Chapter 07 Transformer

download Chapter 07 Transformer

of 48

description

Transformer

Transcript of Chapter 07 Transformer

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    1

    Transformers

    Table of Content

    Section Content Page

    1 Introduction 2

    2 Principal of operation 3

    3 Induced voltage (EMF equation) 4

    4 Transformer construction 7

    4.1 Transformer construction of the core 8

    4.2 Transformer laminations 9

    4.3 Transformer core types 9

    4.4 Transformer winding arrangement 10

    5 Transformer dot orientation 11

    6 Transformer Primary tap change 12

    7 Transformer core losses 13

    7.1 Hysteresis losses 13

    7.2 Eddy current losses 13

    7.3 Copper losses 14

    8 Transformer loading 15

    8.1 Transformer at NO-Load 15

    8.2 Transformer On-Load 16

    9 Three phase ideal transformer 20

    10 Three phase transformer construction 26

    11 Equivalent circuit transformer 26

    11.1 Equivalent circuit of an ideal transformer

    at No-Load 27

    11.2 Equivalent circuit of an ideal transformer

    On-Load 30

    11.3 Equivalent circuit of real transformer 31

    11.4 Approximate Equivalent circuit of

    Transformer 34

    12 Losses and efficiency of transformer 35

    12.1 Iron losses or core losses 36

    12.2 Core losses 38

    12.3 Short circuit test 39

    12.4 Efficiency of single phase transformer 40

    13 Current transformer 39

    14 Autotransformer 44

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    2

    Transformers

    7.1. Introduction

    In its simplest form a single-phase transformer consists

    of two windings, wound on an iron core one of the windings is

    connected to an ac source of supply f. The source supplies a

    current to this winding (called primary winding) which in turn

    produces a flux in the iron core.

    This flux is alternating in nature (Refer Figure 6.1). If the

    supplied voltage has a frequency f, the flux in the core also

    alternates at a frequency f. the alternating flux linking with

    the second winding, induces a voltage E2 in the second winding

    (called secondary winding). [Note that this alternating flux

    linking with primary winding will also induce a voltage in the

    primary winding, denoted as E1. Applied voltage V1 is very

    nearly equal to E1].

    If the number of turns in the primary and secondary windings

    is N1 and N2 respectively, we shall see later in this unit that

    E1 / E2 = N1 / N2.

    The load is connected across the secondary winding, between

    the terminals a1, a2. Thus, the load can be supplied at a

    voltage higher or lower than the supply voltage, depending

    upon the ratio N1 / N2.

    Figure (7.1) Basic arrangement of transformer

    .When a load is connected across the secondary winding it

    carries a current I2, called load current. The primary current

    correspondingly increases to provide for the load current, in

    addition to the small no load current. The transfer of power

    from the primary side (or source) to the secondary side (or

    load) is through the mutual flux and core. There is no direct

    electrical connection between the primary and secondary sides.

    In an actual transformer, when the iron core carries

    alternating flux, there is a power loss in the core called

    core loss, iron loss or no load loss. Further, the primary and

    secondary windings have a resistance, and the currents in

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    3

    primary and secondary windings give rise to I2R losses in

    transformer windings, also called copper losses.

    The losses lead to production of heat in the transformers, and

    a consequent temperature rise. Therefore, in transformer,

    cooling methods are adopted to ensure that the temperature

    remains within limit so that no damage is done to windings

    insulation and material.

    7.2. Principal of operation

    A transformer operates on the principle of mutual

    inductance between two (and sometimes more) inductively

    coupled coils. It consists of two windings in close proximity

    as shown in fig (7.2).

    The two windings are coupled by magnetic induction. (There is

    no conductive connection between the windings). One of the

    windings called primary, has N1 turns is energized by a

    sinusoidal voltage E1. The second winding, called secondary,

    has N2 turns and feeds the load. The alternating current in the

    primary winding sets up an alternating flux in the core. The

    secondary winding is linked by most of this flux and emfs are

    induced in the two windings. The emf induced in the secondary

    winding drives a current through the load connected to this

    winding. Energy is transferred from the primary circuit to the

    secondary circuit through the medium of the magnetic field.

    A power transformer in which the secondary voltage is higher

    than the primary is called a step-up power transformer; if the

    secondary voltage is less than the primary, the device is

    known as a step-down power transformer. The product of current

    times voltage is constant in each set of coils, so that in a

    step-up power transformer, the voltage increase in the

    secondary is accompanied by a corresponding decrease in the

    current.

    Figure (7.2)

    A transformer makes use of Faraday's law and the ferromagnetic

    properties of an iron core to efficiently raise or lower AC

    voltages. It of course cannot increase power so that if the

    voltage is raised, the current is proportionally lowered and

    vice versa.

    Faraday's Law

    Any change in the magnetic environment of a coil of wire will

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    4

    cause a voltage (emf) to be "induced" in the coil. No matter

    how the change is produced, the voltage will be generated. The

    change could be produced by changing the magnetic field

    strength, moving a magnet toward or away from the coil, moving

    the coil into or out of the magnetic field, rotating the coil

    relative to the magnet, etc.

    Figure (7.3)

    7.3. Induced voltage (EMF equation)

    If the flux, , linking a coil of N turns and inductance,

    L, varies sinusoidally at frequency f, then

    t sinmax ---------------------------(6.1)

    Where max is the peak value of the flux

    Then the induced emf (voltage) , from Faradays law (voltage =

    rate of change of flux linkage) is,

    tNtdt

    dN

    dt

    dNe

    cossin

    maxmax

    2sin2cos2

    maxmax

    tfNtfNe ---------(6.2)

    The peak value of the induced emf is max2 fN .

    The rms (root mean square) value, E, of the induced emf is,

    maxmax 44.422

    1fNfNE volt ----------(6.3)

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    5

    Example 1

    The primary winding of a 50 hz transformer has 480

    turns and is fed from 6400 v supply, find,

    (a) the peak value of the flux in the core.

    (b) Secondary voltage if the secondary winding has 20 turns.

    Solution:

    (a) From eqn. 6.3

    06.04805044.4

    6400max

    Wb

    (b) Voltage induced in secondary winding = 4.44x50x20x0.06 = 266.4 V

    Transformation ratio

    If Np and Ns are the number of turns in the primary and

    secondary winding and Ep and Es are the rms values of primary

    and secondary induced emf, eqn 6.3 gives

    max44.4 NfE pp ---------------- (6.4a)

    max44.4 NfE ss ----------------- (6.4b)

    Therefore,

    N

    N

    E

    E

    s

    p

    s

    p ------------------------ (6.5)

    Thus the ratio of primary to secondary voltage is the same as

    the ratio of primary winding turns to the secondary winding

    turns. This ratio (Np/Ns) is known as transformation ratio. By

    selecting this ratio properly the transformation can be done

    from any convenient input voltage to any convenient output

    voltage. If Np is greater than Ns, the secondary voltage will

    be lower than the primary voltage and the transformer is known

    as step down transformer. If Ns is greater than Np, the

    secondary voltage would be higher than the primary voltage and

    then the device is known as step up transformer.

    If the losses in a two winding transformer are neglected, the

    volt amperes in the primary and secondary must be equal.

    Therefore,

    IEIE sspp

    N

    N

    I

    I

    E

    E

    s

    p

    p

    s

    s

    p ---------------------- (6.6)

    Where Ip and Is are the currents in the primary and secondary

    windings respectively. Thus the current is transformed in the

    reverse ratio of the voltage. If the transformer steps up the

    voltage, it steps down the current and vise verse.

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    6

    Figure (7.4)

    Figure (7.5)

    Examples:

    1. step down transformer

    2. Step up transformer

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    7

    3. Transformation ratio

    Primary

    Windings

    Secondary

    Voltage

    Turns

    Ratio

    Primary

    Voltage

    Secondary

    Voltage

    Terns

    Ratio

    480 240 2/1 600 120 5/1

    480 120 4/1 600 208 2.88/1

    480 24 20/1 208 120 1.73/1

    7.4. Transformer construction

    The construction of a simple two-winding transformer

    consists of each winding being wound on a separate limb or

    core of the soft iron form which provides the necessary

    magnetic circuit.

