Climaveneta Europe Company
Transcript of Climaveneta Europe Company
C l i m a v e n e t a
Europe Company
KEY CUSTOMERS- Railways and motorways
- Internet providers
- Armed Forces
- Public sector
- Radio and TV companies
- TELECOM operators
The new high-efficiency air conditioner COOLBLADE adds the finishing touch to the already prominent presence on the world industrial air-conditioning scenario.
It has been designed to satisfy the conditioning requirements of technological rooms, offering features that make it suitable for all the various applications in daily use and from which we demand utmost reliability.
CENTRALLY CONTROLLED SYSTEMS- Banks
- Hotel
- Airports
- Retail and distribution industry
- Museums and Libraries
- Medium/large companies
FINAL APPLICATIONS- Data dispatching nodes
- Call Centers
- Data collecting centers
- Internet centers
- Cloud Computing Centers
Marketing features
Global efficiency
Outstanding performances
Total versatility
Intelligent control
Total compatibility
02
IndexIntroduction
Outstanding performances
Total versatility
Intelligent control
Total compatibility
Technical features
direct expansion air cooled
direct expansion water cooled
chilled water
dual fluid air cooled / dual fluid water cooled
free cooling
04
05
06
07
08
09
09-10
11-12
13-14
15-17
18-19
03
Close air-conditioning means not only compliance with the severest environmental parameters but also with the specific requirements of the site, such as EFFICIENCY, FLEXIBILITY, OPERATING RELIABILITY AND RESPECT FOR THE ENVIRONMENT, which today’s products must satisfy. COOLBLADE has been created to meet all these requirements, exploiting the renowned capacity to supply total quality airconditioning systems
EXCELLENT SHR PERFORMANCEAs is known, electronic equipment develops solely SENSIBLE heat loads and therefore needs dedicated air conditioning to deal with this.
That is why COOLBLADE has been made; to ensure maximum SENSIBLE cooling capacity to the detriment of the LATENT capacity, which would be a sheer waste of energy in these applications.
This is of basic importance for transforming all the supplied energy into a real room temperature control.The result is a high SHR, minimum of 0.85 and a maximum of1. In order to have the utmost SENSIBLE and not latent type of cooling.
EFFICIENCY MOST OF ALLNowadays efficiency is no longer considered as just energy saving in respect of the single unit, but takes into account both the PERFORMANCE of the whole system and its COMPLETE RELIABILITY and MODULARITY over the years.
In offering COOLBLADE as a solution to technological cooling problems, we have been concentrated on the use of known quality parts and integration with BMS (building management systems).
Standard solutions- SCROLL compressors- Thermostat valve with internal pressure equalization- Electronic thermostat (optional)- Standard centrifugal fans- High efficiency EC INVERTER ventilation (optional)- Standard condensation control (DX versions)- Electric reheat or with hot water- Immersed electrode humidifying system- Intelligent dehumidifying system with constant airflow- Semi-graphic control display- Connection to traditional BMS
SHR for TECHNOLOGICALApplication
SHR for COMFORTApplication
Introduction
04
1
5
6
7
8
13
14
9
10
11
3
2
4
5% 40%
95% 60%
MAIN BOARD
MAIN SWITCH
HEATERS
INVERTER EC FANS
COMPRESSOR
DRIER FILTER
LIQUID LINE VALVE
SIGHT GLASS
THERMOSTATIC VALVE
HUMIDIFIER
DEHUMIDIFICATION VALVE
TEMP. & HUMIDITY SENSOR
USER TERMINAL
1
2
3
4
5
6
7
8
9
10
11
13
14
EC INVERTER FANSThis new technology with electronically commutated motor increases the efficiency of the COOLBLADE system, optimizing running costs through state-of-the-art electronics, which are used to change parameters such as:- Flow rate- cooling capacity- External pressure- Noise level
Thereby guaranteeing best operation of the system at any moment, and in particular:1 Continuous adjustment of air flow2 Intelligent and low-noise system of air conveyance
throughout the whole appliance3 Up to 45% saving in the chilled water units
THE MOST COMPACT DESIGNIt is a known fact that the set loads (W/m2) in technological applications are continuously increasing.This is mainly due to the increase in data traffic, giving rise to new equipment with an increasingly greater capacity of transmission, which in turn develops a higher heat load to be dispersed.
This requires ever better performance from the air- conditioning system that should, however, take up as little space as possible, leaving it for the transmission equipment.
COOLBLADE is the air-conditioner with the best SUPPLIED POWER / FOOT PRINT ratio in the market.Because space means value.
Outstanding performances
05
10 18 29 50 70
33,336,0 37,3
40,9 42,5kW / m2
kW /
m2
45,040,035,030,025,020,015,010,0
5,00,0 09 19 29 50 70
31,939,7 38,0
42,5 44,0kW / m2
kW /
m2
45,040,035,030,025,020,015,010,0
5,00,0
2.000
1.800
1.600
1.400
1.200
1.000
800
600
400
0,10 /kW 0,08 /kW 0,05 /kW
DIRECT EXPANSION RANGE
Cooling Capacity (kW) Cooling Capacity (kW)
CHILLED WATER RANGE
EC INVERTER FANS TECHNOLOGYThe most advanced solution for energy saving
EC FANSPlug in fansCentrifugal
Energy saving by EC INVERTER Fans Vs. standard traditional fans
Models Models
euro euro euro
Ene
rgy
savi
ng (y
ear e
uro)
DIRECT EXPANSION WATER COOLEDcooling capacity:8-104kW
The condensation heat is dispersed in an internal plate-type exchanger connected in turn to a water circuit. The water of condensation may come from a well, local water mains or closed circuits such as cooling towers or dry coolers.
