CONTENT
EPE METALCLAD SWITCHGEARS SERIESEPE 12A20 / 25 - 12KV METALCLAD SWITCHGEAR
EPE 10D - 12KV METALCLAD SWITCHGEAREPE 24A25 - 24KV METALCLAD SWITCHGEAREPE 36A25 - 36KV METALCLAD SWITCHGEAR
EPE METALCLAD SWITCHGEARS AMS SERIES12kV AMS METALCLAD SWITCHGEAR24kV AMS METALCLAD SWITCHGEAR
40.5KV AMS METALCLAD SWITCHGEAR
36KV COMPACT GAS SWITCHGEARHICLAD 30GA 36KV COMPACT GAS SWITCHGEAR
FEP SF6 GAS CIRCUIT BREAKER40.5KV FEP SF6 GAS CIRCUIT BREAKER
RING MAIN UNITOIL RING MAIN UNITSF6 RING MAIN UNIT
1234
567
8
9
1011
Indoor air insulated metalclad switchgear.
Vacuum circuit breaker is mounted on truck for horizontal withdrawal and isolation.
Integral fault making earthing switch, class A on the circuit side. Busbar earthing truck is optional.
GENERAL DESCRIPTION
Other values are available on request.
Other values are available on request.
12A20 / 2512kV METALCLAD SWITCHGEAR
Rated voltageRated currentRated frequencyRated insulation level-Power frequency withstand voltage-Lightning impulse withstand voltage
Rated short circuit breaking currentRated short circuit withstand currentRated short circuit making current (peak)Mechanical enduranceRated operating sequence/duty
Rated closing timeRated opening timeRated breaking time
Standard trip/close supply (1)Standard motor charging supply (2)
kVAHz
kV/ 1 minkV, 1.2/50 μs
kA, rmskA/3skA10,000
0-0.3s-CO-3min-CO
msmsms
VdcVdc (Vac)
12630/1250/2000
50
28/3275/85
50/6320/2550/63
<60<50<60
30/11030/110(240 Vac)
Circuit Breaker Model VFT-12
Rated voltageRated frequencyRated insulation level-Power frequency withstand voltage/min-Lightning impulse withstand voltage (peak)
Rated normal current of BusbarRated short time withstand currentRated peak withstand currentStandard degree of protection (1) Enclosure Compartment
Dimension Width Depth Height
kVHz
kVkV, 1.2/50 μs
AkA/3skA
mmmmmm
1250
28/3275/85
800/1250/20002050
4X3X
600, 800, (2000A) 2200,2250 (with PT)
2300
1250
28/3275/85
2563
Switchgear Model 12A20 12A25
The values below are given for normal operating condition as defined in IEC 60298, IEC 60694, IEC 62271-100 / 200
Mechanical intelocks are provided to safeguards against maloperation.
Design type tested to IEC 62271-100/200, IEC 60298, IEC 60056, IEC 60694
1
The cubicle is an earthed, metallic enclosure which is fully metalclad as defined in IEC 60298. The cubicle is divided into the following compartments which are seperated by metallic partitions: Busbars Circuit breaker Cables, earthing switch and instrument transformers
Low voltage auxiliary equipment when required
Each medium voltage compartment is provided with a pressure relief flap.
The standard degree of protection for the enclosure is IP4X and for the partitions is IP3X. Other values are available on request.
CUBICLE
Other values are available on request.
Other values are available on request.
Circuit Breaker Model VFT-12D
Switchgear Model EPE 10D
The values below are given for normal operating condition as defined in IEC 60298, IEC 60694
10D12kV METALCLAD SWITCHGEAR
2
Other values are available on request.
Rated voltageRated frequencyRated insulation level-Power frequency withstand voltage/min-Lightning impulse withstand voltage (peak)
Rated normal current in BusbarShort time withstand currentPeak withstand currentStandard degree of protection (1) Enclosure Compartment
Dimension Width Depth Height
kVHz
kVkV, 1.2/50 μs
AkA/3skA
mmmmmm
1250
2850
800/1250/20002563
3X2X
700 1950 2400
Rated voltageRated currentRated frequencyRated insulation level-Power frequency withstand voltage-Lightning impulse withstand voltage
Rated short circuit breaking currentRated short circuit withstand currentRated short circuit making current (peak)Mechanical enduranceRated operating sequence/duty
Rated closing timeRated opening timeRated breaking time
Standard trip/close supply (1)Standard motor charging supply (2)
kVAHz
kV/ 1 minkV, 1.2/50 μs
kA, rmskA/3skA10,000 times
0-0.3s-CO-3min-CO
msmsms
VdcVdc (Vac)
12630/1250/2000
50
2875
252563
605060
30/11030/110(240 Vac)
All control and indicating devices are located on the front of the circuit breaker unit. These include manual close/open knob, manual charging slot, position switch, operation counter, close/open indicator, spring charged and discharged indicator.