    This magnetic circuit, know more commonly as the "transformer

    core" is designed to provide a path for the magnetic field to

    flow around, which is necessary for induction of the voltage

    between the two windings.

    However, this type of transformer construction were the two

    windings are wound on separate limbs is not very efficient

    since the primary and secondary windings are well separated

    from each other.

    This results in a low magnetic coupling between the two

    windings as well as large amounts of magnetic flux leakage

    from the transformer itself. But as well as this "O" shapes

    construction, there are different types of "transformer

    construction" and designs available which are used to overcome

    these inefficiencies producing a smaller more compact

    transformer.

    The efficiency of a simple transformer construction can be

    improved by bringing the two windings within close contact

    with each other thereby improving the magnetic coupling.

    Increasing and concentrating the magnetic circuit around the

    coils may improve the magnetic coupling between the two

    windings, but it also has the effect of increasing the

    magnetic losses of the transformer core. As well as providing

    a low reluctance path for the magnetic field, the core is

    designed to prevent circulating electric currents within the

    iron core itself.

    Circulating currents, called "eddy currents", cause heating

    and energy losses within the core decreasing the transformers

    efficiency. These losses are due mainly to voltages induced in

    the iron circuit, which is constantly being subjected to the

    alternating magnetic fields setup by the external sinusoidal

    supply voltage.

    One way to reduce these unwanted power losses is to construct

    the transformer core from thin steel laminations. In all types

    of transformer construction, the central iron core is

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    8

    constructed from of a highly permeable material made from thin

    silicon steel laminations assembled together to provide the

    required magnetic path with the minimum of losses.

    The resistivity of the steel sheet itself is high reducing the

    eddy current losses by making the laminations very thin. These

    steel laminations vary in thicknesses from between 0.25 mm to

    0.5 mm and as steel is a conductor, the laminations are

    electrically insulated from each other by a very thin coating

    of insulating varnish or by the use of an oxide layer on the

    surface.

    Figure (7.6)

    7.4.1. Transformer construction of the core

    Generally, the name associated with the construction of

    a transformer is dependant upon how the primary and secondary

    windings are wound around the central laminated steel core.

    The two most common and basic designs of transformer

    construction are the Closed-core Transformer and the Shell-

    core Transformer. In the "closed-core" type (core form)

    transformer, the primary and secondary windings are wound

    outside and surround the core ring. In the "shell type" (shell

    form) transformer, the primary and secondary windings pass

    inside the steel magnetic circuit (core) which forms a shell

    around the windings as shown below.

    Figure (7.7)

    In both types of transformer core design, the magnetic flux

    linking the primary and secondary windings travels entirely

    within the core with no loss of magnetic flux through air.

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    9

    In the core type transformer construction, one half of each

    winding is wrapped around each leg (or limb) of the

    transformers magnetic circuit as shown above.

    The coils are not arranged with the primary winding on one leg

    and the secondary on the other but instead half of the primary

    winding and half of the secondary winding are placed one over

    the other concentrically on each leg in order to increase

    magnetic coupling allowing practically all of the magnetic

    lines of force go through both the primary and secondary

    windings at the same time.

    However, with this type of transformer construction, a small

    percentage of the magnetic lines of force flow outside of the

    core, and this is called "leakage flux".

    Shell type transformer cores overcome this leakage flux as

    both the primary and secondary windings are wound on the same

    centre leg or limb which has twice the cross-sectional area of

    the two outer limbs. The advantage here is that the magnetic

    flux has two closed magnetic paths to flow around external to

    the coils on both left and right hand sides before returning

    back to the central coils. This means that the magnetic flux

    circulating around the outer limbs of this type of transformer

    construction is equal to /2.

    As the magnetic flux has a closed path around the coils, this

    has the advantage of decreasing core losses and increasing

    overall efficiency.

    7.4.2. Transformer laminations

    But you may be wondering as to how the primary and

    secondary windings are wound around these laminated iron or

    steel cores for this types of transformer constructions. The

    coils are firstly wound on a former which has a cylindrical,

    rectangular or oval type cross section to suit the

    construction of the laminated core. In both the shell and core

    type transformer constructions, in order to mount the coil

    windings, the individual laminations are stamped or punched

    out from larger steel sheets and formed into strips of thin

    steel resembling the letters "E's", "L's", "U's" and "I's" as

    shown below.

    7.4.3. Transformer core types

    These lamination stampings when connected together form

    the required core shape. For example, two "E" stampings plus

    two end closing "I" stampings to give an E-I core forming one

    element of a standard shell-type transformer core. These

    individual laminations are tightly butted together during the

    transformers construction to reduce the reluctance of the air

    gap at the joints producing a highly saturated magnetic flux

    density. Transformer core laminations are usually stacked

    alternately to each other to produce an overlapping joint with

    more lamination pairs being added to make up the correct core

    thickness. This alternate stacking of the laminations also

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    10

    gives the transformer the advantage of reduced flux leakage

    and iron losses. E-I core laminated transformer construction

    is mostly used in isolation transformers, step-up and step-

    down transformers as well as auto transformers.

    Figure (7.8)

    7.4.4. Transformer winding arrangements

    Transformer windings form another important part of a

    transformer construction, because they are the main current-

    carrying conductors wound around the laminated sections of the

    core. In a single-phase two winding transformer, two windings

    would be present as shown.

    The one which is connected to the voltage source and creates

    the magnetic flux called the primary winding, and the second

    winding called the secondary in which a voltage is induced as

    a result of mutual induction. If the secondary voltage is less

    than that of the primary the transformer is called a "step-

    down transformer", and if the secondary voltage is greater

    then it is called a "step-up transformer".

    The type of wire used as the main current carrying conductor

    in a transformer winding is either copper or aluminum. While

    aluminum wire is lighter and generally less expensive than

    copper wire, a larger cross sectional area of conductor must

    be used to carry the same amount of current as with copper so

    it is used mainly in larger power transformer applications.

    Small kVA power and voltage transformers used in low voltage

    electrical and electronic circuits tend to use copper

    conductors as these have a higher mechanical strength and

    smaller conductor size than equivalent aluminum types. The

    downside is that when complete with their core, these

    transformers are much heavier.

    Transformer windings and coils can be broadly classified in to

    concentric coils and sandwiched coils. In core-type

    transformer construction, the windings are usually arranged

    concentrically around the core limb as shown above with the

    higher voltage primary winding being wound over the lower

    voltage secondary winding. Sandwiched or "pancake" coils

    consist of flat conductors wound in a spiral form and are so

    named due to the arrangement of conductors into discs.

    Alternate discs are made to spiral from outside towards the

    centre in an interleaved arrangement with individual coils

    being stacked together and separated by insulating materials

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    11

    such as paper of plastic sheet. Sandwich coils and windings

    are more common with shell type core construction.

    Helical Windings also known as screw windings are another very

    common cylindrical coil arrangement used in low voltage high

    current transformer applications. The windings are made up of

    large cross sectional rectangular conductors wound on its side

    with the insulated strands wound in parallel continuously

    along the length of the cylinder, with suitable spacers

    inserted between adjacent turns or discs to minimize

    circulating currents between the parallel strands.

    The coil progresses outwards as a helix resembling that of a

    corkscrew. The insulation used to prevent the conductors

    shorting together in a transformer is usually a thin layer of

    varnish or enamel in air cooled transformers. This thin

    varnish or enamel paint is painted onto the wire before it is

    wound around the core. In larger power and distribution

    transformers the conductors are insulated from each other

    using oil impregnated paper or cloth.

    The whole core and windings is immersed and sealed in a

    protective tank containing transformer oil. The transformer

    oil acts as an insulator and also as a coolant.

