Chemical clean agent fire suppression systems
Transcript of Chemical clean agent fire suppression systems
Chemical clean agent fire suppression system
Technical data sheets
Unit 36-38
APD Industrial park
Elsecar street, Kya Sand
South Africa
Tel: +27 (0)11 708 0160
www.redg.co.za
HFC 227 ea
FK-5-1-12
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 2
Section I - Table of contents
Section Description Page No
I Table of contents 2
II HFC 227 agent specification and physical properties 3
III FK-5-1-12 agent specification and physical properties 4
IV
Chemical gas cylinders – 16L
Chemical gas cylinders – 28L
Chemical gas cylinders – 51L
Chemical gas cylinders – 81L
Chemical gas cylinders – 142L
5
6
7
8
9
V Chemical gas cylinder valves DN 33 and DN 50 10
VI Pressure monitoring devices 11
VII Actuators for gas cylinder valves 12
VIII 33mm High pressure flexible discharge hoses 50mm High pressure flexible discharge hoses
13
IX Nozzles – 360 degree 14
X Nozzles – 180 degrees 15
XI Cylinder mounting straps 16
XII Cylinder pipe clamps 17
XIII Warning signage 18
XIV General arrangement 19
XV Hydraulic design calculation – HFC 227ea 20-21
XVI Hydraulic design calculation – FK-5-1-12 22-23
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 3
Section II - HFC 227 Agent specification and physical properties
DESCRIPTION 1. Characteristics and uses – HFC 227 ea (P/N REDHFC227) General Extinguishant HFC 227ea shall comply with the specification according to Table 1. HFC 227ea is a colourless, almost odourless, electrically non-conductive gas with a density approximately six times that of air. The physical properties are given in Table 2.
HFC 227ea extinguishes fires mainly by physical means, but also by some chemical means.
Table 1 — Specification for HFC 227ea
Property Requirement
Purity 99,6% by mass, min.
Acidity 3 x 10 -6 by mass, max.
Water content 10 x 10 -6 by mass, max.
Non-volatile residue 0,01 % by mass, max.
Suspended matter or sediment None visible
Table 2 — Physical properties of HFC 227ea
Property Unit Value
Molecular mass - 170
Boiling point at 1,013 bar (absolute) a oC -16,4
Freezing point oC -127
Critical temperature oC 101,7
Critical pressure bar abs a 29,26
Critical volume cm3/mol 274
Critical density kg/m3 573
Vapour pressure bar abs a 3,90
Liquid density kg/m3 1 410
Saturated vapour density kg/m3 31,035
Specific volume of superheated vapour m3/kg 0,1374
Chemical formula CF3CHFCF3
Chemical name Heptafluoropropane a 1 bar = 0,1 Mpa = 10 5 Pa; 1 Mpa – 1 N/mm2
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 4
Section III - FK-5-1-12 Agent specification and physical properties
DESCRIPTION 2. Characteristics and uses – FK-5-1-12 (P/N FG-FK5112) General Extinguishant FK-5-1-12 shall comply with the specification according to Table 3. FK-5-1-12 is a clear, colourless, almost odourless, electrically non-conductive gas with a density approximately 11 times that of air. The physical properties are given in Table 4. FK-5-1-12 extinguishes fires mainly by physical means, but also by some chemical means
Table 3 — Specification for FK-5-1-12
Property Requirement
Purity 99,9% by mass, min.
Acidity 3 x 10 -6 by mass, max.
Water content 0.001 by mass, max.
Non-volatile residue 0,03 % by mass, max.