DIRECT EXPANSION AIR COOLEDcooling capacity:8-101kW
Refrigerant for heat transfer is used in these direct expansion units.
AIR COOLED DUAL FLUIDWARET COOLED DUAL FLUID
cooling capacity:24-100kW
A P R I M A R Y c i r c u i t , m a d e b y a chilled water circuit (CW) generally connected to an external chiller, plus a SECONDARY circuit in direct expansion (DX) who is considered as BACK-UP. Such units are particulary indicated anywhere RELIABILITY, SAFETY and REDUNDANCY are required.
FREE COOLINGcooling capacity:25-102kW
A PRIMARY direct expansion circuit (DX) plus a SECONDARY chilled water circuit (CW) generally connected to an external dry cooler who is considered as "support" to the primary one. Such units are particulary indicated anywhere EFFICIENCY & ENERGY SAVING are required.
CHILLED WATERcooling capacity:9-220kW
Water coming generally from a chiller is used in these units to transfer the heat. The flow of liquid through the unit water coil is controlled through an internal 2 or 3-way valve.
All-round flexibility seen as a service offered for any type of system. COOLBLADE provides customers with the most flexible solutions.
TYPES OF COOLING
AIRFLOW CONFIGURATIONOVERThe versions called OVER with airoutflow from the top generally have the air intake at the front, rear or bottom of the unit, according to customer choice, and the outflow from the top is along ducts behind suspended ceilings or front delivery plenums.
UNDERThe versions called UNDER with air outflow under the floor have the air intake on the top of the unit taking air directly from the environment or through intake ducts or plenums.
FRONTThe versions called FRONT with air outflow from the upper front pare of the unit have the air intake at the front, so there is no necessity to add an additional front outlet plenum.
Total versatility
OVER unit with front intake and delivery plenum
UNDER unit with top intake and front delivery plenum
OVER unit with top intake and undefloor delivery
FRONT unit with front intake and upper front delivery
OVER unit with front intake and top delivery
OVER unit with underfloor intake and top delivery
OVER unit wi th rear intake and top deliver
06
COOLBLADE has an intelligent electronic heart that allows it to keep a constant control over all the operating and environmental parameters of the site.The COOLBLADE electronic unit is open and configurable to specific user requirements both in site and particularly in the factory with dedicated customisation.
ELECTRONICSSTANDARD FUNCTIONS
■ Semi-graphic display 132 x 64 pixel■ Programmable software■ ICONS Graphic Display■ General alarm■ Automatic reset after blackout■ Compressor FIFO management■ Integral LAN system■ Standby management■ Automatic rotation■ Serious alarms■ Clock card■ Emergency function
MAIN OPTIONS
■ Serial cards for BMS interconnection■ Fire-smoke alarms■ Flooding alarm■ Electronic thermostat control■ SMS alarm
OPTIONS AND MAIN ACCESSORIES
STANDARD
Structure- Multi-speed centrifugal fans- High efficiency Copeland Scroll compressors- High and low side pressure switches- Filters EU4- R-410A Refrigerant- 3-way valves (CW)- Intelligent dehumidifier device with constant airflow
Electronic unit- Semi-graphic display 132 x 64pixel- LAN, integral Local Area Network- Buffer battery- Record 100 alarms
OPTIONALS
Structure- EC INVERTER RADIAL-BLADE fans- Hot water reheat system- FILTER F5-F6-F7-F8 (built into the structure)- Soundproofed plenum- Electronic thermostat- Condensing control
Electronic unit- Serial cards for BMS interfacing- DC INVERTER FAN control software- Driver for electronic thermostat control
07
Intelligent control
08
Total compatibility
COOLBLADE is totally in line with the known policy of full respect for the environment in which we live and for human health and safety. The use of recyclable materials and eco-compatible refrigerants R410A to current standards and legislation, make COOLBLADE a state-of-the-art product in this sense.NOISELESS COLD
Modern telephone applications in residential areas must satisfy increasingly severer requirements in terms of noise pollution. COOLBLADE then propose a large range to satisfy such requests, often customized base on customer requests and site conditions.Main systems are:- Centrifugal fans (STD)- EC INVERTER FANS (OPT) with air flow modulation
capability- Paneling clad in soundproofing material (STD)
ADVANCED SUPERVISION
solutions of compatibility for all the most common BMSs available on the market today, such as:
- MODBUS- METASYS- BACNET- TREND- LONWORKS- SNMP/TCPIP
to satisfy every single customer requirement and to offer the possibility of communicating with the global network.
MAINTENANCE
The design of the new COOLBLADE models was based on the need to simplify routine and extraordinary maintenance work carried out during the lifetime of the product.The refrigerant circuit area is completely separate from the fan area, thereby allowing routine maintenance to be carried out also with the unit in operation.
All servicing operations, even the most critical ones, can be accomplished by a full front access.That is why all the front panels are openable and can even be removed thanks to simple hinges.
