Climaveneta Europe Company

20
Climaveneta Europe Company

Transcript of Climaveneta Europe Company

Page 1: Climaveneta Europe Company

C l i m a v e n e t a

Europe Company

Page 2: Climaveneta Europe Company

KEY CUSTOMERS- Railways and motorways

- Internet providers

- Armed Forces

- Public sector

- Radio and TV companies

- TELECOM operators

The new high-efficiency air conditioner COOLBLADE adds the finishing touch to the already prominent presence on the world industrial air-conditioning scenario.

It has been designed to satisfy the conditioning requirements of technological rooms, offering features that make it suitable for all the various applications in daily use and from which we demand utmost reliability.

CENTRALLY CONTROLLED SYSTEMS- Banks

- Hotel

- Airports

- Retail and distribution industry

- Museums and Libraries

- Medium/large companies

FINAL APPLICATIONS- Data dispatching nodes

- Call Centers

- Data collecting centers

- Internet centers

- Cloud Computing Centers

Marketing features

Global efficiency

Outstanding performances

Total versatility

Intelligent control

Total compatibility

02

Page 3: Climaveneta Europe Company

IndexIntroduction

Outstanding performances

Total versatility

Intelligent control

Total compatibility

Technical features

direct expansion air cooled

direct expansion water cooled

chilled water

dual fluid air cooled / dual fluid water cooled

free cooling

04

05

06

07

08

09

09-10

11-12

13-14

15-17

18-19

03

Page 4: Climaveneta Europe Company

Close air-conditioning means not only compliance with the severest environmental parameters but also with the specific requirements of the site, such as EFFICIENCY, FLEXIBILITY, OPERATING RELIABILITY AND RESPECT FOR THE ENVIRONMENT, which today’s products must satisfy. COOLBLADE has been created to meet all these requirements, exploiting the renowned capacity to supply total quality airconditioning systems

EXCELLENT SHR PERFORMANCEAs is known, electronic equipment develops solely SENSIBLE heat loads and therefore needs dedicated air conditioning to deal with this.

That is why COOLBLADE has been made; to ensure maximum SENSIBLE cooling capacity to the detriment of the LATENT capacity, which would be a sheer waste of energy in these applications.

This is of basic importance for transforming all the supplied energy into a real room temperature control.The result is a high SHR, minimum of 0.85 and a maximum of1. In order to have the utmost SENSIBLE and not latent type of cooling.

EFFICIENCY MOST OF ALLNowadays efficiency is no longer considered as just energy saving in respect of the single unit, but takes into account both the PERFORMANCE of the whole system and its COMPLETE RELIABILITY and MODULARITY over the years.

In offering COOLBLADE as a solution to technological cooling problems, we have been concentrated on the use of known quality parts and integration with BMS (building management systems).

Standard solutions- SCROLL compressors- Thermostat valve with internal pressure equalization- Electronic thermostat (optional)- Standard centrifugal fans- High efficiency EC INVERTER ventilation (optional)- Standard condensation control (DX versions)- Electric reheat or with hot water- Immersed electrode humidifying system- Intelligent dehumidifying system with constant airflow- Semi-graphic control display- Connection to traditional BMS

SHR for TECHNOLOGICALApplication

SHR for COMFORTApplication

Introduction

04

1

5

6

7

8

13

14

9

10

11

3

2

4

5% 40%

95% 60%

MAIN BOARD

MAIN SWITCH

HEATERS

INVERTER EC FANS

COMPRESSOR

DRIER FILTER

LIQUID LINE VALVE

SIGHT GLASS

THERMOSTATIC VALVE

HUMIDIFIER

DEHUMIDIFICATION VALVE

TEMP. & HUMIDITY SENSOR

USER TERMINAL

1

2

3

4

5

6

7

8

9

10

11

13

14

Page 5: Climaveneta Europe Company

EC INVERTER FANSThis new technology with electronically commutated motor increases the efficiency of the COOLBLADE system, optimizing running costs through state-of-the-art electronics, which are used to change parameters such as:- Flow rate- cooling capacity- External pressure- Noise level

Thereby guaranteeing best operation of the system at any moment, and in particular:1 Continuous adjustment of air flow2 Intelligent and low-noise system of air conveyance

throughout the whole appliance3 Up to 45% saving in the chilled water units

THE MOST COMPACT DESIGNIt is a known fact that the set loads (W/m2) in technological applications are continuously increasing.This is mainly due to the increase in data traffic, giving rise to new equipment with an increasingly greater capacity of transmission, which in turn develops a higher heat load to be dispersed.

This requires ever better performance from the air- conditioning system that should, however, take up as little space as possible, leaving it for the transmission equipment.

COOLBLADE is the air-conditioner with the best SUPPLIED POWER / FOOT PRINT ratio in the market.Because space means value.

