Chigo Inverters Manual
Transcript of Chigo Inverters Manual
-
7/22/2019 Chigo Inverters Manual
1/52
DC Inverter Split Air-Condition Unit
SERVICE MANUAL
-
7/22/2019 Chigo Inverters Manual
2/52
- 1 -
Table of Contents
1. The model and the air conditioning unit parameters...........................................................1
2. Units operating working conditions and temperature range ............................................8
3. Units characteristic..................................................................................................................11
4. Indoor and outdoor units size ...............................................................................................26
5. Indoor and outdoor unit explosion diagram and spare parts list .....................................30
6. The analysis of indoor malfunction code ............................................................................35
7. The analysis of the complete units malfunction code.........................................................50
-
7/22/2019 Chigo Inverters Manual
3/52
- 2 -
1The model and the air conditioning unit parameters1.1 the model.
-
7/22/2019 Chigo Inverters Manual
4/52
- 3 -
1.2. The air conditioners parameter.
-
7/22/2019 Chigo Inverters Manual
5/52
- 4 -
-
7/22/2019 Chigo Inverters Manual
6/52
- 5 -
-
7/22/2019 Chigo Inverters Manual
7/52
- 6 -
-
7/22/2019 Chigo Inverters Manual
8/52
- 7 -
-
7/22/2019 Chigo Inverters Manual
9/52
- 8 -
-
7/22/2019 Chigo Inverters Manual
10/52
- 9 -
-
7/22/2019 Chigo Inverters Manual
11/52
- 10 -
2 RATING CONDITIONS and Operating Limits
2.1 RATING CONDITIONS
Standard conditions in accordance with ISO 5151, and EN 14511.
Cooling:
Indoor: 27 DB 19 WB
Outdoor:35DB 24 WB
Heating:
Indoor: 20 DB 15 WB
Outdoor: 7 DB 6 WB
2.2 Operat ing Limits
Outdoor
Upper limit (DB) 46Cooling
Lower limit (DB) 5
Upper limit (DB) 24Heating
Lower limit (DB) -15
Voltage 1PH 220-240V
-
7/22/2019 Chigo Inverters Manual
12/52
- 11 -
3 Units characteristic R410a
Low noise level
Wide operating range with outdoor air temperatures, cooling:5-46,heating:-15-24
High efficiency and energy saving Air filters easy to remove and clean
Twin rotary compressor
Auto-restart after a power supply blackout
Single-phase power supply thanks to DC inverter technology low consumption
Dynamic refrigerant control by DC inverter compressor and circuit, electronic valve and fuzzy logic
managed by a powerful micro program
EEV for each indoor unit
-
7/22/2019 Chigo Inverters Manual
13/52
- 12 -
-
7/22/2019 Chigo Inverters Manual
14/52
- 13 -
The compressors energy consumption graph .
COP (W/W)/2ND
The compressors condensing pressure graph .
-
7/22/2019 Chigo Inverters Manual
15/52
- 14 -
Indoor Units Data
Indoor Units Capacity For 2.0KW
Capacity Model
2.0KW CMV-V20G3A-M75/81/84/85/87/88/95/96
Cooling Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [0C]
OUTDOOR
ENTERING AIR DB
TEMPERATURE
[0C] DATA 22/15 24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal
SC 80 - 105 % of nominal
-10 - 20
(protection range) PI 25 - 50 % of nominal
TC 1.94 2.06 2.18 2.32 2.44
SC 1.72 1.75 1.79 1.82 1.8525
PI 0.49 0.50 0.51 0.51 0.53
TC 1.84 1.96 2.10 2.22 2.34
SC 1.67 1.70 1.75 1.79 1.8230
PI 0.55 0.55 0.56 0.57 0.58
TC 1.74 1.88 2.00 2.12 2.26
SC 1.63 1.67 1.70 1.73 1.7735
PI 0.60 0.61 0.62 0.63 0.64
TC 1.66 1.78 1.90 2.04 2.16
SC 1.58 1.62 1.65 1.70 1.7340PI 0.66 0.67 0.68 0.69 0.69
TC 1.54 1.66 1.80 1.92 2.04
SC 1.53 1.56 1.60 1.63 1.6846
PI 0.73 0.74 0.74 0.76 0.76
