COMPACT VENTILATION UNIT LG 3200
Systematic ventilation.
COMFORT VENTILATION
EU Regulation 1253/2014
EN13141-7:2010
for residential buildingsfor non-residential buildings
ErP2018
COMPACT VENTILATION UNIT LG 3200 PAGE 2
Product description
Area of application
The LG 3200 comfort ventilation unit with passive house certificate consists of a compact, thermal bridge-free and 50 mm heat insulated housing made of galvanised steel sheeting, external powder coating in RAL 9010, a highly efficient heat recovery system with air/air counter-flow heat exchanger, an
automatic 100% bypass with energy-saving radial fans in the latest EC motor technology with optional CO
2 sensor
module for demand-based comfort ventilation operation, filter ODA ISO ePM1 55% in the outdoor air and filter ETA ISO Coarse 90% in the extract air, internally wired control electronics.
Optional enhancements such as constant volume flow regulation, constant pressure regulation or our enhanced, efficiency-optimised fan optimiser regulation complement the extensive basic functions. Compact ventilation unit suitable for free-standing installation in frost-free rooms.
The LG 3200 and LG 3200 S comfort ventilation unit is used as a central unit for up to 40 apartments, schools, doctor's surgeries, offices and similar
applications and for the controlled mechanical aeration and ventilation of larger apartment buildings. The range of use extends fundamentally to residential
buildings in passive or low-energy construction, with an adjustable air volume flow up to approx. 3400 m³/h.
1 Supply air 300 x 800 mm 2 Extract air 300 x 800 mm 3 Outdoor air 300 x 800 mm 4 Exhaust air 300 x 800 mm 5 Counterflow heat exchanger 6 Exhaust air fan 7 Supply air fan 8 Control system 9 Bypass damper with actuator 10 Extract air filter 11 outdoor air filter 12 Condensate tray 13 Cable inlets 1 x M32, 2 x M20, 10 x M16 14 Electric preheater battery (optional),
with an optional heat insulation 15 Electric reheater battery (optional) 16 Outdoor air shut-off valve (optional) 17 Exhaust air shut-off valve (optional) 18 Pre-filter box for electric heating
radiators (optional, recommended by the manufacturer)
19 Height adjustable feet 20 Condensate drain 21 Flexible connections top
Optional: Hot water preheater battery and hot water reheater battery for duct installation
Figure: LG 3200 R (right-hand version)The PI-HMI operating unit is delivered separately.
Layout sketch LG 3200 (free-standing installation)Air line connection: outdoor air / exhaust air / supply air / extract air (W x H) 300 x 800 mmAir line connection: with connecting profile P30
1652
20401980
800
805
170
1370
125
480685
300
5911
1614
8
10
7
1920
12
6
4 3 13 1
983,
4
300
51,2121
30051,2
17
2
21 2121
121
300
490
2120
15
21
18
245
580
450
1652
20401980
800
805
170
1370
125
480685
300
5911
1614
8
10
7
1920
12
6
4 3 13 1
983,
4
300
51,2121
30051,2
17
2
21 2121
121
300
490
2120
15
21
18
245
580
450
COMPACT VENTILATION UNIT LG 3200 PAGE 3
Layout sketch LG 3200 S (free-standing installation)Air line connection: outdoor air / extract air (W x H) 300 x 800 mmAir line connection: exhaust air / supply air (W x H) 486 x 786 mmAir line connection: with connecting profile P30
1 Supply air 486 x 786 mm 2 Extract air 300 x 800 mm 3 Outdoor air 300 x 800 mm 4 Exhaust air 486 x 786 mm 5 Counterflow heat exchanger 6 Exhaust air fan 7 Supply air fan 8 Control system 9 Bypass damper with actuator 10 Extract air filter 11 Outdoor air filter 12 Condensate pan 13 Cable inlets 1 x M32, 2 x M20, 10 x M16 14 Electric preheater battery (optional),
with an optional heat insulation 15 Electric reheater battery (optional) 16 Outdoor air shut-off valve (optional) 17 Exhaust air shut-off valve (optional) 18 Pre-filter box for electric heating
radiators (optional, recommended by the manufacturer)
19 Height adjustable feet 20 Condensate drain 21 Flexible connections top 22 Flexible connections side
Optional: Hot water preheater battery and hot water reheater battery for duct installation
Figure: LG 3200 SR (right-hand version)The PI-HMI operating unit is delivered separately.
