1 Part Number 18014, Revision H, 09/01/2017 Clean Agent HFC-227ea CG2XXXX227-BXXXX Automatic, 175°F (79°C) Sizes: 25-1000 cu. ft. 0.7-28.3 cu. m MA2XXXX227-BLXXX Manual/Automatic, 175°F (79°C) Sizes: 25-1500 cu. ft. 0.7-42.5 cu. m Owner’s Manual & Installation Instructions Project ID: 0003045895 U.S. Coast Guard Approved No. 162.029/249/0 No. 162.029/251/0 Read and comply with all instructions, warnings and limitations before installing, servicing or removing this device.

Transcript of CG2XXXX227-BXXXX MA2XXXX227-BLXXX...Fireboy FM Component Approved HFC-227ea Systems are approved for...

  • 1 Part Number 18014, Revision H, 09/01/2017

    Clean Agent HFC-227ea

    CG2XXXX227-BXXXX Automatic, 175°F (79°C)

    Sizes: 25-1000 cu. ft. 0.7-28.3 cu. m

    MA2XXXX227-BLXXX

    Manual/Automatic, 175°F (79°C) Sizes: 25-1500 cu. ft. 0.7-42.5 cu. m

    Owner’s Manual &

    Installation Instructions

    Project ID: 0003045895

    U.S. Coast Guard Approved No. 162.029/249/0 No. 162.029/251/0

    Read and comply with all instructions, warnings and limitations before installing, servicing or removing this device.

  • 2 Part Number 18014, Revision H, 09/01/2017

    Additional copies of this manual are available at no charge by contacting the manufacturer, distributor or dealer. Fireboy-Xintex reserves the right to change features without notice. General Information 3 Specifications 4 Operation of Fireboy Fire Extinguisher 7 Marine Installation Instructions 8 Before Installation 8 Selecting Location 8 Mounting Fireboy System 10 Cable Installation (P/N: E-4209-XXX, XXX = Length in Feet) 11 Routing Cable 12 Legend Plate and T-Handle 13 Connecting Cable to Cylinder 15 Accommodating Diesel Engines 18 Installing Indicator Lamp (P/N: 90107) 18

    Mounting Indicator Lamp 18 Wiring Indicator Lamp 19

    Connecting to Powered Ventilation 20

    Installation Checklist 21 Maintaining Fireboy Fire Extinguisher 22 Disconnection and Inspection of Manual Discharge Cable 22 Maintaining the Indicator Lamp Circuit 23 Health and Safety 23 Additional Equipment 25 Safety Data Sheet 26 Returning Fireboy-Xintex Equipment 32 Recharging Fireboy Extinguishers 32 3 Year Limited Warranty 33

  • 3 Part Number 18014, Revision H, 09/01/2017

    General Information

    Fireboy Automatic (CG series) and Manual/Automatic (MA) series Fire Extinguishing Systems are manufactured for a broad range of applications, including marine, industrial, and commercial uses. This booklet is intended to outline the proper installation of the system for marine applications; most applications are similar. If further technical advice is required, information is available by contacting Fireboy-Xintex. Fireboy FM Component Approved HFC-227ea Systems are approved for use in normally occupied spaces and are approved for use within the European Union. The National Fire Protection Agency defines normally occupied enclosure or space as “an enclosure or space where one or more persons are present under normal conditions.” (NFPA-2001). SDS Sheets are available at no charge from the manufacturer and online at www.fireboy-xintex.com. Referenced Agencies: Bureau Veritas 3663 N. Sam Houston Pkwy. E., Suite 200 Houston, TX 88034 National Fire Protection Agency 1 Batterymarch Park Quincy, MA 02269-9101 NFPA 2001, Standard on Clean Agent Fire Extinguishant Systems FM Approvals 1151 Boston Providence Turnpike Norwood, MA 02062 United States Coast Guard 2100 Second Street SW Washington, DC 20593-0001 RINA 10 Upper Belgrave Street London, SWIX 8BQ

  • 4 Part Number 18014, Revision H, 09/01/2017

    General Information Continued

    WARNING:

    1. NEVER INSTALL A FIREBOY SYSTEM ON THE UNDERSIDE OF A HATCH COVER OR ON AN ACCESS DOOR THAT MAY OPEN OR SEPARATE IN AN EXPLOSION

    2. NEVER INSTALL THE ACTUATOR OF A FIREBOY SYSTEM IN CLOSE PROXIMITY TO EXHAUST MANIFOLDS OR TURBOCHARGERS. RADIATED HEAT MAY CAUSE PREMATURE ACTUATION

    3. NEVER INSTALL THE ACTUATOR OF A FIREBOY SYSTEM BELOW THE CYLINDER (UPSIDE DOWN)

    4. NEVER INSTALL A FIREBOY SYSTEM WHERE IT WILL TRAP OR BE IN DIRECT CONTACT WITH WATER

    5. NEVER INSTALL A FIREBOY UNIT IN A COMPARTMENT LARGER THAN ITS VOLUME RATING

    6. NEVER COMBINE THE VOLUME RATING OF TWO OR MORE FIREBOY UNITS TO PROTECT A GIVEN COMPARTMENT

    7. THIS DEVICE SHALL NOT BE INSTALLED OR USED IN AIRCRAFT AND/OR RACING VEHICLES 8. DIESEL POWERED CRAFT MUST ALSO INSTALL THE AUTOMATIC ENGINE SHUTDOWN

    SYSTEM OR THIS SYSTEM MAY NOT EXTINGUISH THE FIRE (SEE ADDITIONAL EQUIPMENT)

    9. FIREBOY SYSTEMS ARE NOT, NOR ARE THEY INTENDED TO BE, EXPLOSION SUPPRESSION DEVICES. THEY DO NOT LESSEN THE NEED TO INSPECT FOR FIRE HAZARDS AND TO VENTILATE ANY AREA WHERE FLAMMABLE FUMES MAY ACCUMULATE.

