Submittal Trane A Division of American Standard Inc.
Prepared For: Seminole County Government
Date: February 02, 2006
Job Name: Seminole County Services Air Cooled Chillers
Trane is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 6 Air-Cooled Water Chillers Trane 1151 Keller Road Orlando, FL 32810-5924 Phone: (407)660-1111 Fax: (407)660-0303
The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval.
J:\JOBS\43\41802\2\Seminole County Services Air Cooled Chillers submittal.doc
Table Of Contents Product Summary.............................................................................. Error! Bookmark not defined. Air-Cooled Water Chillers (Large Tonnage) (Items A1 - A3)
Tag Data ...................................................................................................Error! Bookmark not defined. Product Data .............................................................................................Error! Bookmark not defined. Performance Data .....................................................................................Error! Bookmark not defined. Mechanical Specifications.........................................................................Error! Bookmark not defined. Unit Dimensions ........................................................................................Error! Bookmark not defined. Weight, Clearance & Rigging Diagram......................................................Error! Bookmark not defined. Field Wiring ...............................................................................................Error! Bookmark not defined.
Field Installed Options - Part/Order Number Summary Air-Cooled Water Chillers (Large Tonnage) ..............................................Error! Bookmark not defined.
Seminole County Services Air Cooled Chillers February 02, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 3 of 17
Tag Data - Air-Cooled Water Chillers (Qty: 6) Item Tag(s) Qty Description Model Number A1 CGAF-C25 1 25 Ton Packaged Air-Cooled Chiller CGAFC25E A2 CGAF-C50 2 50 Ton Packaged Air-Cooled Chiller CGAFC50E A3 CGAF-C60 3 60 Ton Packaged Air-Cooled Chiller CGAFC60E
Product Data - Air-Cooled Water Chillers All Units 200 Volt 60 Hertz 3 Phase 40 to 50 degree F Water Setpoint UL/ CSA Approval Unit Spring Isolators (Fld) Unit Mounted Terminal Block Trane Communications Interface Module (TCI) R-407C Notes: Disconnect switches not included.
Seminole County Services Air Cooled Chillers February 02, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 4 of 17
Performance Data - Air-Cooled Water Chillers Tags CGAF-C25 CGAF-C50 CGAF-C60 Total cooling capacity (tons) 23.32 42.77 54.65 Ent evaporator temp (F) 54.00 54.00 54.00 Lvg evaporator temp (F) 44.00 44.00 44.00 Ambient temperature (F) 95.00 95.00 95.00 Evaporator fouling factor (hr-sq ft-deg F/Btu) 0.00001 0.00001 0.00001 Evaporator flow rate (gpm) 55.79 102.32 130.75 Saturated suction temp (F) 37.23 37.69 38.24 Cooling fluid PD (ft H2O) 6.15 7.42 6.00 Compressor power (kW) 25.92 46.98 62.22 Fan power (kW) 2.70 5.40 5.40 System power (kW) 28.62 52.38 67.62 EER @ ARI (EER) 9.8 9.7 9.7 COP @ ARI (COP) 2.80 2.80 2.80 IPLV @ ARI (IPLV) 14.6 14.5 15.0 Min circuit ampacity (A) 124.00 224.00 270.00 Max fuse size (A) 175.00 250.00 300.00 Recommended dual element (A) 150.00 250.00 300.00 Circuit 1 compressor 1 LRA (A) 269.00 409.00 409.00 Circuit 1 compressor 1 RLA (A) 39.30 55.50 56.90 Circuit 1 compressor 2 LRA (A) 409.00 269.00 409.00 Circuit 1 compressor 2 RLA (A) 56.90 35.50 56.90 Circuit 2 compressor 1 LRA (A) 0.00 409.00 409.00 Circuit 2 compressor 1 RLA (A) 0.00 55.50 56.90 Circuit 2 compressor 2 LRA (A) 0.00 269.00 409.00 Circuit 2 compressor 2 RLA (A) 0.00 35.50 56.90 Fan quantity (Each) 3.00 6.00 6.00 FLA per fan (A) 4.10 4.10 4.10 Part load step 1 (%) 40.00 30.00 25.00 Ambient at step 1 (F) 59.00 55.00 55.00 Capacity at step 1 (tons) 12.22 14.57 15.93 Unit power at step 1 (kW) 8.26 10.70 11.30 EER @ ARI at step 1 (EER) 15.3 17.0 18.3 Part load step 2 (%) 60.00 60.00 50.00 Ambient at step 2 (F) 71.00 71.00 65.00 Capacity at step 2 (tons) 16.89 31.17 35.08 Unit power at step 2 (kW) 13.48 24.87 25.17 EER @ ARI at step 2 (EER) 13.8 13.5 15.2 Part load step 3 (%) - 80.00 75.00 Ambient at step 3 (F) - 83.00 80.00 Capacity at step 3 (tons) - 37.73 46.16 Unit power at step 3 (kW) - 37.42 43.41 EER @ ARI at step 3 (EER) - 11.3 11.9 Outdoor - 63 Hz (dB) 96 97 97 Outdoor - 125 Hz (dB) 91 92 92 Outdoor - 250 Hz (dB) 92 92 92 Outdoor - 500 Hz (dB) 91 93 94 Outdoor - 1 kHz (dB) 88 89 91 Outdoor - 2 kHz (dB) 87 89 89 Outdoor - 4 kHz (dB) 84 87 87 Outdoor - 8 kHz (dB) 82 85 85 A weighted sound power (dBA) 94 96 97 A weighted sound pressure (dBA) 67 69 70 Min operating weight (lb) 2085.0 3900.0 4885.0 Max operating weight (lb) 2370.0 4435.0 5820.0
Seminole County Services Air Cooled Chillers February 02, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 5 of 17