    7.5. Transformer dot orientation

    We can not just simply take a laminated core and wrap one

    of the coil configurations around it. We could but we may find

    that the secondary voltage and current may be out-of-phase

    with that of the primary voltage and current. The two coil

    windings do have a distinct orientation of one with respect to

    the other. Either coil could be wound around the core

    clockwise or anticlockwise so to keep track of their relative

    orientations "dots" are used to identify a given end of each

    winding. This method of identifying the orientation or

    direction of a transformers windings is called the "dot

    convention". Then a transformer windings are wound so that the

    correct phase relations exist between the winding voltages

    with the transformers polarity being defined as the relative

    polarity of the secondary voltage with respect to the primary

    voltage as shown below.

    Figure (7.9)

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    12

    The first transformer shows its two "dots" side by side on the

    two windings. The current leaving the secondary dot is "in-

    phase" with the current entering the primary side dot. Thus

    the polarities of the voltages at the dotted ends are also in-

    phase so when the voltage is positive at the dotted end of the

    primary coil, the voltage across the secondary coil is also

    positive at the dotted end. The second transformer shows the

    two dots at opposite ends of the windings which means that the

    transformers primary and secondary coil windings are wound in

    opposite directions. The result of this is that the current

    leaving the secondary dot is 180o "out-of-phase" with the

    current entering the primary dot. So the polarities of the

    voltages at the dotted ends are also out-of-phase so when the

    voltage is positive at the dotted end of the primary coil, the

    voltage across the corresponding secondary coil will be

    negative. Then the construction of a transformer can be such

    that the secondary voltage may be either "in-phase" or "out-

    of-phase" with respect to the primary voltage.

    In transformers which have a number of different secondary

    windings, each of which is electrically isolated from each

    other it is important to know the dot polarity of the

    secondary windings so that they can be connected together in

    series-aiding (secondary voltage is summed) or series-opposing

    (the secondary voltage is the difference) configurations.

    The ability to adjust the turns ratio of a transformer is

    often desirable to compensate for the effects of variations in

    the primary supply voltage, the regulation of the transformer

    or varying load conditions. Voltage control of the transformer

    is generally performed by changing the turns ratio and

    therefore its voltage ratio whereby a part of the primary

    winding on the high voltage side is tapped out allowing for

    easy adjustment.

    The tapping is preferred on the high voltage side as the volts

    per turn are lower than the low voltage secondary side.

    7.6. Transformer primary tap changes

    Figure (7.10)

    In this simple example, the primary tap changes are calculated

    for a supply voltage change of 5%, but any value can be

    chosen. Some transformers may have two or more primary or two

    or more secondary windings for use in different applications

    providing different voltages from a single core.

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    13

    7.7. Transformer core losses

    The ability of iron or steel to carry magnetic flux is

    much greater than it is in air, and this ability to allow

    magnetic flux to flow is called permeability. Most transformer

    cores are constructed from low carbon steels which can have

    permeabilities in the order of 1500 compared with just 1.0 for

    air. This means that a steel laminated core can carry a

    magnetic flux 1500 times better than that of air. However,

    when a magnetic flux flows in a transformers steel core, two

    types of losses occur in the steel. One termed "eddy current

    losses" and the other termed "hysteresis losses".

    7.7.1. Hysteresis losses

    Transformer Hysteresis Losses are caused because of the

    friction of the molecules against the flow of the magnetic

    lines of force required to magnetise the core, which are

    constantly changing in value and direction first in one

    direction and then the other due to the influence of the

    sinusoidal supply voltage. This molecular friction causes heat

    to be developed which represents an energy loss to the

    transformer. Excessive heat loss can overtime shorten the life

    of the insulating materials used in the manufacture of the

    windings and structures. Therefore, cooling of a transformer

    is important. Also, transformers are designed to operate at a

    particular supply frequency. Lowering the frequency of the

    supply will result in increased hysteresis and higher

    temperature in the iron core. So reducing the supply frequency

    from 60 Hertz to 50 Hertz will raise the amount of hysteresis

    present, decreased the VA capacity of the transformer.

    7.7.2. Eddy current losses

    Transformer Eddy Current Losses on the other hand are caused

    by the flow of circulating currents induced into the steel

    caused by the flow of the magnetic flux around the core. These

    circulating currents are generated because to the magnetic

    flux the core is acting like a single loop of wire.

    Since the iron core is a good conductor, the eddy currents

    induced by a solid iron core will be large. Eddy currents do

    not contribute anything towards the usefulness of the

    transformer but instead they oppose the flow of the induced

    current by acting like a negative force generating resistive

    heating and power loss within the core.

    Figure (7.11) laminating the Iron Core

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    14

    Eddy current losses within a transformer core cannot be

    eliminated completely, but they can be greatly reduced and

    controlled by reducing the thickness of the steel core.

    Instead of having one big solid iron core as the magnetic core

    material of the transformer or coil, the magnetic path is

    split up into many thin pressed steel shapes called

    "laminations".

    The laminations used in a transformer construction are very

    thin strips of insulated metal joined together to produce a

    solid but laminated core as we saw above. These laminations

    are insulated from each other by a coat of varnish or paper to

    increase the effective resistivity of the core thereby

    increasing the overall resistance to limit the flow of the

    eddy currents.

    The result of all this insulation is that the unwanted induced

    eddy current power-loss in the core is greatly reduced, and it

    is for this reason why the magnetic iron circuit of every

    transformer and other electro-magnetic machines are all

    laminated. Using laminations in a transformer construction

    reduces eddy current losses. The losses of energy, which

    appears as heat due both to hysteresis and to eddy currents in

    the magnetic path, is known commonly as "transformer core

    losses".

    Since these losses occur in all magnetic materials as a result

    of alternating magnetic fields. Transformer core losses are

    always present in a transformer whenever the primary is

    energized, even if no load is connected to the secondary

    winding. Also these hysteresis and the eddy current losses are

    sometimes referred to as "transformer iron losses", as the

    magnetic flux causing these losses is constant at all loads.

    7.7.3. Copper losses

    But there is also another type of energy loss associated

    with transformers called "copper losses". Transformer Copper

    Losses are mainly due to the electrical resistance of the

    primary and secondary windings.

    Most transformer coils are made from copper wire which has

    resistance in Ohms, (). This resistance opposes the

    magnetizing currents flowing through them. When a load is

    connected to the transformers secondary winding, large

    electrical currents flow in both the primary and the secondary

    windings, electrical energy and power (or the I2 R) losses

    occur as heat.

    Generally copper losses vary with the load current, being

    almost zero at no-load, and at a maximum at full-load when

    current flow is at maximum. Transformers with high voltage and

    current ratings require conductors of large cross-section to

    help minimize their copper losses.

    Then we can define an ideal transformer as having:

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    15

    1. No Hysteresis loops or Hysteresis losses 0

    2. Infinite Resistivity of core material giving zero Eddy

    current losses 0

    3. Zero winding resistance giving zero I2R copper losses 0

    7.8. Transformer loading

    In the previous transformer section, we have assumed that

    the transformer is ideal, that is one in which there are no

    core losses or copper losses in the windings.

    However, in real transformers there will always be losses

    associated with the transformer loading as the transformer is

    put "on-load". But what do we mean by:

    7.8.1. Transformer at No-Load

    Well first let's look at when the transformer is in a

    "no-load" condition that is without a secondary current

    flowing.

    A transformer is said to be on "no-load" when its secondary

    side winding is open circuited, in other words, the

    transformer loading is zero.

    When an AC sinusoidal supply is connected to the primary

    winding of a transformer, a small current, IOPEN will flow

    through the primary coil winding due to the presence of the

    primary supply voltage. With the secondary circuit open,

    nothing connected a back EMF along with the primary winding

    resistance acts to limit the flow of this primary current.

    Obviously, this no-load primary current (Io) must be

    sufficient to maintain enough magnetic field to produce the

    required back emf. Consider the circuit below.

