CITY OF GERMANTOWN
Transcript of CITY OF GERMANTOWN
ADDENDUM NO. 5 – COG2022-04 Elevated Water Tank
Page 1of 1
CITY OF GERMANTOWN ADDENDUM NO.5
COG2022-04 ELEVATED WATER TANK
The attached items on the above-named Project will be updated and adjusted (if required) by this Addendum No. 5 so as to reflect the revision to the Request for Bids: Clarification: Funding: There is a good possibility some of this project will be funded with ARP money, the awarded contractor will be required to provide their DUNS number and be registered with SAM.gov Questions: The following questions have been submitted: Question: What level of containment is required for this project? Answer: Due to the proximity of the tank in relation to surrounding structures and roads, full containment with top cap will be required. The Contractor shall supply, install, operate and maintain a Class 3A shroud conforming to SSPC Guide 6. Question: Will there be a laydown area identified? Answer: A laydown area of approximately 150 feet by 100 feet will either be utilized on the City of Germantown property to the east of the site or on the adjacent subdivision property. The final location will be somewhat dependent on the state of development of the subdivision at the time the laydown area is needed. Question: Could the number of load tests required be verified? Answer: Based on the recommendation of the Geotechnical Engineer, if auger cast piles are utilized with a Factor of Safety of 3, then a static load test is not required.
Plans: E0-1 – Electrical Legend and Notes E1-0 – Electrical – Site Plan E1-1 – Electrical – Building Plans E2-1 0 Electrical Details
In some cases, the above items may be clarifications and further explanations of the Specifications in the Request for Bid. However, any changes to the Specifications will be incorporated in the Contract Documents for this Project. All CONTRACTORS must acknowledge receipt of this Addendum No. 5 on the attached Addendum Acknowledgement form when submitting a Bid for consideration.
Lisa A. Piefer October 4, 2021 Lisa A. Piefer Date Procurement & Risk Director
ADDENDUM ACKNOWLEDGEMENT
Page 1 of 1
ADDENDA ACKNOWLEDGEMENT FORM
Bidder acknowledges receipt of the following addenda (as applicable): Addendum No. 1 __________________________ Dated ________________________ Addendum No. 2___________________________ Dated ________________________ Addendum No. 3 __________________________ Dated ________________________ Addendum No. 4 __________________________ Dated ________________________ Addendum No. 5 __________________________ Dated ________________________ Addendum No. 6 __________________________ Dated ________________________ (Name of Bidder) By: Title:
ELECTRICAL GENERAL NOTES:
1. PROVIDE LABOR AND MATERIALS NECESSARY FOR A COMPLETE AND FULLY OPERATIONAL ELECTRICAL SYSTEM/INSTALLATION.
2. MATERIALS AND INSTALLATION TO COMPLY WITH CODES, LAWS, AND ORDINANCES OF FEDERAL, STATE, AND LOCAL GOVERNING BODIES HAVING JURISDICTION.
3. MATERIALS AND EQUIPMENT TO BE LISTED AND/OR LABELED BY U.L., ETL, CSA, OR ANOTHER RECOGNIZED TESTING LABORATORY.
4. SECURE AND PAY FOR PERMITS, GOVERNMENTAL FEES, TAXES AND LICENSES NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF ALL ELECTRICAL WORK.
5. PREPARE AND SUBMIT TO GOVERNMENTAL AGENCIES, UTILITY COMPANIES, AND LOCAL CODE OFFICIALS, SHOP DRAWINGS AND/OR INSTALLATION DETAILS WHICH ARE REQUIRED BY THESE AGENCIES FOR THEIR APPROVAL.
6. NOTIFY THE ARCHITECT, ENGINEER, AND PROJECT MANAGER IN WRITING OF ANY MATERIALS OR APPARATUS BELIEVED TO BE INADEQUATE, UNSUITABLE, IN VIOLATION OF LAWS, ORDINANCES, RULES, OR REGULATIONS OF THE AUTHORITIES HAVING JURISDICTION.
7. INSTALL ELECTRICAL WORK AS INDICATED ON THE ELECTRICAL CONSTRUCTION DOCUMENTS. SUBMIT SHOP DRAWINGS OF EQUIPMENT TO BE INSTALLED INDICATING FLOOR PLAN LAYOUT, ELEVATIONS, AND DIMENSIONS FOR APPROVAL OF THE ENGINEER PRIOR TO INSTALLATION. MAINTAIN CODE REQUIRED CLEARANCES IN FRONT OF ALL ELECTRICAL EQUIPMENT.
8. CAREFULLY EXAMINE THE CONTRACT DOCUMENTS, MAKE A SCHEDULED ARRANGEMENT WITH THE PROJECT MANAGER TO VISIT THE SITE, AND THOROUGHLY BECOME FAMILIAR WITH THE BUILDING STANDARDS AND LOCAL CONDITIONS RELATING TO THE WORK.
