City Multi VRF
Telephone: 01707 282880MELSmart Technical Services: 0161 866 6089Technical Help - option 1Warranty - option 3Training - option 6 followed by option 1
email: [email protected]
website: airconditioning.mitsubishielectric.co.uk
website: recycling.mitsubishielectric.co.uk
UNITED KINGDOM Mitsubishi Electric Europe Living Environmental Systems DivisionTravellers Lane, Hatfield, Hertfordshire, AL10 8XB, England General Enquiries Telephone: 01707 282880 Fax: 01707 278881
IRELAND Mitsubishi Electric Europe Westgate Business Park, Ballymount, Dublin 24, IrelandTelephone: Dublin (01) 419 8800 Fax: Dublin (01) 419 8890 International code: (003531)
Country of origin: United Kingdom – Japan – Thailand – Malaysia. ©Mitsubishi Electric Europe 2014. Mitsubishi and Mitsubishi Electricare trademarks of Mitsubishi Electric Europe B.V. The company reserves the right to make any variation in technical specification to theequipment described, or to withdraw or replace products without prior notification or public announcement. Mitsubishi Electric is constantlydeveloping and improving its products. All descriptions, illustrations, drawings and specifications in this publication present only generalparticulars and shall not form part of any contract. All goods are supplied subject to the Company’s General Conditions of Sale, a copy ofwhich is available on request. Third-party product and brand names may be trademarks or registered trademarks of their respective owners.
Printed in September 2014
The ultimate heating and cooling solution for your building
City Multi VRF Air ConditioningToday’s commercial buildings are increasingly airtight and filled with heat generating office equipmentand lighting, which presents a problem for anyonetrying to maintain a stable and comfortableinternal environment.
Buildings account for around half of all UK greenhouse emissions, so legislation is demanding higher standards of air quality and increased energy efficiency.
With continual improvements through extensive research anddevelopment, our innovative and pioneering City Multi VRF air conditioning systems deliver the ultimate in efficiency andability whilst providing comfort and control to many building types.
The name Mitsubishi is synonymous with excellenceFounded in 1921, Mitsubishi Electric is now a global, marketleading environmental technologies manufacturer. In the UK,the Living Environmental Systems Division provides pioneeringsolutions that cool, heat, ventilate and control our buildings insome of the most energy efficient ways possible.
We believe that global climate challenges need local solutions.Our aim is to help individuals and businesses reduce the energyconsumption of their buildings and their running costs.
Providing accurate and controlled comfort all year round, ourair conditioning range can work on their own or in conjunctionwith other systems in a hybrid solution. Whatever the requirement we offer a solution that matches the needs of almost any building.
At Mitsubishi Electric we have evolved and today we offer advanced environmental systems that really can make a world of difference.
Heat RecoverySimultaneous heating and cooling with the benefit of heat recovery. By moving energy where it’s needed, input is reduced by up to 30%. Offering flexibility, operability, comfort and control, making it ideal for hotels, offices and leisure.
The Innovative City Multi VRF RangeUtilising two key variations, our City Multi range can provide a buildings heating or cooling through a heat pump system, or heating and cooling at the same timeusing a heat recovery system.
City Multi - Mitsubishi Electric’sanswer to large scale VRF
Page 5Page 4
First developed 30 years ago, City Multi is themarket leader in VRF technology. Specifically designed to deliver comfort and control fortoday’s building requirements, it addresses all the key market issues.
VRF stands for Variable Refrigerant Flow. VRF is a multi anddirect expansion type air conditioning system where one outdoor unit is connected with multiple indoor units, intelligentlymodulating the flow of refrigerant depending upon the capacityrequirements of each zone within the building. Its ultimate purpose is to regulate the internal air temperature and comfortlevels in the most effective and efficient manner possible.
Optimised delivery with minimal energy consumption year round - Designed from day one to work effectively in realapplications in the UK market, City Multi delivers the best possibleperformance. This means it’s most efficient operation, at part load,is optimised for the majority of the year, making City Multi ideal forthe UK’s temperate climate and providing the highest seasonalefficiencies available.
Comfort and Control - We provide market-leading solutionsto continually control and monitor equipment, dynamically optimising the capacity delivery to ensure minimal energy consumption with maximum comfort. These intelligent systemscan constantly report on performance, allowing building ownersto optimise efficiency and minimise energy consumption.
Constant development and innovation mean that City Multi VRF canbe applied into any building. The latest VRF technology includes:
Unique flat tube aluminium heat exchangerIncreased and automatic refrigerant temperature controlHot gas defrost, improving comfort during winter
Heat PumpOne outdoor unit provides all indoor units
heating or cooling at a given time. Ideal for open plan offices, call centres or retail.
The optionsAir conditioning systems need to extract or reject energy to enable the heating and cooling process tooperate. This can be done via air, ground or water and our wide range of products are designed tomaximise efficiency regardless of source.
Heat RecoveryCapacity (kW) Heat PumpAir source
Water source
Side blow small capacityMedium to large capacitySpecific R22/R407c ReplaceFull heating capacity down to -15ºCCombination of refrigerant and waterApplicable to water and ground source
12-1622-14022-10122-5622-2822-101
XX
XX
XXXXXX
The Benefits of City MultiUsing Mitsubishi Electric’s unique Branch Controller (BC), the City Multi heat recovery system only requires 2 refrigerant pipes throughoutthe entire VRF system to deliver simultaneousheating and cooling with heat recovery.
The technology lies in the BC, which houses a liquid/gas separator, allowing the outdoor unit to deliver a mixture (two-phase) of hot gas for heating and liquid for cooling, all through the same pipe. When this mixture arrives at the BC, it is separated and the correct phase delivered toeach indoor unit depending on the individual requirement of either heating or cooling. Recovered energy is returned to the BC and re-distributed where required. Traditional three-pipe systems need a separate pipe for each of the refrigerant phases.
Outstanding technological benefits:
Central control and distribution point - easy design,install and maintenance
Efficient, flexible and scalable design
Reduced piping, space requirements and reduced connections - saving cost and time
Less potential leakage points - key for F-Gas checks
Optimised refrigerant pressure control within the BC ensuring minimal power input for maximumcapacity output
Optional isolation valves on each port
World first andonly 2 pipe VRFheat recoverysystem
OUTDOOR UNIT BC CONTROLLER
INDOOR UNITS
OUTDOOR UNIT
INDOOR UNITSSOLENOID BOX
3 Pipe System2 Pipe System 20ConnectionSites
58ConnectionSites
Page 7Page 6
Mitsubishi Electric Other Manufacturers
Wide range of capacities 12-140kW delivered capacity per system
Extensive range of indoor units Over 80 indoor units of varying capacity including floor standing, ducted, ceiling cassettes, ceilingsuspended and wall mounted; up to 50 indoor units can be connected to one system
Selectable system evaporating temperatureBy changing system evaporating temperature, there are various options for indoor units to offer increased air off temperatures, higher SHF and improved comfort, with the benefit of energy saving
Choice of two defrost methodsOffering the traditional reverse defrost method or the new hot gas defrost technology, allowing completeflexibility in design, with the latter providing continuous heat to indoor units during the defrost cycle
Modular systemCompact and decentralised modules allow simple phased installations
Flexible piping configurationProviding an effortless design and transfer of internal layout changes (for example Cat A to Cat B)
Simple to designVRF offers simple design with everything inbuilt for operation and smart control
Fully integrated control solutionsUser friendly control solutions which can be integrated through 24/7 access over the internet
Additional heat recoveryProvides hot water, heat to air curtains and interlocks with Mitsubishi Electric’s Lossnay mechanicalheat recovery ventilation
Refrigerant detection systems and pump downSystems available to enable compliance with EN378 - Safety of Building Occupants, and can helpachieve recognition within BREEAM Pollution Prevention Assessment
Flexible installation locationHigh static pressure fans, low noise mode, low unit height and optional acoustic kits make locatingthe outdoor units easy
Low start currentsAll our outdoor units are fully inverter driven resulting in 8 amp starting current for all models
Wide operating rangeAir source systems are available to operate as low as -25°C and up to 52°C ambient. Water sourcesystems are available for ground source applications with water as low as -5°C up to 45°C
Replace Technology rangeReuse of existing R22 or R407c pipework, whilst allowing the upgrade to some of the most efficientsystems available in the market
Backward compatibilityEnabling the use of the latest VRF technology and controls on existing VRF systems
Optimised run hoursModular VRF systems intelligently rotate the master unit, to ensure equal operation of individual units.The modules work together as a system to ensure they work at the most efficient point at all times
Exceptional reliabilityEasy maintenance with simple access to all control boards to the front of the units
For many years, air sourced VRF has been themost popular and widely used air conditioningsystem in commercial buildings.
Because of this, specifiers, installers and building owners arelooking for more than just another VRF system; they’re lookingfor the right solution to provide comfort and efficiency to theirbuilding and its occupants. YLM answers these needs by offering the market leading solution.
Systems are available to deliver from 22-101kW capacity to a building in both heat pump and heat recovery variants.
The Ultimate Heating and Cooling SolutionYLM benefits from a unique aluminium flat tube heatexchanger, increased and automated refrigerant temperature control, optimised design of the refrigerant circuit and components and the ability to provide heat during defrost.
Increased efficiencyDesigned from day one for seasonal efficiency, City Multi YLMensures optimum performance year round in real UK applications.The improvements offer up to 27% annual energy savingscompared to the previous equivalent City Multi systems.
City Multi YLM -the most advancedair cooled VRF system ever
Previous City Multi Models
Page 9Page 8
Unique flat tube aluminium heat exchanger*1
A pivotal step change in providing more effective and efficient heat transfer, the City Multi YLM models use a unique flat tube aluminium micro-channel heat exchanger. Protected with a sacrificial zinc coating, the aluminium heat exchanger is ideal for the UK environment.
*1 Unique to City Multi EP YLM models
Reduced weight, module size and refrigerant volume The new aluminium heat exchanger has more benefits than just efficiency:
Ideal for hotels, the 28kW heat recovery module has a 25% smaller footprintthan the previous equivalent
45, 50, 56kW systems now use a single module, reducing the footprint by 30%and weight by up to 126kg
The new design offers 10% less system refrigerant volume than previous models, allowing a more cost effective system where EN378*2 restrictions are in place
*2 EN378 - British and European standard including refrigerant safety for building occupants
WorldFirstinVRF
Increased Efficiency
Sea
sona
l Effi
cien
cy In
crea
se (%
)
130
120
110
100EP YJM2010
EP YKM2013
P YLM2015
EP YLM2015
P YJM2010
New City Multi Models
6%
18%
23%
33%
NEWmodelsavailable
PUHY-EP200, 250YLM-APURY-EP200, 250YLM-A
PUHY-EP300, 350YLM-APURY-EP300, 350YLM-A
PUHY-EP400, 450, 500YLM-APURY-EP400, 450, 500YLM-A
Higher Heat TransferImproved EfficiencyReduced Weight & Module SizeReduced Refrigerant Volume
Circular Copper Tube
Standard DX Heat Exchanger NEW YLM Heat Exchanger
30% More Piping - Flat Aluminium Tube
17% More Contact with Piping
26% More Contact with Refrigerant
Smaller Pitch & Pipe Chamber
P = Standard variantEP = High efficiency variant
Standard
Hi 1
Hi 2
Hi 3
0
6
9
14
9ºC
12ºC
14ºC
16ºC
0.78
0.87
0.92
0.96
100%
75%
60%
50%
New compressorDesigned for partial load, thus higher seasonal efficiencies
Delivering heating and cooling in a comfortablemanner is highly important to ensure occupantsatisfaction.
The temperate UK climate often demands close control of capacity, both sensible and latent as well as off coil temperature. City Multi YLM offers two optional solutions to improve comfort delivered into the building:
1. Automated dynamic control of refrigerant evaporating temperature based on internal load, provides added comfort whilst improving seasonal efficiency by 8%.
City Multi YLM -Improved comfortwhilst saving energy
Page 11Page 10
2. Increase and fix system evaporating temperatureto enable increased indoor unit SHF, air off temperature conditions and therefore efficiency and comfort.
Improved comfort during defrost Defrost is an integral part of a heat pump running cycle during winter. The effect can be easily managedwith good design and control, for example ensuring the equipment is sized at a low ambient condition,setback temperature control is used and the grille design is considered.
To improve the defrost design even further, YLM offers the choice to either provide standard reverse defrost or can continue to provide indoor units heat during the defrost cycle by utilising hot gas defrost technology. Available on all YLM models, heat pump and heat recovery in single and multiple modules.
Improved flow distribution of refrigerant circuitMaximum energy transfer with minimal input
Option TargetEvaporatingTemperature
Typical air off SHFTotalCapacity
Target Evaporating Temperature (ºC)
10
8
6
4
2
0
Temperature difference between room and setpoint (ºC)
0 1 2
Control Active
Single module defrost Modular defrost
Reduced standby power by up to 50%Using induction heated compressor
Redesigned bellmouth grilleReduced static pressure losses, minimising power input of new DC fan motor
1
2
3
4
1
3
2
4
The YLM design has been fully optimised, enabling the most efficient and effective VRF system available:
Please note, the system may occasionally have to run a reverse defrost cycle.
SystemEfficiency
100%
105%
110%
115%
Notes: For indication only at steady state condition. Operating parameters estimated using a PEFY-P63VMA indoor unit and a PURY-EP200YLM-A outdoor unit. Internal condition: 21°CDB, 15°CWB, high fan speed. Outdoor condition: 27°CDB, 19°CWB. ‘Hi’ evaporating settings will require assisted application, please contact your local sales office for more details.
Outdoor unit heat exchanger is split in twoOne half defrostsOne half continues to provide heat to indoor unitsHot gas defrost operates down to 1ºC outdoorsBelow this reverse defrost operates
Two or three module systemsOne module defrostsThe other module continues to provide heat to indoor unitsModular hot gas defrost operates down to -5ºC outdoorBelow this reverse defrost operates
Hot gas defrost technology
Page 12
Offering solutions designed to match the challenges of modern buildings, City Multi VRF can now be installed in an ever increasing array of applications.
VRF technology in small capacityUtilising all the benefits of VRF technology, the low capacityPUMY models (12-16kW) have been redesigned with a focuson seasonal efficiency making them ideal for discreet application requirements:
New series designed for seasonal efficiency - 25% less annual energy consumption
Increased pipe runs improve flexibility - total 300m, furthest 150m
Further developments in 2015:Range extending further with 20kW side blow PUMY heat pump model
LEV boxes offer flexibility and diversification of indoor compatibility, enabling a mixture of M Series, Mr Slim and City Multi all on one system. The mix could incorporate ducted floor standing and stylish Zen wall mount units on one PUMY system
City Multi - the most flexibleair cooled VRF system ever
HVRF - The Modern Alternative
Set to rival traditional heating and cooling, the new HVRF system delivers optimumcomfort and efficiency, using an innovative combination of unique 2-pipe refrigeranttechnology and water to provide simultaneous heating and cooling with heat recovery.
