![Page 1: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/1.jpg)
V8/2311/PF/CD03
Construction Details
![Page 2: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/2.jpg)
Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland.
T +353 49 4336998 F+353 49 4336823 E [email protected] W kore-system.com
Table of Contents
![Page 3: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/3.jpg)
KORE Insulated Foundation System - Block External Leaf & Slab over Insulation
EPS 300 EPS 300
EPS 300
EPS 100
EPS 100
30-50MM T3 BLINDING ON MINIMUM 200MM T2PERMEABLE ON T1 STRUCTURAL IN ACCORDANCE WITH S.R 21:2014 + A1:2016AND ANNEX E FOR GRANULAR FILL
170MM KORE FILL DIAMONDBONDED BEAD INSULATIONTHERMAL CONDUCTIVITY 0.033W/MK
100MM STANDARDBLOCK OUTER LEAF
WALL TIES TO MANUFACTURERSSPECIFICATIONS AND DETAILS
RADON BARRIER BELOW FIRST LAYER OF INSULATION WITHRADON RESISTING SEALING TAPE TO AVOID RISINGMOISTURE LAPPING UP AND OVER PROFILE MINIMUM OF150MM FROM GROUND LEVEL
100MM STANDARD CONCRETE BLOCKINNER LEAF
15MM INTERNAL SAND CEMENT RENDER(INCLUDES AIRTIGHT PARGE COAT)
CONCRETE FLOOR SLAB TO ENGINEERSSPECIFICATIONS AND DETAILSPLINTH MINIMUM 150MM ABOVE
GROUND LEVEL
UPSTAND REMOVED AFTERCONCRETE HAS CURED
LAND DRAIN AROUND PERIMETER OF BUILDING OUTFALLING TOSTORMWATER SOAKWAY
RADON BARRIER/ DPM
RADON/DPM EXTENDS 1M FROMFACE OF EPS UPSTAND
25
0
1000
STEPPED DPC
FOOTPATH LEVEL
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - Block External leaf and slab over insulation
/ 03/02/2020
CWI_14A
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
²²²
![Page 4: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/4.jpg)
EPS 100
EPS 100
EPS 100
30
01
50
20
0
200 215
EPS 300
NOTE:THICKNESS OF EPS UPSTAND TO SUIT THICKNESS OFEXTERNAL INSULATION.
ADDITIONAL RADON/DPM LAID 1M FROM FACEOF EPS AND RETURNED UP FACE OF THECEMROCK TO FOOTPATH LEVEL.
EXTERNAL INSULATION
215MM MASONRY
RADON BARRIER
30-50MM T3 BLINDING ON MINIMUM 200MM T2PERMEABLE ON T1 STRUCTURAL IN ACCORDANCEWITH S.R 21:2014 + A1:2016 AND ANNEX EFOR GRANULAR FILL
KORE Insulated Foundation System - Solid Wall & External Wall Insulation
LAND DRAIN AROUND PERIMETER OF BUILDINGOUTFALLING TO STORMWATER SOAKWAY
CEM-ROCK EXTREME/CEMENTITIOUS BOARD ONVERTICAL FACE OF EPS300BONDED WITH PU FOAM)
25
0
CONCRETE FLOOR SLAB TO ENGINEERSSPECIFICATIONS AND DETAILS,REINFORCEMENTTO SUIT SPECIFIC LOADING
1000
STEPPED DPC
FOOTPATH LEVEL
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
/ 03/02/2020
EWI_89A
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
KORE Foundation with Solid Wall EWI
²²²
![Page 5: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/5.jpg)
30
01
50
100 125 75
25
0
EPS 100
EPS 100
EPS 100
EPS 300
RADON BARRIER
30-50MM T3 BLINDING ON MINIMUM 200MM T2PERMEABLE ON T1 STRUCTURAL IN ACCORDANCE WITH S.R 21:2014 + A1:2016AND ANNEX E FOR GRANULAR FILL
REINFORCEMENT TO SUITSPECIFIC LOADING
NOTE:THICKNESS OF EPS UPSTAND TO SUIT THICKNESS OFEXTERNAL INSULATION.