9. PROVIDE TEMPORARY POWER AND WIRING FOR THE PERFORMANCE OF OTHER TRADES, FOR THE ENTIRE PERIOD OF CONSTRUCTION AND REMOVE TEMPORARY WIRING AT THE COMPLETION OF CONSTRUCTION. INCLUDE COSTS FOR ESTABLISHING AND REMOVING TEMPORARY POWER IN BID.
10. ALL MATERIALS AND EQUIPMENT SHALL BE ERECTED, INSTALLED, TOOLED, CONNECTED, CLEANED, ADJUSTED, TESTED, CONDITIONED, AND PLACED IN SERVICE IN ACCORDANCE WITH THE MANUFACTURER'S DIRECTIONS AND RECOMMENDATIONS.
11. UNDER NO CONDITIONS MAY STRUCTURAL WORK BE CUT, EXCEPT AT THE DIRECTION OF THE ARCHITECT/ENGINEER OR THEIR REPRESENTATIVE.
12. SHOP DRAWINGS TO INCLUDE MANUFACTURER'S NAMES, CATALOG NUMBERS, CUTS, DIAGRAMS, AND OTHER SUCH DESCRIPTIVE DATA AS MAY BE REQUIRED TO IDENTIFY AND REVIEW THE EQUIPMENT. SUBMITTALS TO BE IN LOGICAL GROUPS (FOR EXAMPLE ALL LUMINARIES). PARTIAL SUBMITTALS WILL NOT BE REVIEWED.
13. PROVIDE "AS-BUILT" DOCUMENTATION AND HARD COPY REPRODUCIBLE DRAWINGS AT THE COMPLETION OF THE PROJECT AND SUBMIT TO THE ARCHITECT AND THE ENGINEER. AS-BUILT DRAWINGS SHALL INDICATE EXACT CIRCUIT NUMBERS, LOCATIONS OF ALL DEVICES, CEILING FIXTURES, AND RACEWAY FOR LIGHTING, TELECOMMUNICATIONS AND POWER DISTRIBUTION SYSTEMS AS INSTALLED.
14. ALL MATERIAL, EQUIPMENT, WIRING DEVICES, ETC. SHALL BE NEW AND OF COMMERCIAL GRADE UNLESS SPECIFICALLY INDICATED AS EXISTING TO BE REUSED ON DRAWINGS.
15. EXCEPT AS NOTED OTHERWISE, WORK REQUIRED FOR THE ELECTRICAL INSTALLATION AS SHOWN ON DRAWINGS SHALL INCLUDE ALL LABOR, INSTALLATION METHODS, EQUIPMENT, AND MATERIALS AND SHALL BE IN STRICT COMPLIANCE WITH ALL BUILDING STANDARDS.
16. PROVIDE A COMPLETE METAL RACEWAY SYSTEM, FITTINGS AND ENCLOSURES FOR ALL ELECTRICAL WIRING SYSTEMS TO BE INSTALLED FOR THE PROJECT. SYSTEMS SHALL INCLUDE, BUT NOT BE LIMITED TO POWER, COMMUNICATIONS, SECURITY, AND PAGING.
17. MINIMUM CONDUIT SIZE SHALL BE 3/4 INCH FOR GENERAL LIGHTING AND POWER CIRCUITRY UNLESS OTHERWISE INDICATED AND/OR REQUIRED BY CODE.
18. FLEXIBLE CONDUIT CONNECTIONS TO RECESSED LIGHTING FIXTURES SHALL BE MADE WITH FLEXIBLE STEEL CONDUIT, 1/2 INCH MINIMUM, INCLUDING AN INSULATED COPPER GREEN EQUIPMENT GROUNDING CONDUCTOR.
19. WIRE NUMBER 8 AND SMALLER FOR USE IN INTERIOR DRY LOCATIONS SHALL BE TYPE THWN THERMOPLASTIC 600 VOLT INSULATED COPPER CONDUCTORS. FEEDERS AND POWER WIRING NUMBER 6 AND LARGER SHALL BE TYPE THW 600 VOLT INSULATED COPPER. WIRE WHICH IS INSTALLED IN RACEWAY IN MOIST OR DAMP LOCATIONS SHALL BE THW, 600 VOLT INSULATED COPPER CONDUCTORS. NO WIRE SMALLER THAN NUMBER 12 AWG SHALL BE USED FOR LIGHTING OR POWER.
20. BRANCH CIRCUIT HOMERUN WIRING:
A. GENERAL PURPOSE BRANCH CIRCUIT HOMERUNS CONSISTING OF TWO NETWORKS SHALL HAVE PHASE, NEUTRAL AND GROUND CONDUCTORS INCREASED TO NUMBER 10 AWG, THWN AS A MINIMUM. WHERE HOMERUN (ONE OR MORE NETWORKS) EXCEEDS 100 LINEAR FEET, CONDUCTOR SIZE SHALL BE INCREASED ONE TRADE SIZE.
