CHAPTER SIX · 2021. 3. 1. · 092 CHAPTER SIX AC-AC CONVERSION: INTEGRAL-CYCLE CONTROL 6.1...
Transcript of CHAPTER SIX · 2021. 3. 1. · 092 CHAPTER SIX AC-AC CONVERSION: INTEGRAL-CYCLE CONTROL 6.1...
092
CHAPTER SIX
AC-AC CONVERSION: INTEGRAL-CYCLE
CONTROL
6.1 INTRODUCTION When a full supply voltage of complete cycles is applied across the
load by two thyristors connected back-to-back or triac in the circuit shown
in Fig.5.1, Chapter Five, followed by complete cycles of extinction, the
load voltage waveforms are described as “integral-cycle” or “burst firing”
control. The advantage of this form of control is that when the ON-OFF
switching takes place at zero voltage, the higher order harmonics due to
switching are greatly reduced. Moreover, large current transient resulting
from switching at any arbitrary angle during the voltage cycle as in the
case of phase-angle control, are eliminated.
6.2 SINGLE-PHASE CIRCUIT WITH VOLTAGE CONTROL BY
INTEGRAL-CYCLE TRIGGERING (CASE OF RESISTIVE
LOAD)
Fig. 6.1 shows a typical cycle consists of N conducting cycles in a total
period of T supply cycles. The load voltage with resistive load may be
defined in terms of the supply period by the following equation:
Fourier analysis of Eq.(6.1) for the period 2π is found to be
indeterminate. However, the waveform of Fig.6.1(b) is periodic in the
control period of T supply cycles; hence it is mathematically convenient
to express vL in terms of the control period T rather than of the supply
period 2π as suggsted in reference [36], hence, Eq.(6.1) may be written as:
Power Electronics and Drives
092
Fig.6.1 Typical load voltage waveform for integral-cycle control of
resistive load for N = 2, T = 4.
⁄
⁄
where Vm is the peak value of the supply voltage. Fourier coefficients for
the function of Eq.(6.2) are found to be :
For n ≠ T
∫
⁄
∫
⁄
∫
⁄
Chapter 6 : Integral Cycle Control
090
The magnitude cn of the harmonic, for n≠T, is found to be:
√
(
)
The phase angle between the supply voltage and the current harm-
onic is given by
Substituting Eqs.(6.5) and (6.7) into Eq.(6.11) above yields
⁄
⁄
⁄
⁄
6.3 HARMONIC AMPLITUDE SPECTRA OF INTEGRAL-CYCLE
WAVEFORMS
Integral-cycle control is found to generate waveforms that produce
both subharmonic components of the supply frequency and higher order
harmonics. Hence, this type of voltage control is differing from the phase-
angle control discussed in Chapter Five which produces only higher order
harmonics. For example, with integral cycle control, the case n = 1 in
Eqs.(6.4) to (6.10) represents the (1 ∕ subharmonic of supply
frequency which is generally represents the lowest subharmonic that can
occur. In Fig.6.1, for example, the lowest subharmonic voltage is one-
fourth of supply frequency since T = 4. The 1 ∕ T subharmonic is not
necessarily the harmonic of smallest magnitude, since with certain values
of N and T it is possible for a subharmonic to exceed the value of the
supply frequency component as it will be seen from the examples of the
following subsections.
Power Electronics and Drives
092
6.3.1 The Supply Frequency Component (n =T)
Unlike the phase-angle control, in integral-cycle, the value n = T,
representing the supply frequency, which forms a special case for which
Eqs.(6.4) to (6.10) are indeterminate. If one proceeds from the basic
integrals, the following results are obtained:
∫
⁄
⁄
∫
⁄
[
]
The magnitude = T of the supply frequency component is therefore
given in terms of the rms value of the supply voltage, Vs , thus
√
√
Since , the supply frequency component of current is always in
time phase with the supply voltage. However, this result does not mean
that an integral-cycle circuit operates at unity power factor because, for
part of the control period, the supply current is not in time phase with the
supply voltage. But actually, for part of the control period during which
there is no conduction, T-N cycles, the supply current is zero. For the
waveform of Fig.6.1(b) the magnitude of the supply frequency component
of current is, from Eq.(6.10), of value 2 ∕ 4 = 0.5 per unit of the corresp-
onding sinusoidal value at the same supply voltage. It is to be noted that
the magnitude of the supply frequency component of current is propor-
tional to the number of conducting cycles N.
6.3.2 Zero-Value Harmonics
By examining Eq.(6.6), it is seen that, provided n ≠ T, the term
sin(nπN/T) is zero if nπ ∕ T has any integral value. Since N ∕ T ≤ 1 this
means that is zero for certain values of n > 1. Hence, sin(nπN/T) is
zero if :
Chapter 6 : Integral Cycle Control
092
when N = 2, T = 4, as in Fig.6.1(b), the amplitude of harmonics is zero
when n =2,6,8 etc, corresponding to k = 1,3,4, respectively. The harmonic
spectrum for N = 2, T = 4 is given in Fig.6.2, it is seen that the supply
frequency component n = T is dominant and that the subharmonic n =3,
corresponding to 3 ∕ 4 of supply frequency, is the greatest non-supply
frequency harmonic.
Fig.6.2 Harmonic amplitudes of load voltage for integral-cycle control
for N = 2, T = 4.
6.3.3 Higher Order Harmonic Frequency Components (n ˃ T)
Eq.(6.10) gives the harmonic amplitude of all higher order harmonic
frequency components. The harmonic phase-angle of any indinidual
harmonic is given by Eq.(6.13). However, it is found that, with certain
N ∕ T ratios give rise to subharmonic amplitudes, which exceed that of the
supply frequency component. An example of this occurs in the harmonic
spectrum produced with N =1, T = 4 (Fig.6.3) where, for a 50 Hz supply,
the n = 3 harmonic component exceeds the (supply frequency) comp-
onent. The large subharmonic current components that produced in this
technique may be used in a.c. motor drives.
Fig.6.3 Harmonic amplitude
spectrum for integral-cycle
waveform N=1, T=4 .