    10. IN CASE OF ACCIDENTAL DISCHARGE, EVACUATE PROTECTED SPACE AND VENTILATE. DO NOT RETURN TO AREA UNTIL SPACE IS CLEAR OF AGENT. REFER TO HEALTH AND SAFETY SECTION (PAGE 23).

    Specifications

    CG2XXXX227-BXXXX and MA2XXXX227-BLXXX series extinguishers discharge automatically at a temperature of 175°F (79°C). MA2XXXX227-BLXXX series extinguishers may be discharged manually at any temperature. All models introduce an atmospheric concentration of 8.7% into the protected space. This concentration includes a 30% safety factor to the 6.7% Minimum Extinguishing Concentration (MEC). Operational temperature range of extinguishers is 32°F (0°C) to 130°F (54°C).

    Volume

    Protected Diameter

    Total Height

    Agent Weight

    Shipping Weight

    System Pressure (@70° F)

    Model Number ft³ m³ in mm in mm lbs kgs lbs kgs psi

    CG20025227-BXXXX 25 0.7 3.3 85 9.5 241 1.1 0.5 5 2.4 240

    CG20050227-BXXXX 50 1.4 3.3 85 13.3 338 2.2 1.0 8 3.7 240

    CG20075227-BXXXX 75 2.1 4.3 110 15.6 396 3.2 1.5 13 6.0 240

    CG20100227-BXXXX 100 2.8 4.3 110 15.6 396 4.3 2.0 14 6.4 240

    CG20125227-BXXXX 125 3.5 4.3 110 15.6 396 5.4 2.5 15 6.9 240

    CG20150227-BXXXX 150 4.3 5.1 130 17.2 436 6.5 2.9 20 9.2 240

  • 5 Part Number 18014, Revision H, 09/01/2017

    Volume

    Protected Diameter

    Total Height

    Agent Weight

    Shipping Weight

    System Pressure (@70° F)

