CO2 cooling pressure drop measurements R. Bates, R. French, G. Viehhauser, S. McMahon.
-
Upload
ann-mckinney -
Category
Documents
-
view
221 -
download
2
Transcript of CO2 cooling pressure drop measurements R. Bates, R. French, G. Viehhauser, S. McMahon.
CO2 cooling pressure drop measurements
R. Bates, R. French, G. Viehhauser, S. McMahon
Objective
• Measure the pressure drops over our cooling pipes– Aim to measure straight pipe and compare to calculations– Our stave with its few wiggles– Pixel disk 1/12th – Change of pipe ID to understand this effect
• Measure the HTC of the CO2 system• Measure
– for warm running (commissioning)– cold operation (T=-25 to -35C)– function of massflow, power load, input vapour quality, pipe
inner diameter, pipe wiggles
Items to measure• Vapour quality at input 0 to x – we should understand the effect of a non-
zero Vi
• Vapour quality at output = 0.5• Enthalpy = 310J/g (at -35C) • Power = 170/100W (short and long stave) & ~100W for 1/12th of Pixel disk
– Detector power = 20W– Includes EOS card– Linear power density along pipe = 0.67 & 0.4 W/cm
• Required Mass flow = 1.2/0.7 g/s• Input fluid temperature ideally -35C• Measure room temperature operations as well
– Available enthalpy halved so mass flow needs to double– No detector current and therefore run-away less of a concern
Pixel disks Cooling pipe geometries
• 2 possible geometries
• HEX modules = 9W• Quad = 6W• Total = 9*9 + 3*6 = 99W + EOS card + Leakage current
CERN Blg158 CO2 cooling test stand(possibly a blow-off system at CERN as well)
• LHCb type Accumulator system
• PLC/SCADA control• PVSS interface
Schematic• Mass flow 0.5 to 15 g/s• Saturation temperature -27C to 25C• Input vapour quality 0.05 to 1
P-H diagram
• Pressure in 1,4,4’,5,6 defined by Acumulator
• 1 to 2 pump increases pressure, plus adds heat
• Cold liquid adjusted to required input enthalpy by heater to get to 3‘
• 3’ to 4 via needle valve• 4 to 5 boiling in stave• 5 to 6 cooling in HEX
Requirements on our side• VCR ½ inch connections• Tested to 120bar
– At start up go to almost 70Bar• Insulated
– Put in a box full of soft foam– Use the box as a transport box
• Insulated box has a relief valve > 100 mbar over pressure– Prevent CO2 pressure build up in box if stave leaks– Sized to allow CO2 out if stave ruptures without pressure build up in external box
• Leak tested to < 10-4 mbar.l.s-1
• Inlet needle valve• Temperature and pressure sensors• Power load heaters and power supplies• DAQ
Pipes that we have
• Range of pipes as staves available– S/S 3.175 mm OD; 2.775mm ID; 0.2mm wall thickness– Ti 2.275 mm OD; 2.035mm ID; 0.12mm wall thickness
• Lengths of 1.2m with and without SMC bend– Also need to add a pixel pipe
• For pipe as heater need low resistivity connection to pipe.– Copper blocks fabricated and soldered to pipe– Need to check connection fine
Using the pipe as a heaterS/S Titanium (Ti-6Al-4V)
Resistivity/ Ohm-cm 7.4e-5 4.2e-5
Outer wall diameter/ mm 3.175 2.275
Wall thickness/ mm 0.2 0.12
Resistance/ Ohm/cm 3.96e-3 5.17e-3
Module + EOS Power on stave/ W
150 150
Sensor power/ W 20 20
Total power/ W 170 170
Current/ A 13.4 11.7
Voltage/ V 12.7 14.5
Assumes a stave length of 120cmPipe heater length = 2 x stave lengthFor safety put HV in the centre of the pipe and GND at each endFor SCT cooling tests using Delta Elektronika SM- D7020-D: 35V/20A
HTC• To measure HTC need the fluid temperature and the inside pipe temperature in
heat path.• Fluid temperature = outside pipe temperature for zero heat flux; i.e. Thermally
Isolated– Measure outside pipe temperature with NTC.
• For heat load use pipe• Inside pipe temperature = Measure outside pipe temperature in heated section
and use knowledge of k_S/S or k_Ti
– Measure outside pipe temperature with NTC.• HTC f(x) => requires distributed heat load
– Add electrical connections along pipe and bridge gap with copper braid. 8cm sections and 2cm gaps.
– Power density increases a little– S/S: 15A,with ΔV= 0.5V per unit– Ti: 13A,with ΔV= 0.5V per unit
Other items• Safety values
– Still to do– Used Swagelok for C3F8/C2F6 have range to suite pressure
• DAQ– Have system for Temp/Pressure (Voltage) measurements based on Analogue
devices FPGA evaluation board with Labview software– Requires a little work to duplicate.
• Insulated box– R.F. has identified such, use as transport box
• Relief valve– Still to do
• Flow meter/Temperature sensors/Pressure sensors– Flow meter in Oxford– Temperature sensors from
Measurement matrix for stavesTmax= -35°C Mass flow [g/s]
Linear power density [W/cm] 0.7 1.2
0.8 3 1
0.7 2 1
0.6 2 2
0.5 2 3
0.4 1 3
Tmax= -30°C Mass flow [g/s]
Linear power density [W/cm]
0.7 1.2
0.8 3 2
0.7 3 2
0.6 3 3
0.5 3 3
0.4 2 3
Tmax= -25°C Mass flow [g/s]Linear power density [W/cm]
0.7 1.2
0.8 3 20.7 3 20.6 3 30.5 3 30.4 2 3
Tmin=15°C Mass flow [g/s]
Linear power density [W/cm]
1.4 2.4
0.8 3 2
0.7 3 1
0.6 3 2
0.5 2 3
0.4 1 3
L.P.D Short strips = 0.67 W/cm; Long strips =0.4 W/cm