Compact IO Hubs with IO-Link – TBIL-S… -...

35
Your Global Automation Partner Instructions for Use TBIL-S… Compact IO Hubs with IO-Link

Transcript of Compact IO Hubs with IO-Link – TBIL-S… -...

Page 1: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

Your Global Automation Partner

Instructions for Use

TBIL-S…Compact IO Hubs with IO-Link

Page 2: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

2 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

Page 3: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 3

Table of Contents1 About These Instructions ..................................................................................................................  5

1.1 Target groups...................................................................................................................  51.2 Explanation of symbols used ........................................................................................  51.3 Additional documents....................................................................................................  51.4 Feedback about these instructions..............................................................................  5

2 Notes on the Product .........................................................................................................................  62.1 Product Identification ....................................................................................................  62.2 Scope of Delivery.............................................................................................................  62.3 Legal requirements.........................................................................................................  62.4 Manufacturer and service ..............................................................................................  6

3 For Your Safety....................................................................................................................................  73.1 Intended Use ....................................................................................................................  73.2 General safety notes .......................................................................................................  7

4 Product Description ...........................................................................................................................  84.1 Device Overview..............................................................................................................  84.1.1 Display Elements..............................................................................................................................  84.2 Properties and Features.................................................................................................  94.3 Functions and Operating Modes..................................................................................  9

5 Mounting............................................................................................................................................  105.1 Grounding the device................................................................................................... 10

6 Connecting ........................................................................................................................................  116.1 Connecting the supply voltage and IO-Link ............................................................ 116.2 Connecting Digital Sensors and Actuators .............................................................. 12

7 Parameterizing and Configuring ..................................................................................................  147.1 Parameters...................................................................................................................... 14

8 Operating ...........................................................................................................................................  228.1 Process Input Data ........................................................................................................ 228.2 Process Output Data ..................................................................................................... 258.3 LED Displays ................................................................................................................... 258.3.1 IO-Link................................................................................................................................................ 258.3.2 Channel-LEDs .................................................................................................................................. 258.4 Evaluating Diagnostic Data......................................................................................... 268.5 IO-Link Events ................................................................................................................ 278.6 IO-Link Error Codes ....................................................................................................... 28

9 Troubleshooting ...............................................................................................................................  29

10 Maintenance......................................................................................................................................  30

11 Repair ..................................................................................................................................................  3011.1 Returning devices.......................................................................................................... 30

12 Disposal ..............................................................................................................................................  30

13 Technical Data ..................................................................................................................................  3113.1 General technical data.................................................................................................. 3113.2 Technical Data – TBIL-S…-8DIP .................................................................................. 32

Page 4: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

Table of Contents

4 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

13.3 Technical Data – TBIL-S…-8DXP................................................................................. 33

14 Appendix: Declaration of Conformity ..........................................................................................  34

Page 5: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 5

1 About These InstructionsThese operating instructions describe the structure, functions and the use of the product andwill help you to operate the product as intended. Read these instructions carefully before usingthe product. This is to avoid possible damage to persons, property or the device. Retain the in-structions for future use during the service life of the product. If the product is passed on, passon these instructions as well.

1.1 Target groupsThese instructions are aimed a qualified personal and must be carefully read by anyonemounting, commissioning, operating, maintaining, dismantling or disposing of the device.

1.2 Explanation of symbols usedThe following symbols are used in these instructions:

DANGERDANGER indicates a dangerous situation with high risk of death or severe injury ifnot avoided.

WARNINGWARNING indicates a dangerous situation with medium risk of death or severe in-jury if not avoided.

CAUTIONCAUTION indicates a dangerous situation of medium risk which may result in minoror moderate injury if not avoided.

NOTICENOTICE indicates a situation which may lead to property damage if not avoided.

NOTENOTE indicates tips, recommendations and useful information on specific actionsand facts. The notes simplify your work and help you to avoid additional work.

u CALL TO ACTIONThis symbol denotes actions that the user must carry out.

a RESULTS OF ACTIONThis symbol denotes relevant results of actions.

1.3 Additional documentsThe following additional documents are available online at www.turck.com:n Data sheetn EC Declaration of Conformityn Commissioning manual IO-Link devices

1.4 Feedback about these instructionsWe make every effort to ensure that these instructions are as informative and as clear as pos-sible. If you have any suggestions for improving the design or if some information is missing inthe document, please send your suggestions to [email protected].