Outstanding performances

05

10 18 29 50 70

33,336,0 37,3

40,9 42,5kW / m2

kW /

m2

45,040,035,030,025,020,015,010,0

5,00,0 09 19 29 50 70

31,939,7 38,0

42,5 44,0kW / m2

kW /

m2

45,040,035,030,025,020,015,010,0

5,00,0

2.000

1.800

1.600

1.400

1.200

1.000

800

600

400

0,10 /kW 0,08 /kW 0,05 /kW

DIRECT EXPANSION RANGE

Cooling Capacity (kW) Cooling Capacity (kW)

CHILLED WATER RANGE

EC INVERTER FANS TECHNOLOGYThe most advanced solution for energy saving

EC FANSPlug in fansCentrifugal

Energy saving by EC INVERTER Fans Vs. standard traditional fans

Models Models

euro euro euro

Ene

rgy

savi

ng (y

ear e

uro)

Page 6: Climaveneta Europe Company

DIRECT EXPANSION WATER COOLEDcooling capacity:8-104kW

The condensation heat is dispersed in an internal plate-type exchanger connected in turn to a water circuit. The water of condensation may come from a well, local water mains or closed circuits such as cooling towers or dry coolers.

DIRECT EXPANSION AIR COOLEDcooling capacity:8-101kW

Refrigerant for heat transfer is used in these direct expansion units.

AIR COOLED DUAL FLUIDWARET COOLED DUAL FLUID

cooling capacity:24-100kW

A P R I M A R Y c i r c u i t , m a d e b y a chilled water circuit (CW) generally connected to an external chiller, plus a SECONDARY circuit in direct expansion (DX) who is considered as BACK-UP. Such units are particulary indicated anywhere RELIABILITY, SAFETY and REDUNDANCY are required.

FREE COOLINGcooling capacity:25-102kW

A PRIMARY direct expansion circuit (DX) plus a SECONDARY chilled water circuit (CW) generally connected to an external dry cooler who is considered as "support" to the primary one. Such units are particulary indicated anywhere EFFICIENCY & ENERGY SAVING are required.

CHILLED WATERcooling capacity:9-220kW

Water coming generally from a chiller is used in these units to transfer the heat. The flow of liquid through the unit water coil is controlled through an internal 2 or 3-way valve.

All-round flexibility seen as a service offered for any type of system. COOLBLADE provides customers with the most flexible solutions.

TYPES OF COOLING

AIRFLOW CONFIGURATIONOVERThe versions called OVER with airoutflow from the top generally have the air intake at the front, rear or bottom of the unit, according to customer choice, and the outflow from the top is along ducts behind suspended ceilings or front delivery plenums.

UNDERThe versions called UNDER with air outflow under the floor have the air intake on the top of the unit taking air directly from the environment or through intake ducts or plenums.

FRONTThe versions called FRONT with air outflow from the upper front pare of the unit have the air intake at the front, so there is no necessity to add an additional front outlet plenum.

Total versatility

OVER unit with front intake and delivery plenum

UNDER unit with top intake and front delivery plenum

OVER unit with top intake and undefloor delivery

FRONT unit with front intake and upper front delivery

OVER unit with front intake and top delivery

OVER unit with underfloor intake and top delivery

OVER unit wi th rear intake and top deliver

06

Page 7: Climaveneta Europe Company

COOLBLADE has an intelligent electronic heart that allows it to keep a constant control over all the operating and environmental parameters of the site.The COOLBLADE electronic unit is open and configurable to specific user requirements both in site and particularly in the factory with dedicated customisation.

ELECTRONICSSTANDARD FUNCTIONS

■ Semi-graphic display 132 x 64 pixel■ Programmable software■ ICONS Graphic Display■ General alarm■ Automatic reset after blackout■ Compressor FIFO management■ Integral LAN system■ Standby management■ Automatic rotation■ Serious alarms■ Clock card■ Emergency function

MAIN OPTIONS

■ Serial cards for BMS interconnection■ Fire-smoke alarms■ Flooding alarm■ Electronic thermostat control■ SMS alarm

OPTIONS AND MAIN ACCESSORIES

STANDARD

Structure- Multi-speed centrifugal fans- High efficiency Copeland Scroll compressors- High and low side pressure switches- Filters EU4- R-410A Refrigerant- 3-way valves (CW)- Intelligent dehumidifier device with constant airflow

Electronic unit- Semi-graphic display 132 x 64pixel- LAN, integral Local Area Network- Buffer battery- Record 100 alarms

OPTIONALS

Structure- EC INVERTER RADIAL-BLADE fans- Hot water reheat system- FILTER F5-F6-F7-F8 (built into the structure)- Soundproofed plenum- Electronic thermostat- Condensing control

Electronic unit- Serial cards for BMS interfacing- DC INVERTER FAN control software- Driver for electronic thermostat control

07

Intelligent control

Page 8: Climaveneta Europe Company

08

Total compatibility

COOLBLADE is totally in line with the known policy of full respect for the environment in which we live and for human health and safety. The use of recyclable materials and eco-compatible refrigerants R410A to current standards and legislation, make COOLBLADE a state-of-the-art product in this sense.NOISELESS COLD

Modern telephone applications in residential areas must satisfy increasingly severer requirements in terms of noise pollution. COOLBLADE then propose a large range to satisfy such requests, often customized base on customer requests and site conditions.Main systems are:- Centrifugal fans (STD)- EC INVERTER FANS (OPT) with air flow modulation

capability- Paneling clad in soundproofing material (STD)

ADVANCED SUPERVISION

solutions of compatibility for all the most common BMSs available on the market today, such as:

- MODBUS- METASYS- BACNET- TREND- LONWORKS- SNMP/TCPIP

to satisfy every single customer requirement and to offer the possibility of communicating with the global network.

MAINTENANCE

The design of the new COOLBLADE models was based on the need to simplify routine and extraordinary maintenance work carried out during the lifetime of the product.The refrigerant circuit area is completely separate from the fan area, thereby allowing routine maintenance to be carried out also with the unit in operation.

