Cleanroom Airflow Modeling to Determine the Required …cctr/seminar/seminar4.pdf · Cleanroom...
Transcript of Cleanroom Airflow Modeling to Determine the Required …cctr/seminar/seminar4.pdf · Cleanroom...
Cleanroom Airflow Modeling to Determine the Required Air Change Rate (Phase 1)
Engsysco
Principal Investigator
Wei Sun, P.E.Principal, Director of Engineering
Engsysco, Inc.Ann Arbor, Michigan, USA
Co-Investigators
Sponsored by TC 9.11ASHRAE Annual Meeting
(June 22, 2008, Salt Lake City, UT)
John Mitchell Particle Measuring Systems, Inc.
Boulder, Colorado, USA
Keith B. Flyzik Micro-Clean, Inc.
Bethlehem, Pennsylvania, USA
Shih-Cheng Hu, Ph.D National Taipei University of Technology
Taipei, Taiwan
Junjie Liu, Ph.D Tianjin University
Tianjin, China
Strategies of Cleanroom Fan Energy Conservation
During Operational PhaseUse Flow Demand Control to cut down unnecessary airflow over-supply
During Design PhaseUse Modeling to Determine the Airflow ChangeRate (AHR) to maintain the required cleanliness classification
Air Change Rate - Cleanroom vs. General-Purpose Room
Cleanrooms utilize much higher airflow rates than for general-purpose buildings, energy saving potential from airflow rate reduction is significant.
Type
of F
acili
ties
Air Change Per Hour (ACH)6
General Purpose Spaces – To Meet Heating & Cooling Loads
25 600
Cleanroom Spaces- To Mainly Dilute and Remove Particles
540
10%
15
Cleanroom Air Change Rate - Existing Guidelines
IEST Recommended Practices RP-12
Classification
ISO Class FS-209 Class
Air Change Per Hour
Range 8 100,000 5 – 48 7 10,000 60 – 90 6 1,000 150 – 240 5 100 240 – 480 4 10 300 – 540 3 1 360 – 540 2 360 – 600 1
This practice was based on old experience, in which air change rates were arbitrarily selected Solely based on room cleanliness classes.
High volume airflows have been utilized to meet FS-209 standard, and IEST (RP) for decades
IEST Recommended (RP-12) Air Change Rate For Cleanrooms
5
150
240
300
360360360
4890
240
480
540540
600600
600
100
200
300
400
500
600
700
0 1 2 3 4 5 6 7 8 9
ISO Cleanliness Class
Air
Cha
nge
Per H
our (
AC
H)
Cleanroom Air Change Rate,Existing Practices & Problems
Intuitively, ACR should be based on the required cleanliness class and the activities being performed in the space. Activities that generate higher level of dust would need higher ACH than those that generate at lower level.
Most design/operating engineers choose to obey the existing guideline to avoid being challenged. However, to have a scientific justification to save fan energy, modeling to have a quantitative toolis required.
Cleanroom Air Change Rate,Existing Practices & Problems
Cleanroom airflow rate should be provided “as needed” instead of “picking an arbitrary rate from the table”, a better approach should be similar as those of building heating/cooling load calculations utilized today.