Power Electronics and Drives
092
6.4 RMS LOAD VOLTAGE, LOAD POWER AND POWER FACTOR The rms voltage VL of the function vL(ωt) in Fig.6.1(b) is given by:
√
with sinusoidal operation N=T and therefore, =Vs , voltage is not a
continuous function but can only exist at the discrete steps defined by the
values of N and T. This is true in general for all voltage, current and
power relationships in integral-cycle systems. In a resistive circuit the
load voltage and current have identical waveforms. The average power in
the load is, irrespective of waveform, given by
where R is the load resistance in (Ω).
In a circuit with resistive load of resistance R, the average power is
defined by
The distortion factor of the load voltage is defined by ratio of the rms
value of the supply frequency component to the total rms value. For an
integral-cycle waveform
√
Since the displacement angle ψT is zero, the supply frequency component
of the current is always in time-phase with the supply voltage. This does
not mean that an integral-cycle circuit operates at unity power factor
because, for part of the control period, the supply current is not in time-
phase with the supply voltage. Indeed for part of the control cycle, there is
no supply current at all, hence
The power factor is therefore:
√ ⁄
Chapter 6 : Integral Cycle Control
092
Example 6.1
Two thyristors are connected in inverse-parallel for control of the power
flow from a single-phase a.c. supply vs = 300 sinωt to a resistive load with
R =10 Ω. The thyristors are operated with integral-cycle triggering mode
consisting of two cycles of conduction followed by two cycles of extin-
ction. Calculate:
(a) The rms value of the output voltage.
(b) The rms value of the current drawn from the source.
(c) The power delivered to the load.
Solution
(a) In this case N = 2 , T = 4. From Eq.(6.21), the rms value of the load
voltage is
√
√ √
(b) The current drawn from the source = current drawn by the load
(c) The power delivered to the load. From Eq.(6.23)
Example 6.2
In a single-phase resistive circuit in which the load voltage is controlled
by integral-cycle triggering mode of a pair of inverse-parallel connected
thyristors as shown in Fig.5.1 (Chapter Five). The output voltage
waveform consisting of 9 cycle of conduction followed by 18 cycles of
extinction. If the rms input supply voltage is 230V, 50Hz, and R = 20Ω ,
calculate :
(a) The rms value of the load current.
(b) The input power factor.
(c) Average and rms values of the current through the thyristors.
(d) What must be the thyristor ratings?
Power Electronics and Drives
092
Solution : The given data is
Vs = 230V, R = 20 Ω , N = 9 and T = 9+18=27
(a) The rms value of the load current,
√
√
((b) Actual load power =
The supply current is the same as the load current, i.e.
,
hence, the input power in VA = Therefore the supply power factor is
The power factor can also be calculate directly from Eq.(6.25) as
√
√
√
(c) To find the average and rms values of the thyristor currents:
Since the load is resistive we can express the current through the load by
√
Each thyristor carries half cycle during one supply period, Fig.6.4, hence
the average value of the current during one supply period is
∫
Since on thyristor conducts N cycles in a total period of T cycles, hence
the duty cycle of the thyristor will be N/T and the average current of the
thyristor T1 is :
Chapter 6 : Integral Cycle Control
092
√
√
Since both the thyristors share the load current equally, their average
current will be the same, hence
Rms value of the thyristor current can be calculate as
√
∫
√
∫
√
√
√
Since both the thyristors share the load current equally, their rms current
will be the same, hence
(d) Thyristor rating must be: Current I = 10 A, Voltage V = 250 V, PRV
= 2 250 = 500V
Fig.6.4 Currents through thyristors T1 and T2.
Power Electronics and Drives
099
6.5 INTEGRAL-CYCLE CONTROL OF SERIES RESISTIVE –
INDUCTIVE LOAD
Fig.6.5 shows a single-phase thyristor controller used to feed a series
resistance-inductance load. When the thyristors are triggered by long
pulses at a triggering angle equal to zero in integral-cycle triggering
mode, sinusoidal operation results. A typical steady-state cycle is shown
in Fig.6.6 for control period T=3 cycles and conduction period N =2
cycles.
Fig.6.5 Single-phase thyristor controller for series R-L load.
Fig.6.6 Load voltage and current waveforms for series resistance-
inductance load with T= 3 and N =2 cycles.
Analysis of the voltage and current waveforms with R- L load
For zero voltage triggering the load voltage cycle consists of N
conducting cycles in a total period of T supply cycles. Waveforms of the
voltage and current at the R-L load terminals are shown in Fig. 6.6. It is
evident that neither the load voltage nor the load current is zero at the end
Chapter 6 : Integral Cycle Control
222
of the interval 2πN as would be the case for resistive load. Extinction of
voltage and current occurs by natural commutation at an angle of
(2πN+ x) which is immediately prior to a natural current zero.
Analysis of load voltage waveform (Exact solution)
If the source impedance is neglected, the supply voltage is simply given
by
For a control period of T supply cycles, the load voltage is represented by
Fourier analysis of Eq.(6.27) results in the expression shown below:
For n ≠ T
( ,
-
)
( ,
-
)
*
+
The phase angle n between the supply voltage and the current harm-
onic is given by
Power Electronics and Drives
222
The supply frequency harmonic component, when n =T, will be :
∫
∫
Approximate analysis
In most practical cases, it is found that the extinction angle of the load
current (x) is nearly equal to the load angle . To simplify the analysis it
is convenient to assume that x . The approximate solution of the
previous equations are then
( ,
-
)
( ,
-
)
Chapter 6 : Integral Cycle Control
220
*
+
√
If the angle is very small as the case of resistive load Eqs.(6.40) –
(6.46) reduced to
(
)
Current waveform analysis:
The load current waveforms shown in Fig.6.6 resulting from the on-off
switching action of the thyristors consists of a steady-state sinusoidal
component iss plus a decaying exponential component itr with the time
constant τ = L/R. During the on period, the current through R-L load will
be:
The solution of this equation gives the steady state and transient solutions
as follows:
In terms of the control period T:
Power Electronics and Drives
222
where
| |
| | √
(a) Equation (6.50) must satisfy the initial and final conditions
If we substitute these values in Eq.(6.49) it will result in the following
useful equation
(b) Fourier analysis is found to give the following expressions:
The Exact Solution for n ≠ T
∫
∫
∫
∫
∫
∫
Chapter 6 : Integral Cycle Control
222
The solution of the above equations yields:
[
]
*
+
The amplitude of the harmonic :-
[ (
)
(
)
]
The phase angle ψn of the nth harmonic is:
The Fourier coefficient of the supply frequency component (n=T) are
∫
∫
∫
∫
Power Electronics and Drives
222
Solution of these two equations gives
The amplitude of the supply frequency component is
√
or
and the phase angle is
The Approximate Solution
Approximate solution can be achieved when we assume that In
this case the Fourier coefficients of the harmonic are:
[
]
*
+
Chapter 6 : Integral Cycle Control
222
Harmonic content of the load current waveform Harmonic frequency spectra of the line (load) current in a single-phase
circuit with R-L load is shown in Fig. 6.6 for N=2, T=4, representing 50%
power transfer. Also Fig.6.7 shows the current waveform frequency
spectra of pure resistive load for the same power transfer case for
comparison.