Mechanical Specifications - Air-Cooled Water Chillers (Large Tonnage) Item: A1 - A3 Qty: 6 Tag(s): CGAF-C25, CGAF-C50, CGAF-C60 General All chillers are factory run-tested to confirm proper operation. Units are checked on computer based test stand at typical ambient and water conditions and control operation is monitored. Units ship with a full operating charge of refrigerant and oil. Units are constructed of 14-gauge welded galvanized steel frame with 14 and 16-gauge galvanized steel panels and access doors. Unit surface is phosphatized and finished with an air-dry paint. This air-dry paint finish is durable enough to withstand a 1000-consecutive-hour salt spray application in accordance with standard ASTM B117. A flow switch is included as ship-with item to be field installed at the outlet of the evaporator. The flow switch is required as a safety interlock to prevent operation of unit without evaporator flow. General A strainer (with installation hardware) is included as a ship-with item to be field installed at the inlet of the evaporator. The strainer is required to prevent collection of particles within the evaporator. Strainer is field installed to facilitate ease of installation. Compressor Trane 3-D Scroll compressors have simple mechanical design with only three (3) major moving parts. Scroll type compression provides inherently low vibration. 3-D compliance provides a completely enclosed compression chamber which leads to increased efficiency. Exhaustive testing on the 3D Scroll, including start up with the shell full of liquid, has proven that slugging does not fail involutes. Direct-drive, 3600 rpm, suction gas-cooled hermetic motor. Trane 3D Scroll compressor includes centrifugal oil pump, oil level sightglass and oil charging valve. Evaporator The evaporator shall be braze plate construction with a waterside working pressure of 300 PSIG and a refrigerant side of working pressure of 225. Etched foil heaters protect the evaporator to ambient of -20 degrees F. Condenser Fans Direct-drive vertical discharge condenser fans are statically and dynamically balanced. Three phase thermal overload protected with permanently lubricated ball bearings. Controls Compressor contactors and unit controls are in a weather tight enclosure with knockouts for field installed wiring. The chiller unit utilizes a DDC microprocessor control system which is suitable for comfort and process cooling applications. The control system is factory installed in the main control panel with the necessary internal controls and run tested. Terminal blocks for field power wiring connections are standard. Units provide a location for a non-fused disconnect switch with an external handle for safety. Unit mounted microprocessor controls provide compressor anti-short cycle protection. The unit is equipped with a Human Interface Panel with a 16 key keypad, a 2 line by 40 character English display to provide the operator with full adjustment and display of control data function. The unit controls can be used as a stand-alone controller or as part of a building management system. The display can be read and adjusted without opening any unit panels. Decorative Grilles Decorative grilles provide protection from exterior damage to coil surface and other interior unit components. Grilles are factory mounted louvered, galvanized steel panels finished with an air dry paint. Grilles cover all air accessible ends of the unit. Refrigerant Circuits with 2-Stage Capacity Modulation for 20 - 30 Ton Units The unit has a single refrigeration circuit with two (2) compressors manifolded together utilizing a passive oil system. The refrigerant circuit includes an liquid line solenoid valve, filter drier, sight glass with moisture indicator, thermostatic expansion valve and service valves (liquid and discharge). Capacity modulation is accomplished by turning compressors on and off. The unit has two capacity stages. The standard leaving chilled water temperature range is 40 to 50 F [4.5 to 10 C]. Refrigerant Circuits with 4-Stage Capacity Modulation for 40 - 60 Ton Units The unit has dual refrigeration circuits. Each circuit has two (2) compressors manifolded together utilizing a passive oil system. Each refrigerant circuit includes an liquid line solenoid valve, filter drier, sightglass with moisture indicator,thermostatic expansion valve and service valves (liquid and discharge). Capacity modulation is accomplished by turning compressors on and off. The unit has four capacity stages. The standard leaving chilled
Seminole County Services Air Cooled Chillers February 02, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 6 of 17
water temperature range is 40 to 50 F [4.5 to 10 C]. Trane Communication Interface Module ( TCI ) The TCI provides interface to Trane's Integrated Comfort system ( ICS ), which allows control and monitoring of the unit by Tracer building management system. Spring Isolators Spring isolators are available for field installation under the unit frame. Condenser Coils with Aluminum Fins Air-cooled condenser coils have configured aluminum fins mechanically bonded to seamless copper tubing and integral subcooling circuits. Condenser coils are factory leak tested under water with 425 psig [2930.4 kPa] air pressure.