Heating Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
ID COIL ENTERING AIR DB TEMPERATURE [0C]
OD COIL
ENTERING
AIR DB/WB
TEM PERATU RE
[0C]
DATA 15 20 25
-15/-16 TC 1.54 1.42 1.32
PI 0.40 0.44 0.48
-10/-12 TC 1.70 1.58 1.49
PI 0.48 0.52 0.57
-7/-8 TC 1.82 1.73 1.61
PI 0.55 0.59 0.63
-1/-2 TC 1.90 1.80 1.68
PI 0.58 0.62 0.66
2/1 TC 1.94 1.82 1.73
-
7/22/2019 Chigo Inverters Manual
16/52
- 15 -
PI 0.60 0.64 0.68
7/6 TC 2.50 2.40 2.30
PI 0.63 0.67 0.71
10/9 TC 2.64 2.54 2.42
PI 0.67 0.71 0.75
15/12 TC 2.78 2.69 2.57
PI 0.70 0.74 0.78
1524 TC 85 - 105 % of nominal(Protection Range) PI 80 - 120 % of nominal
Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
Cooling Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
25 30 35 40 45
Outdoor Temperature (deg C)
Capacity
Ratio
32/23
29/27
27/19
24/17
22/15
Heating Capacity Ratio Vs. Outdoor Temperature
Heating Capacity Correction Factor
0
0.2
0.4
0.6
0.8
11.2
1.4
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (deg C)
Capacity
Ratio
15
20
25
-
7/22/2019 Chigo Inverters Manual
17/52
- 16 -
Indoor Units Capacity For 2.5KW
Capacity Model
2.5KW CMV-V25G3A-M75/81/84/85/87/88/95/96
Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [0C]
OUTDOOR
ENTERING AIR DB
TEMPERATURE
[0C] DATA 22/15 24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal
-10 - 20 SC 80 - 105 % of nominal
(protection range) PI 25 - 50 % of nominal
TC 2.42 2.57 2.73 2.89 3.05
25 SC 1.72 1.75 1.79 1.82 1.86
PI 0.58 0.59 0.60 0.61 0.62TC 2.30 2.46 2.62 2.77 2.93
30 SC 1.67 1.71 1.74 1.78 1.81
PI 0.65 0.66 0.67 0.68 0.69
TC 2.18 2.34 2.50 2.66 2.82
35 SC 1.63 1.66 1.70 1.74 1.77
PI 0.71 0.72 0.74 0.75 0.76
TC 2.07 2.23 2.38 2.54 2.70
40 SC 1.59 1.62 1.66 1.69 1.73
PI 0.78 0.79 0.80 0.81 0.82
TC 1.93 2.09 2.24 2.40 2.56
46 SC 1.53 1.57 1.60 1.64 1.67
PI 0.86 0.87 0.88 0.89 0.91
Heating Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
ID COIL ENTERING AIR DB TEMPERATURE [0C]
OD COIL
ENTERING
AIR DB/WB
TEM PERATU RE
[0C]
DATA 15 20 25
-15/-16 TC 1.92 1.77 1.65
PI 0.49 0.54 0.59
-10/-12 TC 2.13 1.98 1.86
PI 0.59 0.64 0.70
-7/-8 TC 2.28 2.16 2.01
PI 0.67 0.72 0.77
-1/-2 TC 2.37 2.25 2.10
PI 0.71 0.75 0.80
2/1 TC 2.43 2.28 2.16
PI 0.73 0.78 0.83
-
7/22/2019 Chigo Inverters Manual
18/52
- 17 -
7/6 TC 3.12 3.00 2.88
PI 0.77 0.82 0.87
10/9 TC 3.30 3.18 3.03
PI 0.82 0.87 0.92
15/12TC
3.48 3.36 3.21PI 0.86 0.90 0.96
15-24 TC 85 - 105 % of nominal
(Protection Range) PI 80 - 120 % of nominal
L E G E N D
TC Total Cooling Capacity, kW
SC Sensible Capacity, Kw
PI Power Input, kW
WB Wet Bulb Temp., (
o
C)DB Dry Bulb Temp., (oC)
ID Indoor
OD Outdoor
Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
Cooling Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
25 30 35 40 45Outdoor Temperature (deg C)
Capacity
Ratio
32/23
29/27
27/19
24/17
22/15
-
7/22/2019 Chigo Inverters Manual
19/52
- 18 -
Heating Capacity Ratio Vs. Outdoor Temperature
Heating Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (deg C)
Capacity
Ratio
15
20
25
Indoor Units Capacity For 3.5KW
Indoor Units Capacity For 3.5KW
Capacity Model
CMV-V35G3A-M75/81/84/85/87/88/95/963.5KW
CMV-V35G3A-P84/94/98
Cooling Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [0C]
OUTDOOR
ENTERING AIR DB
TEMPERATURE
[0C] DATA 22/15 24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal
-10 - 20 SC 80 - 105 % of nominal
(protection range) PI 25 - 50 % of nominal
TC 3.40 3.61 3.82 4.06 4.2725 SC 3.03 3.09 3.15 3.21 3.27
PI 0.86 0.87 0.89 0.90 0.93TC 3.22 3.43 3.68 3.89 4.10
30 SC 2.94 3.00 3.09 3.15 3.21PI 0.96 0.97 0.99 1.00 1.02
TC 3.05 3.29 3.50 3.71 3.96