Suspended matter or sediment None visible
Table 4 — Physical properties of HFC 227ea
Property Unit Value
Molecular mass - 316,04
Boiling point at 1,013 bar (absolute) a oC 49,2
Freezing point oC -108
Critical temperature oC 168.66
Critical pressure bar abs a 18.646
Critical volume cm3/mol 494,5
Critical density kg/m3 639.1
Vapour pressure bar abs a 0,3260
Liquid density kg/m3 1,616
Saturated vapour density kg/m3 4,3305
Specific volume of superheated vapour m3/kg 0,0719
Chemical formula CF3 CF2C(O)CF(CF3)2
Chemical name Dodecafluoro-2-methylpentan-3-one a 1 bar = 0,1 Mpa = 10 5 Pa; 1 Mpa – 1 N/mm2
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 5
Section IV - Chemical gas cylinders
P/N FG-CYL16 16 L Refillable Welded Steel Gas Cylinder – Fill range 8.0kg to 18.0kg
Outside diameter 254mm dia 1 Shell Min. 4mm 2 Top Domed End Min. 4mm 3 Bottom Domed End Min. 4mm 4 Valve thread 2.5” – 12UN-2B 5 Foot ring Min. 3mm Regulation 2010/35 TPED + ADR Pneumatic test pressure Min. 6 Bar Design and manufacturing code EN13322-1 Design pressure Max. 46 Bar Test pressure 69 Bar Design Temperature -20 / + 65 deg Celsius
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 6
Section IV - Chemical gas system cylinders
P/N FG-CYL28 28 L Refillable Welded Steel Gas Cylinder – Fill range 14.0kg to 31.5kg
Outside diameter 254mm dia 1 Shell Min. 4mm 2 Top Domed End Min. 4mm 3 Bottom Domed End Min. 4mm 4 Valve thread 2.5” – 12UN-2B 5 Foot ring Min. 3mm Regulation 2010/35 TPED + ADR Pneumatic test pressure Min. 6 Bar Design and manufacturing code EN13322-1 Design pressure Max. 46 Bar Test pressure 69 Bar Design Temperature -20 / + 65 deg Celsius
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 7
Section IV - Chemical gas system cylinders
P/N FG-CYL51 51 L Refillable Welded Steel Gas Cylinder – Fill range 24.5kg to 56.5kg
Outside diameter 254mm dia 1 Shell Min. 4mm 2 Top Domed End Min. 4mm 3 Bottom Domed End Min. 4mm 4 Valve thread 2.5” – 12UN-2B 5 Foot ring Min. 3mm Regulation 2010/35 TPED + ADR Pneumatic test pressure Min. 6 Bar Design and manufacturing code EN13322-1 Design pressure Max. 46 Bar Test pressure 69 Bar Design Temperature -20 / + 65 deg Celsius
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 8
Section IV - Chemical gas system cylinders
P/N FG-CYL81 81 L Refillable Welded Steel Gas Cylinder – Fill range 39.0kg to 90.5kg
Outside diameter 315mm dia (+_2) 1 Shell Min. 4mm 2 Top Domed End Min. 4mm 3 Bottom Domed End Min. 4mm 4 Valve thread 3” – 12UN-2B 5 Foot ring Min. 3mm Regulation 2010/35 TPED + ADR Pneumatic test pressure Min. 6 Bar Design and manufacturing code EN13322-1 Design pressure Max. 46 Bar Test pressure 69 Bar Design Temperature -20 / + 65 deg Celsius
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 9
Section IV - Chemical gas system cylinders
P/N FG-CYL142 142 L Refillable Welded Steel Gas Cylinder – Fill range 68.0kg to 158.5kg
Outside diameter 405mm dia 1 Shell Min. 4mm 2 Top Domed End Min. 4mm 3 Bottom Domed End Min. 4mm 4 Valve thread 3” – 12UN-2B 5 Foot ring Min. 3mm Regulation 2010/35 TPED + ADR Pneumatic test pressure Min. 6 Bar Design and manufacturing code EN13322-1 Design pressure Max. 46 Bar Test pressure 69 Bar Design Temperature -20 / + 65 deg Celsius
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 10
Section V - Chemical gas system valves
Cylinder Valves DN33 P/N FGF2050003
• Seat diameter – 33mm
Article no. Inlet thread Outlet thread Burst discs Gauge port? Dip tube connection
F2050003 2,5”-12UN-2A 1 7/8”-12UN-3A 60bar* yes 1,5”-16UN
VDS, UL, FM APPROVED
Cylinder Valves DN50 P/N FGF2060004
• Seat diameter – 50mm
Article no. Inlet thread Outlet thread Burst discs Gauge port? Dip tube connection
F2060004 3”-12UN-2A 2,5” -12UNJ 60bar* yes 2,125”-16UN
VDS, UL, FM APPROVED
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 11
Section VI - Pressure monitoring devices
Monitoring Devices
Special patented thread connection which enables to assemble and disassemble the gauges even under pressure
without causing any leakages.