All servicing operations, even the most critical ones, can be accomplished by a full front access.That is why all the front panels are openable and can even be removed thanks to simple hinges.

In a policy of “total communication” COOLBLADE offers various solutions for interconnection to the most modern BMSs, aimed at satisfying varying needs.

GLOBAL SUPERVISION

firmware protocol for total management of all the air- conditioning parameters, including:

- Detection and transmission of alarms from remote- Change of data from remote- Recording of data and alarms- Sending of SMS via GSM modem

all through dedicated serial cards and supervision systems both in LOCAL and REMOTE mode.

COOLBLADE IS TOTAL COMMUNICATION

RESPECT FOR THE ENVIROMENT

Page 9: Climaveneta Europe Company

09

TECHNICAL FEATURES:

SAU/O-DAU/O 007÷100

Type: DIRECT EXPANSION, AIR COOLED,upflow or downflow or frontflow version

Available Versions

STD Cooling only without condensation control device

MOD Cooling only with condensation control device through external unit fans regulation

Evolution

UNIT DESCRIPTIONCooling capacity per direct expansion air cooled unit is from 7 to 101kW.Particularly suitable for air-conditioning technological applications, server and CED rooms and all technological applications in general.

■ Unit for installing inside or outside the room to be air-conditioned.

■ Maximum resistance to rust thanks to galvanized sheet metal structures and panels with powder-coated paint finish.The panels are lined with sound-insulating material.

■ The reliability and functionality of the compressor and all the other components are guaranteed by partners who are world leaders in their sector.

■ Double-inlet centrifugal fan units directly coupled and suspended on vibration-isolation mountings.The fans are of the forward-bladed type for maximum efficiency and low noise.

■ Condensation control for maximum low noise (optional).

■ Standard G4 filtering section, F5-F8 optional, under CEN- EN 779 rule with the separation degree 90,1% ASHRAE. The filter is auto extinguishing type.

■ The microprocessor controls the compressor activation times with FIFO logic, thereby regulating the cooling capacity; it also controls the operating alarms with the possibility of interfacing to supervisor and

remote-servicing systems.

■ Electrical box under IEC 204-1/EN60204-1 rules.

■ Refrigerant circuit consisting in the standard version of a thermostat with external valve for internal pressure relief, solenoid valve, high/low pressure safety pressure switch, liquid indicator light and dehydrating filter.

STANDARD UNIT COMPOSITION

Page 10: Climaveneta Europe Company

2

10

DIMENSION/WEIGHT

Mode

D W

H

mm

mm

mm

kg

600

550

1980

800

700

1980

1000

790

1980

1550

790

1980

1990

890

1980

2490

890

1980

008

130 145 210 215 225 367 385 509 509 449 509 509 529 697 737 757 888 918

SAU/O DAU/O

013 017 020 025 030 035 040 045 035 045 050 055 060 070 080 090 100

Direct Expansion Air Cooled

008

SAU/O DAU/O

013 017 020 025 030 035 040 045 035 045 050 055 060 070 080 090 100Model

Width

Depth

Height

Net Weight

NOTE(1)return air:24℃ relative humidity:50%ESP 20 Pa(2)measured at 1.5m height and 2m front free field(3)For the units SA008-025 configure AC fans, have three kinds of airsupply way , they are upflow delivery, downflow delivery

and front delivery. As the SAO and SAU, the unit with frontflow delivery can be expressed as SAF. And the unit SA025 also can configure EC fans, and the relative technical parameter is not showed in the table, please consult the Climaveneta Factory.

(4)The humidifying capacity and heating capacity showed in the table is standard data, and we can enlarge the capacity in response to the customer requirement.

NOTE: (1)The dimension of units DAU/O 060 070 080 showed in the table is the situation which the unit configure EC and AC fans, and the units dimension is

2100mm×790mm×1980mm when the units fit out belt-driven fans.(2)The dimension of units SAU/O 025 showed in the table is the situation which the unit configure AC fans, and the units dimension is

1000mm×790mm×1980mm when the units fit out belt-driven and EC fans.