NOTE:EPS GRADE, ALL REINFORCEMENT AND GROUNDBUILD-UP DETAILS AND SPECIFICATIONS TO SUIT SPECIFICSITE AND LOADING REQUIREMENTS
ICF WALL
KORE Insulated Foundation System - ICF Wall
LAND DRAIN AROUND PERIMETER OF BUILDINGOUTFALLING TO STORMWATER SOAKWAY
CEM-ROCK EXTREME/CEMENTITIOUS BOARD ONVERTICAL FACE OF EPS300BONDED WITH PU FOAM)
CONCRETE FLOOR SLAB TOENGINEERS SPECIFICATIONSAND DETAILS
1000
STEPPED DPC
FOOTPATH LEVEL
ADDITIONAL RADON/DPM LAID 1M FROM FACEOF EPS AND RETURNED UP FACE OF THECEMROCK TO FOOTPATH LEVEL.
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - ICF Wall
/ 03/02/2020
ICF_07A
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
²²²
![Page 6: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/6.jpg)
EPS 100
EPS 100
EPS 100
EPS 300
EPS 300
RADON BARRIER
WIDTH OF CONCRETE TO SUIT LOADS
INSULATION BETWEENSTUDS
TIMBER FRAME
UPSTAND REMOVED AFTERPOURING RINGBEAM
300MM LONG CUT-OUTS INBOTTOM OF EPS ATSPECIFIED INTERVALS
RINGBEAM FOR OUTERBLOCKWORK
MASONRY OUTER LEAF
30-50MM T3 BLINDING ON MINIMUM 200MM T2PERMEABLE ON T1 STRUCTURAL IN ACCORDANCE WITH S.R 21:2014 + A1:2016AND ANNEX E FOR GRANULAR FILL
KORE Insulated Foundation System - Twin Framed Timber Frame Wall
LAND DRAIN AROUND PERIMETER OF BUILDINGOUTFALLING TO STORMWATER SOAKWAY
25
0
RADON/DPM EXTENDS 1M FROMFACE OF EPS UPSTAND
1000
STEPPED DPC
FOOTPATH LEVEL
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - Twin Framed Timber Wall
/ 03/02/2020
TF_06A
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
²²²
![Page 7: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/7.jpg)
EPS 100
EPS 100
EPS 100EPS 300
EPS 300
EPS 300
UPSTAND REMOVED AFTERPOURING RINGBEAM
300MM LONG CUT-OUTS INBOTTOM OF EPS AT 1.2M C/C
2No. H12 BARS(1T,1B)
140MM TIMBER FRAME
EXTERNAL MASONRY
VENTILATED CAVITY BETWEENTIMBER FRAME ANDEXTERNAL FINISH
REINFORCEMENT TO SUITSPECIFIC LOADING
DPC TO OVERLAP AIRTIGHTMEMBRANE BY 100MM
NOTE:EPS PROFILE/GRADE, REINFORCEMENTAND FILL MATERIAL SPECIFICATION TOSUIT SPECIFIC LOAD/CONDITIONSINVOLVED
RADON BARRIER
30-50MM T3 BLINDING ON MINIMUM 200MM T2PERMEABLE ON T1 STRUCTURAL IN ACCORDANCE WITH S.R 21:2014 + A1:2016AND ANNEX E FOR GRANULAR FILL
LAND DRAIN AROUND PERIMETER OF BUILDINGOUTFALLING TO STORMWATER SOAKWAY
KORE Insulated Foundation System -Timber Frame Wall & Masonry Outer Leaf250
RADON/DPM EXTENDS 1M FROMFACE OF EPS UPSTAND
CONCRETE FLOOR SLAB TOENGINEERS SPECIFICATIONSAND DETAILS
1000
FOOTPATH LEVEL
ANCHORING DETAIL TODESIGNER SPECIFICATION
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - Timber frame wall and Masonry Outer leaf
/ 03/02/2020
TF_10A
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
²²²
![Page 8: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/8.jpg)
CEM-ROCK EXTREME/CEMENTITIOUS BOARD ONVERTICAL FACE OF EPS300BONDED WITH PU FOAM)
MIN 25MM VENTILATIONGAP TO BE MAINTAINED
140MM TIMBER FRAME
EXTERNAL FINISH
REINFORCEMENT TO SUITSPECIFIC LOADING
RADON BARRIER/ DPM
DPC TO OVERLAP AIRTIGHTMEMBRANE BY 100MM
NOTE:ALL REINFORCEMENT AND FILL MATERIAL DEPTHS UNDERFOUNDATION ARE INDICATIVE ONLY, SPECIFIC DETAILSDESIGNED ON A CASE BY CASE BASIS
EPS 100
EPS 100
EPS 100EPS 300
KORE Insulated Foundation System -Timber Frame Wall & Cladding Outer Leaf
30-50MM T3 BLINDING ON MINIMUM 200MM T2PERMEABLE ON T1 STRUCTURAL IN ACCORDANCE WITH S.R 21:2014 + A1:2016AND ANNEX E FOR GRANULAR FILL
LAND DRAIN AROUND PERIMETER OF BUILDINGOUTFALLING TO STORMWATER SOAKWAY
25
0
CONCRETE FLOOR SLAB TOENGINEERS SPECIFICATIONSAND DETAILS
1000
FOOTPATH LEVEL
ADDITIONAL RADON/DPM LAID 1M FROM FACEOF EPS AND RETURNED UP FACE OF THECEMROCK TO FOOTPATH LEVEL.
