No.Equipment/testdata Permissiblelimits Reference
A) DewpointofSF6gas DewpointvaluesasperAnnxII
B) Dewpointofoperatingair -45Deg.CatATM.Pressure
C) CBOperatingtimings 400kV220KV
a)Closingtime(Max.) 150MS200MS
b)Triptime(Max.) 25MS35MS
c)Close/triptime,Polediscrepancy
PhasetoPhase(Max.) 3.33MS3.33MS
-Breaktobreak(Max.)ofsamephase 2.5MS2.5MS
D) PIRtime
BHELmake 12-16MS ManufacturersRecommendations
ABBmake 8-12MS ManufacturersRecommendations
NGEFmake 8-12MS ManufacturersRecommendations
M&Gmake 8-12MS ManufacturersRecommendations
TELKmake 8-12MS ManufacturersRecommendations
ABBmake(HVDC) 8-12MS ManufacturersRecommendations
E)
PIRopeningtimepriortoopeningof
maincontacts(ABB,CGL,NGEFmakeCBs) 5MS(Min.)atratedpressure ManufacturersRecommendations
F)
Pirandmaincontactsoverlaptime
[BHEL,M&G,ABB(imported)makeCBs] 6MS(Min.)atratedpressure ManufacturersRecommendations
G) Tandeltaofgradingcapacitors 0.007at20Deg.C
H) Capacitanceofgradingcapacitors Within+10%/-5%oftheratedvalue IEC359
I) ContactresistanceofCB 150M.Ohm
J) ContactresistanceofCBterminalconnector 10M.Ohmperconnector NGC,UKrecommendations
K) IRvalue:
1.Phaseearth
1000MOhm(Min.)by
5.0/10.0kVMegger
2.Acrossopencontacts
1000MOhm(Min.)by
5.0/10.0kVMegger
3.Controlcables 50MOhm(Min.)by0.5kVMegger
L) Pressureswitchsettings
-SF6gaspressureswitches Within+0.1Barofsetvalue
-Operatingairpr.Switches Within+0.1Barofsetvalue
-Operatingoilpr.Switches Within+0.1Barofsetvalue
M) BDVofoilusedforMOCB
-Atthetimeoffilling 40kVat2.5mmGap(Min.) Mfgs.Recommendation
-DuringO&M 20kVat2.5mmGap.(Min.) Mfgs.Recommendation