The circuit breaker is mounted on truck for horizontal withdrawal and isolation. Both the ‘service’ and ‘isolate/test’ positions are within the compartment.
Safety shutters are provided within the circuit breaker compartment. These automatic safety shutters cover the busbars and feeder spouts when the circuit breaker is at the ‘isolate/test’ position. They can be padlocked in the closed position if so desired and kept open for testing and maintenance purposes by means of manually operated catches, which in turn are self cancelling when the circuit breaker is returned to the unit.
24A2524kV METALCLAD SWITCHGEAR
Other values are available on request.
Other values are available on request.
Circuit Breaker Model VJ 22
Switchgear Model 24A25
The values below are given for normal operating condition as defined in IEC 60298, IEC 60694
Vacuum Circuit Breaker
2
Other values
IEC
3
Rated voltageRated frequencyRated insulation level-Power frequency withstand voltage/min-Lightning impulse withstand voltage (peak)
Rated normal current in BusbarShort time withstand currentPeak withstand currentStandard degree of protection (1) Enclosure Compartment
Dimension Width Depth Height
kVHz
kVkV, 1.2/50 μs
AkA/3skA
mmmmmm
2450
50125
1250/200025
62.5
1P3X1P2X
900, 1100 (2000A panel)3000, 3500 (with PT)
2350
Rated voltageRated currentRated frequencyRated insulation level-Power frequency withstand voltage-Lightning impulse withstand voltage
Rated short circuit breaking currentRated short circuit withstand currentRated short circuit making current (peak)Mechanical enduranceRated operating sequence/duty
Rated closing timeRated opening timeRated breaking time
Standard trip/close supply (1)Standard motor charging supply (2)
kVAHz
kV/ 1 minkV, 1.2/50 μs
kA, rmskA/3skA10,000 times
0-0.3s-CO-3min-CO
msmsms
VdcVdc (Vac)
24630/1250/2000
50
50125
2525
62.5
505070
110110
VCB cannot be engaged or withdrawn unless it is open.
VCB can only be closed or opened if it is fully engaged or isolated. (not in-between)
VCB cannot be engaged if the control plug is removed.
VCB cannot be engaged when the earthing switch is closed and vice-versa.
Key interlocks are provided if required (optional).
Safety Interlocks
Other values are available on request.
Other values are available on request.
Circuit Breaker Model VJ 32 VJ 32D
Switchgear Model 36A25 36A25
The values below are given for normal operating condition as defined in IEC 60298, IEC 60694
Single Bus Double Bus
36A2536kV METALCLAD SWITCHGEAR
4
Rated voltageRated frequencyRated insulation level-Power frequency withstand voltage/min-Lightning impulse withstand voltage (peak)
Rated normal current in BusbarShort time withstand currentPeak withstand currentStandard degree of protection (1) Enclosure Compartment
Dimension Width Depth Height
kVHz
kVkV, 1.2/50 μs
AkA/3skA
mmmmmm
3650
70170
1250/200025
62.5
1P3X1P2X
1100 11003650 36502150 2350
Rated voltageRated currentRated frequencyRated insulation level-Power frequency withstand voltage-Lightning impulse withstand voltage
Rated short circuit breaking currentRated short circuit withstand currentRated short circuit making current (peak)Mechanical enduranceRated operating sequence/duty
Rated closing timeRated opening timeRated breaking time
Standard trip/close supply (1)Standard motor charging supply (2)
kVAHz
kV/ 1 minkV, 1.2/50 μs
kA, rmskA/3skA10,000 times
0-0.3s-CO-3min-CO
msmsms
VdcVdc
36800/1250/2000
50
70170
2525
62.5
605070
30/11030/110(240 Vac)
* Forced cooling ventilation is required ** DC Resistance of current transformer
������������������ ������� ����
Description
5
Rated voltageRated FrequencyRated insulation level-Power frequency withstand voltage/min-Lightning impulse withstand voltage (peak)
Rated normal current in BusbarShort time withstand currentPeak withstand currentS tandard degree of protection (1) Enclosure Compartment
DimensionW idth
Depth Height
kVHz
kVkV
AAkA
mmmmmm
7.2/12/15/17.550/60
4275/95
630/1250/1600/2000/2500/3150/4000630/1250/1600/2000/2500/3150/4000
50/63/80/125/130
4X2X
650 (800,1000)22501400
�������������������� ���������������
Circuit Breaker Model Rated voltageRated currentRated frequencyRated insulation level-Power frequency withstand voltage-Lightning impulse withstand voltage
