Bridge Components - 3.01 1-888-880-9191 components Transmission Line Support Systems Transmission Line Bridge Kits Transmission Line Bridge Kits come in widths of 1' (305 mm) to 3' (914 mm) and lengths of 10' (3.048 m) to 30' (9.144 m). When ordering kits you may choose from either the Direct-Burial or Anchor-Bolt style pipe columns or the B2230 Bridge Kit designed to work with our 900 series Towers. Each kit includes the steel and hardware for a complete bridge system. The Bridge Channels and Splices are formed of 11-gauge (3 mm) steel. The Pipe Columns are 3-1/2" (89 mm) OD pipe. Stabilizers or X- Brace Kits are included where required. All material is galvanized. All components may be ordered separately for custom applications. Bridge B501 B130 B509 B508 B503 Stabilizer/ Product Bridge Pipe Pipe Canopy Canopy Straight & X-Bracing Number Size (mm x m) Channel Column Head Adapter Sleeve Angle (qty) Hinge Splice Kit (qty) B2212 1' x 10' (305 x 3.048) 1 2 2 B2213 1' x 20' (305 x 6.096) 2 3 3 1 B593 (2) B2214 1' x 30' (305 x 9.144) 3 4 4 2 B593 (2) B2215 2' x 10' (610 x 3.048) 2 4 4 B1117 (2) B2216 2' x 20' (610 x 6.096) 4 6 6 B1117 (3) 2 B1468 (2) B2217 2' x 30' (610 x 9.144) 6 8 8 B1117 (4) 4 B1468 (2) B2218 3' x 10' (914 x 3.048) 3 4 4 B514 (2) B2219 3' x 20' (914 x 6.096) 6 6 6 B514 (3) 3 B1469 (2) B2220 3' x 30' (914 x 9.144) 9 8 8 B514 (4) 6 B1469 (2) B2230 * 2' x 10' (610 x 3.048) * This kit is to be used with Valmont Microflect's 900 Series Tower Bridge B501 B126 B509 B508 B503 Stabilizer/ Product Bridge Pipe Pipe Canopy Canopy Straight & X-Bracing Number Size (mm x m) Channel Column Head Adapter Sleeve Angle (qty) Hinge Splice Kit (qty) B2221 1' x 10' (305 x 3.048) 1 2 2 B2222 1' x 20' (305 x 6.096) 2 3 3 1 B593 (2) B2223 1' x 30' (305 x 9.144) 3 4 4 2 B593 (2) B2224 2' x 10' (610 x 3.048) 2 4 4 B1117 (2) B2225 2' x 20' (610 x 6.096) 4 6 6 B1117 (3) 2 B1468 (2) B2226 2' x 30' (610 x 9.144) 6 8 8 B1117 (4) 4 B1468 (2) B2227 3' x 10' (914 x 3.048) 3 4 4 B514 (2) B2228 3' x 20' (914 x 6.096) 6 6 6 B514 (3) 3 B1469 (2) B2229 3' x 30' (914 x 9.144) 9 8 8 B514 (4) 6 B1469 (2) Anchor-Bolted Pipe Column Kit Direct-Burial Pipe Column Kit Canopy Angle B501 Bridge Channel B508 Canopy Adapter Sleeve X-Bracing Kit B126 Anchor-Bolted Pipe Column Bridge height is adjustable 10’ (3.048 m) min. 12’ (3.658 max. Consists of: Consists of:

Transcript of components Transmission Line Support Systems - …€¦ · components Transmission Line Support...

Page 1: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

Bridge Components - 3.011-888-880-9191

componentsTransmission Line Support Systems

Transmission Line Bridge KitsTransmission Line Bridge Kits come in widths of 1' (305mm) to 3' (914 mm) and lengths of 10' (3.048 m) to 30'(9.144 m). When ordering kits you may choose fromeither the Direct-Burial or Anchor-Bolt style pipe columnsor the B2230 Bridge Kit designed to work with our 900series Towers. Each kit includes the steel and hardwarefor a complete bridge system. The Bridge Channels andSplices are formed of 11-gauge (3 mm) steel. The PipeColumns are 3-1/2" (89 mm) OD pipe. Stabilizers or X-Brace Kits are included where required. All material isgalvanized. All components may be ordered separately forcustom applications.

Bridge B501 B130 B509 B508 B503 Stabilizer/Product Bridge Pipe Pipe Canopy Canopy Straight & X-BracingNumber Size (mm x m) Channel Column Head Adapter Sleeve Angle (qty) Hinge Splice Kit (qty)B2212 1' x 10' (305 x 3.048) 1 2 2 — — — —

B2213 1' x 20' (305 x 6.096) 2 3 3 — — 1 B593 (2)

B2214 1' x 30' (305 x 9.144) 3 4 4 — — 2 B593 (2)

B2215 2' x 10' (610 x 3.048) 2 4 — 4 B1117 (2) — —

B2216 2' x 20' (610 x 6.096) 4 6 — 6 B1117 (3) 2 B1468 (2)

B2217 2' x 30' (610 x 9.144) 6 8 — 8 B1117 (4) 4 B1468 (2)

B2218 3' x 10' (914 x 3.048) 3 4 — 4 B514 (2) — —

B2219 3' x 20' (914 x 6.096) 6 6 — 6 B514 (3) 3 B1469 (2)

