Ch1 Standard Espanolmx
-
Upload
erudiel-a-juarez -
Category
Documents
-
view
163 -
download
11
Transcript of Ch1 Standard Espanolmx
![Page 1: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/1.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Hubbell Premise Wiring
MISSIONCRITICAL
Ing. Mauricio Fuentes Rodriguez
Especificador de conectividad
E-mail: [email protected]
Tel: (477) 306 91 88
![Page 2: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/2.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TelecomunicacionesCódigos, Estándares y
Regulaciones
Entrenamiento Hubbell Mission Critical
![Page 3: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/3.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Contenidos
Definición C ódigos, Estándares y Regulaciones
Organizaciones de la Industria de Cableado
Estructurado
Evolución de los Estándares de Cableado
Estructurado
Estándares IEEE 802.3 Ethernet
Revisión de los Estándares de Cableado
Estructurado
![Page 4: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/4.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Definición de C ódigo
Códigos son documentos publicados que establecen provisiones, reglas y practicas aceptables que:• Garanticen la calidad de la construcción e
instalación• Salvaguarde a personas y propiedad de peligros
Los C ódigos son legalmente aplicables por la Autoridad que Tiene Jurisdicción (AHJ)
El código m ás riguroso tiene prioridad
![Page 5: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/5.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Cumplimiento de C ódigos
Los códigos no garantizan el desempeño de sistema• Las instrucciones del fabricante y estándares deben ser
seguidos
Violaciones en los códigos pueden resultar en:• Desempeño pobre de la red• Detención del trabajo y multas• Certificado de Ocupación demorado• Trabajos adicionales costosos • Choque eléctrico o fuego• Equipo dañado• Pérdida de Garantía
![Page 6: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/6.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
NFPA 70: National Electric Code
Artículos clave del NEC Articulo 250.8: Conexión Equipo de Puesta a Tierra
• Uso de tormillos de puesta a tierra regulados.
Articulo 800.133A: Separación de cableado Potencia y Datos• Conductores de Potencia y comunicaciones se permiten en la misma
canaleta, caja de salida, caja unión, u otro accesorio, si se brinda una separación física por medio de una barrera física permanente y listada.
Articulo 800.133C: Suporte de Conductores• Cables de Comunicación no deben estar unidos por ningún medio al exterior
de un conduit o canaleta como medio de soporte
Articulo 800.154A: Cables Plenum• Cables instalados en ductos, plenums u otros espacios usados para aire
ambiental deben ser Tipo CMP. Esto incluye cables puesta a tierra.• Cable abandonado no se permite ser dejados en el lugar
NEC se actualiza cada 3 años (2005, 2008, 2011, 201 4 ………)
![Page 7: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/7.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Definición Estándar
Los estándares son documentos publicados que especif ican los requisitos m ínimos del diseño y el desempeño• Voluntariamente aceptados por las Industrias participantes
• No son obligados por ley• Establecen prácticas de instalación para lograr el desempeño deseado
Los estándares publicados son ratificados por la votac ión del comité
Comités de estándares : • Tienen una política abierta de participación para la industria
• Asigna grupos de trabajo para resolver asuntos técnicos• Asigna grupos de enlace para resolver los conflictos con otros
estándares
Las Organizaciones de estándares (ANSI, TIA, EIA) tien en superioridad oficial sobre los comités de trabajo
![Page 8: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/8.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Beneficios de los Estándares de Cableado
Interoperabilidad de componentes y sistemas• Promueven independencia de proveedores• Acomoda movimientos, agregados y cambios• Garantiza conectividad de sistema abierto
Cumplimiento de los estándares asegura el desempeño de sistema• Operación del sistema libre de errores• Desempeño del Sistema = Certeza de la aplicación para
usuarios finales
Retorno de la Inversión mejorado• Mayor vida útil con la instalación apropiada• Costo más bajo del sistema que utiliza hardware estándar• Menores costos de mantenimiento e instalación
![Page 9: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/9.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Cumplimiento de Estándares
Violación de los estándares puede resultar en:• Desempeño pobre del sistema• Fallo de equipos• Violaciones potenciales al código• Perdida de garantias• Problemas de compatibilidad de hardware
Exceder los estándares es la meta de los fabricante s• Margen de desempeño garantiza integridad del sistema• Evitan resultados al limite de las pruebas• Garantizan confiabilidad a largo plazo
![Page 10: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/10.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Códigos & Responsabilidad de Estándares
Fabricantes de Productos
Fabricantes de Cable
Fabricantes de equipos de prueba
Diseñadores
Especificadores
Instaladores
![Page 11: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/11.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Organizaciones de la
Industria de Cableado
Estructurado
Entrenamiento Hubbell Mission Critical
![Page 12: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/12.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Organizaciones: Estándares
ANSIAmerican National Standards Institute
• Organización voluntaria sin fines de lucro fundada en 1918
• Coordina la aprobación global de estándares TIA
Telecommunications Industry Association• Desarrolla los estándares para el equipo de la red,
cable, inalámbrico y comunicaciones de satélite• Se une a EIA en 1988
EIAElectronic Industries Alliance
• Fundada en 1924 como una Asociación de Fabricantes de Radio.
• Desarrolla los estándares para sistemas electrónico s residenciales, industriales, defensa y aeroespacial es
• Sector de Telecomunicaciones trabaja en conjunto co n TIA.
![Page 13: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/13.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Organizaciones: Estándares
IEEEInstitute of Electrical & Electronic Engineers• Organización global m ás grande de estándares de
electrónica• Desarrolla estándares para redes locales y metro• Publica la serie de estándares IEEE 802 Ethernet
Telcordia Technologies (Antes Bellcore)• Antigua unidad de investigación “baby bell” luego del
rompimiento de AT&T en 1984 .• Desarrolla la infraestructura global de telecomunic aciones y
software• Publica los estándares de confiabilidad para sistem as de larga
distancia
CSACanadian Standards Association• CSA T500 estándares de telecomunicaciones descontin uados• CSA adopto los estándares ANSI/TIA/EIA
![Page 14: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/14.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Organizaciones de prueba y seguridad
UL Underwriters Laboratories• Organización de pruebas independiente sin fines de lucro• Proporciona las calificaciones de aceptabilidad par a productos
eléctricos• Clasificaciones: Listado, Clasificado, Reconocido, Verificado
ETL Electrical Testing Laboratories Inc.• Pruebas independientes de producto para el desempeñ o
conforme a los estándares• Escribe reportes de verificación de terceros
Telcordia Technologies• Prueba y califica el equipo para proveedores de ser vicio
grandes
![Page 15: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/15.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Pruebas y Certificación de Productos
Beneficios de Pruebas por Terceros
Comprobación imparcial de desempeño
Mantiene los fabricantes honestos
Aumenta la integridad del producto
Mejora la confianza de cliente
Brinda ventajas sobre marcas inferiores
![Page 16: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/16.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
IEEE 802.3Estándares de redes:Definición Ethernet
Entrenamiento Hubbell Mission Critical
![Page 17: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/17.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Nota a los Instaladores
Por que discutir la IEEE 802.3 Ethernet ?