Rated short circuit breaking currentRated short circuit withstand currentRated short circuit making current (peak)Electrical endurance
Rat ed operating sequence/duty
Rated closing timeRated opening timeRated breaking time
Rated auxiliary control voltage
kVAHz
kV/ 1 minkV, peak
kA, rmskA/4skA
274 (Class E2 in accordance with
O-0.3s-CO-180s-CO(up to 40kA)
msmsms
7.2/12/15/17.5630/1250/1600/2500/3150/400050/60
4275/95
20/25/31.5/40/5020/25/31.5/40/5050/63/80/125/130
35-7525-3540-50
IEC 62271-100 and GB 1984-2003)
O-0.3s-CO-180s-CO(50kA)
V AC110/220;DC 110/220
IEC 62271-100/200
* DC Resistance of current transformer
��!����������������� ������� �����
6
DescriptionRated voltageRated frequencyRated insulation level-Power frequency withstand voltage/min-Lightning impulse withstand voltage (peak)
Rated normal current in BusbarShort time withstand current (4s)Peak withstand currentStandard degree of protection (1) Enclosure Compartment
DimensionWidth
Depth Height
kVHz
kVkV
AAkA
mmmmmm
2450/60
50/65125
630/1250/1600/2000/250020/25/31.550/63/80
1P4X1P2X
800 (1000)16802250
��!����������������� ���������������
Circuit Breaker Model Rated voltageRated currentRated frequencyRated insulation level-Power frequency withstand voltage-Lightning impulse withstand voltage
Rated short circuit breaking currentRated short circuit withstand currentRated short circuit making current (peak)Electrical endurance
Rated operating sequence/duty
Rated closing timeRated opening timeRated breaking time
Rated auxiliary control voltage
kVAHz
kV/ 1 minkV, peak
kA, rmskA/4skA
274 (Class E2 in accordance with
O-0.3s-CO-180s-CO
msmsms
24630/1250/1600/2000/250050
50/65125
20/25/31.520/25/31.550/63/80
505070
DescripRated voRated freRated ins-Power fr-Lightnin
Rated noShort timPeak witStandardSS Enclos Compa
DimensioWidth
Depth Height
IEC 62271-100 and GB 1984-2003)
O-0.3s-CO-180s-CO
V AC110/220;DC 110/220
IEC 62271-100/200
* Forced cooling ventilation is required ** DC Resistance of current transformer
!"#$��������������� ������� ����
7
DescriptionRated voltageRated frequencyRated insulation level-Power frequency withstand voltage/min-Lightning impulse withstand voltage (peak)
Rated normal current in BusbarShor t time withstand current (4s)Peak withstand currentStandard degree of protection (1) Enclosure Compartment
Dimension Width Depth Height
kVHz
kVkV
AAkA
mmmmmm
33/36/40.550/60
95185
630/1250/1600/2000/2500/315025/31.563/80
1P4X1P2X
120025002400
�!"#$�����
Circuit Breaker Model
Rated voltageRated currentRated frequencyRated insulation level-Power frequency withstand voltage-Lightning impulse withstand voltage
Rated short circuit break ing currentRated shor t circuit withstand currentRated short circuit making current (peak)Electrical endurance
Rat ed operating sequence/duty
Rated closing timeRated opening timeRated breaking time
Rated auxiliary control voltage
kVAHz
kV/ 1 minkV, peak
kA, rmskA/4skA
274 (Class E2 in accordance with
O-0.3s-CO-180s-CO
msmsms
33/36/40.5630/1250/1600/2000/2500/315050/60
95185
25/31.525/31.563/80
55-8025-4060
IEC 62271-100 and GB 1984-2003)
O-0.3s-CO-180s-CO
V AC 110/220;DC 110/220
������������ ���������������
IEC 62271-100/200
Switchgear typeApplicable standardsClasification of switchgearService condition
Rated voltage (kV)Rated current (A)Rated frequency (Hz)Insulation level- 1 min power frequency (kV rms)- 1.2x50 μs impulse (kV peak)Rated short-time withstand current (kA-sec)Degree of protection HV compartmentLV compartmentOperating boxGas pressureRated pressure (MPa)Low pressure alarm stage-1 (MPa)Low pressure alarm stage-2 (MPa)High pressure (MPa)Operation of 3-position isolatorAuxiliary voltageControl circuit (Vdc)Motor circuit (Vac/Vdc)
BGA-36IEC 60298, BS 5227
SF6-insulated metal enclosedAltitude <1000m�������������� ��������������������Relative humidity - 24 Hrs, average <95%-1 month average <90%
361250, 2000
50/60
7017025-3
IP65IP40IP30
0.080.060.050.12
Motorized/manual
110240/110
Switchgear Model HICLAD-30GA
�� ����%"��%&��� '��� ��������� ����
��(�)*� �*��+�
The standard factory-assambled switchgear developed on the basis of a modem design concept and technology with SF6 gas insula-tion.