35 SC 2.88 2.94 3.00 3.06 3.12
PI 1.06 1.08 1.09 1.11 1.12
TC 2.91 3.12 3.33 3.57 3.78
40 SC 2.79 2.85 2.91 3.00 3.06
PI 1.16 1.18 1.19 1.21 1.22
TC 2.70 2.91 3.15 3.36 3.5746 SC 2.70 2.76 2.82 2.88 2.97
PI 1.28 1.30 1.31 1.33 1.34
-
7/22/2019 Chigo Inverters Manual
20/52
- 19 -
Heating Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
ID COIL ENTERING AIR DB TEMPERATURE [0C]
OD COIL
ENTERING
AIR DB/WB
TEM PERATU RE
[0C]
DATA 15 20 25
-15/-16 TC 2.56 2.36 2.20
PI 0.67 0.73 0.80
-10/-12 TC 2.84 2.64 2.48
PI 0.80 0.87 0.94
-7/-8 TC 3.04 2.88 2.68
PI 0.91 0.98 1.04
-1/-2 TC 3.16 3.00 2.80
PI 0.95 1.02 1.09
2/1 TC 3.24 3.04 2.88
PI 0.99 1.05 1.12
7/6 TC 4.16 4.00 3.84
PI 1.04 1.11 1.18
10/9 TC 4.40 4.24 4.04
PI 1.11 1.18 1.24
15/12 TC 4.64 4.48 4.28
PI 1.17 1.23 1.301524 TC 85 - 105 % of nominal
(Protection Range) PI 80 - 120 % of nominal
Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
Cooling Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.21.4
25 30 35 40 45
Outdoor Temperature (deg C)
Capacity
Ratio
32/23
29/27
27/19
24/17
22/15
-
7/22/2019 Chigo Inverters Manual
21/52
- 20 -
Heating Capacity Ratio Vs. Outdoor Temperature
Heating Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
-15 -10 -5 0 5 10 15 20Outdoor Temperature (deg C)
Capacity
Ratio
15
20
25
Indoor Units Capacity For 5.0KW
Capacity Model
5.0KW CMV-V50G3A-P75/81/84/85/87/88/95/96
Cooling Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [0C]
OUTDOOR
ENTERING AIR DB
TEMPERATURE
[0C] DATA 22/15 24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal
-10 - 20 SC 80 - 105 % of nominal
(protection range) PI 25 - 50 % of nominal
TC 4.85 5.15 5.45 5.80 6.1025 SC 4.55 4.64 4.73 4.82 4.91
PI 1.23 1.25 1.28 1.29 1.33TC 4.60 4.90 5.25 5.55 5.85
30 SC 4.41 4.50 4.64 4.73 4.82PI 1.37 1.39 1.42 1.44 1.47
TC 4.35 4.70 5.00 5.30 5.65
35 SC 4.32 4.41 4.50 4.59 4.68
PI 1.51 1.54 1.56 1.59 1.61
TC 4.15 4.45 4.75 5.10 5.40
40 SC 4.19 4.28 4.37 4.50 4.59
PI 1.65 1.68 1.70 1.73 1.75TC 3.85 4.15 4.50 4.80 5.10
46 SC 4.05 4.14 4.23 4.32 4.46PI 1.83 1.86 1.87 1.90 1.92
-
7/22/2019 Chigo Inverters Manual
22/52
- 21 -
Heating Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed
ID COIL ENTERING AIR DB TEMPERATURE [0C]
OD COIL
ENTERING
AIR DB/WB
TEM PERATU RE
[0C]
DATA 15 20 25
-15/-16 TC 3.71 3.42 3.19
PI 0.97 1.06 1.16
-10/-12 TC 4.12 3.83 3.60
PI 1.16 1.26 1.37
-7/-8 TC 4.41 4.18 3.89
PI 1.32 1.42 1.51-1/-2 TC 4.58 4.35 4.06
PI 1.38 1.48 1.58
2/1 TC 4.70 4.41 4.18
PI 1.43 1.53 1.63
7/6 TC 6.03 5.80 5.57
PI 1.51 1.61 1.71
10/9 TC 6.38 6.15 5.86
PI 1.61 1.71 1.80
15/12 TC 6.73 6.50 6.21
PI 1.69 1.79 1.88
15-24 TC 85 - 105 % of nominal
(Protection Range) PI 80 - 120 % of nominal
-
7/22/2019 Chigo Inverters Manual
23/52
- 22 -
Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
Cooling Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
25 30 35 40 45
Outdoor Temperature (deg C)
Capacity
Ratio
32/23
29/27
27/19
24/17
22/15
Heating Capacity Ratio Vs. Outdoor Temperature
Heating Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (deg C)
Capacity
Rat
io
15
20
25
-
7/22/2019 Chigo Inverters Manual
24/52
- 23 -
Capacity Correction Factor Due to Tubing Length (One Way)
Cooling
Heating
-
7/22/2019 Chigo Inverters Manual
25/52
- 24 -
Pressure Curve
Model
CMV-V40H13AD CMV-50V3A-E2 CMV-V71T3AT CMV-V80T3AQ
Cooling--------------Test Model
Heating-----------Test Model
-
7/22/2019 Chigo Inverters Manual
26/52
- 25 -
ELECT RICAL D ATA
Model CMV-V40H13AD
Power Supply 220-240V 1PH 50Hz
Connected to OutdoorMaximum Current 8 A