    Model Number ft³ m³ in mm in mm lbs kgs lbs kgs psi

    CG20175227-BXXXX 175 4.9 5.1 130 17.2 436 7.6 3.4 21 9.6 240

    CG20200227-BXXXX 200 5.7 5.1 130 17.2 436 8.6 3.9 22 10.0 240

    CG20225227-BXXXX 225 6.4 6.3 160 17.3 439 9.7 4.4 29 13.2 240

    CG20250227-BXXXX 250 7.0 6.3 160 17.3 439 10.8 4.9 30 13.6 240

    CG20275227-BXXXX 275 7.8 6.3 160 17.3 439 11.9 5.4 31 14.1 240

    CG20300227-BXXXX 300 8.5 6.3 160 17.3 439 13.0 5.9 32 14.5 240

    CG20325227-BXXXX 325 9.2 7.1 180 17.2 437 14.0 6.4 37 16.9 240

    CG20350227-BXXXX 350 10.0 7.1 180 17.2 437 15.1 6.9 38 17.4 240

    CG20375227-BXXXX 375 10.6 7.1 180 17.2 437 16.2 7.4 39 17.8 240

    CG20400227-BXXXX 400 11.3 7.1 180 19.4 493 17.3 7.9 43 19.5 240

    CG20450227-BXXXX 450 12.7 7.1 180 19.4 493 19.4 8.8 45 20.4 240

    CG20500227-BXXXX 500 14.1 7.1 180 27.4 696 21.6 9.8 55 24.8 240

    CG20550227-BXXXX 550 15.6 7.1 180 27.4 696 23.8 10.8 57 25.7 240

    CG20600227-BXXXX 600 17.0 7.1 180 27.4 696 25.9 11.8 60 27.0 240

    CG20650227-BXXXX 650 18.4 7.1 180 27.4 696 28.1 12.8 62 28.3 240

    CG20700227-BXXXX 700 19.8 7.1 180 27.4 696 30.2 13.7 64 29.2 240

    CG20750227-BXXXX 750 21.2 7.1 180 33.3 846 32.4 14.7 70 31.6 360

    CG20800227-BXXXX 800 22.6 7.1 180 33.3 846 34.6 15.7 73 33.0 360

    CG20850227-BXXXX 850 24.0 7.1 180 33.3 846 36.7 16.7 76 34.3 360

    CG20900227-BXXXX 900 25.5 7.1 180 33.3 846 38.9 17.7 77 35.1 360

    CG20950227-BXXXX 950 26.9 7.1 180 33.3 846 41.0 18.7 80 36.4 360

    CG21000227-BXXXX 1000 28.3 10.0 254 21.4 544 43.2 19.6 93 42.2 360

    MA20025227-BLXXX 25 0.7 3.3 85 9.5 241 1.1 0.5 5 2.4 240

    MA20050227-BLXXX 50 1.4 3.3 85 13.3 338 2.2 1.0 8 3.7 240

    MA20075227-BLXXX 75 2.1 4.3 110 15.6 396 3.2 1.5 13 6.0 240

    MA20100227-BLXXX 100 2.8 4.3 110 15.6 396 4.3 2.0 14 6.4 240

    MA20125227-BLXXX 125 3.5 4.3 110 15.6 396 5.4 2.5 15 6.9 240

    MA20150227-BLXXX 150 4.3 5.1 130 17.2 436 6.5 2.9 20 9.2 240

    MA20175227-BLXXX 175 4.9 5.1 130 17.2 436 7.6 3.4 21 9.6 240

    MA20200227-BLXXX 200 5.7 5.1 130 17.2 436 8.6 3.9 22 10.0 240

    MA20225227-BLXXX 225 6.4 6.3 160 17.3 439 9.7 4.4 29 13.2 240

    MA20250227-BLXXX 250 7.0 6.3 160 17.3 439 10.8 4.9 30 13.6 240

    MA20275227-BLXXX 275 7.8 6.3 160 17.3 439 11.9 5.4 31 14.1 240

  • 6 Part Number 18014, Revision H, 09/01/2017

    Specifications Continued

    Volume

    Protected Diameter

    Total Height

    Agent Weight

    Shipping Weight

    System Pressure (@70° F)

    Model Number ft³ m³ in mm in mm lbs kgs lbs kgs psi

    MA20300227-BLXXX 300 8.5 6.3 160 17.3 439 13.0 5.9 32 14.5 240

    MA20325227-BLXXX 325 9.2 7.1 180 17.2 437 14.0 6.4 37 16.9 240

    MA20350227-BLXXX 350 10.0 7.1 180 17.2 437 15.1 6.9 38 17.4 240

    MA20375227-BLXXX 375 10.6 7.1 180 17.2 437 16.2 7.4 39 17.8 240

    MA20400227-BLXXX 400 11.3 7.1 180 19.4 493 17.3 7.9 43 19.5 240

    MA20450227-BLXXX 450 12.7 7.1 180 19.4 493 19.4 8.8 45 20.4 240

    MA20500227-BLXXX 500 14.1 7.1 180 27.4 696 21.6 9.8 55 24.8 240

    MA20550227-BLXXX 550 15.6 7.1 180 27.4 696 23.8 10.8 57 25.7 240

    MA20600227-BLXXX 600 17.0 7.1 180 27.4 696 25.9 11.8 60 27.0 240

    MA20650227-BLXXX 650 18.4 7.1 180 27.4 696 28.1 12.8 62 28.3 240

    MA20700227-BLXXX 700 19.8 7.1 180 27.4 696 30.2 13.7 64 29.2 240

    MA20750227-BLXXX 750 21.2 7.1 180 33.3 846 32.4 14.7 70 31.6 360

    MA20800227-BLXXX 800 22.6 7.1 180 33.3 846 34.5 15.6 73 33.0 360

    MA20850227-BLXXX 850 24.0 7.1 180 33.3 846 36.7 16.7 76 34.3 360

    MA20900227-BLXXX 900 25.5 7.1 180 33.3 846 38.9 17.7 77 35.1 360

    MA20950227-BLXXX 950 26.9 7.1 180 33.3 846 41.0 18.7 80 36.4 360

    MA21000227-BLXXX 1000 28.3 10.0 254 21.4 544 43.2 19.6 93 42.2 360

    MA21050227-BLXXX 1050 29.7 10.0 254 21.4 544 45.3 20.5 96 43.5 360

    MA21100227-BLXXX 1100 31.1 10.0 254 21.4 544 47.5 21.6 99 44.9 360

    MA21150227-BLXXX 1150 33.0 10.0 254 27.5 699 49.7 22.6 108 49.0 360

    MA21200227-BLXXX 1200 34.0 10.0 254 27.5 699 51.8 23.6 111 50.3 360

    MA21250227-BLXXX 1250 35.4 10.0 254 27.5 699 54.0 24.5 113 51.3 360

    MA21300227-BLXXX 1300 36.8 10.0 254 27.5 699 56.1 25.4 116 52.6 360

    MA21350227-BLXXX 1350 38.2 10.0 254 27.5 699 58.3 26.5 119 54.0 360

    MA21400227-BLXXX 1400 39.6 10.0 254 27.5 699 60.5 27.5 121 54.9 360

    MA21450227-BLXXX 1450 41.0 10.0 254 27.5 699 62.6 28.5 124 56.2 360

    MA21500227-BLXXX 1500 42.5 10.0 254 27.5 699 64.8 29.5 126 57.2 360

    Low Profile Models

    CG20750227-B4XXX 750 21.2 10.0 254 21.4 544 32.4 14.7 80 36.3 360

    CG20800227-B4XXX 800 22.6 10.0 254 21.4 544 34.5 15.6 83 37.6 360

    CG20850227-B4XXX 850 24.0 10.0 254 21.4 544 36.7 16.7 86 39.0 360

    CG20900227-B4XXX 900 25.5 10.0 254 21.4 544 38.9 17.7 88 39.9 360

  • 7 Part Number 18014, Revision H, 09/01/2017

    Volume

    Protected Diameter

    Total Height

    Agent Weight

    Shipping Weight

    System Pressure (@70° F)

    Model Number ft³ m³ in mm in mm lbs kgs lbs kgs psi

    CG20950227-B4XXX 950 26.9 10.0 254 21.4 544 41.0 18.7 91 41.3 360

    MA20750227-BL4XX 750 21.2 10.0 254 21.4 544 32.4 14.7 80 36.3 360

    MA20800227-BL4XX 800 22.6 10.0 254 21.4 544 34.5 15.6 83 37.6 360

    MA20850227-BL4XX 850 24.0 10.0 254 21.4 544 36.7 16.7 86 39.0 360

    MA20900227-BL4XX 900 25.5 10.0 254 21.4 544 38.9 17.7 88 39.9 360

    MA20950227-BL4XX 950 26.9 10.0 254 21.4 544 41.0 18.7 91 41.3 360 All above models are approved under U.S.C.G. # 162.029/249/0, # 162.029/251/0. When specifications listed on the label differ from this manual, the information listed on the label is correct. 240psi = 1655kPa = 16.5Bar 360psi = 2482kPa = 24.8Bar

    Operation of Fireboy Fire Extinguisher

    Manual operation of MA2XXXX227-BLXXX Systems 1. In case of fire, do not wait for automatic actuation. 2. Close all hatches leading to the protected compartment. 3. Shutdown all forced ventilation devices, engines, generators and electrical systems. 4. Remove the safety pin from the “FIRE” T-handle, and pull firmly.

