Coding System - JICA · Treatment plant Kimisagara TPKI Nyamirambo (21) Treatment plant Kizanye...
Transcript of Coding System - JICA · Treatment plant Kimisagara TPKI Nyamirambo (21) Treatment plant Kizanye...
-
9.1 Coding System of WASAC
Coding System
Standard
Version Log
Version Date Author Note
F 1 16th March 2017 Celestin MWAMBUTSA
F1 25-06-2018 M. Brouwer Added locations
別添 9
-
9.1 Coding System of WASAC
1 Table of Contents 1 Introduction ..................................................................................................................................... 3
2 Encoding .......................................................................................................................................... 3
3 Functional decomposition ............................................................................................................... 3
4 ANNEX I: Tables location-oriented code ......................................................................................... 6
4.1 Branch number ........................................................................................................................ 6
4.2 Location name ......................................................................................................................... 7
5 ANNEX 2: Process groups ................................................................................................................ 9
6 ANNEX 3: Process steps ................................................................................................................. 10
7 ANNEX 3: Modules ........................................................................................................................ 11
8 ANNEXES 4: Components .............................................................................................................. 11
-
9.1 Coding System of WASAC
1 Introduction Encoding is something like naming in the form of a code. It is not necessary, that the code also
replaces the common designations in the parlance. WASAC has chosen to naming and coding as
much as possible to distract from the functional denomination.
The code must be applied to all relevant given as core parts of the plant and then forms the means of
identification of the element and the key to all this available information. Because the encryption
system is derived from the structure of treatment plants, in the most meaningful and simple way as
possible. This document also describes the methodology of defining and clarifying the locations.
Encryption is used on Piping and Instrumentation Diagrams (P&IDs), electrical and mechanical
drawings, in controlling processes, and displaying process.
2 Encoding The encoding conforms to the following principles:
Unique design
Assigning a code expires according to a tight structure
Process oriented
The code says something about the position within the production process of the indicated
process part
Functional decomposition of processes
The encoding follows the Division of the process in functional parts.
Applicable to all current and future processes on (drinking) water locations
The structure is part of the process but gives no restrictions to the process.
3 Functional decomposition In order to be able to describe the functioning of production sites, for example for the design of the
process Automation, a breakdown structure is made of the process in functional parts (functional
decomposition). This breakdown structure continues in P&ID, process descriptions and operating
plans. By defining a functional decomposition can also clear the encoding be set up.
For the method of decomposition is chosen for the standard "Batch control" part 1: Models and
terminology (NEN-EN-IEC 61512-1), also known as "s88". Although this standard out of automating
batch processes but this system of Division is no longer apply to the processes at WASAC.
The breakdown of the process takes place in accordance with this standard in seven layers which a
corresponding WASAC names, as shown in the following table.
-
9.1 Coding System of WASAC
Denomination
in accordance
with
IEC 61512-1-
NEN:
WASAC
naming:
Area Location
name
Technical installation
Process cell Process
group Process name
Unit Process
step
Equipment
module
Module
Functional title Control
module
Component
The location name provides information on the location of a production or distribution location
within the organization. The location name and code is in whole WASAC unique and is sufficient to
identify the location.
The process name gives a main classification of the process. The process is divided into process
groups and process steps
A process step is an important contribution to the production process such as Raw water,
treatments or distribution.
For a good understanding, a distinction is made in primary and auxiliary (secondary) process steps. By
primary steps runs the water of Raw water towards treatment. Here may be multiple steps in
series. There may also be more steps of the same type are switched one after another, these are
then numbered in the direction of the water flow. Supporting processes work for one or more steps
in the same group. Per group are only the established steps possible. The functional title gives the
function of a part of the process from that operation.
A module is a part of a step as a filter, a pump (Group), and (between) reservoir to decoupling of
process steps. Per step there may be different module be used. For a number of steps are specific
module that can be used only in that step.
As the last decomposition there are components that can be divided into valves, measurements and
equipment. The distinction between the components is focused on the function, this is determined
by the component and not by the location of the component in the process or the medium what the
component is edited.