B. ALL BRANCH CIRCUITS, FEEDERS, AND HOMERUNS SHALL BE PROVIDED WITH AN INSULATED COPPER GREEN GROUNDING CONDUCTOR ROUTED IN THE SAME CONDUIT. GROUNDING CONDUCTOR SHALL BE SIZED PER THE REQUIREMENTS OF NEC SECTION 250.
C. HOMERUN LENGTH SHALL BEGIN AT THE CENTRAL POINT OF ALL DISTRIBUTED CIRCUITS TO THE PANELBOARD CIRCUIT BREAKER.
21. ALL CIRCUIT BREAKERS SHALL BE BOLT ON TYPE. AIC RATING OF CIRCUIT BREAKER SHALL MATCH AIC RATING OF PANELBOARD IN WHICH IT IS INSTALLED. THE CONTRACTOR SHALL PROVIDE A TYPEWRITTEN PANEL DIRECTORY FOR EACH PANEL AT THE COMPLETION OF THE PROJECT. EACH CIRCUIT BREAKER SHALL BE LABELED TO IDENTIFY LOAD TYPE AND LOCATION.
22. VERIFY THE CEILING CONSTRUCTION TYPE WITH ARCHITECTURAL DETAILS BEFORE ORDERING LIGHTING FIXTURES IN ORDER TO CONFIRM PROPER MOUNTING.
23. EACH SWITCH, LIGHT, RECEPTACLE, OR OTHER MISCELLANEOUS DEVICE SHALL BE PROVIDED WITH A GALVANIZED OR SHERARDIZED PRESSED STEEL OUTLET BOX OF THE KNOCKOUT TYPE, OF NOT LESS THAN NUMBER 14 U.S. GAUGE STEEL. CONDUITS SHALL BE FASTENED WITH LOCKNUTS AND BUSHINGS AND ALL UNUSED KNOCKOUTS SHALL BE LEFT SEALED. THERE SHALL BE SUFFICIENT ROOM FOR WIRES AND BUSHINGS AND DEEP BOXES SHALL BE INSTALLED WHERE REQUIRED. BOXES SHALL BE SECURELY AND ADEQUATELY SUPPORTED.
24. IN SUSPENDED CEILINGS, SUPPORT CONDUITS AND JUNCTION BOXES DIRECTLY FROM THE STRUCTURAL SYSTEM, DECK OR FRAMING PROVIDED FOR THAT PURPOSE. LIGHTING BRANCH CIRCUIT CONDUITS SHALL NOT BE CLIPPED TO THE CEILING SUPPORT WIRES OR SPLINE UNLESS THE CEILING SYSTEM HAS BEEN SPECIFICALLY DESIGNED FOR THAT PURPOSE AND APPROVAL HAS BEEN GRANTED BY THE ARCHITECT AND THE ENGINEER.
25. NUMBERED CIRCUITS SHOWN ON PLAN ARE FOR THE CONVEYANCE OF DESIGN INTENT ONLY. ACTUAL FIELD CONDITIONS WILL AFFECT CIRCUITRY. INDICATE THE ACTUAL CIRCUIT NUMBERS INSTALLED ON THE "AS-BUILT" DRAWINGS.
26. ALL HANGER AND/OR ROD SUPPORT SYSTEMS SHALL BE SUPPORTED TO THE BOTTOM RIB OF THE METAL DECK, WHERE APPLICABLE.
27. PROVIDE ALL NECESSARY PROPERLY SIZED WALL OR MILLWORK MOUNTED BOXES, RINGS, SUPPORTS, AND DEVICES AS REQUIRED VIA COORDINATION WITH ARCHITECTURAL WALL SECTIONS, AND MILLWORK DETAILS.
28. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THESE DRAWINGS. WHERE MORE STRINGENT REQUIREMENTS THAN THOSE DESCRIBED HEREIN OR AS SET FORTH UNDER CODES, LAWS, AND ORDINANCES OF FEDERAL, STATE, AND LOCAL GOVERNING BODIES HAVING JURISDICTION, THOSE GREATER REQUIREMENTS SHALL BE ADHERED TO.
29. EMERGENCY LUMINARIES SHALL BE PROVIDED WITH AN INTEGRAL EMERGENCY BACKUP TO ILLUMINATE THE FIXTURES IN THE EVENT OF A POWER FAILURE. ALL COMPONENTS SHALL BE IN COMPLIANCE WITH NFPA 101 AND NFPA 70 SECTION 700. THE BATTERY SHALL MAINTAIN 87.5% OF THE NOMINAL BATTERY VOLTAGE AFTER 1.5 HOURS TO COMPLY WITH NEC SECTION 700 AND UL 924.