    Automatic operation of CG2XXXX227-BXXXX and MA2XXXX227-BLXXX systems

    Actuation of a Fireboy fire extinguisher occurs at 175°F (79°C) and is entirely dependent on the intensity of the fire.

    Signs of actuation 1. A loud sound similar to small arms fire. 2. A loud sound of rushing air. 3. The green indicator lamp is not illuminated. 4. A stalled engine.

    When actuation occurs

    1. Immediately shutdown all engines, powered ventilation, and electrical systems. 2. Extinguish all smoking materials. 3. Do not open the engine compartment. 4. The protected space may see an increase in pressure during discharge. Appropriate

    relief vents may be needed where structural integrity of protected space is in question.

  • 8 Part Number 18014, Revision H, 09/01/2017

    Operation of Fireboy Fire Extinguisher Continued

    After actuation 1. Before inspecting for damage, allow the agent to “soak” the compartment for at least

    15 minutes and wait for hot metals or fuels to cool. 2. Have approved portable extinguishers in hand and ready for use. 3. Do not breathe fumes or vapors caused by the fire and/or suppression agent. They are

    hazardous and toxic. Refer to Health and Safety section (Page 23). 4. Forced ventilation will often be necessary. Care should be taken to readily dissipate

    hazardous atmospheres and not merely move them to another location. Consideration should be given to exhaust paths when opening or venting the enclosure after discharge. Ventilation should not be directed near any area that might be used as a gathering spot for personnel.

    Marine Installation Instructions

    Before Installation 1. Check the system for damage during shipment. 2. Check the pressure gauge to be sure the gauge pointer lies within the green zone at 70°F

    (21°C). 3. The correct weight is shown on the label for the appropriate model. 4. Select an interior location not directly subject to weather or seawater. 5. Confirm the volume of the compartment to be protected in cubic feet or cubic meters

    by multiplying the width, by the length, by the depth at the keel; make no deductions for installed equipment.

    6. Verify calculated volume with volume shown on label and model specifications section.

    Selecting a Location 1. Do not install a Fireboy system rated for less cubic volume than the volume of the

    compartment to be protected. 2. The maximum approved distance from the cylinder nozzle to ceiling is 20in (508mm). 3. Orientation:

    Mounting up to 90° from vertical is permissible

    Install on the forward or aft vertical bulkhead of the engine compartment as near to the centerline of the vessel (keel) as possible.

    To prevent accelerated corrosion, do not mount directly to an aluminum/metal surface. Maintain galvanic isolation between the extinguisher and metal mounting surface.

    Direct the actuator towards the opposite bulkhead or towards the engine(s)

    Avoid installing athwart ship (perpendicular to the keel) on sailboats

  • 9 Part Number 18014, Revision H, 09/01/2017

    4. The approved ceiling height of the protected space is as follows:

    Models 025-300: 2.2ft (0.7m) to 6.3ft (1.9m)

    Models 325-700: 3.0ft (0.9m) to 7.0ft (2.1m)

    Models 750-1500: 4.0ft (1.2m) to 9.0ft (2.7m)

    5. The maximum approved radial reach and area of coverage is as follows:

    Models 025-300: 10.6ft (3.2m), 89.3ft² (8.3m²)

    Models 325-700: 13.4ft (4.1m), 144ft² (13.4m²)

    Models 750-1500: 19.4ft (5.9m), 303ft² (28.1m²)

  • 10 Part Number 18014, Revision H, 09/01/2017

    Mounting Fireboy system

    DANGER:

    ACCIDENTAL DISCHARGE DURING HANDLING OR INSTALLATION MAY CAUSE SERIOUS INJURY. DO NOT LIFT, CARRY, OR HANDLE BY ACTUATOR, PRESSURE SWITCH, OR CABLE. WEAR EYE PROTECTION WHEN INSTALLING OR SERVICING CYLINDER. REFER TO HEALTH AND SAFETY SECTION (PAGE 23).

    Models 025-200

    1. Use appropriate size and length bolts and lock washers and secure using all 4 mounting holes.

    2. Mounting hardware can be installed with cylinder clamped in bracket.

    Models 225-700 1. Generously loosen cylinder clamps and remove cylinder. 2. Locate cylinder in safe and secure location to prevent cylinder from tipping. 3. Use appropriate size and length bolts and lock washers and secure bracket using all

    6 mounting holes. 4. With bracket secured, place cylinder back in bracket and tighten cylinder clamps.