(a)
(b)
Fig.6.7 Harmonic amplitude spectra of the load current : (a) With R-L load
for N = 2, T = 4, (b) With R-load for N = 2, T = 4.
It is evident from Fig.6.6(a) that the current waveform for R-L load has
same harmonics as that of the case of resistive load shown in Fig.6.7(b).
However, the amplitudes of the harmonics are different in magnitude and
phases. Also the load current in case of R-L load has a significant d.c.
Power Electronics and Drives
222
component which does not exist in case of R-load. Table 6.1 gives a
comparison between the two cases for clarity.
Table 6.1 comparison between R-load and R-L load results for N=2, T=4.
Amplitude(p.u.)
Case of R-L
load
Amplitude(p.u.)
Case of R-load
Frequency
(Hz)
Harmonic
order
0.09 0 0 DC component
0.25 0.17 12.5 1/T
0.6 0 25 2/T
0.43 0.37 37.5 3/T
0.53 0.5 50 4/T
0.28 0.3 62.5 5/T
0.14 0 75 6/T
0.45 0.9 87.5 7/T
0.10 0 100 8/T
6.6 INTEGRAL-CYCLE CONTROL IN THREE-PHASE CIRCUITS
In this section, the analytical properties of an integral-cycle control
waveforms of voltage and current in each part of various three-phase
loads will be considered. Due to its characteristic feature of permitting
complete cycles of load current followed by complete cycles of
extinction, integral-cycle control is not feasible for all the connections by
which a three-phase load may be supplied with three-phase power. Only
those configurations in which each phase operates independently of the
other two phases results in symmetrical operation are obviously suitable.
6.6.1 Four-Wire, Star-Connected, Resisitive Load Consider the four-wire circuit shown in Fig.6.8. This circuit consists of
three single-phase circuits with their operations separated in time phase
by 120˚. The return current path is provided by the neutral connection.
Each series single-phase R-load is connected in series with a pair of
thyristors in the supply lines. Integral-cycle triggering is used which is
symmetrical in the three phases with the onset at voltage zero. The load
voltage cycle in each phase consists of N conducting cycles in a total
period of T supply cycles. Waveforms of the voltage and current at the
load terminals with N = 2, T = 4 are shown in Fig.6.9. If the source
impedance is negligible, and the supply voltage of phase-a is taken as a
reference, then
van= Vm sin ωt
vbn = Vm sin( ωt - 2 π / 3) (6.75)
vcn = Vm sin( ωt - 4 π / 3)
Chapter 6 : Integral Cycle Control
222
Fig.6.8 Four-wire system with voltage control by integral-cycle triggering
mode of thyristors, case of R-load.
For a control period of T supply cycles, the load voltage for the three
phases are represented by the following equations:
(
)
and the current in each phase will be
Irrespective of the phase shift between the three phases, Fourier
coefficients of the voltage waveform are the same as those given in
Eqs.(6.2) to (6.7) for equal control period T. Therefore, harmonic spectra
of the three phases are similar to each other as calculated and displayed in
Fig.6.10. The current harmonic coefficients for each phase will have the
same harmonic coefficients of the voltage since the load is resistive.
However the neutral current, for the same control period T for the three
phases as shown in Fig.6.9, flows only when one or two phases conduct
Power Electronics and Drives
229
simultaneously. When the three phases conduct the neutral current will be
zero for balanced load.
Fig.6.9 Current waveforms in the three phases and neutral for R-load with
voltage control by integral-cycle triggering mode of thyristors for
N = 2, T = 4.
Fig.6.10 Frequency spectra of the load voltage waves in the three phases
for N=2, T=4,with R-load.
Chapter 6 : Integral Cycle Control
222
Neutral current harmonic analysis Now using the relations given in Eqs.(6.2) to (6,7) to evaluate Fourier
coefficients for the current in each phase one can obtain,
For n ≠ T
Similarly :
For the neutral current since it is the summation of the phase currents,
thus,
aon = anA+ anB + anC
Similarly bon = bnA+ bnB + bnC
Further mathematical simplification of the above two equations yields
Power Electronics and Drives
222
[
]
[
]
The amplitude con of the nth order harmonic is,
and the phase-angle is:
Frequency spectrum of the neutral current wave of Fig.6.9 for N=2, T=4
is shown in Fig.6.11. It should be noted that only odd harmonics exist
since, for even harmonics, Con = 0.
Fig.6.11 Frequency spectrum of the neutral current waveform for
N=2,T=4.
The supply frequency component when n = T of the neutral current
For n=T, Fourier coefficients ao(n=T), bo(n=T) and co(n=T) of Eq.(6.50)
can be evaluated for the current in each phase using the relations given in
Eqs. (6.28) to (6.30), thus
ao(n=T) = 0 (6.94)
b o(n=T) = 0 (6.95)
c o(n=T) = 0 (6.96)
Chapter 6 : Integral Cycle Control
220
Hence the supply frequency component is totally suppressed in the
neutral current. Oscillogram of phase – a load voltage waveform va and
neutral current wave in with resistive load is shown in Fig.6.12 for
clarity.
Fig.6.12 Oscillogram of the phase-a load voltage waveform va and
neutral current wave in with resistive load for N = 2, T = 4.
6.6.2 Four-Wire, Star-Connected, Series R-L Load
Figure 6.13 shows a three-phase, four-wire circuit with R-L load and
voltage controlled by integral-cycle triggering mode of thyristors.
Waveforms of the voltage and currents at the load terminals with N = 2,
T = 3 are shown in Fig. 6.14.