30. REFER TO MECHANICAL AND PLUMBING ENGINEERING DRAWINGS FOR EXACT LOCATIONS OF ALL MECHANICAL AND PLUMBING EQUIPMENT
STRIP LIGHT.
SYMBOL DESCRIPTION
EMERGENCY LIGHTING UNIT.
LED INTERIOR LIGHTING LETTER ADJACENT TO LUMINAIRE DENOTES TYPE. SEE LUMINAIRE SCHEDULE.
SYMBOL DESCRIPTION
WALL PACK
LED EXTERIOR LIGHTING LETTER ADJACENT TO LUMINAIRE DENOTES TYPE. SEE LUMINAIRE SCHEDULE.
AREA LIGHT ON POLE.
TOGGLE SWITCH - SPST, 20A, 125V.
TOGGLE SWITCH - VACANCY SENSING. SENSOR SWITCH WSX WH OR APPROVED EQUAL
SYMBOL DESCRIPTION
OS
LIGHTING CONTROL DEVICES
DS OUTDOOR RATED PHOTOSWITCH
OSETOGGLE SWITCH - VACANCY SENSING. SENSOR SWITCH WSX 2P FAN WH OR APPROVED EQUAL
SYMBOL DESCRIPTION
POWER DISTRIBUTION
PANELBOARD, 240/120V 1PH 3W
SAFETY SWITCH, NON-FUSED, SIZE AS INDICATED ON PLAN
DIRECT CONNECTION TO EQUIPMENT.
SYMBOL DESCRIPTION
CONDUCTORS, CABLES, BOXES, AND GROUNDING
CONDUCTORS IN CONDUIT CONCEALED IN OR ABOVE CEILING OR IN WALL
CONDUCTORS IN CONDUIT CONCEALED BELOW FLOOR OR BELOW GRADE.
EQUIPMENT GROUNDING CONDUCTOR.
CONDUCTORS IN CONDUIT EXPOSED ON CEILING OR WALL
JUNCTION BOXJ
TELECOM GROUND BARTGB
SYMBOL DESCRIPTION
TOGGLE SWITCH, MOTOR RATED, WITH POLES FOR LOAD SERVED.
SUBSCRIPT: WP - WEATHERPROOF
RECEPTACLE, DUPLEX, GFCI, NEMA 5-20R.
RECEPTACLE, DUPLEX, GFCI, NEMA 5-20R, COUNTERTOP HEIGHT.
WIRING DEVICES
WP
RECEPTACLE, DUPLEX, NEMA 5-20R.
M
SYMBOL DESCRIPTION
COMMUNICATIONS AND SECURITY
DATA OUTLET WITH 3/4"C AND CAT6 CABLE.
TH
IS D
OC
UM
EN
T IS
TH
E P
RO
PE
RT
Y O
FA
2H
, IN
C.,
AN
D A
LL C
OM
MO
N L
AW
, S
TA
TU
TO
RY
AN
D O
TH
ER
RE
SE
RV
ED
RIG
HT
S S
HA
LL B
E R
ET
AIN
ED
BY
SA
ME
.
AN
Y C
HA
NG
ES
MA
DE
TO
TH
IS D
OC
UM
EN
T W
ITH
OU
T
HE
EX
PR
ES
S W
RIT
TE
N C
ON
SE
NT
OF
A2H
, IN
C.,
SH
ALL B
E P
RO
HIB
ITE
D A
ND
AR
E S
UB
JE
CT
TO
LE
GA
L
PR
OS
EC
UT
ION
. IF
CH
AN
GE
S A
RE
MA
DE
WIT
HO
UT
CO
NS
EN
T,
TH
E L
IAB
ILIT
Y O
F A
NY
CLA
IM IS
AC
CE
PT
ED
BY
TH
E R
ES
PO
NS
IBLE
PA
RT
Y M
AK
ING
TH
E C
HA
NG
E.
A2H, INCORPORATEDENGINEER:
DEVELOPER:
A2H, INC.
SCALE:
PROJECT:
REVIEWED:
LOCATION:
DATE:
DRAWN BY:
CHECKED BY:
REVISIONS
SURVEY:
DIVISION OF ENGINEERING
DATE:
DATE:
GERMANTOWN, TENNESSEE
ELEVATED WATER TOWER
GERMANTOWN, TENNESSEE
GERMANTOWN PUBLIC WORKS
ITEM NO.
DESCRIPTION OF CHANGEAPPROVAL DATE
AS INDICATED
DESIGN REVIEW COMMISSION
DWG NO.
CITY ENGINEER DATE DEPUTY CITY ENGINEER DATE
07/06/19
PLANS NOT VALID FOR CONSTRUCTION UNTIL SIGNED BY CITY ENGINEER
C:\
Use
rs\m
ichae
lla\D
ocum
ents
\19
457
- E
lectr
ical_
mic
ha
ellJ
4V
FV
.rvt
9/2
9/2
02
1 4
:44
:44 P
M
ELECTRICAL LEGEND AND NOTES
MCL
CDR
19457
E0.1
7/30/21
B1N.T.S.