The HICLAD-30GA is fully type-tested, indoor type, 36 kV metal-clad switchgear, factory asembled under rigorous quality control and tests.
VCB modelApplicable standardsRated voltage (kV)Rated current (A)Rated frequency (Hz)Insulation level- 1 min power frequency (kV rms)- 1.2x50 μs impulse (kV peak) Rated short circuit breaking current (kA)Rated short circuit making current (kA peak)Rated short-time withstand current (kA-sec)Operating duty
Rated closing time (sec)Rated opening time (sec)Rated break time (sec) Rated TRV for terminal faultRate of rise (kV/μs)TRV peak voltage (kV)Type of operating mechanism Tripping systemSpring charging motorAuxiliarry voltage (Vac/Vdc)Output (W)Current (A)Closing coilAuxiliary voltage (Vdc)Current (A)Tripping coilAuxiliary voltage (Vdc)Current (A)
VGA-32IEC 62271-100
361250, 2000
50/60
70170256325
0-0.3sec-CO-3min-CO0-0.3sec-CO-3min-CO
0.050.050.07
0.57 62
Motor charged spring stored energyShunt trip
240/11060
1.5A 230 Vac
1105A
1106A
Vacuum Circuit-Breaker (VCB) It is designed to accomodate high-performance vacuum circuit breaker (VCB) which has been designed, manufactured and tested in accordance with IEC 56 and BS 5311.
The switchgear itself conforms to IEC 60298 and BS 5227, and the all primary components employed therein are in accordance with the relevant IEC and/ or BS Standars. The modern production process has been introduced for the manufacture of main components, primarily in sheet-metal forming and gas-tight tank, the technique of gas tightness and jointing frameworks,surface protection and so on.
SF6 gas insulation used in conjunction with vacuum circuit-breaker (VCB) has set new standard with respect to:
Operational realiability and availability Reduced maintenance work Safety for operators Free from environmental pulution Reduced dimensions and less space requirements Capability of current interuption with zero gas pressure (at atmospheric pres sure) Motorised Busbar Live Transfer Discon nectors are provided for double Busbar switchgears
8
)*� �*��+�
!"#$���,�������,&���(� ��������������
DescriptionRated voltageRated currentRated frequency Rated insulation level- Power frequency withstand voltage/min- Lightning impulse withstand voltage (peak)Rated short circuit breaking currentRated short time withstand current (4s)Rated short circuit making current (peak)Rated peak value withstand current (peak)Rated operating sequence
Rated auxiliary control voltageMechanical endurance
Annual leakage rateSF6 rated pressureSF6 alarm pressure
kVA
Hz
kVkVkAkAkAkA
VNo. oftimes %/YMPaMPa
40.5630/1250/1600/2000/250050/60
9518525/31.525/31.563/8063/80O-0.3s-CO-180s-COO-180s-CO-180s-COAC 110/220;DC 110/220
10000< 0.10.35 ± 0.020.28 ± 0.01
9
Rated voltageRated Insulation Level- 1.2/50 Wave-Form- Power FrequencyRated normal current - Switch- BusbarsRated Breaking Current - Oil switches onlyMaximum Fuse Rating
Fused switches to IEC 420Fault Ratings (Lines and Earth Switches)- ASTA certified to IEC265, BS5463, and complies also with AS1025Additional Proving Tests- Generally in accordance with BS2631-1955,AS1025 and AS2024
254 mm
359 mm
12 kV15.5 kV
Up to 15.5 kV
Up to 110 kVUp to 50 kV RMS
630 A630 A 630 A at 0.7 pf100 A at 6.6 kV80 A at 11 kV150 A at 6.6 kV120 A at 11 kV80 A at 15.5 kV
20 kA21.9 kA RMS3 second rating55.9 kA pk. make
Technical Specification
�'-�'7�8*��(The ROSSS consists of three switch units, whereas the ROKSS is a switch-fuse unit, combined with two switch units. In both units the switch and/ or switch fuses are mounted side by side in common welded steel tanks.