Pressure Gauge with Switching Contact (Type F053)
Part no. Pressure range Switching point Switching type*
FGF0530015 0-60bar 22,5bar Normally open (NO)
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 12
Section VII - Chemical gas system actuators
P/N COF1120004 – Electrical Actuator
for P/N F2050003 and F2060004 valves
– VDS, UL, FM APPROVED
Technical Data:
power supply 24VDC +/- 4VDC
power consumption 12W
current 0,5A
P/N COF0150007 – Reset tool for Electrical Actuator COF1120004
- VDS, UL, FM APPROVED
P/N COF1120011 - VDS, UL, FM APPROVED
Pneumatic Actuator P/N F2050003 and F2060004 valves
pilot pressure: pmin. = 20 bar at max. cylinder pressure 360 bar
Connections: 2 x G1/8"
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 13
Section VIII - High pressure discharge hoses
Discharge Hose DN33 (P/N KDFM056)
Discharge Hose – 2 1/2" 12UN (female, turnable) to G 2" (male)
Part-no. Length “L”
KDFM056 510mm
Adaptor - Included
• For orientation of tubes with 90°-ellbow
Discharge Hose DN50 (P/N KDFM057
• Pwmax – 70bar
• Nominal wide – 50mm
Discharge Hose – 2 1/2" 12UN (female, turnable) to G 2" (male)
Part-no. Length “L”
KDFM057 600mm
Adaptor - included
• For orientation of tubes with 90°-ellbow
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 14
Section IX - Discharge Nozzles – 360 degrees
360 deg NOZZLES: The required orifice diameter has to be determined by our specialized design software
and drilled out to the calculated orifice size.
VDS, UL, FM APPROVED
article
application nozzle bores external sizes orifice
Chemical gas
bore
diameter thread 360°
nozzle
cross
section height
wrench
size
orifice
diameter
working pressure b t d h w a
bar mm mm mm² mm mm mm
F0036015 90 Ø15 G 1/2” 8 x Ø5,4 183,2 36 30 3 – 12
F00360020 90 Ø20 G 3/4” 16 x Ø5 314,2 46 38 4 – 16
F00360025 90 Ø25 G 1” 16 x Ø6,3 498,8 55 45 6 – 20
F00360032 90 Ø32 G 1
1/4” 16 x Ø8 804,2 64 50 8 – 25
F00360040 n.a. Ø40 G 1
1/2” 24 x Ø8,2 1267,4 77 60 10 – 32
F00360050 n.a. Ø50 G 2” 24 x
Ø10,2 1961,1 94 80 12 – 40
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 15
Section X - Discharge Nozzles – 180 degrees
180 deg NOZZLES. The required orifice diameter has to be determined by our specialized design software and
drilled out to the calculated orifice size.