DC inverter water pumps
Heat /cool flow and return headers Heat exchangers
8 ports
Water piping providing heating or cooling simultaneously
2 and 3 way control valves
Page 13
Extended lineup in 2015
Capacity from 22-56kWusing YLM
8 and 16 ports available withmaster and slave option
Ducted and floor standing
Outdoor HBC Indoor
2 refrigerant pipes
Hybrid Branch Controller (HBC) Water based fan coilsHVRF heat recovery outdoor unit
Valves, pumps and heat exchangers allcontained within the HBC
No refrigerant in occupied spaces, so no need for leak detection
Simplified 2 pipe design and installation
Manageable phased installation through modular system design
Cat A to Cat B is simple through HBC system design
High sensible cooling and stable roomtemperatures for maximum comfort
Simultaneous heating and cooling with full heatrecovery between fan coils and building zones
Heat recovery defrost method enables typical defrosttimes of 5 minutes with immediate return to heating
Intuitive load adjusting flow control valves, inverter driven pumps and heat recovery formaximum efficiency
Quiet operation through water based fan coils
City Multi - water cooled VRF solution
Ideal where outdoor space is limited, building heat recovery and efficiency is demandedand a water loop is available, City Multi water cooled models provide the ultimate solution.
First developed 15 years ago, the City Multi water cooled system utilises water instead of air as an energytransfer medium, but benefits from all the same technology and flexibility of an air sourced VRF. Availablein heat pump (22-101kW) and heat recovery (22-69kW) units.
Page 15Page 14
From the end of 2014 it will be illegal to use R22 refrigerant*3 to service and maintain air conditioning, yet there are estimated to be around 750,000*4
systems still in use that rely on R22.
Specifically designed for the maturing refurbishment sector,City Multi Replace systems enable the reuse of existing R22 /R407c pipework, whilst also allowing the upgrade to some ofthe most efficient systems available in the market.
Solutions available:
Heat pump (22-101kW)Heat Recovery (22-34kW)
Replace Multi will clean the existing pipework during commissioning, removing any deposits and mineral oil thatwould have ordinarily meant that new pipework would havebeen called for. The major benefits of this include:
Saving on cost and timeMinimising any potential disruption and downtime
For more information visit replace.mitsubishielectric.co.uk
City Multi - The ideal solutionfor replacing any existing VRF brand
A sustainable and flexible solution for tall buildings:Apply and network the energy through a water loop, within the building and between buildings - optimising efficiency
Utilise geothermal, rivers or lakes, landlord loops, waste heat from server cooling or other processes
Unit located indoors on each floor, ensuring design flexibility with pipework. Compact and quiet unit minimising outdoor plant space and maximising occupied space
City Multi water cooled models offer double heat recovery through refrigerant and water, no defrost and a refrigerant cooled inverter with no heat rejection to the internal space
1
23
4
1 1
2
4
3
*3 The EC Ozone Regulation (No. 1005/2009) was introduced tocontrol and phase out the remaining uses of all Ozone DepletingSubstances (ODS) such as R22 refrigerant. This has led to a totalban on its use for service and maintenance by the start of the year 2015.
*4 Mitsubishi Electric’s estimate in 2012.
Zubadan - full capacity down to -15ºCCity Multi Zubadan heat pumps (available from 22-56kW)achieve an excellent heating performance even when theoutdoor air temperature is as low as -25ºC, with full heatingcapacity at an outdoor temperature of -15°C.
The technology, which uses a flash injection circuit, ensuresreduced defrost frequency and time and a very quick deliveryof heating on start-up ensuring optimal comfort to occupants.
Heat pump air curtains Providing a solution to allow open door trading in retail or for hotel and leisure outlets, VRF heat pump air curtains can provide significant energy savings compared to conventional systems such as direct electric heatingor low, medium or high pressure hot water.
Easy to install with low noise levels, the units can be used with heat recovery systems to optimise waste heat. Availablein recessed or exposed, 1m, 1.5m or 2m variants.
Sanitary hot water Mitsubishi Electric’s hot water generation unit can be added to a heat recovery VRF system to utilise waste heat.
The system upgrades the waste heat to provide sanitary hot water up to 70ºC for bathrooms, showers or kitchens.
City Multi - Adding furtherenergy efficiency to a building
Close control coolingSpecially designed high sensible cooling solution, the PFD inverter driven system offers high efficiency with close control of temperature to ±1°C.
Recovering quickly after power failure and offering inbuilt back up and rotate functionality, the down flow floor standing system is available to connect to both air or water cooled VRF heat pump systems in 28 or 56kW.
Refrigerant detection systemsAnswering demands from EN378 refrigerant safety and BREEAM building environmental assessment, the high specification refrigerant detection systems supply a total refrigerant detection package.
The systems are designed to identify and minimise air conditioning gas leaks, with the option of providing refrigerant pump down of City Multi VRF heat recovery systems.
Page 17Page 16
City Multi Indoor UnitsUp to 50 indoor units can be connected to one City Multi outdoor unit includingfloor standing, ducted, ceiling cassettes, ceiling suspended, wall mounted, air curtain, fresh air and water heating types making them suitable for medium to large buildings that demand high performance with optimum efficiency.
Page 18 Page 19
4 way blow 600x600mm
(LEV interface required)
Ancillary Units
Floor Standing
Wall Mounted
Ceiling
Ducted
Cassette
4 way blow 1 way blow
Slimline
Ceiling suspended
Zen designer in black, silver and white Standard wall mount
Medium static High static
High static ducted Exposed Exposed design
Heat pump air curtain Hot water generation Fresh air processing
The need for control is paramount in order to optimise the performance of any air conditioning,heating or ventilation system and minimise its running costs and the emissions generated. Mitsubishi Electric offer a wide range of controloptions designed to do just this.
Monitoring and reporting capabilities are also increasingly requested by customers with major energy needs and required by legislation and building regulations.
Variables such as user habits, energy consumption patterns and outside temperature can now be used to inform system management and control.
Remote Controllers Backlight Simplified 0.5ºC set point adjustment Dual set point Touch screen M-Net controller Built in occupancy sensor Built In brightness sensor
Centralised Controllers Touch screen Up to 50 indoors Dedicated hotel interface Night set back Web server Energy monitoring Trend logging
Remote MonitoringWeb portal Smartphone and tablet app GPRS / 3G / 4G or Wi-Fi Energy monitoring
InterfacesSimple on/off Simple run/faults 0 to 10VDC Fan speed controlFire alarm Pulse meters Sensors
BEMS InterfacesModbus / BACnet LonWorks Trend Low cost solutions
Key features are dependant on controller type
Key Features
Page 20 Page 21
Controls - Mitsubishi Electricoffers a versatile range of control products to complementVRF Systems
Case Studies, Application and Product Information
Services and Support at every step of the wayAt Mitsubishi Electric, we have examined how we support the market throughout thecomplete lifecycle of our products - literally from cradle to grave. Whether in pre-salesdesign and specification, installation and maintenance support, right through to ourfree recycling programme, we can offer innovative solutions that deliver thequality and excellence you would expect to help make a world of difference.
MELSmart Technical ServicesTo keep our products working at their optimum, we have developed the MELSmart approach to ensureour customers are able to maximise the energy efficiency of their building's services right from the start.
MELSmart offers a range of support that includes:
24/7/365 Technical Help DeskFault finding & trouble shootingCommissioningSpare parts & warrantyMaintenance and system health checksCPD accredited product training hosted at various venues across the UK
Partner ProgrammeEstablished since 2005 and designed to raise industry standards, our Partner Programme assures endusers of a consistently high level of installation and after sales service that supports our systems. Ourinstallation partners comply with the necessary building regulations and meet specific industry, programmeand CSR standards. They are also reviewed on a regular basis to ensure they continue to meet the required standards that makes them eligible to be part of the Mitsubishi Electric Partner Programme.
MELFinance SolutionsWe developed MELFinance Solutions to respond to current market conditions and the need for customersto manage cash flow, while benefitting from the installation of leading technology to reduce carbonemissions and operational costs.
MELFinance Solutions can help customers fund the cost of new equipment and its installation via hire-purchase finance. Put simply, this means that (subject to financial status), a customer can repay the combination of 'fixed asset' and maintenance costs over an agreed period of between 1 to 5 years.MELFinance Solutions offers a flexible alternative to a traditional bank loan that provides significant cashflow and tax benefits. For further information please go to MELFinanceSolutions.co.uk
For further information on any of our products or additional services and tools, please visit our websitelivingenvironmentalsystems.mitsubishielectric.co.uk
Page 22
Customer comfort is paramount for the hotel sector but with legislation focusing attention on energy use and seeking to limit the use of refrigerant in occupiedspaces, hotel owners need building services that will deliver energy efficiency and high levels of comfort.
What is needed is a system that can also incorporate easy to use controls linked to room cards, whilstgiving owners the ability to programme the air conditioning to deliver comfort in the most energy efficientways possible. With a comprehensive range of City Multi units available, there is an ideal solution for almost any situation.
Flexible layout and phased installation
Low refrigerant volume / leak detection / HVRF (EN 378)
Slimline 1.7kW ducted and wall mounted indoor units
Simplified maintenance access with the heat recovery branch controller in one place
Integrated controls including simplified, central, Melcotel and remote cloud based options
Case StudyHotelAir Conditioning
The system is controlled with the Melcotel control interface which has helped to monitor and reduce energy consumption, CO2 emissions and running costs. A Mini M2M interface was also installed to monitor the energy consumption and the Melcotel settings.
The highly efficient City Multi heat recovery system can integrate with both hotel room key cards and individual window sensors to ensure that rooms are not using energy when they are unoccupied. Stylishyet simple to use room controllers are used to fit in with the décor of the room whilst allowing guests tocontrol their own comfort.
The ability to phase installation and complete flexibility of design reduces hotel downtime, allowing work tobe completed with minimum disruption to guests. With an advanced range of wall, floor, ceiling-mountedand ducted indoor units including the 1.7kW models and the stylish Zen range, there is a City Multi solution for almost any hotel.
The Premier Inn Hotel, Leicester has installed a high efficiency heat recovery CityMulti VRF air conditioning system to provide heating and cooling to all of the 135bedrooms as well as the bar, restaurant and back offices.
The modernisation of Monza House in Southampton included the installation of the pioneering City MultiHVRF system which now means that the offices are simultaneously heated and cooled without using refrigerant in occupied spaces. HVRF uses water to replace the majority of the internal refrigerant used in traditional VRF systems which removes the need for leak detection equipment and allows more properties to benefit from the flexibility of both design and operation that VRF can bring.
The system is still able to deliver simultaneous heating and cooling in a simplified two-pipe design but between the HBC box and the indoor fan coils, the air conditioning uses water piping and still offers highsensible cooling and stable room temperatures for maximum comfort. HVRF has other significant key benefits which open its use up to many other buildings. Having no refrigerant in occupied spaces whilstdelivering simultaneous heating and cooling via quiet fan coils means HVRF is particularly suited to applications such as modern offices, hotels and high end residential situations.
When Working Environments was looking to amalgamate three different office locations into one, the company wanted to provide a modern, comfortable environmentfor staff and customers and turn the interior of the building into a ‘Centre of Excellence’.
Modern offices and commercial buildings need air conditioning systems that providethe highest levels of comfort and freshness, as energy efficiently as possible.
The ideal system will incorporate easy to use controls that end users are comfortable with, and allow forfully programmable scheduling that accommodates flexible working patterns.
Legislation is also seeking to limit or restrict the use of refrigerants in occupied spaces. What is needed isa system that delivers the fresher and more balanced internal air temperatures needed combined with theadvanced efficiency of modern air conditioning, City Multi answers that need.
Continuous heating defrost offers greater comfortIncreased and automatic refrigeration temperature controlPAR-U02-MEDA PIR meeting room control and TG2000 for centralised control with energy monitoringBC with port isolationSolutions to monitor, control and optimiseLow noise indoor units Simple Cat A to Cat B fit out
Case StudyOfficeAir Conditioning
Page 25Page 24
Case StudyRetail / LeisureAir Conditioning
Case StudyMixed UseAir Conditioning
Page 27Page 26
Retail and Leisure facilities require systems that operate as efficiently as possible,providing customer comfort that maximises energy and cost saving potential. Retailers with multiple sites also need to be able to monitor building services from one central location or remotely, to maintain efficiency and control.
Heat recovery and effective controls are essential for small and large leisure applications: cooling is requiredall year around in the gym, whereas heating is required in changing and reception areas. It is therefore keyto control the heat recovery air conditioning system properly to ensure maximum energy savings.
Heat recovery air conditioning linking with hot water generation and heat pump air curtain
Ideal for cellular and open plan situations
Flexibility of design and fit out with unique two-pipe heat recovery
Cost effective centralised control and remote monitoring
Dual set point to save energy and improve comfort
Self-lowering grille – ideal for reducing maintenance in high ceiling situations
The old heating system was made up of an assortment of equipment including electrical and oil-fuelledheaters, which were extremely inefficient and costly to run and left some areas of the store cold whilstover-heating others. The ideal replacement proved to be the combination of a PWFY hot water generation unit running off City Multi VRF heat recovery air conditioning.
The PWFY unit sits in the store’s plant room in place of the old oil boiler and is linked to both the air conditioningand the hot water cylinder. The unit uses excess heat from the VRF system and transfers it to the hotwater supply. Space-saving City Multi units have been fitted outside the building which link to indoor ceiling cassettes in the store to ensure an even and pleasant temperature throughout.
Before installing the new system the Dagenham store was using 306,989kWh of energy a year at a costof £33,769, plus a further £3.5K spend on oil. The new system uses just 267,677kWh per annum at acost of £29,444, which means The Co-operative is using 39,312 kWh less energy providing them with a saving of £7,824 over previous bills.
The refurbishment of the heating and cooling system at the Co-operative’s foodstore in Dagenham has allowed the company to improve comfort levels whilst reducing energy consumption and emissions.
As we look for ways to balance population growth in crowded city centres, moremixed use properties are being developed, often combining retail, office, leisure andliving spaces in the same building.
This offers a tremendous opportunity for energy saving across the development and the flexibility and outstanding performance of the City Multi range allows heat to be transferred across a community to reduce overall consumption and lower emissions.
Maximise efficiency by using various energy sources, including open loops and ground source andintegrate the water loop into and between buildingsHigh levels of comfort and efficiency Complete flexibility of control and designAn integrated solution that works effectively with other Mitsubishi Electric energy saving technologies Advanced controllability works with BEMS and other smart devices, such as PC’s, tablets andphones to deliver complete automation for apartment ownersIndependent billing available with City MultiLEV kit and Zen indoor units add style to the hotel rooms
The development has prompted the Department of Energy & Climate Change (DECC) to research andpublish a national water source heat map, which points to significant opportunities for open water heatpump installations across the country.