Establish Mathematical Model –Configuration 1 (Conventional Primary Loop)
RA
EA
SA
Q
OAOA+RASA
Space ImpurityConcentration
ExhaustAir
LeakageAir
Particle Generation
Deposition
Cs
Space
D
G
Efficiency Ea
SupplyAir
ReturnAir
MakeupAirCo
CeCs
Cs
HC
FILT
ERCC
AHU Unit
HEP
A
Efficiency Eb
V = Space volume (ft3)OA = Rate of makeup airflow (volume/time)SA = Rate of supply airflow (volume/time)RA = Rate of return airflow (volume/time)EA = Rate of exhaust airflow (volume/time)Q = Rate of leakage airflow (volume/time)Cs = Impurity concentration in space
(parts/volume)Co = Impurity concentration in makeup air
(parts/volume)Es = Filter efficiency (mass basis)G = Rate of impurity generation in space,
averaged throughout the space (parts/volume/time)
D = Rate of impurity deposition from air to surface in space, averaged throughoutthe space (parts/volume/time)
T = TimeEa = AHU filters’ combined efficiency
[ = 1 - (1 - E2)·(1 - E1)]Eb = Ceiling HEPA filter efficiency
Establish Mathematical Model –Configuration 1 (Conventional Primary Loop)
RA
EA
SA
Q
OAOA+RASA
Space Impurity Concentration
ExhaustAir
LeakageAir
Particle Generation
Deposition
Cs
Space
D
G
Efficiency Ea
SupplyAir
ReturnAir
MakeupAirCo
CeCs
Cs
HC
FILT
ERCC
AHU Unit
HEP
A
Efficiency Eb
Indoor Particle Balance Differential Equation
During Time Interval : dt
Room particle count change: dCS
= Supply air particle addition+ Room particle internal generation- Return air particle removal- Exhaust air particle removal+ Leakage air particle removal/addition- Particle deposition on surface
Indoor Particle Balance Differential EquationdtVDdtCQdCV S ⋅⋅dtCEAdtCRAdtVGdtEECRACOA ESHUSOS −⋅⋅−⋅⋅−⋅⋅−⋅⋅+⋅−⋅−⋅⋅+⋅=⋅ )1()1()(
SA = OA+RA, SA = EA+Q+RA
Room Mass Balance Equation
With basic operations, define:
Establish Mathematical Model –Configuration 1 (Conventional Primary Loop)
ar)EEE(Em HUHU =⋅⋅−++
bACRC
DGmEEo
HU =⋅−
+⋅−⋅− )1()1(
Equation to Calculate Room Particle Concentration:
otACRa
oSOST CabeC
abCC ⋅⎟
⎠⎞
⎜⎝⎛+⋅⎟
⎠
⎞⎜⎝
⎛ ⋅⎟⎠⎞
⎜⎝⎛−= ⋅⋅−
Room Particle Concentration is a function of variables of:
If t→∞,
Establish Mathematical Model –Configuration 1 (Conventional Primary Loop)
Room air change rate ACR,Room particle generation G, (data survey)AHU filters’ combined efficiency EU,Room HEPA efficiency EH,Particle deposition rate on exposed surfaces DOutdoor particle concentration CO,Outdoor air/supply air ratio m
)1()(
)1()1()1(
mEEEEmACR
GCmEEC
abC
HUHU
OHU
oST −⋅⋅−++
⋅−+⋅⋅−⋅−
=⋅⎟⎠⎞
⎜⎝⎛=
θ
oHUHU
oHU
oST CmEEEEm
ACRCDGmEE
CabC ⋅
⎥⎥⎥⎥
⎦
⎤
⎢⎢⎢⎢
⎣
⎡
−⋅⋅−++⋅−+⋅−⋅−
=⋅⎟⎠⎞
⎜⎝⎛=
)1()(
)1()1(
Effect of Internal Particle Generation Rate on Room Particle Concentration
Room Particle Concentration versus Air Change Rate (Steady State)
- Effect of Internal Particle Generation Rate
0.1
1.0
10.0
100.0
1,000.0
10,000.0
100,000.0
1,000,000.0
0 100 200 300 400 500 600
Supply Air ACH (Air Change Per Hour)
Con
cent
ratio
n (N
umbe
r of P
artic
les
Per F
T3 )
G=1
G=10
G=100
G=1000
G=10000
Condition:
OA/SA=5%CO=1x106
EU=95%EH=99.97%θ =5%
Internal Particle Generation Rate:G = Rate of impurity generation unit floor area, averaged throughout the space
Unit: Particals/FT3/Min.