B2220 3' x 30' (914 x 9.144) 9 8 — 8 B514 (4) 6 B1469 (2)

B2230 * 2' x 10' (610 x 3.048) — — — — — — —

* This kit is to be used with Valmont Microflect's 900 Series Tower

Bridge B501 B126 B509 B508 B503 Stabilizer/Product Bridge Pipe Pipe Canopy Canopy Straight & X-BracingNumber Size (mm x m) Channel Column Head Adapter Sleeve Angle (qty) Hinge Splice Kit (qty)

B2221 1' x 10' (305 x 3.048) 1 2 2 — — — —

B2222 1' x 20' (305 x 6.096) 2 3 3 — — 1 B593 (2)

B2223 1' x 30' (305 x 9.144) 3 4 4 — — 2 B593 (2)

B2224 2' x 10' (610 x 3.048) 2 4 — 4 B1117 (2) — —

B2225 2' x 20' (610 x 6.096) 4 6 — 6 B1117 (3) 2 B1468 (2)

B2226 2' x 30' (610 x 9.144) 6 8 — 8 B1117 (4) 4 B1468 (2)

B2227 3' x 10' (914 x 3.048) 3 4 — 4 B514 (2) — —

B2228 3' x 20' (914 x 6.096) 6 6 — 6 B514 (3) 3 B1469 (2)

B2229 3' x 30' (914 x 9.144) 9 8 — 8 B514 (4) 6 B1469 (2)

Anchor-Bolted Pipe Column Kit

Direct-Burial Pipe Column Kit

Canopy Angle

B501 BridgeChannel

B508 CanopyAdapter Sleeve

X-Bracing Kit B126 Anchor-BoltedPipe Column

Bridge height isadjustable10’ (3.048 m) min.12’ (3.658 max.

Consists of:

Consists of:

Page 2: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

1-888-880-91913.02 - Bridge Components

componentsTransmission Line Support Systems

Trapeze Support Kitfor Snap-In or Cushion HangersTrapeze Support Kits provide support for transmissionlines on angle brackets suspended with 3/8" diameterthreaded rod below 2' (610 mm) or 3' (914 mm) widesupport bridges. The Trapeze Kits are available in single,double, or triple tiers for both widths of support bridges.As shown in the illustration, one leg of each angle bracketis furnished with holes for Snap-In Hangers and the otherleg with holes for Cushion Hangers. Using the B1757Adapter (page 6.01), the 3/4" (19 mm) diameter holes forSnap-In Hangers may be converted to 7/16" (11 mm) foruse with Cushion Hangers. Hardware is included.

2' (610 mm)

3/8" diathreaded rodand hardware

Snap-InHangers(p. 6.07)

7/16" (11 mm) diaholes for CushionHangers

3/4" (19 mm) diaholes for Snap-InHangers

B501 orB502 BridgeChannels

Angle bracketspositioned tosupport eitherSnap-In Hangers orCushion Hangers

Cushion Hangers(p. 6.01–6.04)

Typical installation option usingCushion Hangers

Typical installation option usingCoax Blocks

Product Bridge Support Threaded Hangers SupportedNumber Width Tiers Rod Length Cushion Snap-InB1888 2' (610 mm) Single 1' (305 mm) 5 8

B1889 2' (610 mm) Double 1' 6" (457 mm) 10 16

B1890 2' (610 mm) Triple 2' (610 mm) 15 24

B1891 3' (914 mm) Single 1' (305 mm) 8 13

B1892 3' (914 mm) Double 1' 6" (457 mm) 16 26

B1893 3' (914 mm) Triple 2' (610 mm) 24 39

B1890 shown

B501 or B502Bridge Channel(p. 3.03)

B1292 Cross (p. 2.04)

B864 3/8" Nut, B868 3/8"Lock Washer & B872 3/8"Flat Washer (p. 14.01)

B1271 3/8" x 1' (305 mm)Threaded Rod (p. 14.11)

Cushion HangerAssembly (p 6.02-6.05)

3/8" Nut &Lock Washer(p. 14.01)

B238 3/8" x 1/2"Round Head Screw& Lock Washer

B501 or B502Bridge Channel(p. 3.03)

Coax Blocksand Hardware(p. 6.06)

Page 3: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

Bridge Components - 3.031-888-880-9191

componentsTransmission Line Support Systems

Hanger Bracketfor Snap-In Hangers, CushionHangers, or Butterfly HangersHanger Brackets, supporting both Snap-In Hangers(p. 6.02), Cushion Hangers (p. 6.02-6.04) or ButterflyHangers (p. 6.07) bolt below B501 and B502 Bridge Chan-nels to provide protected horizontal support for transmissionline runs. The Hanger Brackets are available in two models,supporting the number of Hangers shown below.