The £70 million mixed-use development at Kingston Heights is getting the energy for its hot water, heatingand cooling directly from the River Thames. The development has been created by NHP Leisure Developmentson the site of a former power station right in the heart of Kingston upon Thames, and 200 metres from thebanks of the river. The 137 apartments and a 142-bedroom hotel, all benefit from the cutting-edge heat pumpsystem that harvests naturally stored energy in the river. The community heating scheme takes renewableheat from the sun, stored in the river water and boosts it to the temperature required for the underfloorheating and hot water needed by residents - as well as delivering the air conditioning required by the hotel.
When the new hotel, with meeting, banqueting and conference facilities, is completed at the end of 2014,this will increase the efficiency of the heating scheme further still as it will derive all its heating and hotwater, as well as its cooling, from the open water heat pump installation. Heat recovered from coolingthe individual hotel rooms will also be reclaimed and returned to the community system to support the heating and hot water demand for the whole site.
A mixed use development in the heart of Kingston upon Thames has highlightedthe potential of open water sources as a renewable energy source that can be readily replicated in many of our major towns and cities.
AwardWinningHeat PumpTechnology
Product InformationAir Conditioning City Multi
Range Model 12kW 14kW 16kW 22kW 28kW 34kW 40kW 45kW 50kW
WY SeriesPQHY-P*1
WR2 SeriesPQRY-P*1
NewStandardPUMY-P
StandardPUHY-P*1
NewHigh EfficiencyPUHY-EP (YLM)
StandardPURY-P*1
NewHigh EfficiencyPURY-EP(YLM)
ReplacePUHY-RP
ReplacePURY-RP
ZubadanPUHY-HP
HVRFPURY-WP*1
85kW80kW73kW69kW63kW 90kW 96kW 101kW108kW 113kW118kW 124kW 130kW136kW 140kW56kWP112 P125 P140 P200 P250 P300 P350 P400 P450 P750P700P650P600P550 P800 P850 P900 P950 P1000 P1050 P1100 P1150 P1200 P1250P500
SSS
SSS
SSS
SSS
SSS
SS
SS
SS
LLL
LLS
LLS
LSS
LSS
SSS
LL
LS
LL
LL
LL
LS
XLXL
XLXL
XLXL
XLXL
LS
LS
SS
SS
XLL
XLXL
LL
LL
SS
SS
SS
S S S
L L
L L
L
S
S S L L XL XL
S S S L L XL
S S L L XL XL
S S S L L XL
S S S S
XL
S
S
XL
XLLL
XLLL
XLXLL
LLL
LSS
LSS
LSS
XLXL
XLL
XLL
LL
LL
LS
LS
SS
SS
Water Cooled
Heat Pum
pHeat Recovery
Air Cooled
PageNumber
32
32
34
35
35
37
38
40
45
44
44
Page 29Page 28
Heat
Recovery
Heat Pum
p
*1. Updating in 2015 S Small chassis (920mm wide) L Large chassis (1220mm wide) XL Extra Large chassis (1750mm wide) New in 2015
2015
2015
Product InformationAir Conditioning City Multi
Indoor Model Range 1.7kW 2.2kW 2.8kW 3.6kW
HVRF Indoor Units
Range 1.7kW 2.2kW 2.8kW 3.6kW 4.5kW 5.6kWP15 P20 P25 P32 P40 P50
Cassette
Ducted
Ceiling
Wall
Floor
4-Way BlowPLFY-P-VBM
4-Way Blow Small 600x600PLFY-P-VCM
1-Way BlowPMFY-P-VBM
Slim CeilingPEFY-P-VMS1
Ceiling ConcealedPEFY-P-VMA
High Static CeilingPEFY-P-B-VMH(S)
Ceiling SuspendedPCFY-P-VKM
Wall MountedPKFY-P-VBM
Wall MountedPKFY-P-VHM
Wall MountedPKFY-P-VKM
Floor Standing DuctedPFFY-P-VLRM(M)*3
Floor Standing ChassisPFFY-P-VLEM
Floor StandingPFFY-P-VKM
Ducted Slim CeilingPEFY-WP-VMS1
Floor Floor Standing High StaticPEFY-WP-VLRMM
Ceiling ConcealedPEFY-WP-VMA
Note: HVRF system can only be configured with HVRF outdoor and indoor units. Note: PFD is only available to connect with PUHY-P250YJM and PQHY-P250YHM heat pump systems.
Model
Fresh Air
WaterHeater
Outdoor AirGUF-RD4
Hot Water GenerationPWFY-P-BU
AirCurtain
Air Curtain HPHP-DX*4
*2. Only available when using PAC-LV11 LEV kit interface, available in black, silver and white. *3. Available with or without static pressure. *4. Available as recessed or exposed versions.
4.5kW 5.6kW 7.1kW 9.0kW 11.2kW 14.0kW 16.0kW 22.4kW 28.0kWP15 P20 P25 P32 P40 P50 P63 P80 P100 P125 P140 P200 P250
Close Control
Range 28kW 56kWP250 P500
Down FlowFloor Standing
PFD-P250
PFD-P500
Model
Wall Mounted ZenMSZ-EF*2
Page 31Page 30
CAPACITY (kW) Heating (nominal) Cooling (nominal) Heating (UK) Cooling (UK)POWER INPUT (kW) Heating (nominal) Cooling (nominal) Heating (UK) Cooling (UK)COP / EER (nominal)SCOP / SEERMax no. OF CONNECTABLE INDOOR UNITSMAX CONNECTABLE CAPACITY AIRFLOW (m3/min)PIPE SIZE mm (in) Gas Liquid SOUND PRESSURE LEVEL (dBA)WEIGHT (kg)DIMENSIONS (mm) Width Depth HeightELECTRICAL SUPPLYPHASESTARTING CURRENT (A)NOMINAL SYSTEM HeatingRUNNING CURRENT (A)* CoolingGUARANTEED OPERATING RANGE (ºC) Heating / CoolingFUSE RATING (BS88) - HRC (A)MAINS CABLE No. Cores
CAPACITY (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)POWER INPUT (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)COP / EER (nominal)SCOP / SEERMAX No. OF CONNECTABLE INDOOR UNITSMAX CONNECTABLE CAPACITYAIRFLOW (m3/min) HighPIPE SIZE mm (in) Gas Liquid SOUND PRESSURE LEVEL (dBA)SOUND POWER LEVEL (dBA)WEIGHT (kg)DIMENSIONS (mm) Width Depth(1650mm without legs) HeightELECTRICAL SUPPLY*PHASE*STARTING CURRENT (A)*NOMINAL SYSTEM HeatingRUNNING CURRENT (A)* CoolingGUARANTEED OPERATING RANGE (ºC) Heating / CoolingFUSE RATING (MCB sizes BS EN 60947-2) - (A)*MAINS CABLE No. Cores*
CAPACITY (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)POWER INPUT (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)COP / EER (nominal)SCOP / SEERMAX No. OF CONNECTABLE INDOOR UNITSMAX CONNECTABLE CAPACITYAIRFLOW (m3/min) HighPIPE SIZE mm (in) Gas Liquid SOUND PRESSURE LEVEL (dBA)SOUND POWER LEVEL (dBA)WEIGHT (kg)DIMENSIONS (mm) Width Depth(1650mm without legs) HeightELECTRICAL SUPPLY*PHASE*STARTING CURRENT (A)*NOMINAL SYSTEM HeatingRUNNING CURRENT (A)* CoolingGUARANTEED OPERATING RANGE (ºC) Heating / CoolingFUSE RATING (MCB sizes BS EN 60947-2) - (A)*MAINS CABLE No. Cores*
CAPACITY (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)POWER INPUT (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)COP / EER (nominal)SCOP / SEERMAX No. OF CONNECTABLE INDOOR UNITSMAX CONNECTABLE CAPACITYAIRFLOW (m3/min) HighPIPE SIZE mm (in) Gas LiquidSOUND PRESSURE LEVEL (dBA)SOUND POWER LEVEL (dBA)WEIGHT (kg)DIMENSIONS (mm) Width Depth(1650mm without legs) HeightELECTRICAL SUPPLY*PHASE*STARTING CURRENT (A)*NOMINAL SYSTEM HeatingRUNNING CURRENT (A)* CoolingGUARANTEED OPERATING RANGE (ºC) Heating / CoolingFUSE RATING (MCB sizes BS EN 60947-2) - (A)*MAINS CABLE No. Cores*
CAPACITY (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)POWER INPUT (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)COP / EER (nominal)SCOP / SEERMAX No. OF CONNECTABLE INDOOR UNITSMAX CONNECTABLE CAPACITYAIRFLOW (m3/min) HighPIPE SIZE mm (in) Gas LiquidSOUND PRESSURE LEVEL (dBA)SOUND POWER LEVEL (dBA)WEIGHT (kg)DIMENSIONS (mm) Width Depth(1650mm without legs) HeightELECTRICAL SUPPLY*PHASE*STARTING CURRENT (A)*NOMINAL SYSTEM HeatingRUNNING CURRENT (A)* CoolingGUARANTEED OPERATING RANGE (ºC) Heating / CoolingFUSE RATING (MCB sizes BS EN 60947-2) - (A)*MAINS CABLE No. Cores*
STANDARD HEAT PUMP100.090.0100.087.082.825.7027.1032.3823.9017.48
3.89 / 3.325.19 / 5.82
5050-130% OU Capacity
370 / 21034.93 (1-3/8”)19.05 (3/4”)
6484
290 + 2501750 + 1220
7601710
380-415v, 50HzThree8 / 839.741.8
-20~15.5 / -5~461 x 40 / 1 x 324 + earth
108.096.0102.695.088.328.4229.6237.8026.1518.07
3.80 / 3.244.82 / 6.07
5050-130% OU Capacity
370 / 21041.28 (1-5/8”)19.05 (3/4”)
64.584.5
290 + 2501750 + 1220
7601710
380-415v, 50HzThree8 / 843.945.7
-20~15.5 / -5~461 x 40 / 1 x 324 + earth
113.0101.0107.499.492.930.0532.0639.9727.6519.56
3.76 / 3.154.77 / 5.84
5050-130% OU Capacity
370 / 37041.28 (1-5/8”)19.05 (3/4”)
6585
290 + 2901750 + 1750
7601710
380-415v, 50HzThree8 / 846.449.5
-20~15.5 / -5~461 x 40 / 1 x 404 + earth
PUHY-P800YSJM-A PUHY-P850YSJM-A PUHY-P900YSJM-A
STANDARD HEAT PUMP119.5108.0113.5105.299.430.0230.5039.9327.6218.61
3.98 / 3.544.97 / 6.52
5050-130% OU Capacity
210 / 170 / 17041.28 (1-5/8”)19.05 (3/4”)
64.584.5
250 + 215 + 2001220 + 920 + 920
7601710
380-415v, 50HzThree8 / 8 / 846.447.1
-20~15.5 / -5~461 x 32 / 1 x 25 / 1 x 20
4 + earth
127.0113.0120.7111.8104.033.1532.1044.0930.5019.58
3.83 / 3.524.86 / 6.33
5050-130% OU Capacity
210 / 170 / 17041.28 (1-5/8”)19.05 (3/4”)
64.584.5
250 + 215 + 2151220 + 920 + 920
7601710
380-415v, 50HzThree8 / 8 / 851.249.6
-20~15.5 / -5~461 x 32 / 1 x 25 / 1 x 25
4 + earth
132.0118.0125.4116.2108.634.1033.8145.3531.3720.62
3.87 / 3.494.91 / 6.34
5050-130% OU Capacity
210 / 210 / 17041.28 (1-5/8”)19.05 (3/4”)
6585
250 + 250 + 2151220 + 1220 + 920
7601710
380-415v, 50HzThree8 / 8 / 852.752.2
-20~15.5 / -5~461 x 32 / 1 x 32 / 1 x 25
4 + earth
140.0124.0133.0123.2114.136.0835.7347.9933.1921.80
3.88 / 3.474.92 / 6.41
5050-130% OU Capacity
210 / 210 / 21041.28 (1-5/8”)19.05 (3/4”)
6585
250 + 250 + 2501220 + 1220 + 1220
7601710
380-415v, 50HzThree8 / 8 / 855.755.2
-20~15.5 / -5~461 x 32 / 1 x 32 / 1 x 32
4 + earth
PUHY-P950YSJM-A PUHY-P1000YSJM-A PUHY-P1050YSJM-A PUHY-P1100YSJM-A
MINI HEAT PUMP14.012.511.611.53.042.792.711.87
4.61 / 4.483.95 / 6.39
950-130% OU Capacity
11015.88 (5/8”)9.52 (3/8”)
491231050330+301338
220-240v, 50HzSingle5
13.4212.32
-20~15 / -5~461 x 323
14.012.511.611.53.042.792.711.87
4.61 / 4.483.95 / 6.39
950-130% OU Capacity
11015.88 (5/8”)9.52 (3/8”)
491251050330+301338
380-415v, 50HzThree54.624.24
-20~15 / -5~461 x 164 + earth
16.014.013.312.93.743.463.332.32
4.28 / 4.054.14 / 6.39
1050-130% OU Capacity
11015.88 (5/8”)9.52 (3/8”)
501231050330+301338
220-240v, 50HzSingle5
16.5115.27
-20~15 / -5~461 x 323
16.014.013.312.93.743.463.332.32
4.28 / 4.054.14 / 6.39
1050-130% OU Capacity
11015.88 (5/8”)9.52 (3/8”)
501251050330+301338
380-415v, 50HzThree55.685.26
-20~15 / -5~461 x 164 + earth
18.015.514.914.34.474.523.983.03
4.03 / 3.433.92 / 6.13
1250-130% OU Capacity
11015.88 (5/8”)9.52 (3/8”)
511231050330+301338
220-240v, 50HzSingle5
19.7319.95
-20~15 / -5~461 x 323
18.015.514.914.34.474.523.983.03
4.03 / 3.433.92 / 6.134
1250-130% OU Capacity
11015.88 (5/8”)9.52 (3/8”)
511251050330+301338
380-415v, 50HzThree56.796.87
-20~15 / -5~461 x 164 + earth
PUMY-P112VKM PUMY-P112YKM PUMY-P125VKM PUMY-P125YKM PUMY-P140VKM PUMY-P140YKM
STANDARD HEAT PUMP25.022.425.022.821.35.845.627.365.783.23
4.28 / 3.985.18 / 7.02
1750-130% OU Capacity
17019.05 (3/4”)9.52 (3/8”)
56761909207601710
380-415v, 50HzThree89.08.6
-20~15.5 / -5~461 x 204 + earth
31.528.031.528.726.67.347.409.257.274.26
4.29 / 3.785.12 / 6.85
2150-130% OU Capacity
17022.2 (7/8”)9.52 (3/8”)**
58782009207601710
380-415v, 50HzThree811.311.4
-20~15.5 / -5~461 x 204 + earth
37.533.535.632.331.59.259.0012.408.975.81
4.05 / 3.724.93 / 6.23
2650-130% OU Capacity
17022.2 (7/8”)9.52 (3/8”)**
59792159207601710
380-415v, 50HzThree814.213.9
-20~15.5 / -5~461 x 254 + earth
45.040.042.838.737.611.1911.0114.9910.857.10
4.02 / 3.634.88 / 6.33
3050-130% OU Capacity
21028.58 (1-1/8”)12.7 (1/2”)
608025012207601710
380-415v, 50HzThree817.217.0
-20~15.5 / -5~461 x 324 + earth
50.045.047.543.042.312.8213.1117.1812.448.46
3.90 / 3.435.01 / 6.14
3450-130% OU Capacity
21028.58 (1-1/8”)12.7 (1/2”)
618125012207601710
380-415v, 50HzThree819.820.2
-20~15.5 / -5~461 x 324 + earth
56.050.050.748.746.014.6215.4716.6713.309.75
3.83 / 3.234.96 / 5.82
3950-130% OU Capacity
37028.58 (1-1/8”)15.88 (5/8”)
628229017507601710
380-415v, 50HzThree822.523.9
-20~15.5 / -5~461 x 404 + earth
PUHY-P200YJM-A PUHY-P250YJM-A PUHY-P300YJM-A PUHY-P350YJM-A PUHY-P400YJM-A PUHY-P450YJM-A
STANDARD HEAT PUMP63.056.057.054.851.515.0315.3817.1313.689.69
4.19 / 3.645.12 / 6.53
4350-130% OU Capacity
170 / 17028.58 (1-1/8”)15.88 (5/8”)
6181
200 + 200920 + 9207601710
380-415v, 50HzThree8 / 823.223.7
-20~15.5 / -5~461 x 20 / 1 x 204 + earth
69.063.062.460.058.016.8717.1619.2315.3510.81
4.09 / 3.674.99 / 6.39
4750-130% OU Capacity
170 / 17028.58 (1-1/8”)15.88 (5/8”)
61.581.5
215 + 200920 + 9207601710
380-415v, 50HzThree8 / 826.026.5
-20~15.5 / -5~461 x 25 / 1 x 204 + earth
76.569.069.266.663.518.8818.7521.5217.1811.81
4.05 / 3.684.94 / 6.58
5050-130% OU Capacity
210 / 17028.58 (1-1/8”)15.88 (5/8”)
6282
250 + 2001220 + 920
7601710
380-415v, 50HzThree8 / 829.128.9
-20~15.5 / -5~461 x 32 / 1 x 204 + earth
81.573.073.870.967.220.4720.3923.3418.6312.85
3.98 / 3.584.93 / 6.30
5050-130% OU Capacity
210 / 17028.58 (1-1/8”)15.88 (5/8”)
62.582.5
250 + 2151220 + 920
7601710
380-415v, 50HzThree8 / 831.631.5
-20~15.5 / -5~461 x 32 / 1 x 254 + earth
88.080.088.076.673.622.2722.4728.0620.7114.49
3.95 / 3.565.06 / 6.20
5050-130% OU Capacity
210 / 21034.93 (1-3/8”)19.05 (3/4”)
6383
250 + 2501220 + 1220
7601710
380-415v, 50HzThree8 / 834.434.7
-20~15.5 / -5~461 x 32 / 1 x 324 + earth
95.085.095.082.778.224.6724.7031.0822.9415.93
3.85 / 3.445.09 / 6.06
5050-130% OU Capacity
210 / 21034.93 (1-3/8”)19.05 (3/4”)
63.583.5
250 + 2501220 + 1220
7601710
380-415v, 50HzThree8 / 838.138.1
-20~15.5 / -5~461 x 32 / 1 x 324 + earth
PUHY-P500YSJM-A PUHY-P550YSJM-A PUHY-P600YSJM-A PUHY-P650YSJM-A PUHY-P700YSJM-A PUHY-P750YSJM-A
Note: * A separate power supply is required for each module. Where more than one figure is quoted there are multiple modules. **12.7(1/2”) if P250 furthest length ≥ 90m, P300 furthest length ≥ 40m.
