and improve

    removals of dissolved organics.

    Resources

    Water resources are under pressure from increasing population, especially in arid regions,

    and greater use of water per capita due to economic development. Some attempts have

    been made to reduce water usage through conservation programmes, but so far this has

    just had the effect of containing growth.

    Not only is demand rising, but traditional resources will become less available in the future.

    Water supply is currently obtained mainly from freshwater resources, as illustrated by Table

  • 8/11/2019 Conventional System

    9/27

    1 below [1]. Surface water is the most important water resource, but groundwater is also a

    significant contributor accounting for 36% of total. New resources such as desalination and

    wastewater reuse accounted for just 0.5% of the total in 2005. However, the balance of

    resource supply will undergo a fundamental change in the coming decades. Groundwater is

    effectively a non-renewable resource. Millennia are required for groundwater resources to

    accumulate, but these resources can be depleted in just a few years.

    Combined with the inexorable reduction of groundwater availability, the quality of

    groundwater is under threat due to a variety of factors, such as saline intrusion near the

    coast as the water table declines due to over abstraction. Also groundwaters are becoming

    contaminated by industrial and agricultural residuals caused by increasing fertiliser and

    pesticide since the Second World War. The effect of this activity has taken some decades to

    become established, but since the early 1990's, treatment processes have been required in

    the developed world for groundwater sources to control contaminant levels.

    In the long term, new sources such as desalination and wastewater reuse will have to

    replace groundwater, and the beginning of this trend has already started to occur. Growth

    of novel resources significantly above the underlying growth rate of water use is therefore

    assured for the foreseeable future. On top of this, the growth rates for membrane filtration

    processes will be even greater, as membranes become established as the dominant

    technical solution. Thus currently desalination and wastewater reuse markets have annual

    growth rates of 8% and 14% respectively, but the use of membrane filtration in these

    applications is growing at 17% or more [1,2].

  • 8/11/2019 Conventional System

    10/27

    Currently, 10% of water abstracted is collected as wastewater, and just under half of this is

    treated prior to disposal [1]. However, only a small fraction of treatment is to a reuse

    standard. Wastewater is therefore available as an abundant resource for treatment to a

    reuse standard. Most reuse at the moment is destined for industry and agriculture, with just

    11% for municipal use. However, municipal applications are undergoing dramatic growth,

    which will be illustrated by the case study at the end of the paper.

    Energy Use

    Unfortunately, these novel water sources require much more energy for treatment than

    traditional freshwater resources, and this will become a major consideration for the future.

    In particular, desalination is very energy intensive, and this provides an important

    motivation for developing wastewater reuse as the default option where resource

    constraints occur, leaving desalination for situations where there is no other choice. Energy

    efficiency in water supply is now recognised as a major driver for the selection of alternative

    resources.

  • 8/11/2019 Conventional System

    11/27

    Ion Exchange

    The ion exchange technology is used for different water treatment applications:

    Softening (removal of hardness)

    De-alkalisation (removal of bicarbonate)

    Decationisation (removal of all cations)

    Demineralisation (removal of all ions)

    Mixed bed polishing

    Nitrate removal

    Selective removal of various contaminants

    Softening

    Natural water contains calcium and magnesium ions (see water analysis) which form salts

    that are not very soluble. These cations, together with the less common and even less

    soluble strontium and barium cations, are called together hardness ions. When the water

    evaporates even a little, these cations precipitate. This is what you see when you let water

    evaporate in a boiling kettle on the kitchen stove.

    Hard water also forms scale in water pipes and in boilers, both domestic and industrial. It

    may create cloudiness in beer and soft drinks. Calcium salts deposit on the glasses in your

    dishwasher if the city water is hard and you have forgotten to add salt.

    Strongly acidic cation exchange resins (SAC, see resin types) used in the sodium form

    remove these hardness cations from water. Softening units, when loaded with these

    cations, are then regenerated with sodium chloride (NaCl, table salt).

  • 8/11/2019 Conventional System

    12/27

    Reactions

    Here the example of calcium:

    2 R-Na + Ca++ ---> R2-Ca + 2 Na+

    R represents the resin, which is initially in the sodium form. The reaction for magnesium is

    identical.

