Citect SCADA Configuration...SCADA Point Count •Maximum number of runtime variable tags that can...

37
Citect SCADA Pricing Synergist SCADA Inc Version 1.3 - August 21, 2012 Synergist SCADA INC 1

Transcript of Citect SCADA Configuration...SCADA Point Count •Maximum number of runtime variable tags that can...

Citect SCADA Pricing Synergist SCADA Inc Version 1.3 - August 21, 2012

Synergist SCADA INC 1

#1 Rule: Always work with your local Schneider Sales Representative to properly price and license your Vijeo Citect SCADA licenses

2

USB License Keys

• Contain License CALs “Client Access Licenses”

• CALs are shared across the network to any server that require it

• Typical CALS: • Full License

• Required to run an IO / Alarm / Report / Trend server

• Includes 1 client license which can run locally on the server (Or can be used by another computer if the Computer Setup Wizard Full License box is checked)

• Client • Control Client

• View Only Client

• Web / Internet Control Client

• Web / Internet View Only Client

3

SCADA Point Count

• Maximum number of runtime variable tags that can be used by your system

• Memory or Disk variable do NOT count against your points

4

Citect’s “Dynamic” Point Count

• Citect / Vijeo Citect 7.0 and higher use a “dynamic-point licensing” model (See Knowledgebase article Q4939 )

• Citect uses the Dynamic Runtime count of all tags used

• Alarms

• Trends

• Reports

• Events

• Page Tags

• Super Genies

• TagRead() and TagWrite() Cicode functions

• DDE, OPC, ODBC, ADO or the CTAPI (Historian)

5

Variable count != Point count

• 1200 Variable Tags defined in your project may not require a 1200 point license.

• The runtime Dynamic point count in your project is often much lower than your total variable count.

6

! WARNING:

If the Runtime Dynamic Point Count is

ever greater than the license’s point

count, a license error will occur and

Citect will shutdown.

Version Licensing Changes

• V2.0 - V6.10

• V7.0, V7.10, V7.20

• V7.3+ 7

Tag Count in Citect 7.3+

•No more “Double Point” counting in multi-process mode

•Tags shared by different processes in multi-process mode will now be only counted once

8

Viewing The Dynamic Count • Using the Citect Kernel’s “General” View you can see the

current Dynamic count (you may need to resize the window)

9

Helpful Citect.ini Parameters

• [General]WatermarkedPointCount Enables displaying of “watermark messages” when the dynamic point count reaches the limit set points

• [General]PointCountHigh Percentage at which “watermark message” will be displayed

• [General]PointCountHighHigh Percentage at which a 2nd “watermark message” will be displayed

• [General]PointLimitMsg Determine weather Citect will stop the point limit from being exceeded or simply shutdown.

10

*DISABLED BY DEFAULT

Citect CAL License Types

• Full Licenses

• Control Client Licenses

• Web Control Client Licenses

• View-Only Client Licenses

• Web View-Only Client Licenses

• Speciality Drivers

• Historian

• Ampla 11

Full Licenses

• Full Licenses

• A Full license is a scalable HMI/SCADA system that can be used across all industries. It provides users and Integrators a fullyfeatured, flexible HMI/SCADA system that includes over 100 drivers.

12

How Citect Validates a License

13

CAL exists

SCADA Points

VALID LICENSE

Example License Key

• SCADA Point Count 42,000

• CALs for 1x Full Licenses, 1x Control Client, 1x View Only Client …

14

1 Full + Dongle key Per Server

• Each Physically Separated Server will Require 1 Full License

4 Servers = 4 Dongle Keys with 4 full licenses

15

4 Full

Licenses

1 Display

Client

42,000

SCADA POINT

COUNT

Required License Key

• Here is the required license key for 41,392 points, 4 Servers and 1 Control Client We will need 4 licenses with this configuration

16

Client Licenses • Clients typically retrieve their licenses from the IO Server’s

license key

17

1 Full

License

With 6 Client

CALs

42,000

SCADA POINT

COUNT

Required License Key

• Here is the required license key for 38,832 points, 1 Server and 6 Control Client We only have 1 server so we only need 1 key with 6 client CALs

18

Software Keys

• In Citect / Vijeo Citect 7.30 we now have the option of using Software keys

• Please contact your local Schneider Sales Representative for more details.

19

Pricing Citect Licensing

• Three Components to Citect Licenses:

•Support Units •License Price •USB Key Price

20

Support Units

Listed next to the license price of all software is a “Support Unit”. Multiply the support units by the associated dollar support level price.

21

Support Unit Types

• Silver • Citect Upgrades Not Provided

• Gold • Upgrades Provided

• Day time support only

• Gold Plus • Upgrades Provided

• 24 / 7 Support

22

Support Unit Part Numbers

• VJC = Vijeo Citect SCADA

• CIT = Citect SCADA

23

Support Type Price Citect / VijeoCitect Part Numbers Historian Part Numbers Facilities Part Number

Silver $ XXX109102 VJH109102 CIT109139

Gold $$ XXX109103 VJH109103 CIT109125

GoldPlus $$$ XXX109138 VJH109130 CIT109126

Support Unit Part Example

•1500 Point Full License Citect SCADA

•Gold Plus Support

24

Sample Support Unit Calculation

25

$$$

$

Solution Support Unit Calculation

26

Single Key Version Upgrade Only

• Allows the customer to do a one-time upgrade to the latest version and does not include access to the website or Technical Support Engineers.

• The upgrade only can be purchased on an individual key but must purchase upgrade for all licenses on the key.

27

Support Reinstatement

• If a site has expired more than 3 months then a reinstatement fee applies. This is because upgrades are included in the Gold or GoldPlus Support Offerings.

• In addition, the first year of Gold or GoldPlus Support must be purchased and then the new support dates will be valid a year from purchase date.

28

Citect SCADA License Example

• 1500 Point Full License Citect SCADA

29

$$$

USB Key Example

30

Citect License Total Estimate Example

• 1500 Point Full License Citect SCADA

• Gold Plus Support

• USB License Key

31

Citect License Total Calculation

32

$$$

$

Citect License Total Solution

•33

Citect License Example #2

• New Vijeo Citect Customer purchasing a 1,500 point Full

• 2 floating View-Only Clients

• 1 year of GoldPlus support

• USB License Key

34

Citect License Example #2 Solution

35

Citect Example #3 Multi-Key Order Example

• New CitectSCADA Customer purchasing an Unlimited point Full

• Redundant Full license,

• 1 Web View-Only Clients,

• 1 Redundant Web View-Only Clients

• 2 stand alone Unlimited Control Clients

• Software key packs (USB)

36

Citect Multi-Key #3 Solution

37