    Models 225-700 0.44in (11.2mm) Dia. Through Hole 6 Places 225-300 P/N: 93014 325-375 P/N: 93015 400-450 P/N: 93016 500-700 P/N: 93017

    Models 075-125 0.20in (5.1mm) Dia. Through Hole 4 Places 075-125 P/N: 93012 Models 150-200 0.27in (6.9mm) Dia. Through Hole 4 Places 150-200 P/N: 93013

    Models 025-050 0.18in (4.8mm) Dia. Through Hole 4 Places 025 P/N: 93010 050 P/N: 93011

  • 11 Part Number 18014, Revision H, 09/01/2017

    Models 750-1500 1. Use appropriate size and length bolts and lock washers and fasten to bulk head. 2. Mount the Shelf Brackets using the 6 mounting holes. Be sure to include unistrut

    while mounting bracket. 3. Locate upper bracket 1in (25.4mm) below the top weld seam of cylinder. Be sure to

    include spacer while mounting unistrut. 4. Install Clamps in unistrut and tighten with provided fasteners.

    Cable Installation (P/N: E-4209-XXX, XXX = Length in Feet)

    WARNING:

    1. ALL FIREBOY MA2XXXX227-BLXXX SYSTEM INSTALLATIONS MUST USE ONLY GENUINE FIREBOY CABLES AND ASSOCIATED COMPONENTS THAT ARE ENGINEERED SPECIFICALLY FOR THIS APPLICATION. NOTHING ELSE WILL PROVIDE THE INTENDED DEGREE OF SAFETY AND RELIABILITY INHERENT IN THESE SYSTEMS.

    2. ANY SUBSTITUTION WILL VOID ALL LABORATORY AND COAST GUARD APPROVALS AND FIREBOY-XINTEX WARRANTIES, AND MAY RESULT IN AN INOPERATIVE SYSTEM, AND UNSAFE AND HAZARDOUS CONDITIONS.

    3. NEVER INSTALL A MANUAL RELEASE HANDLE IN THE SPACE TO BE PROTECTED. 4. NEVER INSTALL A CABLE ON A CG2XXXX227-BXXXX SERIES. FOR USE ON

    MA2XXXX227-BLXXX SERIES ONLY.

    NOTE:

    1. IF A DUAL RELEASE ADAPTER (DRA-1001) IS TO BE USED WITH THIS INSTALLATION, FOLLOW THE INSTRUCTIONS ENCLOSED WITH THAT UNIT AT THIS TIME.

    2. FACTORY MUTUAL AND THE USCG REQUIRE MANUAL ACTUATION CABLES FOR ALL INSTALLATIONS OVER 1000 CU.FT.

    0.56in (14.2mm) Dia. Through Hole 10 Places

    Washer (P/N: 61007) Nut (P/N: 61009)

    Bolt (P/N: 61006)

    Shelf Bracket 600-750 P/N: 93090-100 800-1500 P/N: 93050-100

    Unistrut 600-750 P/N: 93092 800-1500 P/N: 93052

    Clamp 600-750 P/N: 93094 800-1500 P/N: 93054

    Spacer 600-750 P/N: 93092 800-1500 P/N: 93052

  • 12 Part Number 18014, Revision H, 09/01/2017

    Cable Installation Continued

    CAUTION:

    DO NOT CONNECT CABLE TO CYLINDER AT THIS TIME!

    Routing the Cable 1. Locate the legend plate (1.9in (48mm) x 3.6in (92mm) with 7/16in (11.1mm) hole) for

    the manual release handle.

    On a solid and secure surface (Minimum of ¼in (6.4mm) thick)

    In full view of the operator

    With enough clearance for the cable ferrule to extend approximately 12in (304.8mm) behind the panel

    Angle Adaptor CAA-0285-01 available where clearance is limited 2. Using the legend plate as a template, locate and drill a 13/32in (10.3mm) hole. 3. Route the cable in the most direct manner, with as few bends as possible, to the

    cylinder location.

    Do not bend in a radius of less than 6in (152.4mm) (a 12in (304.8mm) circle)

    Follow the same route as manufacturer installed cables, if possible (Example: Steering, throttle, and transmission cables)

    Do not subject cable to pinching or crushing, rubbing, extreme vibration, sharp bending or kinking, or extremes of heat or cold

    Do not exceed 1440° of total bends (Example: 16 bends x 90° = 1440°)

    Use the shortest allowable cable whenever possible

    Maximum manual cable length is 100ft (30.5m) 4. Secure loose sections of the cable with the included nylon clamps.

    Do not clamp cable in a bend

    Do not crush cable with clamps

  • 13 Part Number 18014, Revision H, 09/01/2017

    Legend Plate and T-Handle

    Thread Ferrule onto Cable using 3 full revolutions. Adjust Ferrule so that holes are parallel to the floor and tighten Nut.

    Note: Do NOT thread further than Ferrule’s internal threads.

    Ferrule

    3/8-24 Nut

    Lock Washer

    Helm

    NOTE: Temperature must be above +50°F (10°C) for proper adhesion.

    Legend Plate

    Peel off paper and Press legend plate firmly press in place. Install 3/8-24 Nut and Lock Washer on Cable and position through hole. Leave enough space to tighten later.

    Cable P/N: 90033-XXX

    3/8-24 Nut P/N: 50002

    Safety Pin P/N: ALPP-0247-01

    Helm

    13/32in (10.3mm) Hole

    Lock Washer P/N: 14104

    Legend Plate P/N: 90237

    Ferrule P/N: F-1001-01

    O-Ring P/N: AS 568-202

    T-Handle P/N: K-2016R

    Drill 13/32in (10.3mm) hole in desired location for Pull Station.

  • 14 Part Number 18014, Revision H, 09/01/2017

    Legend Plate and T-Handle Continued

    O-Ring

    T-Handle Slide O-Ring onto Cable. Thread T-Handle onto Cable 7 Full turns. Make sure not to obstruct through hole.