The encoding follows the decomposition and is divided as follows:
-
9.1 Coding System of WASAC
aaaa aan aann
a = alphabet letters
n = numbers digits
Location code/number
Proces group
Module + number
Component + number
Location oriented
Process oriented
a aa
Proces step
4 characters
1 character
2 + 1 characters
2 + 2 characters
2 characters
Functional oriented
nn
Branche number 2 characters
-
9.1 Coding System of WASAC
4 ANNEX I: Tables location-oriented code
4.1 Branch number Description code part: characters: Note:
BUGESERA 16
GICUMBI 09
GIKONDO 23
HUYE 06
KACYIRU 20
KANOMBE 25
KARONGI 12
MUHANGA 02
MUSANZE 04
NGOMA 08
MUHIMA 24
NYAGATARE 15
NYAMAGABE 11
NYAMIRAMBO 21
NYANZA 07
NYARUGENGE 26
REMERA 22
RUBAVU 03
RUHANGO 17
RUSIZI 05
RWAMAGANA 10
-
9.1 Coding System of WASAC
4.2 Location name
Description code part: characters: Note:
Treatment plant Byimana TPBY Gikondo (23)
Treatment plant Cyampirita TPCY Nyagatare (15)
Treatment plant Cyondo TPCO Nyagatare (15)
Treatment plant Cyunyu TPCU Rusizi (05)
Treatment plant Gihengeri TPGI Nyagatare (15)
Treatment plant Gihira TPGH Rubavu (03)
Treatment plant Gihogwe TPGO Nyarugenge (26)
Treatment plant Gihuma TPGU Muhunga (02)
Treatment plant Jali TPJA Nyarugenge (26)
Treatment plant Kadahokwa TPKA Huye (06)
Treatment plant Kanwiriri TPKN Nyagatare (15)
Treatment plant Kanyabusage TPKY Ngoma (08)
Treatment plant Karenge TPKR Kanombe (25)
Treatment plant Kimisagara TPKI Nyamirambo (21)
Treatment plant Kizanye Mpazi TPKZ Nyarugenge (26)
Treatment plant Mburabuturo TPMB Nyarugenge (26)
Treatment plant Mpanga TPMP Nyanza (07)
Treatment plant Muhazi TPMU Rwamagana (10)
Treatment plant Mutobo TPMU Musanze (04)
Treatment plant Ngenda TPNG Bugesera (16)
Treatment plant Nyagatare TPNY Nyagatatre (15)
Treatment plant Nyamabuye TPNA Gicumbi (09)
Treatment plant Nzove TPNZ Nyarugenge (26)
Treatment plant Rawasaburo TPRA Ngoma (08)
Treatment plant Rwampara TPRW Nyamirambo (21)
Treatment plant Rwasama TPRS Nyagatare (15)
Treatment plant Rwabigeyo A TPRB Nyagatare (15)
Treatment plant Rwabigeyo B TPRI Nyagatare (15)
-
9.1 Coding System of WASAC
Treatment plant Tovu TPTO Nyagatare (15)
Treatment plant ?? TP??
Booster pump station Kabindi BPKA Nyagatare (15)
Booster pump station Rwimondo BPRW Nyagatare (15)
Booster pump station ?? BP??
Reservoir Ntora RSNT Kacyiru (20)
Reservoir New Mt. Kigali Reservoir RSKR Nyamirambo (21)
Reservoir ?? RS??