Inrush Current 15A
Starting Current 1A
Circuit breaker 20A
Power supply wiring - No. x cross section 31.5 mm26680mm
Interconnecting cable - No. x cross section 41.0 mm26300mm
Model CMV-50V3A-E2
Power Supply 220-240V 1PH 50Hz
Connected to Outdoor
Maximum Current 11 A
Inrush Current 35A
Starting Current 1A
Circuit breaker 20A
Power supply wiring - No. x cross section 32.5 mm26480mm
Interconnecting cable - No. x cross section 41.0 mm26300mm
Model CMV-V52E23AT
Power Supply 220-240V 1PH 50Hz
Connected to Outdoor
Maximum Current 11A
Inrush Current 35A
Starting Current 1A
Circuit breaker 20A
Power supply wiring - No. x cross section 32.5 mm26480mm
Interconnecting cable - No. x cross section41.0 mm26300mm
Model CMV- V71T3AT
Power Supply 220-240V 1PH 50Hz
Connected to Outdoor
Maximum Current 16A
Inrush Current 35A
Starting Current 2A
Circuit breaker 20A
Power supply wiring - No. x cross section 32.5 mm2
6480mmInterconnecting cable - No. x cross section 41.0 mm
26200mm
-
7/22/2019 Chigo Inverters Manual
27/52
- 26 -
Model CMV-V80T3AQ
Power Supply 220-240V 1PH 50Hz
Connected to Outdoor
Maximum Current 16A
Inrush Current 35A
Starting Current 2A
Circuit breaker 20A
Power supply wiring - No. x cross section 32.5 mm26480mm
Interconnecting cable - No. x cross section 41.0 mm216100mm
Note:
Inrush current is the current when power is up. (charging the DC capacitors at outdoor unit
controller).
Starting current is the current when starting the compressor
-
7/22/2019 Chigo Inverters Manual
28/52
- 27 -
4. OUTLINE DIMENSI ON OF OUTDOOR AND INDOOR
4.1 Outline dimension of outdoor Units
CMV-V40H13AD
CMV-50V3A-E2/ CMV-V52E23AT
-
7/22/2019 Chigo Inverters Manual
29/52
- 28 -
CMV- V71T3AT/ CMV-V80T3AQ
4 2 the outdoor unit mounting dimensions
-
7/22/2019 Chigo Inverters Manual
30/52
- 29 -
the bodys dimension mounting dimensionsDimensions
Code
outdoor
units typeA B C D E
CMV-V40H13AD 845 304 542 510 278
CMV-50V3A-E2 900 352 590 505 310
CMV-V52E23AT 900 352 590 505 310
CMV-V71T3AT/
CMV-V80T3AQ900 388 837 600 358
4 3 The indoor unit mounting dimensions
unitmm
-
7/22/2019 Chigo Inverters Manual
31/52
- 30 -
the bodys dimension mounting dimensionsDimensions
Code
indoor
units type
A B C D E F
CMV-V20G3A/MXX 800 280 195 490 / /
CMV-V25G3A/MXX 800 280 195 490 / /
CMV-V35G3A/MXX 800 280 195 490 / /
CMV-V35G3A/PXX 900 296 220 583 257.5 257.5
CMV-V50G3A/PXX 900 296 220 583 257.5 257.5
-
7/22/2019 Chigo Inverters Manual
32/52
31
5 The outdoor unit structure exploded view .5.1 outdoor unit :CMV-V40H13AD
NO. description name number
1 Front Grill 1
2 Front Plate 1
3 Axial flow fan 1
4 Motor 1
5 Motor support 16 Condenser 1
7 Top panel 1
8 Electric box 1
9 Rear Grill 1
10 Right panel 1
11 handle 1
12 Valve installation plate 1
13 A DN4 DN4 valve 1
14 A DN8 DN8 valve 1
15 B DN4 DN4 valve 1
16 B DN8 DN8 valve 1
17 Capillary Assy 1
18 Electronic expansion valve 2
19 Four-way valve assembly 1
20 Steam liquid segregator 1
21 Compressor 1
22 Partition board 1
23 Base 1
-
7/22/2019 Chigo Inverters Manual
33/52
32
5.2 outdoor un it : CMV-50V3A-E2/ CMV-V52E23AT
-
7/22/2019 Chigo Inverters Manual
34/52
33
NO. description name number
1 front grill 1
2 front panel 1
3 fan 14 motor 1
5 motor bracket assemble 1
6 left grill 1
7 left pole 1
8 top cover 1
9 rear grill 1
10 condenser 1
11 4-way valve 1
12 muffle 113 filter 1
14 controllor 1
15 control box cover 1
16 electrical control box 1
17 A DN8 DN8 valve for A unit 1
18 A DN4 DN4 valve for A unit 1
19 B DN8 DN8 valve for B unit 1
20 B DN4 DN4 valve for B unit 1
21 valve installation plate 122 handle 1