Page 6: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

Notes on the ProductManufacturer and service

6 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

2 Notes on the Product

2.1 Product IdentificationThese instructions are valid for the following devices:n TBIL-S3-8DIPn TBIL-S3-8DXPn TBIL-S4-8DIPn TBIL-S4-8DXP

2.2 Scope of DeliveryThe scope of delivery includes:n I/O hubn Dummy plugs for M8 or M12 connectorsn Label clips

2.3 Legal requirementsThe device falls under the following EU directives:n 2014/30/EU (electromagnetic compatibility)n 2011/65/EU (RoHS Directive)

2.4 Manufacturer and serviceHans Turck GmbH & Co. KG Witzlebenstraße 7 45472 Muelheim an der Ruhr Germany

Turck supports you with your projects, from initial analysis to the commissioning of your applic-ation. The Turck product database contains software tools for programming, configuration orcommissioning, data sheets and CAD files in numerous export formats. You can access theproduct database at the following address: www.turck.de/productsFor further inquiries in Germany contact the Sales and Service Team on:

n Sales: +49 208 4952-380n Technology: +49 208 4952-390

Outside Germany, please contact your local Turck representative.

Page 7: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 7

3 For Your SafetyThe product is designed according to state-of-the-art technology. However, residual risks stillexist. Observe the following warnings and safety notices to prevent damage to persons andproperty. Turck accepts no liability for damage caused by failure to observe these warning andsafety notices.

3.1 Intended UseThese devices are designed solely for use in industrial areas.The block modules of the TBIL-S… series are IO-Link devices and serve as I/O hub between fielddevices (sensors/actuators) and the IO-Link master. The hubs provide 8 digital I/O channels. Depending on the device type, the devices provide 8 digital inputs for connecting digitalsensors or 8 digital DXP channels for connecting digital sensors and actuators. In the deviceswith DXP channels, each I/O channel can be used as digital in- or output without additionalconfiguration. The device is designed in IP67/IP69K and can be mounted directly in the field.The devices may only be used as described in these instructions. Any other use is not in accord-ance with the intended use. Turck accepts no liability for any resulting damage.

3.2 General safety notesn The device may only be assembled, installed, operated, parameterized and maintained by

professionally-trained personnel.n The device may only be used in accordance with applicable national and international regu-

lations, standards and laws.n The device only meets the EMC requirements for industrial areas and is not suitable for use

in residential areas.

Page 8: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

Product DescriptionDevice Overview

8 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

4 Product DescriptionThe I/O hubs of the TBIL-S… series connect up to 8 digital sensors or up to sensors or actuatorswith one IO-Link master port.4 device types are available:n TBIL-S3-8DIP: 8 digital input channels, 8 M8 connectorsn TBIL-S3-8DXP: 8 digital I/O, 8 M8 connectors, each channel can be used as digital in- or

output without additional configurationn TBIL-S4-8DIP: 8 digital input channels, 4 M12 connectorsn TBIL-S4-8DXP: 8 digital I/O, 4 M12 connectors, each channel can be used as digital in- or

output without additional configurationThe devices are designed in a fully encapsulated housing with degree of protection IP67/IP69K.

4.1 Device Overview

16 [0.63]22.2 [0.87]26.8 [1.06]

31.6 [1.24]

132 [5.20]6.1 [0.24]

144 [5.67]

M12 x 1

Ø 4.3 [0.17]

Ø 4.3 [0.17]

P1 C2

C7 C6

C1

C5

C0

C4

Fig. 1: Dimensions TBIL-S3-…

16 [0.63]24.9 [0.98]26.8 [1.06]

31.6 [1.24]

132 [5.20]6.1 [0.24]

144 [5.67]

M12 x 1

Ø 4.3 [0.17]

Ø 4.3 [0.17]

C3P1 C2 C1 C0

Fig. 2: Dimensions TBIL-S4-…

4.1.1 Display ElementsThe device has the following LED indicators:n IO-Link communicationn I/O status

Page 9: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 9

4.2 Properties and Featuresn Fibre-glass reinforced housingn Shock and vibration testedn Fully potted module electronicsn Protection class IP67/IP69Kn IO-Link diagnostics for short-circuit and supply over- and undervoltagen TBIL-S3-…: 1 digital input channel or 1 universal digital channel per M8 connector

TBIL-S4-…: 2 digital input channels or 2 universal digital channels per M12 connectorn metal connectors

4.3 Functions and Operating ModesThe I/O hubs with IO-Link of the TBIL-S series connect up to 8 digital sensors or 8 digital sensorsand actuators with one IO-Link master port.The device provides diagnostics for power supply and short circuit of the sensors and actuatorson the IO-Link master.