    The above reaction is an equilibrium. It can be reversed by increasing the sodium

    concentration on the right side. This is done with NaCl, and the regeneration reaction is:

    R2-Ca + 2 Na+ ---> 2 R-Na + Ca++

    What happens to the water

    Raw water softened water

    The water salinity is unchanged, only the hardness has been replaced by sodium. A small

    residual hardness is still there, its value depending on regeneration conditions.

    Uses of softeners:

    Treatment of water for low pressure boilers

    In Europe, most dishwashers have a softening cartridge at the bottom of the

    machine

  • 8/11/2019 Conventional System

    13/27

    Breweries and soft drink factories treat the water for their products with food grade

    resins

    Softening the water does not reduce its salinity: it merely removes the hardness ions and

    replaces them with sodium, the salts of which have a much higher solubility, so they don't

    form scale or deposits.

    De-alkalisation

    This particular process uses a weakly acidic cation resin. This resin type is capable of

    removing hardness from water when it also contains alkalinity. After treatment, the water

    contains carbon dioxide, that can be eliminated with adegasifier tower.The cation resin is

    very efficiently regenerated with an acid, usually hydrochloric acid.

    Reactions

    Here the example of calcium:

    2 R-H + Ca++(HCO3)2 R2-Ca + 2 H++ 2 HCO3

    and the hydrogen cations combine with the birarbonate anions to produce carbon dioxide

    and water:

    H++ HCO3

    CO2+ H2O

    What happens to the water

    Raw water

    WAC (H)

    Decarbonated water

    http://dardel.info/IX/processes/degasser.htmlhttp://dardel.info/IX/processes/degasser.htmlhttp://dardel.info/IX/processes/degasser.htmlhttp://dardel.info/IX/processes/degasser.html
  • 8/11/2019 Conventional System

    14/27

    Recombination of hydrogen and bicarbonate and removal of carbon dioxide with the

    degasifier:

    Decarbonated water

    DEG

    Degassed water

    The salinity has decreased. Temporary hardness is gone

    De-alkalisation is used:

    In breweries

    In household drinking water filters

    For low pressure boilers

    As a first step before the SAC exchange in demineralisation

    De-alkalisation reduces the salinity of water, by removing hardness cations and bicarbonate

    anions.

    Decationisation

    The removal of all cations is seldom practiced, except as a first stage of the demineralisation

    process, or sometimes in condensate polishing where the decationiser precedes a mixed

    bed unit. A strongly acidic cation exchange resin (SAC) is used in the H+form.

    Reactions

    Here the example of sodium, but all cations react in the same way:

    R-H + Na+

    R-Na + H+

  • 8/11/2019 Conventional System

    15/27

    The equilibrium reaction is reversed for regeneration by increasing the hydrogen

    concentration on the right side. This is done with a strong acid, HCl or H2SO4:

    R-Na + H+ R-H + Na

    +

    What happens to the water

    Raw water

    SAC (H)

    Decationised water

    DEG

    Decat + degassed

    water

    In the second step, adegasifieris used again to remove the carbon dioxide formed by

    combining the bicarbonate anions and the released hydrogen cation. The water salinity isreduced, and the water is now acidic. A small sodium leakage is shown.

    Demineralisation

    For many applications, all ions in the water must be removed. In particular, when water is

    heated to produce steam, any impurity can precipitate and cause damage. As there are

    cations and anions in the water, we must use two different types of resins: a cation

    exchanger and an anion exchanger. This combined arrangement produces pure water, as

    presented in thegeneral introduction. Demineralisation is also called deionisation. The

    cation resin is used in the hydrogen form (H+) and the anion resin in the hydroxyl form (OH

    ), so that the cation resin must be regenerated with an acid and the anion resin with an

    alkali.

    http://dardel.info/IX/processes/degasser.htmlhttp://dardel.info/IX/processes/degasser.htmlhttp://dardel.info/IX/processes/degasser.htmlhttp://dardel.info/IX/IX_Intro.html#deminhttp://dardel.info/IX/IX_Intro.html#deminhttp://dardel.info/IX/processes/degasser.html
  • 8/11/2019 Conventional System

    16/27

    Adegasifier is used to remove the carbon dioxide created after cation exchange when the

    water contains a significant concentration of bicarbonate.

