Operating principle of the closing resistor: Step 1: CB fully open Step 2: Closing (beginning of insertion) Step 3: Closing (end of insertion) Step 4: CB fully closed (in service) R Resistor Contact Arcing Contact Main Contact R Resistor Contact Open – Resistor in Circuit Arcing Contact Closed Main Contact R Arcing Contact Closed Main Contact Resistor Contact Closed (5-8 ms after arcing contact) - Resistor bypassed R Arcing Contact Closed Main Contact Closed Resistor Contact Closed – Resistor bypassed

description

elec

Transcript of Closing Resistor

Page 1: Closing Resistor

Operating principle of the closing resistor:

Step 1: CB fully open

Step 2: Closing (beginning of insertion)

Step 3: Closing (end of insertion)

Step 4: CB fully closed (in service)

R

Resistor Contact

Arcing Contact

Main Contact

R

Resistor Contact Open – Resistor in Circuit

Arcing Contact Closed

Main Contact

R

Arcing Contact Closed

Main Contact

Resistor Contact Closed (5-8 ms after arcing contact) - Resistor bypassed

R

Arcing Contact Closed

Main Contact Closed

Resistor Contact Closed – Resistor bypassed

Page 2: Closing Resistor

Step 5: Opening (Main contact)

Step 6: Opening (Arcing contact)

Step 7: CB fully open (Resistor contact open)

Advantages:1. Resistor switching controlled by main contact system – High reliability2. Resistor always remains bypassed after closing – No possibility of short circuit current

flowing through resistor – No explosions

R

Arcing Contact Closed

Main Contact

Resistor Contact Closed – Resistor bypassed

R

Arcing Contact

Main Contact

Resistor Contact Closed – Resistor bypassed

R

Resistor Contact – Opens >100 ms after arcing contact

Arcing Contact

Main Contact