Page 10: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

MountingGrounding the device

10 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

5 MountingThe device is mounted via four M4 screws on a flat and pre-drilled mounting surface.� Attach the module to the mounting surface with two M4 screws. The maximum tighten-

ing torque for the screws is 1.3 Nm

31.8

132

M4 (2 x)

max. 1.3 Nm

Fig. 3: Mounting the device to a mounting surface (example: TBIL-S3-…)

5.1 Grounding the device� When mounting on a mounting plate, fasten the device with an M4 metal screw.a The FE connection of the device is connected to the reference potential of the installation

via the M4 metal screw.

Page 11: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 11

6 Connecting

WARNINGPenetration of liquids or foreign objects through leaking connectionsDanger to life due to malfunction� Fasten the M12 connectors with a tightening torque of 0.8 Nm.� Always seal unused connectors with respective protection caps.

6.1 Connecting the supply voltage and IO-Link

WARNINGDefective power supply unitDanger to life due to dangerous voltages on touchable parts� Only use SELV or PELV power supplies in accordance with EN ISO 13849-2, which

allow a maximum of 60 VDC or 25 VAC in the event of a fault.

For the connection to IO-Link and the supply voltage, a 5-pole M12 connector is available.

Fig. 4: M12 connector for the connection to IO-Link

� Connect the device to the supply voltage and IO-Link according to the pin assignment.

4

13

2

5

1 = 24 VDC

2 = n.c.

3 = GND

4 = C/Q (IO-Link)

5 = n.c.

Fig. 5: Pin assignment IO-Link

Page 12: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

ConnectingConnecting Digital Sensors and Actuators

12 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

6.2 Connecting Digital Sensors and Actuators

Connecting Digital Sensors and Actuators – TBIL-S3-…

For connecting digital sensors and actuators, 3-pin M8 connectors are available.

Fig. 6: TBIL-S3-…: M8 connector for connecting digital sensors and actuators

� Connect the sensors to the device according to the pin assignment.

3 1

4

v

1 = VAUX

3 = GND

4 = Signal InC0…C7

Fig. 7: Pin assignment TBIL-S3-8DIP

� Connect the sensors and actuators to the device according to the pin assignment.

3 1

4

v

1 = VAUX

3 = GND

4 = Signal In/OutC0…C7

Fig. 8: Pin assignment TBIL-S3-8DIP

Page 13: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 13

Connecting Digital Sensors and Actuators – TBIL-S4-…

For connecting digital sensors and actuators, 5-pin M12 connectors are available.

Fig. 9: TBIL-S4-…: M12 connector for connecting digital sensors and actuators

� Connect the sensors to the device according to the pin assignment.

4

1 3

2

5

v1 = VAUX

2 = Signal In

3 = GND

4 = Signal In

5 = FEC0...C3

Fig. 10: Pin assignment TBIL-S4-8DIP

� Connect the sensors and actuators to the device according to the pin assignment.

4

1 3

2

5

v1 = VAUX

2 = Signal In/Out

3 = GND

4 = Signal In/Out

5 = FEC0...C3

Fig. 11: Pin assignment TBIL-S4-8DXP

Page 14: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

Parameterizing and ConfiguringParameters

14 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

7 Parameterizing and Configuring

7.1 Parameters

IO-Link object directory – ISDU device parameters: Direct Parameter Page

ISDU IndexHex.(Dec.)

Sub index Object name Access Length [Byte]

Meaning/default value

0x00 (0)

Direct Parameter Page 1 readonly

16

0x07 Vendor ID readonly

2 0x013D(ID for Turck)0x08

0x09 Device ID readonly

3 e.g. TBIL-S3-8DXP:0x1E22130x0A

0x0B

IO-Link object directory – ISDU device parameters: Identification

ISDU IndexHex.(Dec.)