In a policy of “total communication” COOLBLADE offers various solutions for interconnection to the most modern BMSs, aimed at satisfying varying needs.
GLOBAL SUPERVISION
firmware protocol for total management of all the air- conditioning parameters, including:
- Detection and transmission of alarms from remote- Change of data from remote- Recording of data and alarms- Sending of SMS via GSM modem
all through dedicated serial cards and supervision systems both in LOCAL and REMOTE mode.
COOLBLADE IS TOTAL COMMUNICATION
RESPECT FOR THE ENVIROMENT
09
TECHNICAL FEATURES:
SAU/O-DAU/O 007÷100
Type: DIRECT EXPANSION, AIR COOLED,upflow or downflow or frontflow version
Available Versions
STD Cooling only without condensation control device
MOD Cooling only with condensation control device through external unit fans regulation
Evolution
UNIT DESCRIPTIONCooling capacity per direct expansion air cooled unit is from 7 to 101kW.Particularly suitable for air-conditioning technological applications, server and CED rooms and all technological applications in general.
■ Unit for installing inside or outside the room to be air-conditioned.
■ Maximum resistance to rust thanks to galvanized sheet metal structures and panels with powder-coated paint finish.The panels are lined with sound-insulating material.
■ The reliability and functionality of the compressor and all the other components are guaranteed by partners who are world leaders in their sector.
■ Double-inlet centrifugal fan units directly coupled and suspended on vibration-isolation mountings.The fans are of the forward-bladed type for maximum efficiency and low noise.
■ Condensation control for maximum low noise (optional).
■ Standard G4 filtering section, F5-F8 optional, under CEN- EN 779 rule with the separation degree 90,1% ASHRAE. The filter is auto extinguishing type.
■ The microprocessor controls the compressor activation times with FIFO logic, thereby regulating the cooling capacity; it also controls the operating alarms with the possibility of interfacing to supervisor and
remote-servicing systems.
■ Electrical box under IEC 204-1/EN60204-1 rules.
■ Refrigerant circuit consisting in the standard version of a thermostat with external valve for internal pressure relief, solenoid valve, high/low pressure safety pressure switch, liquid indicator light and dehydrating filter.
STANDARD UNIT COMPOSITION
2
10
DIMENSION/WEIGHT
Mode
D W
H
mm
mm
mm
kg
600
550
1980
800
700
1980
1000
790
1980
1550
790
1980
1990
890
1980
2490
890
1980
008
130 145 210 215 225 367 385 509 509 449 509 509 529 697 737 757 888 918
SAU/O DAU/O
013 017 020 025 030 035 040 045 035 045 050 055 060 070 080 090 100
Direct Expansion Air Cooled
008
SAU/O DAU/O
013 017 020 025 030 035 040 045 035 045 050 055 060 070 080 090 100Model
Width
Depth
Height
Net Weight
NOTE(1)return air:24℃ relative humidity:50%ESP 20 Pa(2)measured at 1.5m height and 2m front free field(3)For the units SA008-025 configure AC fans, have three kinds of airsupply way , they are upflow delivery, downflow delivery
and front delivery. As the SAO and SAU, the unit with frontflow delivery can be expressed as SAF. And the unit SA025 also can configure EC fans, and the relative technical parameter is not showed in the table, please consult the Climaveneta Factory.
(4)The humidifying capacity and heating capacity showed in the table is standard data, and we can enlarge the capacity in response to the customer requirement.
NOTE: (1)The dimension of units DAU/O 060 070 080 showed in the table is the situation which the unit configure EC and AC fans, and the units dimension is
2100mm×790mm×1980mm when the units fit out belt-driven fans.(2)The dimension of units SAU/O 025 showed in the table is the situation which the unit configure AC fans, and the units dimension is
1000mm×790mm×1980mm when the units fit out belt-driven and EC fans.
Direct Expansion Air Cooled
8.0
7.4
0.92
1
1.87
2200
--
1
--
--
0.30
--
46
3
2.25
3
6
13.2
11.7
0.90
1
3.0
2650
--
1
--
--
0.46
--
42
3
2.25
3
6
17.2
15.9
0.92
1
3.69
4750
--
1
--
--
0.84
--
52
5
3.75
3
6
20.0
18.1
0.91
1
4.2
4750
--
1
--
--
0.84
--
52
5
3.75
3
6
25.0
22.5
0.90
1
4.91
5750
--
1
--
--
1.50
--
51
5
3.75
3
6
30.5
30.0
0.98
1
6.01
8400
1
1
1
2.16
2.07
1.60
65
5
3.75
3
9
35.1
33.5
0.95
1
6.3
9180
1
1
1
2.17
2.26
1.90
67
5
3.75
3
9
40.5
39.7
0.98
1
7.66
13000
--
2
--
3.3
2.35
62
5
3.75
3
15
45.2
44.0
0.97
1
8.64
15200
2
2
2
3.89
3.45
3.59
65
5
3.75
3
15
35.6
35.3
0.99
2
7.27
11550
2
2
2
2.81
2.39
2.14
60
5
3.75
3
15
48.5
43.5
0.90
2
9.62
15200
-
2
2
-
3.45
3.62
65
5
3.75
3
15
50.1
48.5
0.97
2
10.5
15400
2
2
2
3.58
3.45
3.76
65
5
3.75
3
15
56.4
53.2
0.94
2
12.0
14850
2
2
2
3.62
3.82
3.26
65
5
3.75
3
15
63.5
62.0
0.98
2
12.0
21300
2
2
2
6.50
4.74
4.07
56
8
6
3
18
71.7
70.5
0.98
2
13.9
22000
2
2
2
6.50
5.17
4.41
57
8
6
3
18
80.2
78.0
0.98
2
15.9
23000
2
2
2
7.30
5.72
4.99
59
8
6
3
18
92.2
90.5
0.98
2
17.9
27000
-
3
3
-
6.79
6.2
64
8
6
3
18
101.0
98.7
0.98
2
21.9
28000
-
3
3
-
6.79
6.73
65
8
6
3
18
Power supply
Refrigerant
Cooling performances
Total cooling capacity (1)
Sensible cooling capacity (1)
SHR (1)
Compressors
Quantity
Power abs.