ELECTRICAL LEGEND
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL NUMBER CCT INPUT WATT FIXTURE MOUNTINGA 4FT STRIP LIGHT LITHONIA LIGHTING CSS L48 MVOLT 35K 80CRI 35K 44 VA CEILING/SURFACE MOUNT
E EMERGENCY LIGHTING UNIT LITHONIA LIGHTING ELM2L M12 N/A 1 VA WALL MOUNT 7' AFF
SP POLE MOUNTED SITE LUMINAIRE LITHONIA LIGHTING DSX1 LED P2 40K T4M MVOLT 40K 70 VA MOUNT TO 15' SQUARE POLE WITH 3' CONCRETE BASE. POLE: LITHONIA SSS 15' 4G DM19AS DDBXD
SW WALL PACK LITHONIA LIGHTING WDGE2 LED P3 80CRI VW 40K 40K 23 VA WALL MOUNT 9' AFF
D1N.T.S.
LIGHTING FIXTURE SCHEDULE
SUBSTITUTION PACKAGE REQUIREMENTS:
1. MANUFACTURER'S TRADE NAMES OR CATALOG NUMBERS USED IN THIS SCHEDULE DENOTE TYPE, SIZE, QUALITY, AND DESIGN OF EQUIPMENT REQUIRED.
2. WHERE A SUBSTITUTE LIGHTING PACKAGE IS SUBMITTED FOR ENGINEER REVIEW, PROVIDE ALL FIXTURE CUTSHEETS WITH OPTIONS CLEARLY INDICATED. PROVIDE AN ELECTRONIC COPY OF PHOTOMETRIC CALCULATIONS FOR EACH SPACE WITH VISUAL LIGHTING SOFTWARE.
3. FURNISH SPECIFIED MATERIALS WHERE SUBSTITUTIONS ARE NOT APPROVED.
N.T.S.
C4 GENERAL NOTES
1 ADD #1 08/06/2021
2 SINGLE PHASE SERVICE 09/30/2021
2
CITY OF GERMANTOWN(PARCEL 2)2.63 ACRES
CITY OF GERMANTOWN(PARCEL 1)2.37 ACRES
PROPOSED WILDER PUDZONING: R - RESIDENTIAL
DS
OHE
OHE
OHE
UG
S
UG
S
UG
S
UG
S
UG
S
UG
S
UG
S
UG
S
UG
S
UG
S
UG
S
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
UG
T
UG
T
UG
TU
GT
UG
TU
GT
UG
TU
GT
UG
TU
GT
UG
TU
GT
GG
G
G
G
G
G
G
G
G
G
G
G
G
G
G
GG
G
GG
GG
GG
1
A
2
B
C
D
SP
SP
SW
SW
2#10,#10G,1"CLP-9
MOUNT PHOTOSWITCH ON ROOF. SEE DETAIL B5 THIS SHEET
MOUNT TO INSIDE OF WATER TOWER 4' AFF
WP
WP
LP-7
2#10,#10G,1"C
POPLAR PIKE
EXISTING UTILITY POLE
UNDERGROUND SECONDARY (UGS) SEE RISER DIAGRAM
UNDERGROUND TELECOM (1) 4" C TO TELECOM PEDESTAL. COORDINATE WITH TELECOM UTILITY PROVIDER FOR LOCATION AND ROUTING
WPLP-16
DEHUMIDIFIER.MOUNT TO INSIDE OF WATER TOWER 4' AFF(VERIFY LOCATION)
WP
SP
PROVIDE #2 BARE COPPER GROUND WIRE BELOW GRADE. BOND TO WATER TOWER, LIGHT POLES, FENCE, TGB, AND MAIN SERVICE GROUND
2#10,#10G,1"C
WATER TOWER HEATER7.5KW240V
LP-10,12
2#8,#10G,1"CWP
EXISTING OVERHEAD ELECTRICAL (OHE)
LP
2
2
EXISTING UTILITY POLE
2
PVC TO R.G.S.
COUPLING
60"
24"
3".
3"
MIN.
STEEL CONDUIT
RIGID GALVANIZED
AND WIRING
CONCRETE BASE
FINISH GRADE
3000 PSI
POLE MANUFACTURER
RECOMMENDED BY
ANCHOR BOLTS (AS
45° CHAMFER
STUB CONDUIT UP 6" MIN.
FIXTURE SCHEDULE)
LIGHT POLE (SEE
36"
2"
24"
BASE COVER
(4) #5 VERTICAL W/ #3 TIES, TOP (4) @ 6" O.C. REMAINING @ 12" O.C.