Galvanized

3/4" (19 mm) dia holes forSnap-In Hangers

7/16" (11 mm) dia holes forCushion Hangers

1' (305 mm)

B501 or B502Bridge Channel

4" (102 mm)

2-1/2" (64 mm)

2-1/2" (64 mm)

Snap-In Hanger

TransmissionLine

Length

B1910 Shown

Product Hangers SupportedNumber Snap-In Cushion Butterfly LengthB1752 12 6 10 1' 4-5/8" (422 mm)

B1910 16 8 14 1' 9-5/8" (549 mm)

1'(305 mm)

2" (51 mm) 4"(102 mm)

2"(51 mm)

2-1/2"(64 mm)

All slots are 7/16" (11 mm) x7/8" (22 mm)

Center holes are 9/16"(14 mm) dia

1' 2"(356 mm)

2' 6"(762 mm)

2' 6"(762 mm)

2' 6"(762 mm)

1' 2"(356 mm)

1"(25 mm)10'

(3.048 m)

1"(25 mm)

4" (102 mm)

1"(25 mm)

4" (102 mm)

1"(25 mm)

2' 6" (762 mm)

1' 2" (356 mm)5' (1.524 m)

Center holes are 9/16"(14 mm) dia

1' 2" (356 mm)

Bridge ChannelBridge Channels provide support for horizontal transmis-sion line runs as well as protection from hazards, such asfalling ice. The channels are formed of 11-gauge (3 mm)steel and are hot-dip galvanized after fabrication. All slotsare 7/16" (11 mm) x 7/8" (22 mm) long for 3/8" diameterhardware. Each section includes ten 3/8" diameter x1-1/4" long bolts, nuts, lockwashers, and flatwashers forsplicing or support. If cutting is required to accommodateunusual angles or lengths, the B186 Touch-up Kit orB364 Touch-up Spray (p. 13.04) is recommended fortreating raw metal edges.

B501

B502

Detail

ProductNumber DescriptionB501 10' (3.048 m) long

B502 5' (1.524 m) long

Page 4: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

1-888-880-91913.04 - Bridge Components

componentsTransmission Line Support Systems

The upper hole is usedfor hinging the splice 25° max.

3" (76 mm)1"(25 mm)

1" (25 mm)

2-11/16" (68 mm)1-13/16" (46 mm)

5"(127 mm)

Straight & Hinged Splice*A Splice is used to join two sections of Bridge Channel whenthe joint does not occur at a Pipe Head. A Splice is also usedas a hinge to accommodate vertical angles. It is made of 11-gauge (3 mm) galvanized steel. Hardware is not provided.

Galvanized

0°–45°

Adjustable 0° - 45° Splice*

An Adjustable Splice is used to make horizontal bendsfrom 0°-45°, either right or left. Made of galvanized plate.Hardware is not provided.

Galvanized

* A Pipe Column must be within 2' (610 mm) of either side of the B503or B504 Splice.

Holes are 7/16" (11 mm) diameter Slots are 7/16" (11 mm) x 1" (25 mm).

ProductNumber DescriptionB503 Straight & Hinged Splice

ProductNumber DescriptionB504 Adjustable 0°-45° Splice

Extension is 2'(610 mm) long

45°

Extension Kitfor Bridge ChannelAn Extension Kit permits a 45° extension at the end of aBridge Channel to accommodate the bending radius oftransmission line runs. Eleven bolt assemblies, 3/8"diameter x 1-1/4" long, are provided.

The kit is galvanized after fabrication.

B512 WallSupport Angle

1' 2"(356 mm)

1' 6"(457 mm)

Corner FillerCorner Fillers are used to provide ice protection for 90°bends of transmission line runs, or when a wider area ofice protection is needed over an Entry Panel. They aremade of 11-gauge (3 mm) hot-dip galvanized steel. Four3/8" diameter bolts, nuts, flatwashers and lockwashersare provided.

ProductNumber DescriptionB1133 Extension for Bridge Channel

ProductNumber DescriptionB505 Corner Filler

Page 5: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

Bridge Components - 3.051-888-880-9191

componentsTransmission Line Support Systems

Splice Stiffener Kitfor Bridge ChannelsSplice Stiffener Kit is intended to support short BridgeChannel extensions or provide additional structuralsupport to other Bridge Channel joints. The Kit is notintended to replace Pipe Heads or Canopy Angles forsupport of full length Bridge Channels.

Kit includes two angles 2" (51 mm) x 2" (51 mm) x3/16" (5 mm), 2' 9" (838 mm) long and is galvanized afterfabrication. Hardware is not included.

2' 9"(838 mm)

B501 or B502Bridge Channels

ProductNumber DescriptionB1223 Splice Stiffener Kit

Heavy Duty Splice Stiffener Kitfor Bridge ChannelsStiffener Kit enables two B501 Bridge Channels, splicedtogether, to span 20' (6.10 m) between supports. Thereinforced Bridge Channels will support 30 psf(1,436 N/m2) dead load. The Kit includes two angles 3-1/2"(89 mm) x 3" (76 mm) x 1/4" (6 mm), 7' 9" (2.362 m)long. Hardware is included.

ProductNumber DescriptionB1904 Heavy Duty Splice Stiffener Kit

13

' 4"

(4.0

64

m)

Ove

rall

15

' 4"

(4.6

74

m)

Ove

rall

2' 8" (813 mm)

4" (102 mm) OD3-1/2"(89 mm) OD

3' 4" (1.016 m)min embedmentin concrete

Grade

12'(3.658 m)

10'(3.048 m)

Direct-Burial Pipe Columns

B273

B130

Pipe Columns are all 3-1/2" (89 mm) OD at the top andwill accept any of the Pipe Heads, Truss Supports, orCanopy Supports shown in this section. When determin-ing maximum height of the Pipe Columns, add the2' (610 mm) of adjustment, available from the Pipe Headsand Trusses. All columns are hot-dip galvanized. Themaximum spacing for Pipe Columns is 10' 1" (3.073 m)for Bridge Channels, and 20' (6.096 m) for GratingBridge Channels.Direct-Burial Pipe Columns

Direct-Burial Footingfor B130 and B273Excavations for Pipe Column footings, in normal soil,should be prepared as illustrated below.