El propósito es entender la relación entre el desempeño de la red y la calidad de la instalación del cableado estructurado.
Que define el desempeño de la red?
Transferencia de Datos cumple expectativas:
Si la aplicación usada trabaja en forma correcta
![Page 18: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/18.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Estandard IEEE 802.3 Ethernet
Proceso de Transferencia de Mensajes Ethernet Equipos en la red tienen una dirección MAC y un IP
Marcos Ethernet son diseccionados a través de la red
Colisiones de marcos en los nodos son secuenciados por prioridad
Un dominio de transmisión dentro de un edificio es una LAN
Una red con múltiples dominios es una WAN
Un router es usado para conectar múltiples dominios de transmisión
![Page 19: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/19.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Modelo Open Systems Interconnect
El Modelo OSI define los procesos de transmisión de mensajes
Transferencia de mensajes es entre dispositivos y s istemas
Cada capa sirve la capa superior en la pirámide de protocolo
Cableado Estructurado es la Capa Física
Capa Física
Capa Enlace de Datos
Capa Red
Capa Transporte
Capa Sesión
Capa Presentación
Capa Aplicación
![Page 20: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/20.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Definición Capas OSI
APLICACION : Permite el cambio de información entre sistemas de operativos diferentes
PRESENTACION: Realiza la conversión de mensajes, encriptación, desencriptación, traducción de códigos
SESION: Sincroniza y controla la transferencia de mensajes entre dispositivos de la red (start, stop, cancel)
TRANSPORTE: Monitorea la calidad de la transferencia de datos
RED: Controla la transferencia de mensajes entre las LAN’s
ENLACE DE DATOS : Controla la transferencia de mensajes entre dispositivos
FISICA: Transmite, recibe, y transfiere bits de datos sobre diferentes medios (cobre, fibra, coaxial, etc.)
![Page 21: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/21.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Nota a los Instaladores
Capa de Transporte y Calidad de Datos
La Calidad en la transferencia de Datos a través de U TP depende de la instalación
EJEMPLO: Fuentes EMI causan errores bit a través del cableado UTP
Errores Bit causan Desempeño de la red lento
Por que los errores bit causan redes lentas?
Paquetes de Datos Corruptos son rechazados por la capa de Transporte y el mensaje debe ser re-transmitido
![Page 22: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/22.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Nota a los Instaladores de Cable
Desempeño de Crosstalk depende de:
Calidad del cable y componentes
Calidad de la instalación del cableado y rutas
Calidad de la terminación de cable en cada extremo
Que es calidad?
Calidad es conformidad con especificaciones, estándares y practicas aplicables
![Page 23: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/23.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Entrenamiento Hubbell Mission Critical
Revisión de Estándares de
Cableado
![Page 24: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/24.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Estándares Base TIA/EIA
ANSI/TIA/EIA-568-B.1: Estándar de Cableado de Telecomunicaciones en Edificios Comerciales: Requerimientos Generales
ANSI/TIA/EIA-568-B.2: Estándar de Cableado de Telecomunicaciones en Edificios Comerciales: Componentes para Par Trenzado Balanceado
TIA/EIA-TSB-155: Caracteriza Cableados de Categoría 6 existentes para soportar 10 Gbit/s Ethernet
ANSI/TIA/EIA-568-B.3: Componentes Fibra Óptica TIA/EIA-TSB-140: Guías Adicionales para pruebas de campo de
Longitud, Perdidas y Polaridad de Sistemas de Fibra Óptica ANSI/TIA/EIA-569-B: Estándar para Rutas y Espacios
Telecomunicaciones en Edificios Comerciales ANSI/TIA/EIA-570-B: Cableado Telecomunicaciones
Residencial
![Page 25: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/25.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Estándares Base TIA/EIA
ANIS/TIA/EIA-606-A: Estándar para la Administración de Infraestructura de Telecomunicaciones en Edificios Comerciales
ANSI J-STD-607-A: Requerimientos para el Aterramiento de Telecomunicaciones de Edificios Comerciales
ANSI/TIA/EIA-598-B: Codificación de colores para Cable Fibra Óptica
ANSI/TIA/EIA-758: Estándar de Cableado Telecomunicaciones de Planta Externa propiedad del cliente.
ANSI/TIA/EIA-862: Estándar de Cableado para Automatizacion de Edificios Comerciales
ANSI/TIA/EIA-942: Infraestructura Telecomunicaciones para Data Centers
ANSI/TIA/EIA-1005: Estándar para Infraestructura deTelecomunicaciones Industriales
![Page 26: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/26.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Estándares Base Internacionales
ISO/IEC 11801: Tecnología Información – Cableado Genérico para Cableado Estructurado de Clientes
ISO/IEC 18010: Tecnología Información – Rutas y Espacios para Cableado Estructurado de Clientes
CENELEC EN 50173: Tecnología Información – Sistemas de Cableado Genérico
CENELEC EN 50174: Tecnología Información – Instalación de Cableado – Especificación y Garantía de Calidad
![Page 27: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/27.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
ISO 11801 vs. TIA/EIA -568
ISO 11801 define clases de C a F:
Cat 7 (No Reconocida)
600 MHzF
Cat 6a (AugmentedCat 6)
500 MHz-
Cat 6250 MHzE
Cat 5e100 MHzD
Cat 316 MHzC
TIA-568-B CategoríaAnchoBandaISO 11801 Clase
![Page 28: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/28.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
ISO 11801 vs. TIA -568
Tipos adicionales de Cable permitidos: 120 ohm ScTP y 100 ohm STP Fibra MonoModo a la salida del Área de Trabajo es soportada Clase F es una aplicación de Par Trenzado Apantallado
Terminología Diferente: Distribuidor Piso (FD) = Conexión Cruzada Horizontal (HC) Distribuidor de Edificio (BD) = Conexión Cruzada Principal (MC) Distribuidor Campus (CD) (solo en ISO/IEC 11801)
Requerimientos para cableado en UTP son los mismos que en TIA/EIA
Por ISO/IEC 11801:
![Page 29: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/29.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Norma TIA/EIA -568-B
‘568-B estándar son 3 documentos individuales:
TIA/EIA-568-B.1Estándar de Cableado de Telecomunicaciones en
Edificios Comerciales: Requerimientos Generales (2001)
TIA/EIA-568-B.2Componentes para Par Trenzado Balanceado (2001)
TIA/EIA-568-B.3Componentes Fibra Óptica (2000)
![Page 30: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/30.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Norma TIA/EIA-568-B.1
568-B.1: Estándar de Cableado de Telecomunicaciones en Edificios Comerciales: Requerimientos Generales
• Liberado (4/01):
• Establece Guías de Cableado Estructurado
• “TR” (Telecommunications Room ) reemplaza “TS”
• Prueba de Enlace Permanente reemplaza al Enlace Básico
• Categoría 4 eliminada
• Categoría 5 descontinuada
• Especificaciones UTP balanceado 100-ohm asignado a ‘568-B.2
• Especificación Componentes de Fibra asignado a ‘568 -B.3
![Page 31: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/31.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-568-B.1: Elementos Clave
Cableado Horizontal
Cableado Backbone
Enlace Permanente & Canal
Área de Trabajo (WA)
Cuarto Telecomunicaciones (TR)
Cuarto de Equipo (ER)
Instalaciones de Entrada (EF)
![Page 32: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/32.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Cableado Estructurado TIA -568-B.1
Legend
X
X
X
X
WA
WA
TR
HC
MC ER
EF
Cableado Horizontal
Cableado Backbone
HC
Cableado Backbone
XIC
XHC
MC = Main cross-connectWA = Work AreaIC = Intermediate cross-connectHC = Horizontal cross-connectTR = Telecommunications RoomER = Equipment RoomEF = Entrance facility
TR TR
Cables Horizontales : HC a cada WA
Cables de Backbone : MC a cada TR
![Page 33: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/33.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-568-B Cableado Horizontal
Conexión Cruzada: 2 patch panels con patch cords
Backbone Cables
Sw
itch
Cordones Equipo
Patch Cords
RutaHorizontal
Cableado Horizontal 90 metros max.