Seminole County Services Air Cooled Chillers February 02, 2006 Unit Dimensions - Air-Cooled Water Chillers (Large Tonnage) Item: A1 Qty: 1 Tag(s): CGAF-C25
DIA. X 4 MTG HOLES
CONNECTIONS BOTTOM
CONTROL CONN.32mm X 114mm1 1/4" X 4 1/2"
AIR FLOW
343mm
1727mm
1'-1 1/2"
5'-8"
LEFT SIDE VIEW
2'-3 1/4"
CO
MP
692mm
OPTIONAL DAMPER
PANELCONTROL
6'-1 3/8"965mm3'-2"
1864mm
NO OBSTRUCTIONS
889mm2'-11"3'-3 5/8"
1006mm
3'-1 3/8"
949mm
28mm
3" CONDUIT MAIN POWER
28mm
1 3/32" (1X) HEAT TAPE POWER
181mm
DETAIL "A"
92mm3 5/8"
83mm
149mm
5 7/8"
3 1/4"
248mm9 3/4"
2'-9"838mm
7 1/8"
76mm
19mm3/4"
1 3/32" (4X) 30V MAX.
70mm2 3/4"
LIFTING LOCATIONSDIA. HOLES (4)
FRONT VIEW
6'-6"1981mm
5 1/8"130mm
457mm1'-6"
11 1/2"
292mm
LINE VOLTAGE
SLOT
92mm3 5/8" DIA.
111mm
156mm
64mm2 1/2"
2438mm
MINIMUM CLEARANCE
MINIMUM CLEARANCE
8'-0"
1527mm5'-0 1/8"
8'-0"2438mm
TOP VIEW
1832mm
70mm2 3/4"
1
1060mm3'-5 3/4"
DOOR
180SWING
SEE DETAIL "A"
203mm
2
3
1 1/4"32mm
4
4'-9 1/2"1461mm
2242mm7'-4 " 1/4
6'- "1/88"
6 "1/8
4 "3/8
2" Grooved Pipe
Water Outlet
2" Grooved Pipe
Front ViewAccess Hole Locations
Water Inlet
1' 3"
9"
2' 6"762mm
381mm
229mm
Connection
Connection
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 7 of 17
Seminole County Services Air Cooled Chillers February 02, 2006 Unit Dimensions - Air-Cooled Water Chillers (Large Tonnage) Item: A2 Qty: 2 Tag(s): CGAF-C50
CONNECTIONS BOTTOMSEE DETAIL "A"
1 1/4" X 5 1/4" SLOT32mm X 133mm
CONTROL CONN.
AIR FLOWNO OBSTRUCTIONS
6'-6 3/8"1991mm
LEFT SIDE VIEW
CO
MP
1'-4 1/4"413mm
OPTIONAL DAMPER
CONTROLPANEL
4'-6"1371mm
1854mm6'-1"
1'-1 1/2"343mm
2'-11"889mm
3'-3 5/8"
1006mm
3'-1 3/8"
949mm
3" CONDUIT MAIN POWER76mm
28mm
7 1/8"248mm
92mm3 5/8"
DETAIL "A"
181mm
83mm
149mm
5 7/8"
3 1/4"
9 3/4"
838mm2'-9"
1 3/32" (1X) HEAT TAPE POWER
28mm
1 3/32" (4X) 30V MAX.
70mm2 3/4"
2 1/2"64mm
FRONT VIEW
92mmLINE VOLTAGE
178mm
127mm5"
356mm 7"1'-2"
133mm5 1/4"
3 5/8" DIA
8'-7 1/2"2629mm
LIFTING LOCATIONSDIA HOLES (4)
1 1/4"
7'-1 5/8"2175mm
32mm
1241mm 1241mm
3/4" DIA. X 6 MTG HOLES
SWING
70mm2 3/4"
1060mm180
19mm
1
3'-5 3/4" DOOR
2
TOP VIEW
3 5
4 6
8 1/8"206mm
4'-0 7/8"
9'-5 7/8"2892mm
4'-0 7/8"
8'-0"
MINIMUM CLEARANCE2438mm
2245mm7'-4 3/8"
8'-0"2438mm
MINIMUM CLEARANCE
Rear View
Water Inlet
3" Grooved PipeConnection
1' 1"
Water OutletConnection3" Grooved Pipe
5'
9-1/2"
2' 6"
Access Hole Locations336mm
1528mm
241mm
756mm
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 8 of 17
Seminole County Services Air Cooled Chillers February 02, 2006 Unit Dimensions - Air-Cooled Water Chillers (Large Tonnage) Item: A3 Qty: 3 Tag(s): CGAF-C60
CONTROL CONN.32mm X 114mm
1 1/4" X 5 1/4" SLOT
SEE DETAIL "A"CONNECTIONS BOTTOM
NO OBSTRUCTIONSAIR FLOW
LEFT SIDE VIEW
CO
MP
413mm1'-4 1/4"
OPTIONAL DAMPER
CONTROLPANEL 1371mm
4'-6"
1991mm
1854mm6'-1"
6'-6 3/8"
343mm1'-1 1/2"
2'-11"889mm1006mm
3'-3 5/8"
3'-1 3/8"
949mm
3" CONDUIT MAIN POWER
76mm
DETAIL "A"
92mm3 5/8"
83mm
149mm
7 1/8"181mm
5 7/8"
3 1/4"
248mm9 3/4"
2'-9"838mm
1 3/32" (1X) HEAT TAPE POWER
28mm
1 3/32" (4X) 30V MAX.