VDS, UL, FM APPROVED
article
application nozzle bores external sizes orifice
Chemical gas
bore
diameter thread 360°
nozzle
cross
section height
wrench
size
orifice
diameter
working pressure b t d h w a
bar mm mm mm² mm mm mm
F00180015 90 Ø15 G 1/2” 5 x Ø6,7 176,3 36 30 3 – 12
F00180020 90 Ø20 G 3/4” 9 x Ø5 317,3 46 38 4 – 16
F00180025 90 Ø25 G 1” 9 x Ø8,4 498,8 55 45 6 – 20
F00180032 90 Ø32 G 1
1/4” 9 x Ø10,7 809,3 64 50 8 – 25
F00180040 n.a. Ø40 G 1
1/2” 14 x Ø10,7 1258,9 77 60 10 – 32
F00180050 n.a. Ø50 G 2” 14 x Ø13,4 1974,4 94 80 12 – 40
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 16
** the required orifice diameter has to be calculated by a suitable flow calculation software or method!!!
Section XI - Cylinder mounting straps
CYLINDER STRAPS Cylinder straps are used to secure the cylinder in place. Two per single cylinder system or a single row in a multiple cylinder system. The straps must be connected into unistrut which is secured to any structurally solid surface. Anchoring into plaster or any other facing material is not acceptable. DESCRIPTION Cylinder Straps are made of Stainless Steel. All mounting hardware is supplied by the system installer. M10 mild steel bolt and nut included for assembly.
Part Number Cylinder size Cylinder O/D
FG-CLMP01 16L and 28L 254mm dia.
FG-CLMP02 51L and 81L 315mm dia.
FG-CLMP03 142L 405mm dia.
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 17
Section XII - Cylinder pipe clamps
2 PIECE PIPE CLAMPS
Supplied as a one-piece including fastener
Body and screw - galvanised steel (EG)
Design load of 200kg (safety factor of 5)
Suitable for distribution pipework
Part Number
Overall Diameter
Bolt size mm
Material Thickness (mm)
RED001 (1/2”) M6 x M 20 1.6
RED002 (3/4”) M6 x M 20 1.6
RED003 (1”) M6 x M 20 1.6
RED004 (1 ¼”) M6 x M 20 1.6
RED005 (1 ½”) M8 x M20 2
RED006 (2”) M8 x M20 2
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 18
Section XIII - Warning signage
Safety signs shall be installed at all entrances to chemical gas system protected areas and manual operation points
P/N REDFM09 (HFC 227ea)
P/N REDFK09 (FK 5 1 12)
Manual release chemical gas system caution signage
To be installed at any chemical gas system manual release
point
Door caution signage
To be installed at the entrance to every Chemical Gas protected area.
CAUTION!
This area is protectedby a gaseous fireextinguishing system
When alarm soundor upon gas dischargeevacuate hazard area immediately.
After discharge do re-emter untilthoroughly ventilated
NOT
CAUTION!
This area is protectedby a gaseous fireextinguishing system
When alarm soundor upon gas dischargeevacuate hazard area immediately.
After discharge do re-emter untilthoroughly ventilated
NOT
P/N REDFM08 (HFC 227) P/N REDFM08A (FK-5-1-12)
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 19
Section XIV - General arrangement for chemical gas systems
A - Discharge hose
B - Electric actuator
C – Valve
D - Pressure monitoring device
E - Cylinder
Pipe Sealant:
Only PTFE tape or SWAK may be used as pipe sealants for the piping and fittings
Piping:
Black Seamless, ASTM A-Grade B
Pipe Fittings:
3000lb steel
All open- ended piping shall be pneumatically tested in a closed circuit for a period of 10 min at 3 bar. At the end of 10 min, the pressure drop shall not exceed 20 % of the test pressure
A
B
C
E
D
-
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 20
Section XV - Sample hydraulic flow calculation for HFC 227ea
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 21
Section XV - Sample hydraulic flow calculation for HFC 227ea
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 22
Section XVI - Sample hydraulic flow calculation for FK-5-1-12
Chemical clean agent fire suppression systems
Red G – Chemical clean agent fire suppression systems – data sheets Page 23
Section XVI - Sample hydraulic flow calculation for FK-5-1-12