23 right panel 1
24 expand valve 2
25 compressor 1
26 compressor pad 1
27 partition board 1
28 base assemble 1
-
7/22/2019 Chigo Inverters Manual
35/52
34
5.3outdoor unit : CMV-V71T3AT/ CMV-V80T3AQ
-
7/22/2019 Chigo Inverters Manual
36/52
35
NO. description name number
1 top panel 1
2 electric box 1
3 rear Grill 1
4 partition board 15 four-way valve 1
6 electronic expansion valve 1
7 desiccation filter 1
8 right panel 1
9 large handle 1
10 valve installation plate 1
11 oil separator 1
12 high-pressure tank 1
13 compressor 114 base 1
15 condenser 1
16 motor support 1
17 DC motor 1
18 axial flow fan 1
19 front Grill 1
20 front Plate 1
21 left protect net 1
22 left panel 123 vapor-liquid separator 1
24 back panel 2
25 DN10 DN10 cut-off valve 1
26 DN8 DN8 cut-off valve 1
27 electronic control box support plate 1
28 small hand-pumped 1
29 front maintenance board 1
-
7/22/2019 Chigo Inverters Manual
37/52
36
6The analysis of indoor malfunction code internal wiring get loose, whichwill cause malfunction.
indoor detailed malfunction1.when indoor unit live wire is disconnected its lamp panel cant display.
Live wire is off
2.when the transformers secondary and primary disconnect or indoor fuse is off the indoor unit lamppanel cant display.
Transformer secondary is off
Transformer primary is off
The relevant transfomer primarysocket
-
7/22/2019 Chigo Inverters Manual
38/52
37
Indoor unit fuse is off.
The indoor unit fuse
The condition that the lamp panel
cant display
3.1when the indoor null line is off the system displays F1 code 2when indoor communication wire is off the system also displays F1 code
The inserted slice to null line
The indoor unit null line is off
-
7/22/2019 Chigo Inverters Manual
39/52
38
2the indoor communication wire isoff.
Communication wire socket.
the indoor lamp panel displays F1 code.
4. when indoor fan mainline or feedback wire is offthe indoor lamp panel displays F4 code. After directlyinsert it wellTo restart the unit to recover normal .
Indoor fan mainline is off
The relevant socket with indoor fan mainline
-
7/22/2019 Chigo Inverters Manual
40/52
39
indoor fan feedback wire is off
the relevant socket with indoor feedback
wire
The lamp panel displays F4 code.
5.when indoor sensor has the problem, the lamp will display F2 F3 code. When indoor coil outlet , inletand middle temperature sensor appear malfunction, the lamp panel displays F3 code; when indoor
temperature sensor appears fault, the lamp panel shows F2 fault code.
Indoor temperature sensor plug
the relevant socket of indoor temperature
sensor plug
-
7/22/2019 Chigo Inverters Manual
41/52
40
The lamp panel alternately displays F2,F3fault code.
6.when outdoor temperature sensor is off or loose contact the indoor lamp panel displays F6 faultcode.
the relevant socket of outdoor temp.
sensor.
The outdoor temperature sensor isoff or loose contact.
-
7/22/2019 Chigo Inverters Manual
42/52
41
The indoor lamp panel displays F6fault code.
7.when the system appears mode conflict the indoor lamp panel shows d1 code.
the indoor lamp panel showsd1code.
8.when the system is in the defrosting conditionThe lamp panel displays dF code.
The lamp panel displays dF code.
-
7/22/2019 Chigo Inverters Manual
43/52
42
The outdoor electrical control fault code of the America 12K model .1.the outdoor module temperature sensor is off or loose contact the lamp panel shows F6 code.
the outdoor module temperature sensor
is off or loose contact .
the relevant socket with the outdoormodule temperature sensor plug .