70mm2 3/4"
28mm
64mm2 1/2"LINE VOLTAGE
178mm
127mm5"
356mm1'-2"
7"
133mm
3 5/8" DIA
5 1/4"
92mm
FRONT VIEW
2629mm8'-7 1/2"
DIA HOLES (4)LIFTING LOCATIONS
32mm
2175mm7'-1 5/8"
1 1/4"
1241mm1241mm
3/4" DIA. X 6 MTG HOLES
SWING
70mm2 3/4"
1060mm180
19mm
1
3'-5 3/4" DOOR
2
TOP VIEW
3 5
4 6
206mm8 1/8" 4'-0 7/8"
9'-5 7/8"2892mm
4'-0 7/8"
8'-0"2438mm
MINIMUM CLEARANCE
2245mm7'-4 3/8"
MINIMUM CLEARANCE2438mm
8'-0"
Rear View
Water Inlet
3" Grooved PipeConnection
Water Outlet
3" Grooved PipeConnection
1' 1"
5'
9-1/2"
2' 6"
Access Hole Locations336mm
1528mm
241mm
756mm
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 9 of 17
Seminole County Services Air Cooled Chillers February 02, 2006 Weight, Clearance & Rigging Diagram - Air-Cooled Water Chillers (Large Tonnage) Item: A1 Qty: 1 Tag(s): CGAF-C25
2085.0 lb
2085.0 lb 700.0 lb 470.0 lb 490.0 lb 425.0 lb
72 1/4"8 1/16"
57 1/2"
1 1/4"
49 1/16"
29"
NOTES:
TO PREVENT INJURY OR DEATH AND POSSIBLE EQUIPMENTDAMAGE, DO NOT USE CHAIN (CABLES) OR SLINGS EXCEPTAS SHOWN AND USE CABLES STRONG ENOUGH TO SUPPORTUNIT WEIGHT. TEST LIFT UNIT TO ENSURE PROPER BALANCEAND RIGGING.
WARNING!!!
SHIPPING WEIGHT
OPERATING WEIGHT
1 2 3 4
UNIT MOUNTING POINTS
1. OPERATING WEIGHT INCLUDES REFRIGERANT, OIL AND WATER.2. SHIPPING WEIGHT INCLUDES REFRIGERANT AND OIL CHARGES.3. IF THE UNIT IS INSTALLED IN A WELL, THE DEPTH OF THE WELL MUST NOT EXCEED THE HEIGHT OF THE UNIT. THE TOP OF THE UNIT MUST HAVE UNRESTRICTED AIRFLOW.
UNIT WEIGHT
UNIT CLEARANCE
UNIT RIGGING
UNIT MOUNTING POINT
NO OBSTRUCTIONAIR FLOW
CLEARANCE 48"
1 4
2 3
CONTROL PANEL DOOR SWING 180
FRONT OF UNIT
84" TO TOP OF UNIT
96" FIELDSUPPLIED SPREADERBAR
CONTROL PANEL
2 1/2"X4 LIFTING HOLES
CLEARANCE 96"
CLEARANCE 96"
CLEARANCE 96"
CENTER OF GRAVITY AND UNIT WEIGHT
CONTROL PANEL
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 10 of 17
Seminole County Services Air Cooled Chillers February 02, 2006 Weight, Clearance & Rigging Diagram - Air-Cooled Water Chillers (Large Tonnage) Item: A2 Qty: 2 Tag(s): CGAF-C50
3900.0 lb
3900.0 lb 685.0 lb 715.0 lb 720.0 lb 750.0 lb 505.0 lb 525.0 lb
8 3/16"
48 7/8" 48 7/8"
85 5/8"
1 5/16"
58"
46"
NOTES:
TO PREVENT INJURY OR DEATH AND POSSIBLE EQUIPMENTDAMAGE, DO NOT USE CHAIN (CABLES) OR SLINGS EXCEPTAS SHOWN AND USE CABLES STRONG ENOUGH TO SUPPORTUNIT WEIGHT. TEST LIFT UNIT TO ENSURE PROPER BALANCEAND RIGGING.
WARNING!!!