TR HC
Salidas
![Page 34: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/34.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-568-B Cableado Horizontal
Interconexión: Un patch panel, no patch cords
Backbone Cables
Sw
itch
Cordones Equipo
RutaHorizontal
Cableado Horizontal90 meters max.
TR
Salidas
HC
![Page 35: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/35.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-568-B Enlace Permanente
Longitud Max. 90 metros: Interconexión o Con. Cruza da
1 Punto Consolidación permitido por zona de cableado
CP
CP
![Page 36: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/36.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-568-B Canal
Longitud Max. 100 meters: Interconexión o Con. Cruza da
1 Punto Consolidación permitido por zona de cableado
CP
CP
Interconexión
Conexión Cruzada
![Page 37: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/37.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Conexión Cruzada vs. Interconexión
Ventajas del esquema de conexión cruzada:• Administración de la red mas flexible• Permite movimientos de personal de oficina
Desventajas del esquema de conexión cruzada :• Se requieren dos Patch Panels• Se necesita más espacio de Rack• Se requieren cordones extra para conexión cruzada
Otras desventajas:• Cordones de Equipo deben ser cortados y cableados directo
al panel• Poncheo de Patch Cords multifilares es menos recomendado
![Page 38: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/38.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Addenda Publicada TIA-568-B.1
568-B.1-1: “Radio de Curvatura Minino para PatchCab le en 4-pair UTP y 4-pair ScTP” (8/01)
568-B.1-2: “Especificaciones de Aterramiento de sis temas de cableado apantallado” (2/03)
568-B.1-3: “Distancias soportables y Atenuación de Canal para Aplicaciones de Fibra Óptica por tipo de FO ” (2/03)
568-B.1-4: “Reconocimiento de Categoría 6 y Fibra Ó ptica Multimodo 50/125µm 850 nm Laser-Optimized” (2/03)
568-B.1-5: “Cableado de Telecomunicaciones para Gabinetes de Telecomunicaciones” (3/04)
![Page 39: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/39.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Arquitectura de Cableado Horizontal
Workstation1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
Topología Estrella: Tiraje de cable a cada salida
HC
Estación
Enlace Permanente
![Page 40: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/40.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Norma TIA/EIA -568-B.2
568-B.2: Componentes Cableado Par Trenzado
• Liberado 4/01, reemplaza 568-A Componentes Cobre
• Cat 3 y Cat 5e categorías reconocidas
• Absorbe todos los TSB’s y Addenda de ‘568A
• Nuevas Especificaciones para Cableado 100 ohm ScTP
• Nuevas Especificaciones para Cat 5e balanced 100-ohm UTP
• Requerimientos de Desempeño para Hardware de Conexiones
• Desempeño para Cordones y Jumpers
• Especificaciones Cat 6 100-ohm UTP en addendum B.2-1
![Page 41: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/41.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-568-B.2: Elementos Clave
Pruebas de Confiabilidad para cables y componentes U TP
• Eléctricas
• Mecánicas
• Ambientales
Pruebas de Parámetros de Transmisión y Especificacione s
• Crosstalk (NEXT, FEXT, PSNEXT, PSELFEXT)
• Perdida de Inserción (Insertion Loss)
• Perdida de Retorno (Return Loss)
• Retardo (Delay and Delay Skew)
![Page 42: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/42.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-568-B.2 Addenda Publicada
B.2-1: “Especificaciones Desempeño Transmisión para Cableado 4-Pares 100 Ω Categoría 6” (6/02)
B.2-2: “Componentes Cableado Par Trenzado” (8/01)
B.2-3: “Consideraciones Adicionales para Determinar Pasa/Falla en Perdida de Retorno y Perdida de Inserción (Insertion Loss, Return Loss)”(3/02)
B.2-4: “Requerimientos de Confiabilidad para conexiones sin soldadura enHardware de Conexión” (6/02)
B.2-5: “Correcciones a TIA/EIA-568-B.2”
B.2-6: Procedimientos de Prueba a Componentes Categoría 6 (1/04)
![Page 43: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/43.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Norma TIA/EIA -568-B.3
TIA-568-B.3 Componentes Cableado Fibra Óptica • Liberada 4/00. Reemplaza TIA-568A (1991)
Elementos Clave de TIA -568-B.3:• Especificaciones Cable, conectores y empalmes de Fib ra
Óptica :• Perdida de Inserción (Insertion Loss)• Perdida de Retorno (Return Loss)• Atenuación del Cable
• Radio de Curvatura del Cable y m áxima tensión de halado• Especificaciones y pruebas de confiabilidad para
Conectores:• Ópticas• Mecánicas• Ambientales
![Page 44: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/44.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-568-B.3 Addenda Publicada
568B.3-1: “Additional Transmission Performance Specifications for 50/125 Micron Optical FiberCabling Systems” (4/02)
Soporta Transmisión de datos a 10 Gb/s hasta 300m (984 ft.) sobre Fibra Óptica de 50 micras
• Transmisores usan lasers VCSEL
• VCSEL = Vertical Cavity Surface Emitting Laser
• Fibra es Optimizada para Laser
![Page 45: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/45.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
IEEE 802.3: Fibra 10 Gbit Ethernet
IEEE 802.3ae: 10Gb/s Ethernet Sobre Fibra Óptica
• Liberada en Junio 2002
Tipos de Fibra y Ancho de Banda a Longitudes de Onda 850/1300nm
• Fibra Multimodo Premium 62.5/125 (500/500 MHz-km)
• Fibra Multimodo 50/125 (500/500 MHz-km)
• Fibra Multimodo Optimizada Laser 50/125 (2000 MHz-km VCSEL)
• Fibra Monomodo 9/125 ( >>2000 MHz-km)
![Page 46: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/46.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Trabajo en Proceso Subcomite TIA
Addendum TIA/EIA-568-B.2-10: Cableado Cat 6A
• Introducción a Especificaciones Cableado Cat 6 Aumentada
(Cat 6A)
• Soporta standard IEEE 802.3 10GBASE-T
• Parámetros Alien Crosstalk definidos a 500 MHz
• ANEXT, AFEXT, PSANEXT, PSAFEXT
• IEEE 802.3an 10GBASE-T estándar soportado
• Cables Reconocidos para incluir UTP, STP y ScTP
• IEEE 802.3 PoE y PoE+ soportados
![Page 47: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/47.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Por qu é 568-C?