3-1/2" (89 mm) and4" (102 mm) OD PipeColumns

4" (102 mm)

Grade

3' 4" (1.016 m) min

4" (102 mm)

1' (305 mm) dia

ProductNumber DescriptionB130 10' (3.048 m) Direct-Burial Pipe Column

B273 12' (3.658 m) Direct-Burial Pipe Column

7' 9" (2.362 m)

Page 6: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

1-888-880-91913.06 - Bridge Components

componentsTransmission Line Support Systems

Pipe Column Base Plate

Anchor Bolt Footingfor B126, B279, B280, and B1641Excavations for Pipe Column footings, in normal soil,should be prepared as illustrated below. Galvanizedanchor bolts, lock washers and nuts are included with theindicated anchor-bolt style Pipe Columns.

4-1/2"(114 mm)

3/4" (19 mm)

7/8" (22 mm)dia hole for3/4" diaanchor bolt

Transmission Line RunDirection oftransmission line run is90° to anchor boltinstallation

10" (254 mm)

8" (203 mm)

8"(203 mm)

4" (102 mm)

2-1/2" (64 mm)projection

3/4" diaanchor bolts

Grade

3' 4"(1.016 m) min

1'(305 mm) dia

4"(102 mm) OD

4"(102 mm)OD

4"(102 mm)OD

4' 8"(1.422 m)

4' 8"(1.422 m)

2' 8"(813 mm)

3-1/2"(89 mm)OD

10'(3.048 m)

12'(3.658 m)

14'(4.267 m)

16'(4.877 m)

Anchor-Bolt Pipe ColumnsPipe Columns are all 3-1/2" (89 mm) OD at the top andwill accept any of the Pipe Heads, Truss Supports, orCanopy Supports shown in this section. When determin-ing maximum height of the Pipe Columns, add the 2'(610 mm) of adjustment, available from the Pipe Headsand Trusses. All Columns are hot-dip galvanized. Themaximum spacing for Pipe Columns is 10' 1" (3.073 m)for Bridge Channels, and 20' (6.096 m) for GratingBridge Channels.

Anchor-bolt style Pipe Columns are available either withor without the anchor bolt weldment. The anchor boltweldment consists of two 3/4" diameter x 4' (1.219 m)long bolts and tie bars.

B1641

B280

B279

B126

Pipe Column Anchor-bolts Anchor-boltsHeight Included Excluded10' (3.048 m) B126 B126X

12' (3.658 m) B279 B279X

14' (4.267 m) B280 B280X

16' (4.877 m) B1641 B1641X

Anchor-Bolt Pipe Columns

Page 7: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

Bridge Components - 3.071-888-880-9191

componentsTransmission Line Support Systems

Pipe Columnfor Roof InstallationThe B293 Pipe Column provides a versatile means forrooftop installation of transmission line runs. The PipeColumn bolts directly to the roof or to a concrete pad. Withthe 2' (610 mm) adjustment of either a B509 Pipe Head orB510 Truss Support, the Pipe Column provides an overallheight from 3' 4" (1.016 m) to 5' 4" (1.626 m). The PipeColumn is hot-dip galvanized after fabrication and two 1/2"diameter x 2" long galvanized lag bolts are included.

Non-penetrating Roof-Mounted Coax Bridge Kits are alsoavailable on page 5.01.

3' 4"(1.016 m)

2' 6"(762 mm)

5" (127 mm)

3-1/2"(89 mm)OD pipe

The B509 Pipe Headsupports Bridge Channelor Square Rail

9/16" (14 mm)dia hole

2' 4" (711 mm)

ProductNumber DescriptionB293 Pipe Column for Roof Installation

Truss Supportfor Two Bridge ChannelsThe Truss Support is used to support two 1' (305 mm)wide Bridge Channels. The pipe sleeve allows a 2'(610 mm) adjustment above the height of the PipeColumn and is locked in place with two 1/2" diameter setscrews. The parts are hot-dip galvanized after fabricationand four hookbolt assemblies are furnished.

6-1/2" (165 mm) gap

9-1/4"(235 mm)

9-1/4" (235 mm)

9/16" (14 mm)dia holes

CL

CL

CL

ProductNumber DescriptionB510 Truss Support for two Bridge Channels

B510X Truss Support without the pipe sleeve

Pipe Headfor Bridge ChannelPipe Heads are used with Pipe Columns to install 1'(305 mm) wide Bridge Channels. They allow a 2'(610 mm) adjustment above the height of the PipeColumn and are locked in place with two 1/2" diameterset screws spaced 5" (127 mm) apart. Channels areattached to the Pipe Head using their 3/8" diameterhardware or using the hookbolts provided with the PipeHead. The Pipe Head arm may be inverted to provide foran inverted Bridge Channel installation. Galvanized

The Bridge Channel bolts are used to splice the Channel at the Pipe Head.