1652
20401980
580
486
786
2120
805
170
1370
480685
475 300 490 300 475
2550
59
17
11
1416 8 10
15
7
1920
12
6
4
3 13 2 1
983,
4
21
21
22
22
18
12524
5
450
1652
20401980
580
486
786
2120
805
170
1370
480685
475 300 490 300 475
2550
59
17
11
1416 8 10
15
7
1920
12
6
4
3 13 2 1
983,
4
21
21
22
22
18
12524
5
450
COMPACT VENTILATION UNIT LG 3200 PAGE 4
The compact ventilation unit LG 3200 is available in several different versions:• Right or left-hand depending on the
position of the supply air connection• With side exhaust air and supply air
connecting pieces, type LG 3200 S
• With or without electrical preheater battery built up to the compact ventilation unit for frost protection of the heat exchanger
• With or without electrical reheater battery built up to the compact ventilation unit
The unit may also be optionally equipped with the following additional functions:• See optional accessories
Versions
LG 3200 version Left-hand version Right-hand version
Item no. without preheater and reheater battery 08LG3200-L 08LG3200-R
Item no. with a built up electrical preheater battery
08LG3200-L-V 08LG3200-R-V
Item no. with a built up electrical reheater battery
08LG3200-L-N 08LG3200-R-N
Item no. with a built up electrical pre and reheater battery
08LG3200-L-V-N 08LG3200-R-V-N
Item no. optional with hot water reheater battery for external assembly in a horizontal duct (type dep. on heating output requirement)
40LG080200 or 40LG080260
40LG080200 or 40LG080260
Item no. shut-off valve with motor LM 24 A
08AKE800300 08AKE800300
LG3200L
LG3200R
LG 3200 S version Left-hand version Right-hand version
Item no. without preheater and reheater battery 08LG3200-SL 08LG3200-SR
Item no. with a built up electrical preheater battery
08LG3200-SL-V 08LG3200-SR-V
Item no. with a built up electrical reheater battery
08LG3200-SL-N 08LG3200-SR-N
Item no. with a built up electrical pre and reheater battery
08LG3200-SL-V-N 08LG3200-SR-V-N
Item no. optional with hot water reheater battery for external assembly in a horizontal duct (type dep. on heating output requirement)
40LG080200 or 40LG080260
40LG080200 or 40LG080260
Item no. shut-off valve with motor LM 24 A
08AKE800300 + 08AKE786486 08AKE800300 + 08AKE786486 LG3200SL LG3200SR
12
3
4
14
3 2
14
3
2
32 1
4
1 Outdoor air
2 Supply air
3 Extract air
4 Exhaust air
1 Outdoor air
2 Supply air
3 Extract air
4 Exhaust air
COMPACT VENTILATION UNIT LG 3200 PAGE 5
Technical specificationsThe technical specifications were measured by Lucerne Polytechnic – Engineering & Architecture, Centre for Integral Building Technology.
COMFORT VENTILATION UNIT
Dimensions: (W x H x D) 2040 x 1655 x 1000 mmHousing in double-shell construction made of galvanized sheet steel, 50 mm heat insulationAir line connections LG 1400: outdoor air / exhaust air / supply air / extract air (W x H) 300 x 800 mm Air line connections LG 1400 S: outdoor air / exctract air (W x H) 300 x 800 mm and exhaust air / supply air (W x H) 486 x 786 mm Connection profile: P30Condensate connection with syphon and mechanical sealing device ø 40 mm at the bottom Electrical connection without preheater battery: 400 V/50 Hz/20 AElectrical connection with preheater battery: 400 V/50 Hz/40 ADegree of protection: IP 20Permitted ambient temperature for the unit: + 5° C to + 40° CWeight without accessories: approx. 390 kg
FANS (factory setting)
Air volume flow:Fan speed/low speed: 1600 m³/h Fan speed/high speed: 3000 m³/h
Air volume flow setting range: 900 – 3400 m³/hStop operating condition: 6.5 W
The characteristic curves shown are valid for the device design with an outdoor air filter of quality class F7 (EN 779), extract air filter of quality class G4 (EN 779).
CHARACTERISTIC EXTERNAL PRESSURE INCREASE - AIR VOLUME FLOW (for volume flow constant function)
The characteristic curves provide the external pressure (p
ext.) available for the
duct system.
TOTAL OUTPUT
The SFP values shown [Wh/m³] take into account power consumption for both fans for supply air and exhaust air as well as the power consumption of the control system.
DEGREE OF RECOVERY IN ACCORDANCE WITH EN 308
(where extract air is 21 °C / 40% r.H.)
PRESSURE-VOLUME FLOW CHARACTERISTIC CURVE FOR LG 3200 WITH V CONSTANT FUNCTION
PRESSURE-VOLUME FLOW CHARACTERISTIC CURVE FOR LG 3200 WITHOUT V CONSTANT FUNCTION
PASSIVE HOUSE CERTIFIED IN ACCORDANCE WITH PHI CRITERIA