    Figure (7.12) transformer "No-load"

    The ammeter above will indicate a small current flowing

    through the primary winding even though the secondary circuit

    is open circuited. This no-load primary current is made up of

    the following two components:

    1. An in-phase current, IE which supplies the core losses (eddy current and hysteresis).

    2. A current, IM at 90o to the voltage which sets up the magnetic flux.

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    16

    Figure (7.13)

    Note that this no-load primary current, Io is very small

    compared to the transformers normal full-load current. Also

    due to the iron losses present in the core as well as a small

    amount of copper losses in the primary winding, Io does not

    lag behind the supply voltage, Vp by exactly 90o, (cos = 0),

    there will be some small phase angle difference.

    Example

    A single phase transformer has an energy component, IE of 2

    Amps and a magnetizing component, IM of 5 Amps. Calculate the

    no-load current, Io and resulting power factor.

    7.8.2. Transformer On-Load

    When an electrical load is connected to the secondary winding

    of a transformer and the transformer loading is therefore

    greater than zero, current flows in the secondary winding due

    to the induced secondary voltage, set up by the magnetic flux

    created in the core from the primary current.

    This secondary current, IS which is determined by the

    characteristics of the load, creates a secondary magnetic

    field, S in the transformer core which flows in the exact

    opposite direction to the main primary field, P.

    These two magnetic fields oppose each other resulting in a

    combined magnetic field of less magnetic strength than the

    single field produced by the primary winding alone when the

    secondary circuit was open circuited. This combined magnetic

    field reduces the back EMF of the primary winding causing the

    primary current, IP to increase slightly.

    The primary current continues to increase until the cores

    magnetic field is back at its original strength, and for a

    transformer to operate correctly, a balanced condition must

    always exist between the primary and secondary magnetic

    fields. This results in the power to be balanced and the same

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    17

    on both the primary and secondary sides. Consider the circuit

    below.

    Figure (7.14) Transformer "On-load"

    We know that the turns ratio of a transformer states that the

    total induced voltage in each winding is proportional to the

    number of turns in that winding and also that the power output

    and power input of a transformer is equal to the volts times

    amperes, (V x I). Therefore:

    But we also know previously that the voltage ratio of a

    transformer is equal to the turns ratio of a transformer as:

    "voltage ratio = turns ratio". Then the relationship between

    the voltage, current and number of turns in a transformer can

    be linked together and is therefore given as:

    Where:

    NP/NS = VP/VS represents the voltage ratio

    NP/NS = IS/IP represents the current ratio

    Note that the current is inversely proportional to both the

    voltage and the number of turns. This means that with a

    transformer loading on the secondary winding, in order to

    maintain a balanced power level across the transformers

    windings, if the voltage is stepped up, the current must be

    stepped down and vice versa. In other words, higher voltage lower current or lower voltage higher current. The total current drawn from the supply by the primary winding is the

    vector sum of the no-load current, Io and the additional

    supply current, I1 as a result of the secondary transformer

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    18

    loading and which lags behind the supply voltage by an angle

    of . We can show this relationship as a phasor diagram.

    Figure (7.15) Transformer Loading Current

    If we are given currents, IS and Io, we can calculate the

    primary current, IP by the following methods.

    Figure (7.16)

    Example

    A single phase transformer has 1000 turns on its primary

    winding and 200 turns on its secondary winding. The

    transformers "no-load" current taken from the supply is 3 Amps

    at a power factor of 0.2 lagging. Calculate the primary

    winding current, IP and its corresponding power factor, when

    the secondary current supplying a transformer loading is 280

    Amperes at 0.8 lagging.

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    19

    You may have noticed that the phase angle of the primary

    current, P is very nearly the same as that of the secondary

    current phase angle, S. This is due to the fact that the no-

    load current of 3 amperes is very small compared to the larger

    56 amperes drawn by the primary winding from the supply.

    Actual real life, transformer windings have impedances of XL

    and R.

    These impedances need to be taken into account when drawing

    the phasor diagrams as these internal impedances cause voltage

    drops to occur within the transformers windings.

    The internal impedances are due to the resistance of the

    windings and an inductance drop called the leakage reactance

    resulting from the leakage flux.

    These internal impedances are given as:

    Figure (7.17)

    So the primary and secondary windings of a transformer possess

    both resistance and reactance. Sometimes, it can be more

    convenient if all these impedances are on the same side of the

    transformer to make the calculations easier.

    It is possible to move the primary impedances to the secondary

    side or the secondary impedances to the primary side. The

    combined values of R and L impedances are called "Referred

    Impedances" or "Referred Values". The object here is to group

    together the impedances within the transformer and have just

    one value of R and XL in our calculations as shown.

    Figure (7.18) Combining Transformer Impedances

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    20

    In order to move a resistance from one side of the transformer

    to the other, we must first multiply them by the square of the

    turns ratio, (Turns Ratio2) in our calculations.

    So for example, to move a resistance of 2 from one side to

    the other in a transformer that has a turns ratio of 8:1 will

    have a new resistive value of: 2 x 82 = 128 's.

    Note that if you move a resistance from a higher voltage side

    the new resistance value will increase and if you move the

    resistance from a lower voltage side its new value will

    decrease. This applies to the load resistance and reactance as

    well.

    7.9. Three phase ideal transformer

    Since three-phase is used so often for power distribution

    systems, it makes sense that we would need three-phase

    transformers to be able to step voltages up or down. This is

    only partially true, as regular single-phase transformers can

    be ganged together to transform power between two three-phase

    systems in a variety of configurations, eliminating the

    requirement for a special three-phase transformer. However,

    special three-phase transformers are built for those tasks,

    and are able to perform with less material requirement, less

    size, and less weight than their modular counterparts. A

    three-phase transformer is made of three sets of primary and

    secondary windings, each set wound around one leg of an iron

    core assembly. Essentially it looks like three single-phase

    transformers sharing a joined core as in Figure below.

    Figure (7.19)

    Three phase transformer core has three sets of windings.

    Those sets of primary and secondary windings will be connected

    in either or Y configurations to form a complete unit. The

    various combinations of ways that these windings can be

    connected together in will be the focus of this section.

    Whether the winding sets share a common core assembly or each

    winding pair is a separate transformer, the winding connection

    options are the same:

    Primary - Secondary

    Y - Y

    Y

    Y

    -

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    21

    The reasons for choosing a Y or configuration for

    transformer winding connections are the same as for any other

    three-phase application: Y connections provide the opportunity

    for multiple voltages, while connections enjoy a higher

    level of reliability (if one winding fails open, the other two

    can still maintain full line voltages to the load).

    Probably the most important aspect of connecting three sets of

    primary and secondary windings together to form a three-phase

    transformer bank is paying attention to proper winding phasing

    (the dots used to denote polarity of windings).

    Remember the proper phase relationships between the phase

    windings of and Y: (Figure below)

    Figure (7.20)

    (Y) The center point of the Y must tie either all the - or

    all the + winding points together.

    () The winding polarities must stack together in a

    complementary manner (+ to -).

    Getting this phasing correct when the windings aren't shown in

    regular Y or configuration can be tricky. Let me illustrate,

    starting with Figure below.

    Figure (7.21)

    Inputs A1, A2, A3 may be wired either or Y, as may

    outputs B1, B2, B3. Three individual transformers are to be

    connected together to transform power from one three-phase

    system to another. First, I'll show the wiring connections for

    a Y-Y configuration: Figure below

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    22

    Figure (7.22)

    Phase wiring for Y-Y transformer.

    Note in Figure above how all the winding ends marked with dots

    are connected to their respective phases A, B, and C, while

    the non-dot ends are connected together to form the centers of

    each Y. Having both primary and secondary winding sets

    connected in Y formations allows for the use of neutral

    conductors (N1 and N2) in each power system.

    Now, we'll take a look at a Y- configuration: (Figure below)

    Figure (7.23)

    Phase wiring for Y- transformer.