ANCHORING DETAIL TODESIGNER SPECIFICATION
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - Timber Frame with Cladding Outer Leaf
/ 03/02/2020
TF_46A
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
![Page 9: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/9.jpg)
45
0
EPS 100
EPS 100
25
0
EPS 100
EPS 300
15
01
00
10
01
00
EPS 300
HEAVILY LOADEDINTERNAL WALL
WIDTH OF THICKENINGDESIGNED TO SUIT LOADING
RADON BARRIER
30-50MM T3 BLINDING ONMINIMUM 200MM T2PERMEABLE ON T1 STRUCTURAL IN ACCORDANCE WITH S.R21:2014 + A1:2016 ANDANNEX E FOR GRANULAR FILL
KORE Insulated Foundation System - Internal Loadbearing Wall
EPS 100
EPS 100
EPS 100
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - Internal Loadbearing Wall
/ 03/02/2020
GEN_01A
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
Psi Value based on 650mm of concrete thickening
width and 250mm depth of underlying concrete.
Note : Psi value will vary depending on project design
![Page 10: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/10.jpg)
EPS 100
EPS 100
45
0
25
0
EPS 100
15
01
00
10
01
00
RADON BARRIER
LIGHTLY LOADEDINTERNAL WALL
WIDTH OF THICKENINGDESIGNED TO SUIT LOADING
30-50MM T3 BLINDING ONMINIMUM 200MM T2PERMEABLE ON T1 STRUCTURAL IN ACCORDANCE WITH S.R21:2014 + A1:2016 ANDANNEX E FOR GRANULAR FILL
KORE Insulated Foundation System - Internal Non-Loadbearing Wall
EPS 100
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - Internal Non-Loadbearing Wall
/ 03/02/2020
GEN_02A
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
Psi Value based on 400mm of concrete thickening
width and 250mm depth of underlying concrete.
Note : Psi value will vary depending on project design
![Page 11: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/11.jpg)
KORE Insulated Foundation System - Timber Frame Separating Wall Foundation Detail
EPS 100
EPS 100
EPS 100
EPS 300
15
01
00
10
01
00
EPS 300
RADON BARRIER
SELECTED TIMBER FRAMECONSTRUCTION SYSTEM
DRAINAGE CHANNEL TO BE CAST BETWEENDWELLINGS AS SHOWN IN I.S. 440
30-50mm T3 BLINDING ONMINIMUM 200mm T2PERMEABLE ON T1 STRUCTURALIN ACCORDANCE WITH S.R.21:2014 + A1:2016 AND ANNEXE FOR GRANULAR FILL
WIDTH OF THICKENING DESIGNED BY SUITABLE
STRUCTURAL ENGINEER TO SUIT LOADINGS
REINFORCING STEEL TO STRUCTURALENGINEER'S DETAIL
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - Timber Frame Separating wall
/ 03/02/2020
SD 001A
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
Psi Value based on 800mm of concrete thickening
width and 250mm depth of underlying concrete.