Product InformationAir Conditioning City Multi Specifications
Heat Pump Outdoor Unit (Y Series) Specifications
Page 33Page 32
STANDARD HEAT PUMPCAPACITY (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)POWER INPUT (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)COP / EER (nominal)SCOP / SEERMAX No. OF CONNECTABLE INDOOR UNITSMAX CONNECTABLE CAPACITYAIRFLOW (m3/min) HighPIPE SIZE mm (in) Gas LiquidSOUND PRESSURE LEVEL (dBA)SOUND POWER LEVEL (dBA)WEIGHT (kg)DIMENSIONS (mm) Width Depth(1650mm without legs) HeightELECTRICAL SUPPLY*PHASE*STARTING CURRENT (A)*NOMINAL SYSTEM HeatingRUNNING CURRENT (A)* CoolingGUARANTEED OPERATING RANGE (ºC) Heating / CoolingFUSE RATING (MCB sizes BS EN 60947-2) - (A)*MAINS CABLE No. Cores*
145.0130.0137.8127.6119.637.2738.3449.5734.2923.39
3.89 / 3.394.86 / 6.24
5050-130% OU Capacity
370 / 210 / 21041.28 (1-5/8”)19.05 (3/4”)
65.585.5
290 + 250 + 2501750 + 1220 + 1220
7601710
380-415v, 50HzThree8 / 8 / 857.659.2
-20~15.5 / -5~461 x 40 / 1 x 32 / 1 x 32
4 + earth
150.0136.0142.5132.0125.139.2640.8452.2236.1224.91
3.82 / 3.334.84 / 6.16
5050-130% OU Capacity
370 / 210 / 21041.28 (1-5/8”)19.05 (3/4”)
6686
290 + 250 + 2501750 + 1220 + 1220
7601710
380-415v, 50HzThree8 / 8 / 860.663.1
-20~15.5 / -5~461 x 40 / 1 x 32 / 1 x 32
4 + earth
156.5140.0148.7137.7128.840.8642.9454.3437.5926.19
3.83 / 3.264.86 / 5.96
5050-130% OU Capacity
370 / 370 / 21041.28 (1-5/8”)19.05 (3/4”)
6686
290 + 290 + 2501750 + 1750 + 1220
7601710
380-415v, 50HzThree8 / 8 / 863.166.3
-20~15.5 / -5~461 x 40 / 1 x 40 / 1 x 32
4 + earth
PUHY-P1150YSJM-A PUHY-P1200YSJM-A PUHY-P1250YSJM-A
Note: * A separate power supply is required for each module. Where more than one figure is quoted there are multiple modules.
CAPACITY (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)POWER INPUT (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)COP / EER (nominal)SCOP / SEERMAX No. OF CONNECTABLE INDOOR UNITSMAX CONNECTABLE CAPACITYAIRFLOW (m3/min) High PIPE SIZE mm (in) Gas LiquidSOUND PRESSURE LEVEL (dBA)SOUND POWER LEVEL (dBA)WEIGHT (kg)DIMENSIONS (mm) Width Depth(1650mm without legs) HeightELECTRICAL SUPPLY * PHASE*STARTING CURRENT (A)*NOMINAL SYSTEM RUNNING CURRENT (A)* Heating /CoolingGUARANTEED OPERATING RANGE (ºC) Heating / CoolingFUSE RATING (MCB sizes BS EN 60947-2) - (A)*MAINS CABLE No. Cores*
HIGH EFFICIENCY HEAT PUMPCAPACITY (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)POWER INPUT (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)COP / EER (nominal)SCOP / SEERMAX No. OF CONNECTABLE INDOOR UNITSMAX CONNECTABLE CAPACITYAIRFLOW (m3/min) High PIPE SIZE mm (in) Gas LiquidSOUND PRESSURE LEVEL (dBA)SOUND POWER LEVEL (dBA)WEIGHT (kg)DIMENSIONS (mm) Width Depth(1650mm without legs) HeightELECTRICAL SUPPLY * PHASE*STARTING CURRENT (A)*NOMINAL SYSTEM RUNNING CURRENT (A)* Heating /CoolingGUARANTEED OPERATING RANGE (ºC) Heating / CoolingFUSE RATING (MCB sizes BS EN 60947-2) - (A)*MAINS CABLE No. Cores*
100.090.0100.087.078.225.1823.4331.5123.3710.72
3.97 / 3.84- / -50
50~130% OU Capacity200 / 200 / 17534.93 (1-3/8”)19.05 (3/4”)
6586.5
252 + 252 + 2081220 + 1220 + 920
7401710
380-415v, 50HzThree8 / 8 / 838.9 / 36.2
-20~15.5 / -5~521 x 25 / 1 x 25 / 1 x 20
4
108.096.0102.695.085.227.7625.5337.0425.3511.80
3.89 / 3.76- / -50
50~130% OU Capacity200 / 200 / 17541.28 (1-5/8”)19.05 (3/4”)
65.586.5
252 + 252 + 2081220 + 1220 + 920
7401710
380-415v, 50HzThree8 / 8 / 842.9 / 39.4
-20~15.5 / -5~521 x 25 / 1 x 25 / 1 x 20
4
113.0101.0107.499.489.629.0427.2238.7426.5212.58
3.89 / 3.71- / -50
50~130% OU Capacity200 / 200 / 20041.28 (1-5/8”)19.05 (3/4”)
6687
252 + 252 + 2521220 + 1220 + 1220
7401710
380-415v, 50HzThree8 / 8 / 844.8 / 42.0
-20~15.5 / -5~521 x 25 / 1 x 25 / 1 x 25
4
PUHY-EP800YSLM-A PUHY-EP850YSLM-A PUHY-EP900YSLM-A
ZUBADAN HEAT PUMPCAPACITY (kW) Heating (nominal) Cooling (nominal) Heating (UK) Cooling (UK)POWER INPUT (kW) Heating (nominal) Cooling (nominal) Heating (UK) Cooling (UK)COP / EER (nominal)SCOP / SEERMAX No. OF CONNECTABLE INDOOR UNITSMAX CONNECTABLE CAPACITYAIRFLOW (m3/min) HighPIPE SIZE mm (in) Gas LiquidSOUND PRESSURE LEVEL (dBA)SOUND POWER LEVEL (dBA)WEIGHT (kg)DIMENSIONS (mm) Width Depth(1650mm without legs) HeightELECTRICAL SUPPLY*PHASE*STARTING CURRENT (A)*NOMINAL SYSTEM RUNNING CURRENT (A)* Heating /CoolingGUARANTEED OPERATING RANGE (ºC)FUSE RATING (MCB sizes BS EN 60947-2) - (A)*MAINS CABLE No. Cores*
25.022.428.019.96.526.4011.024.99
3.83 / 3.50- / 3.5017
50-130% OU Capacity225
19.05 (3/4”)12.7 (1/2”)
56732209207601710
380-415v, 50HzThree8
10.0 / 9.8-25~15.5 / -5~46
1 x 324 + earth
31.528.035.324.98.949.0615.117.07
3.52 / 3.09- / 3.1521
50-130% OU Capacity225
22.2 (7/8”)12.7 (1/2”)
57742209207601710
380-415v, 50HzThree8
13.8 / 14.0-25~15.5 / -5~46
1 x 324 + earth
50.045.056.040.113.3512.8622.5610.03
3.74 / 3.49- / 3.6234
50-130% OU Capacity225 / 225
28.58 (1-1/8”)15.88 (5/8”)
5976
220 + 220920 + 9207601710
380-415v, 50HzThree8 / 8
20.6 / 19.8-25~15.5 / -5~461 x 32 / 1 x 324 + earth
63.056.070.649.818.0418.1630.4914.16
3.49 / 3.08- / 3.2543
50-130% OU Capacity225 / 225
28.58 (1-1/8”)15.88 (5/8”)
6077
220 + 220920 + 9207601710
380-415v, 50HzThree8 / 8
27.8 / 28.0-25~15.5 / -5~461 x 32 / 1 x 324 + earth
PUHY-HP200YHM-A PUHY-HP250YHM-A PUHY-HP400YSHM-A PUHY-HP500YSHM-A
HIGH EFFICIENCY HEAT PUMP25.022.425.022.820.05.735.197.245.702.21
4.36 / 4.31- / -17
50~130% OU Capacity175
22.2 (7/8”)9.52 (3/8”)
5779.52089207401710
380-415v, 50HzThree8
8.8 / 8.0-20~15.5 / -5~52
1 x 204
31.528.031.528.725.07.686.899.617.643.00
4.10 / 4.06- / -21
50~130% OU Capacity175
22.2 (7/8”)9.52 (3/8”)**
60802089207401710
380-415v, 50HzThree8
11.8 / 10.6-20~15.5 / -5~52
1 x 204
37.533.535.634.229.99.168.5612.229.103.66
4.09 / 3.91- / -26
50~130% OU Capacity200
28.58 (1-1/8”)9.52 (3/8”)**
618225212207401710
380-415v, 50HzThree8
14.1 / 13.2-20~15.5 / -5~52
1 x 254
45.040.042.741.135.812.5311.6916.7212.465.00
3.59 / 3.42- / -30
50~130% OU Capacity200
28.58 (1-1/8”)12.7 (1/2”)
6182.52521220740 1710
380-415v, 50HzThree8
19.3 / 18.0-20~15.5 / -5~52
1 x 324
PUHY-EP200YLM-A PUHY-EP250YLM-A PUHY-EP300YLM-A PUHY-EP350YLM-A
HIGH EFFICIENCY HEAT PUMPCAPACITY (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)POWER INPUT (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)COP / EER (nominal)SCOP / SEERMAX No. OF CONNECTABLE INDOOR UNITSMAX CONNECTABLE CAPACITYAIRFLOW (m3/min) High PIPE SIZE mm (in) Gas LiquidSOUND PRESSURE LEVEL (dBA)SOUND POWER LEVEL (dBA)WEIGHT (kg)DIMENSIONS (mm) Width Depth(1650mm without legs) HeightELECTRICAL SUPPLY * PHASE*STARTING CURRENT (A)*NOMINAL SYSTEM RUNNING CURRENT (A)* Heating /CoolingGUARANTEED OPERATING RANGE (ºC) Heating / CoolingFUSE RATING (MCB sizes BS EN 60947-2) - (A)*MAINS CABLE No. Cores*
63.056.057.054.549.919.6818.7222.4619.148.68
3.20 / 2.99- / -43
50~130% OU Capacity370
28.58 (1-1/8”)15.88 (5/8”)
63.583.53321750 7401710
380-415v, 50HzThree8
30.4 / 28.9-20~15.5 / -5~52
1 x 634
56.050.050.748.744.516.0914.7918.3715.657.08
3.48 / 3.38- / -39
50~130% OU Capacity370
28.58 (1-1/8”)15.88 (5/8”)
638331817507401710
380-415v, 50HzThree8
24.8 / 22.8-20~15.5 / -5~52
1 x 404
69.063.062.460.055.917.7316.6220.2416.198.04
3.89 / 3.79- / -47
50~130% OU Capacity200 / 175
28.58 (1-1/8”)15.88 (5/8”)
63.584.5
252 + 2081220 + 920
7401710
380-415v, 50HzThree8 / 8
27.4 / 25.6-20~15.5 / -5~521 x 25 / 1 x 20
4
76.569.069.266.661.219.6618.5922.4417.968.83
3.89 / 3.71- / -50
50~130% OU Capacity200 / 200
28.58 (1-1/8”)15.88 (5/8”)
6485
252 +2521220 + 1220
7401710
380-415v, 50HzThree8 / 8
30.3 / 28.7-20~15.5 / -5~521 x 25 / 1 x 25
4
PUHY-EP500YLM-APUHY-EP450YLM-A PUHY-EP550YSLM-A PUHY-EP600YSLM-A
HIGH EFFICIENCY HEAT PUMPCAPACITY (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)POWER INPUT (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)COP / EER (nominal)SCOP / SEERMAX No. OF CONNECTABLE INDOOR UNITSMAX CONNECTABLE CAPACITYAIRFLOW (m3/min) High PIPE SIZE mm (in) Gas LiquidSOUND PRESSURE LEVEL (dBA)SOUND POWER LEVEL (dBA)WEIGHT (kg)DIMENSIONS (mm) Width Depth(1650mm without legs) HeightELECTRICAL SUPPLY * PHASE*STARTING CURRENT (A)*NOMINAL SYSTEM RUNNING CURRENT (A)* Heating /CoolingGUARANTEED OPERATING RANGE (ºC) Heating / CoolingFUSE RATING (MCB sizes BS EN 60947-2) - (A)*MAINS CABLE No. Cores*
81.573.073.870.964.820.0718.1522.9118.338.59
4.06 / 4.02- / -50
50~130% OU Capacity175 / 175 / 17528.58 (1-1/8”)15.88 (5/8”)
6384.5
208 + 208 + 208920 + 920 + 920
7401710
380-415v, 50HzThree8 / 8 / 831.0 / 28.0
-20~15.5 / -5~521 x 20 / 1 x 20 / 1 x 20
4
88.080.088.076.669.521.6720.1527.1220.129.17
4.06 / 3.97- / -50
50~130% OU Capacity200 / 175 / 17534.93 (1-3/8”)19.05 (3/4”)
63.585.5
252 + 208 + 2081220 + 920 + 920
7401710
380-415v, 50HzThree8 / 8 / 833.4 / 31.1
-20~15.5 / -5~521 x 25 / 1 x 20 / 1 x 20
4
95.085.095.082.773.823.9221.8529.9322.1910.21
3.97 / 3.89- / -50
50~130% OU Capacity200 / 175 / 17534.93 (1-3/8”)19.05 (3/4”)
64.585.5
252 + 208 + 2081220 + 920 + 920
7401710
380-415v, 50HzThree8 / 8 / 836.9 / 33.7
-20~15.5 / -5~521 x 25 / 1 x 20 / 1 x 20
4
PUHY-EP650YSLM-A PUHY-EP700YSLM-A PUHY-EP750YSLM-A
Note: * A separate power supply is required for each module. Where more than one figure is quoted there are multiple modules. **12.7(1/2”) if EP250 furthest length ≥ 90m, EP300 furthest length ≥ 40m.