Object name Access Length [Byte]

Meaning/default value

Comment

0x10(16)

VendorName

readonly

16 Turck

0x11(17)

Vendor Text readonly

32 www.turck.com

0x12(18)

ProductName

readonly

32 e.g. TBIL-S3-8DXP

0x13(19)

Product ID readonly

16 Ident no. of the device:e.g. 100002595 forTBIL-S3-8DXP

0x14(20)

Product Text readonly

32 I/O hub

0x15(21)

SerialNumber

readonly

16 Sequential serial number

0x16(22)

Hardware ID read/write

8 Hardware ID of thedevice, e.g. V1.0

0x17(23)

FirmwareRevision

readonly

16 Firmware version ofthe device, e.g.V1.0.7.0

0x18(24)

Application Specific Tag

read/write

32 Default "***" Customer-specific orapplication-specificdata can be stored inthis field.

0x19(25)

Function Tag read/write

32 Default "***" The application-spe-cific device functioncan be stored in thisfield.

Page 15: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 15

ISDU IndexHex.(Dec.)

Object name Access Length [Byte]

Meaning/default value

Comment

0x1A(26)

Location Tag read/write

32 Default "***" The application-spe-cific installation loca-tion of the device canbe stored in this field.

IO-Link object directory – ISDU device parameters: Preferred Index (parameters anddiagnostics of the digital in- and outputs)

ISDU IndexHex.(dec.)

Object name Access Length [Byte]

Meaning

0x40(64)

Parameter ID read/write

4 Customer-specific ID, for free use

0x41(65)

InvertingInput

read/write

1 Invert digital input

0x42(66)

Activate Output

read/write

1 Activate outputonly for TBIL-S…-8DXP

0x43(67)

Impulse StretchingInput

read/write

8 Pulse stretching input

0x44(68)

Short Circuit Recovery

read/write

1 Manual output reset after overcurrentonly for TBIL-S…-8DXP

0x45(69)

Failsafe read/write

2 Output After Erroronly for TBIL-S…-8DXP

0x46(70)

Under Voltage Diagnostics

read/write

2 Undervoltage Diagnosis (defining thethreshold value for the undervoltag dia-gnostics)

Diagnostics0x50(80)

Supply Error readonly

2 n Over- and undervoltage supplyn Overcurrent VAUX connector C0…C7 or

C0…C3

0x51(81)

Output Short Circuit

readonly

1 Overcurrent output 0…7only for TBIL-S…-8DXP

Page 16: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

Parameterizing and ConfiguringParameters

16 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

Invert Digital Input – 0x41 (65), Sub Index 0

This parameter inverts the state of the digital input in the process image.

Format Length

Byte 1 byte 1 bit per channel

Default values are shown in bold.

Value Meaning

0 No1 Yes Input signal inverted

n TBIL-S3-8DIPn TBIL-S3-8DXP

Byte 0

Bit offset

7 6 5 4 3 2 1 0

C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4

n TBIL-S4-8DIPn TBIL-S4-8DXP

Byte 0

Bit offset

7 6 5 4 3 2 1 0

C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4

NOTEThis parameter can also be set for all connectors of the module via the IODD.

Page 17: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 17

Activate Output – 0x42 (66), Sub Index 0

this parameeter activates or deactivates the output function of the digital channel.

Format Length

Byte 1 byte 1 bit per channel

Default values are shown in bold.

Value Meaning

0 No Output function deactivated, channel can only be used as input

1 Yes Output function activated, channel can be used as in- or output

n TBIL-S3-8DXP

Byte 0

Bit offset

7 6 5 4 3 2 1 0

C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4

n TBIL-S4-8DXP

Byte 0

Bit offset

7 6 5 4 3 2 1 0

C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4

NOTEThis parameter can also be set for all connectors of the module via the IODD.

Page 18: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

Parameterizing and ConfiguringParameters

18 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

Pulse Stretching Input – 0×43 (67)

This parameter defines the duration of the pulse stretching for digital input edges in multiplesof 10 ms. This allows that even short signals with longer PLC cycle times can be detected.

Format Length

Array of Bytes 8 byte 1 byte per channel

Default values are shown in bold.