LUMINARIES
PANELBOARD
NEUTRAL
UNSWITCHED HOT
SPST SWITCH
PHOTO SWITCH
SWITCHED HOT
SWITCHED HOT
NEUTRAL
TH
IS D
OC
UM
EN
T IS
TH
E P
RO
PE
RT
Y O
FA
2H
, IN
C.,
AN
D A
LL C
OM
MO
N L
AW
, S
TA
TU
TO
RY
AN
D O
TH
ER
RE
SE
RV
ED
RIG
HT
S S
HA
LL B
E R
ET
AIN
ED
BY
SA
ME
.
AN
Y C
HA
NG
ES
MA
DE
TO
TH
IS D
OC
UM
EN
T W
ITH
OU
T
HE
EX
PR
ES
S W
RIT
TE
N C
ON
SE
NT
OF
A2H
, IN
C.,
SH
ALL B
E P
RO
HIB
ITE
D A
ND
AR
E S
UB
JE
CT
TO
LE
GA
L
PR
OS
EC
UT
ION
. IF
CH
AN
GE
S A
RE
MA
DE
WIT
HO
UT
CO
NS
EN
T,
TH
E L
IAB
ILIT
Y O
F A
NY
CLA
IM IS
AC
CE
PT
ED
BY
TH
E R
ES
PO
NS
IBLE
PA
RT
Y M
AK
ING
TH
E C
HA
NG
E.
A2H, INCORPORATEDENGINEER:
DEVELOPER:
A2H, INC.
SCALE:
PROJECT:
REVIEWED:
LOCATION:
DATE:
DRAWN BY:
CHECKED BY:
REVISIONS
SURVEY:
DIVISION OF ENGINEERING
DATE:
DATE:
GERMANTOWN, TENNESSEE
ELEVATED WATER TOWER
GERMANTOWN, TENNESSEE
GERMANTOWN PUBLIC WORKS
ITEM NO.
DESCRIPTION OF CHANGEAPPROVAL DATE
AS INDICATED
DESIGN REVIEW COMMISSION
DWG NO.
CITY ENGINEER DATE DEPUTY CITY ENGINEER DATE
07/06/19
PLANS NOT VALID FOR CONSTRUCTION UNTIL SIGNED BY CITY ENGINEER
C:\
Use
rs\m
ichae
lla\D
ocum
ents
\19
457
- E
lectr
ical_
mic
ha
ellJ
4V
FV
.rvt
9/2
9/2
02
1 4
:44
:45 P
M
ELECTRICAL - SITE PLAN
MCL
CDR
19457
E1.0
7/30/21
1" = 20'-0"
D1 ELECTRICAL SITE PLAN
NORTH
N.T.S.
C5 POLE BASE DETAIL RAISED
N.T.S.
B5 PHOTOSWITCH WIRING DIAGRAM
1 ADD #1 08/06/2021
2 SINGLE PHASE SERVICE 09/30/2021
UG
T
UG
T
UG
T
1
A
2
B
C
D
STORAGE
100
TLT
101
BREEZEWAY
C100
OS
OS-E
A
A
A
E
LP-3
E
1
A
2
B
C
D
STORAGE
100
TLT
101
BREEZEWAY
C100
LP-6
LP-2
WP
METER
TGB
TELECOM GROUND BAR
TO TELECOM PEDESTAL. SEE SITE PLAN
EF
1
EF
6
EUH
1
120V1/16 HP
LP-4
LP-8
120V1/8 HP
240V4000W
LP-25,27
WATER TOWER CONTROL PANEL(VERIFY LOCATION)
LP-13
LP-5
2#10, #10G, 3/4"C
TIE INTO LIGHT SWITCH SERVING SPACE
WP
30W HEATER FOR BACKFLOW ASSEMBLY
LP-1
LP
2
TH
IS D
OC
UM
EN
T IS
TH
E P
RO
PE
RT
Y O
FA
2H
, IN
C.,
AN
D A
LL C
OM
MO
N L
AW
, S
TA
TU
TO
RY
AN
D O
TH
ER
RE
SE
RV
ED
RIG
HT
S S
HA
LL B
E R
ET
AIN
ED
BY
SA
ME
.
AN
Y C
HA
NG
ES
MA
DE
TO
TH
IS D
OC
UM
EN
T W
ITH
OU
T
HE
EX
PR
ES
S W
RIT
TE
N C
ON
SE
NT
OF
A2H
, IN
C.,
SH
ALL B
E P
RO
HIB
ITE
D A
ND
AR
E S
UB
JE
CT
TO
LE
GA
L
PR
OS
EC
UT
ION
. IF
CH
AN
GE
S A
RE
MA
DE
WIT
HO
UT
CO
NS
EN
T,
TH
E L
IAB
ILIT
Y O
F A
NY
CLA
IM IS
AC
CE
PT
ED
BY
TH
E R
ES
PO
NS
IBLE
PA
RT
Y M
AK
ING
TH
E C
HA
NG
E.