    Note how the secondary windings (bottom set, Figure above) are

    connected in a chain, the dot side of one winding connected

    to the non-dot side of the next, forming the loop. At

    every connection point between pairs of windings, a connection

    is made to a line of the second power system (A, B, and C).

    Now, let's examine a -Y system in Figure below.

    Figure (7.24)

    Phase wiring for -Y transformer.

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    23

    Such a configuration (Figure above) would allow for the

    provision of multiple voltages (line-to-line or line-to-

    neutral) in the second power system, from a source power

    system having no neutral. And finally, we turn to the -

    configuration, (Figure below)

    Figure (7.25)

    Phase wiring for - transformer.

    When there is no need for a neutral conductor in the secondary

    power system, - connection schemes (Figure above) are

    preferred because of the inherent reliability of the

    configuration.

    Three phase transformer configurations and calculations

    In a delta connected group of transformers, the line voltage,

    VL is equal to the phase voltage, VL = VPH. But the current in

    each phase winding is given as: IL / 3 (or IL = IPH x 3) where

    IL is the line current.

    In a star connected group of transformers, the line voltage, VL

    is equal to 3 the phase voltage, VL = 3VPH. But the current

    in each phase winding is given as: IPH = IL where IL is the line

    current.

    Example of Delta-Delta

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    24

    Example of Delta-Star

    Example of Star-Star

    Example of Star-Delta

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    25

    TR 1:5 1:n

    Connection Line Voltage Line Current

    Primary Secondary Primary Secondary

    -

    EL

    n*EL

    IL

    ILn

    - 3*n*EL IL3*n

    - n*EL ILn

    - n*EL3 3*ILn

    -

    480

    5*480=2400

    100

    1005=20

    - 3*480*5=4156 1003*5=11.55

    - 5*480=2400 1005=20

    - 5*4803=1386 3*1005=34.64

    Example 1

    150 KVA Delta-Star transformer bank, 480 v primary, 208/120 v

    secondary. Calculate, TR, ILP, ILS

    Example 2

    3 Star-Delta transformer, ELP=6600, ILP=10 A, TR 12:1,

    calculate ELS, EphP, and ILS

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    26

    7.10. Three phase transformer construction

    Figure (7.26)

    The three-limb core-type three-phase transformer is the most

    common method of three-phase transformer construction allowing

    the phases to be magnetically linked. Flux of each limb uses

    the other two limbs for its return path with the three

    magnetic fluxes in the core generated by the line voltages

    differing in time-phase by 120 degrees. Thus the flux in the

    core remains nearly sinusoidal, producing a sinusoidal

    secondary supply voltage.

    The shell-type five-limb type three-phase transformer

    construction is heavier and more expensive to build than the

    core-type. Five-limb cores are generally used for very large

    power transformers as they can be made with reduced height.

    Shell-type transformers core materials, electrical windings,

    steel enclosure and cooling are much the same as for the

    larger single-phase types.

    7.11. Equivalent circuit of transformer

    The performance of a transformer at no load and at load is

    influenced by mutual flux, the leakage fluxes, the winding

    resistances and the iron losses. For the purpose of

    performance evaluation, the effect of these is represented on

    an electrical circuit, in the form of resistances and

    reactances. Such an electrical circuit is called equivalent

    circuit.

    In this section, we will develop the equivalent circuit of a

    single-phase transformer in the following steps:

    (a) Equivalent circuit of an ideal transformer at no load

    (b) Equivalent circuit of an ideal transformer on load

    (c) Equivalent circuit at load

    (d) Equivalent circuit referred to primary side

    (e) Approximate equivalent circuit.

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    27

    7.11.1. Equivalent circuit of an ideal transformer at No

    Load

    Under certain conditions, the transformer can be treated as an

    ideal transformer. The assumptions necessary to treat it as an

    ideal transformer are :

    (a) Primary and secondary windings have zero resistance. This

    means that ohmic loss (I2R loss), and resistive voltage drops

    in windings are zero.

    (b) There is no leakage flux, i.e. the entire flux is mutual

    flux that links both the primary and secondary windings.

    (c) Permeability of the core is infinite this means that the

    magnetizing current needed for establishing the flux is zero.

    (d) Core loss (hysteresis as well as eddy current losses) are

    zero.

    We have earlier learnt that:

    (n is a constant, known as voltage transformation ratio or

    turns ratio).

    For an ideal transformer, V1 = E1 and E2 = V2.

    Even at no load, a transformer draws some active power from

    the source to provide the following losses in the core:

    (a) Eddy-current loss, and

    (b) Hysteresis loss.

    The current responsible for the active power is nearly in

    phase with V1 (applied voltage) and is known as core-loss

    current. A transformer when connected to supply, draws a

    current to produce the flux in the core. At no-load, this flux

    lags nearly by 90o behind the applied voltage V1. The

    magnetizing current, denoted by Im is in phase with the flux

    and thus, lags behind the applied voltage by nearly 90o.

    The phasor sum of the core loss component of current Ic and the

    magnetizing current Im is equal to the no-load current I0.

    Ic = I0 cos 0 and Im = I0 sin 0

    Core loss = P0 = V1 I0 (cos 0)

    Where 0 is the phase angle between V1 and I0, and, (cos 0) is the no load power factor.

    The phase relationship between applied voltage V1, no-load

    current I0, and its components Ic, Im is shown in Fig 7.27(a).

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    28

    Figure (7.27)

    In the form of equivalent circuit, this can be represented as

    Fig 7.27(b), in which Rc is a resistance representing core loss

    and Xm is an inductive reactance (called magnetizing

    reactance).

    Note that the current in the resistance is in phase with V1 and

    Xm being an inductive reactance, the current Im in this branch

    lags V1 by 90o as shown in the phasor diagram of Fig 7.27(a).

    (The representation in Fig 7.27, assumes that V1 = E1 (equal to

    and in opposition to V1).

    This implies that the primary winding resistance and leakage

    reactance are neglected.

    Similarly, in the secondary winding of transformer mutually

    induced emf is antiphase with V1 and its magnitude is

    proportional to the rate of change of flux and the number of

    secondary turns. (You will learn about the concept of leakage

    reactance when you study about the equivalent circuit at

    load).

    The equivalent circuit parameters Rc and Xm can also be

    expressed as conductance and susceptance Gc, Bm such that

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    29

    Example

    At no-load a transformer has a no-load loss of 50 W, draws a

    current of 2A (RMS) and has an applied voltage of 230V (RMS).

    Determine:

    (i) no-load power factor, (ii) core loss current, and (iii) magnetizing current. Also, calculate the no-load circuit parameter (Rc, Xm) of the transformer.

    Solution

    Pc = 40 W, Io = 2 A, E1 = 230 V

    Pc = V1 Io coso

    Magnetizing current,

    Im = I0 sino

    = 2 sin(83.76o)

    = 1.988 A

    Core-loss current,

    Ic = Io coso

    = 2 0.108

    = 0.216 A

    This equivalent circuit is shown below.

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    30

    7.11.2. Equivalent circuit of an ideal transformer On Load

    Under certain conditions the transformer can be

    treated as an ideal transformer. The idealizing assumptions

    are listed below

    (a) Both primary and secondary windings have zero resistance.

    This means, no ohmic power loss and no resistive voltage

    drop.

    (b) No leakage flux, i.e. all the flux produced is confined to

    the core and links both the windings

    (c) Infinite permeability of the core. This means no zero

    magnetizing current is needed to establish the requisite

    amount of flux in the core, i.e. Im = 0.

    (d) Core-loss (hysteresis as well as eddy-current loss) is

    zero, i.e. Ic = 0.

    Assumptions (a), (b) and (d) mean that copper losses, and

    iron losses being zero, the efficiency of the transformer

    is 100%. Since Im = Ic = 0, Io = 0.

    Figure (7.28)

    As per earlier derived equation

    where, V1 is supply voltage and V2 is voltage across load

    terminals.