District Meter Area (DMA) 0-99 DM01 Maximum is 99
DMA Kibagabaga DM01 Remera (22)
DMA Free Trade Zone / Masoro DM02 Remera (22)
DMA Kinyinya DM03 Remera (22)
DMA Bumbogo DM04 Remera (22)
DMA Nyarutarama DM05 Remera (22)
DMA Kimironko 1 DM06 Remera (22)
DMA Kimironko 2 DM07 Remera (22)
DMA Bibare DM08 Remera (22)
DMA Amahoro Stadium DM09 Remera (22)
DMA Nyakabanda DM10 Remera (22)
DMA Rukiri DM11 Remera (22)
DMA Nyabasindu DM12 Remera (22)
DMA Ndera DM01 Kanombe (25)
DMA Masaka & Rusheshe DM02 Kanombe (25)
DMA Kabuga DM03 Kanombe (25)
DMA Samaduha DM04 Kanombe (25)
DMA Gasogi DM05 Kanombe (25)
DMA Gishore DM06 Kanombe (25)
DMA Gako & Ayabaraya DM07 Kanombe (25)
DMA Kamashashi & Nyarugunga DM08 Kanombe (25)
DMA Buanza DM09 Kanombe (25)
-
9.1 Coding System of WASAC
DMA Kabeza DM10 Kanombe (25)
DMA Rwimbogo & Nonko DM11 Kanombe (25)
DMA Muyumbu DM12 Kanombe (25)
Location code:
The location code consists of 6 letters and/or numbers, they are combined from the list with branch
numbers and location names. This combination is unique.
On the same site multiple processes are possible. Also it may be that there are different types are
present in the same location (e.g. a water tower on a water treatment location) the location will then
get the broadest indication (in the example, so water treatment).
The numbering of the DMAs (District Meter Areas) are rising to a maximum of 99.
5 ANNEX 2: Process groups Description code: characters: Note:
Raw water R
Boreholes B
treatment T
Distribution D
Chemicals C
General G
-
9.1 Coding System of WASAC
6 ANNEX 3: Process steps Description PROCESS STEP
Procesgroup Raw water: ---
Raw water transport RT
River RV
Raw water reservoir RR
Water hammer tank WH
Dam DM
Procesgroup treatment: ---
Disinfection DI
Filtration FT
Clarifier CF
Treatment supporting ---
Hypochlorite make HM
Chlorine make CM
Disinfection DS
Backwashing BW
Algae floc dosing1 AF
Process Group Distribution: D ---
Treated water transport TT
Treated water reservoir TR
Disinfection DS
Meter chamber MC
Water hammer tank WH
General: G
Common elements CE
-
9.1 Coding System of WASAC
Description PROCESS STEP
Electrical supply ES
7 ANNEX 3: Modules Description MODULE
River RVx
Raw water intake RIx
Mixing chamber MCx
Dosing DOx
Clarifier CFx
Lamella separator LMx
Filter FLx
Quality monitoring QMx
Pipe PPx
Pump group PGx
Distribution group DGx
Reservoir RSx Also Sump and tank
Tank TKx
Unit UNx Also: merged unit
Lagoon LGx rinse water pond
Water tower WTx
Dam DMx
Customer meters CMx
Meter Chamber MCx
8 ANNEXES 4: Components Name Component
Valves:
-
9.1 Coding System of WASAC
Electrical operated valve EVxx
Manuel operated valve MVxx
Pneumatic operated valve PVxx
Measurements:
Pressure indicator PIxx
Pressure transmitter PTxx
Pressure switch PSxx
Level indicator LIxx
Level transmitter LTxx
Level switch LSxx
Ph-transmitter POxx
Quality instrument QIxx
Chlorine instrument CIxx
Turbidity instrument TIxx
TDS instrument DIxx
Conductivity sensor GOxx
Hardness sensor HOxx
Oxygen sensor ZOxx
Flow indicator FIxx
Flow transmitter FTxx
Flow meter pulse FQxx
Flow switch FSxx
Secondary:
Energy monitoring EMxx
Intrusion detector IBxx
Current measurement IMxx
-
9.1 Coding System of WASAC
Power measurement PMxx
Temperature measurement TMxx
Voltage measurement UMxx
Regulator XRxx
UPS UPxx
Data logger (RTU/PLC) DLxx
Tools:
Centrifuge CFxx
Air compressor ACxx
Pump PPxx
Mixer MXxx
Dosing pump DPxx
Scraper SPxx
Hypochlorite generator HGxx
Secondary:
Transformer TFxx
UPS unit UPxx