    The cation resin is usually located before the anion resin: otherwise if the water contains

    any hardness, it would precipitate in the alkaline environment created by the OH

    form

    anion resin as Ca(OH)2or CaCO3, which have low solubility.

    Layout SAC(DEG)SBA

    Let us first consider a simple demineralisation system comprising a strong acid cation

    exchange resin in the H+form, a degasifier (optional) and a strong base anion exchange resin

    in the OH

    form. The first step is decationisation as shown above:

    RSAC-H + Na+ RSAC-Na + H

    +

    With calcium insead of sodium (also valid for magnesium and other divalent cations):

    2 RSAC-H + Ca++

    (RSAC)2-Ca + 2 H+

    In the second step, all anions are removed with the strong base resin:

    RSBA-OH + Cl

    RSBA-Cl + OH

    The weak acids created after cation exchange, which are carbonic acid and silicic acid

    (H2CO3and H2SiO3) are removed in the same way:

    RSBA-OH + HCO3

    RSBA-HCO3

    + OH

    And finally, the H+ions created in the first step react with the OH

    ions of the second step to

    produce new molecules of water. This reaction is irreversible:

    H++ OH

    H2O

    1 & 2: Cation exchange beginning with the removal of temporary hardness (WAC, as in

    dealkalisation) followed by the removal of all remaining cations (SAC):

    http://dardel.info/IX/processes/degasser.htmlhttp://dardel.info/IX/processes/degasser.html
  • 8/11/2019 Conventional System

    17/27

    Raw water

    WAC (H)

    Decarbonated water

    SAC (H)

    Decationised water

    3 & 4: Anion exchange begining after degassing with the removal of strong acids (WBA)

    followed by the removal of weak acids (SBA):

    Decat + degassed

    water

    WBA (FB)

    Partially

    demineralised

    SBA (OH)

    Demineralised water

    A full demineralisation line is shown below, with a cation exchange column (WAC/SAC),

    adegasifier,an anion exchange column (WBA/SBA), and a polishing mixed bed unit. The use

    of a weakly acidic resin and the degasifier column are conditioned by the presence of

    hardness and alkalinity in the feed water, as explained in the previous sections.

    http://dardel.info/IX/processes/degasser.htmlhttp://dardel.info/IX/processes/degasser.htmlhttp://dardel.info/IX/processes/degasser.htmlhttp://dardel.info/IX/processes/degasser.html
  • 8/11/2019 Conventional System

    18/27

    A demineralisation line (click to enlarge)

    Regeneration

    Regeneration is done inthoroughfare,which means that the regenerant first goes through

    the strong resin, which requires an excessof regenerant, and the regenerant not consumed

    by the strong resin is usually sufficient to regenerate the weak resin without additional

    dosage.

    The cation resins are regenerated with a strong acid, preferably HCl, because H2SO4can

    precipitatecalcium.

    The anion resins are regenerated with caustic soda.

    Ads by surf and keep

    Regeneration of the demineralisation line (click to enlarge)

    The quality obtained is the same as in the simple SAC-SBA layout, but because the weak

    resins are practicallly regenerated "free of charge", the regenerant consumption is

    considerably lower. Additionally, the weak resins have a higher operating capacity than the

    strong resins, so the total volume of ion exchange resins is reduced.

    Uses

    Examples of demineralisation:

    http://dardel.info/IX/processes/regeneration.html#thoroughfarehttp://dardel.info/IX/processes/regeneration.html#thoroughfarehttp://dardel.info/IX/processes/regeneration.html#thoroughfarehttp://dardel.info/IX/processes/ProcessPicts/AmberpackDM_regen.jpghttp://dardel.info/IX/processes/ProcessPicts/AmberpackDM.jpghttp://dardel.info/IX/processes/ProcessPicts/AmberpackDM_regen.jpghttp://dardel.info/IX/processes/ProcessPicts/AmberpackDM.jpghttp://dardel.info/IX/processes/regeneration.html#thoroughfare
  • 8/11/2019 Conventional System

    19/27

  • 8/11/2019 Conventional System

    20/27

    What happens to the water

    Practically nothing is left:

    Demineralised water

    SAC (H) + SBA

    (OH)

    Nothing is left

    Mixed bed polishing produces a water with less than 0.1 S/cm conductivity. With

    sophisticated design and appropriate resins, the conductivity of pure water (0.055 S/cm)

    can be achieved. Residual silica values can be as low as 1 g/L.