ProductNumber DescriptionB509 Pipe Head for Bridge Channel

B501 orB502BridgeChannel

The PipeHead hookboltssupport the BridgeChannel away froman end

9" (229 mm)

1"(25 mm)

Channel

PipeLC

LC

Page 8: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

1-888-880-91913.08 - Bridge Components

componentsTransmission Line Support Systems

Canopy Adapter Sleeve

Angle can be mounted inverted to support inverted Channel

Canopy AngleThe Canopy Angle (B1117, B514, or B1582) and CanopySleeve (B508) are designed for use with Pipe Columns.The 2' 6" (762 mm) long Sleeve allows a 2' (610 mm)adjustment and is locked in place with two 1/2" diameterset screws. The B1117 and B514 Angles are 3-1/2" (89mm) x 2-1/2" (62 mm) x 1/4" (6 mm). The B1582 Angleis 3-1/2" (89 mm) x 2-1/2" (62 mm) x 1/4" (6 mm). Theunits are galvanized after fabrication.

Canopy Angle may be inverted on the B508 Canopy Adaptor Sleeve tosupport an inverted Bridge Channel

B1117, B514,or B1582Canopy Angles

1/2" dia bolt andlockwasher includedwith B508 Sleeve

2' 6"(762 mm)

B508Sleeve

3-1/2" (89 mm)OD Pipe Column

1/2" dia bolt andlockwasher includedwith B508 Sleeve

B1117, B514,or B1582Canopy Angle

B162 ClipAngle

1/2" dia mountinghardware required(not included)

B508 Sleeve

3-1/2" (89 mm)OD Pipe Column

Wal

l

1/2" dia bolt andlockwasher includedwith B508 Sleeve

2' 4-1/2" (724 mm)–B11173' 4-1/2" (1.029 m)–B5144' 4-1/2" (1.334 m)–B1582

B508 Sleeve

3-1/2" (89 mm)OD Pipe Column

2' 5-5/8" (752 mm)–B11173' 5-5/8" (1.057 m)–B5144' 5-5/8" (1.362 m)–B1582

1/2" dia mounting hardwarerequired (not included)

B162 CornerClip Angle

B508 Sleeve

3-1/2" (89 mm) ODPipe Column

Wal

l

ProductNumber DescriptionB508 Canopy Adapter Sleeve

ProductNumber DescriptionB1117 Canopy Angle for 2' (610 mm) bridge

B514 Canopy Angle for 3' (914 mm) bridge

B1582 Canopy Angle for 4' (1.219 m) bridge

1/2" dia wallattachment hardwareis not included

2' 6" (762 mm)

Canopy Wall Support BracketThe Canopy Wall Suport Bracket supports a 1' (305 mm)to 3" (914 mm) wide bridge running parallel to a walland is used above building entries for transmission lineswith a large bend radius. If the wall height allows, theBracket is oriented with the Bridge Channels mountedbelow the Bracket. If not the Bracket is inverted and theBridge Channels mounted on top, with the transmissionlines routed around the diagonal angle of the Bracket. The1/2"diameter hardware for wall mounting is not included.

The Bracket is galvanized after fabrication.

Preferred Mounting

Alternate Mounting

ProductNumber DescriptionB507 Canopy Support Bracket

Use this mountingorientation when the wallheight allows

2' 6"(762 mm)

Wal

l

Use this mountingorientation for a short wallheight

Transmission lines can berouted around theBracket’s diagonal angle

2' 6"(762 mm)

Wal

l

3' (914 mm)

Page 9: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

Bridge Components - 3.091-888-880-9191

componentsTransmission Line Support Systems

Stabilizer Kitfor Pipe ColumnRecommended for bracing Pipe Columns when supportbridges are long and/or heavily loaded. Minimizes columnand bridge wobble. Supports bridge in either longitudinalor transverse directions.

The kit is galvanized after fabrication.

Footing Detail

B593 includes:1 - 3-1/2" (89 mm) OD pipe clamp1 - Pipe 2-3/8" (60 mm) OD x 10' (3.048 m) long1 - Angle 3" (76 mm) x 3" (76 mm) x 1/4" (6 mm), 2' (610 mm) long3 - 1/2" dia x 1-3/4" bolts, nuts & lock washers

See footingdetail below

4" (102 mm)

2' (610 mm) min

9" (229 mm) min9" (229 mm) min

ProductNumber DescriptionB593 Stabilizer Kit for Pipe Column

11/16" (17 mm) diahole for 1/2" diahardware (hardwarenot included)

7" (178 mm)hole to hole

8"(203 mm)

8"(203 mm)

1' 2-7/8"(378 mm)

Wall Support BracketThe B506 Wall Support Bracket suppports a singel BridgeChannel running parallel to a wall. Holes in the Bracketenable the Bridge Channel to be bolted directly or sup-ported with hookbolts. The 1/2" diameter hardware forwall mounting is not included.

Galvanized

ProductNumber DescriptionB506 Wall Support Bracket

Bracket can be mounted inverted to support inverted Bridge Channel

Hookbolt installation Bolted through channel

Page 10: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

1-888-880-91913.10 - Bridge Components

componentsTransmission Line Support Systems

X-Bracing Kitfor Support BridgesThe X-Bracing Kit is recommended for stabilizing PipeColumns used in 2' (610 mm), 3' (914 mm), or4' (1.219 m) wide bridges. The Kit minimizes sway andwobble of the support bridge and may also be used withthe B593 Stabilizer Kit for additional bracing.