    When load is applied, let the impedance of load be ZL, as shown

    in Fig (7.28) Sinusoidal current i2 flows through the

    secondary.

    Therefore, secondary winding creates an mmf F2 = N2i2 which

    opposes the flux .

    But mutual flux is invariant with respect to load (otherwise

    V1 = e1 balance is disturbed).

    As a result, the primary winding starts drawing a current i1

    from the source so as to create mmf F1 = N1i1 which at all

    times cancels out the load-caused mmf N2i2 so that is

    maintained constant independent of the magnitude of the load

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    31

    current which flows in the secondary winding. This implies

    that for higher load, more power will be drawn from the supply

    (Instantaneous power into primary) = (Instantaneous power out

    of secondary)

    In terms of rms values,

    i.e. VA output = VA input, i.e. V1I1 = V2I2

    The circuit representation of Fig (7.28), can be simplified by

    referring the load impedance and secondary current to the

    primary side. From Fig (7.28), we see that

    V2 = I2ZL

    Where

    is said to be the load impedance referred to the primary side.

    From V2 = I2 ZL we can also easily obtain V2 = I2 ZL

    Where

    is secondary terminal voltage referred to primary side, and

    is secondary current referred to primary side.

    In the ideal transformer, I1 = I2 and V1 = V2.

    7.11.3. Equivalent circuit of a real transformer

    In real conditions, in addition to the mutual flux which links

    both the primary and secondary windings transformer, has a

    component of flux, which links either the primary winding or

    the secondary, but not both.

    This component is called leakage flux. The flux which links

    only with primary is called primary leakage flux, and the flux

    which links only with secondary is called secondary leakage

    flux. Fig 7.28 shows schematically the mutual and the leakage

    flux.

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    32

    From our knowledge of magnetic circuits, we know that a flux

    lining with a winding is the cause of inductance of the

    winding (Inductance = Flux linkage per ampere).

    Since in a transformer the flux is alternating, its flux

    linkage gives rise to an induced voltage in the winding. Thus,

    primary leakage flux (which is proportional to I1) causes an

    induced voltage, which acts as a voltage drop.

    Similarly for the secondary leakage flux. The effect of these

    induced EMFs are, therefore, represented as inductive leakage

    reactances Xl1, Xl2.

    Xl1 and Xl2 are called leakage reactances of the primary and

    secondary respectively. These are also denoted as X1, X2.

    The windings of the transformer have resistance R1, R2. These

    resistances cause a voltage drop I1R1 and I2R2, as also ohmic

    loss I12R1 and I2

    2R2.

    To sum up, in a Real Transformer,

    (a) Both the primary and secondary windings possesses resistance. As a result, the value of actual impressed

    voltage across the transformer is the voltage V1 less the

    drop across the resistance R1. Moreover, the copper loss in

    the primary winding is I21R1 and in the secondary winding

    I22R1.

    (b) A Real Transformer has some leakage flux, as shown in the

    Fig 7.28 These fluxes, as discussed earlier, lead to self-

    reactances Xl1 and Xl2 for the two windings respectively.

    (c) The magnetizing current cannot be zero. Its value is

    determined by the mutual flux m. The mutual flux also

    determines core-loss taking place in the iron parts of the

    transformer. The value of Io does not depend on load and

    hence the iron-loss or core-loss is constant which is not

    zero.

    Considering the effects of resistances and leakage reactances,

    a transformer can be visualized as shown in Fig 7.29.

    Figure (7.29) Representation of transformer showing leakage

    reactances

    In the form of equivalent circuit, this can be represented as

    in Fig 7.30.

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    33

    Figure (7.30) Exact equivalent circuit of real transformer

    The use of this equivalent circuit is difficult and

    calculations involved are laborious. For most practical

    purposes (like calculations of voltage regulation and

    efficiency) we need only a simplified form of equivalent

    circuit. We will now proceed to first obtain a simplified

    equivalent circuit and then to obtain an approximate

    equivalent circuit.

    Equivalent Circuit Referred to Primary Side

    We will now refer the impedance R2 + jXl2 to the primary side

    i.e. to the left hand side of the ideal transformer. We have

    seen earlier that a load impedance ZL can be referred to

    primary side as Z'L, where

    Similarly Z2 = R2 + jXl2 can be referred to the primary side as

    where Z'2 is said to be the secondary winding impedance

    referred to the primary side.

    Eq. (4) can be re-written as

    Equating real and imaginary parts

    R'2 is the secondary winding resistance referred to primary,

    and X'l2 is the secondary winding leakage reactance referred to

    primary side.

    Fig (7.30) can now be modified (i.e. referring the secondary

    resistance and reactance to the primary side) to get the

    equivalent circuit shown in Fig (7.31)

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    34

    Figure (7.31) Exact Circuit with secondary parameters referred

    to primary side

    The secondary terminal voltage V2 and secondary current I2 can

    also be referred to the primary side using the relations.

    These referred quantities V'2 and I'2 are also marked in Fig

    (7.31)

    7.11.4. Approximate equivalent circuit of transformer

    Transformers which are used at a constant power frequency (say

    50 Hz), can have very simplified approximate equivalent

    circuits, without having a substantial effect on the

    performance evaluation (efficiency and voltage regulation).

    It should be borne in mind that higher the VA or KVA rating

    of the transformers, better are the approximation-based

    evaluation results.

    It is assumed that V1 ~ E1 (V1 is approximately equal to E1)

    even under conditions of load.

    This assumption is justified because the values of winding

    resistance and leakage reactances are very small. Therefore,

    the exciting current drawn by the parallel combination of

    conductance Gc and susceptance Bm would not be affected

    significantly by shifting it to the input terminals. With this

    change, the equivalent circuit becomes as shown in Fig (7.32).

    Figure (7.32) Equivalent circuit referred to primary side

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    35

    Denoting

    R1 + R'2 = R'eq

    and

    Xl2 + X'l2 = X'eq

    The equivalent circuit becomes as shown in Fig (7.33) R'eq, X'eq

    are called the equivalent resistance and equivalent reactance

    referred to primary side.

    Figure (7.33) Approximate Equivalent Circuit

    If only voltage regulation is to be calculated even the

    excitation branch can be neglected and the equivalent circuit

    becomes as shown in Fig (7.34).

    Figure (7.34) Most simplified form of approximate equivalent

    circuit

    7.12. Losses and efficiency of transformer

    A transformer doesn't contain any rotating part so it is

    free from friction and windage losses. In transformer the

    losses occur in iron parts as well as in copper coils. In iron

    core the losses are sum of hysteresis and eddy current losses.

    The hysteresis losses are Ph fBxmax and eddy current loss is

    equal to Pe a f2Bmax.

    Where f is frequency Bmax is maximum flux density.

    We know that the maximum flux density is directly proportional

    to applied voltage so, if the applied voltage is constant then

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    36

    the flux density is constant and the hysterises losses are

    proportional to f and eddy current losses are proportional to

    f2.

    7.12.1 Iron losses or core losses

    To minimize hysteresis loss in transformer, we use Cold Rolled

    Grain Oriented (CRGO) silicon steel to build up the iron core.

    Eddy current loss

    When the primary winding variable flux links with iron core

    then it induces some EMF on the surface of core. The

    magnitude of EMF is different at various points in core. So,

    there is current between different points in Iron Core having

    unequal potential.

    These currents are known at eddy currents. I2R loss in iron

    core is known as eddy current loss.

    These losses depend on thickness of core. To minimize the

    eddy current losses we use the Iron Core which is made of

    laminated sheet stampings. The thickness of stamping is

    around 0.5 mm.

    Determination of iron or core losses

    Practically we can determine the iron losses by performing

    the open circuit test.

    Open circuit test

    We perform open circuit test in low voltage winding in

    transformer keeping the high voltage winding open.

    The circuit is connected as shown in Fig (7.35). The

    instruments are connected on the LV side. The advantage of

    performing the test from LV side is that the test can be

    performed at rated voltage.