Fig.6.13 Four-wire system with voltage control by integral-cycle
triggering mode of thyristors, case of R-L load.
Power Electronics and Drives
222
Fig.6.14 Waveforms for the three-phase, four-wire system with voltage
control by integral-cycle triggering mode of thyristors for N = 2,
T=3.
Voltage waveform analysis Let the notation 1, 2, 3 denote the three phases A, B, and C respectively.
Thus the notation for the supply voltage (vj) for any jth phase will have the
general form as follows :
Chapter 6 : Integral Cycle Control
222
where for the three-phase:
1 2 3
1
j 1, 2, 3
0, 2 /3, 4 /3
Ltan
R
Similarly the general equation of the VLj will be
Fourier analysis of Eq.(6.98) results in the expressions shown below for
the exact solution:
For n ≠ T
( ,
( )-
( ))
( ,
( )-
( ))
and the amplitude cn of the nth harmonic is
*
+
The phase angle between the supply voltage and the current harm-
onic for the jth phase is given by
The supply frequency harmonic component, when n =T, will be:
Power Electronics and Drives
222
[ ]
[ ]
Hence,
Approximate analysis
In most practical cases, it is found that the extinction angle if the load
current (x) is nearly equal to the load angle . To simplify the analysis it
is convenient to assume that x . Approximate solutions of the previous
equations are then
( ,
( )-
( ))
( ,
( )-
( ))
*
+
( ,
( )-
( ))
( ,
( )-
( ))
Chapter 6 : Integral Cycle Control
222
Fourier coefficient of the supply frequency component (n = T):
[ ]
[ ]
If the angle is very small as the case of resistive load, equations (6.108)
to (6.111) are reduced to
(
)
Harmonics phase-angle relationships
Plot of the magnitude and phase-angle of nth frequency component of
load current is shown in Fig.6.15. It is seen that, the phase displacement
angles of the subharmonics and the higher order harmonics are unbal-
anced. Evaluating the phase-angle relationships of an individual harmonic
or subharmonic, it can be prove that the nth frequency component of load
current in phase A (n1) leads that of phase B (n2) by n120
T
and (n2)
leads (n3) by n120
T
also.
However, if the phase displacement of the jth phase (j) is shifted accor-
ding to the following relationship:
where, j represent the new shifting angle and
j 1 1 2 3m 1,2,...,T 1. m 0, 0, 2 /3, and 4 /3
Power Electronics and Drives
222
(a)
Fig. 4
Phase displacement angles for
T = 2 and N = 1, R -load (a) phase displacement angles for the
1 st harmonic (25Hz) (b) phase displacement angles for the supply frequency component (c) phase
displacement angles for the 3 rd
harmonic (75Hz) (d) phase displacement angles for the 5 th
harmonic (125Hz)
(b)
(c) (d)
Fig. 6.15 Phase displacement angles for N = 1 and T = 2, R-load:
(a) Phase displacement angles for the 1st harmonic (25 Hz),
(b) Phase displacement angles for the supply frequency
component, (c) Phase displacement angles for the 3rd harmonic
(75 Hz), (d) Phase displacement angles for the 5th harmonic
(125 Hz).
This new value of j do not affect the amplitude and phase-angle
relationships of the supply frequency component at the load voltages. It
can be seen from Eq.(6.111), that the amplitude of the nth harmonic is
independent of j , which means that, the variation of j does not affect the
harmonic amplitude spectrum of the jth phase. Only the phase-
displacement angle n of the nth harmonic is changed as could be seen
from Eq.(6.111). The phase-displacement angle nj of the nth harmonic
varies with the variation of mj.
Now after shifting the load voltage waveform of phase B or C or both
by multiple of 2π, the nth frequency component of load current in phase A
(n1) will lead that of phase B (n2) by
2
n(120 360 m )
T
(6.120)
Chapter 6 : Integral Cycle Control
222
and (n1) leads (n3) by:
3
n(240 360 m )
T
(6.121)
The harmonic amplitude spectrum and the phase-angle relationships
for the load voltage waveforms of with N =1, T =2 are shown in Figs.6.16
and 6.17 respectively. It is seen that, the phase-displacement angles of the
subharmonics and the higher order harmonics are unbalanced. Now, if the
phase-displacement angle of phase B, i.e., n2 is shifted by 180 then the
phase-displacement angles of the 1st harmonic (25Hz) and the 5th
harmonic (125Hz), as for example, become balanced.
The new values of n2 for the 1st, 3rd and 5th harmonics which are
12 = 210o, 32 = 270 and 52 =150o respectively give the value m2 = 1
and the new value of 2 is equal to 480o. The harmonic amplitude
spectrum and the phase-displacement angles of the supply frequency
component remains unchanged with the new value of 2, while the phase-
displacement angles of the 1st, 3rd and 5th harmonics changed as shown in
Fig.6.18(a), (c) and (d) respectively. It is found that this shifting technique
makes the phase-displacement angles of the nth harmonic order balanced
(120 between the phases) except when n is 3 or a multiple of 3 where in
this case the phase-displacement angles become in-phase for all values of
N and T except when T is a multiple of 3. Also it is noticed that the phase
shifting of the phase-displacement angles used in this technique is
independ on the value of N. This means that, the values of 2 and 3 that
makes nth order harmonic balanced for certain values of N and T can make
it balanced as well for the same value of T with N = N-1, N-2,.. ,1.
Table 6.2 shows the values of m2 and m3 which make the phase-
displacement angle of the nth harmonic either balanced or in phase for
typical values of T and N. This technique cannot correct the phase
displacement-angles of a particular subharmonic or higher order harmonic
if T is a multiple of three.
Table 6.2: The phase-displacement angles for typical values of T and N.
T N m2 m3
2 1 1 0
4 3-1 1 2
5 4-1 3 1
7 6-1 2 4
8 7-1 5 2
10 9-1 3 6
Power Electronics and Drives
229
Ampl
itude
(per
uni
t)
Frequency (Hz)
Fig.6.16 Harmonic amplitude spectrum for T = 2 and N = 1, R-load.
.