Non-residential building:Area of application: 950 to 1800 m³/h at an external pressure of 259 PaHousing seal-tightness: external leakage 0,3 %, internal leakage 0,9 %Heat recovery rate: ŋ
HR, eff = 84 %
Comfort criterion: Tsupply air= +16,5 °C bei Toutdoor air= -10 °CFlow efficiency: ŋ
el = 0,41 Wh/m³
Residential building:Area of application: 950 to 2200 m³/h at an external pressure of 236 PaHousing seal-tightness: external leakage 0,3 %, internal leakage 0,9 %Heat recovery rate: ŋ
HR, eff = 82 %
Comfort criterion: Tsupply air= +16,5 °C bei Toutdoor air= -10 °CFlow efficiency: ŋ
el = 0,41 Wh/m³
CERTIFIED ACCORDING TO EN13141-7:2010
Thermodynamic tests at air volume flow rates 908/2120/3075 m³/h (at outdoor-temp. +7 °C (+1 x Ref. +2 °C), at extract air temp.+20 °C): Extract air side = 76 %/75 %/70 % and supply air side = 88 %/87 %/88 %Flow efficiency: ŋel = 0,19/0,28/0,45 Wh/m³
900
800
700
600
500
400
300
200
100
500 1000 1500 2000 2500 3000 3500 4000
ext
. pre
ssur
e in
crea
se [
Pa]
Air volume flow [m3/h]
Speed 3000 m3/hSpeed 2400 m3/hSpeed 1600 m3/hSpeed 1000 m3/h
0.70 Wh/m3
0.60 Wh/m3
0.50 Wh/m3
0.40 Wh/m3
0.30 Wh/m3
900
800
700
600
500
400
300
200
100
500 1000 1500 2000 2500 3000 3500 4000
ext
. pre
ssur
e in
crea
se [
Pa]
Air volume flow [m3/h]
Speed 10 VSpeed 8 VSpeed 6 VSpeed 4 V
0.70 Wh/m3
0.60 Wh/m3
0.50 Wh/m3
0.40 Wh/m3
0.30 Wh/m3
92
90
88
86
84
82
80
800 1200 1600 2000 2400 2800 3200
Eff
icie
ncy
leve
l [%
]
Air volume flow [m3/h]
TABL
= + 21 °C and + 23 °C for 40 % r.H. - 10 °CT
AUL= - 6 °C
- 3 °C
ŋ = T
ZUL - T
AUL
T
ABL - T
AUL
COMPACT VENTILATION UNIT LG 3200 PAGE 6
SOUND DATA
(with an external pressure increase of 100/200 Pa)
Technical specifications
Volu
me
flow
V
[m³/
h]pt = 100 pa pt = 200 pa
Lw [dB/Oct]
L W [d
B]
L WA [d
B(A
)]
Lw [dB/Oct]
L W [d
B]
L WA [d
B(A
)]
63 H
z
125
Hz
250
Hz
500
Hz
1000
Hz
2000
Hz
4000
Hz
8000
Hz
63 H
z
125
Hz
250
Hz
500
Hz
1000
Hz
2000
Hz
4000
Hz
8000
Hz
Supply air connecting pieces
1600 34 43 58 61 67 64 57 44 70 70 40 49 64 67 73 70 63 50 76 76
2200 42 49 68 69 74 71 64 53 77 77 48 55 74 75 80 77 70 59 83 83
2400 45 51 71 72 76 73 66 56 80 79 51 57 77 78 82 79 72 62 86 85
3000 53 57 82 79 84 80 74 65 88 87 59 63 88 85 90 86 80 71 94 93
3200 56 59 85 82 86 82 76 68 90 89 62 65 91 88 92 88 82 74 96 95
outdoor air connecting pieces
1600 25 37 49 46 44 38 22 11 52 48 31 43 55 52 50 44 28 17 58 54
2200 30 42 55 52 50 44 30 19 58 54 36 48 61 58 56 50 36 25 64 60
2400 32 44 57 54 52 46 33 21 60 56 38 50 63 60 58 52 39 27 66 62
3000 37 49 63 60 58 52 40 25 66 62 43 55 69 66 64 58 46 31 72 68
3200 39 51 65 62 60 54 43 27 68 64 45 57 71 68 66 60 49 33 74 70
Extract air connecting pieces
1600 24 40 57 48 43 37 22 15 57 51 30 46 63 54 49 43 28 21 63 57
2200 31 45 62 54 49 43 27 14 63 56 37 51 68 60 55 49 33 20 69 62
2400 33 47 64 56 51 45 29 14 65 58 39 53 70 62 57 51 35 20 71 64
3000 40 52 69 62 57 51 34 13 70 64 46 58 75 68 63 57 40 19 76 70
3200 42 54 71 64 59 53 36 13 72 66 48 60 77 70 65 59 42 19 78 72
Exhaust air connecting pieces
1600 34 43 71 60 67 65 56 47 73 71 40 49 77 66 73 71 62 53 79 77
2200 42 49 76 68 74 71 62 54 79 77 48 55 82 74 80 77 68 60 85 83
2400 45 51 78 71 76 73 64 56 81 79 51 57 84 77 82 79 70 62 87 85
3000 52 57 83 79 83 79 70 63 88 86 58 63 89 85 89 85 76 69 94 92
3200 55 59 85 82 85 81 72 65 90 88 61 65 91 88 91 87 78 71 96 94
Housing
1600 32 45 49 44 44 40 36 10 52 48 38 51 55 50 50 46 42 16 58 54
2200 39 49 58 49 50 47 44 19 60 55 45 55 64 55 56 53 50 25 66 61
2400 41 50 61 51 52 49 47 22 63 58 47 56 67 57 58 55 53 28 69 64
3000 48 54 70 56 58 57 54 31 71 65 54 60 76 62 64 63 60 37 77 71
3200 50 55 73 58 60 59 57 34 74 68 56 61 79 64 66 65 63 40 80 74
Remark: Tolerances ± 2 dB for acoustic data
COMPACT VENTILATION UNIT LG 3200 PAGE 7
CONTROL UNIT
The ventilation units come equipped as standard with an inte-grated control and regulation system. The settings on the venti-lation unit are carried out using an integrated web server, limit-ed settings can also be carried out via the colour touch display PI-HMI. In addition, the current operating status conditions and system values such as operating type, fan speed, temperatures, etc. are displayed on the control system. Signal lamps display the operation (green) and faults (flashing red) including as plain text displays. Auto matic or manual mode can be selected.