Direct Expansion Air Cooled

8.0

7.4

0.92

1

1.87

2200

--

1

--

--

0.30

--

46

3

2.25

3

6

13.2

11.7

0.90

1

3.0

2650

--

1

--

--

0.46

--

42

3

2.25

3

6

17.2

15.9

0.92

1

3.69

4750

--

1

--

--

0.84

--

52

5

3.75

3

6

20.0

18.1

0.91

1

4.2

4750

--

1

--

--

0.84

--

52

5

3.75

3

6

25.0

22.5

0.90

1

4.91

5750

--

1

--

--

1.50

--

51

5

3.75

3

6

30.5

30.0

0.98

1

6.01

8400

1

1

1

2.16

2.07

1.60

65

5

3.75

3

9

35.1

33.5

0.95

1

6.3

9180

1

1

1

2.17

2.26

1.90

67

5

3.75

3

9

40.5

39.7

0.98

1

7.66

13000

--

2

--

3.3

2.35

62

5

3.75

3

15

45.2

44.0

0.97

1

8.64

15200

2

2

2

3.89

3.45

3.59

65

5

3.75

3

15

35.6

35.3

0.99

2

7.27

11550

2

2

2

2.81

2.39

2.14

60

5

3.75

3

15

48.5

43.5

0.90

2

9.62

15200

-

2

2

-

3.45

3.62

65

5

3.75

3

15

50.1

48.5

0.97

2

10.5

15400

2

2

2

3.58

3.45

3.76

65

5

3.75

3

15

56.4

53.2

0.94

2

12.0

14850

2

2

2

3.62

3.82

3.26

65

5

3.75

3

15

63.5

62.0

0.98

2

12.0

21300

2

2

2

6.50

4.74

4.07

56

8

6

3

18

71.7

70.5

0.98

2

13.9

22000

2

2

2

6.50

5.17

4.41

57

8

6

3

18

80.2

78.0

0.98

2

15.9

23000

2

2

2

7.30

5.72

4.99

59

8

6

3

18

92.2

90.5

0.98

2

17.9

27000

-

3

3

-

6.79

6.2

64

8

6

3

18

101.0

98.7

0.98

2

21.9

28000

-

3

3

-

6.79

6.73

65

8

6

3

18

Power supply

Refrigerant

Cooling performances

Total cooling capacity (1)

Sensible cooling capacity (1)

SHR (1)

Compressors

Quantity

Power abs.

Fan

Air flow

N° Centrifugal fans

N° AC fans

N° EC fans

Centrifugal fans power abs.

AC fans power abs.

EC fans power abs.

ESP

Sound pressure level (2)

Humidifier

Humidifying capacity

Power abs.

Heaters

Steps

Power abs.

V/Ph/Hz

kW

kW

kW

m3/h

kW

kW

kW

Pa

dB(A)

kg/h

kW

kW

380/3N/50

R410A

20-350

Page 11: Climaveneta Europe Company

11

TECHNICAL FEATURES:

SWU/O-DWU/O│ 008÷100

Type: DIRECT EXPANSION, WATER COOLED,upflow or downflow version

Available Versions

Evolution

UNIT DESCRIPTIONCooling capacity per direct expansion water cooled unit is from 8 to 104kW.Particularly suitable for air-conditioning technological applications, server and CED rooms and all technological applications in general.

■ Unit for installing inside or outside the room to be air-conditioned.

■ Maximum resistance to rust thanks to galvanized sheet metal structures and panels with powder-coated paint finish.The panels are lined with sound-insulating material.

■ The reliability and functionality of the compressor and all the other components are guaranteed by partners who are world leaders in their sector.

■ Double-inlet centrifugal fan units directly coupled and suspended on vibration-isolation mountings.The fans are of the forward-bladed type for maximum efficiency and low noise.

■ Condensation control for maximum low noise (optional).

■ Standard G4 filtering section, F5-F8 optional, under CEN- EN 779 rule with the separation degree 90,1% ASHRAE. The filter is auto extinguishing type.

■ The microprocessor controls the compressor activation times with FIFO logic, thereby regulating the cooling capacity; it also controls the operating alarms with the possibility of interfacing to supervisor and

remote-servicing systems.

■ Electrical box under IEC 204-1/EN60204-1 rules.

■ Refrigerant circuit consisting in the standard version of a thermostat with external valve for internal pressure relief, solenoid valve, high/low pressure safety pressure switch, liquid indicator light and dehydrating filter.

STANDARD UNIT COMPOSITION

Page 12: Climaveneta Europe Company

12

DIMENSION/WEIGHT

Model

D W

H

mm

mm

mm

kg

600

500

1980

161 177 266 280 328 381 399 528 467 528 528 554 725 766 791 888 918

1000

500

1980

1000

790

1980

1550

790

1980

1990

890

1980

2490

890

1980

008

SWU/O DWU/O

010 018 020 025 030 035 045 045035 050 060 065 075 085 095 100

Direct Expansion Water Cooled Unit

Model008

SWU/O DWU/O

010 018 020 025 030 035 045 035 045 050 060 065 075 085 095 100

Width

Depth

Height

Net Weight

Direct Expansion Water Cooled Unit

NOTE(1)return air:24℃ relative humidity:50%ESP 20 Pa(2)measured at 1.5m height and 2m front free field(3)The humidifying capacity and heating capacity showed in the table is standard data, and we can enlarge the capacity in

response to the customer requirement.

Power supply

Refrigerant

Cooling performances

Total cooling capacity (1)

Sensible cooling capacity (1)

SHR (1)

Compressors

Quantity

Power abs. (1)

Plate condenser

Quantity

Water Flow (1)

Total pressure drops (1)

Fan

Air flow

N° Centrifugal fans

N° AC fans

N° EC fans

Centrifugal fans power abs.

AC fans power abs.

EC fans power abs.

ESP

Sound pressure level (2)

Humidifier

Humidifying capacity

Power abs

Heaters

Steps

Power abs.