    The pH valueshould not be used as a process control, as pH meters are unable to operate at

    1 S/cm conductivity or below.

    Uses

    Treatment of water pre-demineralised with ion exchange resins

    Polishing of reverse osmosis permeate

    Polishing of sea water distillate

    Treatment ofturbine condensate in power stations

    Treatment of process condensate in various industries

    Production of ultra-pure water for the semiconductors industry

    Service de-ionisation(with off-site regenerated columns)

    http://dardel.info/IX/processes/condensate.htmlhttp://dardel.info/IX/processes/condensate.htmlhttp://dardel.info/IX/processes/condensate.htmlhttp://dardel.info/IX/processes/SDI.htmlhttp://dardel.info/IX/processes/SDI.htmlhttp://dardel.info/IX/processes/SDI.htmlhttp://dardel.info/IX/processes/condensate.html
  • 8/11/2019 Conventional System

    21/27

    Nitrate removal

    Nitrate can be removed selectively from drinking water using strong base anion resins in the

    chloride cycle, i.e. regenerated with a NaCl brine. The reaction is:

    RSBA-Cl + NO3

    RSBA-NO3+ Cl

    What happens to the water

    Raw water

    SBA (Cl)

    Denitrated water

    Conventional SBA resins can be used, but they also remove sulphate from water. See

    theselectivity table. Depending on the resin type, some (selective resins) or all (non-

    selective) sulphate is removed. Bicarbonate is only removed partially at the beginning of the

    service run.

    Uses

    Mainly municipal water treatment

    http://dardel.info/IX/other_info/selectivity_a.htmlhttp://dardel.info/IX/other_info/selectivity_a.htmlhttp://dardel.info/IX/other_info/selectivity_a.htmlhttp://dardel.info/IX/other_info/selectivity_a.html
  • 8/11/2019 Conventional System

    22/27

    Selective removal of various other contaminants

    Selective removal of metals and other contaminants is mainly used for drinking water and

    for waste. Many of these applications require special resins: chelating resin making stable

    metal complexes, for instance.

    Examples

    Removal of boron (boric acid) from drinking water

    Removal of nitrate from drinking water (shownabove)

    Removal of perchlorate from drinking water

    Removal of heavy metals from waste: Cd, Cr, Fe, Hg, Ni, Pb, Zn

    In many of these applications, a residual concentration in the g/L range is possible.

    Some contaminants are difficult to remove with ion exchange, due to a poor selectivity of

    the resins. Examples: As, F, Li. See theperiodic systemof the elements with some ion

    exchange data.

    http://dardel.info/IX/processes/processes.html#denitrhttp://dardel.info/IX/processes/processes.html#denitrhttp://dardel.info/IX/processes/processes.html#denitrhttp://dardel.info/IX/other_info/Mendeleev.htmlhttp://dardel.info/IX/other_info/Mendeleev.htmlhttp://dardel.info/IX/other_info/Mendeleev.htmlhttp://dardel.info/IX/other_info/Mendeleev.htmlhttp://dardel.info/IX/processes/processes.html#denitr
  • 8/11/2019 Conventional System

    23/27

    Air Stripping

    Air stripping is a full-scale technology in which volatile organics are partitioned from ground water

    by greatly increasing the surface area of the contaminated water exposed to air. Types of aeration

    methods include packed towers, diffused aeration, tray aeration, and spray aeration.

    Air stripping involves the mass transfer of volatile contaminants from water to air. For ground water

    remediation, this process is typically conducted in a packed tower or an aeration tank. The typical

    packed tower air stripper includes a spray nozzle at the top of the tower to distribute contaminated

    water over the packing in the column, a fan to force air countercurrent to the water flow, and a

    sump at the bottom of the tower to collect decontaminated water. Auxiliary equipment that can be

    added to the basic air stripper includes an air heater to improve removal efficiencies; automated

    control systems with sump level switches and safety features, such as differential pressure monitors,

    high sump level switches, and explosion-proof components; and air emission control and treatment

    systems, such as activated carbon units, catalytic oxidizers, or thermal oxidizers. Packed tower air

    strippers are installed either as permanent installations on concrete pads or on a skid or a trailer.