Note : Psi value will vary depending on project design
![Page 12: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/12.jpg)
WIDTH OF THICKENING DESIGNED BY SUITABLE
STRUCTURAL ENGINEER TO SUIT LOADINGS
KORE Insulated Foundation System - Light Gauge Steel Frame Separating Wall Foundation Detail
EPS 100
EPS 100
EPS 100
EPS 300
15
01
00
10
01
00
EPS 300
RADON BARRIER
SELECTED LIGHT GAUGE STEEL FRAMECONSTRUCTION SYSTEM FIXED TOSTRUCTURAL ENGINEER'S DETAIL
REINFORCING STEEL TO STRUCTURALENGINEER'S DETAIL
30-50mm T3 BLINDING ONMINIMUM 200mm T2PERMEABLE ON T1 STRUCTURALIN ACCORDANCE WITH S.R.21:2014 + A1:2016 AND ANNEXE FOR GRANULAR FILL
DRAINAGE CHANNEL TO BE CAST BETWEENDWELLINGS AS SHOWN IN I.S. 440
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - LGS Separating Party Wall
EF01/05/2019
SD 002E
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
![Page 13: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/13.jpg)
WIDTH OF THICKENING DESIGNED BY SUITABLE
STRUCTURAL ENGINEER TO SUIT LOADINGS
KORE Insulated Foundation System - Solid Concrete Block Separating Wall Foundation Detail
EPS 100
EPS 100
EPS 100
EPS 300
15
01
00
10
01
00
EPS 300
RADON BARRIER
SELECTED CONCRETE BLOCK WALL TOSTRUCTURAL ENGINEER'S DETAIL(ACOUSTIC REQUIREMENTS BY OTHERS)
REINFORCING STEEL TOSTRUCTURAL ENGINEER'S DETAIL
DPC
30-50mm T3 BLINDING ONMINIMUM 200mm T2PERMEABLE ON T1 STRUCTURALIN ACCORDANCE WITH S.R.21:2014 + A1:2016 AND ANNEXE FOR GRANULAR FILL
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation -Masonry Separating Wall
/ 03/02/2020
SD 003A
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
Psi Value based on 800mm width of
underlying concrete thickening.
Note :Width of thickening and Psi value will
vary depending on project design
![Page 14: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/14.jpg)
WIDTH OF THICKENING DESIGNED BY SUITABLE
STRUCTURAL ENGINEER TO SUIT LOADINGS
KORE Insulated Foundation System - Cavity Block Wall Separating Wall Foundation Detail
EPS 100
EPS 100
EPS 100
EPS 300
15
01
00
10
01
00
EPS 300
RADON BARRIER
SELECTED CONCRETE BLOCK CAVITYWALL TO STRUCTURAL ENGINEER'S DETAIL
REINFORCING STEEL TO STRUCTURALENGINEER'S DETAIL
DPC
30-50mm T3 BLINDING ONMINIMUM 200mm T2PERMEABLE ON T1 STRUCTURALIN ACCORDANCE WITH S.R.21:2014 + A1:2016 AND ANNEXE FOR GRANULAR FILL
DRAINAGE CHANNEL TO BE CAST BETWEENDWELLINGS AS REQUIRED
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - Concrete Block Separating Party Wall
EF01/05/2019
SD 004E
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
![Page 15: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/15.jpg)
EPS 300
EPS 300
EPS 100
EPS 100
EPS 100
SELECTED FULLHEIGHT WINDOW
UPSTAND REMOVED AFTERCONCRETE HAS CURED
EPS 300
10
01
00
10
01
50
WIDTH OF THICKENING DESIGNED BY
SUITABLE STRUCTURAL ENGINEER
TO SUIT LOADINGS
KORE Insulated Foundation System - Full Height Glazing Detail
REINFORCING STEEL TOSTRUCTURAL ENGINEER'S DETAIL
RADON TO EXTEND 1m BEYONDEDGE OF FOUNDATION
300mm LONG CUT-OUTS IN BOTTOM OF EPS(SPACING OF CUT OUTS WILL DEPEND ON
STRUCTURAL ENGINEERS DESIGN AND DRAWINGS)
REINFORCING STEEL TOSTRUCTURAL ENGINEER'S DETAIL
BLOCK POSITIONED AS ITWOULD BE IN TIMBER
FRAME CONSTRUCTION
15
0
LAND DRAIN AROUNDPERIMETER OF BUILDING
OUTFALLING TO STORMWATERSOAKAWAY (NOT TO BE
DISCHARGED TO COUNCILSURFACE WATER OR MAIN
SEWER SYSTEM)
2No. 65mm HIGHSOAP BLOCKS
30-50mm T3 BLINDING ONMINIMUM 200mm T2PERMEABLE ON T1 STRUCTURALIN ACCORDANCE WITH S.R.21:2014 + A1:2016 AND ANNEXE FOR GRANULAR FILL
RADON BARRIER
The support for the door orfull height glazing threshold need to bechecked subject to the final door orglazing weight and setting out.
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - Full Height Glazing on Foundation System
AON 01/05/2019
SD 005E
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
![Page 16: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/16.jpg)
EPS 300 EPS 300
EPS 300
EPS 100
EPS 100
EPS 100
WALL CHASED TO ALLOW ESBDUCTWORK TO ROUTE TO ESB
METER BOX
SELECTED TIMBER FRAMECONSTRUCTION SYSTEM
UPSTAND REMOVED AFTERCONCRETE HAS CURED
10
01
00
10
01
50
WIDTH OF THICKENING DESIGNED BY
SUITABLE STRUCTURAL ENGINEER
TO SUIT LOADINGS
KORE Insulated Foundation System - ESB Duct Penetration of Foundation System
REINFORCING STEEL TOSTRUCTURAL ENGINEER'S DETAIL
RADON BARRIER TO BE PENETRATED WITH ESBDUCT. RADON BARRIER TO BE SEAL TO DUCT IN
ACCORDANCE WITH RADON BARRIERMANUFACTURERS INSTRUCTIONS
BLOCK ON EDGE WITHCEMENT RENDER FINISH
ESB DUCT THROUGHFOUNDATION SYSTEM
RADON TO EXTEND 1m BEYONDEDGE OF FOUNDATION
LAND DRAIN AROUNDPERIMETER OF BUILDING
OUTFALLING TO STORMWATERSOAKAWAY (NOT TO BE
DISCHARGED TO COUNCILSURFACE WATER OR MAIN
SEWER SYSTEM)
30-50mm T3 BLINDING ONMINIMUM 200mm T2PERMEABLE ON T1STRUCTURAL INACCORDANCE WITH S.R.21:2014 + A1:2016 ANDANNEX E FOR GRANULAR FILL
300mm LONG CUT-OUTS IN BOTTOM OF EPS(SPACING OF CUT OUTS WILL DEPEND ON
STRUCTURAL ENGINEERS DESIGN AND DRAWINGS)
NOTE:CARE TO BE TAKEN WHENCUTTING/TRIMMING EPSINSULATION TO FORM SERVICEPENETRATIONS TO ENSUREMINIMIZATION OF GAPS. PLEASEUSE SUITABLE TOOLS
RADON BARRIER
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - ESB DUCT PENETRATION
AON 01/05/2019
SD 006E
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
![Page 17: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/17.jpg)
EPS 300 EPS 300
EPS 300
EPS 100
EPS 100
EPS 100
BLOCK ON EDGE WITH
CEMENT RENDER FINISH
SELECTED TIMBER FRAMECONSTRUCTION SYSTEM
UPSTAND REMOVED AFTERCONCRETE HAS CURED
10
01
00
10
01
50
WIDTH OF THICKENING DESIGNED BY
SUITABLE STRUCTURAL ENGINEER
TO SUIT LOADINGS
KORE Insulated Foundation System - Service Penetration to Floor Slab
REINFORCING STEELTO STRUCTURALENGINEER'S DETAIL
REINFORCING STEEL TOSTRUCTURAL ENGINEER'S DETAIL
SERVICE CONDUIT TO
DWELLING HOUSE (e.g.
KITCHEN ISLAND)
UPSTAND REMOVED AFTERCONCRETE HAS CURED
RADON BARRIER TO BE PENETRATED WITHSERVICE DUCT. RADON BARRIER TO BE SEALEDTO DUCT IN ACCORDANCE WITH RADONBARRIER MANUFACTURERS INSTRUCTIONS
SERVICE DUCTTHROUGH
FOUNDATIONSYSTEM
SERVICE PIPE SLEEVEDTHROUGH CONCRETE SLAB
RADON TO EXTEND 1m BEYONDEDGE OF FOUNDATION
LAND DRAIN AROUND PERIMETEROF BUILDING OUTFALLING TO
STORMWATER SOAKAWAY (NOTTO BE DISCHARGED TO COUNCIL
SURFACE WATER OR MAINSEWER SYSTEM)
30-50mm T3 BLINDING ONMINIMUM 200mm T2PERMEABLE ON T1STRUCTURAL INACCORDANCE WITH S.R.21:2014 + A1:2016 ANDANNEX E FOR GRANULAR FILL
300mm LONG CUT-OUTS IN BOTTOM OF EPS(SPACING OF CUT OUTS WILL DEPEND ON
STRUCTURAL ENGINEERS DESIGN AND DRAWINGS)
NOTE:CARE MUST BE TAKEN WHENCUTTING/TRIMMING EPSINSULATION TO FORM SERVICEPENETRATIONS TO ENSUREMINIMISATION OF GAPS. PLEASEUSE SUITABLE TOOLS
RADON BARRIER
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - Service Penetration to Floor Slab
AON 01/05/2019
SD 007E
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
![Page 18: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/18.jpg)
EPS 300 EPS 300
EPS 300
EPS 100
EPS 100
EPS 100
BLOCK ON EDGE WITH
CEMENT RENDER FINISH
SELECTED TIMBER FRAMECONSTRUCTION SYSTEM
UPSTAND REMOVED AFTERCONCRETE HAS CURED
10
01
00
10
01
50
KORE Insulated Foundation System - Waste Pipe Detail
REINFORCING STEEL TOSTRUCTURAL ENGINEER'S DETAIL
REINFORCING STEEL TOSTRUCTURAL ENGINEER'S DETAIL
RADON TO EXTEND 1m BEYONDEDGE OF FOUNDATION
WASTE PIPETHROUGH
FOUNDATIONSYSTEM
WASTE PIPE TO DWELLING
HOUSE (e.g. Toilet Waste)
RADON BARRIER TO BE PENETRATED WITHSERVICE DUCT. RADON BARRIER TO BE SEALEDTO DUCT IN ACCORDANCE WITH RADONBARRIER MANUFACTURERS INSTRUCTIONS
SERVICE PIPE SLEEVEDTHROUGH CONCRETE SLAB
LAND DRAIN AROUND PERIMETEROF BUILDING OUTFALLING TO
STORMWATER SOAKAWAY (NOTTO BE DISCHARGED TO COUNCIL
SURFACE WATER OR MAINSEWER SYSTEM)
30-50mm T3 BLINDING ONMINIMUM 200mm T2PERMEABLE ON T1STRUCTURAL INACCORDANCE WITH S.R.21:2014 + A1:2016 ANDANNEX E FOR GRANULAR FILL
300mm LONG CUT-OUTS IN BOTTOM OF EPS(SPACING OF CUT OUTS WILL DEPEND ON
STRUCTURAL ENGINEERS DESIGN AND DRAWINGS)
WIDTH OF THICKENING DESIGNED BY
SUITABLE STRUCTURAL ENGINEER
TO SUIT LOADINGS
NOTE:CARE MUST BE TAKEN WHENCUTTING/TRIMMING EPSINSULATION TO FORM SERVICEPENETRATIONS TO ENSUREMINIMISATION OF GAPS. PLEASEUSE SUITABLE TOOLS
RADON BARRIER
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - Waste Pipe Through Foundation System
AON 01/05/2019
SD 008E
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
![Page 19: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/19.jpg)
EPS 300 EPS 300
EPS 300
EPS 100
EPS 100
EPS 100
BLOCK ON EDGE WITH
CEMENT RENDER FINISH
SELECTED TIMBER FRAMECONSTRUCTION SYSTEM
UPSTAND REMOVED AFTERCONCRETE HAS CURED
10
01
00
10
01
50
REINFORCING STEEL TOSTRUCTURAL ENGINEER'S DETAIL
RADON TO EXTEND 1m BEYONDEDGE OF FOUNDATION
REINFORCING STEEL TOSTRUCTURAL ENGINEER'S DETAIL
KORE Insulated Foundation System - Oil Pipe Service Penetration (Internal Oil Boiler)
LAND DRAIN AROUND PERIMETEROF BUILDING OUTFALLING TO