568B promulgada en 2001 (Actualización 5 años?)
Varios Addendums desde 2001.
• 6 Adendums a 568-B.1• 10 Adendums a 568-B.2• 1 Adendum a 568-B.3
![Page 48: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/48.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA 568-C
Nueva Estructura.• 568-C.0 Cableado Estructurado Genérico• 568-C.1 Cableado Edificios Comerciales
• 568-C.2 Componentes de Cableado Cobre• 568-C.3 Componentes de Cableado Fibra.
Nueva organización se hace con el objetivo de mejor ar y simplificar el proceso de emisión de estándares eliminando información duplicada y creando una base com ún.
![Page 49: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/49.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Tipos de Documentos TIA
Standard Comunes
ANSI/TIA 606-B
Admin. Telcom
ANSI/TIA
568-C.0
Cableado Genérico
ANSI/TIA 569-BRutas y Espacios
ANSI J-STD 607ASistema Puesta a Tierra
ANSI/TIA 862AutomatizaciónEdificios
Standard Infraestructura
ANSI/TIA 1005
Cableado Industrial
ANSI/TIA
568-C.01
Cableado Comercial
ANSI/TIA 570-BCableado Residencial
ANSI/TIA 942
Data Center
ANSI/TIA 758APlanta Externa(OSP)
Standard Componentes
ANSI/TIA
568-C.2
Componentes UTP
ANSI/TIA
568-C.3
Componentes Fibra Óptica
Documentos de los estándares se pueden dividir en tres grupos según su aplicación:
![Page 50: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/50.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
568-C.0 Cableado Estructurado Gen érico
Se convierte en la Se convierte en la ““ basebase ”” de otros de otros estest áándares.ndares.
•Necesidad de tener estándar no solo para Edificios de Oficinas sino todo tipo de Edificio Comercial (aeropuertos, hospitales, etc.)
• Mayor facilidad de actualización de estándares.
• Mantiene mucha información de la anterior 568-B.1
Destinado aDestinado a: Usuarios, Diseñadores, Instaladores.
![Page 51: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/51.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
568-C.0 Cableado Estructurado Gen érico
InformaciInformaci óón contenida:n contenida:
• Información com ún a sistemas de cableado redes: Establece como se construye una red con
topología estrella Establece requerimientos de cableado
• Nomenclatura de cableado genérica
![Page 52: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/52.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
568-C.0 Cableado Estructurado Gen érico
Cambios TCambios T éécnicos:cnicos:
• Radio de Curvatura propuesto a 4X tanto para UTP co mo FTP.
• Radio de Curvatura del PatchCord cambia de 0.25” a 1X para contemplar nuevos cables.
• Categoría 6A es reconocida.
• Desentorche máximo Cat6A 0.5”
• Reconoce Fibra Óptica Monomodo para cableado Horizontal.
![Page 53: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/53.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
568-C.0 Revisiones
• Adendum 1: Cambia Referencias de 568-B.2 a 568-C.2.
• Agrega Fibra Óptica OM4 (no reconocida actualmente)
•Busca hacer genéricos los MUTOA y Puntos de Consolidación para aplicaciones fuera de ambientes de oficina.
![Page 54: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/54.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
568-C.1 Cableado Edificios Comerciales
No es un documento independiente como el 568-B1
Se basa en 568-C.0 e indica excepciones.
Especifico para Edificios de Oficinas.
Documento con menos aplicaciones en instalaciones como colegios o Universidades.
Destinado aDestinado a: Usuarios, Diseñadores, Instaladores.
![Page 55: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/55.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
568-C.1 Cableado Edificios Comerciales
Cambios TCambios T éécnicos:cnicos: Incorpora los Addendums 568-B.1 : Categoría 6 Categoría 6A Fibra Óptica 850 nm 50/125µm
Optimizada Laser. Telecomunications Enclousures (TE) Cableado Centralizado Recomendación para usar FO 850nm 50 µm Optimizada Láser para ediciones comerciales.
![Page 56: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/56.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Nueva Nomenclatura
568-C.0 y 568-C.1
Tomado de Cabling and Maintenence
![Page 57: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/57.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA568-C.0 Topolog ía Genérica
DC
DB DB
DA DA
EO EO EO EO EO EO EO
Cab
ling
Sub
syst
em3
Cab
ling
Sub
syst
em1
Cab
ling
Sub
syst
em3
Cab
ling
Sub
syst
em2
Cab
ling
Sub
syst
em1
Nomenclatura:Nomenclatura:
EO Equipment Outlet
DA Distributor A
DB Distributor B
DC Distributor C
CP Opcional
![Page 58: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/58.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA568-C.1Topología Edificio Comercial
MC
IC IC
HC HC
TO TO TO TO TO TO TO
Bac
kbon
eC
ablin
gB
ackb
one
Cab
ling
Hor
izon
tal
Cab
ling
Nomenclatura:Nomenclatura:
TO Telecom. Outlet
MC Main XConnect
IC Interm. XConnect
HC Horizontal XConnect
CP Opcional
Bac
kbon
eC
ablin
gH
oriz
onta
l C
ablin
g
![Page 59: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/59.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
568-C.2 Componentes de Cableado Cobre
Incluye las especificaciones de los componentes y cableado de sistemas de cobre.
Requerimientos de prueba para Cat3, Cat5e, Cat6 y Cat6A (trasladados a este apartado).
Publicado en el 2009.
Destinado aDestinado a: Fabricantes.
![Page 60: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/60.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
568-C.3 Componentes Ópticos Cableado
PropProp óósitosito
Servir como un documento independiente no ligado a las normas comerciales.