The lamp panel shows F6 code .
2.The outdoor unit DC busbar voltage is abnormal the lamp panel shows F7code.
The PN power wire are off .
-
7/22/2019 Chigo Inverters Manual
44/52
43
The lamp panel shows F7code.
3.the outdoor module drive wire is off the lamp panel shows FC code .
The outdoor module drive wire is off .
The matching socket with the outdoormodule drive wire
The matching socket with the outdoormodule drive wire .
The outdoor module drive wire isoff .
-
7/22/2019 Chigo Inverters Manual
45/52
44
The lamp panel shows FC code .
4the wave filtering board and mainboard power wire is off or loose contactthe lamp panel shoes F1 code .the wave filtering board and mainboard powerwire is off or loose contact
The matching socket with the wavefiltering board and mainboard power wire
the lamp panel shoes F1 code .
-
7/22/2019 Chigo Inverters Manual
46/52
45
5. the evaporator middle temperature and condenser middle temperature sensor is off the lamp paneldisplays P8 code .
the evaporator middle temperature andcondenser middle temperature sensor is off
the lamp panel displays P8 code
-
7/22/2019 Chigo Inverters Manual
47/52
46
The 67th
style indoor lamp panel
The timing lamp The turbo lamp The running lamp
The indoor unit faulty display:
Faulty contents Trouble display
Communication faultThe running lamp lightens all the timethe turbo lamp
lightens 2 times and then extinguish 2 seconds
Indoor fan faultThe running lamp lightens all the timethe turbo lamp
lightens 5 timesand then extinguish 2 seconds
Indoor temp. sensor faultThe running lamp lightens all the timethe turbo lamp
lightens 3 times and then extinguish 2 seconds
Indoor coil outlet temp. sensor faultThe running lamp lightens all the timethe turbo lamp
lightens 4 timesand then extinguish 2 seconds
Indoor coil inlet temp. sensor fault The running lamp lightens all the timethe turbo lamplightens 4 times and then extinguish 2 seconds
Indoor coil middle temp. sensor faultThe running lamp lightens all the timethe turbo lamp
lightens 4 times and then extinguish 2 seconds
Mode conflictThe running lamp lightens 1 time and then extinguish
1 second
Defrosting or anti cold airThe timing lamp lightens 1 time and then extinguish
1 second
The outdoor unit faulty display:
Faulty contents Trouble display
the outdoor unit transducer module
protection faulty
The timing lamp lightens all the timethe turbo lamp
lightens 2 times and then extinguish 2 seconds
over current of outdoor unit The timing lamp lightens all the timethe turbo lamplightens 3 times and then extinguish 2 seconds
discharge temp. of compressor too high,
outside ambient temp. too high, switch
temp. of compressor crust cut off, temp.
of module too high
The timing lamp lightens all the timethe turbo lamp
lightens 4 times and then extinguish 2 seconds
The outdoor unit DC busbar voltage is
abnormal
The timing lamp lightens all the timethe turbo lamp
lightens 7 times and then extinguish 2 seconds
lack refrigerant or reverse valve faultThe timing lamp lightens all the timethe turbo lamp
lightens 8 times and then extinguish 2 seconds
outdoor sensor faultThe running lamp lightens all the timethe turbo lamp
lightens 7 times and then extinguish 2 seconds
outdoor unit drive fault, start compressor
failure
The running lamp lightens all the timethe turbo lamp
lightens 6 times and then extinguish 2 seconds
-
7/22/2019 Chigo Inverters Manual
48/52
47
The 85th
style indoor lamp panel
The timing lamp The sleeping lamp The running lamp
Faulty contents Trouble display
Communication faultThe timing lamp lightens all the timethe sleeping lamp
lightens 2 times and then extinguish 2 seconds
Indoor fan faultThe timing lamp lightens all the timethe sleeping lamp
lightens 5 times and then extinguish 2 seconds
Indoor temp. sensor faultThe timing lamp lightens all the timethe sleeping lamp
lightens 3 times and then extinguish 2 seconds
Indoor coil outlet temp. sensor faultThe timing lamp lightens all the timethe sleeping lamp
lightens 4 times and then extinguish 2 seconds
Indoor coil inlet temp. sensor faultThe timing lamp lightens all the timethe sleeping lamp
lightens 4 times and then extinguish 2 seconds
Indoor coil middle temp. sensor faultThe timing lamp lightens all the timethe sleeping lamp
lightens 4 times and then extinguish 2 seconds
Mode conflictThe timing lamp lightens 1 time and then extinguish
1 second
Defrosting or anti cold airThe running lamp lightens 1 time and then extinguish
1 second
Faulty contents Trouble display
the outdoor unit transducer module
protection faulty
The running lamp lightens all the timethe sleeping lamp
lightens 2 times and then extinguish 2 seconds
over current of outdoor unitThe running lamp lightens all the timethe sleeping lamp
lightens 3 times and then extinguish 2 seconds
discharge temp. of compressor too high,
outside ambient temp. too high, switch
temp. of compressor crust cut off, temp.