(a)
Fig. 4
Phase displacement angles for
T = 2 and N = 1, R-load (a) phase displacement angles for the
1st harmonic (25Hz) (b) phase displacement angles for the supply frequency component (c) phase
displacement angles for the 3rd
harmonic (75Hz) (d) phase displacement angles for the 5th
harmonic (125Hz)
(b)
(c) (d)
Fig.6.17 Phase displacement angles for T = 2 and N = 1, R-load (before
correction): (a) Phase displacement angles for the 1st harmonic
(25Hz), (b) Phase displacement angles for the supply frequency
component, (c) Phase displacement angles for the 3rd harmonic
(75Hz), (d) Phase displacement angles for the 5th harmonic
(125Hz).
Chapter 6 : Integral Cycle Control
202
(a) (b)
(c) (d)
Fig.6.18 Phase displacement angles for T = 2 and N = 1, R-load (after
correction): (a) 1st harmonic (25Hz), (b) Supply frequency
component (50Hz), (c) 3rd harmonic (75Hz), (d) 5th harmonic
(125Hz)..
2. Analysis of load current waveform
A general solution for the current in any phase can be obtained by
expressing the current through the jth phase in terms of the control period
T as follows:
( )
where
are given in Eqs.(6.51) to (6.53).
(a) Equation (6.122) must satisfy the initial and final conditions
Power Electronics and Drives
202
(b) Expressions (6.122) to (6.124) are directly applicable to determine
Fourier component of the jth phase. Hence for n≠T, assuming approx-
imate solution:
( ,
( )-
)
( ,
( )-
)
The amplitude cnj of the nth harmonic of the jth phase is
[
]
(6.128)
The phase-angle of the nth harmonic of the jth phase is
( )
The supply frequency component (for n =T)
[
]
Chapter 6 : Integral Cycle Control
200
[
]
( )
( )
Neutral current waveform analysis The waveform of the current flowing through the neutral wire may be
obtained by addition of the three instantaneous line current waveforms.
For T=3, N=2, the neutral current waveform is shown in Fig.6.14(d). Let
io be the instantaneous value of the neutral current, where
Combining Eq.(6.124) and Eq.(6.134) for j = 1, 2, 3, gives
⁄
(
)
(
)
⁄
⁄
(
) (
) ⁄
⁄
(
)
(
)
(
)
Fourier analysis of Eq. (6.135) yields,
Power Electronics and Drives
202
The d.c. component of the neutral current is
√
(6.137)
Equation (6.137) gives the magnitude cn of the nth harmonic, for n ≠ T,
of the neutral current by simply multiplying the magnitude cnj of the phase
current, Eq.(6.128), by the factor
.The expression (6.137)
can be considered as a general solution for R and R-L loads since, for
R-load, if we substitute into the above expressions , giving aoo = 0,
and
Supply frequency harmonic component, corresponding to n = T , does not
then exist in the neutral current. This is because the supply frequency
components of the three line currents are balanced, with resistive loads.
The phase angle, , between the nth neutral current harmonic and the
reference voltage va is given, with resistive load, by
Harmonic content of the load voltage and current waveforms of R-L
load
With integral-cycle triggering mode of thyristors, it is evident from
Fig.6.14, in three-phase 4-wire system, that the three load voltage
waveforms are identical and so are the three load current waveforms. The
supply frequency components are found to be balanced, since they are
120˚ apart in time-phase. In general the resultant phase voltages are
unbalanced in that they do not sum to zero at every instant of the overall
cycle. This is due to the fact that the phase-displacement angles
of a particular harmonic or subharmonic component
are given by different functions of N. As a result current flows discontin-
Chapter 6 : Integral Cycle Control
202
uously in the neutral wire. It is also worth to mention that the neutral
current contains a considerable d.c. component, as it is obvious from
Eq.(6.136), which is three times of the phase component, Eq.(6.108). .
For R-L load, the harmonic frequency spectra of the line currents and
neutral current of the 4-wire star-connection are given in Fig. 6.19.
Fig.6.19 Frequency spectra of the line and neutral current waves for
N=2,T=4.
The per unit values of these current were calculated for given values of
N and T. Frequency spectra for N=2 , T=4 , = π/3 , Fig. 6.19, show that
the neutral current contains both subharmonics and higher harmonic
components, of the same order as the phase current waveforms, except
that there is no supply frequency component or its multiples. If the control
period T is increases, with ratio N/T constant, the neutral current is found
to diminish and its value goes to zero for T ˃˃ 1.
6.7 OTHER FORMS OF INTEGRAL-CYCLE CONTROL
Integral-cycle control often results in considerable power loss but it is
preferably used type of control in many industrial applications such as
temperature control and d.c. motor drives. As a frequency changer, this
type of control proves to be inefficient because the supply frequency
component often exists as an effective component in the output voltage.
Complete removal of the supply frequency component from the output
waveform is considerably difficult due to the necessary use of physically
large adding, subtracting, and phase-shifting components because the
signals are at high level of power. Moreover, suppression of the supply
frequency component using these techniques results in high losses and
implementing expensive equipment. On the other hand, ICC has many
Power Electronics and Drives
202
advantages over phase-angle control as it generates less number of
harmonics, reduces the electromagnetic interference and possesses all the
advantages of zero voltage switching techniques.
It was also shown elsewhere, that ICC in its conventional form is not
feasible for a.c. drives application. The reason for that is the three-phase
waveforms produced are rich of subharmonics of the supply frequency
which are unbalanced neither in phases nor in amplitudes.The effects of
these subharmonics on the motor causes vibration, noise, and temperature
rise in the motor windings. To improve ICC performance, two anti-phase
ICC waves are triggered alternatively to produce phase modulated like or
bi-phase integral cycle controlled (BPICC) voltage or current waveforms.
The technique uses bi-phase integral cycle controlled waveforms is called,
elsewhere, angle or phase modulation of discrete form. The bi-phase
integral cycle control gives high efficiency of conversion as well as
eliminates completely the supply frequency component and most of the
power associated with the supply frequency component is transferred to
the desired frequency component, and the output voltage waveform
contains little harmonics.
6.7.1 Bi-Phase Power Converter The bi-phase power converter is depicted in Fig.6.20. The converter
consists of three single-phase center-tapped transformers supplying three-
Fig.6.20 Three-phase, 4-wire, star-connected load supplied by a three
single-phase centre-tapped power transformers to realize bi-
phase ICC waveforms.
phase load via groups of inverse parallel connected thyristors. If the in-
phase and anti-phase supply voltage waveforms are switched ON at zero
voltage instant alternatively in a control period of T supply cycles, then
for the case of R- load, the output voltage waveform per phase will be as
shown in Fig.6.21.