Especificar los parámetros de transmisión de los componentes
Destinado aDestinado a: Fabricantes.
![Page 61: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/61.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
568-C.3 Componentes Ópticos Cableado
Nomenclatura FONomenclatura FO
Parámetros de desempeño de transmisión (Tabla 1) in cluye referencias a la nomenclatura ISO (ver ejemplo)• OM1, OM2 y OM3• OS1 y OS2
![Page 62: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/62.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Nomenclatura
![Page 63: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/63.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
568-C.3 Componentes Ópticos Cableado
Colores del Conector
A menos que se use el color para algún propósito en particular los conectores se deben identificar hast a donde sea posible con los siguientes colores:• Multimodo: Beige, Negro, Aqua• Monomodo: Azul• Monomodo Férula de contacto Angulado: Verde
![Page 64: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/64.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
568-C.4 Componentes Coaxial
Broadband Coaxial Cablingand Component Standard.
Consolida toda la información sobre componentes coaxial en un solo documento.
Referencia para todos los comités (Residencial, DataCenter)
Etapa inicial de Desarrollo.
![Page 65: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/65.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Diseño 10 Gbit UTP: ANEXT
ANEXT: Alien Cross Talk –Señal de interferencia entre pares en cables adyacentes y conectores
Factores:
• Densidad de Puertos en el Panel
• Distancia desde el Transmisor
•Densidad de Fajos de Cable
• Numero de cables
• Frecuencia de la señal
ANEXTANEXT
ANEXT Puerto a Puerto
ANEXT Cable a Cable
![Page 66: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/66.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Diseño 10 GbE UTP: ANEXT
ANEXT: Jack a Jack
Factores:
• Densidad de placas
• Distancia de separación
![Page 67: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/67.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Diseño Cable Categoría 6A
Nuevo Diseño de la chaqueta aire/dieléctrico
.350” max diámetro permitido
Nuevo 22 AWG diámetro de cable
Aislante del cable mas grueso
Entorche mas “apretado”
Separador de pares mas grueso
![Page 68: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/68.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Supresión ANEXT Categoría 6A
Peor Caso: 6-alrededor-1 PSANEXT
Otros cables energizados como “perturbadores”
Cable Central es la “victima”
Cable Cat 6A debe pasar:
• ANEXT
• AFEXT
• PSANEXT
• PSAFEXT
![Page 69: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/69.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Cat 6A: Nota para Diseñadores e Instaladores
Diámetros de cable m ás grandes afectan el diseño e instalación:
• Tamaño del grupo de halado
• Radio de Curvatura
• Cantidad de llenado de Rutas
• Selección de Cajas de Salida
•Referirse a las Practicas de Instalación Hubbell
•Objetivo Futuro: Reducir el Diámetro del Cable
![Page 70: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/70.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-TSB-155: Mitigación Cat 6 Canales instalados en cableado Categoría 6:
• Soporta 10GBASE-T hasta 37 metros
• Longitudes de 37 a 55 metros dependes del ANEXT ambiental
• Longitudes > 55 metros requieren procedimientos demitigación
TSB-155: Cat 6 Procedimientos Mitigación:
• Desamarrar cables y separar patch cords
• Usar PatchCords y Cordones de Equipos tipo ScTP
• Reemplazar conectores y Patch Panels con componentes Cat 6A
• Pruebas de campo para Alien crosstalk a 500 MHz
![Page 71: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/71.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Futuro : Grupo de Estudio IEEE 802.3
IEEE 802.3: Propuesta 100 Gb/s Ethernet
Realidad: Un transmisión de datos a 100 Gbit/s llenar ía un Disco Duro de 100 Gbyte en 8 segundos!
• Nota: 1 byte = 8 bits
![Page 72: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/72.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-569-B Actualización Standard
TIA/EIA-569-B: Estándar para Rutas y Espacios Telecomunicaciones en Edificios Comerciales • Liberado en 2004• Reemplaza TIA/EIA-569-A (1998)
![Page 73: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/73.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-569-B: Elementos Clave
Rutas: Rutas de Cableado Horizontal
Rutas de Cableado Backbone
Rutas de Entrada de Servicio
Espacios: Áreas de Trabajo
Cuartos de Telecomunicaciones y de Equipos
Facilidades de Entrada
Gabinetes, Salidas, Empalmes y Cajas de Halado
![Page 74: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/74.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Rutas: Criterios Generales de Diseño• Tamaño y trazado
• Longitud máxima de cada tramo
• Capacidad de llenado de Cable – 40% max
• Mínimo radio de curvatura
• Máximo número de curvas en un tramo
• Puesta a Tierra
• Firestopping
• Separación de fuentes de potencia y de EMI
• Métodos de soporte y reglas de distancias
• Requerimientos Ambientales – “debe ser un área seca”
TIA-569-B: Elementos Clave
![Page 75: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/75.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Espacios (TR, ER, EF, TE): Criterios de Diseño Gene rales• Tamaño, diseño, ubicación
• Espacios libres en Racks de Equipos
• Apertura de puertas
• Materiales y altura de cielos
• Materiales y Capacidades de los pisos
• Contraemchapes de Plywood
• Iluminación, potencia, HVAC
• Requerimientos de rutas
• Puesta a Tierra
• Firestopping
TIA-569-B: Elementos Clave
![Page 76: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/76.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Que pasa si no hay espacio para el “TR” en un edific io?• No se deben usar bodegas o cuartos de limpieza
• Un cuarto especifico para el “TR” puede no estar disponible
Solución: Un gabinete (TE) puede servir como TR• Permitido por addendum TIA-568-B.1-5
• incorporado en TIA-568C.1
• Un TE sirviendo como TR debe cumplir con estándar TIA-569-B
Realidad: La mayoría de los edificios nunca son
diseñados para tener un TR en cada piso
Nota para Diseñadores e Instaladores
![Page 77: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/77.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-569-B: Segunda Revisión
Será TIA-569-C
Objetivo principal hacerlo un estándar com ún
Ámbito cubrirá todo tipo de aplicación y no se limit ara a edificios comerciales de oficinas.
Cambios:• Contenido de Potencia y Ruido era especifico para 1Gb E
y no para 10GbE.• Se reconocen problemas potenciales con guías actuales
y aplicaciones 10GbE en Cat6A UTP
![Page 78: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/78.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TSB-190
Consolida información sobre m últiples aplicaciones operando en diferentes categorías de cable o con diferente construcción en la misma ruta.
Indica que toda nueva aplicación para 10GBaseT debe ser Cat6A .
Indica que no hay problema en tener fajos de 2 fabricantes Cat6A (complaint) en forma adyacente.