of module too high
The running lamp lightens all the timethe sleeping lamp
lightens 4 times and then extinguish 2 seconds
The outdoor unit DC busbar voltage is
abnormal
The running lamp lightens all the timethe sleeping lamp
lightens 7 times and then extinguish 2 seconds
lack refrigerant or reverse valve faultThe running lamp lightens all the timethe sleeping lamp
lightens 8 times and then extinguish 2 seconds
outdoor sensor faultThe timing lamp lightens all the timethe sleeping lamp
lightens 7 times and then extinguish 2 seconds
outdoor unit drive fault, start compressor
failure
The timing lamp lightens all the timethe sleeping lamp
lightens 6 times and then extinguish 2 seconds
-
7/22/2019 Chigo Inverters Manual
49/52
48
6.3 The malfunction of indoor and outdoor unit
1The common malfunction code analysis and solutions!The faultcode
The fault content The reason of fault and its solutions
F1 The communication fault
1The communication wire is broken off. Please checkwhether the wire is disentwined;2Please check whether the electrical control board isdamaged. It should be replaced when it is damaged;
3Please check whether the power ground wire is reliable;
4Please check whether the unit is abnormal caused by theexternal interference. If it is, then find the interferingsources, and remove them.
F2The indoor temperature
sensor fault
1Check whether the resistance of sensor is normal,otherwise replace it;
2Check whether the sensor wire is short circuit or opencircuit, and whether the plug is well contacted, whetherthere is welding off or rosin joint on the electric controlboard, repair it if there is any above;
3When the 1 and 2 are both normal, then the componentor integrated circuit is damaged, the electric control board
should be replaced.
F3The indoor coil
temperature sensor fault
1Check whether the resistance of sensor is normal,
otherwise replace it;
2Check whether the sensor wire is short circuit or opencircuit, and whether the plug is well contacted, whetherthere is welding off or rosin joint on the electric controlboard ,repair it if there is any above;
3When the 1 and 2 are both normal, then the componentor integrated circuit is damaged, the electric control board
should be replaced.
F4
Indoor PG motor fault(tap motor hasnt so
breakdown )
1Check whether the contact of the plug of the motor wire
and socket is well. Please make sure it is well contacted;
2Check whether the indoor motor has damaged, the
motor should be replaced when it is damaged;
3Check whether the controllable silicon and other
components on the electric control board have damaged
replace the controllable silicon or electric control boardwhen they are damaged;
4Check whether the indoor fan is unobstructed whenrunning, please fix the indoor fan again when it isobstructed.
F5 IPM protection
1Check whether the supply voltage is out of ranging from150 to 270V(overvoltage and undervoltage protection);Measuring the actual current, if the current is greater thanthe rated current of 2A,it is over-temperature protection;If the above are normal, that is IPM module internal circuit
fault protection, so please replace the IPM module.
F6 The outdoor sensor fault
1Check whether the resistance of sensor is normal,otherwise replace it;
2Check whether the sensor wire is short circuit or opencircuit, and whether the plug is well contacted, whetherthere is welding off or rosin joint on the electric control
board, repair it if there is any above;
3When the 1 and 2 are both normal ,then the componentor integrated circuit is damaged, the electric control boardshould be replaced.
-
7/22/2019 Chigo Inverters Manual
50/52
49
F7
The outdoor coiltemperature sensor fault
Including the
mid-point of tube
inspiratory gas
1Check whether the resistance of sensor is normal,otherwise replace it;
2Check whether the sensor wire is short circuit or opencircuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric controlboard, repair it if there is any above;
3When the 1 and 2 are both normal, then the componentor integrated circuit is damaged, the electric control boardshould be replaced.
F9 Exhaust gas sensor failure
1Check whether the resistance of sensor is normal,otherwise replace it;
2Check whether the sensor wire is short circuit or open
circuit, and whether the plug is well contacted, whetherthere is welding off or rosin joint on the electric controlboard, repair it if there is any above;
3When the 1 and 2 are both normal, then the componentor integrated circuit is damaged, the electric control boardshould be replaced.
FAThe communication faultbetween the wire
controller and the indoorPCB
1 check whether the wire controllers connecting wire isshort circuit or loose, please make it connect well;
2 Check the connecting linewire controllerPCBwhether they are loose or have a bad contact. Please
make them have a good contact.