DIMENSIONS
Item Dimensions Item Number
PI-HMI with Connec-ting cable, length 1 m and double-sided RJ12 connector
(W x H x D) 80 x 121 x 42 mm
included in the delivery
OPTIONAL: BUILDING AUTOMATION – NETWORKING OPTIONSThe Pichler-Air2-System offers multiple networking options as integration into a higher level building automation system.• Integratred webserver• Modbus RTU• Modbus TCP/IP• BACnet• KNX-GatewayThe corresponding bus connection is activated/parameterized at the factory according to the customer's order.
SIGNAL EXCHANGE• Low rpm input• High rpm input• Error message Level A (shutdown of the system)• External start input• External stop input (optional)• External fire alarm input (optional)• Operational
FUNCTIONS OF THE PICHLER CONTROL• Preheater battery, electric or PWW• Reheater battery, electric or PWW• Cooling battery PKW / DX• Air ventilation and humidification• Continuously controlled heat/"cold" recovery
via the counterflow heat exchanger and bypass• Air filter monitoring with pressure sensors
(static or dynamic)• External air compensation• Summer nights cooling (only for weekly program)• Weekly program
CONTROL METHODS
• Constant volume flow control• Constant pressure control (optional)• PICHLER System Optimiser (optional)• Air quality control CO
2 (sensor required)
• Air quality control VOC VOC (sensor required)• External control signal 0-10 V (optional)
Operation
Colour touch display PI-HMI Optimized operation with the Pichler-System-Optimizer
COMPACT VENTILATION UNIT LG 3200 PAGE 8
Integrated webserver plant status
Function Description Standard Optional*
Ventilation control method:
Constant volume flow control
Constant pressure control
PICHLER System Optimiser
Air quality control CO2
Air quality control VOC
External control signal 0-10 V
Temperature control method
Constant supply air temperature
Constant extract air temperature
Ancillary functions External air compensation
Summer nights cooling (only for weekly program)
Possible heating and cooling components
External electric pre-heater battery
Control of an external E-re-heater battery
DX cooler controller
Control of a water pre-heater battery
Control of a water re-heater battery
Control of a water cooling battery
Control of a water combi battery
Communication Integrated web server
Modbus TCP/IP
Modbus RTU (not possible with System Optimiser!)
BACnet
KNX-Gateway
Signal exchange hardware
Analog input for VOC/CO2 sensor (on terminal)
Low rpm input
High rpm input
Shut-off valves 2x Belimo LM24A control (on terminal)
Error message Level A (floating max. 30V / 3A)
Error message Level B (Maintenance message)
External start input (inverted)
External stop input (on terminal)
External fire alarm input (on terminal)
Operational (floating max. 30V / 3A)
* The options must be specified in the order and will attract additional costs!
Functional overview
COMPACT VENTILATION UNIT LG 3200 PAGE 9
SPARE FILTER
Will ensure perfect hygiene and air quality given regular replacement, also proper functionality and efficient operation of the equipment.
Item Item number
Filter ODA ISO ePM1 55% (outdoor air)
40LG050170 (standard)
Filter ETA ISO Coarse 90% (extract air)
40LG050180 (standard)
Filter ODA ISO ePM1 85% (outdoor air)
50LG050190
Filter ETA ISO ePM10 70% (extract air)
40LG050200
DEMAND-ORIENTED VENTILATION CONTROL
CO2 or VOC sensors for demand-oriented ventilation control.
The ventilation unit will automatically increase or reduce the air volumes depending on the quality of the air in the room. The sensors are designed for flush and surface mounting.Colour: whiteDimensions: W x H x D = 85 x 85 x 35 mmAmbient temperature: 10-50°CMeasuring range: 0-2000 ppmSensor supply voltage: 24V AC/DCControl signal: 0-10 V
Item Item number
CO2 sensor 07RCO248330
Needs-based operation via the CO2 or VOC sensor module only functions in automatic mode. The assignment of the fan speeds, the ppm and humidity values can be changed via the integrated web server.
BUTTERFLY VALVES
Frames and galvanised slats, with mounted actuator LM24A-F.LG 3200: 2 x 08AKE800300LG 3200S: 1 x AKE800300 + 1 x AKE786486
Item Dimensions Item number
Butterfly valve for devices with overhead connections with a flan-ge: P30, actuator LM24A-F
Connection: W x H = 800 x 300 mm
08AKE800300
Butterfly valve for devices with connections with a flange, which are positioned at the side: P30, actuator LM24A-F
Connection: W x H = 786 x 486 mm
08AKE786486
CANVAS CONNECTION
Made of laminated and highly tear-resistant fabric and with double-sided flanges made of galvanized sheet steel. P30 flange. Elongated length : 150 mmLG 3200: 4 x 08STELG3200LG 3200S: 2 x 08STELG3200 + 2 x 08STELG3200S
Item Dimensions Item number
Canvas connection for devices with overhead connections
Connection: W x H = 800 x 300 mm
08STELG3200
Canvas connections for devices with connections that are positioned at the side
Connection: W x H = 786 x 486 mm
08STELG3200S
ELECTRIC PREHEATING RADIATOR
Can be connected to the external air connection pipe of the comfort ventilation device. Electric preheating module with in-finitely variable control 0 to 10 V as freeze protection for the counter current heat exchanger.Power: 12 kW We strongly recommend the use of an additional pre-filter (item number 08VFBG4800300).