On both units, the tank is fitted with four hinged access covers. The left-hand covers the ROKSS gives access to the fuses while the other covers on both the ROSSS and ROKSS permit contact or cable testing on the circuit switches and switch-fuse where fitted.
In addition to the normal non-extinsible and extensible ROKSS units a direct connected tee-off switch-fuse version is available for mounting directly onto a transformer. The flange lines up with a standard transformer flange.
�'�����9�����9�89���'-�'7�8*��(The ROS is a single switch units whereas the ROK is a single switch fuse unit.
The oil filled welded steel tank is common to both types and is fitted with two hinged access covers. The right-hand cover gives access to the circuit switch for contact inspection or cable testing. On the ROK unit the left hand cover gives access to the three oil immersed fuses.
Technical Specification Rated voltageRated Insulation Level- 1.2/50 Wave-Form- Power FrequencyRated normal current - Switch- BusbarsRated Breaking Current - ROS onlyMaximum Fuse Rating - ROK only
Fused switches to IEC 420Fault Ratings (Lines and Earth Switches)- ASTA certified to IEC265, BS5463, and complies also with AS1025Additional Proving Tests- Generally in accordance with BS2631-1955,AS1025
Up to 15.5 kV
Up to 110 kVUp to 50 kV RMS
630 A630 A 630 A at 0.7 pf100 A at 6.6 kV80 A at 11 kV150 A at 6.6 kV120 A at 11 kV80 A at 15.5 kV
20 kA21.9 kA RMS3 second rating55.9 kA pk. make
254 mm
359 mm
12 kV15.5 kV
10
11
SF� RING MAIN UNIT��������� ����
The Sabre VRN 2a (6a) is compact SF6 insulated Vacuum Ring Main Unit (RMU). The unit can be mounted to the smallest distribution transformer or be sited in a free standing format. Designed to be used both indoors and outdoors, the unit has a long service life and requires virtually zero maintenance.
Design
Bracketed dimensions are alternative lower heightDimensions in millimetres
Under licensed by Lucy Switchgear
12
VRN2a VRN6a
Rated Voltage
Impulse Withstand Voltage (kV Peak)
Normal Current
Ring Switches
Circuit Breaker
Busbar
Short Circuit Peak Making Current
Ring Switches
Tee-off Circuit Breaker
Short Circuit Breaking Current
Tee-off Circuit Breaker
3 Second Short Time Current
Ring Switches
Tee-off Circuit Breaker
Earth Switch Peak Making Current
Ring Switches
Tee-off Circuit Breaker
Internal Arc Rating
Freestanding
Transformer Mounted
Gas Pressure
MOP
IP Rating
Up to IP54W
Dimensions
Height (mm)
Width (mm)
Depth (mm)
Weight (kg)
Weight of SF6 (kg)
Protection
TLF - Time Limit Fuse
Auxiliary Powered Relay
Self Powered Relay
Testing Standards Applicable
IEC 62271-103
IEC 62271-100
IEC 62271-102
IEC 60056
IEC 60265-1
IEC 60129
IEC 60694
IEC 60298
ENA TS 41-36
IEC 62271-200
12kV (15.5kV)
75kV (95kV)
630A
250A
630A
50kA
50kA
20kA RMS
20kA
20kA
50kA
7.9kA
20kA 1 sec
20kA 1 sec in ENA Housing
zero bar (G)
Up to IP54W
1715, 1635 or 1415
950
1080
350
1.46
12kV (15.5kV)
75kV (95kV)
630A
630A
630A
50kA
50kA
20kA RMS
20kA
20kA
50kA
50kA
20kA 1 sec
20kA 1 sec in ENA Housing
zero bar (G)
Up to IP54W
1775, 1690 or 1470
950
1080
360
1.46
Technical Data (rating in brackets are optimal)
Key features- Compact Design
- 12kV and 15.5kV
- Indoor / Outdoor application
- Mimic Diagram
- Vacuum tee off circuit breakers
- Enhanced duty, in excess of IEC requirements
- Pre-wired for motor actuation
- Fault passage indicators
- Common switching chamber
- Full ratings with zero atmospheric pressure
- Isolation in clean SF6 gas
Options
���������All options provide transformer over current protection for phase to phase faults. Earth protection covering phase to earth faults is also available if required.
�� �������Internal arc test cable boxes are available with IEC and ENA specifications.Interlocked cable boxes are also provided as options.
���������The Sabre VRN2a can be pre-wired for automation. Single or double rotary actuators can be easily and rapidly fitted on site whilst the unit is in service - no access is required to the internal workings of the RMU.
Distributor: