Compatibility Report Comtrol IO-Link Master SICK WTT2SLC-2P3292A00 Photoelectric Sensor

Transcript of Comtrol IO-Link Master & Sick WTT2SLC-2P3292A00The sensor was tested using the IO-Link Master...

  • Compatibility Report

    Comtrol IO-Link Master

    SICK

    WTT2SLC-2P3292A00 Photoelectric Sensor

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 2

    Contents

    Contents .................................................................................................................................................................................. 2

    Test Report Overview ............................................................................................................................................................. 3

    IO-Link Master - IO-Link Diagnostics Page ............................................................................................................................. 4

    Configuring IO-Link Settings ................................................................................................................................................... 5

    After Configuring Port-Friendly Names and Implementing Automatic Data Storage Upload ................................................. 7

    Setting Up Passwords ............................................................................................................................................................. 8

    WTT2SLC-2P3292A00 Configuration ..................................................................................................................................... 9

    Locating the IODD Files ...................................................................................................................................................... 9

    Loading IODD Files ........................................................................................................................................................... 10

    Verifying that the Correct IODD Files Are Loaded ............................................................................................................ 13

    Changing Parameters on the WTT2SLC-2P3292A00 with the GUI ..................................................................................... 14

    Changing Parameters Using the ISDU Interface............................................................................................................... 17

    Using the Automatic Data Storage Feature .......................................................................................................................... 20

    Clearing Data Storage ........................................................................................................................................................... 27

    Using the Manual Data Storage UPLOAD Feature............................................................................................................... 29

    Resetting the Sensor to Factory Defaults ............................................................................................................................. 31

    Using the Manual Data Storage DOWNLOAD Feature ........................................................................................................ 34

    Using the Device Validation Feature ..................................................................................................................................... 36

    Incompatible Device Attached to Port ............................................................................................................................... 36

    Comtrol IO-Link Master and EtherNet/IP (EIP) ..................................................................................................................... 39

    Comtrol IO-Link Master EDS Files .................................................................................................................................... 42

    Comtrol IO-Link Master AOI Files ..................................................................................................................................... 42

    Comtrol IO-Link Master Program Examples ...................................................................................................................... 42

    Comtrol IO-Link Master and the SLC/PLC-5/MicroLogix Interface ................................................................................... 43

    Comtrol IO-Link Master and Modbus/TCP ............................................................................................................................ 44

    Comtrol IO-Link Master and PROFINET IO .......................................................................................................................... 46

    Comtrol IO-Link Master and OPC UA ................................................................................................................................... 48

    Comtrol IO-Link Master Web Interface Features .................................................................................................................. 49

    Network Settings Page ...................................................................................................................................................... 49

    Miscellaneous Settings Page ............................................................................................................................................ 50

    Load/Save Settings (Cloning the Configuration) ............................................................................................................... 51

    Clear Settings Page (Resetting IO-Link Master Default Settings) ..................................................................................... 52

    Log Files ............................................................................................................................................................................ 52

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 3

    Test Report Overview

    The SICK WTT2SLC-2P3292A00 photoelectric sensor operates properly with the Comtrol IO-Link Master. This report contains the following topics:

    • IO-Link Master – IO-Link Diagnostics page

    • Configuring IO-Link settings

    • Setting up passwords

    • Configuring the sensor with the IODD file

    • Changing sensor parameters with the ISDU Interface

    • Resetting the sensor back to factory defaults

    • Using the Data Storage feature (automatic and manual)

    • Using the Device Validation feature

    The sensor was tested using the IO-Link Master DR-8-EIP (DIN rail IP20 model) with the illustrated image and application versions. The IO-Link Master firmware is field upgradable.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 4

    This report does not illustrate all Comtrol IO-Link Master features, such as: EtherNet/IP and Modbus/TCP configuration, uploading the latest software, or network configuration.

    IO-Link Master - IO-Link Diagnostics Page

    Upon connection to the IO-Link Master, the WTT2SLC-2P3292A00 immediately displays in the IO-Link Diagnostics page without any configuration.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 5

    Configuring IO-Link Settings

    There is no configuration required to getting the IO-Link device operating. It is not even necessary to configure the Minimum Cycle Time, as the IO-Link Master negotiates the required Cycle Time with each IO-Link device. If you are attaching a digital IO device, you must select the appropriate Port Mode (Digital-In or Digital-Out).

    This example shows configuring friendly port names and implementing Automatic Data Storage. The Device Validation and Manual Data Storage features are discussed later in the report.

    Automatic upload occurs when the Automatic Upload Enable option is set to On and one of these conditions exists:

    • There is no upload data stored on the gateway and the IO-Link device is connected to the port.

    • The IO-Link device has the DS upload bit on; generally because you have changed the configuration through Teach buttons or the IO-Link Master web interface.

    The report illustrates how data is uploaded to the IO-Link Master when the IO-Link device is connected. After using the web interface to change parameters; you can reset the IO-Link device to factory defaults and then download the data storage back to the device.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 6

    You can refresh the IO-Link Master to view that Automatic Data Storage was implemented or view the IO-Link Diagnostics page as is illustrated in the next subsection.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 7

    After Configuring Port-Friendly Names and Implementing Automatic Data Storage Upload

    The IO-Link Diagnostics page now displays friendly the Port Name and shows that Automatic Upload data storage has been implemented.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 8

    Setting Up Passwords

    The IO-Link Master ships from the factory without passwords and administrative permissions are granted. You can use the Advanced | Accounts page to set up passwords for the IO-Link Master. Admin, Operator, and User permissions are defined in the help system on the Accounts page.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 9

    WTT2SLC-2P3292A00 Configuration

    You can use the Comtrol IO-Link Master to configure the IO-Link device. When an IODD file is loaded on the IO-Link Master, you can use the GUI on the top of the IO-Link Device – Port page to change parameter settings. If an IODD file is not loaded, you can use the ISDU Interface on the bottom of the IO-Link Device – Port page

    This section discusses the following topics:

    • Locating and loading IODD files

    • Verifying that the correct IODD file is loaded

    • Changing IO-Link device parameters using the GUI and ISDU interface

    Locating the IODD Files

    You can easily locate the IODD files using the Sick web site.

    1. Go to sick.com, enter wtt2slc-2p3292a00 in the search box and click the link.

    http://www.sick.com/

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 10

    2. Click the Download button and then may need to accept the EULA before saving the zip file.

    Loading IODD Files

    IODD file packages must be unzipped and the appropriate files located and re-zipped or loaded individually.

    1. Click Attached Devices | IODD Files.

    2. Click the UPLOAD FILE button.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 11

    3. Click the CHOOSE FILE button.

    4. Select the file set (zip) or xml file to upload and click the UPLOAD button. If there are files in the IODD file set that are not required by the associated xml file, the IO-Link Master does not load the files, and displays an Ignored Files message, click Ok.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 12

    5. The IODD Files page now displays the IODD file loaded on the IO-Link Master.

    6. If you want to view the xml file, click the corresponding IODD FILENAME in the table.

    7. Optionally, click the hyperlink to view the xml file in your browser.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 13

    Verifying that the Correct IODD Files Are Loaded

    Use the IO-Link Device Configuration Summary page to verify that the correct IODD files for the attached IO-Link devices have been loaded on the IO-Link Master. The correct file is loaded if an xml file name displays in the IODD Name field.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 14

    Changing Parameters on the WTT2SLC-2P3292A00 with the GUI

    1. The WTT2SLC-2P3292A00 displays as expected in the PORT page.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 15

    2. Click the EDIT button to make parameter changes. In this example, these parameters were changed:

    • Index 1087 = 150 (default = 1)

    • Index 1088 = 200 (default = 1)

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 16

    3. Click the SAVE button to observe that the settings were changed.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 17

    Changing Parameters Using the ISDU Interface

    This shows using the IO-Link ISDU Interface to change configuration parameters.

    Please note:

    • You must enter the decimal value for the ISDU Block Index and ISDU Sub-index.

    • You must enter the hexadecimal value in the interface.

    • The following screenshots do not illustrate the system responses. The IO-Link Master responds with a command executed notification.

    The following shows how to use the IO-Link ISDU Interface to change IO-Link device configuration parameters.

    1. Expand the IO-Link Device ISDU Interface at the bottom of the page.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 18

    The following images do not display the complete web page.

    2. Verify that the sensor responds to queries.

    a. Enter the ISDU Block Index.

    b. Click GET.

    3. Change Index 1087 to 152 (00 98) and click SET.

    4. To verify the parameter change, click the REFRESH button.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 19

    5. You can review the process data by selecting Process Data in the drop list next to Port 1.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 20

    Using the Automatic Data Storage Feature

    The following examples illustrate how use the Automatic Data Storage feature. The PHOTOELECTRIC SENSOR was configured in the Configuring IO-Link Settings discussion.

    In this section, we will first disable Automatic Upload Data Storage, reset the sensor back to factory defaults, and then use the Automatic Download Data Storage feature to restore the previously configured parameters.

    This example automatically uploads data storage using the previous values.

    1. Access the Configuration | IO-Link Settings page.

    2. Click the EDIT button on the corresponding port.

    3. Click Automatic Upload Enable to Off.

    4. Click SAVE.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 21

    5. In this step, we will reset the sensor back to the factory default settings using the GUI.

    a. Click Attached Devices | Port 1.

    b. Click the Command button.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 22

    c. Click the Restore Factory button.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 23

    d. Click the Ok button to refresh the page so that you can verify the changes.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 24

    e. Notice that the parameters have returned to their factory default settings.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 25

    6. Click Configuration | IO-Link Settings.

    a. Click the EDIT button.

    b. Set Automatic Download Enable to On.

    c. Click SAVE.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 26

    7. You can return to the Port page and verify that the parameters have been uploaded. Note the yellow highlighted parameters were downloaded.

    Parameter changes that are determined by the IODD file and made in the GUI are automatically uploaded to the IO-Link Master but parameter changes made using the ISDU Interface are only uploaded if you use Index 2 to trigger an upload.

    This example did not use Index 2 to trigger the upload to 152. This was the value set using the GUI, not the ISDU interface.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 27

    Clearing Data Storage

    This is how you can clear the data storage on an IO-Link Master port.

    1. Click the Configuration | IO-Link Settings.

    2. Click the EDIT button.

    3. In this example, we also need to change Automatic Download Enable to Off.

    4. Click the Clear button.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 28

    5. Click the Continue button.

    6. Click the Ok button to the Done message.

    7. Click SAVE.

    8. Notice that the Storage Contents is now empty.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 29

    Using the Manual Data Storage UPLOAD Feature

    The section shows how manual data storage works. The sensor contains the previously configured settings.

    1. If necessary, click Configuration | IO-Link Settings.

    2. Click the EDIT button.

    3. Click the UPLOAD button.

    4. Click the CONTINUE button.

    5. Click the OK button to the Done message.

    6. Click the SAVE button.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 30

    7. Notice that there is now Storage Contents.

    8. The next step is to return the sensor to the factory default settings.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 31

    Resetting the Sensor to Factory Defaults

    The sensor can be returned to the factory defaults.

    1. Click Attached Devices | Port 1 (in this example).

    2. Click the Command button.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 32

    3. Click the Restore Factory button.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 33

    4. Click the Ok button to refresh the table and then you can verify that the parameters returned to their factory default values.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 34

    Using the Manual Data Storage DOWNLOAD Feature

    This section shows how the manual download data storage feature works.

    1. Click Configuration | IO-Link and then click the EDIT button.

    2. Click the DOWNLOAD button.

    3. Click the CONTINUE button.

    4. Click the Ok button when the Done message appears and then click the CANCEL or SAVE button.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 35

    5. Click Attached Devices | Port 1 to verify that the parameters were downloaded on the sensor.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 36

    Using the Device Validation Feature

    The WTT2SLC-2P3292A00 supports Compatible Device Validation.

    This report does not illustrate Identical Device Validation because there was only one sensor available and two sensors are required to illustrate Identical Device Validation.

    Incompatible Device Attached to Port

    1. In the IO-Link Configuration page, click EDIT, set Device Validation mode to Compatible.

    2. Click the GET ATTACHED button.

    3. Click SAVE.

    4. Remove the WTT2SLC-2P3292A00 and connect another IO-Link device (not a WTT2SLC-2P3292A00).

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 37

    5. The IO-Link LED on the IO-Link Master is now flashing red to indicate that an incompatible device is connected to the port. In addition, the IO-Link Diagnostics page displays that an incompatible device is attached to the port.

    Last Events towards the bottom of the Diagnostics page also indicates that the wrong sensor is attached.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 38

    6. Re-attach the WTT2SLC-2P3292A00 and notice that it immediately begins operating.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 39

    Comtrol IO-Link Master and EtherNet/IP (EIP)

    This section provides a brief overview about EtherNet/IP interface and configuration on the Comtrol EIP IO-Link series. In addition, it discusses the EDS and AOI files.

    These interfaces provide the ability to retrieve port and device status information, input and output process data and access to IO-Link device ISDU (SPDU) data blocks. Indexed Service Data Unit (ISDU) is sometimes referred to as Service Protocol Data Unit (SPDU).

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 40

    The EtherNet/IP Settings page provides many configuration options. This illustrates a partial screen shot, you must scroll through the table to view all of the available settings.

    Please note that you may need to set the appropriate PDI Data Block Size (To PLC) for each port for EtherNet/IP communciations.

    For detailed information about the EIP interface, functionality descriptions, and CIP object definitions, refer to the IO-Link Master EtherNet/IP and Modbus/TCP Library.

    http://downloads.comtrol.com/IO_Link_Master/4_EIP/Docs/IOLM_EIP_Library.pdfhttp://downloads.comtrol.com/IO_Link_Master/4_EIP/Docs/IOLM_EIP_Library.pdf

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 41

    The Comtrol IO-Link Master also provides in depth diagnostic information.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 42

    Comtrol IO-Link Master EDS Files

    You can easily add the IOLM and its associated Electronic Data Sheet (EDS) files to Rockwell software.

    You can download the EDS files from: http://downloads.comtrol.com/html/IOLM_EIP_eds_files.htm. In addition, this download page provides information on the following topics:

    • Configuring RSLinx

    • Adding EDS Files to Rockwell software

    In addition, you can refer to the IO-Link Master EtherNet/IP and Modbus/TCP Library, which also provides procedures and information about EDS files.

    Comtrol IO-Link Master AOI Files

    After installing the EDS files, you may want to download and use the AOI (Add On Instructions) for the IO-Link Master: http://downloads.comtrol.com/html/IOLM_EIP_AOI_files.htm.

    Please note that the following documents are included with the Comtrol IOLM AOI file package:

    • Comtrol_IOLM_IO_x_Port AOI Installation and Configuration Guide (IOLM_ IO_AOI_Install_Config_Guide.pdf)

    • Comtrol_IOLM_ISDU AOI Installation and Configuration Guide (IOLM_ ISDU_AOI_Install_Config_Guide.pdf)

    Comtrol IO-Link Master Program Examples

    The sample program files provide an example using an RSLogix 5000 PLC program, which is intended to provide basic working functionality for ladder logic.

    • Through a Class 1 connection, provide a PDI data block with the IO-Link port status, auxiliary bit status and the PDI data.

    • Through explicit messages, provide the ability to send both read and write ISDU requests to the IO-Link devices and receive the responses.

    • Through explicit messages, provide the Device Information block.

    Note: Although the program examples illustrate RSLogix 5000, the IO-Link Master works with other brands/models of EtherNet/IP PLCs, such as Omron.

    The program example shows you how to perform the following steps to run the example PLC program on your ControlLogix family PLC.

    1. Import the PLC program into RSLogix 5000

    2. Configure the Controller

    3. Add the EtherNet/IP Module Interface

    4. Configure the Ethernet Module

    5. Example PLC Program Operation

    6. User Defined Data Structures

    Please refer to the chapter in the IO-Link Master EtherNet/IP and Modbus/TCP Library manual titled, ControlLogix Family – Example PLC Programs for detailed information.

    You can download the example programs from the Comtrol ftp site or download page. When you execute the example program file, it unzips in a Comtrol\IOLM\EtherNetIP\Example Programs directory on your system with CompactLogix and ControlLogix subdirectories.

    http://downloads.comtrol.com/html/IOLM_EIP_eds_files.htmhttp://downloads.comtrol.com/IO_Link_Master/4_EIP/Docs/IOLM_EIP_Library.pdfhttp://downloads.comtrol.com/html/IOLM_EIP_AOI_files.htmhttp://downloads.comtrol.com/IO_Link_Master/4_EIP/Docs/IOLM_EIP_Library.pdfftp://ftp.comtrol.com/IO_Link_Master/4_EIP/Software/plc_example_programs/ethernetip/http://downloads.comtrol.com/html/IOLM_EIP_program_examples.htm

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 43

    Comtrol IO-Link Master and the SLC/PLC-5/MicroLogix Interface

    The IOLM provides support for the SLC, PLC-5 and MicroLogix PLCs. The following features are supported:

    • Rx PDI data, both Polling and Write-to-File modes.

    • Tx PDO data, both PLC-Writes and Read-From-File modes.

    • PCCC based messages transferred by means of the PCCC CIP object, including:

    o SLC Typed Read Message

    o SLC Typed Write Message

    o PLC-5 Typed Read Message (Logical ASCII address format)

    o PLC-5 Typed Write Message (Logical ASCII address format)

    • Receive, transmit and statistics data.

    • Standard PLC-5/SLC file naming conventions.

    • Controlled message rate to the PLC when operating in the Write-to-File receive method. This is accomplished by setting the Maximum PLC Update Rate.

    Please refer to the chapter in the IO-Link Master EtherNet/IP and Modbus/TCP Library manual titled, SLC/PLC-5/MicroLogix Interface, which provides the requirement, messages, and process data (PDI and PDO) access through PCCC messages.

    http://downloads.comtrol.com/IO_Link_Master/4_EIP/Docs/IOLM_EIP_Library.pdf

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 44

    Comtrol IO-Link Master and Modbus/TCP

    This section provides a brief overview about Modbus/TCP configuration, which is supported on both the Comtrol EtherNet/IP (EIP) IO-Link Master and the Comtrol PROFINET IO (PNIO) IO-Link Master families.

    You can use the Modbus/TCP Settings page to define the ISDU data settings, process data settings and transfer mode settings. Please note that you must first enable the Modbus feature at the bottom of this page to integrate Modbus/TCP with your IO-Link Master.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 45

    For detailed information about the Modbus/TCP interface, function codes, address definitions and multiple port process data (PDI/PDO) access via Modbus/TCP, refer to the appropriate documents:

    • IO-Link Master EtherNet/IP and Modbus/TCP Library

    • IO-Link Master PROFINET IO and Modbus/TCP User Guide

    The IO-Link Master also provides a comprehensive diagnostics page for Modbus/TCP.

    http://downloads.comtrol.com/IO_Link_Master/4_EIP/Docs/IOLM_EIP_Library.pdfhttp://downloads.comtrol.com/io_link_master/8_PNIO/Docs/IOLM_PNIO_UserGuide.pdf

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 46

    Comtrol IO-Link Master and PROFINET IO

    This section provides a brief overview about PROFINET IO configuration and diagnostics in the Comtrol PNIO IO-Link series web interface. In addition, it discusses GSDML files.

    PROFINET IO configuration procedures vary between software versions but the following configuration steps are required in all cases. Refer to your STEP 7 documentation, if you require step-by-step procedures.

    1. Download, unzip, and upload the GSD file for the IO-Link Master (IOLM). You can download the GSDML files from: http://downloads.comtrol.com/html/IOLM_PNIO_gsdml_files.htm.

    2. Insert the IOLM in the PROFINET IO system.

    3. Configure the IP address for the IOLM.

    4. Assign the PROFINET Device Name.

    5. Set the IO Device Update Time.

    6. Configure the IO-Link ports.

    a. Configure IO-Link port modules.

    b. Configure port status modules.

    c. If desired, configure data storage, automatic or manual - upload or download.

    d. If desired, configure device validation and data validation.

    7. Use the chapter titled, PROFINET IO Reference Information in the IO-Link Master PROFINET IO and Modbus/TCP User Guide to complete configuration after attaching the IO-Link devices.

    The User Guide provides detailed PROFINET IO configuration procedures using STEP 7 V5.5 and TIA Portal V13.

    Note: The Comtrol IO-Link Master supports other brands of PROFINET IO Controllers, for example, GE.

    The Comtrol IO-Link Master PNIO web interface provides a PROFINET IO Configuration page:

    http://downloads.comtrol.com/html/IOLM_PNIO_gsdml_files.htmhttp://downloads.comtrol.com/io_link_master/8_PNIO/Docs/IOLM_PNIO_UserGuide.pdfhttp://downloads.comtrol.com/io_link_master/8_PNIO/Docs/IOLM_PNIO_UserGuide.pdf

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 47

    The Comtrol IO-Link Master PNIO web interface provides in depth diagnostic information.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 48

    Comtrol IO-Link Master and OPC UA

    This section provides a brief preview about the OPC UA Configuration and Diagnostics web pages. Please refer to the Comtrol IO-Link Master and OPC UA Application Notes, which illustrates how to use the Comtrol IO-Link Master with OPC UA.

    This image displays the OPC UA Settings page.

    This illustrates the OPC UA Diagnostics page when there is an active OPC UA client connection.

    http://downloads.comtrol.com/IO_Link_Master/4_EIP/Docs/TechTips

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 49

    Comtrol IO-Link Master Web Interface Features

    In addition to easily configuring the IO-Link devices attached to the Comtrol IO-Link Master, the web interface provides several other useful pages:

    • Network Settings

    • Misc Settings

    • Load/Save Settings

    • Clear Settings

    • Log Files

    Please note that other Comtrol IO-Link Master features are discussed in the following sections.

    Network Settings Page

    You can easily change network settings using the web page.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 50

    Miscellaneous Settings Page

    The MISC Settings page provides these features:

    • Menu Bar Hover Shows Submenu - This option displays sub-menus for a category when you hover over the category name and allows you to select any page.

    For example, if you hover over Advanced, the SOFTWARE, ACCOUNTS, LOG FILES, and LICENSES sub-menus display. You can click any submenu and avoid opening the default (first) menu for a category.

    • Enable PDO Write From Attached Devices Port Page - When enabled, it allows you to write PDO data to IO-Link slaves from the Attached Devices | Port page in the web user interface. Please note: the PDO write will not

    allow writes if the IOLM has a PLC connection. This should never be enabled in a production environment.

    • LED Flash - You can force the IO-Link port LEDs on the IOLM into a flashing tracker pattern that allows you to easily identify a particular unit.

    • IO-Link Test Event Generation – You can send messages to the IO-Link device and that information can be confirmed using the IO-Link Diagnostics page. It is a handy feature to determine that a device is receiving messages.

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 51

    Load/Save Settings (Cloning the Configuration)

    The ability to save and load Comtrol IO-Link Master configuration files is a useful feature when deploying many IOLMs with the same or similar configuration requirements.

    The IOLM configuration file contains:

    • IOLM gateway configuration (all settings)

    • Data storage contents uploaded to the IO-Link Master

    • IODD files loaded on the IO-Link Master

    1. You must first save the IO-Link Master settings before you can clone the settings.

    2. Connect another IO-Link Master and if necessary, configure the IP address so that you can open the IOLM web page.

    Refer to the Comtrol IO-Link EtherNet/IP and Modbus/TCP Library, Comtrol IO-Link PROFINET IO and Modbus/TCP User Guide, or the Comtrol IO-Link Master Initial Installation and Configuration Application Note for information about programming an IP address that works on your network.

    3. Click Configuration | LOAD/SAVE and then click the Browse button to the location where you saved the configuration file from the first IO-Link Master.

    4. Select the settings that you want to upload to the new IO-Link Master and click the LOAD button.

    ftp://ftp.comtrol.com/IO_Link_Master/4_EIP/Docs/IOLM_EIP_Library.pdfftp://ftp.comtrol.com/IO_Link_Master/4_PNIO/Docs/IOLM_PNIO_UserGuide.pdfftp://ftp.comtrol.com/IO_Link_Master/4_PNIO/Docs/IOLM_PNIO_UserGuide.pdfftp://ftp.comtrol.com/IO_Link_Master/4_EIP/Docs/TechTips/Initial_IOLM_Setup.pdf

  • 8/20/2018 Comtrol IO-Link Master | SICK WTT2SLC-2P3292A00 P a g e | 52

    Clear Settings Page (Resetting IO-Link Master Default Settings)

    Another handy feature is the ability to clear some or all IOLM settings, which includes:

    • All of the IODD files uploaded to the IO-Link Master.

    • All of the IO-Link data storage on the IO-Link Master

    • All of the network settings

    Log Files

    The IO-Link Master provides four different log files that you can view, export, or clear:

    • Syslog (system log) displays line-by-line activity records.

    • dmesg displays Linux kernel messages.

    • top displays which programs are using most of the memory and CPU.

    • ps displays the running programs

    All log files start up automatically during the startup cycle. Each log file has a size limit of 100KB.

    Note: Typically, log files are intended to be used by Technical Support in the event there is a problem.

    ContentsTest Report OverviewIO-Link Master - IO-Link Diagnostics PageConfiguring IO-Link Settings/After Configuring Port-Friendly Names and Implementing Automatic Data Storage Upload/Setting Up PasswordsWTT2SLC-2P3292A00 ConfigurationLocating the IODD FilesLoading IODD FilesVerifying that the Correct IODD Files Are Loaded

    Changing Parameters on the WTT2SLC-2P3292A00 with the GUIChanging Parameters Using the ISDU Interface

    Using the Automatic Data Storage Feature/Using the Manual Data Storage UPLOAD FeatureResetting the Sensor to Factory DefaultsUsing the Manual Data Storage DOWNLOAD FeatureUsing the Device Validation FeatureIncompatible Device Attached to Port

    Comtrol IO-Link Master and EtherNet/IP (EIP)Comtrol IO-Link Master EDS FilesComtrol IO-Link Master AOI FilesComtrol IO-Link Master Program ExamplesComtrol IO-Link Master and the SLC/PLC-5/MicroLogix Interface

    Comtrol IO-Link Master and Modbus/TCPComtrol IO-Link Master and PROFINET IOComtrol IO-Link Master and OPC UAComtrol IO-Link Master Web Interface FeaturesNetwork Settings PageMiscellaneous Settings PageLoad/Save Settings (Cloning the Configuration)Clear Settings Page (Resetting IO-Link Master Default Settings)Log Files