![Page 79: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/79.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-570-B Actualización Standard
TIA-570-B: Cableado Residencial y Multi-Propietarios• Liberado en 2004• Reemplaza ‘570-A (1999)• Define nuevo Cableado “Grado 2”
Grado 1: Voz/Data/Video• (1) Categoría 3 o 5e, y (1) 75-ohm cable coaxial• Teléfono, Satélite, CATV, y Servicios de Data por marcado
[Nuevo] Grado 2: Voz/Data Alta-Velocidad, Video, Multimedia• Permite Cat 5e o Cat 6, 75-ohm coax, y Fibra Multimodo• Teléfono, TV, Internet Alta Velocidad, LAN, Seguridad, y
Multimedia
![Page 80: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/80.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-570-B Actualización Standard
TIA-570-A addenda incorporada en TIA -570-B:• 570-A-1: “Cableado de Seguridad” (2002) • 570-A-2: “Cableado de Control” (2002)• 570-A-3: “Cableado Audio” (2002)
TIA-570-B es ahora un estándar de cableado residencial multimedia
manejará el futuro los servicios de alta velocidad
• 10 Gb/s Ethernet en el Hogar
![Page 81: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/81.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-570-B: Elementos Clave
Punto Demarcación (DP): interfase externa entre el Proveedor de Acceso (AP) y el dueño de la residencia
Dispositivo de Interfase de Red (NID): conexión física del cable del AP’s con el cable ADO
Salida del Desconectador Auxiliar (ADO): cable de conexión del DD desde el NID
Dispositivo Distribución (DD): facilidad de distribución del cable de la Conexión Cruzada
Salida de Telecomunicaciones (TO): Salida de pared para la terminación de los cables desde el DD
![Page 82: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/82.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-570-B Esquema de Cableado
To AP
DPNID
ADO
DD
TO #1
TO #2
TO #nOutside Inside
Nota: Para unidades Multi-morada (MDU ’s), cada arrendatario tiene un cable ADO y un DD por separado
![Page 83: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/83.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Dispositivo Distribución Residencial
“Triple play” y mas:
• Voz
• Data
• Video
• Audio
• TV
• Seguridad
• Automatización Residencial
![Page 84: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/84.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
ANSI/TIA/EIA 606Administración y Etiquetado
![Page 85: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/85.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-606-A Actualización Standard
TIA/EIA-606-A: Estándar para la Administración de Infraestructura de Telecomunicaciones en Edificios Comerciales• Liberado en 2002• Reemplaza TIA/EIA-606 (1993)
Cuatro Clases de Administración Definidas:
• Clase 1: Edificio Sencillo, 1 TR, 1 Piso, no OSP
• Clase 2: Edificio Sencillo, múltiples TR’s, no OSP
• Clase 3: Múltiples Edificios (Campus) con OSP
• Clase 4: Multi-Campus, múltiples OSP
![Page 86: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/86.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-606-A: Elementos Clave
Identificadores de Infraestructura deben:• Asociados exclusivamente a cada elemento• Caracteres descriptivos uniformes• Relaciones con registros master
Registros deben:
• Mantenerse para cada elemento identificado
• Rastreable a identificaciones de cómo se construyó
• Actualizado para movimientos, agregados o cambios (MAC’s)
![Page 87: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/87.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-606-A: Elementos Clave
Etiquetas deben:
• Claramente visibles con el color apropiado, contraste y tamaño• Generadas por maquinas en medios permanentes• Resistentes a la humedad, calor y luz ultravioleta• Capaces de sobrevivir la vida útil del cableado - 15 a 25 años
No mas marcadores “Sharpie” o etiquetas con masking tape
Nota: Utilizar los marcadores Sharpie solo para etiquetado preliminar
![Page 88: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/88.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-606-A: Elementos Clave
Elementos Administración Edificios Clase 1 & 2:• Espacios Telecomunicaciones (Salidas, TR’s, ER, EF, TE’s)
• Puertos de Switch y ranuras de tarjetas NIC
• Cables Horizontales y conexiones
• Cables Backbone y conexiones
• Pares de Cobre y Fibra del Backbone
• TMGB y TGB’s
• Firestops
• Rutas de Cableado (opcional)
Nota: Clase 1 tendría solamente 1 TR y 1 TGB
![Page 89: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/89.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
1E-A46
TIA-606-A: Elementos Clave
Ejemplo: Identificador de Enlace Horizontal• FL = Identificador de Piso y TR
• A = 1 o 2 letras identificando el panel HC
• NN = número de puerto del panel HC o # localización del bloque
Patch Panel A
Puerto #46
Identificador TR#1Piso #1Ubicación: Ala Este
Formato: FLFLFLFL----ANNANNANNANN
![Page 90: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/90.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-606-A: Elementos Clave
Ejemplo: Identificador TGB • FL = Identificador de Piso y TR• TGB01 = Identificador para TGB #1
FormatoFormatoFormatoFormato: FL: FL: FL: FL----TGBNNTGBNNTGBNNTGBNN
1E-TGB01
TGB #1Identificador TR#1
Piso #1
Ubicación: Ala Este
![Page 91: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/91.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-606-A: Elementos Clave
Ejemplo: Registro de Enlace Horizontal
patch panel 48-puertos, Cat 6Tipo Conexión Cruzada
Cat 6 jack / HubbellTipo Conector/Fabricante
Puerto #2Posición Faceplate
Cuarto 202Ubicación de la salida
265 ft.Longitud del Cable
HubbellFabricante del Cable
UTP Cat 6 plenum, azulTipo de Cable
1A-B47I.D. Enlace
![Page 92: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/92.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-606-A: Elementos Clave
Ejemplo: Registro de Enlace Horizontal cont.
Joe Smith / XYZ Cable co.Técnico Servicio / compañía
Re-terminado y probado 3/7/05 – cable roto
Registro de Servicio
Switch Cisco puerto #47Circuito del Equipo
ConduitRuta a la Salida
Fluke DTX1800 / PasoCertificador/ Resultados
XYZ Cable Co.Instalador Certificado
CD en departamento ITS.Ubicación de Prueba Datos
12/15/04Fecha Instalación
![Page 93: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/93.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-606-A: Elementos Clave
Elementos Administración Campus Clase 3:• Todos los elementos Clase 2
• Cables de backbone del Campus y conexiones
• Pares de Cobre y Fibra del Backbone del Campus
• Identificadores de Edificios y EF
• Rutas entre edificios (opcional)
![Page 94: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/94.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Nota para Instaladores
Las buenas practicas de etiquetado y los registros detallados son críticos para:
• Manejo de la Red instalada por parte de los Usuarios Finales
• Mantenimiento y búsqueda de problemas
• Procesar reclamos de Garantía con fabricantes de cable y componentes
Usuarios Finales Satisfechos = Repetición de Nego cios
![Page 95: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/95.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-606-A: Revisión
No hay cambios significativos.
Objetivo principal hacerlo un Standard com ún.