Item Item number
Item no. with electric preheating radiator for right-hand version
08LG3200-R-V, SR-V
Item no. with electric preheating radiator for left-hand version
08LG3200-L-V, SL-V
Item no. with electric preheating and reheating radiator for right-hand version
08LG3200-R-V-N, SR-V-N
Item no. with electric preheating and reheating radiatorfor left-hand version
08LG3200-L-V-N, SL-V-N
CO2 sensor
Accessories
COMPACT VENTILATION UNIT LG 3200 PAGE 10
PRE-FILTER BOX FOR ELECTRIC HEATING COILS
The external filter box is to be used as a pre-filter for devices with electric preheating coils. Filter class ISO Coarse 70%. The pre-filter box must be insulated on site and can be installed directly on the heating radiator.
DIMENSIONS
Item Dimensions Item number
Pre-filter box for LG 3200, with pre-filter mat ISO Coarse 70%, galvanised
(W x H x D) 800 x 300 x 200 mm
08VFBG4800300
Spare filter mat ISO Coarse 70% for LG 3200
(W x H) 795 x 283 mm
08EFG4283795
FILTER AND WARM WATER PREHEATING RADIATOR BOX
Insulated enclosure, consisting of a filter unit and a hot water pre-heating battery. The outside air filter of the ventilation unit is inserted into the filter and hot water pre-heating battery box. Only in connection with an additional duct temperature sensor (item number 40LG0400011A) and a three-way motor control valve (Art. Nr. 07R3..LR24ASR).Air volume: 3200 m³/hAir inlet temperature: -16 °CAir outlet temperature: 0 °CMedium: 55/45 °CGlycol fraction: 30%Power: 17,51 kW
Item Dimensions Item number
Filter and warm water preheating radiator box, isolated
(W x H x D) 800 x 695 x 960 mm
08HBOXLG3200
Filter and warm water preheating radiator box
Pre-filter box for protecting the electric preheating coil
0,27 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm
LG3200 Vorfilterbox Filterauflage006_VFB_A_LG32002006
0,425 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm
LG3200 Vorfilterbox Filter Deckel005_VFB_A_LG32001005
0,535 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm
LG3200 Vorfilterbox Filter 2004_VFB_A_LG32001004
0,517 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm
LG3200 Vorfilterbox Filter 1003_VFB_A_LG32001003
1,864 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm
LG3200 Vorfilterbox Rahmen 2002_VFB_A_LG32001002
2,126 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm
LG3200 Vorfilterbox Rahmen 1001_VFB_A_LG32001001
0 kgDichtband Dichtband 3x15 L=173,240LG060170270 kgDichtband Dichtband 3x15 L=271,840LG06017026
0,005 kgCr(III) Linsenschraube M6x16 BN4825 ecosyn-fix verzinkt
40LG03213045
0 kgStahl, weich, unlegiert EINNIETMUTTER M6 mit Rändelung Stahl verz.
40LG03024044
0,064 kgFiltermatte G4 LG3200 Vorfilterbox Filter14FILTERMATTEEU40,23 m²
2
0,068 kgStahlbl. verz. 1,5 mm ECKWINKEL C3012JKSBPW3081
StücklisteGewichtMATERIALZULIEFERERBenennungArtikel Nr.Stk.Pos
A
123
C
E
1
D
23
B
7
A
EINBAUVORSCHLAG
C
4
4567
E
D
56
B
Benennung:
Datum:Gezeichnet:
Kunde:Blatt Nr.
Dateiname:Maßstab:DIESER PLANUNGSVORSCHLAG IST NUR IN VERBINDUNG MIT UNSEREN VORBEMERKUNGEN GÜLTIG!
BEHÖRDENAUFLAGEN SIND BAUSEITIG ABZUKLÄREN UND UNBEDINGT EINZUHALTEN!
NATURMASZE UND HÖHENKOTEN SIND ZU ÜBERPRÜFEN!UNSTIMMIGKEITEN SIND MIT DEM PLANVERFASSER ABZUKLÄREN!ALLE MASZE SIND VOR DER AUSFÜHRUNG VOM KUNDEN ZU PRÜFEN!
Geprüft:Diese Zeichnung stellt nach den Urh. Ges § 24 unser geistiges Eigentum dar und darf ohne unsere ausdrückliche Zustimmung weder Konkurrenzfirmen, noch dritten Personen weitergegeben werden. Die unbefugte bzw. bestimmungswidrige Verwendung dieser Unterlagen ist nicht gestattet und wird gerichtlich verfolgt.