Fan
Air flow
N° Centrifugal fans
N° AC fans
N° EC fans
Centrifugal fans power abs.
AC fans power abs.
EC fans power abs.
ESP
Sound pressure level (2)
Humidifier
Humidifying capacity
Power abs.
Heaters
Steps
Power abs.
V/Ph/Hz
kW
kW
kW
m3/h
kW
kW
kW
Pa
dB(A)
kg/h
kW
kW
380/3N/50
R410A
20-350
11
TECHNICAL FEATURES:
SWU/O-DWU/O│ 008÷100
Type: DIRECT EXPANSION, WATER COOLED,upflow or downflow version
Available Versions
Evolution
UNIT DESCRIPTIONCooling capacity per direct expansion water cooled unit is from 8 to 104kW.Particularly suitable for air-conditioning technological applications, server and CED rooms and all technological applications in general.
■ Unit for installing inside or outside the room to be air-conditioned.
■ Maximum resistance to rust thanks to galvanized sheet metal structures and panels with powder-coated paint finish.The panels are lined with sound-insulating material.
■ The reliability and functionality of the compressor and all the other components are guaranteed by partners who are world leaders in their sector.
■ Double-inlet centrifugal fan units directly coupled and suspended on vibration-isolation mountings.The fans are of the forward-bladed type for maximum efficiency and low noise.
■ Condensation control for maximum low noise (optional).
■ Standard G4 filtering section, F5-F8 optional, under CEN- EN 779 rule with the separation degree 90,1% ASHRAE. The filter is auto extinguishing type.
■ The microprocessor controls the compressor activation times with FIFO logic, thereby regulating the cooling capacity; it also controls the operating alarms with the possibility of interfacing to supervisor and
remote-servicing systems.
■ Electrical box under IEC 204-1/EN60204-1 rules.
■ Refrigerant circuit consisting in the standard version of a thermostat with external valve for internal pressure relief, solenoid valve, high/low pressure safety pressure switch, liquid indicator light and dehydrating filter.
STANDARD UNIT COMPOSITION
12
DIMENSION/WEIGHT
Model
D W
H
mm
mm
mm
kg
600
500
1980
161 177 266 280 328 381 399 528 467 528 528 554 725 766 791 888 918
1000
500
1980
1000
790
1980
1550
790
1980
1990
890
1980
2490
890
1980
008
SWU/O DWU/O
010 018 020 025 030 035 045 045035 050 060 065 075 085 095 100
Direct Expansion Water Cooled Unit
Model008
SWU/O DWU/O
010 018 020 025 030 035 045 035 045 050 060 065 075 085 095 100
Width
Depth
Height
Net Weight
Direct Expansion Water Cooled Unit
NOTE(1)return air:24℃ relative humidity:50%ESP 20 Pa(2)measured at 1.5m height and 2m front free field(3)The humidifying capacity and heating capacity showed in the table is standard data, and we can enlarge the capacity in
response to the customer requirement.
Power supply
Refrigerant
Cooling performances
Total cooling capacity (1)
Sensible cooling capacity (1)
SHR (1)
Compressors
Quantity
Power abs. (1)
Plate condenser
Quantity
Water Flow (1)
Total pressure drops (1)
Fan
Air flow
N° Centrifugal fans
N° AC fans
N° EC fans
Centrifugal fans power abs.
AC fans power abs.
EC fans power abs.
ESP
Sound pressure level (2)
Humidifier
Humidifying capacity
Power abs
Heaters
Steps
Power abs.