Page 35Page 34
REPLACE HEAT PUMPCAPACITY (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)POWER INPUT (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)COP / EER (nominal)SCOP / SEERMAX No. OF CONNECTABLE INDOOR UNITSMAX CONNECTABLE CAPACITYAIRFLOW (m3/min) HighPIPE SIZE mm (in) Gas LiquidSOUND PRESSURE LEVEL (dBA)SOUND POWER LEVEL (dBA)WEIGHT (kg)DIMENSIONS (mm) Width Depth(1650mm without legs) HeightELECTRICAL SUPPLY*PHASE*STARTING CURRENT (A)*NOMINAL SYSTEM RUNNING CURRENT (A)* Heating /CoolingGUARANTEED OPERATING RANGE (ºC) Heating / CoolingFUSE RATING (MCB sizes BS EN 60947-2) - (A)*MAINS CABLE No. Cores*
25.022.425.022.821.25.695.687.345.633.30
4.39 / 3.94- / 6.4217
50-130% OU Capacity185
28.58 (1-1/8”)12.7 (1/2”)
56762309207601710
380-415v, 50HzThree8
8.7 / 8.7-20~15.5 / -5~46
1 x 204 + earth
31.528.031.528.726.67.227.629.317.154.42
4.36 / 3.67- / 7.0521
50-130% OU Capacity185
28.58 (1-1/8”)12.7 (1/2”)
57772559207601710
380-415v, 50HzThree8
12.1 / 12.7-20~15.5 / -5~46
1 x 204 + earth
37.533.536.032.631.59.428.9812.439.145.84
3.98 / 3.73- / 5.6526
50-130% OU Capacity185
28.58 (1-1/8”)12.7 (1/2”)
59792559207601710
380-415v, 50HzThree8
15.2 / 14.4-20~15.5 / -5~46
1 x 254 + earth
45.040.043.239.237.612.6011.7916.6312.227.67
3.57 / 3.39- / 5.4630
50-130% OU Capacity185
34.93 (1-3/8”)15.88 (5/8”)
60802559207601710
380-415v, 50HzThree8
20.2 / 18.9-20~15.5 / -5~46
1 x 324 + earth
50.045.048.043.542.311.3811.8715.1411.047.72
4.39 / 3.79- / 5.3732
50-130% OU Capacity185 / 185
34.93 (1-3/8”)15.88 (5/8”)
5979
230 + 230920 + 9207601710
380-415v, 50HzThree8 + 8
17.5 / 18.3-20~15.5 / -5~461 x 20 / 1 x 204 + earth
56.050.050.448.746.012.8113.7714.6111.668.68
4.37 / 3.63- / 5.6732
50-130% OU Capacity185 / 185
34.93 (1-3/8”)15.88 (5/8”)
59.579.5
255 + 230920 + 9207601710
380-415v, 50HzThree8 + 8
20.7 / 22.2-20~15.5 / -5~461 x 20 / 1 x 204 + earth
63.056.056.754.851.514.4415.6816.4713.149.88
4.36 / 3.57- / 7.7132
50-130% OU Capacity185 / 185
34.93 (1-3/8”)15.88 (5/8”)
6080
255 + 255920 + 9207601710
380-415v, 50HzThree8 + 8
24.2 / 26.2-20~15.5 / -5~461 x 20 / 1 x 204 + earth
69.063.062.160.058.016.6217.5018.9515.1211.03
4.15 / 3.60- / 6.0032
50-130% OU Capacity185 / 185
34.93 (1-3/8”)15.88 (5/8”)
6181
255 + 255920 + 9207601710
380-415v, 50HzThree8 + 8
27.3 / 28.7-20~15.5 / -5~461 x 25 / 1 x 204 + earth
76.569.068.966.663.519.2218.5921.9217.4911.72
3.98 / 3.71- / 5.9032
50-130% OU Capacity185 / 185
34.93 (1-3/8”)19.05 (3/4”)
6282
255 + 255920 + 9207601710
380-415v, 50HzThree8 + 8
31.1 / 30.8-20~15.5 / -5~461 x 25 / 1 x 254 + earth
81.573.073.470.967.221.7321.0924.7819.7713.29
3.75 / 3.46- / 5.5032
50-130% OU Capacity185 / 185
41.28 (1-5/8”)19.05 (3/4”)
62.582.5
255 + 255920 + 9207601710
380-415v, 50HzThree8 + 8
35.0 / 34.0-20~15.5 / -5~461 x 32 / 1 x 254 + earth
PUHY-RP200YJM-B
PUHY-RP250YJM-B
PUHY-RP300YJM-B
PUHY-RP350YJM-B
PUHY-RP400YSJM-B
PUHY-RP450YSJM-B
PUHY-RP500YSJM-B
PUHY-RP550YSJM-B
PUHY-RP600YSJM-B
PUHY-RP650YSJM-B
Note: * A separate power supply is required for each module. Where more than one figure is quoted there are multiple modules.
50.045.044.943.040.113.1512.2615.0112.796.16
3.80 / 3.67- / -34
50~130% OU Capacity320
28.58 (1-1/8”)12.7 (1/2”)62.582.53181750740 1710
380-415v, 50HzThree8
20.3 / 18.9-20~15.5 / -5~52
1 x 404
PUHY-EP400YLM-A
CAPACITY (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)POWER INPUT (kW) Heating (nominal) Cooling (nominal) High Performance Heating (UK) COP Priority Heating (UK) Cooling (UK)COP / EER (nominal)SCOP / SEERMAX No. OF CONNECTABLE INDOOR UNITSMAX CONNECTABLE CAPACITYAIRFLOW (m3/min) HighPIPE SIZE mm (in) Gas LiquidSOUND PRESSURE LEVEL (dBA)SOUND POWER LEVEL (dBA)WEIGHT (kg)DIMENSIONS (mm) Width Depth(1650mm without legs) HeightELECTRICAL SUPPLY*PHASE*STARTING CURRENT (A)*NOMINAL SYSTEM HeatingRUNNING CURRENT (A)* CoolingGUARANTEED OPERATING RANGE (ºC) Heating / CoolingFUSE RATING (MCB sizes BS EN 60947-2) - (A)*MAINS CABLE No. Cores*
REPLACE HEAT PUMP88.080.088.076.673.620.1322.2225.3718.7214.45
4.37 / 3.60- / 6.0332
50~130% OU Capacity185 / 185 / 18541.28 (1-5/8”)19.05 (3/4”)
61.581.5
255 + 255 + 230920 + 920 + 920
7601710
380-415v, 50HzThree8 + 8 + 833.036.4
-20~15.5 / -5~461 x 20 / 1 x 20 / 1 x 20
4 + earth
95.085.095.082.778.221.7824.1427.4520.2615.70
4.36 / 3.52- / 6.2332
50~130% OU Capacity185 / 185 / 18541.28 (1-5/8”)19.05 (3/4”)
6282
255 + 255 + 255920 + 920 + 920
7601710
380-415v, 50HzThree8 + 8 + 836.539.7
-20~15.5 / -5~461 x 20 / 1 x 20 / 1 x 20
4 + earth
100.090.0100.087.082.823.7525.4929.9322.0916.57
4.21 / 3.53- / 5.9232
50~130% OU Capacity185 / 185 / 18541.28 (1-5/8”)19.05 (3/4”)
62.582.5
255 + 255 + 255920 + 920 + 920
7601710
380-415v, 50HzThree8 + 8 + 839.342.0
-20~15.5 / -5~461 x 25 / 1 x 20 / 1 x 20
4 + earth
108.096.0103.794.088.326.4727.1135.2124.0916.54
4.08 / 3.54- / 5.8932
50~130% OU Capacity185 / 185 / 18541.28 (1-5/8”)19.05 (3/4”)
63.583.5
255 + 255 + 255920 + 920 + 920
7601710
380-415v, 50HzThree8 + 8 + 843.244.1
-20~15.5 / -5~461 x 25 / 1 x 25 / 1 x 20
4 + earth
113.0101.0108.598.392.928.3928.2937.7625.8317.26
3.98 / 3.57- / 5.6032
50~130% OU Capacity185 / 185 / 18541.28 (1-5/8”)19.05 (3/4”)
6484
255 + 255 + 255920 + 920 + 920
7601710
380-415v, 50HzThree8 + 8 + 845.945.7
-20~15.5 / -5~461 x 25 / 1 x 25 / 1 x 25
4 + earth
PUHY-RP700YSJM-B PUHY-RP750YSJM-B PUHY-RP800YSJM-B PUHY-RP850YSJM-B PUHY-RP900YSJM-B
Note: * A separate power supply is required for each module. Where more than one figure is quoted there are multiple modules.