SHIPPING WEIGHT
OPERATING WEIGHT
1 2 3 4
UNIT MOUNTING POINTS
1. OPERATING WEIGHT INCLUDES REFRIGERANT, OIL AND WATER.2. SHIPPING WEIGHT INCLUDES REFRIGERANT AND OIL CHARGES.3. IF THE UNIT IS INSTALLED IN A WELL, THE DEPTH OF THE WELL MUST NOT EXCEED THE HEIGHT OF THE UNIT. THE TOP OF THE UNIT MUST HAVE UNRESTRICTED AIRFLOW.
UNIT WEIGHT
UNIT CLEARANCE
UNIT RIGGING
CENTER OF GRAVITY AND UNIT WEIGHT
NO OBSTRUCTIONAIR FLOW
CLEARANCE 48"
1 5
2 6
CONTROL PANEL DOOR SWING 180
FRONT OF UNIT
84" TO TOP OF UNIT
96" FIELD SUPPLIED SPREADER BAR
5 6
4
3
CONTROL PANEL 2 1/2"X4 LIFTING HOLES
CLEARANCE 96"
CLEARANCE 96"CLEARANCE 96"
UNIT MOUNTING POINTSCONTROL PANEL
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 11 of 17
Seminole County Services Air Cooled Chillers February 02, 2006 Weight, Clearance & Rigging Diagram - Air-Cooled Water Chillers (Large Tonnage) Item: A3 Qty: 3 Tag(s): CGAF-C60
4865 in3
4885.0 lb 885.0 lb 820.0 lb 855.0 lb 985.0 lb 985.0 lb 720.0 lb
8 3/16"
48 7/8" 48 7/8"
85 5/8"
1 5/16"
58"
47"
NOTES:
TO PREVENT INJURY OR DEATH AND POSSIBLE EQUIPMENTDAMAGE, DO NOT USE CHAIN (CABLES) OR SLINGS EXCEPTAS SHOWN AND USE CABLES STRONG ENOUGH TO SUPPORTUNIT WEIGHT. TEST LIFT UNIT TO ENSURE PROPER BALANCEAND RIGGING.
WARNING!!!
SHIPPING WEIGHT
OPERATING WEIGHT
1 2 3 4
UNIT MOUNTING POINTS
1. OPERATING WEIGHT INCLUDES REFRIGERANT, OIL AND WATER.2. SHIPPING WEIGHT INCLUDES REFRIGERANT AND OIL CHARGES.3. IF THE UNIT IS INSTALLED IN A WELL, THE DEPTH OF THE WELL MUST NOT EXCEED THE HEIGHT OF THE UNIT. THE TOP OF THE UNIT MUST HAVE UNRESTRICTED AIRFLOW.
UNIT WEIGHT
UNIT CLEARANCE
UNIT RIGGING
CENTER OF GRAVITY AND UNIT WEIGHT
NO OBSTRUCTIONAIR FLOW
CLEARANCE 96"
1 5
2 6
CONTROL PANEL DOOR SWING 180
FRONT OF UNIT
84" TO TOP OF UNIT
96" FIELD SUPPLIED SPREADER BAR
5 6
4
3
CONTROL PANEL 2 1/2"X4 LIFTING HOLES
CLEARANCE 96"
CLEARANCE 96"CLEARANCE 96"
UNIT MOUNTING POINTSCONTROL PANEL
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 12 of 17
Seminole County Services Air Cooled Chillers February 02, 2006 Field Wiring - Air-Cooled Water Chillers (Large Tonnage) Item: A1 - A3 Qty: 6 Tag(s): CGAF-C25, CGAF-C50, CGAF-C60
2. Phantom lines indicate alternate circuitry or available sales options.
447
448
449
450
495
500
501
502
503
533
534
537
12
NC
450
NO
498
499
448449
445
446
538
IMPORTANT!DO NOT ENERGIZE
UNIT UNTIL CHECK-OUTAND START-UP PROCEDURE
HAS BEEN COMPLETED
DEVICE PREFIX LOCATION CODE
AREA LOCATION
1
2
3
4
5
6
CONTROL PANEL
FAN SECTION
COMPRESSOR SECTION
EXTERNAL FACTORY MTD DEVICE
CUSTOMER OR FIELD PROVIDED
SHIP W/FIELD INSTALLED DEVICE
COM
ALARMOUTPUT
NC
447
NO
445446
COM
ICEMAKINGOUTPUT
1TB5
1
2
3
4
13
14
15
5
6
7
8
9
16
17
18
19
20
10
11
21
22
496
497
CAUTIONUSE COPPER CONDUCTORS ONLY!UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT OTHER TYPES OFCONDUCTORS.FAILURE TO DO SO MAY CAUSEDAMAGE TO THE EQUIPMENT.
HAZARDOUS VOLTAGE!DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTSBEFORE SERVICING.
AVERTISSEMENTWARNINGVOLTAGE HASARDEUX!
FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSE SEVEREPERSONAL INJURY OR DEATH.