V/Ph/Hz
kW
kW
kW
l/h
kPa
m3/h
kW
kW
kW
Pa
dB(A)
kg/h
kW
kW
8.0
7.4
0.92
1
1.47
1
1629
8
2750
1
-
1
0.48
-
0.30
50
3
2.25
3
4
10.6
10.1
0.95
1
1.91
1
2148
14
2890
1
-
1
0.48
-
0.36
50
3
2.25
3
4
18.0
17.9
0.99
1
3.26
1
3660
5
5390
2
-
2
0.95
-
0.55
53
5
3.75
3
8
20.9
20.0
0.96
1
3.93
1
4262
7
5580
2
-
2
0.95
-
0.62
53
5
3.75
3
8
26.4
24.8
0.94
1
4.28
1
5274
23
7150
1
1
1
1.70
1.58
0.93
56
5
3.75
3
9
31.6
30.5
0.97
1
5.38
1
6357
30
8800
1
1
1
2.16
2.07
1.77
60
5
3.75
3
9
36.4
34.6
0.95
1
6.24
1
7331
27
9180
1
1
1
2.17
2.26
1.86
60
5
3.75
3
9
47.4
46.2
0.97
1
6.91
1
9343
30
13500
2
2
2
3.89
3.45
3.48
64
5
3.75
3
15
36.8
35.8
0.97
2
6.42
2
2x3718
24
11550
2
2
2
2.81
2.39
2.13
59
5
3.75
3
15
47.4
46.9
0.99
2
8.5
2
2x4896
21
13500
2
2
2
3.58
3.45
3.6
64
5
3.75
3
15
52.7
52.1
0.99
2
8.53
2
2x5262
21
14850
2
2
2
3.58
3.45
3.21
64
5
3.75
3
15
60.5
56.0
0.93
2
10.76
2
2x6130
30
14850
2
2
2
3.62
3.82
3.26
64
5
3.75
3
15
65.8
65.7
1.00
2
10.77
2
2x6584
33
20900
2
2
2
6.50
4.74
5.14
67
8
6
3
18
75.7
74.3
0.98
2
12.38
2
2x7575
30
20900
2
2
2
6.50
5.17
5.14
67
8
6
3
18
85.5
81.2
0.95
2
13.54
2
2x8514
26
21740
2
2
2
27.30
5.72
5.77
67
8
6
3
18
95.5
93.7
0.98
2
15.90
1
19161
31
27500
-
3
3
-
6.79
6.09
67
8
6
3
18
104.7
100.4
0.96
2
19.15
1
21304
39
27500
-
3
3
-
6.79
6.15
67
8
6
3
18
380/3N/50
R410A
20-350
13
Type:CHILLED WATER CHILLED WATER(DUAL COIL)up flow or downflow version
Available Versions
STD Cooling only,with 3-way valve
UNIT DESCRIPTIONCooling capacity per chilled water unit is from 9 to 220kW.
■ Unit for installing inside or outside the room to be air-conditioned.
■ Maximum resistance to rust thanks to galvanized sheet metal structures and panels with powder-coated paint finish.The panels are lined with sound-insulating material.
■ EC inverter radial-blade fans.The fans are of the backward-blade type for maximum efficiency and low noise.
■ Standard G4 filtering section, F5-F8 optional, under CEN- EN 779 rule with the separation degree 90,1% ASHRAE. The filter is auto extinguishing type.
■ The microprocessor controls the operating alarms with the possibility of interfacing to supervisor and
remote-servicing systems.
■ Electrical box under IEC 204-1/EN60204-1 rules.
STANDARD UNIT COMPOSITION
TECHNICAL FEATURES:
SCU/O-D │ 025÷100
SCU/O-B │ 025÷100
D W
H
mm
mm
mm
kg
600
500
1980
1000
500
1980
800
700
1980
1550
790
1980
1990
890
1980
2490
890
1980
2990
890
1980
009
120 130 200 210 260245 290 330 379369 385 396 476 495 516 610 650 680 720 760
011 016 020 030025 035 040 060050 070 080 090 100 120 140 160 180 200 220
SCU/O
14
DIMENSION/WEIGHT
Chilled Water Unit
Model
Width
Depth
Height
Net Weight
Chilled Water Unit
NOTE(1) CONDITION 1
Return air:30℃,RH:30%, the temperature IN/OUT chilled water :10℃/15℃,ESP:20PaCONDITION 2Return air:24℃,RH:50%, the temperature IN/OUT chilled water :7℃/12℃,ESP:20PaReturn air:24℃,relative humidity:50%; the temperature In/Out of chilled water:7℃/12℃;ESP 20 Pa
(2) Measured at 1.5m height and 2m front free field(3) The humidifying capacity and heating capacity showed in the table is standard data, and we can enlarge the capacity
in response to the customer requirement.