STANDARD HEAT RECOVERYCAPACITY (kW) Heating (nominal)
Cooling (nominal)
High Performance Heating (UK)
COP Priority Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
High Performance Heating (UK)
COP Priority Heating (UK)
Cooling (UK)
COP / EER (nominal)
SCOP / SEER
MAX No. OF CONNECTABLE INDOOR UNITS
MAX CONNECTABLE CAPACITY
AIRFLOW (m3/min) High
PIPE SIZE mm (in) Gas
Liquid
SOUND PRESSURE LEVEL (dBA)
SOUND POWER LEVEL (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY*
PHASE*
STARTING CURRENT (A)*
NOMINAL SYSTEM Heating
RUNNING CURRENT (A)* Cooling
GUARANTEED OPERATING RANGE (ºC) Heating / Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)*
MAINS CABLE No. Cores*
25.0
22.4
25.0
22.8
21.3
5.69
5.18
7.17
5.63
2.98
4.39 / 4.32
4.87 / 7.27
20
50~150% OU Capacity
185
15.88 (5/8”)
19.05 (3/4”)
56
76
240
920
760
1710
380-415v, 50Hz
Three
8
8.7
8.0
-20~15.5 / -5~46
1 x 20
4 + earth
31.5
28.0
31.5
28.7
26.6
7.32
7.05
9.22
7.25
4.05
4.30 / 3.97
4.98 / 6.99
25
50~150% OU Capacity
185
19.05 (3/4”)
22.2 (7/8”)
57
77
240
920
760
1710
380-415v, 50Hz
Three
8
11.3
10.8
-20~15.5 / -5~46
1 x 20
4 + earth
37.5
33.5
35.6
32.3
31.5
8.78
8.67
11.77
8.52
5.59
4.27 / 3.86
5.04 / 6.42
30
50~150% OU Capacity
185
19.05 (3/4”)
22.2 (7/8”)
59
79
245
920
760
1710
380-415v, 50Hz
Three
8
13.5
13.4
-20~15.5 / -5~46
1 x 25
4 + earth
45.0
40.0
42.8
38.7
37.6
10.89
11.33
14.59
10.56
7.31
4.13 / 3.53
4.95 / 6.32
35
50~150% OU Capacity
225
19.05 (3/4”)
28.58 (1-1/8”)
60
80
270
1220
760
1710
380-415v, 50Hz
Three
8
16.8
17.5
-20~15.5 / -5~46
1 x 32
4 + earth
50.0
45.0
47.5
43.0
42.3
12.75
13.55
17.09
12.37
8.74
3.92 / 3.32
4.96 / 5.81
40
50~150% OU Capacity
225
22.2 (7/8”)
28.58 (1-1/8”)
61
81
270
1220
760
1710
380-415v, 50Hz
Three
8
19.7
20.9
-20~15.5 / -5~46
1 x 40
4 + earth
56.0
50.0
50.7
48.7
46.0
14.58
14.49
16.62
13.27
9.13
3.84 / 3.45
5.13 / 6.21
45
50~150% OU Capacity
360
22.2 (7/8”)
28.58 (1-1/8”)
62
82
320
1750
760
1710
380-415v, 50Hz
Three
8
22.5
22.3
-20~15.5 / -5~46
1 x 40
4 + earth
PURY-P200YJM-A PURY-P250YJM-A PURY-P300YJM-A PURY-P350YJM-A PURY-P400YJM-A PURY-P450YJM-A
STANDARD HEAT RECOVERYCAPACITY (kW) Heating (nominal)
Cooling (nominal)
High Performance Heating (UK)
COP Priority Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
High Performance Heating (UK)
COP Priority Heating (UK)
Cooling (UK)
COP / EER (nominal)
SCOP / SEER
MAX No. OF CONNECTABLE INDOOR UNITS
MAX CONNECTABLE CAPACITY
AIRFLOW (m3/min) High
PIPE SIZE mm (in) Gas
Liquid
SOUND PRESSURE LEVEL (dBA)
SOUND POWER LEVEL (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY*
PHASE*
STARTING CURRENT (A)*
NOMINAL SYSTEM Heating
RUNNING CURRENT (A)* Cooling
GUARANTEED OPERATING RANGE (ºC) Heating / Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)*
MAINS CABLE No. Cores*
56.0
50.0
50.7
48.7
46.0
13.30
12.50
15.16
12.10
7.88
4.21 / 4.00
4.97 / 6.67
45
50~150% OU Capacity
185 / 185
22.2 (7/8”)
28.58 (1-1/8”)
59.5
79.5
240 + 240
920 + 920
760
1710
380-415v, 50Hz
Three
8 / 8
20.5
19.3
-20~15.5 / -5~46
1 x 20 / 1 x 20
4 + earth
63.0
56.0
57.0
54.8
51.5
15.10
14.85
17.21
13.74
9.36
4.17 / 3.77
5.01 / 6.40
50
50~150% OU Capacity
185 / 185
22.2 (7/8”)
28.58 (1-1/8”)
60
80
240 + 240
920 + 920
760
1710
380-415v, 50Hz
Three
8 / 8
23.3
22.9
-20~15.5 / -5~46
1 x 20 / 1 x 20
4 + earth
69.0
63.0
62.4
60.0
58.0
16.95
17.30
19.32
15.42
10.90
4.07 / 3.64
4.88 / 6.20
50
50~150% OU Capacity
185 / 185
28.58 (1-1/8”)
28.58 (1-1/8”)
61
81
245 + 240
920 + 920
760
1710
380-415v, 50Hz
Three
8 / 8
26.2
26.7
-20~15.5 / -5~46
1 x 25 / 1 x 20
4 + earth
76.5
69.0
69.2
66.6
63.5
19.07
19.65
21.74
17.35
12.38
4.01 / 3.51
4.80 / 6.04
50
50~150% OU Capacity
185 / 185
28.58 (1-1/8”)
28.58 (1-1/8”)
62
82
245 + 245
920 + 920
760
1710
380-415v, 50Hz
Three
8 / 8
29.4
30.3
-20~15.5 / -5~46
1 x 25 / 1 x 25
4 + earth
81.5
73.0
73.8
70.9
67.2
20.47
21.53
23.34
18.63
13.56
3.98 / 3.39
4.97 / 5.94
50
50~150% OU Capacity
225 / 185
28.58 (1-1/8”)
28.58 (1-1/8”)
62.5
82.5
270 + 245
1220 + 920
760
1710
380-415v, 50Hz
Three
8 / 8
31.6
33.2
-20~15.5 / -5~46
1 x 32 / 1 x 25
4 + earth
88.0
80.0
88.0
76.6
73.6
22.33
23.95
28.14
20.77
15.45
3.94 / 3.34
5.04 / 5.69
50
50~150% OU Capacity
225 / 185
28.58 (1-1/8”)
34.93 (1-3/8”)
63
83
270 + 245
1220 + 920
760
1710
380-415v, 50Hz
Three
8 / 8
34.5
37.0
-20~15.5 / -5~46
1 x 40 / 1 x 25
4 + earth
PURY-P450YSJM-A1 PURY-P500YSJM-A PURY-P550YSJM-A PURY-P600YSJM-A PURY-P650YSJM-A PURY-P700YSJM-A
Note: * A separate power supply is required for each module. Where more than one figure is quoted there are multiple modules.
Page 36
Heat Recovery Outdoor Unit (R2 Series) Specifications
Page 37
TOTAL PIPING LENGTH
FURTHEST PIPING LENGTH
FURTHEST PIPING LENGTH AFTER 1st BRANCH
BETWEEN INDOOR AND OUTDOOR UNITS - HEIGHT
BETWEEN INDOOR AND INDOOR UNITS - HEIGHT
300m max
150m max
30m max
50m max (40m max if outdoor installed below)
15m max
PUMY-P112-140VKM/YKMPIPING RESTRICTIONS
TOTAL PIPING LENGTH
FURTHEST PIPING LENGTH
FURTHEST PIPING LENGTH AFTER 1st BRANCH
BETWEEN INDOOR AND OUTDOOR UNITS - HEIGHT
BETWEEN INDOOR AND INDOOR UNITS - HEIGHT
1000m max
165m max
40m max
50m max (40m max if outdoor installed below)
15m max
PUHY-P200-1250Y(S)JM-APIPING RESTRICTIONS
TOTAL PIPING LENGTH
FURTHEST PIPING LENGTH
FURTHEST PIPING LENGTH AFTER 1st BRANCH
BETWEEN INDOOR AND OUTDOOR UNITS - HEIGHT
BETWEEN INDOOR AND INDOOR UNITS - HEIGHT
1000m max
165m max
40m*1 max
50 max (40m max if outdoor installed below)
15m*2 max
PUHY-EP200-900Y(S)LM-APIPING RESTRICTIONS
Notes: *1 90m is available. When the piping length is 40m or longer, use the one size larger liquid pipe between the first joint all the way to all indoor units greater than 40m from first joint. *2 30m is available. When the piping length is 15m or longer, use the one size larger liquid pipe between the first joint all the way to all indoor units greater than 15m from first joint.
TOTAL PIPING LENGTH
FURTHEST PIPING LENGTH
FURTHEST PIPING LENGTH AFTER 1st BRANCH
BETWEEN INDOOR AND OUTDOOR UNITS - HEIGHT
BETWEEN INDOOR AND INDOOR UNITS - HEIGHT
300m max
150m max
40m max
50m max (40m max if outdoor installed below)
15m max
PUHY-HP200-500Y(S)HM-APIPING RESTRICTIONS
TOTAL PIPING LENGTH
FURTHEST PIPING LENGTH
FURTHEST PIPING LENGTH AFTER 1st BRANCH
BETWEEN INDOOR AND OUTDOOR UNITS - HEIGHT
BETWEEN INDOOR AND INDOOR UNITS - HEIGHT
300m max (250m for size 600-650)
120m max
40m max
50m max (40m max if outdoor installed below)
15m max
PUHY-RP200-650Y(S)JM-BPIPING RESTRICTIONS
Y Series Piping Restrictions
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
High Performance Heating (UK)
COP Priority Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
High Performance Heating (UK)
COP Priority Heating (UK)
Cooling (UK)
COP / EER (nominal)
SCOP / SEER
MAX No. OF CONNECTABLE INDOOR UNITS
MAX CONNECTABLE CAPACITY
AIRFLOW (m3/min) High
PIPE SIZE mm (in) Gas
Liquid
SOUND PRESSURE LEVEL (dBA)
SOUND POWER LEVEL (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY *
PHASE*
STARTING CURRENT (A)*
NOMINAL SYSTEM RUNNING CURRENT (A)* Heating /Cooling
GUARANTEED OPERATING RANGE (ºC) Heating / Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)*
MAINS CABLE No. Cores*
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
High Performance Heating (UK)
COP Priority Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
High Performance Heating (UK)
COP Priority Heating (UK)
Cooling (UK)
COP / EER (nominal)
SCOP / SEER
MAX No. OF CONNECTABLE INDOOR UNITS
MAX CONNECTABLE CAPACITY
AIRFLOW (m3/min) High
PIPE SIZE mm (in) Gas
Liquid
SOUND PRESSURE LEVEL (dBA)
SOUND POWER LEVEL (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY*
PHASE*
STARTING CURRENT (A)*
NOMINAL SYSTEM RUNNING CURRENT (A)* Heating /Cooling
GUARANTEED OPERATING RANGE (ºC) Heating / Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)*
MAINS CABLE No. Cores*
STANDARD HEAT RECOVERY95.0
85.0
95.0
82.7
78.2
24.05
26.47
30.30
22.37
17.07
3.95 / 3.21
5.05 / 5.75
50
50~150% OU Capacity
225 / 225
28.58 (1-1/8”)
34.93 (1-3/8”)
63.5
83.5
270 + 270
1220 + 1220
760
1710
380-415v, 50Hz
Three
8 / 8
37.1 / 40.9
-20~15.5 / -5~46
1 x 40 / 1 x 32
4 + earth
100.0
90.0
100.0
87.0
82.8
26.04
28.30
32.81
24.22
18.25
3.84 / 3.18
5.07 / 5.66
50
50~150% OU Capacity
225 / 225
28.58 (1-1/8”)
34.93 (1-3/8”)
64
84
270 + 270
1220 + 1220
760
1710
380-415v, 50Hz
Three
8 / 8
40.2 / 43.7
-20~15.5 / -5~46
1 x 40 / 1 x 40
4 + earth
108.0
96.0
102.6
95.0
88.3
28.42
29.26
37.80
26.15
17.85
3.80 / 3.28
4.95 / 6.18
50
50~150% OU Capacity
360 / 225
28.58 (1-1/8”)
41.28 (1-5/8”)
64.5
84.5
320 + 270
1750 + 1220
760
1710
380-415v, 50Hz
Three
8 / 8
43.9 / 45.2
-20~15.5 / -5~46
1 x 40 / 1 x 40
4 + earth
113.0
101.0
107.4
99.4
92.9
30.05
30.23
39.97
27.65
18.44
3.76 / 3.34
4.99 / 6.29
50
50~150% OU Capacity
360 / 360
28.58 (1-1/8”)
41.28 (1-5/8”)
65
85
320 + 320
1750 + 1750
760
1710
380-415v, 50Hz
Three
8 / 8
46.4 / 46.7
-20~15.5 / -5~46
1 x 40 / 1 x 40
4 + earth
PURY-P750YSJM-A PURY-P800YSJM-A PURY-P850YSJM-A PURY-P900YSJM-A
HIGH EFFICIENCY HEAT RECOVERY25.0
22.4
25.0
22.8
20.0
6.41
5.48
8.03
6.37
2.42
3.90 / 4.08
- / -
20
50~150% OU Capacity
185
15.88 (5/8”)
19.05 (3/4”)
59
82.5
218
920
740
1710
380-415v, 50Hz
Three
8
9.9 / 8.4
-20~15.5 / -5~46
1 x 20
4
31.5
28.0
31.5
28.7
25.0
8.45
7.25
10.58
8.40
3.11
3.72 / 3.86
- / -
25
50~150% OU Capacity
185
19.05 (3/4”)
22.2 (7/8”)
60
83.5
218
920
740
1710
380-415v, 50Hz
Three
8
13.0 / 11.2
-20~15.5 / -5~46
1 x 20
4
37.5
33.5
35.6
32.3
29.8
9.97
9.20
13.30
9.68
4.63
3.76 / 3.74
- / -
30
50~150% OU Capacity
230
19.05 (3/4”)
22.2 (7/8”)
62.5
86
260
1220
740
1710
380-415v, 50Hz
Three
8
15.4 / 14.2
-20~15.5 / -5~46
1 x 25
4
45.0
40.0
42.8
38.7
35.6
12.93
12.57
17.25
12.56
5.94
3.48 / 3.18
- / -
35
50~150% OU Capacity
230
19.05 (3/4”)
28.58 (1-1/8”)
62.5
86
260
1220
740
1710
380-415v, 50Hz
Three
8
19.9 / 19.4
-20~15.5 / -5~46
1 x 32
4
50.0
45.0
47.5
43.0
40.1
13.40
12.56
17.88
13.01
6.17
3.73 / 3.58
- / -
40
50~150% OU Capacity
320
22.2 (7/8”)
28.58 (1-1/8”)
62.5
86
338
1750
740
1710
380-415v, 50Hz
Three
8 / 8
20.7 / 19.4
-20~15.5 / -5~46
1 x 32
4
56.0
50.0
50.7
48.7
44.4
15.86
14.83
18.10
14.50
6.94
3.53 / 3.37
- / -
45
50~150% OU Capacity
320
22.2 (7/8”)
28.58 (1-1/8”)
62.5
86
338
1750
740
1710
380-415v, 50Hz
Three
8 / 8
24.5 / 22.9
-20~15.5 / -5~46
1 x 40
4
PURY-EP200YLM-A PURY-EP250YLM-A PURY-EP300YLM-A PURY-EP350YLM-A PURY-EP400YLM-A PURY-EP450YLM-A
63.0
56.0
57.0
54.8
49.7
19.54
18.30
22.30
17.86
7.85
3.22 / 3.06
- / -
50
50~150% OU Capacity
380
22.2 (7/8”)
28.58 (1-1/8”)
63.5
87
351
1750
740
1710
380-415v, 50Hz
Three
8 / 8
30.2 / 28.2
-20~15.5 / -5~46
1 x 63
4
PURY-EP500YLM-A
Note: * A separate power supply is required for each module. Where more than one figure is quoted there are multiple modules.