Chapter 6 : Integral Cycle Control
202
Fig.6.21 Output voltage waveform per phase for the circuit of Fig.6.20 for
the case of resistive load.
For the case of R-L load, the current will not fall to zero after the end
of the zero-phase ICC wave and the load voltage vLj of the jth phase will
be as shown in Fig. 6.22, and it may be defined by the following equation:
Fig.6.22 Load voltage vLj of the jth phase for a bi-phase ICC wave with
R-L load.
( )
( )
vLj
ωt
x/T
x/T
Power Electronics and Drives
202
where N1 = N2 = 1, 2, …, T/2 and T= the control period.
x = current extinction angle and j = angle of phase j , ( j =1,2,3 ) .
Fourier expansions of Eq.(6.140) gives the following results:
For n T and x = (impedance angle), the amplitude cn and the phase
angle ψn of the nth harmonic component for the jth phase may be found as:
ao j = 0 (6.141)
|(
( )
( )
( )
( )
( ) )|
|(
( )
( )
( )
( )
( ) )|
The amplitude cnj of the nth harmonic component for n ≠ T is
√
and the phase angle nj between the supply voltage and the nth current
harmonic is given by
For n = T, which is the supply frequency component:
aTj = 0 and bTj = 0 (6.146)
cTj = 0 and ψTj = 0 (6.147)
Chapter 6 : Integral Cycle Control
202
It is obvious from the above two equations that the amplitude of the
supply frequency component cTj equal to zero.This means that the supply
frequency component is entirely suppressed by this type of converters.
The harmonic amplitude spectrum and phase-displacement angles of the
load voltage waveform of a BPICC wave is shown in Fig.6.23(a) for the
case where N1 = N2 = 2 and T = 4, for R-load.
(a)
(b)
Fig.6.23 Bi-phase ICC converter : (a) Harmonic amplitude spectrm of
phase A, B, and C, (b) Phase angle relationships for N1 = N2 = 2
and T = 4, R-load.
Power Electronics and Drives
209
It is seen from Fig.6.23(a) that the harmonic amplitude spectrum contains
odd harmonics only and the amplitudes of the even harmonics as well as
the supply frequency component are all equal to zero. Also the harmonic
spectrums for the three phases are found to be similar.
As it can be seen from Fig. 6.23(b), the phase displacement angles for
any individual harmonic are found to be unbalanced for the three-phase
system.The unbalanced phase harmonics generated by this type of
converter are found to create severe problem when it is used as an a.c.
drive. However, this problem can be solved by using the phase-shifting
technique mentioned in the previous section. This technique, although it is
simple, it has solved the similar problems associated with integral-cycle
triggering for the three-phase systems. The phase-shifting technique
involves shifting the load voltagevLj of phase B or phase C or both by
multiples of 2π with respect to phase A which is taken as a reference
phase.
By applying the phase shift technique to any BPICC wave , most of the
important harmonic components become balanced in amplitude and phase
displacement. Nevertheless, few of them becomes in-phase. In any case,
the amplitude of an individual harmonic does not affected by the phase-
shifting procedure. This fact is illustrated in Fig.6.24 for the case when
N = 2 and T = 4 after phase angle correction for phase B and C.
Oscillograms for the voltage and current waveforms for highly inductive
load with BPICC are shown in Fig.6.25 for clarity.
Fig.6.24 Phase angle relationships for N1 = N2 and T = 4, R-load after
phase-angle correction.
Chapter 6 : Integral Cycle Control
222
current
Voltage
Fig.6.25 Oscillograms of the voltage and current waveforms for highly
inductive load.
6.7.2 Multi-Conduction and Control Periods Integral-Cycle Triggering
Technique
A typical integral-cycle controlled (ICC) with multi-control period T1,
T2, T3,…,Tn and different conduction cycles N1, N2, N3,…. Nn in a total
control period of T supply cycles is shown in Fig.6.26. This waveform is
periodic in the control period of T supply cycles; hence load voltage with
resistive load may be defined in terms of the control periods rather than of
supply cycles, as mentioned early in this chapter. Hence for a 3-phase,
4-wire system, let the notation 1, 2, 3 denote the three phases A, B and C
respectively. Thus the load voltage vLj for the jth phase ( j=1,2,and 3) will
have the general form given in Eq.(6.148) :
Fig.6.26 Realization of multi-conduction and multi-control period
integral-cycle waveform (MICC) using consecutive ICC
waves with different control periods.
Power Electronics and Drives
222
( )
( )
( )
where
γ 1 = 0 , γ 2 =120⁰ and γ 3 = 240⁰ are the phase angles of the three-phase
voltages.
Ni is the number of conduction (ON) cycles.
T1 = N1 + D1 , T2 = N2 + D2 and T3 = N3 + D3
Fourier analysis of Eq. (6.148) gives the following results:
The zero frequency (d.c.) component coefficient ao is
ao = ao1 + ao2 + ao3 =0
The nth harmonic coefficients are
anj = an1j + an2j + an3j (6.149)
| .
( )
( )
( )
( )
( )/|
bnj = bn1j + bn2j + bn3j
Chapter 6 : Integral Cycle Control
220
| .
( )
( )
( )
( )
( )/|
The amplitude Cnj of the nth harmonic component for n ≠ T is
√
and the phase angle nj between the supply voltage and the nth current
harmonic is given by
The supply- frequency harmonic component (n=T) is found to be
aTj = aT1j + aT2j + aT3j
bTj = bT1j + bT2j + bT3j
√
and the phase angle is
If N = N1 = N2 = N3 then the above two equation becomes
Power Electronics and Drives
222
The supply frequency harmonic component CTj when n=T and N = N1 =
N2 = N3 is
and the phase angle Tj is
Fig.6.27 shows harmonic amplitude spectra of two types of discrete
frequency MICC waveforms for different value of conduction cycle (N1,
N2, N3) and control periods (T1, T2, T3).
Fig.6.27 Harmonic amplitude spectra of phases (A, B, and C) for two types
of MICC waveform.