220/1N/50 380/3N/50
070
SCU/O
009 011 016 020 030025 035 040 050 060 080 090 100 120 140 160 180 200 220
9.1
9.1
1.00
1567
31.1
8.9
8.9
1.00
1529
30
2750
1
0.34
50
3
2.25
3
4
11.2
11.2
1.00
1923
35.4
11.1
10.6
0.95
1898
34.7
2890
1
0.41
50
3
2.25
3
4
Model
20-350
16.8
16.8
1.00
2884
33.4
16.5
16.5
1.00
2836
32.6
5390
2
0.64
53
5
3.75
3
8
22.7
22.7
1.00
3904
69.7
21.8
20.6
0.94
3732
64.3
5580
2
0.74
53
5
3.75
3
8
28.5
28.5
1.00
4890
43
24.0
21.2
0.88
4140
37.5
6000
1
0.90
57
5
3.75
3
9
33.8
33.8
1.00
5820
64
30.0
26.2
0.87
5160
56.7
7000
1
1.33
61
5
3.75
3
9
38.3
38.3
1.00
6580
75
35.2
30.4
0.86
6070
69
7600
1
1.90
62
5
3.75
3
9
46.0
46.0
1.00
7900
54
41.8
36.9
0.88
7190
50.2
10200
1
2.05
59
5
3.75
3
15
54.7
54.7
1.00
9410
62
51.9
44.3
0.85
8930
58.2
10800
1
2.54
62
5
3.75
3
15
65.2
65.2
1.00
11200
90
60.0
52.0
0.87
10300
76.5
13200
2
2.14
63
5
3.75
3
15
75.1
75.1
1.00
12900
50
69.2
60.7
0.88
11900
45.7
15680
2
3.31
66
8
6
3
18
88.9
88.9
1.00
15280
91
82.1
70.2
0.86
14100
76.1
18000
2
4.53
62
8
6
3
18
100.6
100.6
1.00
17300
65
91.4
79.2
0.87
15700
57.5
20550
2
4.32
63
8
6
3
18
111.3
111.3
1.00
19130
90
100.0
87.9
0.88
17200
68.6
23500
2
4.80
59
8
6
3
18
124.3
124.3
1.00
21360
117
118.0
98.2
0.83
20400
110
23600
2
5.05
59
8
6
3
18
140.2
140.2
1.00
24100
133
141.0
114.0
0.81
24200
134
26200
2
4.68
62
8
6
3
18
157.8
157.8
1.00
27130
99
158.0
127.0
0.80
27100
95
29500
3
6.01
64
10
7.5
3
24
171.8
171.8
1.00
29520
99
173.0
140.0
0.81
29800
100
32200
3
7.80
65
10
7.5
3
24
200.2
200.2
1.00
34420
122
195.0
159.0
0.82
33600
118
38000
3
8.19
63
15
11.25
3
24
216
216
1.00
37130
124
219
173
0.79
37800
128
38000
3
8.22
63
15
11.25
3
24
Power supply
Cooling performances(CONDITION 1)
Total cooling capacity (1)
Sensible cooling capacity (1)
SHR (1)
Water side (CONDITION 1)
Water Flow (1)
Total pressure drops (1)
Cooling performances(CONDITION 2)
Total cooling capacity(2)
Sensible cooling capacity(2)
SHR(2)
Water side(CONDITION 2)
Water flow(2)
Total pressure drops(2)
Fan
Air flow
N° EC fans
EC fans power abs.
ESP
Sound pressure level (2)
Humidifier
Humidifying capacity
Power abs.
Heaters
Steps
Power abs.
V/Ph/Hz
kW
kW
l/h
kPa
kW
kW
l/h
kPa
m3/h
kW
Pa
dB(A)
kg/h
kW
kW
15
Type: DUAL FLUID, AIR COOLED, DUAL FLUID, WATER COOLED upflow or downflow version
Available Versions
STD Cooling only without condensation control deviceMOD Cooling only with condensation control device through external unit fans regulation
UNIT DESCRIPTIONCooling capacity per direct expansion air cooled unit is from 24 to 100kW. Dual fluid unit has two different types dual fluid air cooled and dual fluid water cooled. EC fan is used in dual fluid unit with highest efficiency. Unit will be always running under chilled water mode but it will also automatically change to direct expansion mode while failure of chilled water system happens. So dual fluid unit is the most reliable cooling solution to choose for all the customers.
■ Unit for installing inside or outside the room to be air-conditioned.
■ Maximum resistance to rust thanks to galvanized sheet metal structures and panels with powder-coated paint finish.The panels are lined with sound-insulating material.
■ The reliability and functionality of the compressor and all the other components are guaranteed by partners who are world leaders in their sector.
■ EC inverter radial-blade fans.The fans are of the backward-blade type for maximum efficiency and low noise.
■ Condensation control for maximum low noise (optional).
■ Standard G4 filtering section, F5-F8 optional, under CEN- EN 779 rule with the separation degree 90,1% ASHRAE. The filter is auto extinguishing type.
■ The microprocessor controls the compressor activation times with FIFO logic, thereby regulating the cooling capacity; it also controls the operating alarms with the possibility of interfacing to supervisor and
remote-servicing systems.
■ Electrical box under IEC 204-1/EN60204-1 rules.
■ Refrigerant circuit consisting in the standard version of a thermostat with external valve for internal pressure relief, solenoid valve, high/low pressure safety pressure switch, liquid indicator light and dehydrating filter.
STANDARD UNIT COMPOSITION
16
TECHNICAL FEATURES:
SAU/O-D DAU/O-D│ 025-100
SWU/O-D DWU/O-D│ 025-100
D W
H
mm
mm
mm
kg
1000
790
1980
330
1000
790
1980
381
1000
790
1980
399
1550
790
1980
453
1550
790
1980
513
1550
790
1980
508
1550
790
1980
533
2100
790
1980
746
2100
790
1980
766
2650
790
1980
884
2650
790
1980
914
SAU/O-D DAU/O-D
025 030 035 045 035 050 055 060 080 090 100
SAU/O-D DAU/O-D
025 030 035 045 035 050 055 060 080 090 100Model
400/3N/50
R410A
Air Cooled Dual Fluid
Air Cooled Dual Fluid
DIMENSION/WEIGHT
Model
Width
Depth
Height
Net Weight
16
Power supply
Refrigerant
Cooling performances
Direct expansion total cooling capacity (1)
Direct expansion sensible cooling capacity (1)
Direct expansion SHR (1)
Chilled water total cooling capacity (1)
Chilled water sensible cooling capacity (1)
Chilled water SHR
Compressors
Quantity
Power abs. (1)
Fan
Air flow
N° EC fans
EC fans power abs.