STORMWATER SOAKAWAY (NOTTO BE DISCHARGED TO COUNCIL
SURFACE WATER OR MAINSEWER SYSTEM)
30-50mm T3 BLINDING ONMINIMUM 200mm T2PERMEABLE ON T1STRUCTURAL INACCORDANCE WITH S.R.21:2014 + A1:2016 ANDANNEX E FOR GRANULAR FILL
300mm LONG CUT-OUTS IN BOTTOM OF EPS(SPACING OF CUT OUTS WILL DEPEND ON
STRUCTURAL ENGINEERS DESIGN AND DRAWINGS)
20
0
UNDERGROUND
PLASTIC COATED
COPPER OIL FEED
PIPE (MINIMUM
200mm BELOW
LOWEST POINT IN
EPS)
30mm COMPACTED
SAND SURROUNDING
OIL FEED PIPE
SLEEVE PIPE ENCASING
OIL FEED PIPE TO
CONTAIN ANY LEAKS
SLEEVE PIPE ENCASING OIL FEED
PIPE TO CONTAIN ANY LEAKS
UNDERGROUND PLASTIC COATED
COPPER OIL FEED PIPE (MINIMUM
200mm BELOW LOWEST POINT IN EPS)
NOTE:CARE MUST BE TAKEN WHENCUTTING/TRIMMING EPSINSULATION TO FORM SERVICEPENETRATIONS TO ENSUREMINIMISATION OF GAPS. PLEASEUSE SUITABLE TOOLS
RADON BARRIER
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - Oil Pipe Service Penetration
AON 01/05/2019
SD 009E
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
![Page 20: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/20.jpg)
NOTE:
METER BOX DETAILING
TO BE AGREED WITH
GAS SERVICE SUPPLIER
PRIOR TO PANEL
MANUFACTURE
EPS 300 EPS 300
EPS 300
EPS 100
EPS 100
EPS 100
GAS METER BOX
BOARDING TO TIMBER FRAMEMANUFACTURERS SPECIFICATIONS
10
01
00
10
01
50
REINFORCING STEEL TOSTRUCTURAL ENGINEER'S DETAIL
GAS SERVICE PIPE FROMPROVIDER
GAS INLET TO HOUSE
UPSTAND REMOVED AFTERCONCRETE HAS CURED
KORE Insulated Foundation System - GAS Pipe Penetration Through Foundation System
RADON TO EXTEND 1m BEYONDEDGE OF FOUNDATION
GAS PIPE THROUGHFOUNDATION SYSTEM TO
BE SLEEVED
GAS PIPE PROTECTED FROM CORROSION WITHPVC COATING OR WRAP AT 25MM MIN DEPTH
SELECTED TIMBER FRAMECONSTRUCTION SYSTEM
CAVITY CLOSERS TO TIMBER FRAMEMANUFACTURERS SPECIFICATIONS
DETAILING TO TO TIMBER FRAMEMANUFACTURERS SPECIFICATIONS
IN ACCORDANCE WITH I.S. 440
PIPE PENETRATION DETAILS TORADON INSTALLERS DETAILS
20
0
LAND DRAIN AROUND PERIMETEROF BUILDING OUTFALLING TO
STORMWATER SOAKAWAY (NOTTO BE DISCHARGED TO COUNCIL
SURFACE WATER OR MAINSEWER SYSTEM)
30-50mm T3 BLINDING ONMINIMUM 200mm T2PERMEABLE ON T1STRUCTURAL INACCORDANCE WITH S.R.21:2014 + A1:2016 ANDANNEX E FOR GRANULAR FILL
300mm LONG CUT-OUTS IN BOTTOM OF EPS(SPACING OF CUT OUTS WILL DEPEND ON
STRUCTURAL ENGINEERS DESIGN AND DRAWINGS)
WIDTH OF THICKENING DESIGNED BY
SUITABLE STRUCTURAL ENGINEER
TO SUIT LOADINGS
NOTE:CARE MUST BE TAKEN WHENCUTTING/TRIMMING EPSINSULATION TO FORM SERVICEPENETRATIONS TO ENSUREMINIMISATION OF GAPS. PLEASEUSE SUITABLE TOOLS
RADON BARRIER TO BE PENETRATED WITH GASPIPE. RADON BARRIER TO BE SEAL TO DUCT IN
ACCORDANCE WITH RADON BARRIERMANUFACTURERS INSTRUCTIONS
RADON BARRIER
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - GAS Pipe Penetration of Foundation
AON 01/05/2019
SD 010E
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
![Page 21: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/21.jpg)
EPS 300
EPS 300
EPS 100
EPS 100
EPS 100
CORNER POST WITH RECESSEDBASE PLATE (IF REQUIRED)
RADON BARRIER
10
01
00
10
01
50
WIDTH OF THICKENING DESIGNED BY
SUITABLE STRUCTURAL ENGINEER