DECONNECTEZ TOUTES LES SOURCESELECTRIQUES INCLUANT LESDISJONCTEURS SITUES A DISTANCEAVANT D'EFFECTUER L'ENTRETIEN.FAUTE DE DECONNECTER LA SOURCEELECTRIQUE AVANT D'EFFECTUERL'ENTRETIEN PEUT ENTRAINER DESBLESSURES CORPORELLES SEVERESOU LA MORT.
447
448
449
450
495
500
501
502
503
533
534
537
12
NC
450
NO
498
499
448449
445
446
538
IMPORTANT!DO NOT ENERGIZE
UNIT UNTIL CHECK-OUTAND START-UP PROCEDURE
HAS BEEN COMPLETED
DEVICE PREFIX LOCATION CODE
AREA LOCATION
1
2
3
4
5
6
CONTROL PANEL
FAN SECTION
COMPRESSOR SECTION
EXTERNAL FACTORY MTD DEVICE
CUSTOMER OR FIELD PROVIDED
SHIP W/FIELD INSTALLED DEVICE
COM
ALARMOUTPUT
NC
447
NO
445446
COM
ICEMAKINGOUTPUT
1TB5
1
2
3
4
13
14
15
5
6
7
8
9
16
17
18
19
20
10
11
21
22
496
497
CAUTIONUSE COPPER CONDUCTORS ONLY!UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT OTHER TYPES OFCONDUCTORS.FAILURE TO DO SO MAY CAUSEDAMAGE TO THE EQUIPMENT.
HAZARDOUS VOLTAGE!DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTSBEFORE SERVICING.
AVERTISSEMENTWARNINGVOLTAGE HASARDEUX!
FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSE SEVEREPERSONAL INJURY OR DEATH.
DECONNECTEZ TOUTES LES SOURCESELECTRIQUES INCLUANT LESDISJONCTEURS SITUES A DISTANCEAVANT D'EFFECTUER L'ENTRETIEN.FAUTE DE DECONNECTER LA SOURCEELECTRIQUE AVANT D'EFFECTUERL'ENTRETIEN PEUT ENTRAINER DESBLESSURES CORPORELLES SEVERESOU LA MORT.
Connect to 24VACclass 2 circuits only.
Connect to 24VACclass 2 circuits only.
Notes:
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 13 of 17
Seminole County Services Air Cooled Chillers February 02, 2006 Field Wiring - Air-Cooled Water Chillers (Large Tonnage) Item: A1 - A3 Qty: 6 Tag(s): CGAF-C25, CGAF-C50, CGAF-C60
2. Phantom lines indicate alternate circuitry or available sales options.
422
414
424
425411
ICSCONTROLLED 414
415
416
5RT19ICS DEFINED
TEMP
424
5S67EXTERNALAUTO/STOP
SWITCH
434
425
438
437
IMPORTANT!DO NOT ENERGIZE
UNIT UNTIL CHECK-OUTAND START-UP PROCEDURE
HAS BEEN COMPLETED
DEVICE PREFIX LOCATION CODE
AREA LOCATION
1
2
3
4
5
6
CONTROL PANEL
FAN SECTION
COMPRESSOR SECTION
EXTERNAL FACTORY MTD DEVICE
CUSTOMER OR FIELD PROVIDED
SHIP W/FIELD INSTALLED DEVICE
NOCOM
NC
5S71EMERGENCY
STOPSWITCH
435431
5K86ICE
BUILDINGINITIATE
4101
2
3
4
12
13
14
15
5
6
7
8
9
16
17
18
19
20
10
11
21
22
1TB4
416
417
418
421
415
436
403
438
435
431
434
438437
24 VOLT CLASS 2CIRCUIT ONLY)
(CONNECT TO
Remove jumper between 1tb4-16 & 17when required, Contacts rated 12mA @24VDC minimum.
Remove jumper between 1tb4-18 & 19 when required,Contacts rated 12mA @ 24VDC minimum.
Contacts rated12mA @ 24VDC
minimum.
Use BAYSENS016, BAYSENS017 or equivalent.
BLESSURES CORPORELLES SEVERESL'ENTRETIEN PEUT ENTRAINER DESELECTRIQUE AVANT D'EFFECTUERFAUTE DE DECONNECTER LA SOURCEAVANT D'EFFECTUER L'ENTRETIEN.DISJONCTEURS SITUES A DISTANCEELECTRIQUES INCLUANT LESDECONNECTEZ TOUTES LES SOURCESVOLTAGE HASARDEUX!
AVERTISSEMENT
PERSONAL INJURY OR DEATH.BEFORE SERVICING CAN CAUSE SEVEREFAILURE TO DISCONNECT POWER
WARNING
INCLUDING REMOTE DISCONNECTSDISCONNECT ALL ELECTRIC POWER
BEFORE SERVICING.
HAZARDOUS VOLTAGE!
OU LA MORT.