V/Ph/Hz

kW

kW

kW

l/h

kPa

m3/h

kW

kW

kW

Pa

dB(A)

kg/h

kW

kW

8.0

7.4

0.92

1

1.47

1

1629

8

2750

1

-

1

0.48

-

0.30

50

3

2.25

3

4

10.6

10.1

0.95

1

1.91

1

2148

14

2890

1

-

1

0.48

-

0.36

50

3

2.25

3

4

18.0

17.9

0.99

1

3.26

1

3660

5

5390

2

-

2

0.95

-

0.55

53

5

3.75

3

8

20.9

20.0

0.96

1

3.93

1

4262

7

5580

2

-

2

0.95

-

0.62

53

5

3.75

3

8

26.4

24.8

0.94

1

4.28

1

5274

23

7150

1

1

1

1.70

1.58

0.93

56

5

3.75

3

9

31.6

30.5

0.97

1

5.38

1

6357

30

8800

1

1

1

2.16

2.07

1.77

60

5

3.75

3

9

36.4

34.6

0.95

1

6.24

1

7331

27

9180

1

1

1

2.17

2.26

1.86

60

5

3.75

3

9

47.4

46.2

0.97

1

6.91

1

9343

30

13500

2

2

2

3.89

3.45

3.48

64

5

3.75

3

15

36.8

35.8

0.97

2

6.42

2

2x3718

24

11550

2

2

2

2.81

2.39

2.13

59

5

3.75

3

15

47.4

46.9

0.99

2

8.5

2

2x4896

21

13500

2

2

2

3.58

3.45

3.6

64

5

3.75

3

15

52.7

52.1

0.99

2

8.53

2

2x5262

21

14850

2

2

2

3.58

3.45

3.21

64

5

3.75

3

15

60.5

56.0

0.93

2

10.76

2

2x6130

30

14850

2

2

2

3.62

3.82

3.26

64

5

3.75

3

15

65.8

65.7

1.00

2

10.77

2

2x6584

33

20900

2

2

2

6.50

4.74

5.14

67

8

6

3

18

75.7

74.3

0.98

2

12.38

2

2x7575

30

20900

2

2

2

6.50

5.17

5.14

67

8

6

3

18

85.5

81.2

0.95

2

13.54

2

2x8514

26

21740

2

2

2

27.30

5.72

5.77

67

8

6

3

18

95.5

93.7

0.98

2

15.90

1

19161

31

27500

-

3

3

-

6.79

6.09

67

8

6

3

18

104.7

100.4

0.96

2

19.15

1

21304

39

27500

-

3

3

-

6.79

6.15

67

8

6

3

18

380/3N/50

R410A

20-350

Page 13: Climaveneta Europe Company

13

Type:CHILLED WATER CHILLED WATER(DUAL COIL)up flow or downflow version

Available Versions

STD Cooling only,with 3-way valve

UNIT DESCRIPTIONCooling capacity per chilled water unit is from 9 to 220kW.

■ Unit for installing inside or outside the room to be air-conditioned.

■ Maximum resistance to rust thanks to galvanized sheet metal structures and panels with powder-coated paint finish.The panels are lined with sound-insulating material.

■ EC inverter radial-blade fans.The fans are of the backward-blade type for maximum efficiency and low noise.

■ Standard G4 filtering section, F5-F8 optional, under CEN- EN 779 rule with the separation degree 90,1% ASHRAE. The filter is auto extinguishing type.

■ The microprocessor controls the operating alarms with the possibility of interfacing to supervisor and

remote-servicing systems.

■ Electrical box under IEC 204-1/EN60204-1 rules.

STANDARD UNIT COMPOSITION

TECHNICAL FEATURES:

SCU/O-D │ 025÷100

SCU/O-B │ 025÷100

Page 14: Climaveneta Europe Company

D W

H

mm

mm

mm

kg

600

500

1980

1000

500

1980

800

700

1980

1550

790

1980

1990

890

1980

2490

890

1980

2990

890

1980

009

120 130 200 210 260245 290 330 379369 385 396 476 495 516 610 650 680 720 760

011 016 020 030025 035 040 060050 070 080 090 100 120 140 160 180 200 220

SCU/O

14

DIMENSION/WEIGHT

Chilled Water Unit

Model

Width

Depth

Height

Net Weight

Chilled Water Unit

NOTE(1) CONDITION 1

Return air:30℃,RH:30%, the temperature IN/OUT chilled water :10℃/15℃,ESP:20PaCONDITION 2Return air:24℃,RH:50%, the temperature IN/OUT chilled water :7℃/12℃,ESP:20PaReturn air:24℃,relative humidity:50%; the temperature In/Out of chilled water:7℃/12℃;ESP 20 Pa

(2) Measured at 1.5m height and 2m front free field(3) The humidifying capacity and heating capacity showed in the table is standard data, and we can enlarge the capacity

in response to the customer requirement.