Value Meaning

0 disabled Pulse stretching deactivated

1 1…255 Pulse stretching input [*10 ms]

n TBIL-S3-8DIPn TBIL-S3-8DXP

Bit offset

0 8 16 24 32 40 48 56

Sub index

8 7 6 5 4 3 2 1

C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4

n TBIL-S3-8DIPn TBIL-S3-8DXP

Bit offset

0 8 16 24 32 40 48 56

Sub index

16 15 14 13 12 11 10 9

C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4

NOTEThis parameter can also be set for all connectors of the module via the IODD.

Page 19: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 19

Manual Output Reset after Overcurrent – 0x44 (68), Sub Index 0

This parameter defines if a manual reset is necessary after an overcurrent occurred at the digitalchannel.

Format Length

Byte 1 byte 1 bit per channel

Default values are shown in bold.

Value Meaning

0 No Automatic recovery mode

1 Yes Controlled recovery mode (output has to be reset manually)

n TBIL-S3-8DXP

Byte 0

Bit offset

7 6 5 4 3 2 1 0

C7P2 C6P4 C5P4 C4P4 C5P2 C2P4 C1P4 C0P4

n TBIL-S4-8DXP

Byte 0

Bit offset

7 6 5 4 3 2 1 0

C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4

NOTEThis parameter can also be set for all connectors of the module via the IODD.

Page 20: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

Parameterizing and ConfiguringParameters

20 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

Output After Error – 0x45 (69), Sub Index 0

This parameter defines the behavior of the output in case of an interruption of the IO-Link com-munication.

Format Length

Array of Bytes 2 byte 2 bit per channel

Default values are shown in bold.

Value Meaning

00 0 Set output to 0

01 1 Set output to 1

10 Current value Hold current value

11 reserved

n TBIL-S3-8DXP

Byte 1 Byte 0

Bit offset Bit offset

6 4 2 0 6 4 2 0

C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4

n TBIL-S4-8DXP

Byte 1 Byte 0

Bit offset Bit offset

6 4 2 0 6 4 2 0

C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4

NOTEThis parameter can also be set for all connectors of the module via the IODD.

Page 21: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 21

Undervoltage Diagnosis – 0x46 (70), Sub Index 0

This parameter defines threshold value for the undervoltage diagnostics.

Format Length

Array of Bytes 2 byte 1 bit per module

Default values are shown in bold.

Value Meaning

0 Standard (IEC 61131-2)

lower threshold: 19.2 Vupper threshold: 20.4 V

1 Extended lower threshold: 17.5 V

Byte 0

Bit offset

7 6 5 4 3 2 1 0

- - - - - - - Threshold

Byte 1

Bit offset

7 6 5 4 3 2 1 0

- - - - - - - -

Page 22: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

OperatingProcess Input Data

22 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

8 Operating

8.1 Process Input Data

TBIL-S3-8DIP

Byteno.

Bit offset

7 6 5 4 3 2 1 0

Inputs

0 C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4

Module diagnostics

1 Groupdia-gnostics

- - - - Under-voltage

- Over-voltage

Connector diagnostics – overcurrent sensor supply

2 Over-current C7

Over-current C6

Over-current C5

Over-current C4

Over-current C3

Over-current C2

Over-current C1

Over-current C0

TBIL-S3-8DXP

Byteno.

Bit offset

7 6 5 4 3 2 1 0

Inputs

0 C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4

Module diagnostics

1 Groupdia-gnostics

- - - - Under-voltage

- Over-voltage

Connector diagnostics – overcurrent sensor supply

2 Over-current C7

Over-current C6

Over-current C5

Over-current C4

Over-current C3

Over-current C2

Over-current C1

Over-current C0

Channel diagnostics – overcurrent output

3 Over-current C7P4

Over-current C6P4

Over-current C5P4

Over-current C4P4

Over-current C3P4

Over-currentC2P4

Over-current C1P4

Over-currentC0P4

Page 23: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 23

TBIL-S4-8DIP

Byteno.

Bit offset

7 6 5 4 3 2 1 0

Inputs

0 C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4

Module diagnostics

1 Groupdia-gnostics

- - - - Under-voltage

- Over-voltage

Connector diagnostics – overcurrent sensor supply

2 - - - - Over-currentC3

Over-currentC2

Over-currentC1

Over-currentC0

TBIL-S4-8DXP

Byteno.