    When we apply rated voltage then watt meter shows iron losses

    [There is some copper loss but this is negligible when

    compared to iron loss]. The ammeter shows no load current I0

    which is very small [2-5 % of rated current]. Thus, the drops

    in R1 and Xl1 can be neglected.

    Figure (7.35) Open Circuit Test

    We have

    Wo = iron loss

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    37

    Io = no load current

    Under no load conditions the PF is very low (near to 0) in

    lagging region.

    By using the above data we can draw the equivalent parameter

    shown in Fig (7.36).

    Figure (7.36) No Load equivalent circuit from Open Circuit

    test

    Example

    At no load test, a transformer draws a current of 0.2 Ampere

    lagging behind the applied voltage by 80o, when the low

    voltage winding of the transformer is connected to a 500 V

    source. Calculate:

    (a) iron loss and

    (b) components of the no load current.

    Solution

    We have V1 = 500 V, Io = 0.2 A and o = 80o

    cos80o = 0.1736

    PF = cosf ~ 0.174 lagging

    (a) Iron loss = V1Iocos = 500 0.2 0.174 = 17.4 watts

    (b) Components of no load current

    Ic = Iocos = 0.0348 A

    Im = Io sin = 0.197 A or Im = I2o I

    2c = 0.197

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    38

    7.12.2. Copper losses

    In a transformer the primary and secondary winding

    currents increase with increases in load. Due to these

    currents there is some I2R losses. These are known as copper

    losses or ohmic losses. The total I2R loss in both windings at

    rated or full load current is equal to I12R1+I2

    2R2

    [assuming I'1 = I1 , i.e. shunt branch neglected].

    = I12Ro1

    Similarly, it can be shown that

    Copper loss = I22Ro2

    Here I1 and I2 are primary and secondary current. R1 is primary

    winding resistance and R2 is secondary winding resistance.

    R01 is total resistance of winding referred to primary

    Ro2 is total resistance of windings referred to secondary.

    By performing short circuit test we find out copper loss

    experimentally.

    7.12.3. Short circuit test

    Its an indirect method to find out the copper losses. To

    perform this test, we apply a reduced voltage to the primary

    winding through instruments keeping LV winding short

    circuited. The connections are shown in Figure (7.37a).

    We need to apply only 5-10% of rated voltage to primary to

    circulated rated current in the primary and secondary winding.

    The applied voltage is adjusted so that the ammeter shows

    rated current of the winding.

    Under this condition, the watt-meter reading shows the copper

    losses of the transformer. Because of low value of applied

    voltage, iron losses, are very small and can be neglected.

    As applied voltage is very small, small voltage across the

    excitation branch produces very small percentage of exciting

    current in comparison to its full load current and can

    therefore, be safely ignored. As a result, equivalent circuit

    with secondary short circuited can be represented as Fig

    (7.37b).

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    39

    Figure (7.37)

    At a rated current watt meter shows full load copper loss. We

    have:

    Vs = applied voltage

    Is = rated current

    Ws = copper loss

    So we calculate equivalent reactance:

    These Req and Xeq are equivalent resistance and reactance of

    both windings referred in HV side. These are known as

    equivalent circuit resistance and reactance.

    7.12.4. Efficiency of single phase transformer

    Generally we define the efficiency of any machine as a

    ratio of output power to the input power, i.e.

    7.13. Current transformer

    The Current Transformer (C.T.), is a type of "instrument

    transformer" that is designed to produce an alternating

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    40

    current in its secondary winding which is proportional to the

    current being measured in its primary. Current transformers

    reduce high voltage currents to a much lower value and provide

    a convenient way of safely monitoring the actual electrical

    current flowing in an AC transmission line using a standard

    ammeter. The principal of operation of a current transformer

    is no different from that of an ordinary transformer.

    Figure (7.38)

    Typical Current Transformer Unlike the voltage or power

    transformer looked at previously, the current transformer

    consists of only one or very few turns as its primary winding.

    This primary winding can be of either a single flat turn, a

    coil of heavy duty wire wrapped around the core or just a

    conductor or bus bar placed through a central hole as shown.

    Due to this type of arrangement, the current transformer is

    often referred too as a "series transformer" as the primary

    winding, which never has more than a very few turns, is in

    series with the current carrying conductor.

    The secondary winding may have a large number of coil turns

    wound on a laminated core of low-loss magnetic material which

    has a large cross-sectional area so that the magnetic flux

    density is low using much smaller cross-sectional area wire,

    depending upon how much the current must be stepped down. This

    secondary winding is usually rated at a standard 1 Ampere or 5

    Amperes.

    There are three basic types of current transformers: "wound",

    "toroidal" and "bar".

    Wound current transformers

    The transformers primary winding is physically connected in

    series with the conductor that carries the measured current

    flowing in the circuit. The magnitude of the secondary

    current is dependent on the turns ratio of the transformer.

    Toroidal current transformers

    These do not contain a primary winding. Instead, the line

    that carries the current flowing in the network is threaded

    through a window or hole in the toroidal transformer. Some

    current transformers have a "split core" which allows it to

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    41

    be opened, installed, and closed, without disconnecting the

    circuit to which they are attached.

    Bar-type current transformers

    This type of current transformer uses the actual cable or

    bus-bar of the main circuit as the primary winding, which is

    equivalent to a single turn. They are fully insulated from

    the high operating voltage of the system and are usually

    bolted to the current carrying device.

    Current transformers can reduce or "step-down" current levels

    from thousands of amperes down to a standard output of a

    known ratio to either 5 Amps or 1 Amp for normal operation.

    Thus, small and accurate instruments and control devices can

    be used with CT's because they are insulated away from any

    high-voltage power lines. There are a variety of metering

    applications and uses for current transformers such as with

    wattmeter's, power factor meters, watt-hour meters,

    protective relays, or as trip coils in magnetic circuit

    breakers, or MCB's.

    Figure (7.38) Current transformer

    Generally current transformers and ammeters are used together

    as a matched pair in which the design of the current

    transformer is such as to provide a maximum secondary current

    corresponding to a full-scale deflection on the ammeter.

    In most current transformers an approximate inverse turns

    ratio exists between the two currents in the primary and

    secondary windings. This is why calibration of the CT is

    generally for a specific type of ammeter. For most current

    transformers the primary and secondary currents are expressed

    as a ratio such as 100/5.

    This means that when 100 Amps is flowing in the primary

    winding it will result in 5 Amps flowing in the secondary

    winding. By increasing the number of secondary windings, N2,

    the secondary current can be made much smaller than the

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    42

    current in the primary circuit being measured. In other

    words, as N2 increases, I2 goes down by a proportional

    amount. We know from our tutorial on double wound

    transformers that its turns ratio is equal to:

    As the primary usually consists of one or two turns whilst

    the secondary can have several hundred turns, the ratio

    between the primary and secondary can be quite large. For

    example, assume that the current rating of the primary

    winding is 100A. The secondary winding has the standard

    rating of 5A. Then the ratio between the primary and the

    secondary currents is 100A-to-5A, or 20:1.

    In other words, the primary current is 20 times greater than

    the secondary current.

    It should be noted however, that a current transformer rated

    as 100/5 is not the same as one rated as 20/1 or subdivisions

    of 100/5. This is because the ratio of 100/5 expresses the

    "input/output current rating" and not the actual ratio of the

    primary to the secondary currents.

    Also note that the number of turns and the current in the

    primary and secondary windings are related by an inverse

    proportion. But relatively large changes in current

    transformers turns ratio can be achieved by modifying the

    primary turns through the CT's window where one primary turn

    is equal to one pass and more than one pass through the

    window results in the electrical ratio being modified.

    So for example, a current transformer with a relationship of

    say, 300/5 A can be converted to another of 150/5 A or even

    100/5 A by passing the main primary conductor through its

    interior window two or three times as shown.

    This allows a higher value current transformer to provide the

    maximum output current for the ammeter when used on smaller

    primary current lines.