  • 8/11/2019 Conventional System

    24/27

    Aeration tanks strip volatile compounds by bubbling air into a tank through which contaminated

    water flows. A forced air blower and a distribution manifold are designed to ensure air-water

    contact without the need for any packing materials. The baffles and multiple units ensure adequate

    residence time for stripping to occur. Aeration tanks are typically sold as continuously operated skid-

    mounted units. The advantages offered by aeration tanks are considerably lower profiles (less than 2

    meters or 6 feet high) than packed towers (5 to 12 meters or 15 to 40 feet high) where height may

    be a problem, and the ability to modify performance or adapt to changing feed composition by

    adding or removing trays or chambers. The discharge air from aeration tanks can be treated using

    the same technology as for packed tower air discharge treatment.

    Modifying packing configurations greatly increase removal efficiency. A recent innovation is the so-

    called low-profile air stripper that is offered by several commercial vendors. This unit packs a

    number of trays in a very small chamber to maximize air-water contact while minimizing space.

    Because of the significant vertical and horizontal space savings, these units are increasingly being

    used for ground water treatment.

    Air strippers can be operated continuously or in a batch mode where the air stripper is intermittently

    fed from a collection tank. The batch mode ensures consistent air stripper performance and greater

    energy efficiency than continuously operated units because mixing in the storage tanks eliminates

    any inconsistencies in feed water composition.

    The eventual duration of cleanup using an air stripping system may be tens of years and depends on

    the capture of the entire plume from the ground water

  • 8/11/2019 Conventional System

    25/27

    With two treatment plants for drinking water and one treatment plant for recycled water, we can

    process up to 61 million gallons per day. Our pipeline system pumping units can deliver up to 38,000

    gallons per minute. Water may be piped directly to you or into a tank until needed. Because of

    Marin's hilly terrain, about 90 percent of the water must be pumped at least once before it reaches

    the tap. Some water is pumped up to six times.

    Our pipes range in size from the 3/4-inch pipe that connects your water meter to our main to the 42-

    inch transmission pipes that carry source water to the treatment plants. The pipes are made of

    various materials, depending on when and where they were installed. Since the late 1970s, however,

    we've installed only welded steel and polyvinyl chloride (plastic) mains due to their expected long

    life spans

  • 8/11/2019 Conventional System

    26/27

    Question 2: Explain the source of Non Returned Water (NRW)

    a.Distribution pipe

    After passing the treatment process, the water stored in the storage tank is distributed through the

    distribution system. Water distribution can be done with the method:

    A. Gravity

    B. Pump to distribution pipe

    C. The pump and reservoir

    Common features that are in the water distribution system are:

    i. Able to provide adequate clean water

    ii. Distribution system to be effective.

    iii. Piping system capable of supplying water continuously with minimal maintenance.

    iv. Materials used for the distribution pipes shall be durable and long-term adverse impact to

    customers

  • 8/11/2019 Conventional System

    27/27

    Distribution system must be economic in terms of design, layout and construction

    Meter under registration

    Apparent losses are usually caused by water theft, billing errors, or revenue meter under-

    registration. While the first two causes are directly related to water utility management and may be

    reduced by improving company procedures, water meter inaccuracies are considered to be the most

    significant and hardest to quantify. Water meter errors are amplified in networks subjected to water

    scarcity, where users adopt private storage tanks to cope with the intermittent water supply. The

    aim of this paper is to analyse the role of two variables influencing the apparent losses: water meter

    age and the private storage tank effect on meter performance. The study was carried out in Palermo(Italy). The impact of water meter ageing was evaluated in laboratory by testing 180 revenue meters,

    ranging from 0 to 45 years in age. The effects of the private water tanks were determined via field

    monitoring of real users and a mathematical model. This study demonstrates that the impact on

    apparent losses from the meter starting flow rapidly increases with meter age. Private water tanks,

    usually fed by a float valve, overstate meter under-registration, producing additional apparent losses

    between 15% and 40% for the users analysed in this study