    Push T-Handle into Ferrule to align through holes. There will be resistance from O-Ring.

    With Cable DISCONNECTED from extinguisher, take this time to test Cable operation. Cable should slide freely.

    Tamper Seal

    Pin

    Insert Pin into Ferrule and T-Handle through holes. Wrap Tamper Seal through loop of Safety Pin and around Ferrule. Insert end of seal into side marked “ENTER” and pull tight.

  • 15 Part Number 18014, Revision H, 09/01/2017

    Connecting Cable to Cylinder

    Safety Pin

    Extinguisher should be securely mounted and Cable should be routed. Be sure the Safety Pin is in place.

    Insert extinguisher end of Cable through hole in Manifold past retaining slot on Cable.

    Cable Retaining Slot

    Manifold

  • 16 Part Number 18014, Revision H, 09/01/2017

    Connecting Cable to Cylinder Continued

    Insert S-Hook into hole at the top of Actuation Lever.

    S-Hook

    Actuation Lever

    Align retaining slot of Cable with retaining slot of Manifold.

    Manifold Retaining Slot

    S-Hook

    Actuation Lever

  • 17 Part Number 18014, Revision H, 09/01/2017

    Secure Cable to Manifold with Retaining Clip.

    Retaining Clip

    Safety Pin Storage

    With T-Handle previously secured, remove Red Tamper Seal from Extinguisher to remove Safety Pin and store in provided location.

    Cable system is now operational.

    Safety Pin

    Actuation Lever

    Base Bracket

    Red Tamper Seal

  • 18 Part Number 18014, Revision H, 09/01/2017

    Accommodating Diesel Engines

    WARNING:

    FAILURE TO INSTALL AN ENGINE SHUTDOWN BOX WITH A FIREBOY SYSTEM IN ANY DIESEL ENGINE APPLICATION IMPEDES THE FIRE EXTINGUISHER AND MAY PREVENT FIRE EXTINGUISHMENT.

    CAUTION:

    FAILURE TO CONNECT A POWERED VENTILATION SYSTEM IN THE MANNER DESCRIBED BELOW IMPEDES FIRE EXTINGUISHER AND MAY PREVENT FIRE FROM BEING EXTINGUISHED.

    1. Automatic Engine Shutdown units are available through your Fireboy-Xintex

    distributor, dealer or retailer in three, five, eight, and ten circuit models. 2. Follow the installation instructions included with the Automatic Engine Shutdown

    for proper installation. 3. Technical Support for Automatic Engine Shutdowns is available by calling Fireboy-

    Xintex or visiting our website at www.fireboy-xintex.com.

    Installing Indicator Lamp (P/N: 90107)

    Mounting Indicator Lamp

    1. U.S. Coast Guard Rule 162.029 requires an indicator lamp and legend plate at each helm position from which the craft may be operated.

    2. Your Fireboy System is supplied with one (1) indicator lamp and legend plate. Additional indicator lamps and legend plates are available factory direct, or through an authorized dealer.

    3. Select an appropriate location for the indicator lamp and legend plate on or near the instrument panel at the helm and in full view of the operator.

    4. Drill a 9/16in (14.3mm) hole. 5. Remove the backing paper on the legend plate. 6. Feed both wires through 9/16in (14.3mm) hole. 7. Press legend plate firmly press in place.

    Drill 9/16in (14.3mm) Hole

    Helm

    Indicator Lamp P/N: 90107

    NOTE: Temperature must be above +50°F (10°C) for proper adhesion.

    http://www.fireboy-xintex.com/

  • 19 Part Number 18014, Revision H, 09/01/2017

    NOTE:

    THE INDICATOR LAMP SUPPLIED IS FOR 12/24 VDC USE

    WARNING:

    1. AN ELECTRICAL SHORT MAY RESULT IN ELECTRICAL BURN, INJURY OR FIRE 2. BEFORE ATTEMPTING TO WIRE THE INDICATOR LAMP, TURN OFF ALL ELECTRICAL

    CURRENT TO THE IGNITION SWITCH 3. ALL FIREBOY WIRING MUST COMPLY WITH THE AMERICAN BOAT AND YACHT

    COUNCIL STANDARD E-11, TITLED AC AND DC ELECTRICAL SYSTEMS ON BOATS, AVAILABLE FROM ABYC, WWW.ABYCINC.ORG

    Wiring Indicator Lamp

    1. Review all wiring instructions below. 2. Consult a qualified marine electrician if you have any doubts about your ability to

    safely and properly complete the wiring. Ignition systems and electrical systems vary from boat to boat, and the directions which follow, may not apply to your boat.

    3. Assemble the supplies you will need that are not included with your Fireboy System.

    The necessary length of insulated 16 gauge (minimum) stranded wire

    A one-half (0.5) ampere in-line fuse and fuse holder or circuit breaker

    Properly sized insulated crimp-on wire connectors 4. Connect one lead of the fuse to the “ON” position of the starter switch. 5. Connect the other lead of the fuse to the red (+) wire of the LED indicator lamp. 6. Connect the black (-) wire of the indicator lamp to one of the pigtail wires on the

    Fireboy System (as shown below). 7. Do not reverse red and black wire, indicator lamp will not function. 8. Connect the remaining wire from the Fireboy system to ground.

    http://www.abycinc.org/

  • 20 Part Number 18014, Revision H, 09/01/2017

    Connecting to Powered Ventilation

    Engine compartments not equipped with a powered ventilation system require no further wiring. If the engine compartment is equipped with a powered ventilation system, U.S. Coast Guard Rule 162.029 requires that the ground connection of the ventilation system be connected to the Fireboy system.