The kit is galvanized after fabrication.

X-Bracing Kit includes:2 - Horizontal angles2 - Cross-brace angles4 - 5/8" dia x 3-5/8" x 5" U-bolt assemblies5 - 1/2" dia x 1-1/2" bolt, nut and lock washer assemblies(5/8" dia for B1583)

ProductNumber DescriptionB1468 for 2' (610 mm) wide support bridge

B1469 for 3' (914 mm) wide support bridge

B1583 for 4' (1.219 m) wide support bridge

6' (1.829 m)

B505 Corner Filler

1' 11" (584 mm)hole–hole

1' 11" (584 mm)hole–hole

Wall Support AngleThe B512 Wall Support Angle is used to support BridgeChannel and Corner Fillers above the Entry Panel at thewall. The angle is 3" (76 mm) x 3" (76 mm) x 3/16"(5 mm) x 4' (1.219 m) long and is galvanized afterfabrication.

1/2" dia hardwarerequired forattachment to wall (notincluded)

3/8" dia hardwarerequired (not included)

ProductNumber DescriptionB512 Wall Support Angle

Page 11: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

Bridge Components - 3.111-888-880-9191

componentsTransmission Line Support Systems

1' 10" (559 mm)hole-hole

Wall Support AngleThe B511 Wall Support Angle is used to support BridgeChannel above the Entry Panel at the wall. The angle is3" (76 mm) x 2-1/2" (64 mm) x 1/4" (6 mm) x 2'(610 mm) long and is galvanized after fabrication.

Truss Wall Support Anglefor Two Bridge ChannelsThe B1280 Truss Wall Support Angle is used to supporttwo 1' (305 mm) wide Bridge Channels above the Entrypanel at the wall. The angle is 3" (76 mm) x 3" (76 mm) x3/16" (5 mm) x 2' 6-1/2" (775 mm) long and is galva-nized after fabrication.

1/2" dia hardwarerequired for attachmentto building wall (notincluded)

3/8" dia hardwarerequired (not included)

1/2" dia hardware required for attachmentto building wall (not included)

2' 4" (711 mm)hole–hole

3/8" diahardwarerequired (notincluded)

ProductNumber DescriptionB511 Wall Support Angle

ProductNumber DescriptionB1280 Truss Wall Support Angle

Bridge Support at TowerThe location of vertical transmission line runs on a toweris the prime consideration in deciding where and how thehorizontal Bridge should be terminated at the tower.

An easy method for planning and installing the horizon-tal Bridge is to position a Pipe Column near a tower leg,to support the end of the Bridge, as shown below. Thiseliminates any direct attachment to the tower andenables use of Pipe-Leg Support Clamps (section 2) forsupport of the vertical transmission line runs. Whenvertical runs are supported on ladders or center cagestructures, the Pipe Column may be located close tothose vertical-support structures.

When Bridge Channel is to be supported from the tower,the type of tower construction will usually determine thebest method for attaching the Channel. The versatileproducts in this section enable Channels to be sup-ported from the legs, girts, and diagonal braces of thetower. The product illustrations show the most commonmethods used.

PipeColumn

Pipe Head

BridgeChannel

Page 12: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

1-888-880-91913.12 - Bridge Components

componentsTransmission Line Support Systems

Angle from BridgeChannel Support(p 3.14) (ref)

B189 Mounting Tabs usedwithout Clevis. Angle bolteddirectly to Mounting Tabwith 1/2" dia hardware.

Multipurpose clamp

MountingTab

Clevis

multipurposeclamps

3/8" diathreadedrod

M

Mounting Tab & Clevis Kitfor Pipe MembersThese assemblies are designed to provide an adjustableattachment point on a pipe tower without drillingthrough or damaging the protective finish of members.The base of the Mounting Tab is 5" (127 mm) long and isattached to the tower with two multipurpose clamps. A1/2" diameter bolt and nut secure the Clevis to theMounting Tab. A tapped hole in the Clevis accepts 3/8"diameter threaded rod for suspending Bridge Channel.

Mounting Tab and Clevis are galvanized.

B189 includes:1 - 5" (127 mm) Mounting Tab1 - Clevis1 - 1/2" dia x 1-1/2" (38 mm) long bolt, nut, and lockwasher2 - Multipurpose clamps

ProductNumber DescriptionB189 Mounting Tab & Clevis Kit

B573 includes:1 - 5" (127 mm) Mounting Tab1 - Clevis1 - 1/2" dia x 1-1/2" (38 mm) long bolt, nut and lockwasher4 - 3/8" dia ss nuts4 - 3/8" dia ss lockwashers2 - 1-1/2" dia round spacers2 - 3/8" dia x 6" (152 mm) long ss threaded rods

B1309 RoundSpacer

Double-anglegirt (horizontaltower member)

Double-anglediagonal

B573

B501 or B502BridgeChannel

3/8" diaThreaded Rod(not included)

Mounting Tab & Clevis Kitfor Double-Angle MembersThese assemblies are designed to provide an adjustableattachment point on a double-angle diagonal withoutdrilling or damaging the protective finish of members.The base of the Mounting Tab is 5" (127 mm) long and isattached to the tower with two 3/8" diameter x 6"(152 mm) long stainless steel threaded rods. A 1/2"diameter bolt and nut secure the Clevis to the MountingTab. A tapped hole in the Clevis accepts 3/8" diameterthreaded rod for suspending the Bridge Channel.