Sound pressure level (2)
Humidifier
Humidifying capacity
Power abs.
Heaters
Steps
Power abs.
V/Ph/Hz
kW
kW
kW
kW
kW
m3/h
kW
dB(A)
kg/h
kW
kW
33.55
33.04
0.98
33.56
32.81
0.98
1
6,75
8800
1
1,80
60
5
3,75
3
9
24.15
23.17
0.96
25.46
24.06
0.95
1
4,93
6600
1
0,89
56
5
3,75
3
9
29.98
29.28
0,98
30.09
29.16
0.97
1
6,01
8250
1
1,60
60
5
3,75
3
9
43
40.35
0.94
53.55
51.2
0,93
1
7,87
14300
2
3,40
64
5
3,75
3
15
37.32
37.08
0.99
42.85
40.82
0.95
2
7,15
11000
2
2,09
59
5
3,75
3
15
48.33
48.12
0.99
53.55
51.2
0.96
2
9,87
14300
2
3,40
64
5
3,75
3
15
55.84
54.15
0.97
55.03
52.86
0.96
2
11,70
14850
2
3,65
64
5
3,75
3
15
63.21
61.49
0.97
69.34
67.95
0.98
2
12,02
19800
3
4,50
67
8
6
3
18
76.77
74.79
0.97
72.02
71.12
0.99
2
15,40
20900
3
5,20
67
8
6
3
18
88
87.72
0.99
97.47
93.89
0.96
2
17,68
26400
3
6,1
67
8
6
3
18
100.33
97.41
0.97
99.35
96.04
0.97
2
21,36
27120
3
6,1
67
8
6
3
18
NOTE(1) Return air:24℃,relative humidity:50%; the temperature In/Out of chilled water:7℃/12℃;ESP 20 Pa(2) Measured at 1.5m height and 2m front free field(3) The humidifying capacity and heating capacity showed in the table is standard data, and we can enlarge the capacity in
response to the customer requirement.
TECHNICAL FEATURES:
SAU/O-D DAU/O-D│ 025-100
SWU/O-D DWU/O-D│ 025-100
17
Water Cooled Dual Fluid
D W
H
mm
mm
mm
kg
1000
790
1980
330
1000
790
1980
381
1000
790
1980
399
1550
790
1980
453
1550
790
1980
513
1550
790
1980
508
1550
790
1980
533
2100
790
1980
746
2100
790
1980
766
2650
790
1980
884
2650
790
1980
914
SWU/O-D DWU/O-D
025 030 035 045 035 050 055 070 080 090 100
SWU/O-D DWU/O-DModel
035025 030 045 035 050 055 070 080 090 100
400/3N/50
R410A
20-350
Water Cooled Dual Fluid
DIMENSION/WEIGHT
Model
Width
Depth
Height
Net Weight
Power supply
Refrigerant
Cooling performances
Direct expansion water cooled total cooling capacity (1)
Direct expansion water cooled sensible cooling capacity (1)
Direct expansion SHR (1)
Chilled water total cooling capacity (1)
Chilled water sensible cooling capacity (1)
Chilled water SHR
Compressors
Quantity
Power abs. (1)
Plate condenser
Quantity
Water Flow(1)
Water pressure dropin DX mode
Total pressure drops
Fan
Air flow
N° EC fans
EC fans power abs.
ESP
Sound pressure level (2)
Humidifier
Humidifying capacity
Power abs.
Heaters
Steps
Power abs.
V/Ph/Hz
kW
kW
kW
kW
kW
l/h
kPa
kPa
m3/h
kW
Pa
dB(A)
kg/h
kW
kW
33.69
32.72
0.97
33.56
32.51
0.97
1
6,11
1
7002
28
35
8800
1
1,80
60
5
3,75
3
9
25.21
23.99
0.93
25.46
24.06
0.95
1
4,30
1
4900
24
26
6600
1
0,89
56
5
3,75
3
9
31.1
30.05
0.97
30.09
29.16
0.97
1
5,40
1
6330
32
35
8250
1
1,60
60
5
3,75
3
9
47.98
47.55
0.99
53.55
51.2
0.96
1
6,94
1
8430
31
46
14300
2
3,40
64
5
3,75
3
15
38.78
38.57
0.99
42.85
40.82
0.95
2
6,44
2
7380
27
30
11000
2
2,09
59
5
3,75
3
15
50.96
50.25
0.99
53.55
51.2
0.96
2
8,61
2
9810
21
46
14300
2
3,40
64
5
3,75
3
15
55.19
53.64
0.97
55.03
52.86
0.96
2
10,55
2
11954
32
46
14850
2
3,65
64
5
3,75
3
15
71.57
70.33
0.98
69.34
67.95
0.98
2
12,28
2
14360
30
26
19800
3
4,50
67
8
6
3
18
77.58
75.16
0.97
72.02
71.12
0.99
2
13,30
2
16132
28
26
20900
3
5,20
67
8
6
3
18
93.31
92.78
0.99
97.47
93.89
0.96
2
16,03
1
18120
33
53
26400
3
6,1
67
8
6
3
18
102.9
99.75
0.97
99.35
96.04
0.97
2
19,33
1
20830
41
53
27120
3
6,1
67
8
6
3
18
NOTE(1) Return air:24℃,relative humidity:50%; the temperature In/Out of chilled water:7℃/12℃;ESP 20 Pa(2) Measured at 1.5m height and 2m front free field(3) The humidifying capacity and heating capacity showed in the table is standard data, and we can enlarge the capacity
in response to the customer requirement.