Chapter 6 : Integral Cycle Control
222
From Fig.6.27, it is to be noted that this type of control proves to be
inefficient as a frequency changing technique because the supply
frequency component exists as an effective component in the output
voltage. It is also obvious, from Eq.(6.160) that the supply frequency
component cannot be suppressed and its peak value depends on the
number of conduction cycles N and on the control period T. In general,
the harmonic spectrum of the MICC wave shown in Fig.6.27 depends
largely on the values of N1, N2, N3 as well as the values T1, T2, and T3
which may be called the MICC parameters. However, the harmonics
generation with this type of ICC wave can be selected or controlled by a
judicious selection of the values of these parameters. A certain desired
frequency component can be enhanced and other undesirable frequency
components can be eliminated by this technique.
Fig 6.28, shows the amplitude and phase angle relationship of selected
harmonic component for the case N1=N2=1, T1 =2 and T2=3, R-load,
three-phase system. Also from Fig.6.28, it is obvious that the amplitudes
of the harmonic components for a certain frequency are balance for the
three phases, whereas the phase-angle relationships for these components
are found to be unbalanced.
Fig.6.28 Amplitude and phase angle relationship of some selected
harmonic components for the case N1= N2 = 1, T1 = 2,
T2 = 3 and T = 5 , three-phase system, R-load .
Power Electronics and Drives
222
6.7.3 Bi-Phase Multi-Control and and Multi-Conduction Period Integral-
Cycle Control (BPMICC) Technique
In the previous converter which is based on ICC , the supply frequency
component can be entirely eliminated by using two ICC waves with 0⁰
and 180⁰ phase shifted as shown in Fig.6.29 which leads to the Bi-phase
Multi-period Integral-cycle control (BPMICC).This can be achieved by
using the same three-phase converter configuration shown in Fig.6.20.
Fig.6.29 Load voltage vLj of the jth phase for a bi-phase ICC wave.
The load voltage vLj of the jth phase of the waveform of Fig.6.29 may be
defined during the control period T by
( )
( )
vLj
ωt
Chapter 6 : Integral Cycle Control
222
( )
( )
where T1 = N1 + N2 + D1 and T2 = N3 + N4 + D2
Fourier analysis of Eq.(6.161), gives the following results:
For n ≠ T
(
( )
( )
( )
( )
( )
( ) )
(
( )
( )
( )
( ) )
The amplitude cnj of the nth harmonic component for n ≠ T is
√
and the phase angle nj between the supply voltage and the nth current
harmonic is given by
The supply-frequency harmonic component (n=T) is found to be
Power Electronics and Drives
222
√
√
The amplitude cTj of the supply frequency component for n = T and the
phase angle nj are
√
The analysis of the bi-phase ICC wave of Fig.6.29 shows that the
amplitude of the supply frequency component ( i.e. cTj ) equal to zero only
for the cases when N1 = N2 and N3 = N4 or N1=N4 and N2=N3. Plot of the
harmonic amplitude spectrum (per-phase) of the ICC wave for different
values of N1, N2 ,N3,N4 ,T1 and T2 for R- load is shown in Fig.6.30.
Fig.6.30 Harmonic amplitude spectrum per-phase for a bi-phase ICC
wave with N1=N2=N3=N4 =1, and T1 =3, T2 = 4 and T=7.
Fig.6.31 shows the amplitude and phase-angle relationship of some
selected significant harmonic component for the three phases for the case
N1 = N2 = N3 = N4 = 1,T1 = 3 and T = 7. It is to be noted that the supply
Chapter 6 : Integral Cycle Control
222
frequency harmonic component is totally eliminated and the harmonic
spectra for the three phases are the same.
Fig.6.31 Amplitude and phase- angle relation of some selected significant
harmonic component in a bi-phase ICC wave for the case
N1 = N2 = N3 = N4 =1, T1 = 3, and T=7, R-load, 3-phase system.
Also from Fig.6.31, it is obvious that the amplitudes of the harmonic
components for a certain frequency are balance for the three phases, while
the phase-angle relationships for these components are found to be
unbalanced. This problem can be solved using the multiple of 2π phase
Power Electronics and Drives
229
shifting technique discussed in the previous section. Fig.6.32 shows the
phase displacement angle after correction. Matlab program for calculating
the frequency spectra and phase relationships is given in Appendix C.
Fig.6.32 Amplitude and phase-angle relationship of some selected
significant harmonic component in a bi-phase ICC wave for
the case N1 = N2 = N3= N4 = 1, T1 =3, and T=7, R-load after
phase-angle correction.
Chapter 6 : Integral Cycle Control
222
Fig.6.33 shows oscillograms of the load voltage waveforms vLA, vLB for
bi-phase ICC wave for the case when T1=3, T2=4,N1=N2=N3=N4=1.
vLA
vLB
Fig.6.33 Load voltage waveforms (R-load) BPMICC wave for the case
when T1=3, T2=4,N1=N2=N3=N4=1 .
Table 6.3 gives comparison between phase-angle triggering and integral-
cycle triggering.
Table 6.3
Integral-cycle triggering Phase-angle triggering
1) No d.c. component with resistive load
for both the load voltage and current
waveforms in single-phase and three-
phase systems. However, d.c. compo-
nent appears significantly in the line
and neutral currents with R-L load.
2) Odd + even harmonics.
3) Harmonics (even are troublesome in
electricity supply system)
4) Subharmonics are generated in this
type of control. Subharmonic of the
fundamental down to the (1/T)th subh-
armonic.
e.g: N=6 , T=8 : Lowest subharmonic
is 1/8 supply frequency.
1) DC value = 0, no d.c. component
with both resistive and resistive-
inductive loads.
2) Odd, higher harmonics.
3) Higher harmonic voltage <
Fundamental voltage.
4) No generation of subharmonics.
Power Electronics and Drives
222
Integral-cycle triggering results in conduction patterns that contain
subharmonics of the supply frequency and so constitute a form of step-
down frequency changing that can be considered as a form of frequency
changer. Also integral-cycle triggering results in a considerable reduction
in the amplitudes of the higher order harmonics as compared with other
triggering techniques and it is possible that Radio Frequency Interference
(RFI) is negligible. The phase-control switching can produce higher order
harmonics and heavy inrush current while switching on in a cold start,
while integral-cycle control circuits have the advantage of low inrush
current due to zero voltage switching ease in construction and low
hardware cost. Therefore, integral-cycle control loads have been widely
used in resistive loads, such as heaters, oven, furnaces and spot welders.