220/1N/50 380/3N/50

070

SCU/O

009 011 016 020 030025 035 040 050 060 080 090 100 120 140 160 180 200 220

9.1

9.1

1.00

1567

31.1

8.9

8.9

1.00

1529

30

2750

1

0.34

50

3

2.25

3

4

11.2

11.2

1.00

1923

35.4

11.1

10.6

0.95

1898

34.7

2890

1

0.41

50

3

2.25

3

4

Model

20-350

16.8

16.8

1.00

2884

33.4

16.5

16.5

1.00

2836

32.6

5390

2

0.64

53

5

3.75

3

8

22.7

22.7

1.00

3904

69.7

21.8

20.6

0.94

3732

64.3

5580

2

0.74

53

5

3.75

3

8

28.5

28.5

1.00

4890

43

24.0

21.2

0.88

4140

37.5

6000

1

0.90

57

5

3.75

3

9

33.8

33.8

1.00

5820

64

30.0

26.2

0.87

5160

56.7

7000

1

1.33

61

5

3.75

3

9

38.3

38.3

1.00

6580

75

35.2

30.4

0.86

6070

69

7600

1

1.90

62

5

3.75

3

9

46.0

46.0

1.00

7900

54

41.8

36.9

0.88

7190

50.2

10200

1

2.05

59

5

3.75

3

15

54.7

54.7

1.00

9410

62

51.9

44.3

0.85

8930

58.2

10800

1

2.54

62

5

3.75

3

15

65.2

65.2

1.00

11200

90

60.0

52.0

0.87

10300

76.5

13200

2

2.14

63

5

3.75

3

15

75.1

75.1

1.00

12900

50

69.2

60.7

0.88

11900

45.7

15680

2

3.31

66

8

6

3

18

88.9

88.9

1.00

15280

91

82.1

70.2

0.86

14100

76.1

18000

2

4.53

62

8

6

3

18

100.6

100.6

1.00

17300

65

91.4

79.2

0.87

15700

57.5

20550

2

4.32

63

8

6

3

18

111.3

111.3

1.00

19130

90

100.0

87.9

0.88

17200

68.6

23500

2

4.80

59

8

6

3

18

124.3

124.3

1.00

21360

117

118.0

98.2

0.83

20400

110

23600

2

5.05

59

8

6

3

18

140.2

140.2

1.00

24100

133

141.0

114.0

0.81

24200

134

26200

2

4.68

62

8

6

3

18

157.8

157.8

1.00

27130

99

158.0

127.0

0.80

27100

95

29500

3

6.01

64

10

7.5

3

24

171.8

171.8

1.00

29520

99

173.0

140.0

0.81

29800

100

32200

3

7.80

65

10

7.5

3

24

200.2

200.2

1.00

34420

122

195.0

159.0

0.82

33600

118

38000

3

8.19

63

15

11.25

3

24

216

216

1.00

37130

124

219

173

0.79

37800

128

38000

3

8.22

63

15

11.25

3

24

Power supply

Cooling performances(CONDITION 1)

Total cooling capacity (1)

Sensible cooling capacity (1)

SHR (1)

Water side (CONDITION 1)

Water Flow (1)

Total pressure drops (1)

Cooling performances(CONDITION 2)

Total cooling capacity(2)

Sensible cooling capacity(2)

SHR(2)

Water side(CONDITION 2)

Water flow(2)

Total pressure drops(2)

Fan

Air flow

N° EC fans

EC fans power abs.

ESP

Sound pressure level (2)

Humidifier

Humidifying capacity

Power abs.

Heaters

Steps

Power abs.

V/Ph/Hz

kW

kW

l/h

kPa

kW

kW

l/h

kPa

m3/h

kW

Pa

dB(A)

kg/h

kW

kW

Page 15: Climaveneta Europe Company

15

Type: DUAL FLUID, AIR COOLED, DUAL FLUID, WATER COOLED upflow or downflow version

Available Versions

STD Cooling only without condensation control deviceMOD Cooling only with condensation control device through external unit fans regulation

UNIT DESCRIPTIONCooling capacity per direct expansion air cooled unit is from 24 to 100kW. Dual fluid unit has two different types dual fluid air cooled and dual fluid water cooled. EC fan is used in dual fluid unit with highest efficiency. Unit will be always running under chilled water mode but it will also automatically change to direct expansion mode while failure of chilled water system happens. So dual fluid unit is the most reliable cooling solution to choose for all the customers.

■ Unit for installing inside or outside the room to be air-conditioned.

■ Maximum resistance to rust thanks to galvanized sheet metal structures and panels with powder-coated paint finish.The panels are lined with sound-insulating material.

■ The reliability and functionality of the compressor and all the other components are guaranteed by partners who are world leaders in their sector.

■ EC inverter radial-blade fans.The fans are of the backward-blade type for maximum efficiency and low noise.

■ Condensation control for maximum low noise (optional).

■ Standard G4 filtering section, F5-F8 optional, under CEN- EN 779 rule with the separation degree 90,1% ASHRAE. The filter is auto extinguishing type.

■ The microprocessor controls the compressor activation times with FIFO logic, thereby regulating the cooling capacity; it also controls the operating alarms with the possibility of interfacing to supervisor and

remote-servicing systems.

■ Electrical box under IEC 204-1/EN60204-1 rules.

■ Refrigerant circuit consisting in the standard version of a thermostat with external valve for internal pressure relief, solenoid valve, high/low pressure safety pressure switch, liquid indicator light and dehydrating filter.

STANDARD UNIT COMPOSITION

16

TECHNICAL FEATURES:

SAU/O-D DAU/O-D│ 025-100

SWU/O-D DWU/O-D│ 025-100

Page 16: Climaveneta Europe Company

D W

H

mm

mm

mm

kg

1000

790

1980

330

1000

790

1980

381

1000

790

1980

399

1550

790

1980

453

1550

790

1980

513

1550

790

1980

508

1550

790

1980

533

2100

790

1980

746

2100

790

1980

766

2650

790

1980

884

2650

790

1980

914

SAU/O-D DAU/O-D

025 030 035 045 035 050 055 060 080 090 100

SAU/O-D DAU/O-D

025 030 035 045 035 050 055 060 080 090 100Model

400/3N/50

R410A

Air Cooled Dual Fluid

Air Cooled Dual Fluid

DIMENSION/WEIGHT

Model

Width

Depth

Height

Net Weight

16

Power supply

Refrigerant

Cooling performances

Direct expansion total cooling capacity (1)

Direct expansion sensible cooling capacity (1)

Direct expansion SHR (1)

Chilled water total cooling capacity (1)

Chilled water sensible cooling capacity (1)

Chilled water SHR

Compressors

Quantity

Power abs. (1)

Fan

Air flow

N° EC fans

EC fans power abs.