-5°C
1 2 3 4
1-3°C 6-10°C 14-15°C Ext.Temp.°C
100%ModulatingFreeCooling
100%ForcedFreeCooling
PartialFreeCooling
DirectExpansion
Free Cooling Capacity(kW) System's Energy Consumption (kW)
Type:FREECOOLING, WATER COOLED,upflow or downflow version
Available Versions
STD Cooling with 3-way valve
UNIT DESCRIPTIONCooling capacity per free cooling unit is from 25 to 102kW. Free cooling units fit out EC fans normally.Free cooling unit consists of two coils direct expansion water cooled coil and free cooling coil. Unit can automatically switch working mode according to real outdoor temperature.
FREE COOLING CAPACITY
18
2
TECHNICAL FEATURES:
SWU/O-F DWU/O-F│ 025÷100
19
Model
Model
Direct Expansion Water Cooling
Direct Expansion Water Cooling
DIMENSION/WEIGHT
Width
Depth
Height
Net Weight
mm
mm
mm
kg
D W
H
NOTE(1) Return air:24℃,relative humidity:50%; the temperature In of chilled water:7℃;ESP 20 Pa(2) Measured at 1.5m height and 2m front free field(3) The humidifying capacity and heating capacity showed in the table is standard data, and we can enlarge the
capacity in response to the customer requirement.
33.69
32.72
0.97
32.3
30
0.93
1
6,11
1
7002
46
69
8800
1
1,80
60
5
3,75
3
9
25.21
23.99
0.93
24.9
22.9
0.92
1
4,40
1
4900
47
60
6600
1
0,89
56
5
3,75
3
9
31.1
30.05
0.97
30.6
28.1
0.92
1
5,40
1
6330
70
97
8250
1
1,60
60
5
3,75
3
9
47.88
47.55
0.99
47.3
45.1
0.96
1
8,00
1
8430
66
89
14300
2
3,40
64
5
3,75
3
9
38.78
38.57
0.99
38.1
36.4
0.95
2
6,44
2
7380
49
64
11000
2
2,09
59
5
3,75
3
9
50.96
50.25
0.99
50
46.8
0.94
2
8,41
2
9610
58
84
14300
2
3,40
64
5
3,75
3
9
55.19
53.64
0.97
54.5
50.2
0.92
2
10,96
2
12313
57
95
14850
2
3,65
64
5
3,75
3
9
71.57
70.33
0.98
70.3
65.5
0.93
2
12,28
2
14360
65
85
19800
3
4,50
67
8
3,75
3
18
77.58
75.16
0.97
76.7
70
0.91
2
13,30
2
16133
70
91
20900
3
5,20
67
8
3,75
3
18
93.31
92.78
0.99
91.8
86.3
0.94
16,03
1
18120
55
80
26400
3
6,1
67
8
3,75
3
18
102.9
99.75
0.97
102
92.5
0.91
2
19,33
1
20830
68
99
27120
3
6,1
67
8
3,75
3
18
Power supply
Refrigerant
Cooling performances
Direct expansion mode total cooling capacity(1)
Direct expansion mode sensible cooling capacity(1)
Direct expansion SHR(1)
Freecooling mode total cooling capacity(1)
Freecooling mode sensible cooling capacity(1)
Freecooling mode SHR(1)
Compressors
Quantity
Power abs.(1)
Plate condenser
Quantity
Water Flow(1)
Water pressure dropin DX mode
Freecooling mode water pressuredrop
Fan
Air flow
N° fans
fans power abs.
ESP
Sound pressure level(2)
Humidifier
Humidifying capacity
Power abs.
Heaters
Steps
Power abs.
025 030 035 045 035 050 055 070 080 090 100
380/3N/50
R410A
20-350
V/Ph/Hz
kW
kW
kW
kW
kW
l/h
kPa
kPa
m3/h
kW
Pa
dB(A)
kg/h
kW
kW
SWU/O-F DWU/O-F
1000
790
1980
330
1000
790
1980
381
1000
790
1980
399
1550
790
1980
453
1550
790
1980
513
1550
790
1980
508
1550
790
1980
533
2100
790
1980
746
2100
790
1980
766
2650
790
1980
884
2650
790
1980
914
SWU/O-F DWU/O-F
025 030 035 045 035 050 055 070 080 090 100
B601 CRS/01-12-2014 EN-SHThe products are line with GB/T19413
Climaveneta Company HeadquartersClimaveneta Refrigeration Equipment(Shanghai) Co,Ltd.No.328 Minle RoadTel: +86 021 3757 0088Fax: +86 021 3757 0069
Climaveneta SubsidiariesJinchat Engineering (H.K.) Co, Ltd.Room 2003, CCT Telecom Building, 11 Wo Shing Street, Fotan, N.T., Hong Kong Tel: +852 26871755Fax: +852 26873078