Nuevo formato de identificación pero permitirá identificadores antiguos para edificios comerciales orientados a oficinas.
![Page 96: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/96.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Aplicación Practica Administración
Identificación• Identificar todo
Identificadores asignados a los elementos de la infraestructura de telec. Brindar información de ese elemento
• Usar metodología consistente
• Usar etiquetas duraderas
Administración• Áreas:
Terminaciones - paneles/ jacks Medio - cable
Rutas - canaleta / conduit Espacios - cuartos / closets / gabinetes Puesta a Tierra
• Un sistema típico debe incluir: Etiquetas – designar el elemento Diagramas Ordenes de trabajo
Registros - información del elemento. Reportes
DON’T
DO DO NOT
DO NOT USE TAPE GUNS
AVOID HAND WRITTENLABELS
![Page 97: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/97.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
ANSI J-STD-607-A: Puesta a Tierra
![Page 98: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/98.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
J-STD-607-A Actualización Standard
ANSI J-STD-607-A: Requerimientos para el Aterramiento de Telecomunicaciones de Edificios Comerciales• Liberado en 2002• Reemplaza ANSI/TIA/EIA-607 (1994)• Escrito en conjunto por TIA y ATIS (Alliance for
Telecommunications Industry Solutions)
Cambios significativos y agregados• Definición completa de la infraestructura de puesta a tierra• Detalle mejorado de la Barra de Puesta a Tierra• Definición armonizada de Electrodo de Aterrizamiento con el
NEC 2005
![Page 99: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/99.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
J-STD-607-A: Elementos Clave
Key Grounding & Bonding Elements
GEC: Grounding Electrode Conductor
TMGB: Telecommunications Main Grounding Bus bar
TGB: Telecommunications Grounding Bus bar
BCT: B onding Conductor for Telecommunications
TBB: T elecommunications Bonding Backbone
GE: Grounding Equalizer
Definiciones Fundamentales Grounding: una ruta de baja impedancia a tierra Bonding: unión permanente de un conductor a tierra
![Page 100: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/100.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Infraestructura de Puesta a Tierra
TGB #1
TGB #2
TGB #3
TMGBGEC BCT
TBB
1st Piso
2nd Piso
3rd Piso
Entrada de Servicio
El TBB tiene topología Bus
![Page 101: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/101.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Nota a Instaladores y Usuarios Finales
Una Puesta a Tierra apropiada ayuda a proteger el cableado y los equipos de:
• Interferencia Electromagnética (EMI)
• Descargas Electrostáticas (ESD)
• Lazos de tierra y corrientes de falla a tierra
Consecuencias de puesta a tierra inapropiadas:
• Redes lentas por errores de bits
• Computadoras congeladas o datos corruptos
• Daño físico a los equipos de la Red
• Perdida de Garantías en los equipos
![Page 102: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/102.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-758-A Actualización Standard
TIA/EIA-758-A: Customer-Owned Outside PlantTelecommunications Cabling Standard• Liberada en 2004 • Reemplaza TIA/EIA-758 (1999)• Establece guías para cableado OSP, rutas y espacios.
Cables OSP reconocidos :• Fibra Multimodo y monomodo• UTP: blindado y sin blindar • Cable coaxial 75-ohm
Otros medios OSP :• Microondas inalámbricos• Láser inalámbricos punto-a-punto
![Page 103: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/103.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-758-A: Elementos Clave
Rutas OSP:• Ducto y conduit subterráneo• Túneles utilitarios• Poste-a-Poste aéreo con cable mensajero• Cables enterrados directamente
Espacios OSP:• Facilidades de entrada• Gabinetes de empalme• Hoyos de mantenimiento• Pedestales• Gabinetes• Bóvedas
![Page 104: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/104.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-758-A: Elementos Clave
Cableado OSP: Topología Estrella
Edificio#3
Edificio#4
Edificio#2
Cuarto Entrada
Edificio #1 Data Center
MC AP
LEC
Edificio#5
EF
EF
EF
EF
![Page 105: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/105.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-758-A: Elementos Clave
Cable OSP, requerimientos de espacios y rutas• Protección contra ingreso de agua, humedad o suciedad
• Drenaje de agua
• Inmersión de agua
• Temperaturas Extremas : -40c a +85c
• Protección contra roedores
• Protección contra rayos
• Resistencia a elementos ambientales.
NEMA 3R, NEMA 4X, IP67, IP68
• Accesos para mantenimiento
![Page 106: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/106.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA 862 Automatización Edificios
![Page 107: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/107.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-862 Actualización Standard
TIA/EIA-862: Building Automation Cabling Standard for Commercial Buildings• Liberada en 2002• Define cableado BAS por requerimientos TIA/EIA-568B• “Bajo Voltaje” definido como 60V dc máximo
Conexiones equipos BAS a la red LAN:• Terminación directa cables horizontales• Conexión por medio de una salida BAS
Medios Reconocidos :• 100 ohm balanced UTP (Cat 5e, Cat 6)• Fibra Multimodo y monomodo
![Page 108: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/108.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-862: Elementos Clave
Sistemas BAS bajo voltaje pueden operar en el cableado LAN
Cableado BAS de bajo voltaje puede compartir las mismas rutas y espacios del cableado LAN **
Fajos de cable compartidos de BAS y LAN no es recomendado
• Equipos BAS y LAN deben usar cables separados
** Precaución: Ciertos equipos BAS pueden causar interferencia de señales
![Page 109: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/109.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-862: Elementos Clave
Sistemas BAS típicos Seguridad y control de accesos
Sistemas de monitoreo de seguridad CCTV
Alarmas de Servicio
Control de HVAC, potencia e iluminación
Monitoreo paciente / llamadas de enfermera
Busca personas / sistemas de intercomunicación
Relojes master y relojes de tiempo
Sensores y detectores
Sistemas de manejo de emergencias
![Page 110: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/110.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-862: Evolución Futura
Futuro de Sistemas BAS “Convergencia” de funciones BAS y LAN
IEEE 802.3 (PoE) permite equipos BAS ser energizados por la red
PoE y PoE+ va a influenciar diseño BAS
Oportunidad Futura para instaladores de cableado LA N Más cables más ubicaciones
Diversificación en cableado de bajo voltaje multi-función
![Page 111: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/111.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Conectores Audio / Video
RJ-45
RCA component
15-Pin VGA
RCA feed-through +3.5mm stereo jack
S-Video +
RCA composite
HDMI 15-pin
![Page 112: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/112.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Aplicaciones A/V
Sala Lectura Video
• 15-pin VGA• F-connector• RCA• S-video
Audio• 3.5mm• RCA• XLR
Data & Voice• Cat 6
Power – 20 amp
![Page 113: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/113.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-942 Standard Update
TIA/EIA-942: “TelecommunicationsInfrastructure Standard for Data Centers”• Liberado en 2005
• Define instalaciones de computo de gran escala
• Establece guías de diseño generales
Data Centers sirven instituciones grandes• Alcance mas allá de TIA-568B “Equipment Room”
Términos clave:• MDA: Main Distribution Area
• EDA: Equipment Distribution Area
• Computer Room y Operations Center
![Page 114: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/114.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-942 Actualización Standard
Data Center: Infraestructura en gran escala de computadora s
![Page 115: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/115.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Data Center
Espacio utilizado para contener sistemas de computo y sus componentes asociados, como telecomunicaciones y sistemas de almacenaje.