Sound pressure level (2)

Humidifier

Humidifying capacity

Power abs.

Heaters

Steps

Power abs.

V/Ph/Hz

kW

kW

kW

kW

kW

m3/h

kW

dB(A)

kg/h

kW

kW

33.55

33.04

0.98

33.56

32.81

0.98

1

6,75

8800

1

1,80

60

5

3,75

3

9

24.15

23.17

0.96

25.46

24.06

0.95

1

4,93

6600

1

0,89

56

5

3,75

3

9

29.98

29.28

0,98

30.09

29.16

0.97

1

6,01

8250

1

1,60

60

5

3,75

3

9

43

40.35

0.94

53.55

51.2

0,93

1

7,87

14300

2

3,40

64

5

3,75

3

15

37.32

37.08

0.99

42.85

40.82

0.95

2

7,15

11000

2

2,09

59

5

3,75

3

15

48.33

48.12

0.99

53.55

51.2

0.96

2

9,87

14300

2

3,40

64

5

3,75

3

15

55.84

54.15

0.97

55.03

52.86

0.96

2

11,70

14850

2

3,65

64

5

3,75

3

15

63.21

61.49

0.97

69.34

67.95

0.98

2

12,02

19800

3

4,50

67

8

6

3

18

76.77

74.79

0.97

72.02

71.12

0.99

2

15,40

20900

3

5,20

67

8

6

3

18

88

87.72

0.99

97.47

93.89

0.96

2

17,68

26400

3

6,1

67

8

6

3

18

100.33

97.41

0.97

99.35

96.04

0.97

2

21,36

27120

3

6,1

67

8

6

3

18

NOTE(1) Return air:24℃,relative humidity:50%; the temperature In/Out of chilled water:7℃/12℃;ESP 20 Pa(2) Measured at 1.5m height and 2m front free field(3) The humidifying capacity and heating capacity showed in the table is standard data, and we can enlarge the capacity in

response to the customer requirement.

Page 17: Climaveneta Europe Company

TECHNICAL FEATURES:

SAU/O-D DAU/O-D│ 025-100

SWU/O-D DWU/O-D│ 025-100

17

Water Cooled Dual Fluid

D W

H

mm

mm

mm

kg

1000

790

1980

330

1000

790

1980

381

1000

790

1980

399

1550

790

1980

453

1550

790

1980

513

1550

790

1980

508

1550

790

1980

533

2100

790

1980

746

2100

790

1980

766

2650

790

1980

884

2650

790

1980

914

SWU/O-D DWU/O-D

025 030 035 045 035 050 055 070 080 090 100

SWU/O-D DWU/O-DModel

035025 030 045 035 050 055 070 080 090 100

400/3N/50

R410A

20-350

Water Cooled Dual Fluid

DIMENSION/WEIGHT

Model

Width

Depth

Height

Net Weight

Power supply

Refrigerant

Cooling performances

Direct expansion water cooled total cooling capacity (1)

Direct expansion water cooled sensible cooling capacity (1)

Direct expansion SHR (1)

Chilled water total cooling capacity (1)

Chilled water sensible cooling capacity (1)

Chilled water SHR

Compressors

Quantity

Power abs. (1)

Plate condenser

Quantity

Water Flow(1)

Water pressure dropin DX mode

Total pressure drops

Fan

Air flow

N° EC fans

EC fans power abs.

ESP

Sound pressure level (2)

Humidifier

Humidifying capacity

Power abs.

Heaters

Steps

Power abs.

V/Ph/Hz

kW

kW

kW

kW

kW

l/h

kPa

kPa

m3/h

kW

Pa

dB(A)

kg/h

kW

kW

33.69

32.72

0.97

33.56

32.51

0.97

1

6,11

1

7002

28

35

8800

1

1,80

60

5

3,75

3

9

25.21

23.99

0.93

25.46

24.06

0.95

1

4,30

1

4900

24

26

6600

1

0,89

56

5

3,75

3

9

31.1

30.05

0.97

30.09

29.16

0.97

1

5,40

1

6330

32

35

8250

1

1,60

60

5

3,75

3

9

47.98

47.55

0.99

53.55

51.2

0.96

1

6,94

1

8430

31

46

14300

2

3,40

64

5

3,75

3

15

38.78

38.57

0.99

42.85

40.82

0.95

2

6,44

2

7380

27

30

11000

2

2,09

59

5

3,75

3

15

50.96

50.25

0.99

53.55

51.2

0.96

2

8,61

2

9810

21

46

14300

2

3,40

64

5

3,75

3

15

55.19

53.64

0.97

55.03

52.86

0.96

2

10,55

2

11954

32

46

14850

2

3,65

64

5

3,75

3

15

71.57

70.33

0.98

69.34

67.95

0.98

2

12,28

2

14360

30

26

19800

3

4,50

67

8

6

3

18

77.58

75.16

0.97

72.02

71.12

0.99

2

13,30

2

16132

28

26

20900

3

5,20

67

8

6

3

18

93.31

92.78

0.99

97.47

93.89

0.96

2

16,03

1

18120

33

53

26400

3

6,1

67

8

6

3

18

102.9

99.75

0.97

99.35

96.04

0.97

2

19,33

1

20830

41

53

27120

3

6,1

67

8

6

3

18

NOTE(1) Return air:24℃,relative humidity:50%; the temperature In/Out of chilled water:7℃/12℃;ESP 20 Pa(2) Measured at 1.5m height and 2m front free field(3) The humidifying capacity and heating capacity showed in the table is standard data, and we can enlarge the capacity

in response to the customer requirement.