A2H, INCORPORATEDENGINEER:
DEVELOPER:
A2H, INC.
SCALE:
PROJECT:
REVIEWED:
LOCATION:
DATE:
DRAWN BY:
CHECKED BY:
REVISIONS
SURVEY:
DIVISION OF ENGINEERING
DATE:
DATE:
GERMANTOWN, TENNESSEE
ELEVATED WATER TOWER
GERMANTOWN, TENNESSEE
GERMANTOWN PUBLIC WORKS
ITEM NO.
DESCRIPTION OF CHANGEAPPROVAL DATE
AS INDICATED
DESIGN REVIEW COMMISSION
DWG NO.
CITY ENGINEER DATE DEPUTY CITY ENGINEER DATE
07/06/19
PLANS NOT VALID FOR CONSTRUCTION UNTIL SIGNED BY CITY ENGINEER
C:\
Use
rs\m
ichae
lla\D
ocum
ents
\19
457
- E
lectr
ical_
mic
ha
ellJ
4V
FV
.rvt
9/2
9/2
02
1 4
:44
:45 P
M
ELECTRICAL - BUILDING PLANS
MCL
CDR
19457
E1.1
7/30/21
1/4" = 1'-0"
C1 LIGHTING - FIRST FLOOR PLAN1/4" = 1'-0"
C3 POWER - FIRST FLOOR PLAN
NORTHNORTH
1 ADD #1 08/06/2021
2 SINGLE PHASE SERVICE 09/30/2021
COUNTER HEIGHT DUPLEX RECEPTACLE
DUPLEX RECEPTACLE4'-0"
FINISHED FLOOR
DATA OUTLET
FACEPLATE
WALL SWITCHMULTI-GANG
18"
CEILING
240/120V 1PH 3W PANELBOARD SERVICE ENTRANCE RATED NEMA 3R ENCLOSURE
UNDERGROUND SECONDARY -3#1/0, 2.5"C SCH 40 PVC TO RIGID STEEL CONDUIT ABOVE GRADE
MLGW POLE MOUNTED TRANSFORMER
MLGW UTILITY POLE
GRADE
BUILDING
MLGW FEED THROUGH METER
RISER NOTES:
1. TRANSFORMER PROVIDED BY MLGW.
2. METER FURNISHED BY MLGW AND INSTALLED BY CONTRACTOR.
3. COORDINATE CONTRACTOR REQUIREMENTS WITH MLGW PRIOR TO BEGINNING WORK.
4. RUN RIGID STEEL CONDUIT 10FEET UP UTILITY POLE FROM GRADE. PROVIDE 20 FEET OF SLACK CONDUCTORS FROM WEATHERHEAD CONDUIT STANDOFF. WEATHERHEAD AND FINAL CONNECTIONS TO TRANSFORMER BY MLGW.
5. SEE C4 THIS SHEET FOR SERVICE GROUNDING.
6. THE STORAGE/RESTROOM BUILDING IS AN ADDITIVE ALTERNATE. IF ALTERNATE IS NOT ACCEPTED, MOUNT PANELBOARD AND METER TO UNISTRUT WITH CONCRETE BASE AT SAME LOCATION.
3#1/0, 2.5"C
COPPER GROUND ROD5/8" DIAMETER 8FT LENGTH
SEE NOTE 4
2
INTERSYSTEM GROUND BAR
#6 CU
2
2
GENERAL NOTES:
A. REFER TO ELECTRICAL SPECIFICATIONS FOR ADDITIONAL GROUNDING REQUIREMENTS.
B. INSTALL ALL GROUNDING IN ACCORDANCE WITH NEC 250.
C. PROVIDE #2 GROUNDING CABLES UNLESS NOTED OTHERWISE
#2 BARE COPPER GROUNDING ELECTRODE CONDUCTOR (NEC 250.66)
BUILDING STRUCTURAL STEEL (NEC 250.52(A)(2))
CADWELD
MINIMUM OF 20'-0" OF 1/2" REBARIN BUILDING WALL FOOTING (NEC 250.52(A)(3))
GROUND ROD (NEC 250.52(A)(5))
COLD WATER SERVICE ENTRANCE (PROVIDESIMILAR CONNECTION TO FIRE PROTECTIONWATER SERVICE ENTRANCE) NEC 250.52(A)(1)
MAIN SERVICE GROUNDING
(1)#2 TO TGB PER NEC 800.100(D)
PIPE CLAMP (TYP.)
SUPPLY SIDE
JUMPER
CADWELD
CADWELD
VALVE,METEROR UNION
GROUND BUS
NEUTRAL BUS
BONDING JUMPER TO PANELBOARD ENCLOSURE SIZE PER NEC 250.53(C).