    CAUTION:

    FAILURE TO CONNECT A POWERED VENTILATION SYSTEM IN THE MANNER DESCRIBED BELOW IMPEDES FIRE EXTINGUISHER AND MAY PREVENT FIRE FROM BEING EXTINGUISHED.

    Powered Ventilation Systems (Blowers) 1. Determine the maximum current draw of the powered ventilation system. 2. For current draw not exceeding 5 amps connect the negative (-) wire from the

    ventilation blower to the pressure switch at the same point as the indicator lamp. 3. For current draw exceeding 5 amps, use a Fireboy Automatic Engine Shutdown

    system.

    NOTE:

    THE LEGEND PLATE LED IS CONNECTED TO THE PRESSURE SWITCH AT THE SAME POINT THAT AUXILIARY DEVICES CAN BE CONNECTED. CARE MUST BE TAKEN WHEN WIRING OTHER DEVICES TO THE PRESSURE SWITCH TO ENSURE THE PRESENCE OF THE LED DOES NOT AFFECT THE OPERATION OF THE DEVICE. CONTACT FIREBOY-XINTEX TECHNICAL SUPPORT REGARDING ANY INSTALLATION QUESTIONS.

    Use of indicator lamp

    The Fireboy System indicator lamp is designed to announce to the helmsman the state of the fire extinguisher when the ignition key is in the ON position.

    A GLOWING green light indicates the Fireboy system is CHARGED.

    A NON GLOWING light indicates the Fireboy system is DISCHARGED.

  • 21 Part Number 18014, Revision H, 09/01/2017

    INSTALLATION CHECKLIST

    Verified Volume of Protected Space

    Verified Extinguisher Model is for Volume of Protected Space

    Mounted Extinguisher according to installation instructions

    Located extinguisher according to installation instructions

    Orientated extinguisher according to installation instructions

    Nozzle is no greater than 20in (508mm) from ceiling

    Secured Bracket according to installation instructions

    Installed Cable According to installation instructions (MA2XXXX227-BLXXX Series Only)

    Located Manual Release Handle according to installation instructions

    Routed Cable according to installation instructions

    No more than Sixteen 90° Bends (16 x 90° = 1440°)

    Secured Cable according to installation instructions

    Installed Manual Release Handle according to installation instructions

    Connected Cable to extinguisher according to installation instructions

    Removed Safety Pin on Extinguisher (System is operational)

    Installed Indicator Lamp According to installation instructions

    Located Indicator Lamp according to installation instructions

    Mounted Indicator Lamp according to installation instructions

    Wired Indicator Lamp according to installation instructions

    Review Maintenance of system

    Review Health and Safety Section of manual

    Installed Fireboy Automatic Engine Shutdown if required

  • 22 Part Number 18014, Revision H, 09/01/2017

    Maintaining Fireboy Fire Extinguisher

    1. Inspect the pressure gauge and the system daily. Pointer must indicate in green zone at

    70°F (21°C). 2. Compare actuator to illustration below to determine if the extinguisher is charged or

    discharged.

    3. Remove and weigh the complete unit (without brackets) on a certified scale every six (6) months and record on tag provided.

    4. Remove fire extinguisher from service immediately for repair or replacement if measured gross weight is greater than 5% below what is stated on unit’s label (Label Gross Weight x 0.95 = Minimum Allowable Weight).

    5. Inspect cylinder in accordance with CGA C-6, every 5 years OR have cylinder hydrostatic tested every 12 years.

    Disconnection and Inspection of Manual Discharge Cable

    DANGER:

    ACCIDENTAL DISCHARGE DURING HANDLING, INSTALLATION OR INSPECTION MAY CAUSE SERIOUS INJURY. WEAR EYE PROTECTION WHEN INSTALLING OR SERVICING FIRE EXTINGUISHER OR DISCHARGE CABLE.

    Inspect manual discharge cable annually when inspecting the fire extinguisher. 1. Do not remove the safety pin on the T-handle when disconnecting the manual discharge

    cable from the fire extinguisher manifold. 2. Carefully reinstall safety pin through actuation lever. Safety pin should secure actuation

    lever in actuation lever base. (See Page 17) 3. Remove the retaining clip securing the cable located at the slot in the top of the

    manifold. (See Page 17) 4. Carefully push the cable from the backside of the manifold towards the actuator far

    enough to allow the flexible center strand to bend. 5. Remove the “S” hook from the actuation lever. 6. Once the “S” hook is free of the actuation lever, pull the cable out and away from the

    manifold.

    To reconnect the manual discharge cable to the cylinder, refer to “Connecting Cable to Cylinder” section of this manual.

  • 23 Part Number 18014, Revision H, 09/01/2017

    Maintaining the Indicator Lamp Circuit

    Should the indicator lamp fail to come ON when the ignition key is ON 1. Check the pressure gauge and actuator to see if the system has adequate pressure or

    has been discharged. 2. Check fuse. 3. Using a continuity tester, check the electrical pressure switch on the system bottle itself:

    Pull the connectors off the spade terminals and place the probes of the continuity tester directly on the spade connectors

    A closed circuit indicates a functioning pressure switch 4. Check the continuity of the remaining wiring circuit. 5. The indicator lamp is an LED (light emitting diode) and cannot be tested with a

    continuity tester. A simple method to test LED’s is to remove the lamp and touch the Red wire to the + terminal and the black wire to the – terminal of an ordinary 9 volt battery.