TO SUIT LOADINGS
KORE Insulated Foundation System - Corner Post with Recessed Base Plate (If Required)
REINFORCING STEEL TOSTRUCTURAL ENGINEER'S DETAILREINFORCING STEEL TO
STRUCTURAL ENGINEER'S DETAIL
UPSTAND REMOVED AFTERCONCRETE HAS CURED
RADON TO EXTEND 1m BEYONDEDGE OF FOUNDATION
LAND DRAIN AROUND PERIMETEROF BUILDING OUTFALLING TO
STORMWATER SOAKAWAY (NOTTO BE DISCHARGED TO COUNCIL
SURFACE WATER OR MAINSEWER SYSTEM)
300mm LONG CUT-OUTS IN BOTTOM OF EPS(SPACING OF CUT OUTS WILL DEPEND ON
STRUCTURAL ENGINEERS DESIGN AND DRAWINGS) 15
0
BLOCK POSITIONED AS ITWOULD BE IN TIMBER
FRAME CONSTRUCTION
2No. 65mm HIGHSOAP BLOCKS
COMPACFOAM REQUIRED BELOW HIGHPOINT LOADS AS PER STRUCTURALENGINEERS DESIGN AND DRAWINGS
REINFORCED PAD FOUNDATION TOSTRUCTURAL DESIGN AND DRAWINGS
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation - Corner Post Detail
AON 01/05/2019
SD 011E
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
![Page 22: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/22.jpg)
EPS 100
EPS 100
EPS 100EPS 300
EPS 300
EPS 300
300MM LONG CUT-OUTS INBOTTOM OF EPS AT 1.2M C/C
2No. H12 BARS(1T,1B)
LINEAR DRAIN
WINDOW/DOOR
REINFORCEMENT TO SUITSPECIFIC LOADING
DPC TO OVERLAP AIRTIGHTMEMBRANE BY 100MM
NOTE:EPS PROFILE/GRADE, REINFORCEMENTAND FILL MATERIAL SPECIFICATION TOSUIT SPECIFIC LOAD/CONDITIONSINVOLVED
RADON BARRIER
30-50MM T3 BLINDING ON MINIMUM 200MM T2PERMEABLE ON T1 STRUCTURAL IN ACCORDANCE WITH S.R 21:2014 + A1:2016AND ANNEX E FOR GRANULAR FILL
LAND DRAIN AROUND PERIMETER OF BUILDINGOUTFALLING TO STORMWATER SOAKWAY
KORE Insulated Foundation System - Threshold Detail
25
0
RADON/DPM EXTENDS 1M FROMFACE OF EPS UPSTAND
CONCRETE FLOOR SLAB TOENGINEERS SPECIFICATIONSAND DETAILS
1000
RAMP
CONCRETE TO SUPPORTWINDOW/DOOR
Drawn by Airpacks Ltd. t/a KORE
Disclaimer:
KORE Foundation -Threshold Detail
/ 03/02/2020
SD 014A
INSULATION AND ENERGY SAVING SOLUTIONS
Rev:
Date:
Title:
Drawing Nº.:
Drawn:
Project :
Checked: /
The information in this document is to the best of our knowledge, true and accurate.
However and recommendations or suggestions contained within are without
guarantee and as the conditions of use are beyond our control. Recommendations
for use should be verified for suitability and compliance with actual requirements
specifications and any applicabel laws and regulations. KORE technical literature
and our Agrement certificates are all available for download from our website
www.kore-system.com. Airpacks Ltd t/a KORE reserves the right to amend product
specifications without prior notice. Please check that the copy of this literature is
current by contacting the KORE marketing department.
www.kore-system.com
Kilnaleck, Co. Cavan, Ireland Phone: +353 49 4374000 Fax: +353 49 4336823
KORE Standard Details
1 : 10 @ A4Scale:
![Page 23: Construction Details · 2020. 8. 10. · V8/2311/PF/CD03 Construction Details . Airpacks Ltd, KORE System, Kilnaleck, Co. Cavan, Ireland. T +353 49 4336998 F+353 49 4336823 E info@kore-icf.com](https://reader035.fdocuments.net/reader035/viewer/2022071003/5fbfe4cea423c2442444246b/html5/thumbnails/23.jpg)