Mounting Tab and Clevis are galvanized.

A girt can be used to suspend a BridgeChannel with 3/8" diameter threaded rodand B1309 Round Spacer. Rod length can bevaried to level Bridge Channel.

ProductNumber DescriptionB573 Mounting Tab & Clevis Kit

Page 13: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

Bridge Components - 3.131-888-880-9191

componentsTransmission Line Support Systems

B501 or B502Bridge Channel

Pipe-center tochannel-center

Tower leg

Pipe-LegChannelSupport

Channel

Leg

Pipe-Leg Channel SupportSupports Bridge Channel positioned next to pipe tower leg.

Hot-dip galvanized.

Pipe-Leg Channel Support includes:2 - Pipe clamps1 - Angle1 - Flatbar5 - 1/2" dia x 1-3/4" (44 mm) long bolts, nuts and lockwashers2 - 3/8" dia x 5-1/2" (140 mm) long hookbolts, nuts and lockwashers

Product Tower Pipe-Center toNumber Leg OD Channel-CenterFor 1' (305 mm) Bridge

B588 2-7/8" (73 mm) 1' 1/8" (308 mm)

B589 3-1/2" (89 mm) 1' 7/16" (316 mm)

B1202 4" (102 mm) 1' 11/16" (322 mm)

B584 4-1/2" (114 mm) 1' 15/16" (329 mm)

B590 5-9/16" (141 mm) 1' 1-1/2" (343 mm)

B585 6-5/8" (168 mm) 1' 2" (356 mm)

B586 8-5/8" (219 mm) 1' 3" (381 mm)

B591 10-3/4" (273 mm) 1' 4-1/16" (408 mm)

B592 12-3/4" (324 mm) 1' 5-1/16" (433 mm)

B2146 14" (356 mm) 1' 5-11/16" (449 mm)

B2147 16" (406 mm) 1' 6-1/16" (475 mm)

B2148 18" (457 mm) 1' 7-1/16" (500 mm)

B2149 20" (508 mm) 1' 8-1/16" (525 mm)

B2150 22" (559 mm) 1' 9-1/16" (551 mm)

B2151 24" (610 mm) 1' 10-1/16" (576 mm)

For 2' (610 mm) Bridge

B1210 2-7/8" (73 mm) 1' 6-1/8" (460 mm)

B1211 3-1/2" (89 mm) 1' 6-7/16" (468 mm)

B1212 4" (102 mm) 1' 6-11/16" (474 mm)

B1213 4-1/2" (114 mm) 1' 6-15/16" (481 mm)

B1214 5-9/16" (141 mm) 1' 7-1/2" (495 mm)

B1215 6-5/8" (168 mm) 1' 8" (508 mm)

B1216 8-5/8" (219 mm) 1' 9" (533 mm)

B1217 10-3/4" (273 mm) 1' 10-1/16" (560 mm)

B1218 12-3/4" (324 mm) 1' 11-1/16" (586 mm)

B2152 14" (356 mm) 1' 11-11/16" (602 mm)

B2153 16" (406 mm) 2' 11/16" (627 mm)

B2154 18" (457 mm) 2' 1-11/16" (652 mm)

B2155 20" (508 mm) 2' 2-11/16" (678 mm)

B2156 22" (559 mm) 2' 3-11/16" (703 mm)

B2157 24" (610 mm) 2' 4-11/16" (729 mm)

Bridge Channel Supportfor 800 Series TowerThese Bridge Channel Supports mount to Microflect 800Series vertical tower bays with a 5' (1.524 m) face with2-7/8" (73 mm) OD legs or a 9' (2.743 m) face with4-1/2" (114 mm) OD legs. These Bridge Channel Sup-ports may be installed at any height on these tower bays,and the Bridge Channel may be attached at variouspositions across the horizontal angle.Bridge Channel Support is hot-dip galvanized.

TowerLeg

B501 orB502 BridgeChannel

A

A

U-bolts

Tower leg

Mountingbracket

Angle

Channel Support includes:1 - Angle 3" (76 mm) x 3" (76 mm) x 1/4" (6 mm)4 - U-bolt assemblies2 - Mounting brackets2 - Hookbolts with nuts and lockwashers

View A–A

For TowerProduct Bay VerticalNumber Width Pipe-Leg SizeB1136 5' (1.524 m) 2-7/8" (73 mm) OD

B1065 9' (2.743 m) 4-1/2" (114 mm) OD

Page 14: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

1-888-880-91913.14 - Bridge Components

componentsTransmission Line Support Systems

B501 or B502Bridge Channel

B516 Adjustable Clamping Bar

B515 Corner Clip Angle

B513 Support Angle

A

A

Support Anglefor Bridge ChannelTwo methods are shown below for using the B513 SupportAngle to transition a vertical transmission line run to ahorizontal bridge. The single 5' (1.524 m) long Angle isfurnished with 7/16" (11 mm) diameter holes for attachingthe Bridge Channel. The angle size is 2-1/2" (64 mm) x2-1/2" (64 mm) x 3/16" (5 mm). The angle is hot-dipgalvanized and mounting hardware is not included.