Page 18: Climaveneta Europe Company

-5°C

1 2 3 4

1-3°C 6-10°C 14-15°C Ext.Temp.°C

100%ModulatingFreeCooling

100%ForcedFreeCooling

PartialFreeCooling

DirectExpansion

Free Cooling Capacity(kW) System's Energy Consumption (kW)

Type:FREECOOLING, WATER COOLED,upflow or downflow version

Available Versions

STD Cooling with 3-way valve

UNIT DESCRIPTIONCooling capacity per free cooling unit is from 25 to 102kW. Free cooling units fit out EC fans normally.Free cooling unit consists of two coils direct expansion water cooled coil and free cooling coil. Unit can automatically switch working mode according to real outdoor temperature.

FREE COOLING CAPACITY

18

Page 19: Climaveneta Europe Company

2

TECHNICAL FEATURES:

SWU/O-F DWU/O-F│ 025÷100

19

Model

Model

Direct Expansion Water Cooling

Direct Expansion Water Cooling

DIMENSION/WEIGHT

Width

Depth

Height

Net Weight

mm

mm

mm

kg

D W

H

NOTE(1) Return air:24℃,relative humidity:50%; the temperature In of chilled water:7℃;ESP 20 Pa(2) Measured at 1.5m height and 2m front free field(3) The humidifying capacity and heating capacity showed in the table is standard data, and we can enlarge the

capacity in response to the customer requirement.

33.69

32.72

0.97

32.3

30

0.93

1

6,11

1

7002

46

69

8800

1

1,80

60

5

3,75

3

9

25.21

23.99

0.93

24.9

22.9

0.92

1

4,40

1

4900

47

60

6600

1

0,89

56

5

3,75

3

9

31.1

30.05

0.97

30.6

28.1

0.92

1

5,40

1

6330

70

97

8250

1

1,60

60

5

3,75

3

9

47.88

47.55

0.99

47.3

45.1

0.96

1

8,00

1

8430

66

89

14300

2

3,40

64

5

3,75

3

9

38.78

38.57

0.99

38.1

36.4

0.95

2

6,44

2

7380

49

64

11000

2

2,09

59

5

3,75

3

9

50.96

50.25

0.99

50

46.8

0.94

2

8,41

2

9610

58

84

14300

2

3,40

64

5

3,75

3

9

55.19

53.64

0.97

54.5

50.2

0.92

2

10,96

2

12313

57

95

14850

2

3,65

64

5

3,75

3

9

71.57

70.33

0.98

70.3

65.5

0.93

2

12,28

2

14360

65

85

19800

3

4,50

67

8

3,75

3

18

77.58

75.16

0.97

76.7

70

0.91

2

13,30

2

16133

70

91

20900

3

5,20

67

8

3,75

3

18

93.31

92.78

0.99

91.8

86.3

0.94

16,03

1

18120

55

80

26400

3

6,1

67

8

3,75

3

18

102.9

99.75

0.97

102

92.5

0.91

2

19,33

1

20830

68

99

27120

3

6,1

67

8

3,75

3

18

Power supply

Refrigerant

Cooling performances

Direct expansion mode total cooling capacity(1)

Direct expansion mode sensible cooling capacity(1)

Direct expansion SHR(1)

Freecooling mode total cooling capacity(1)

Freecooling mode sensible cooling capacity(1)

Freecooling mode SHR(1)

Compressors

Quantity

Power abs.(1)

Plate condenser

Quantity

Water Flow(1)

Water pressure dropin DX mode

Freecooling mode water pressuredrop

Fan

Air flow

N° fans

fans power abs.

ESP

Sound pressure level(2)

Humidifier

Humidifying capacity

Power abs.

Heaters

Steps

Power abs.

025 030 035 045 035 050 055 070 080 090 100

380/3N/50

R410A

20-350

V/Ph/Hz

kW

kW

kW

kW

kW

l/h

kPa

kPa

m3/h

kW

Pa

dB(A)

kg/h

kW

kW

SWU/O-F DWU/O-F

1000

790

1980

330

1000

790

1980

381

1000

790

1980

399

1550

790

1980

453

1550

790

1980

513

1550

790

1980

508

1550

790

1980

533

2100

790

1980

746

2100

790

1980

766

2650

790

1980

884

2650

790

1980

914

SWU/O-F DWU/O-F

025 030 035 045 035 050 055 070 080 090 100

Page 20: Climaveneta Europe Company

B601 CRS/01-12-2014 EN-SHThe products are line with GB/T19413

Climaveneta Company HeadquartersClimaveneta Refrigeration Equipment(Shanghai) Co,Ltd.No.328 Minle RoadTel: +86 021 3757 0088Fax: +86 021 3757 0069

Climaveneta SubsidiariesJinchat Engineering (H.K.) Co, Ltd.Room 2003, CCT Telecom Building, 11 Wo Shing Street, Fotan, N.T., Hong Kong Tel: +852 26871755Fax: +852 26873078