    Figure (7.39) Current transformer primary Turns Ratio

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    43

    Example

    A bar-type current transformer which has 1 turn on its primary

    and 160 turns on its secondary is to be used with a standard

    range of ammeters that have an internal resistance of 0.2 .

    The ammeter is required to give a full scale deflection when

    the primary current is 800 Amps. Calculate the maximum

    secondary current and secondary voltage across the ammeter.

    We can see above that since the secondary of the current

    transformer is connected across the ammeter, which has a very

    small resistance, the voltage drop across the secondary

    winding is only 1.0 volts at full primary current.

    If the ammeter is removed, the secondary winding becomes open-

    circuited and the transformer acts as a step-up transformer

    resulting in a very high voltage equal to the ratio of:

    Vp(Ns/Np) being developed across the secondary winding.

    So for example, assume our current transformer from above is

    connected to a 480 volt three-phase power line.

    Therefore:

    This is why a current transformer should never be open

    circuited or operated with no-load attached when the main

    primary current is flowing.

    If the ammeter is to be removed, a short-circuit should be

    placed across the secondary terminals first. This is because

    when the secondary is open-circuited the iron core of the

    transformer operates at a high degree of saturation, which

    produces an abnormally large secondary voltage, and in our

    simple example above, this was calculated at 76.8 kV!. This

    high secondary voltage could damage the insulation or cause

    electric shock if the CT's terminals are accidentally touched.

    Handheld Current Transformers

    There are many specialized types of current transformers now

    available. A popular and portable type which can be used to

    measure circuit loading are called "clamp meters" as shown

    below.

    Clamp meters open and close around a current carrying

    conductor and measure its current by determining the magnetic

    field around it, providing a quick measurement reading usually

    on a digital display without disconnecting or opening the

    circuit.

    As well as the handheld clamp type CT, split core current

    transformers are available which has one end removable so that

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    44

    the load conductor or bus bar does not have to be disconnected

    to install it.

    These are available for measuring currents from 100 up to 5000

    amps, with square window sizes from 1" to over 12" (25 to 300

    mm).

    Then to summarize, the Current Transformer, (CT) is a type of

    instrument transformer used to convert a primary current into

    a secondary current through a magnetic medium. Its secondary

    winding then provides a much reduced current which can be used

    for detecting overcurrent, undercurrent, peak current, or

    average current conditions.

    A current transformers primary coil is always connected in

    series with the main conductor giving rise to it also being

    referred to as a series transformer. The nominal secondary

    current is rated at 1 A or 5 A for ease of measurement.

    Construction can be one single primary turn as in Toroidal,

    Donut, or Bar types, or a few wound primary turns, usually for

    low current ratios.

    Current transformers are intended to be used as proportional

    current devices. Therefore a current transformers secondary

    winding should never be operated into an open circuit, just as

    a voltage transformer should never be operated into a short

    circuit. Very high voltages will result from open circuiting

    the secondary circuit of an energized CT so their terminals

    must be short-circuited if the ammeter is to be removed or

    when a CT is not in use before powering up the system.

    7.14. Autotransformer

    Autotransformer Basics

    Unlike the previous voltage transformer which has two

    electrically isolated windings, the primary and the secondary.

    An Autotransformer has only one single voltage winding which

    is usually "tapped" at various points along it to provide a

    percentage of the primary voltage supply across its secondary

    load.

    The autotransformer has the usual magnetic core but only one

    winding, which is common to both the primary and secondary

    circuits.

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    45

    Therefore in an autotransformer the primary and secondary

    windings are both linked together electrically and

    magnetically. This type of transformer design is a lot cheaper

    but the main disadvantage of an autotransformer is that it

    does not have the primary/secondary winding isolation of a

    conventional double wound transformer.

    The section of winding designated as the primary part of the

    winding is connected to the AC power source with the secondary

    being part of this primary winding.

    An autotransformer can also be used to step the supply voltage

    up or down by reversing the connections. If the primary is the

    total winding and is connected to a supply, and the secondary

    circuit is connected across only a portion of the winding,

    then the secondary voltage is "stepped-down" as shown.

    Figure (7.40) Autotransformer design

    When the primary current IP is flowing through the single

    winding in the direction of the arrow as shown, the secondary

    current, IS, flows in the opposite direction. Therefore, in the

    portion of the winding that generates the secondary voltage, VS

    the current flowing out of the winding is the difference of IP

    and IS.

    The Autotransformer can also be constructed with more than one

    single tapping point. Autotransformers can be used to provide

    different voltage points along its winding or increase its

    supply voltage with respect to its supply voltage VP as shown.

    Figure (7.41) Autotransformer with multiple tapping points

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    46

    The standard method for marking an auto-transformer windings

    is to label it with capital (upper case) letters. So for

    example, A, B, Z etc to identify the supply end. Generally the

    common neutral connection is marked as N or n.

    For the secondary tapings, suffix numbers are used for all

    tapping points along the auto-transformers primary winding.

    These numbers generally start at number 1 and continue in

    ascending order for all tapping points as shown.

    Figure (7.41) Autotransformer terminal markings

    An autotransformer is used mainly for the adjustments of line

    voltages to either change its value or to keep it constant. If

    the voltage adjustment is by a small amount, either up or

    down, then the transformer ratio is small as VP and VS are

    nearly equal.

    Currents IP and IS are also nearly equal. Therefore, the

    portion of the winding which carries the difference between

    the two currents can be made from a much smaller conductor

    size, since the currents are much smaller saving on the cost

    of an equivalent double wound transformer.

    However, the regulation, leakage inductance and physical size

    (since there is no second winding) of an autotransformer for a

    given VA or KVA rating are less than for a double wound

    transformer. Autotransformers are clearly much cheaper than

    conventional double wound transformers of the same VA rating.

    When deciding upon using an autotransformer it is usual to

    compare its cost with that of an equivalent double wound type.

    This is done by comparing the amount of copper saved in the

    winding. If the ratio "n" is defined as the ratio of the lower

    voltage to the higher voltage, then it can be shown that the

    saving in copper is: n.100%. For example, the saving in copper

    for the two autotransformers would be:

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    47

    Example

    An autotransformer is required to step-up a voltage from 220

    volts to 250 volts. The total number of coil turns on the

    transformer main winding is 2000. Determine the position of

    the primary tapping point, the primary and secondary currents

    when the output is rated at 10KVA and the economy of copper

    saved.

    Then the primary current is 45.4 amperes, the secondary

    current drawn by the load is 40 amperes and 5.4 amperes flows

    through the common winding. The economy of copper is 88%.

    Disadvantages of an Autotransformer

    1. The main disadvantage of an autotransformer is that it does not have the primary to secondary winding isolation of a

    conventional double wound transformer.

    Then autotransformer's can not safely be used for stepping

    down higher voltages to much lower voltages suitable for

    smaller loads.

    2. If the secondary side winding becomes open-circuited, current stops flowing through the primary winding stopping

    the transformer action resulting in the full primary voltage

    being applied to the secondary circuit.

    3. If the secondary circuit suffers a short-circuit condition, the resulting primary current would be much larger than an

    equivalent double wound transformer due to the increased

    flux linkage damaging the autotransformer.

    4. Since the neutral connection is common to both the primary and secondary windings, earthing of the secondary winding

    automatically earths the primary as there is no isolation

  • Electric Submersible Pumps Mohamed Dewidar 2013

    Chapter 7

    48

    between the two windings. Double wound transformers are

    sometimes used to isolate equipment from earth.

    The autotransformer has many uses and applications including

    the starting of induction motors, used to regulate the voltage

    of transmission lines, and can be used to transform voltages

    when the primary to secondary ratio is close to unity. An

    autotransformer can also be made from conventional two-winding

    transformers by connecting the primary and secondary windings

    together in series and depending upon how the connection is

    made, the secondary voltage may add to, or subtract from, the

    primary voltage