LG3200 Vorfilterbox
LG3200 Vorfilterbox.idw
19.05.2017
MTreiber
Prüfer:
1 von 1 1 : 5
Freimaßtoleranz nach DIN ISO 2768-mHZeichnungsstatus: Freigegeben
Revision:
A
Gespeichert: 12.10.2017 07:11:34
Bauvorhaben: Gewicht:6,633 kg
Auftragsnummer:
J. Pichler Gesellschaft m.b.H 9021 Klagenfurt, Karlweg 5, Postfach 32T +43 (0)46332769, F +43 (0)463 [email protected], www.pichlerluft.at
AMessner08.06.2017Zeichnungsnummer:
000_VFB_A_LG3200Artikelnummer.08VFBG4800300
005
2
0011
006002
5
4
200
359,6
859,6
800
300
004
7
6
7
003
0,27 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm
LG3200 Vorfilterbox Filterauflage006_VFB_A_LG32002006
0,425 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm
LG3200 Vorfilterbox Filter Deckel005_VFB_A_LG32001005
0,535 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm
LG3200 Vorfilterbox Filter 2004_VFB_A_LG32001004
0,517 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm
LG3200 Vorfilterbox Filter 1003_VFB_A_LG32001003
1,864 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm
LG3200 Vorfilterbox Rahmen 2002_VFB_A_LG32001002
2,126 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm
LG3200 Vorfilterbox Rahmen 1001_VFB_A_LG32001001
0 kgDichtband Dichtband 3x15 L=173,240LG060170270 kgDichtband Dichtband 3x15 L=271,840LG06017026
0,005 kgCr(III) Linsenschraube M6x16 BN4825 ecosyn-fix verzinkt
40LG03213045
0 kgStahl, weich, unlegiert EINNIETMUTTER M6 mit Rändelung Stahl verz.
40LG03024044
0,064 kgFiltermatte G4 LG3200 Vorfilterbox Filter14FILTERMATTEEU40,23 m²
2
0,068 kgStahlbl. verz. 1,5 mm ECKWINKEL C3012JKSBPW3081
StücklisteGewichtMATERIALZULIEFERERBenennungArtikel Nr.Stk.Pos
A
123
C
E
1
D
23
B
7
A
EINBAUVORSCHLAG
C
4
4567
E
D
56
B
Benennung:
Datum:Gezeichnet:
Kunde:Blatt Nr.
Dateiname:Maßstab:DIESER PLANUNGSVORSCHLAG IST NUR IN VERBINDUNG MIT UNSEREN VORBEMERKUNGEN GÜLTIG!
BEHÖRDENAUFLAGEN SIND BAUSEITIG ABZUKLÄREN UND UNBEDINGT EINZUHALTEN!
NATURMASZE UND HÖHENKOTEN SIND ZU ÜBERPRÜFEN!UNSTIMMIGKEITEN SIND MIT DEM PLANVERFASSER ABZUKLÄREN!ALLE MASZE SIND VOR DER AUSFÜHRUNG VOM KUNDEN ZU PRÜFEN!
Geprüft:Diese Zeichnung stellt nach den Urh. Ges § 24 unser geistiges Eigentum dar und darf ohne unsere ausdrückliche Zustimmung weder Konkurrenzfirmen, noch dritten Personen weitergegeben werden. Die unbefugte bzw. bestimmungswidrige Verwendung dieser Unterlagen ist nicht gestattet und wird gerichtlich verfolgt.
LG3200 Vorfilterbox
LG3200 Vorfilterbox.idw
19.05.2017
MTreiber
Prüfer:
1 von 1 1 : 5
Freimaßtoleranz nach DIN ISO 2768-mHZeichnungsstatus: Freigegeben
Revision:
A
Gespeichert: 12.10.2017 07:11:34
Bauvorhaben: Gewicht:6,633 kg
Auftragsnummer:
J. Pichler Gesellschaft m.b.H 9021 Klagenfurt, Karlweg 5, Postfach 32T +43 (0)46332769, F +43 (0)463 [email protected], www.pichlerluft.at
AMessner08.06.2017Zeichnungsnummer:
000_VFB_A_LG3200Artikelnummer.08VFBG4800300
005
2
0011
006002
5
4
200
359,6
859,6
800
300
004
7
6
7
003
80096
0
750
595
695
800
960
750
595
695
800
960
750
595
695
revision
COMPACT VENTILATION UNIT LG 3200 PAGE 11
ELECTRIC REHEATING RADIATOR
Can be connected to the supply air connection pipe of the comfort ventilation unit. Electric re-heating module with infi-nitely variable control of 0 to 10V for re-heating the supply air.Power: 4 kW
Item Item number
Item no. with electric reheating radiator for right-hand version
08LG3200-R-N, SR-N
Item no. with electric reheating radiator for left-hand version
08LG3200-L-N, SL-N
Item no. with electric preheating and reheating radiator for right-hand version
08LG3200-R-V-N, SR-V-N
Item no. with electric preheating and reheating radiatorfor left-hand version
08LG3200-L-V-N, SL-V-N
EXTERNAL WARM WATER REHEATING RADIATOR
For reheating the supply air for duct installation (W x H = 800 x 500 mm). Only in connection with an additional duct temperature sensor (item number 40LG0400011A) and a three-way motor control valve (item number 07R3..LR24ASR).Air volume: 3400 m³/hMedium: 60/40 °CDuct connection: W x H = 800 x 500 mmDimensions: W x H x D = 838 x 538 x 450 mm
Number of pipe rows Power Item number
2 PCS approx. 15 kW 40LG080200
3 PCS approx. 20 kW 40LG080260
EXTERNAL COLD WATER COIL
For cooling the supply air for duct installation (W x H = 800 x 500 mm), with integrated condensate drain, housing uninsulated. Only in connection with an additional duct temperature sensor (item number 40LG0400011A) and a three-way motor control valve (item number 07R3..LR24ASR).