FCoutdoor unit driving fault,
starting compressor
failure
1Turn on the power again, and then check whether theoperation of the compressor is normal;
2Check whether the connection of the compressor iscorrect or reliable, otherwise repair it;
3Check whether the components on the electric control
board have been damaged, if they are damaged, thecomponents or the electric control board should be
replaced.;4Check whether the connecting wires are disentwinedbetween the Intelligent Power Module board and the main
board, otherwise make the wires connect firmly .
FF
The outdoor DC motorfault
1Check the resistance value of the DC motor port. If it isshort circuit, please change the DC motor;
2Check the voltage value of the DC motor port
VCC(15Vdc)Vdm(340Vdc),please change the PCB board
if the voltage values are abnormal;
3if all the voltage values of the DC motor port are
normalthe Vsp voltage0~5vis also ok ,it shows that the
inner PCB board of the DC motor is damaged, then changethe DC motor.
FH
The indoor unit
EEPROM error
1Check whether there are false weld and bad contact etcbetween the EEPROM chip block and the electroniccontrol board ;
2Check whether the EEPROM chip pin is broken foot
and the direction of installation is in line with the
EEPROM block;
3When the procedure of EEPROM chip and itself havefault it will appear the code FH. That is the need to replacethe EEPROM chip.
dF Defrosting state The unit is in defrosting statethat is normal.
dI Mode conflictWhen the running mode for No.1 indoor unit is differentfrom No.2 indoor unit, the dF is displayed.
-
7/22/2019 Chigo Inverters Manual
51/52
50
The faultcode
The fault content The reason of fault and solution
P1
Indoor coil
temperature
over-temperature
protection for heating
(thermal overload),
outdoor coil
temperature
overheating protection
for cooling (cooling
overload)
1Check whether the ambient temperature is over the rangeof air-conditioning running temperature ;
2Check whether the indoor coil temperature is higher thanor equal to 63 degrees when heating and check whetherthe outdoor coil temperature is higher than or equal to 65
degrees when cooling, it will appear protection if thevalue is over the above;
3Check whether the parameters of indoor and outdoor coiltemperature sensors are normal, if abnormal, pleasereplace the sensors;
4If the above are normal, check whether the main controlboard output parameters are normal, if abnormal, pleasereplace the main control board.
P2
The outdoor unit
inverter module
protection fault
1Check whether the connection of the compressor is reliable,
otherwise connect firmly again;
2Check whether the fixation between the IPM module and
the radiator is firm.;3Check whether the compressor is well, otherwise replace it;
4Check whether the IPM module is abnormal, otherwisereplace it.
P3Over current of
outdoor unit
1Check whether the ambient temperature exceeds theoperation range for the air conditioner;
2Check whether the current detection circuit is abnormal, theelectric control should be replaced when it is abnormal..
P4
discharge temperature of
compressor is too high, theoutside ambienttemperature
over-temperature, switchoff the compressor shelltemperature, moduletemperatureover-temperature
1Check whether the pressure is normal when the unit isrunning, if it is abnormal, you should detect the leakage andthen welding and adding refrigerant;
2Check whether the ambient temperature is too high or too
low, when the temperature is more than -20 degrees and less55 degrees, it can disappear automatically;
3Check whether temperature switch of compressor isdamage, it should be replaced if it is damaged.
P7
The outdoor unit DC
generatrix voltage is
abnormal
1Check whether the supply voltage is out of ranging from150 to 270V;
2Check the voltage detection circuit of the IPM base board isabnormal, if it is abnormal, the IPM base board or the electriccontrol board should be replaced.
P8lack refrigerant or reverse
valve fault
1Check whether the high and low pressure valves have beenopened, otherwise open the valves;
2Check whether the indoor coil pipe temperature sensor is
normal, if it is abnormal, the sensor should be replaced;3Check whether the indoor coil temperature sensor hung in
the airplease plug it in a correct position if the indoor coiltemperature sensor hung in the air;
4Check the system pressure is abnormal, if it is abnormal,yon should detect leakage and the welding and adding therefrigerant.;
5Please change the outdoor PCB board , if all above arenormal.
PA
protection when indoor
pipe temperature is toolow (Anti-icing)
1Check whether the ambient temperature is over the rangeof air-conditioning running temperature;
2Check the indoor coil temperature is less than or equal to-1 degrees, if more than this value it will be the protectionof;
3Check whether the indoor coil temperature sensor
-
7/22/2019 Chigo Inverters Manual
52/52
parameters are normal, if abnormal it is the replacementof the sensor;
4If the above are normal, check whether the main controlboard output parameters are normal, if abnormal ,pleasereplace the main control board.
PC
Outdoor ambienttemperature
over-temperatureprotection (including highand low)
1Check whether the outdoor ambient temperature is toohigh or too low, when the ambient temperature is lower
than (T> -20, T