Checking Airflow - Ferguson HVAC · 2. Move the blower speed tap for cooling to the heating...
Transcript of Checking Airflow - Ferguson HVAC · 2. Move the blower speed tap for cooling to the heating...
Checking Airflow
When checking Air Flow:
• Make sure that all duct dampers and registers are open and un-blocked
• Ensure that a CLEAN filter is in place
• Make sure that all interior doors are open
• Is The Blower Wheel Clean?
• Is The Evaporator Coil Clean?
• Make Sure You Have approximately 400 CFM Of Air Flow Per Ton
When checking Air Flow (cont.):
Temperature Rise
Temperature Rise
1. Place the indoor fan blower motor speed to it’s original setting for
heat mode operation
2. Subtract your measured return air temperature from your supply
air temperature. This is the Delta-T value.
3. Multiply the Delta-T value by 1.08. Record this value.
4. Divide your BTUH Output by the value you obtained in Step 3.
5. The answer is your actual system airflow.
Airflow Calculations for Furnaces (Heating Mode)
Airflow Calculations For Furnaces
BTUH 100,000
Supply Air Temp: 120 F
Return Air Temp. 70 F
120 F – 70F = 50F (Delta T)
100,000
1.08 X 50
100,000 = 1851 CFM
54
_________________________________ BTUH OUTPUT
1.08 X Temperature Rise ( Delta T) CFM =
____________________________________________________
Example
BTUH = 70,000 x 90% (AFUE) = 63000 BTUH
Return Temperature = 70°F
Supply Temperature = 125°F
∆T = 55°F
63000 BTUH
59.4
1060 =
Sensible Heat Method
CFM = 1060
1. Place the unit in the HEATING mode of operation
2. Move the blower speed tap for cooling to the heating terminal
3. Be sure to disconnect the Heating speed lead and secure it safely
4. Subtract your measured return air temperature from your supply air
temperature. This is the Delta-T value.
5. Multiply the Delta-T value by 1.08. Record this value.
6. Divide your BTUH Output by the value you obtained in Step 5.
7. The answer is your actual system airflow.
Airflow Calculations for Furnaces (Cooling Mode)
Formulas:
Heating Output = KW x 3413 x Corr. Factor
Actual CFM = CFM (from table) x Corr. Factor
BTUH = KW x 3413
BTUH = CFM x 1.08 x Temperature Rise (T)
CFM = KW x 3413
1.08 x T
T = BTUH
CFM x 1.08
3 5 6 8 10 15 20 21
600 17 27 34 39
800 13 20 25 30 40
1000 10 16 20 24 32 48
1200 8 13 17 20 27 40 53 59
1400 7 11 14 17 23 34 46 51
1600 6 10 13 15 20 30 40 44
1800 6 9 11 13 18 27 36 39
2000 5 8 10 12 16 24 32 35
CFMHEAT KIT NOMINAL kW
Formulas
• Static pressure is the resistance to airflow from objects in the air stream
• Filters, coils, heat exchangers, registers, grills, balancing dampers and, of course, the duct itself, are just a few
• After the resistance of these objects is subtracted, the balance is what is available for the duct system
Static Pressure
Air Handler Static Pressure
Furnace Static Pressure
Most Residential Systems Including
Goodman/Amana Are designed To Operate
At 0.5” Water Column maximum Total System Static Pressure
Fan Performance
Static Pressure
Magnehelic or Inclined Manometer
Total System Static Pressure Is A Combination Of Two Readings The First Taken Just Before The Blower And The Other Just After The Blower. The Pressure Drop Between The Two Readings Is The Static Pressure Imposed On The Blower.
+0.3”WC -0.2”WC
Total External Static Pressure =
0.5”WC
Static Pressure In A System Is Typically Determined With The Help Of A Magnehelic, an inclined manometer or a digital manometer
Measuring Devices
Dirty Coil
Blower on Wrong
Speed
Wrong Size Duct
Dirty Filter
Conditions That Affect Duct Static
Understanding Superheat
Superheat Adding HEAT to Steam at 212°F causes the steam to increase in temperature (sensible heat). Heat added to a vapor above the vaporization temperature for that pressure is called Superheat.
212°F Steam
242°F Steam 1325 BTU
15 BTUs Added
242°F Steam
- 212°F Steam = 30°F Superheat
Regardless of what the heat source is;
Sensible & Latent Refer to the process
Or How the heat is being utilized
REMEMBER:
Sensible Heat = change in temperature
(no change in state)
Latent Heat = change of state (no change in temperature)
THE TEMPERATURE AT WHICH AT A GIVEN PRESSURE, THE REFRIGERANT IS NEITHER 100% LIQUID NOR 100% VAPOR
IT IS THE POINT WHERE THE REFRIGERANT IS CHANGING STATE FROM LIQUID TO VAPOR OR VAPOR TO LIQUID
Saturation Point
Saturated Suction Temperature
Pressure
Sat. Evap. Temp.
Evaporator Side
Saturated Liquid Pressure
Sat. Cond. Temp.
Pressure
Condenser Side
WEIGHING METHOD
SUPERHEAT METHOD
SUBCOOLING METHOD
Methods Of Charging Systems
The proper method of charging a heat pump in the heat mode is by weight with the additional
charge adjustments for line size, line length, and other system components.
Weighing The Charge
THIS METHOD CAN BE USED ON ALL TYPES OF REFRIGERATION SYSTEMS
1. DETERMINE THE PROPER WEIGHT OF THE CHARGE FROM THE DATA PLATE ON THE CONDENSING UNIT. THIS WILL USUALLY INCLUDE ENOUGH REFRIGERANT FOR THE STANDARD EVAPORATOR AND 15 FEET OF LINE SET.
2. MEASURE THE AMOUNT OF LINE SET INCLUDED IN THE SYSTEM. USING THE CHARTS IN THE INSTALLATION INSTRUCTIONS, ADD OR SUBTRACT THE PROPER AMOUNT OF REFRIGERANT TO DETERMINE THE FINAL CHARGE.
3. USING A CALIBRATED SCALE, ADD OR REMOVE REFRIGERANT BASED ON YOUR CALCULATIONS
Weighing In Method
R-410A condensers are factory charged for 15 feet of line set. To calculate the amount of extra refrigerant (in ounces) needed for a line set over 15 feet, multiply the additional length of line set by 0.6 ounces. Note for the formula below, the linear feet of line set is the actual length of liquid line (or suction line, since both should be equal) used, not the equivalent length calculated for the suction line. Use subcooling as the primary method for final system charging of long line set system application.
Extra refrigerant needed = (Linear feet of line set – 15 ft) x X oz/ft. Where X = 0.67 for 3/8” liquid tubing.
Weighing Method
Extra refrigerant needed per lineal foot =. Where X = 0.67 for 3/8” liquid tubing and 7/8”.
EXAMPLE: Measured Line Set 25 feet 25 feet Line Set – 15 feet =
10 feet x 0.67 = 6.7 oz.
Weighing Method