Air volume: 3400 m³/hMedium: 7/12 °CNumber of pipe rows: 3 PCSPower: approx. 17 kWDuct connection: W x H = 800 x 500 mmDimensions: W x H x D = 928 x 530 x 395 mm
Item Item number
Cold water coil 40LG080210
Droplet separator for cold water coils
01DE8050
EXTERNAL SUPPLY AIR TEMPERATURE SENSOR
Item Item number
Duct temperature sensor – PT1000 sensor with flange, cable length 5 m
40LG0400011A
ROOM TEMPERATURE SENSOR
Item Item number
Room temperature sensor – PT1000 sensor in the surface-mounted housing
40LG041330
THREE-WAY MOTOR CONTROL VALVE
Three-way control ball valve for the continuous closed-loop con-trol of cold and warm water with a mounted closed-loop control actuator.Belimo drive: LR 24ASRDrive voltage: 24V AC/DCControl signal: 0-10V DCControl ball valve: R3015Mounting position: optional
KVS value Item number
0,63 m³/h 07R309LR24ASR
1,0 m³/h 07R310LR24ASR
1,6 m³/h 07R311LR24ASR
2,5 m³/ 07R312LR24ASR
Warm water reheating radiator Cold water coil Duct temperature sensor
COMPACT VENTILATION UNIT LG 3200 PAGE 12
Data in accordance with EU Regulations 1253-2014
Download from: www.pichlerluft.at
Product fiche System Ventech LG 3200
Seite 1 von 2
Model IDType Two-way ventilation plant for non-residential useDrive type
Internal specific fan power SVLint 1153 [W/(m³/s)]
Thermal transmission ηt_nwla 86,00% [-]
Enclosure sound power level LWA 72 [dB(A)]
1 [m³/s]
3600 [m³/h]actual electrical input power Pel,ges 1,69 [kW]
Airflow speed vnom 1,96 [m/s]
Nominal outside pressure ZUL Δps,ext ZUL 94 [Pa]
Nominal outside pressure ABL Δps,ext ABL 94 [Pa]
Internal pressure drop across ventilation components, ZUL Δps,int ZUL 380 [Pa]
Internal pressure drop across ventilation components, ABL Δps,int ABL 313 [Pa]
Internal pressure drop across non-ventilation components, ZUL Δps,add ZUL 0 [Pa]
Internal pressure drop across non-ventilation components, ABL Δps,add ABL 0 [Pa]
Fan efficiency, ZUL, at nominal external pressure loss and internal pressure loss across ventilation components
ηfan ZUL 60,89 [%]
Fan efficiency, ABL, at nominal external pressure loss and internal pressure loss across ventilation components
ηfan ABL 59,23 [%]
External air leakage (at ±400 Pa) < 1 [%]Internal air leakage (at 250 Pa) < 1 [%]Energy class, ZUL-filter (F7) ** 2100,4 [kWh]Energy class, ABL-filter (G4) ** 1294,1 [kWh]
PICHLER System Ventech LG 3200
Speed control
Other heat recovery system counterflowheat exchanger
Produktdatenblatt PICHLER System Ventech LG 1400
Type of heat recovery *
Nominal airflow qnom
Point 1
Area of application
The apparatus complies with the Eco-design Directive inside the cross-hatched areaThe diagram applies to the reference coNominal air flow [m³/h]ext. pressure [Pa]Point 1Point 2Point 4Point 5Point 3nfiguration (fans, filters, heat
exchangers) without assemblies not for ventilation (e.g. heating coils, louvre flaps, etc.). Additional loss of pressure must be taken into account when installing assemblies not for ventilation.
Page 1 of 2
ZUL = supply airABL = extract air
COMPACT VENTILATION UNIT LG 3200 PAGE 13
Download from: www.pichlerluft.at
Seite 2 von 2
Internal specific fan power SVLint 1177 [W/(m³/s)]
Thermal transmission ηt_nwla 86,00% [-]
Enclosure sound power level LWA 68 [dB(A)]
1 [m³/s]3600 [m³/h]
Nominal external pressure, ZUL Δps,ext ZUL 50 [Pa]
Nominal external pressure, ABL Δps,ext ABL 50 [Pa]
Internal specific fan power SVLint 972 [W/(m³/s)]
Thermal transmission ηt_nwla 86,50% [-]
Enclosure sound power level LWA 73 [dB(A)]
0,917 [m³/s]
2200 [m³/h]Nominal external pressure, ZUL Δps,ext ZUL 272 [Pa]
Nominal external pressure, ABL Δps,ext ABL 272 [Pa]
Internal specific fan power SVLint 291 [W/(m³/s)]
Thermal transmission ηt_nwla 92,00% [-]
Enclosure sound power level LWA 74 [dB(A)]
0,236 [m³/s]850 [m³/h]
Nominal external pressure, ZUL Δps,ext ZUL 829 [Pa]
Nominal external pressure, ABL Δps,ext ABL 829 [Pa]
Internal specific fan power SVLint 267 [W/(m³/s)]
Thermal transmission ηt_nwla 92,00% [-]Enclosure sound power level LWA 65 [dB(A)]
0,236 [m³/s]
850 [m³/h]Nominal outside pressure ZUL Δps,ext ZUL 50 [Pa]
Nominal outside pressure ABL Δps,ext ABL 50 [Pa]
Filter class Final pressuredifference
G1-G4 150 Pa
M5-F7 200 Pa
F8 - F9 300 Pa
Nominal airflow qnom
Nominal airflow qnom
Nominal airflow qnom
Nominal airflow qnom
* Types of heat recovery:
none
Fluid circulation heat exchanger
other heat recovery system
The ventilation unit complies with Eco-design Directive (EU Regulation 1253/2014) as required for 2018.