Bit offset

7 6 5 4 3 2 1 0

Inputs

0 C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4

Module diagnostics

1 Groupdia-gnostics

- - - - Under-voltage

- Over-voltage

Connector diagnostics – overcurrent sensor supply

2 - - - - Over-currentC3

Over-currentC2

Over-currentC1

Over-currentC0

Channel diagnostics – overcurrent output

3 Over-currentC3P2

Over-currentC3P4

Over-currentC2P2

Over-currentC2P4

Over-currentC1P2

Over-currentC1P4

Over-currentC0P2

Over-currentC0P4

NOTEThe diagnoses can also be accessed via IO-Link indices.

Page 24: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

OperatingProcess Input Data

24 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

Designation Meaning

InputsCxPy 0 Input inactive

1 Input active

Module diagnosticsGroup diagnostics 0 No diagnostic mes-

sage

1 Module diagnosticsactive

� Evaluate the bit to monitor the dia-gnostics cyclically.

ð Bit = 0: no diagnostics active

ð Bit = 1: Module diagnostics� Bit = 1: Evaluate further diagnostic

bits to determine the origin of thediagnosctic message.

undervoltage 0 No diagnostic message

1 Undervoltage of supply voltage

Overvoltage 0 No diagnostic message

1 Overvoltage of supply voltage

Connector diagnostics – overcurrent sensor supplyOvercurrent Cx 0 No diagnostic mes-

sage

1 Overload at the sensor supply at the connector.The sensor/actuator supply is protected in groups. If an overloadoccurs at one slot, all diagnostic bits of a group are active.Groups:n TBIL-S3-…: C0…C3, C4…C7n TBIL-S4-…: C0…C1, C2…C3

Channel diagnostics – overcurrent outputOvercurrent CxPy 0 No diagnostic mes-

sage

1 Overlaod at the output/short-circuit

Page 25: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 25

8.2 Process Output Data

TBIL-S3-8DXP

Byteno.

Bit offset

7 6 5 4 3 2 1 0

Outputs

0 C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4

TBIL-S4-8DXP

Byteno.

Bit offset

7 6 5 4 3 2 1 0

Outputs

0 C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4

Designation Meaning

CxPy 0 Output inactive

1 Output active

8.3 LED DisplaysThe device has the following LED indicators:n IO-Link communicationn I/O status

8.3.1 IO-Link

IO-Link LED Meaning

Green flashing IO-Link communication error-free, valid process data are sent

Red IO-Link communication error or module error

Red flashing (1Hz)

IO-Link communication error-free, invalid process data or diagnostic mes-sage

Off no voltage supply

8.3.2 Channel-LEDs

LED 0…7 Meaning (input) Meaning (output)

Green Input active Output active

Red flashing (0.5Hz)

Overload of the sensor supply In devices with group diagnostics, all connector-LEDs of the supply groupflash simultaneously in case of an error.

Red – Output active, overload/overcurrentat output

Off Input inactive Output inactive

Page 26: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

OperatingEvaluating Diagnostic Data

26 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

8.4 Evaluating Diagnostic Data

Group Diagnostics: Undervoltage and Overcurrent Sensor Supply – 0x50 (80), Sub Index 0

Indicates errors in the module and sensor supply:n Group diagnostics: Diagnostics pending at the modulen Over- or undervoltage, per modulen Overcurrent sensor supply VAUX, per connector

Format Length

Array of Bytes 2 byte

0 = no diagnostics1 = diagnostic message

Byte 0

Bit offset

15 14 13 12 11 10 9 8

Group diagnostics - - - - Undervoltagesupply

- Overvoltage supply

TBIL-S3-…

Byte 1

Bit offset

7 6 5 4 3 2 1 0

Over-currentVAUX C7

Over-currentVAUX C6

Over-currentVAUX C5

Over-currentVAUX C4

Over-currentVAUX C3

Over-currentVAUX C2

Over-currentVAUX C1

Over-currentVAUX C0

TBIL-S4-…

Byte 1

Bit offset

7 6 5 4 3 2 1 0

- - - - Over-currentVAUX C3

Over-currentVAUX C2

Over-currentVAUX C1

Over-currentVAUX C0

Page 27: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 27

Overcurrent Output – 0x51 (81), Sub Index 0

Indicates an overcurrent at the corresponding digital output.