Note that sufficient space is provided to bend the transmission line forthe vertical run.

ProductNumber DescriptionB513 Support Angle for Bridge Channel

3/8" diahardware

Double-angle girt

B513SupportAngle

B164 orB1271ThreadedRod

B1309RoundSpacer

View B–B

B513SupportAngle

3/8" diahardware

B515 CornerClip Angle,B174 SpringNut, and 3/8"dia ss hardware

B516 AdjustableClamping Bar

Angle Leg

3/8" dia threaded rod andB1309 Round Spacer

B513 Support Angle

B501 or B502Bridge Channel

Tower Leg Clamp(p. 2.01)

B

B

View A - A

7/16" (11 mm)dia hole

B1577 1/2" diaUniversal Clamp

Spacer

Tower Leg

2-1/8" (54 mm)

Q-Tower

B501 orB502 BridgeChannel Hookbolts

B517 BridgeChannelSupport

A

A

Bridge Channel Supportfor Q-TowerThe B517 Bridge Channel Support mounts directly toQ-Tower angle legs and is designed to support the end ofa Bridge Channel at the tower. This product differs fromthe B516 Adjustable Clamping Bar (page 2.10) whichsupports a B517 Bridge Channel that ends before reach-ing the tower. The B517 Support may be installed at anyheight on the Q-Tower, and the Bridge Channel may beattached at various positions across the horizontal angle.

The Bridge Channel Support is hot-dip galvanized.

B517 includes:1 - Angle 3" (76 mm) x 3" (76 mm) x 1/4" (6 mm), 7' 2" (2.184 m) long2 - Spacers2 - 1/2" dia x 2-1/2" (64 mm) long bolts and lockwashers2 - 3/8" dia hookbolts2 - B1577 Universal Clamps

View A–A

ProductNumber DescriptionB517 Bridge Channel Support for Q-Tower

Page 15: components Transmission Line Support Systems - …€¦ · components Transmission Line Support Systems ... either the Direct-Burial or Anchor-Bolt style pipe columns ... dead load.

Bridge Components - 3.151-888-880-9191

componentsTransmission Line Support Systems

Monopole Channel SupportThe Monopole Channel Support mounts directly to theMonopole, and will support the end of a Bridge Channel.Using the B515 Corner Clip Angle and B513 SupportAngle the Bridge Channel will attach to the Monopoleallowing room for the transmission line to bend fromvertical to horizontal. The Monopole Channel Supportmay be installed at any height on the Monopole.

Galvanized

ProductNumber FitsB1949 16"–18" OD pipe

B1950 20"–22" OD pipe

B1951 24"–26" OD pipe

B1968 28"–30" OD pipe

Bridge Channel Support Systemfor Pipe-Leg Tower FaceThe Bridge Channel Support System enables the attach-ment of a 1' (305 mm) or 2' (610 mm) wide WaveguideBridge on the face of a pipe-leg tower with a vertical faceor with a face taper up to 20:1. The System is composedof three components and the individual products areselected based on the size of the pipe-leg and width of thetower face. The Waveguide Bridge Support Angle isavailable for a 2-7/8" (73 mm) OD or a 4-1/2" (114 mm)OD pipe depending upon the Face-Supports Pipe chosen.(See page 9.02 for the Pipe-Leg Bracket Kit and FaceSupport Pipe) Galvanized

ProductNumber Fits Face Support PipeB2240 Support Angle for 2-7/8" (73 mm) OD pipe

B2262 Support Angle for 4-1/2" (114 mm) OD pipe

Inverted PipeHead arm

All covers hingeopen for easyaccess

5' (1.524 m)

Bridge Channel CoverBridge Channel Covers are designed for use with invertedBridge Channels. Covers provide protection from ice,wind, and other elements. Covers are formed 11-gauge (3mm) steel and are hot-dip galvanized after fabrication. AllCovers are 5' (1.524 m) long. If cutting is required toaccommodate unusual lengths, the B186 Touch-up Kit orB364 Touch-up Spray (page 13.04) is recommended fortreating raw metal edges.Mounting hardware is included.

ProductNumber DescriptionB1220 Cover for 1' (305 mm) wide bridge

B1221 Cover for 2' (610 mm) wide bridge

B1222 Cover for 3' (914 mm) wide bridge

Covered 90° Corner Channelfor Inverted BridgeThe Covered 90° Corner Channel provides a protected90° bend for an inverted covered bridge. The tray of theCorner Channel allows for the bending radius of 2' (610mm) for transmission line and is furnished with tabs atboth ends for bolting to the connecting inverted BridgeChannels. The hinged cover protects from ice and windand is compatible with the Bridge Channel Covers. Boththe tray and the cover are formed with 11-guage (3 mm)steel that is hot-dipped galvanized after fabrication.

2' 4-3/16"(716 mm)

2' 4-3/16"(716 mm)

1' (305 mm)

A

A

CornerChannel

CoverB501 BridgeChannel (ref)

ProductNumber DescriptionB1718 Covered 90° Corner Channel

Section A-A

3' (914 mm)

2' (610 mm)

1'(305 mm)

B515 Corner Clip Angle

Monopole

B501 or B502Bridge Channel

B515 Support Angle

2 7/8" (73 mm) or 4 1/2" (114 mm) ODFace-Support Pipe (p. 9.02)

B501 or B502Bridge Channel