DAMAGE TO THE EQUIPMENT.FAILURE TO DO SO MAY CAUSE
TO ACCEPT OTHER TYPES OFUNIT TERMINALS ARE NOT DESIGNEDUSE COPPER CONDUCTORS ONLY!
CAUTION
CONDUCTORS.
Notes:
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 14 of 17
Seminole County Services Air Cooled Chillers February 02, 2006 Field Wiring - Air-Cooled Water Chillers (Large Tonnage) Item: A1 - A3 Qty: 6 Tag(s): CGAF-C25, CGAF-C50, CGAF-C60
2. Phantom lines indicate alternate circuitry or available sales options.
UNITS WITH MAIN POWERTERMINAL BLOCK (ALL VOLTAGES)
BLOCK SIZE335 AMP 1
WIRE QTY.(1) #6 - 350 MCM
CONNECTOR WIRE RANGE
NOTES
5B1
IMPORTANT!DO NOT ENERGIZE
UNIT UNTIL CHECK-OUTAND START-UP PROCEDURE
HAS BEEN COMPLETED
L1 L2 L3
SEE UNITNAMEPLATE FORLINE VOLTAGE
5K1
5K1-OL5T1 5K1
39
EQUIPMENTGROUND
DEVICE PREFIX LOCATION CODE
AREA LOCATION
1
2
3
4
5
6
CONTROL PANEL
FAN SECTION
COMPRESSOR SECTION
EXTERNAL FACTORY MTD DEVICE
CUSTOMER OR FIELD PROVIDED
SHIP W/FIELD INSTALLED DEVICE
1
2
3
4
5
6
7
8
9
10
11
12
38
39
1TB6
38
CAUTIONUSE COPPER CONDUCTORS ONLY!UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT OTHER TYPES OFCONDUCTORS.FAILURE TO DO SO MAY CAUSEDAMAGE TO THE EQUIPMENT.
HAZARDOUS VOLTAGE!DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTSBEFORE SERVICING.
AVERTISSEMENTWARNINGVOLTAGE HASARDEUX!
FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSE SEVEREPERSONAL INJURY OR DEATH.
DECONNECTEZ TOUTES LES SOURCESELECTRIQUES INCLUANT LESDISJONCTEURS SITUES A DISTANCEAVANT D'EFFECTUER L'ENTRETIEN.FAUTE DE DECONNECTER LA SOURCEELECTRIQUE AVANT D'EFFECTUERL'ENTRETIEN PEUT ENTRAINER DESBLESSURES CORPORELLES SEVERESOU LA MORT.
NOTESA. BLOCK SIZE & DISCONNECT SIZE ARE CALCULATED BY SELECTING THE SIZE GREATER THAN OR EQUAL TO 1.15 X (SUM OF UNIT LOADS). SEE UNIT LITERATURE FOR UNIT LOAD VALUES.
5B1
CUSTOMER CONNECTION WIRE RANGE IMPORTANT!DO NOT ENERGIZE
UNIT UNTIL CHECK-OUTAND START-UP PROCEDURE
HAS BEEN COMPLETED
5S1
L1 L2 L3
SEE UNITNAMEPLATE FORLINE VOLTAGE
5K1
5K1-OL5T1 5K1
39
EQUIPMENTGROUND
DEVICE PREFIX LOCATION CODE
AREA LOCATION
1
2
3
4
5
6
CONTROL PANEL
FAN SECTION
COMPRESSOR SECTION
EXTERNAL FACTORY MTD DEVICE
CUSTOMER OR FIELD PROVIDED
SHIP W/FIELD INSTALLED DEVICE
1
2
3
4
5
6
7
8
9
10
11
12
38
39
1TB6
38
CAUTIONUSE COPPER CONDUCTORS ONLY!UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT OTHER TYPES OFCONDUCTORS.FAILURE TO DO SO MAY CAUSEDAMAGE TO THE EQUIPMENT.
HAZARDOUS VOLTAGE!DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTSBEFORE SERVICING.
AVERTISSEMENTWARNINGVOLTAGE HASARDEUX!
FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSE SEVEREPERSONAL INJURY OR DEATH.
DECONNECTEZ TOUTES LES SOURCESELECTRIQUES INCLUANT LESDISJONCTEURS SITUES A DISTANCEAVANT D'EFFECTUER L'ENTRETIEN.FAUTE DE DECONNECTER LA SOURCEELECTRIQUE AVANT D'EFFECTUERL'ENTRETIEN PEUT ENTRAINER DESBLESSURES CORPORELLES SEVERESOU LA MORT.