Format Length

Byte 1 byte 1 bit per output

0 = no diagnostics1 = diagnostic message

TBIL-S3-8DXP

Byte 0

Bit offset

7 6 5 4 3 2 1 0

Over-currentC7P4

Over-currentC6P4

Over-currentC5P4

Over-currentC4P4

Over-currentC3P4

Over-currentC2P4

Over-currentC1P4

Over-currentC0P4

TBIL-S4-8DXP

Byte 0

Bit offset

7 6 5 4 3 2 1 0

Over-currentC3P2

Over-currentC3P4

Over-currentC2P2

Over-currentC2P4

Over-currentC1P2

Over-currentC1P4

Over-currentC0P2

Over-currentC0P4

8.5 IO-Link Events

EventCode

Description Event Mode

0x5110 Overvoltage supply

0xF4 (appears) Supply voltage too high

0xB4 (disappears)

0x5111 Undervoltage supply

0xF4 (appears) Supply voltage too low

0xB4 (disappears)

0x7710 Overcurrent VAUX con-nector x orovercurrent output x

0xF4 (appears) Group event for Overcurrent:n Overcurrent of the sensor supply at

one of the connectorsor

n overcurrent at one of the outputs (DO0…DO7)

The mapped diagnostics in the processimage of the inputs show which slot oroutput detects an overcurrent.

0xB4 (disappears)

Page 28: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

OperatingIO-Link Error Codes

28 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

8.6 IO-Link Error Codes

Error code Description

0x8011 Index not available

0x8012 Sub Index not available

0x8023 Accesss denied Index cannot be written

0x8030 Parameter value out of range Parameter value out of range

0x8033 Parameter length overrun Length of data to be written does notmatch the length defined for this para-meter.

0x8034 Parameter length underrun

0x8035 Function not available Function not available in the device

0x8041 Inconsistent parameter set Inconsistent parameters

Page 29: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 29

9 TroubleshootingIf the device does not function as expected, first check whether ambient interference is present.If there is no ambient interference present, check the connections of the device for faults.If there are no faults, there is a device malfunction. In this case, decommission the device andreplace it with a new device of the same type.

Page 30: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

MaintenanceReturning devices

30 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

10 MaintenanceEnsure that the plug connections and cables are always in good condition.The devices are maintenance-free, clean dry if required.

11 RepairThe device must not be repaired by the user. The device must be decommissioned if it is faulty.Observe our return acceptance conditions when returning the device to Turck.

11.1 Returning devicesReturns to Turck can only be accepted if the device has been equipped with a Decontaminationdeclaration enclosed. The decontamination declaration can be downloaded from https://www.turck.de/en/retoure-service-6079.php and must be completely filled in, and affixed securely and weather-proof to the outside of thepackaging.

12 DisposalThe devices must be disposed of correctly and must not be included in normalhousehold garbage.

Page 31: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 31

13 Technical Data

13.1 General technical data

Technical data

ConnectorsIO-Link M12×1, 5-pole

Input/output

n TBIL-S3-… M8×1, 3-pole

n TBIL-S4-… M12×1, 5-pole

Permissible torques

n IO-Link 0.8 Nm

n I/O channels M8: 0.4 NmM12: 0.6 Nm

n Mounting (M4 screws) 1.3 Nm

IO-LinkIO-Link specification specified according to version 1.1

Parameterization FDT/DTM, IODD

Transmission rate COM 2: 38.4 kbit/s

Transmission physics Transmission physics, corresponds to 3-wire physics (PHY2)

Standard/directive conformityVibration test According to EN 60068-2-6

Shock test According to EN 60068-2-27

Drop and topple According to EN 60068-2-31/ IEC 60068-2-32

Electro-magnetic compatibility according to EN 61131-2/-6-4

Approvals CE, cULus

UL conditions Encl. type 2, pollution degree 2, rel. humidity ≤ 95 %, indooruseUse UL-certified cables (CYJV or PVVA) suitable for the respective application regarding voltage and current ratings.