Effect of Room HEPA Filter Efficiency on Room Particle Concentration
Room Cleanliness (Concentration) versus Air Change Rate- Effect of Final HEPA Filter Efficiency
0.1
1.0
10.0
100.0
1,000.0
1 10 100 1,000
Supply Air ACH (Air Change Per Hour)
Con
cent
ratio
n (N
umbe
r of P
artic
les
Per F
T3 )
EH=99.97%
EH=99.997%
EH=99.9997%
Condition:
OA/SA=5%CO=1x106
EU=95%G=10θ =5%
Internal Particle Generation Rate:G = Rate of impurity generation unit floor area, averaged throughout the space
Unit: partIcals/FT3/Min.
Effect of Outdoor Air Intake Particle Concentration on Room Particle Concentration
Room Particle Concentration versus Air Change Rate(Steady State)
- Effect of Outdoor Air Intake Particle Concentration
0.1
1.0
10.0
100.0
1,000.0
0 100 200 300 400 500 600
Supply Air ACH (Air Change Per Hour)
Con
cent
ratio
n (N
umbe
r of P
artic
les
Per F
T3 )
Co=100,000
Co=1,000,000
Co=10,000,000
Condition:
OA/SA=10%EU=95%G=10θ = 5%EH = 99.997%
Internal Particle Generation Rate:G = Rate of impurity generation unit floor area, averaged throughout the space
Unit: PartIcals/FT3/Min.
Effect of Outdoor Air Percentage of Supply air on Room Particle Concentration
Room Particle Concentration versus Air Change Rate(Steady State)
- Effect of Outdoor Air Percentage of Supply Air
0.1
1.0
10.0
100.0
1,000.0
0 100 200 300 400 500 600
Supply Air ACH (Air Change Per Hour)
Con
cent
ratio
n (N
umbe
r of P
artic
les
Per F
T3 )
m=5%
m=10%
m=15%
m=20%
Condition:
Co=1x105
EU=95%G=10θ = 5%EH = 99.997%
Internal Particle Generation Rate:G = Rate of impurity generation unit floor area, averaged throughout the space
Unit: PartIcals/FT3/Min.
Model-Based ACH versus IEST RP-Based ACH
Model-Based ACH vs. Recommendation-Based ACH
1
10
100
1,000
10,000
100,000
0 100 200 300 400 500 600
Supply Air ACH (Air Change Per Hour)
Con
cent
ratio
n (N
umbe
r of P
artic
les
Per F
T3 )
G=100, ModelBased
G=1,000, ModelBased
G=5,000, ModelBased
ACH-Low, Rec.Based
ACH-High, Rec.Based
Condition:
OA/SA=10%CO=1x105
EU=95%EH=99.997%θ = 5%
Internal Particle Generation Rate:G = Rate of impurity generation unit floor area, averaged throughout the space
Unit: particals/FT3/Min.
Research Experiments & Validations
Experiments to validate model-based ACR determination have being conducted in three research labs. Final data and conclusions will be published in November, 2008, supported by CEC. Real-world application and software development will start in 2010.Demonstrate cost-effective approaches to lower the Air Change Rate, to reduce fan energy waste.Propose new “Air Change Rate Recommendation” -Group of Charts, to replace existing over-simplified guidelines.
Selected Cleanroom Labs Description
Lab 1Floor Plan
Prep. RoomClass 1,000-10,000
Gown Room(Airlock)Class 100,000
Process RoomClass 1-100
2'x2' FanFilter Unit
2'x4' FanFilter Unit
30"x24' SidewallReturn Grille &Shaft
48"x24' SidewallReturn Grille &Shaft
Symbol
Selected Cleanroom Labs Description
Lab 1Airflow Diagram
1 2 3 4 5 6
7 8 9 10 11
Process RoomClass: 1-100Flow: 4,2874 cfm, 712 ACHSize: 96"x72"x90"(H)
Prep RoomClass: 1,000-10,000Flow: 1,641 cfm, 74 ACH Size: 143"x167"x96"(H)
Gown RoomClass: 100,000Flow: 601 cfm, 77 ACHSize: 96"x88"x96"(H)
AHU
MixingMixing
12
Selected Cleanroom Labs DescriptionLab 2Floor Plan
Testing Cleanroom Class 1-1,000
2'x2' FanFilter Unit
2'x4' FanFilter Unit
48"x12' SidewallReturn Grille &Shaft
Symbol
AirlockClass 10,000
Selected Cleanroom Labs Description
Lab 2Airflow Diagram
DCC DCC
OA
FFU
RA
Particles
MAU
ParticlesNon-unidirectional CleanroomClass: 1 ~ 1,000 Air Velocity = 60~100 FPMTemp.: 72±3°F, R.H.: 45±5%Pressure: +0 ~ 0.08 in.