Generalmente incluyen fuentes de energía redundante o de respaldo, conexiones de comunicaciones redundantes y controles ambientales (por ejemplo aire acondicionado, sistema contra incendios).
![Page 116: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/116.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-942: Elementos Clave
Personal Soporte
Eléctrico & Mecánico
Centro Operaciones
TR
Cuarto Entrada
Cuarto Computo
MC
AP
Cableado Horizontal & Backbone para Data Center
O/S TR’s
EQ EQ EQEQEQ
![Page 117: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/117.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-942: Elementos Clave
Switch Servidor
Cableado Backbone para el Cuarto Computo
Switch Servidor
Switch Servidor
Switch Servidor
MDA
MC, Router, Switch, PBX
Data Center TR
Cuarto Entrada AP
ExternosTR’s
EDA
Cuarto Computo
![Page 118: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/118.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-942: Elementos Clave
Parámetros Clave de Diseño Data Center
Eléctricos• Balanceo de cargas, no-interruptores, circuitos dedicados
• Puesta a tierra y protección de circuitos
• Alarmas, seguridad y control accesos
Mecánicos• Disposición de equipos y capacidad de carga del piso
• Capacidad de enfriamiento del equipo activo
• Trazado de Pasillos Calientes / Pasillos Fríos para enfriamiento de equipos activos
• HVAC, filtración de aire, control humedad
![Page 119: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/119.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-942 Elementos Clave
Parámetros Clave de Diseño Data Center
Arquitecturales• Tamaño cuarto, altura del cielo, puertas, señalización,
contraenchapes, etc.
Tolerancia a Fallas y recuperación de desastres• Rutas de cables horizontales y backbone redundantes
• Servidores y switches Back-up
• Back-up de potencia eléctrica y HVAC
• Ubicación de entradas de AP & SP redundantes
• Protección contra fuego, inundación, y sismos
• Protección contra rayos y picos de voltaje
![Page 120: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/120.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Actualización TIA -942A
Norma TIA -942 aprobada en 2005. Proceso de revisión cada 5 años, ya inicio. Cambios para armonizar esquema de normas:
• Referencias a cableados genéricos y términos con re ferencia a TIA/EIA-568C
• Mueve contenido de Puesta a Tierra a TIA-607B
• Elimina referencia de etiquetado y hace referencia a TIA-606A Adendum 1
• Mueve contenido sobre Racks y Gabinetes a TIA-569C
Incorpora Adendums aprobados. Armoniza términos con norma Internacional IEC
24764 (aprobada recientemente).
![Page 121: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/121.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Actualización TIA -942A
AdendumAdendum 2 2 (a incorporar)(a incorporar) ::
• Aprobada finales 2009
• Busca mejorar la eficiencia del DataCenter
• Mayores rangos de temperatura y humedad por nuevos estudios ASHRAE
• Especifica 3 niveles de iluminación para reducir el uso de potencia.
• Agrega Cat6A como medio aceptado y recomendado de transmisión en UTP.
![Page 122: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/122.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Actualización TIA -942A
Nueva InformaciNueva Informaci óón:n:
• Nueva sección para Diseño Eficiente en energía (adicionales a Adedum 2) con guías para diseño de rutas y espacio para mejorar eficiencia energética.
• Agrega un nuevo espacio “Intermediate Distribution Area”IDA con un segundo nivel de Backbone necesario en DataCenters de gran tamaño.
![Page 123: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/123.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-1005 Cableado Industrial
Borrador del estándar en desarrollo por el SubcomiteTR-42.9 Telecomunicaciones Industriales
Clasificaciones de protección contra ingreso NEMA y IEC adoptadas
![Page 124: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/124.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-1005 Actualización Borrador Standard
Parámetros de diseño MICE:• Mecánicos (golpe, vibración, impacto)
• Ingreso (entrada de contaminantes)
• Clim áticos (temperatura, humedad, exposición U.V., lluvia, etc.)
• Electromagnéticos (EMI – conducido o radiado)
![Page 125: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/125.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-1005: Elementos Clave
Envolventes deben satisfacer clasificaciones NEMA especificas
Conectores deben satisfacer clasificaciones IEC especificas
• IEC especifica la clasificación IP (IngressProtection)
•Ingreso es la entrada de contaminantes
![Page 126: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/126.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-1005: Elementos Clave
Clasificaciones NEMA para Gabinetes
Rocío presurizado de aguaX
Polvo sopladoX
Agua salpicadaXX
Polvo circulanteXX
Lluvia, nieveXX
Caída de SuciedadXXX
CondiciónNEMA 4xNEMA 12NEMA 3R
Nota: NEMA 12 es solamente para uso interno
![Page 127: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/127.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-1005: Elementos Clave
Clasificación Protección contra Ingreso IEC
Mayor numero = Mayor Grado de protección.
Equipo debe ser instalado adecuadamente
IP67
Primer Numero: grado de protección de ingreso de partículas sólidas
Segundo Numero: grado de protección de ingreso de agua
![Page 128: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/128.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA/EIA-1005: Elementos Clave
Clasificación IP Industrial IEC
IP66: Polvo y rocío de agua a baja presión
IP67: Polvo y rocío de agua a alta presión
IP68: Polvo e inmersión en agua
![Page 129: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/129.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
Conector Ethernet Industrial
Estándar RJ-45 Plug & Jack
Clasificación IP67 cuando esta conectado
Recomendado para ambientes hostiles
![Page 130: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/130.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-1179 Hospitales
Healthcare FacilityCabling Standard
Responder a la necesidad de contar con un sistema de cableado optimizado para Hospitales.
![Page 131: Ch1 Standard Espanolmx](https://reader034.fdocuments.net/reader034/viewer/2022042500/547ca2d2b4af9f42138b45d6/html5/thumbnails/131.jpg)
Copyright © 1/02 by Hubbell Premise WiringReproduction restricted by law
TIA-1179 Hospitales
Cambios Notables:
Recomienda Cat6A para nuevas instalaciones
Distancia m áxima en FO puede ser mayor a 90m (UTP) basado en medio y aplicación (según Anexo D TIA-568C.0)
Cat3 no permitida en Cableado Horizontal y solo condicionado a Backbone para aplicaciones de Voz Análoga.