Also it is used in speed control of single-phase induction motor and d.c.
series motor.
As a frequency changing scheme, integral-cycle triggering was found
not feasible for applications in the three-phase systems exploiting this
technique for a.c. motor speed control. This is because the amplitudes and
phase-displacement angles of the higher order harmonic and subharmonic
components of the integral-cycle controlled waveform are determined by
the conduction period N and the control period T and the order of the
individual harmonic. However using the modified integral cycle techni-
ques such as bi-phase ICC or multi-bi-phase ICC together with phase-
angle correction techniques may rectify the situation.
The choice between integral-cycle triggers and phase-angle triggering,
in the circuit of Fig. 6.1 depends partly on whether the long off' time with
integral-cycle control in case of unmodified type is acceptable in the
particular application.
Chapter 6 : Integral Cycle Control
220
PROBLEMS
6.1 Power to a resistive load is to be controlled using integral-cycle triggering
mode of thyristors. A single-phase voltage source of 230V,50Hz is used
to provide current to a 50Ω resistor via a pair of inverse parallel-
connected thyristors which is gated to produce integral cycle voltage
control with number of conducting cycles N = 6 and the total period T
(ON+OFF) is 8 supply cycles. Calculate the power transfer to the resistor,
the current and the power factor of the circuit.
[Ans : PL= 793.5 W, IL= 3.98 A, PF= 0.866]
6.2 A sinusoidal voltage supply vs =300 sinωt is connected to a pair of inverse-
parallel connected thyristors to control power flow to a 20 Ω resistive
heating load. The thyristor are gated to produce burst-firing of the load
current. If the number of conducting cycles N = 3 and the total period
T = 6 supply cycles. Determine the average percentage power transfer to
the load as compared with the operation of the circuit with sinusoidal
voltage .What firing angle would be required with phase-angle controlled
by thyristors to produce the same rms load current?
[Ans : % Power = 50 , α = 90˚]
6.3 A 230V, 50 Hz sinusoidal voltage supply is used to provide power to a
resistive load via a pair of inverse-parallel connected thyristors. The two
thyristors are triggered to give integral-cycle controlled current waveform
in the number of conducting cycles N = 2 and the total control period T =5
supply cycles. Calculate the supply frequency harmonic voltage and the
amplitudes of its immediate harmonic neighbors up to the sixth order
harmonic.
[Ans : cn=T =130V, cn=1 = 43.15V, cn=2 = 49.30V, cn=3 = 64.70V,
cn=4 =115V, cn=5 = - 49V, c n=6 = - 43V]
6.4 One feature of the harmonic properties of integral-cycle controlled thyristor
circuits is the presence of subharmonics of the supply frequency. With a
control period T (ON time + OFF time), the lowest subharmonic is 1\T of
the supply frequency. What are the disadvantages of electrical supplies
containing subharmonics of the fundamental?
6.5 For a single-phase integral-cycle controlled thyristor circuit with resistive
load, show that the rms value of the harmonic load voltage VH (excluding
the supply frequency component when n=T) is given by
Power Electronics and Drives
222
√
Hence prove that, the ratio between the rms value of VH and the rms load
voltage VL is given by
√
6.6 In an integral-cycle controlled thyristor circuit with resistive load switching
at voltage zero, the current, when it flows, is always in time phase with
the supply voltage. Does this mean that the circuit operates at unity power
factor?
6.7 The two main technical disadvantages semiconductor controlled rectifiers
are the generation of radio interference and the distortion of supply
voltage.
(a) Explain briefly the types of radio frequency interference caused
by semiconductor action. What frequency bands are included in
a typical noise spectrum? Describe a simple and cheap way to
demonstrate the principle features of radiated interference such
as frequency spectrum, amplitude-distance, effect of screening
etc. and give typical results of such a demonstration.
(b) Explain how thyristor switching causes distortion of the supply
voltage. If the thyristors are to be switched so as to develop
50% power in a resistive load, discuss the modes of thyristor
triggering that you would recommend to give (i) minimum
supply voltage distortion, (ii) minimum radio interference.
6.8 The voltage of a three-phase 4-wire resistive load is to be controlled by
using three-phase a.c. controller with integral-cycle triggering mode of
thyristors as shown in Fig.6.34. The Three-phase supply is star-connected
with 400V, 50 Hz line to line voltage. (a) For control parameters N = 2
and T = 4, find the load phase current, and the total power transferred to
the load, (b) what is the power factor of the circuit?
[ Ans : IL =16.26 A per-phase, PL =7.933 kW for three phases, (b) PF =
0.707 ]
Chapter 6 : Integral Cycle Control
222
Fig.6.34.
6.9 For the problem 6.8, use equations (6.92) and (6.94) to determine the
supply frequency harmonic voltage and the amplitudes of its immediate
harmonic neighbors for the neutral current.
Note : Use Im = Vm / R , where Vm is the peak of the phase voltage.
[Ans: cn=T = 0V, cn=1=15V, cn=2= 0V , cn=3 = -11.8V, cn=5 = 6.73V]
6.10 An ideal single-phase supply vs = Vm sin ωt provides power to a resistive
load R = 100Ω using the circuit of Fig.6.35. The SCRs of the inverse-
parallel pair are gated to provide integral cycle control mode of triggering
such that the output is d.c. voltage.
(a) Prove that the value of the output d.c. voltage component
produced by the circuit is given by
(
)
(b) Derive an expression for the power transferred to the load in
terms of Vm, N and T (the control period).
(c) Calculate the power when Vm = 300 V , and N =20 , T =30
cycles respectively.
Power Electronics and Drives
222
Fig. 6.35.
[Ans : (b) (
)
, (c) 162.27 W]
6.11 The line currents of a three-phase 3-wire delta-connected resistive load is
to be controlled by using three-phase a.c. controller with integral-cycle
triggering mode of thyristors as shown in Fig.6.36. Prove that the
amplitude of the nth harmonic for n ≠ T for the three phases ( j =A, B,
and C) are given by
√
√
√
and for n=T :
Fig.6.36.