General InformationDimensions (B × L × H) 31.6 × 144 × 26.8 mm

Operating temperature -40…+70 °C

Storage temperature -40…+85 °C

Protection class IP67/IP69K (not evaluated by UL)

Overvoltage category II

Housing material PA6-GF30

Housing color black

Halogen-free Yes

Mounting 2 mounting holes, Ø 4.3 mm

Page 32: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

Technical DataTechnical Data – TBIL-S…-8DIP

32 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

13.2 Technical Data – TBIL-S…-8DIP

Technical data

Power supplyOperating/load voltage 18…30 VDC

Operating current < 120 mA

Sensor/actuator supply VAUX Supply connectors C0…C7 or C…C30.5 A per channel group, short-circuit protec-ted with diagnosticschannel groups:n TBIL-S3-8DIP: C0…C3, C4…C7n TBIL-S4-8DIP: C0…C1, C2…C3

Total current max. 4 A per module

InputsNumber of channels 8 digital pnp inputs (EN 61131-2)

Input voltage 18…30 VDC i.e. from supply voltage

Signal voltage, low level -3 to 5 VDC (EN 61131-2, Type 1 and 3)

Signal voltage, high level 11 to 30 VDC (EN 61131-2, Type 1 and 3)

Input delay 0.010 ms

Max. input current 15 mA

Potential isolation Inputs to FE, 500 VDC

IO-LinkMinimum cycle time 2.2 ms

Page 33: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

V 01.01 | 2019/06 33

13.3 Technical Data – TBIL-S…-8DXP

Technical data

Power supplyOperating/load voltage 18…30 VDC

Operating current < 120 mA

Sensor/actuator supply VAUX Supply connectors C0…C7 or C…C30.5 A per channel group, short-circuit protec-ted with diagnosticschannel groups:n TBIL-S3-8DIP: C0…C3, C4…C7n TBIL-S4-8DIP: C0…C1, C2…C3

Total current max. 4 A per module

InputsNumber of channels 8 digital pnp inputs (EN 61131-2)

Input voltage 18…30 VDC i.e. from supply voltage

Signal voltage, low level -3 to 5 VDC (EN 61131-2, Type 1 and 3)

Signal voltage, high level 11 to 30 VDC (EN 61131-2, Type 1 and 3)

Input delay 0.010 ms

Max. input current 15 mA

Potential isolation Inputs to FE, 500 VDC

OutputsNumber of channels 8 digital pnp outputs

Type of output diagnostics Channel diagnosis

Output voltage 24 VDC from supply voltage

Output current per channel 0.5 A, short-circuit-proof

Output delay 0.15 ms

Load type Ohmic, inductive lamp load

Potential isolation Outputs to FE, 500 VDC

IO-LinkMinimum cycle time 2.8 ms

Page 34: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

Appendix

34 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

14 Appendix: Declaration of Conformity

EU-Konformitätserklärung Nr.: 5035-2M EU Declaration of Conformity No.:

Wir/ We: HANS TURCK GMBH & CO KG WITZLEBENSTR. 7, 45472 MÜLHEIM A.D. RUHR

erklären in alleiniger Verantwortung, dass die Produkte declare under our sole responsibility that the products

Kompakte I/O Module in IP20/IP67: Compact I/O modules in IP20/IP67:

Typen / types: FDN20-*, FDNL-*, FDNP-*, FDP20-*, FGDP-*, FGEN-*, FLDP-*, FLIB-*, FXEN-*, SDPX-*, TBDP-*, TBEN-*, TBIL-*, TBPN-*

auf die sich die Erklärung bezieht, den Anforderungen der folgenden EU-Richtlinien durch Einhaltung der folgenden Normen genügen: to which this declaration relates are in conformity with the requirements of the following EU-directives by compliance with the following standards:

EMV - Richtlinie /EMC Directive 2014 / 30 / EU 26.02.2014EN 61131-2:2007 (Abschnitte / section 8, 9, 10)

RoHS – Richtlinie /RoHS Directive 2011 / 65 / EU 08.06.2011

Weitere Normen, Bemerkungen: additional standards, remarks:

Zusätzliche Informationen: Supplementary infomation:

Mülheim, den 13.07.2018 i.V. Dr. M. Linde, Leiter Zulassungen /Manager Approvals

Ort und Datum der Ausstellung / Name, Funktion und Unterschrift des Befugten / Place and date of issue Name, function and signature of authorized person

Page 35: Compact IO Hubs with IO-Link – TBIL-S… - TURCKpdb2.turck.com.cn/repo/media/_cn/Anlagen/100003857.pdf · 2020. 3. 27. · Notes on the Product Manufacturer and service 6 Hans Turck

Over 30 subsidiaries and over60 representations worldwide!

www.turck.com

100003857 | 2019/06

100003857