Visual filter warningThe ventilation unit has a visual warning to replace the filter. An error message will be displayed on the control panel when the set pressure difference is exceeded.WARNING: The plant will not work efficiently unless the filter is replaced regularly, causing power consumption to increase.
DisposalEquipment that is no longer functional must be uninstalled by a specialist firm and properly disposed of at a suitable facility. The Electrical and Electronic Equipment Act (EAG-VO), implementing Community law Directives 202/95/EC (RoHS) and 2002/96/EC (WEEE Directive) applies.
Point 2
Point 3
Point 4
Point 5
** The energy class is calculated based on the annual operating hours (8760 h) and average pressure loss (see table below for final pressure loss pursuant to ÖNORM EN 13053).
Max. pressure drop across filter pursuant to ÖNORM EN 13053:
Information based on the current state of knowledge of EU Regulation 1253/2014 Download from: www.pichlerluft.at
Page 2 of 2
Systematic ventilation.
J. PICHLERGesellschaft m.b.H.
ÖSTERREICH9021 KLAGENFURT AM WÖRTHERSEEKarlweg 5T +43 (0)463 32769F +43 (0)463 37548
ÖSTERREICH1100 WIENDoerenkampgasse 5T +43 (0)1 6880988F +43 (0)1 6880988-13
Sales offices in Slovenia and Serbia. Sales partners in Germany, Switzerland and Italy.
Responsible for the content: J. Pichler Gesellschaft m.b.H.Photos: Archiv J. Pichler Gesellschaft m.b.H. | Text: J. Pichler Gesellschaft m.b.H. All rights reserved | All photos are symbolic photos | Subject to change without notice | Version: 03/2016 db
COMPACT VENTILATION UNIT LG 3200 PAGE 14
Fans: energy-saving radial fans with state-of-the-art EC motor technology with optional automatic constant volume flow control with an optional constant volume flow control or constant pressure control
Counterflow heat exchanger: highly efficient heat recovery system with an air/air counterflow heat exchanger with an automatic 100% bypass
Air volume flow: of 900 to 3400 m³/h with an external pressure of 100 to 600 Pa
Filters: Filter ODA ISO ePM2,5 65% (outdoor air), Filter ETA ISO Coarse 90% (extract air).
Electric preheater battery: able to be connected to the outdoor air connecting piece of the comfort ventilation unit, with an optional heat insulation.
Hot water reheater battery: for reheating the supply air (for external duct installation)
Housing: made from zinc-plated steel plate with 50 mm thermal insulation
Air line connections LG 1400: outdoor air / exhaust air / supply air / extract air (W x H) 300 x 800 mm
Air line connections LG 1400 S: outdoor air / exctract air (W x H) 300 x 800 mm and exhaust air / supply air (W x H) 486 x 786 mm
Connection profile: P30
Installation position: Free-standing installation
Summer changeover: integrated 100% bypass damper with seal
Optional: building automation – networking options:• Integratred webserver• Modbus RTU• Modbus TCP/IP• BACnet• KNX-GatewayThe corresponding bus connection is activated/parameterized at the factory according to the customer's order.
Electrical connection: using terminals
Service – maintenance – initial startup
OUR COMPACT VENTILATION UNIT LG 3200 HAS BEEN EXTERNALLY INSPECTED BY
• Lucerne Polytechnic – Engineering & Architecture
• TÜV-AUSTRIA Services GmbH, Testing, Inspection and Certification Centre/Vienna
OUR COMPACT VENTILATION UNIT LG 3200 HAS BEEN CERTIFIED BY
• Passivhausinstitut (Passive House Institute) Darmstadt
• energie-cluster.ch, Declaration report by Lucerne Polytechnic
Notice: Our product range includes units with a size up to 10,000 m³/h as well as comprehensive accessories.
LG 3200 and LG 3200 S at a glance!
COMPACT VENTILATION UNIT LG 3200 PAGE 15
Notes
J. PICHLERGesellschaft m.b.H.
AUSTRIA9021 KLAGENFURT AM WÖRTHERSEEKarlweg 5T +43 (0)463 32769F +43 (0)463 37548
AUSTRIA1100 WIENDoerenkampgasse 5T +43 (0)1 6880988F +43 (0)1 6880988-13
Sales offices in Slovenia and Serbia. Sales partners in Germany, Switzerland and Italy.
Responsible for the content: J. Pichler Gesellschaft m.b.H. | Graphics and layout: WERK1Photos: Ferdinand Neumüller, Archiv J. Pichler Gesellschaft m.b.H. | Text: J. Pichler Gesellschaft m.b.H. All rights reserved | All photos are symbolic photos | Subject to change without notice | Version: 02/2020 en/P
Your partner/installer:
Systematic ventilation.
ÖSTERREICH
CROATIA
SLOVENIA
SERBIA
GERMANY
CZECH REPUBLIC
SLOVAKIA
HUNGARY
ITALY
BOSNIA AND HERZEGOVINA
Klagenfurt
Wien
Maribor
Beograd
COMPACT VENTILATION UNIT LG 3200 PAGE 16
ErP 2018Fulfils the requirements of the Ecodesign Directive, in accordance with EU Regulation 1253/2014.
ErP2018