RA
DCC DCC
OA
FFU
RA
Particles
MAU
ParticlesNon-unidirectional CleanroomClass: 1 ~ 1,000 Air Velocity = 60~100 FPMTemp.: 72±3°F, R.H.: 45±5%Pressure: +0 ~ 0.08 in.
RA
Selected Cleanroom Labs DescriptionLab 3Floor Plan
Research CleanroomClass 1,000-10,000ACH: 5-50
HEPA Supply
HEPA Supply
Return(Pattern 1)
Return(Pattern 1)
Return(Pattern 2)
Return(Pattern 2)
AirlockClass 10,000
Prep. RoomClass 10,000
ACH: 5-30 ACH: 5-30
2'x2' HEPASupply
Symbol
2'x2' Return(Ceiling)
2'x2' Return(Low Sidewall)
1'x1' HEPASupply
1'x1' Return(Ceiling)
Pass-Through
Selected Cleanroom Labs Description
Lab 3Airflow Diagram
HEPA Supply
Ceiling
Supply Air
Return Air
Research CleanroomClass 1,000-10,000ACH: 5-50
HEPA Supply
Supply Air
Return Air
Prep. RoomClass 10,000
HEPA Supply
AirlockClass 10,000
Particle Concentration and Distribution under Various Flow Scenarios
A
B
C
E
HEPA Supply
Floor
Sensor Elevation Panes
Ceiling
Sensor Location Plan
12
3 4
5
6
9
10
8
7
13 15
12
14
11
ParticleGenerationPoint
Research CleanroomClass 100-10,000
Prep. RoomClass 10,000
Lab 3Particle Sensor Locations
Particle Concentration and Distribution under Various Flow Scenarios
Space Velocity Profile under Air Change Rate(Flow Pattern: Ceiling Supply & Ceiling Return)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
5 10 15 20 25 30
Air Change Rate Per Hour
Air
Velo
city
(m/s
)
01-A01-C02-A02-C03-B04-A04-B05-A05-B05-C07-C07-E08-C08-E09-E10-B10-E11-C12-A12-C13-B14-A14-C15-B
Sensor Location
Particle Migration Under Pressure Differential Between Rooms
Sealed Pass-Through
Generate Particles in Prep. Room (Contamination Source)
Measure Particle Migration to Cleanroom (Contamination Receiver)
ΔP
Pneumatic Air-Seal Door
12
3 4
65 7
9
8
Particle Deposition on Exposed Surface
Exposed Surfaces Areas (m2) Areas (F2)Unit Surface Particle Deposition Rate (counts/min·m2)
Walls 39.32 423.2 2.13E+03Ceiling 20.16 217.0 2.07E+03Window Glass 3 32.3 3.37E+03Floor 20.16 217.0 4.28E+03
Total 82.64 889.5 97.61%
Room Space Particle Generation Rate: 9,300,000 counts/min., Duration: 4.75 hours=285 min.
Percentage of Particles Removed through Return Air
0.45%0.11%0.93%
Surface Particle Deposition Rate (counts/min.)
8.38E+044.17E+041.01E+048.63E+04
0.90%
Surface Particle Deposition Percentage
2.39%
6.07E+055.90E+059.60E+051.22E+06
Surface Particle Deposition Rate (counts/m2)
Experimental Validations of Cleanroom Airflow Rate Modeling Approach
(Phase 2)
More Test Data
More Mathematical & Statistical Analysis
Conclusions & Recommendations
To Be Published in CEC Research Report In November, 2008, and Available in ASHRAE Chicago Meeting, January 2009.
Q & A