HIGH EFFICIENCY HEAT RECOVERYCAPACITY (kW) Heating (nominal)
Cooling (nominal)
High Performance Heating (UK)
COP Priority Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
High Performance Heating (UK)
COP Priority Heating (UK)
Cooling (UK)
COP / EER (nominal)
SCOP / SEER
MAX No. OF CONNECTABLE INDOOR UNITS
MAX CONNECTABLE CAPACITY
AIRFLOW (m3/min) High
PIPE SIZE mm (in) Gas
Liquid
SOUND PRESSURE LEVEL (dBA)
SOUND POWER LEVEL (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY *
PHASE*
STARTING CURRENT (A)*
NOMINAL SYSTEM RUNNING CURRENT (A)* Heating /Cooling
GUARANTEED OPERATING RANGE (ºC) Heating / Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)*
MAINS CABLE No. Cores*
69.0
63.0
62.4
60.0
55.9
18.44
17.35
21.05
16.86
8.49
3.74 / 3.63
- / -
50
50~150% OU Capacity
230 / 185
28.58 (1-1/8”)
28.58 (1-1/8”)
64.5
88
260 + 218
1220 + 920
740
1710
380-415v, 50Hz
Three
8 / 8
28.5 / 26.8
-20~15.5 / -5~46
1 x 25 / 1 x 20
4
76.5
69.0
69.2
66.6
61.2
20.34
19.54
23.22
18.59
9.80
3.76 / 3.53
- / -
50
50~150% OU Capacity
230 / 230
28.58 (1-1/8”)
28.58 (1-1/8”)
65.5
89
260 + 260
1220 + 1220
740
1710
380-415v, 50Hz
Three
8 / 8
31.4 / 30.2
-20~15.5 / -5~46
1 x 25 / 1 x 25
4
81.5
73.0
73.8
70.9
64.8
22.51
22.12
25.69
20.58
10.79
3.62 / 3.30
- / -
50
50~150% OU Capacity
230 / 230
28.58 (1-1/8”)
28.58 (1-1/8”)
65.5
89
260 + 260
1220 + 1220
740
1710
380-415v, 50Hz
Three
8 / 8
34.7 / 34.1
-20~15.5 / -5~46
1 x 32 / 1 x 25
4
88.0
80.0
88.0
76.6
69.5
25.28
25.97
31.64
23.47
11.85
3.48 / 3.08
- / -
50
50~150% OU Capacity
230 / 230
28.58 (1-1/8”)
34.93 (1-3/8”)
65.5
89
260 + 260
1220 + 1220
740
1710
380-415v, 50Hz
Three
8 / 8
39.0 / 40.1
-20~15.5 / -5~46
1 x 32 / 1 x 32
4
PURY-EP550YSLM-A PURY-EP600YSLM-A PURY-EP650YSLM-A PURY-EP700YSLM-A
HIGH EFFICIENCY HEAT RECOVERYCAPACITY (kW) Heating (nominal)
Cooling (nominal)
High Performance Heating (UK)
COP Priority Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
High Performance Heating (UK)
COP Priority Heating (UK)
Cooling (UK)
COP / EER (nominal)
SCOP / SEER
MAX No. OF CONNECTABLE INDOOR UNITS
MAX CONNECTABLE CAPACITY
AIRFLOW (m3/min) High
PIPE SIZE mm (in) Gas
Liquid
SOUND PRESSURE LEVEL (dBA)
SOUND POWER LEVEL (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY *
PHASE*
STARTING CURRENT (A)*
NOMINAL SYSTEM RUNNING CURRENT (A)* Heating /Cooling
GUARANTEED OPERATING RANGE (ºC) Heating / Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)*
MAINS CABLE No. Cores*
95.0
85.0
95.0
82.7
73.8
26.38
25.99
33.02
24.48
12.11
3.60 / 3.27
- / -
50
50~150% OU Capacity
320 / 320
28.58 (1-1/8”)
34.93 (1-3/8”)
65.5
89
338 + 260
1750 + 1220
740
1710
380-415v, 50Hz
Three
8 / 8
40.7 / 40.1
-20~15.5 / -5~46
1 x 32 / 1 x 32
4
100.0
90.0
100.0
87.0
78.2
26.80
25.93
33.54
24.87
12.34
3.73 / 3.47
- / -
50
50~150% OU Capacity
320 / 320
28.58 (1-1/8”)
34.93 (1-3/8”)
65.5
89
338 + 338
1750 + 1750
740
1710
380-415v, 50Hz
Three
8 / 8
41.4 / 40.0
-20~15.5 / -5~46
1 x 32 / 1 x 32
4
108.0
96.0
102.8
94.8
85.2
29.75
28.48
39.69
27.19
13.29
3.63 / 3.37
- / -
50
50~150% OU Capacity
320 / 320
28.58 (1-1/8”)
41.28 (1-5/8”)
65.5
89
338 + 338
1750 + 1750
740
1710
380-415v, 50Hz
Three
8 / 8
45.9 / 44.0
-20~15.5 / -5~46
1 x 40 / 1 x 32
4
113.0
101.0
107.6
99.2
89.6
32.01
30.98
42.71
29.26
14.11
3.53 / 3.26
- / -
50
50~150% OU Capacity
320 / 320
28.58 (1-1/8”)
41.28 (1-5/8”)
65.5
89
338 + 338
1750 + 1750
740
1710
380-415v, 50Hz
Three
8 / 8
49.4 / 47.8
-20~15.5 / -5~46
1 x 40 / 1 x 40
4
PURY-EP750YSLM-A PURY-EP800YSLM-A PURY-EP850YSLM-A PURY-EP900YSLM-A
Note: * A separate power supply is required for each module. Where more than one figure is quoted there are multiple modules.
Page 38 Page 39
REPLACE HEAT RECOVERYCAPACITY (kW) Heating (nominal)
Cooling (nominal)
High Performance Heating (UK)
COP Priority Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
High Performance Heating (UK)
COP Priority Heating (UK)
Cooling (UK)
COP / EER (nominal)
SCOP / SEER
MAX No. OF CONNECTABLE INDOOR UNITS
MAX CONNECTABLE CAPACITY
AIRFLOW (m3/min) High
PIPE SIZE mm (in) Gas
Liquid
SOUND PRESSURE LEVEL (dBA)
SOUND POWER LEVEL (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY*
PHASE*
STARTING CURRENT (A)*
NOMINAL SYSTEM Heating
RUNNING CURRENT (A)* Cooling
GUARANTEED OPERATING RANGE (ºC) Heating / Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)*
MAINS CABLE No. Cores*
25.0
22.4
24.0
21.8
21.1
5.50
4.95
7.26
5.34
3.61
4.54 / 4.52
- / 5.75
20
50~150% OU Capacity
225
19.05 (3/4”)
28.58 (1-1/8”)
56
76
275
1220
760
1710
380-415v, 50Hz
Three
8
8.9
8.0
-20~15.5 / -5~46
1 x 20
4 + earth
31.5
28.0
30.2
27.4
26.3
7.22
6.82
9.53
7.00
4.98
4.36 / 4.10
- / 5.15
25
50~150% OU Capacity
225
19.05 (3/4”)
28.58 (1-1/8”)
57
77
290
1220
760
1710
380-415v, 50Hz
Three
8
11.9
11.2
-20~15.5 / -5~46
1 x 20
4 + earth
37.5
33.5
36.0
32.6
31.5
8.70
8.35
11.48
8.44
6.10
4.31 / 4.01
- / 4.98
30
50~150% OU Capacity
225
19.05 (3/4”)
28.58 (1-1/8”)
59
79
290
1220
760
1710
380-415v, 50Hz
Three
8
14.6
13.6
-20~15.5 / -5~46
1 x 25
4 + earth
PURY-RP200YJM-B PURY-RP250YJM-B PURY-RP300YJM-B
Page 40 Page 41
BC CONTROLLERSNUMBER OF CONNECTIONS
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
POWER INPUT (kW)
RUNNING CURRENT (A)
FUSE RATING (BS88) – HRC (A)
MAINS CABLE No. Cores
4
24
648
432
284
220-240v, 50Hz
Single
0.085
0.36
6
3
5
27
648
432
284
220-240v, 50Hz
Single
0.104
0.44
6
3
6
28
648
432
284
220-240v, 50Hz
Single
0.123
0.52
6
3
CMB-P104V-G1 CMB-P105V-G1 CMB-P106V-G1
Note: CMB-P-V-G1 units are for use with PURY-P200-350YJM-A, PURY-EP200-350YLM-A & PQRY-P200-300YHM-A units only.
MASTER BC CONTROLLERSNUMBER OF CONNECTIONS
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
POWER INPUT (KW)
RUNNING CURRENT (A)
FUSE RATING (BS88) – HRC (A)
MAINS CABLE No. Cores
8
43
1110
520
289
220-240v, 50Hz
Single
0.161
0.68
6
3
10
48
1110
520
289
220-240v, 50Hz
Single
0.198
0.83
6
3
13
55
1110
520
289
220-240v, 50Hz
Single
0.255
1.07
6
3
16
62
1110
520
289
220-240v, 50Hz
Single
0.312
1.30
6
3
16
69
1110
520
289
220-240v, 50Hz
Single
0.312
1.30
6
3
CMB-P108V-GA1 CMB-P1010V-GA1 CMB-P1013V-GA1 CMB-P1016V-GA1 CMB-P1016V-HA1
SLAVE BC CONTROLLERSNUMBER OF CONNECTIONS
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
POWER INPUT (KW)
RUNNING CURRENT (A)
FUSE RATING (BS88) – HRC (A)
MAINS CABLE No. Cores
4
22
648
432
284
220-240v, 50Hz
Single
0.076
0.32
6
3
8
32
648
432
284
220-240v, 50Hz
Single
0.151
0.63
6
3
16
55
1098
432
284
220-240v, 50Hz
Single
0.301
1.26
6
3
CMB-P104V-GB1 CMB-P108V-GB1 CMB-P1016V-HB1
Notes: CMB-P-V-GA1 units are for use with PURY-P200-650Y(S)JM-A(1), PURY-EP200-650Y(S)LM-A & PQRY-P200-600Y(S)HM-A units only. CMB-P1016V-HA1 unit is for use with PURY-P700-900YSJM-A & PURY-EP700-900YSLM-A units only.
BC Controllers
CITY MULTI BC BOX COMBINATION TABLE
CMB-P V-G1CMB-P V-GA1CMB-P V-HA1CMB-P V-GB1CMB-P V-HB1
MASTERMASTERMASTERSLAVESLAVE
4, 5, 68, 10, 13, 16164, 816
YESYESNOYESYES
NOYESNOYES YES
NONOYESYESYES
MODEL TYPE PORTS P200,250,300,350CMB-P V-GA1
CMB-P V-GA1
CMB-P V-GA1
CMB-P V-GA1
CMB-P V-GA1
CMB-P V-HA1
CMB-P V-HA1
CMB-P V-HA1
CMB-P V-HA1
CMB-P V-HA1
CMB-P V-GB1
CMB-P V-HB1
CMB-P V-GB1
CMB-P V-GB1
CMB-P V-HB1
CMB-P V-GB1
CMB-P V-HB1
CMB-P V-GB1
CMB-P V-GB1
CMB-P V-HB1
--CMB-P V-GB1
CMB-P V-HB1
CMB-P V-HB1
-
-
CMB-P V-GB1
CMB-P V-HB1
CMB-P V-HB1
350
350
350
450
450
350
350
350
450
450
MASTER SUB 1 SUB 2 SUB INDEXP400-650 P700-800
MAXIMUM FAN COIL INDEX PER BC PORT = 140, MAX NUMBER OF FAN COILS = X 3
Note: * A separate power supply is required for each module. Where more than one figure is quoted there are multiple modules.
R2 Series Piping Restrictions
1
(CMY-Y202SS-G2CMY-Y102LS-G2CMY-102SS-G2)
(P200-P250)
(
1
(CMY-Y202SS-G2CMY-Y102LS-G2CMY-102SS-G2)
(P200-P250)
Refer to City Multi Accessories/Optional Extras section for detail.
Please Note: this does not apply to PURY-RP models
(>1 BC CONTROLLER FOR 1 OUTDOOR UNIT)
Total Piping Length
Furthest Piping Length
Length Between OU and BC
Length Between Furthest IU and BC
Height Between OU and IU (OU above IU)
Height Between OU and IU (OU below IU)
Height Between IU and BC
Height Between IU and IU
Height Between BC (Main or Sub) and BC (Sub)
A+B+C+D+E+a+b+c+d+e+f
A+C+E+f
A
B+d or C+D+e or C+E+f
H
H,
h1
h2
h3
(See Table 1)
165m
110m*1
60m*2 (40m)
50m
40m
15m
15m
15m
PIPE SECTION MAX LENGTH
PIPE LENGTH
Notes: *1 Please refer to Graph 1. *2 Height difference between BC controller and furthest indoor unit is zero.
(>1 BC CONTROLLER FOR 2 OUTDOOR UNITS)
Total Piping Length
Furthest Piping Length
Length Between OU and BC
Length Between Furthest IU and BC
Height Between OU and IU (OU above IU)
Height Between OU and IU (OU below IU)
Height Between IU and BC
Height Between IU and IU
Height Between BC (Main or Sub) and BC (Sub)
Length Between Main OU and Sub OU
Height Between Main OU and Sub OU
F+G+H+A+B+C+D+E+a+b+c+d+e+f
F(G)+A+C+E+f
F(G)+A
B+d or C+D+e or C+E+f
H
H,
h1
h2
h3
F+G or H
h4
(See Table 1)
165m
110m*1
60m*2 (40m)
50m
40m
15m
15m
15m
5m
0.1m
PIPE SECTION MAX LENGTH
PIPE LENGTH
Notes: *1 Please refer to Graph 1. *2 Height difference between BC controller and furthest indoor unit is zero.
Page 42 Page 43
R2 Series Piping Restrictions
Note: *1 Please refer to Graph 1.
1000
PURY-P700,750,800,850,900YSJM-A, PURY-EP700,750,800,850,900YSLM-A
PURY-P600,650YSJM-A, PURY-EP600,650YSLM-APURY-P500,550YSJM-A, PURY-EP550YSLM-A
PURY-P350,400,450Y(S)JM-A(1), PURY-EP300,350,400,450,500YLM-A
PURY-P200,250,300YJM-A, PURY-EP200,250YLM-A
900
800
700
600
500
400
300
200
100
0
10 20 30 40 50 60 70 80 90 100 110
Total Extended Pipe Length (m)
Distance Between Outdoor Unit and BC Controller (m)
OUTDOOR MODELP200, P250, P300, EP200, EP250
P350, P400, P450, EP300, EP350, EP400, EP450, EP500
P500, P550, EP550
P600, P650, EP600, EP650
P700, P750, P800, P850, P900, EP700, EP750, EP800, EP850, EP900
550m*1
600m*1
750m*1
800m*1
950m*1
MAX LENGTH
GRAPH 1: TOTAL PIPING LENGTH RESTRICTIONS
TABLE 1: TOTAL PIPE LENGTH
(1 BC CONTROLLER, NO SUB BC CONTROLLER)
Total Piping Length
Furthest Piping Length
Length Between OU and BC
Length Between Furthest IU and BC
Height Between OU and IU (OU above IU)
Height Between OU and IU (OU below IU)
Height Between IU and BC
Height Between IU and IU
A+B+a+b+c+d
A+B+d
A
B+d
H
H,
h1
h2
(See Table 1)
165m
110m*1
60m*2 (40m)
50m
40m
15m
15m
PIPE SECTION MAX LENGTH
PIPE LENGTH
CMB-P-V-GA1/HA1 is used.
(P200-P250)
Notes: *1 Please refer to Graph 1. *2 Height difference between BC controller and furthest indoor unit is zero.