1TB1
5B1 CHILLER PUMP MOTOR
CHILLED SOL PUMP STARTER
ICE BUILDING INITIATE
5RT19
5S1
5K86
5K89
5K1
DEVICE DESIGNATION
DEMAND LIMIT RELAY
ICE DEFINED TEMP. SENSOR
FUSED DISCONNECT
EMERGENCY STOP5S71
5T1 CONTROL TRANSFORMER
5S67 EXTERNAL AUTO STOP SWITCH
HEAT TAPETO 4HR1HEAT TAPETO 4HR1
4HR1 - HEAT TAPE POWER WIRING4HR1 - HEAT TAPE POWER WIRING
200200 L1L1
201201 L2L2 H
N
H
N
115VAC/60HZ15A MAX15A MAX
1TB121TB12
Notes:
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 15 of 17
Seminole County Services Air Cooled Chillers February 02, 2006 Field Wiring - Air-Cooled Water Chillers (Large Tonnage) Item: A1 - A3 Qty: 6 Tag(s): CGAF-C25, CGAF-C50, CGAF-C60
2. Phantom lines indicate alternate circuitry or available sales options.
447
448
449
450
495
500
501
502
503
533
534
537
12
NC
450
NO
498
499
448449
445
446
538
IMPORTANT!DO NOT ENERGIZE
UNIT UNTIL CHECK-OUTAND START-UP PROCEDURE
HAS BEEN COMPLETED
DEVICE PREFIX LOCATION CODE
AREA LOCATION
1
2
3
4
5
6
CONTROL PANEL
FAN SECTION
COMPRESSOR SECTION
EXTERNAL FACTORY MTD DEVICE
CUSTOMER OR FIELD PROVIDED
SHIP W/FIELD INSTALLED DEVICE
COM
ALARMOUTPUT
NC
447
NO
445446
COM
ICEMAKINGOUTPUT
1TB5
1
2
3
4
13
14
15
5
6
7
8
9
16
17
18
19
20
10
11
21
22
496
497
CAUTIONUSE COPPER CONDUCTORS ONLY!UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT OTHER TYPES OFCONDUCTORS.FAILURE TO DO SO MAY CAUSEDAMAGE TO THE EQUIPMENT.
HAZARDOUS VOLTAGE!DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTSBEFORE SERVICING.
AVERTISSEMENTWARNINGVOLTAGE HASARDEUX!
FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSE SEVEREPERSONAL INJURY OR DEATH.
DECONNECTEZ TOUTES LES SOURCESELECTRIQUES INCLUANT LESDISJONCTEURS SITUES A DISTANCEAVANT D'EFFECTUER L'ENTRETIEN.FAUTE DE DECONNECTER LA SOURCEELECTRIQUE AVANT D'EFFECTUERL'ENTRETIEN PEUT ENTRAINER DESBLESSURES CORPORELLES SEVERESOU LA MORT.
447
448
449
450
495
500
501
502
503
533
534
537
12
NC
450
NO
498
499
448449
445
446
538
IMPORTANT!DO NOT ENERGIZE
UNIT UNTIL CHECK-OUTAND START-UP PROCEDURE
HAS BEEN COMPLETED
DEVICE PREFIX LOCATION CODE
AREA LOCATION
1
2
3
4
5
6
CONTROL PANEL
FAN SECTION
COMPRESSOR SECTION
EXTERNAL FACTORY MTD DEVICE
CUSTOMER OR FIELD PROVIDED
SHIP W/FIELD INSTALLED DEVICE
COM
ALARMOUTPUT
NC
447
NO
445446
COM
ICEMAKINGOUTPUT
1TB5
1
2
3
4
13
14
15
5
6
7
8
9
16
17
18
19
20
10
11
21
22
496
497
CAUTIONUSE COPPER CONDUCTORS ONLY!UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT OTHER TYPES OFCONDUCTORS.FAILURE TO DO SO MAY CAUSEDAMAGE TO THE EQUIPMENT.
HAZARDOUS VOLTAGE!DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTSBEFORE SERVICING.
AVERTISSEMENTWARNINGVOLTAGE HASARDEUX!
FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSE SEVEREPERSONAL INJURY OR DEATH.
DECONNECTEZ TOUTES LES SOURCESELECTRIQUES INCLUANT LESDISJONCTEURS SITUES A DISTANCEAVANT D'EFFECTUER L'ENTRETIEN.FAUTE DE DECONNECTER LA SOURCEELECTRIQUE AVANT D'EFFECTUERL'ENTRETIEN PEUT ENTRAINER DESBLESSURES CORPORELLES SEVERESOU LA MORT.
Wires are shieldedtwisted pair.
Connect to 24VACclass 2 circuits only.
Connect to 24VACclass 2 circuits only.
COMMCOMM(1U54)(1U54)
TRACER
(-)
TRACER
(-) (+)(+)
534534 533533
Notes:
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 16 of 17
Seminole County Services Air Cooled Chillers February 02, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 17 of 17
Field Installed Options - Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job.
Product Family - Air-Cooled Water Chillers (Large Tonnage) Item Tag(s) Qty Description Model Number A1 CGAF-C25 1 25 Ton Packaged Air-Cooled Chiller CGAFC25E A2 CGAF-C50 2 50 Ton Packaged Air-Cooled Chiller CGAFC50E A3 CGAF-C60 3 60 Ton Packaged Air-Cooled Chiller CGAFC60E
Field Installed Option Description Part/Ordering Number Unit Spring Isolators