MAIN BONDING JUMPER #2BARE COPPER CONDUCTION
TH
IS D
OC
UM
EN
T IS
TH
E P
RO
PE
RT
Y O
FA
2H
, IN
C.,
AN
D A
LL C
OM
MO
N L
AW
, S
TA
TU
TO
RY
AN
D O
TH
ER
RE
SE
RV
ED
RIG
HT
S S
HA
LL B
E R
ET
AIN
ED
BY
SA
ME
.
AN
Y C
HA
NG
ES
MA
DE
TO
TH
IS D
OC
UM
EN
T W
ITH
OU
T
HE
EX
PR
ES
S W
RIT
TE
N C
ON
SE
NT
OF
A2H
, IN
C.,
SH
ALL B
E P
RO
HIB
ITE
D A
ND
AR
E S
UB
JE
CT
TO
LE
GA
L
PR
OS
EC
UT
ION
. IF
CH
AN
GE
S A
RE
MA
DE
WIT
HO
UT
CO
NS
EN
T,
TH
E L
IAB
ILIT
Y O
F A
NY
CLA
IM IS
AC
CE
PT
ED
BY
TH
E R
ES
PO
NS
IBLE
PA
RT
Y M
AK
ING
TH
E C
HA
NG
E.
A2H, INCORPORATEDENGINEER:
DEVELOPER:
A2H, INC.
SCALE:
PROJECT:
REVIEWED:
LOCATION:
DATE:
DRAWN BY:
CHECKED BY:
REVISIONS
SURVEY:
DIVISION OF ENGINEERING
DATE:
DATE:
GERMANTOWN, TENNESSEE
ELEVATED WATER TOWER
GERMANTOWN, TENNESSEE
GERMANTOWN PUBLIC WORKS
ITEM NO.
DESCRIPTION OF CHANGEAPPROVAL DATE
AS INDICATED
DESIGN REVIEW COMMISSION
DWG NO.
CITY ENGINEER DATE DEPUTY CITY ENGINEER DATE
07/06/19
PLANS NOT VALID FOR CONSTRUCTION UNTIL SIGNED BY CITY ENGINEER
C:\
Use
rs\m
ichae
lla\D
ocum
ents
\19
457
- E
lectr
ical_
mic
ha
ellJ
4V
FV
.rvt
9/2
9/2
02
1 4
:44
:46 P
M
ELECTRICAL DETAILS
MCL
CDR
19457
E2.1
7/30/21
N.T.S.
B4 DEVICE MOUNTING HEIGHT DETAIL
N.T.S.
D1 RISER DIAGRAM
N.T.S.
C4 MAIN SERVICE GROUNDING DETAIL
1 ADD #1 08/06/2021
2 SINGLE PHASE SERVICE 09/30/2021
Notes:
Total Est. Demand: 51 A
RECEPTACLE 3720 VA 100.00% 3720 VA Total Conn.: 51 A
POWER 8130 VA 100.00% 8130 VA Total Est. Demand: 12262 VA
Other 210 VA 100.00% 210 VA Total Conn. Load: 12217 VA
LIGHTING 178 VA 125.00% 223 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 48 A 54 A
Total Load: 5706 VA 6512 VA
29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30
27 500 VA 0 VA 1 20 A SPARE 28
25EUH-1 25 A 2
500 VA 0 VA 1 20 A SPARE 26
23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 SPARE 20 A 1 0 VA 1920 VA 1 20 A DEHUMIDIFIER 16
13 WATER TOWER CONTROL PANEL 15 A 1 500 VA 0 VA 1 20 A SPARE 14
11 SPARE 20 A 1 0 VA 3000 VA 12
9 SITE LIGHTING 20 A 1 252 VA 3000 VA2 40 A WATER TOWER HEATER
10
7 WATER TOWER RECEPTACLES 20 A 1 360 VA 400 VA 1 20 A EF-6 8
5 STORAGE RM RECEPTACLE 20 A 1 180 VA 900 VA 1 20 A STORAGE RM RECEPTACLES 6
3 INTERIOR LIGHTING 20 A 1 132 VA 200 VA 1 15 A EF-1 4
1 BACKFLOW ASSEMBLY HEATER 15 A 1 30 VA 360 VA 1 20 A RESTROOM RECEPTACLE 2
CKT Circuit Description Trip Poles A B Poles Trip Circuit Description CKT
Notes: SERVICE ENTRANCE RATED; INTEGRAL SURGE PROTECTION; COPPER BUS, DOOR-IN-DOOR NEMA 3R
Enclosure: Type 1 MCB Rating: 150 A
Mounting: Surface Wires: 3 Mains Rating: 250 A
Supply From: UTILITY TRANSFORMER Phases: 1 Mains Type: MCB
Location: Volts: 120/240 Single A.I.C. Rating: 10K
Branch Panel: LP2