Please Note: this does not apply to PURY-RP models
CAPACITY (kW) Heating (nominal) Cooling (nominal) High Performance Heating COP Priority Heating Cooling (UK) POWER INPUT (kW) Heating (nominal) Cooling (nominal) High Performance Heating COP Priority Heating Cooling (UK) COP / EER (nominal)
SCOP / SEER
MAX No. OF CONNECTABLE INDOOR UNITS
MAX CONNECTABLE CAPACITY AIRFLOW (m3/min)
PIPE SIZE mm (in) Gas
Liquid
SOUND PRESSURE LEVEL (dBA)
SOUND POWER LEVEL (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width Depth Height (1650 without legs) ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Heating Cooling GUARANTEED OPERATING RANGE (ºC) Heating / Cooling FUSE RATING (MCB sizes BS EN 60947-2) - (A) MAINS CABLE No. CORES
HEAT PUMPCAPACITY (kW) Heating (nominal)
Cooling (nominal)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
COP / EER (nominal)
SCOP / SEER
MAX No. OF CONNECTABLE INDOOR UNITS
MAX CONNECTABLE CAPACITY
PIPE SIZE mm (in) Gas
Liquid
SOUND PRESSURE LEVEL (dBA)
SOUND POWER LEVEL (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1100mm without legs) Height
ELECTRICAL SUPPLY*
PHASE*
STARTING CURRENT (A)*
NOMINAL SYSTEM HeatingRUNNING CURRENT (A)* Cooling
GUARANTEED OPERATING RANGE (ºC) Heating / Cooling
FUSE RATING (BS88) - HRC (A)*
MAINS CABLE No. Cores*
25.0
22.4
4.12
3.92
6.06 / 5.71
5.51 / 5.63
17
50~130% OU Capacity
19.05 (3/4”)
9.52 (3/8”)
47
61
195
880
550
1160
380-415v, 50Hz
Three
8
6.3
6.0
-5~45 / -5~45
1 x 20
4 + earth
31.5
28.0
5.80
5.45
5.43 / 5.13
5.30 / 6.38
21
50~130% OU Capacity
22.2 (7/8”)
9.52 (3/8”)**
49
63
195
880
550
1160
380-415v, 50Hz
Three
8
8.9
8.4
-5~45 / -5~45
1 x 20
4 + earth
37.5
33.5
8.15
7.36
4.60 / 4.55
5.14 / 5.85
26
50~130% OU Capacity
22.2 (7/8”)
9.52 (3/8”)**
50
64
195
880
550
1160
380-415v, 50Hz
Three
8
12.5
11.3
-5~45 / -5~45
1 x 20
4 + earth
50.0
45.0
8.65
8.25
5.78 / 5.45
5.67 / 5.86
34
50~130% OU Capacity
28.58 (1-1/8”)
12.7 (1/2”)
50
64
195 + 195
880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8
13.3
12.7
-5~45 / -5~45
1 x 20 / 1 x 20
4 + earth
56.0
50.0
10.42
9.84
5.37 / 5.08
5.31 / 5.92
39
50~130% OU Capacity
28.58 (1-1/8”)
15.88 (5/8”)
51
65
195 + 195
880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8
16.1
15.2
-5~45 / -5~45
1 x 20 / 1 x 20
4 + earth
63.0
56.0
12.06
11.45
5.22 / 4.89
5.12 / 6.06
43
50~130% OU Capacity
28.58 (1-1/8”)
15.88 (5/8”)
52
66
195 + 195
880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8
18.6
17.6
-5~45 / -5~45
1 x 20 / 1 x 20
4 + earth
69.0
63.0
14.65
13.46
4.70 / 4.68
4.67 / 5.88
47
50~130% OU Capacity
28.58 (1-1/8”)
15.88 (5/8”)
52.5
66.5
195 + 195
880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8
22.6
20.8
-5~45 / -5~45
1 x 20 / 1 x 20
4 + earth
76.5
69.0
17.12
15.48
4.46 / 4.45
5.07 / 5.80
50
50~130% OU Capacity
28.58 (1-1/8”)
15.88 (5/8”)
53
67
195 + 195
880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8
26.4
23.9
-5~45 / -5~45
1 x 20 / 1 x 20
4 + earth
PQHY-P200YHM-A PQHY-P250YHM-A PQHY-P300YHM-A PQHY-P400YSHM-A PQHY-P450YSHM-A PQHY-P500YSHM-A PQHY-P550YSHM-A PQHY-P600YSHM-A HEAT RECOVERY25.022.425.023.021.35.284.796.655.232.78
4.79 / 4.675.00 / 8.43
1350~150% OU Capacity
22515.88 (5/8”)19.05 (3/4”)
608027012207601710
380-415v, 50Hz38.17.4
-20~15 / -5~4620
4 + Earth
31.528.031.529.026.66.986.998.796.914.05
4.51 / 4.004.92 / 7.52
1650~150% OU Capacity
22519.05 (3/4”)22.2 (7/8”)
608027012207601710
380-415v, 50Hz310.810.7
-20~15 / -5~4620
4 + Earth
PURY-WP200YJM-A PURY-WP250YJM-A
Note: The fuse rating is only a typical value, it is the responsibility of a qualified electrician/electrical engineer to select the correct cable size and fuse rating based on current regulation and site specific conditions.
HEAT PUMPCAPACITY (kW) Heating (nominal)
Cooling (nominal)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
COP / EER (nominal)
SCOP / SEER
MAX No. OF CONNECTABLE INDOOR UNITS
MAX CONNECTABLE CAPACITY
PIPE SIZE mm (in) Gas
Liquid
SOUND PRESSURE LEVEL (dBA)
SOUND POWER LEVEL (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1100mm without legs) Height
ELECTRICAL SUPPLY*
PHASE*
STARTING CURRENT (A)*
NOMINAL SYSTEM HeatingRUNNING CURRENT (A)* Cooling
GUARANTEED OPERATING RANGE (ºC) Heating / Cooling
FUSE RATING (BS88) - HRC (A)*
MAINS CABLE No. Cores*
81.5
73.0
14.74
13.96
5.52 / 5.22
4.95 / 5.95
50
50~130% OU Capacity
34.93 (1-3/8”)
19.05 (3/4”)
53
67
195 + 195 + 195
880 + 880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8 / 8
22.7
21.5
-5~45 / -5~45
1 x 20 / 1 x 20 / 1 x 20
4 + earth
88.0
80.0
16.51
15.58
5.33 / 5.13
4.98 / 6.23
50
50~130% OU Capacity
34.93 (1-3/8”)
19.05 (3/4”)
53.5
67.5
195 + 195 + 195
880 + 880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8 / 8
25.5
24.0
-5~45 / -5~45
1 x 20 / 1 x 20 / 1 x 20
4 + earth
95.0
85.0
18.27
17.19
5.19 / 4.94
5.03 / 6.15
50
50~130% OU Capacity
34.93 (1-3/8”)
19.05 (3/4”)
54
68
195 + 195 + 195
880 + 880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8 / 8
28.2
26.5
-5~45 / -5~45
1 x 20 / 1 x 20 / 1 x 20
4 + earth
100.0
90.0
20.74
19.18
4.82 / 4.69
4.85 / 5.89
50
50~130% OU Capacity
34.93 (1-3/8”)
19.05 (3/4”)
54
68
195 + 195 + 195
880 + 880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8 / 8
32.0
29.6
-5~45 / -5~45
1 x 20 / 1 x 20 / 1 x 20
4 + earth
108.0
96.0
23.21
21.20
4.65 / 4.52
4.89 / 5.68
50
50~130% OU Capacity
41.28 (1-5/8”)
19.05 (3/4”)
54.5
68.5
195 + 195 + 195
880 + 880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8 / 8
35.8
32.7
-5~45 / -5~45
1 x 20 / 1 x 20 / 1 x 20
4 + earth
113.0
101.0
25.67
23.22
4.40 / 4.34
4.72 / 5.37
50
50~130% OU Capacity
41.28 (1-5/8”)
19.05 (3/4”)
55
69
195 + 195 + 195
880 + 880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8 / 8
39.6
35.8
-5~45 / -5~45
1 x 20 / 1 x 20 / 1 x 20
4 + earth
PQHY-P650YSHM-A PQHY-P700YSHM-A PQHY-P750YSHM-A PQHY-P800YSHM-A PQHY-P850YSHM-A PQHY-P900YSHM-A
HEAT RECOVERYCAPACITY (kW) Heating (nominal)
Cooling (nominal)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
COP / EER (nominal)
SCOP / SEER
MAX No. OF CONNECTABLE INDOOR UNITS
MAX CONNECTABLE CAPACITY
PIPE SIZE mm (in) Gas
Liquid
SOUND PRESSURE LEVEL (dBA)
SOUND POWER LEVEL (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1100mm without legs) Height
ELECTRICAL SUPPLY*
PHASE*
STARTING CURRENT (A)*
NOMINAL SYSTEM HeatingRUNNING CURRENT (A)* Cooling
GUARANTEED OPERATING RANGE (ºC) Heating / Cooling
FUSE RATING (BS88) - HRC (A)*
MAINS CABLE No. Cores*
25.0
22.4
4.12
3.96
6.06 / 5.65
5.90 / 6.02
20
50~150% OU Capacity
15.88 (5/8”)
19.05 (3/4”)
47
61
181
880
550
1160
380-415v, 50Hz
Three
8
6.3
6.1
-5~45 / -5~45
1 x 20
4 + earth
31.5
28.0
5.80
5.51
5.43 / 5.08
5.36 / 6.37
25
50~150% OU Capacity
19.05 (3/4”)
22.2 (7/8”)
49
63
181
880
550
1160
380-415v, 50Hz
Three
8
8.9
8.5
-5~45 / -5~45
1 x 20
4 + earth
37.5
33.5
8.15
7.44
4.60 / 4.50
5.11 / 5.73
30
50~150% OU Capacity
19.05 (3/4”)
22.2 (7/8”)
50
64
181
880
550
1160
380-415v, 50Hz
Three
8
12.5
11.5
-5~45 / -5~45
1 x 20
4 + earth
50.0
45.0
8.65
8.32
5.78 / 5.40
5.67 / 5.75
40
50~150% OU Capacity
22.2 (7/8”)
28.58 (1-1/8”)
50
64
181 + 181
880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8
13.3
12.8
-5~45 / -5~45
1 x 20 / 1 x 20
4 + earth
56.0
50.0
10.42
9.94
5.37 / 5.03
5.27 / 5.80
45
50~150% OU Capacity
22.2 (7/8”)
28.58 (1-1/8”)
51
65
181 + 181
880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8
16.1
15.3
-5~45 / -5~45
1 x 20 / 1 x 20
4 + earth
63.0
56.0
12.06
11.57
5.22 / 4.84
5.11 / 6.10
50
50~150% OU Capacity
22.2 (7/8”)
28.58 (1-1/8”)
52
66
181 + 181
880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8
18.6
17.8
-5~45 / -5~45
1 x 20 / 1 x 20
4 + earth
69.0
63.0
14.65
13.60
4.70 / 4.63
4.66 / 5.93
50
50~150% OU Capacity
28.58 (1-1/8”)
28.58 (1-1/8”)
52.5
66.5
181 + 181
880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8
22.6
21.0
-5~45 / -5~45
1 x 20 / 1 x 20
4 + earth
76.5
69.0
17.12
15.62
4.46 / 4.41
5.00 / 5.68
50
50~150% OU Capacity
28.58 (1-1/8”)
28.58 (1-1/8”)
53
67
181 + 181
880 + 880
550
1160
380-415v, 50Hz
Three
8 / 8
26.4
24.1
-5~45 / -5~45
1 x 20 / 1 x 20
4 + earth
PQRY-P200YHM-A PQRY-P250YHM-A PQRY-P300YHM-A PQRY-P400YSHM-A PQRY-P450YSHM-A PQRY-P500YSHM-A PQRY-P550YSHM-A PQRY-P600YSHM-A
Note: * A separate power supply is required for each module. Where more than one figure is quoted there are multiple modules. Condensing unit must be installed inside a building. **12.7(1/2”) if P250 furthest length ≥ 90m, P300 furthest length ≥ 40m.
NUMBER OF PORTS
WEIGHT (kg) (Wet)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
POWER INPUT (kW)
RUNNING CURRENT (A)
FUSE RATING (BS88) - HRC (A)
MAINS CABLE NO. CORES
BRANCH CONTROLLER81021600541300
220-240v, 50HzSingle0.472.79163
CMB-WP108V-G
Heat Recovery Outdoor Unit HVRF Series SpecificationsHeat Pump, Water Cooled Condensing Unit (WY Series) Specifications
Heat Recovery, Water Cooled Condensing Unit (WR2 Series) Specifications
Page 44 Page 45
Nominal Conditions: Cooling; indoor 27ºC DB, 19ºC WB; outdoor 35ºC DB, 24ºC WB.Nominal Conditions: Heating; indoor 20ºC DB; outdoor 7ºC DB, 6ºC WB.UK Conditions: Summer; indoor 21ºC DB, 15ºC WB; outdoor 27ºC DB.UK Conditions: Winter; indoor 21ºC DB; outdoor 0°C DB, -1ºC WB.
SEER is calculated according to the ‘Non-Domestic Building Services Compliance Guide’.
SCOP for air source models is calculated according to the following data:
Profile based on COP priority mode. 0.05 x 100% capacity at -10ºCWB outdoor; 0.10 x 75% capacity at -5ºCWB outdoor; 0.55 x 50% capacity at 5ºCWB outdoor; 0.30 x 25% capacity at 12ºCWB outdoor Indoor: 20ºCDB. Pipe Length: 7.5m. Calculation includes defrost correction.
SCOP for water source models is calculated according to the following data:
Profile (25% loading for each condition).100% capacity at 10°C inlet water; 75% capacity at 14°C inlet water50% capacity at 18°C inlet water; 25% capacity at 22°C inlet waterIndoor: 20ºCDB. Pipe Length: 7.5m. Nominal water flow rate.
Hybrid Branch Controller (HBC)
600 = Index25 Index = 1hp600 = 24hp model
PEFY-P25VMAVMA = Sub Name
P = Packaged
E = Ceiling ConcealedL = Cassette CeilingC = Ceiling SuspendedK = Wall MountedF = Floor StandingM = Cassette CeilingW = Water Unit
F = VRF Y = Inverter
P = R407c/R410A VRF WP = HVRF
PUHY-EP600YSLM
P = Packaged
U = AirQ = Water
Y = Inverter
S = Multiple Modules
P = Standard RP = ReplaceEP = High Efficiency HP = Zubadan WP = HVRF
H = Heat PumpR = Heat RecoveryM = Small Heat Pump
YLM = Version
CMB-P1013GA1
1013 = Number of ports i.e. 13
CMB = Branch Controller
G1 = BC BoxGA1/HA1 = Master BC BoxGB1/HB1 = Slave BC Box
P = R407c/R410A VRF WP = HVRF
City Multi Outdoor / Heat Source Units
City Multi Indoor Units
City Multi Branch Controller
City Multi - Model nameexplanations
Page 46
25
25 = Index25 Index = 1hp25 = 1hp model25