Fieldbus requirements able to handle very short frames efficiently able to handle both periodic and aperiodic
traffic bounded response time no single point of failure error detection without retransmission or
correction short geographical scope with a limited
number of i/o’s low cost
7
B.2 Profibus PROcess FIeldBUS DIN 19245 FMS (Fieldbus Message Specification) DP (Distributed Peripheral) PA (Process Automation)
32 stations per segment 9.6, 19.2, 93.75 kbps for segment length
less than 1200 m
8
Medium access control token passing among master stations on
list of active station (LAS) transmission from slave stations only by
master station’s polling
9
Priority mechanism
two priority classes: high and low TTR: target rotation time TRR: real rotation time TTH: token holding time, TTH =TTR - TRR
10
at least one high priority message per token reception regardless of TTH
additional high priority messages only if TTH is still positive
low priority messages after high priority message transmission if TTH is still positive
12
Fieldbus Message Specification (FMS)
application layer program invocation management variable access event management context management (connection
establishment) virtual fieldbus device object object dictionary management
13
B.3 WorldFIP Field Instrumentation Protocol
French standard network configuration and transmission
speed
32 stations per segment up to 256 stations 31.25 kbps, 1Mbps, 2.5 Mbps
14
Medium access control centralized polling bus arbitrator producer-consumer model bus arbitrator transmitting an ID frame for a
certain pair of producer and consumers
elementary cycle with a period equal to that of most frequent message
aperiodic variable and message exchange after periodic data transmission
filling for excess time
17
B.4 표준화 동향 IEC 61158 Fieldbus standard for use in
industrial control systems (IEC/SC/65C) Type 1: IEC Fieldbus Technical Specifications Type 2: Control Net Type 3: Profibus Type 4: Pnet Type 5: HSE of the Fieldbus Foundation Type 6: SwiftNet Type 7: WorldFip Type 8: Interbus
18
표준화 동향 II IEC 61784-1 Digital data communications for measurement
and control, Part 1: Profile sets for continuous and discrete manufacturing relative to fieldbus use in industrial control systems
set of communication profiles based on IEC 61158 to correctly state the compliance to IEC 61158 to avoid divergent implementations
19
Communication Profile Family CPF 1: Foundation Fieldbus CPF 2: ControlNet, EtherNet/IP, DeviceNet CPF 3: PROFIBUS DP, PA, Profinet CPF 4: P-NET CPF 5: WorldFIP CPF 6: INTERBUS CPF 7: SwiftNet (dropped)
CPF 8: CC-Link CPF 9: HART CPF 10: Vnet/IP CPF 11: TCnet CPF 12: EtherCAT CPF 13: Ethernet Powerlink CPF 14: EPA CPF 15: MODBUS CPF 16: SERCOS
20
21
표준화 동향 II ISO 15745 Industrial automation systems
and integration - Open systems application integration frameworks (TC 184 SC5) Part 2: ISO 11898 based control systems DeviceNet, CANKingdom, CANOpen
Part 3: IEC 61158-based control systems P-Net, Profibus, WorldFIP, ControlNet,
Interbus Part 4: Ethernet-based control systems Ethernet/IP, ADS-net, FL-net, Profinet,
Modbus TCP, EtherCAT, Ethernet Powerlink
23
표준화 동향 III SEMI (Semiconductor Equipment and Materials
International) Sensor/actuator network standards DeviceNet SDS(Smart Distributed System) LonWorks Seriplex Profibus-DP Modbus/TCP over TCP/IP CC-Link Ethernet/IP