    6. Should the continuity of the pressure switch indicate an open circuit, the system will have to be returned to the factory for either replacement or repair, depending upon the model involved.

    Health and Safety

    A properly designed and installed suppression system should not present any significant health or safety problems; however, there are basic precautions to be taken to avoid accidents, and aspects of the system operation that should be fully understood.

    HFC-227ea extinguishes fires by causing a cooling effect and by causing a chemical reaction with the combustion products and not by displacement of oxygen as is the extinguishment method of carbon dioxide. The agent therefore provides the ability to utilize the HFC-227ea system in occupied areas.

    HFC-227ea can decompose at high temperatures to form halogen acids. If so, their presence is readily detected as a sharp, pungent odor long before hazardous maximum exposure levels are reached.

    The noise created by the HFC-227ea agent discharging can be loud enough to startle people in the vicinity, but is unlikely to cause any permanent injury. Turbulence caused by high velocity discharge can dislodge substantial objects directly in its path, and cause enough general turbulence within the protected area to move paper and light objects.

    Direct contact with the vaporizing liquid discharged from an HFC-227ea nozzle has a cooling effect on objects and in extreme cases can cause frostbite to the skin. The liquid phase vaporizes rapidly when mixed with air and therefore limits the risk to the immediate vicinity of the nozzle. Reduction in visibility will occur due to the condensation of water vapor.

  • 24 Part Number 18014, Revision H, 09/01/2017

    Health and Safety Continued

    WARNING:

    THE DISCHARGE OF CLEAN AGENT SYSTEMS TO EXTINGUISH A FIRE CAN RESULT IN A POTENTIAL HAZARD TO PERSONNEL FROM THE NATURAL FORM OF THE CLEAN AGENT OR FROM THE PRODUCTS OF COMBUSTION THAT RESULTS FROM EXPOSURE OF THE AGENT TO THE FIRE OR HOT SURFACES. TO AVOID SERIOUS PERSONAL INJURY, UNNECESSARY EXPOSURE OF PERSONNEL TO THESE POTENTIAL HAZARDS MUST BE AVOIDED. HMIS: 2-0-0/HEPTAFLUOROPROPANE/CONTENTS UNDER PRESSURE. 0-0-0/NITROGEN EXPELLANT GAS/VERY COLD, CONTENTS UNDER PRESSURE. CONSULT CHEMOURS, 1007 MARKET STREET, WILMINGTON, DE 19898; MEDICAL EMERGENCY PHONE 800-441-3637 (OUTSIDE THE U.S. 1-302-774-1139). First Aid Skin Maintain at body temperature, thaw affected area with gentle heat. If frostbite occurs,

    seek medical assistance. Do not rub affected area. Eyes Apply gentle heat. Do not allow patient to touch affected area, seek medical assistance. For more information on HFC-227ea, please see the SDS on page 26.

    DANGER:

    1. DO NOT HANDLE BY ACTUATOR 2. DO NOT DROP 3. KEEP AWAY FROM CHILDREN 4. KEEP AWAY FROM EXTREME HEAT 5. DO NOT DISCHARGE ANY FIREBOY AUTOMATIC OR MANUAL/AUTOMATIC SYSTEM

    UNLESS SECURELY FASTENED IN ACCORDANCE WITH THE OWNER’S MANUAL 6. NEVER ATTEMPT TO MANUALLY DISCHARGE A CG2XXXX227-BXXXX FIREBOY SYSTEM 7. NEVER ATTEMPT TO DISASSEMBLE ANY COMPONENT OF THIS SYSTEM 8. ALWAYS WEAR EYE, FACE AND BODY PROTECTION WHEN INSTALLING, REMOVING OR

    WORKING IN THE IMMEDIATE VICINITY OF THIS SYSTEM Principle health hazards

    Death without warning if high concentrations are inhaled

    Reduced oxygen available for breathing

    Frostbite from direct exposure

    Increased susceptibility to the toxicity of excess exposure for individuals with pre-existing diseases of the central nervous system, cardiovascular system, lungs or kidneys

    Toxic by-products are produced when this agent extinguishes fire

  • 25 Part Number 18014, Revision H, 09/01/2017

    Medical instructions

    If high concentrations are inhaled, immediately move the exposed to fresh air and keep calm

    If not breathing, give artificial respiration. Seek medical assistance

    If breathing is difficult give oxygen. Seek medical assistance

    In case of skin contact immediately flush skin with water for 15 minutes

    Treat for frostbite if necessary by gently warming affected area. Seek medical assistance if irritation is present

    In case of eye contact, immediately flush eyes with plenty of water for at least 15 minutes. Seek medical assistance

    Wash contaminated clothing before reuse Fireboy FM Component Approved HFC-227ea Systems contain Heptafluoropropane. Heptafluoropropane has been accepted by the EPA and EU as a suitable alternate to Halon. None of the components in these materials are listed by IARC, NPT, OSHA or ACGIH as a carcinogen.

    Additional Equipment

    Coast Guard Regulation 162.029 requires an indicator lamp be installed at each helm station from which the vessel may be operated.

    An Automatic Discharge Alarm provides both an audible and visual alarm when the system discharges. Includes a 2in (50.8mm) round instrument with a simple three (3) wire hookup. Automatic Engine Shutdown/Override System is required for use with Fireboy systems in diesel powered craft. These additional equipment options are available factory direct or through your dealer. Outside the U.S.A. and Canada, see your dealer.

  • 26 Part Number 18014, Revision H, 09/01/2017

    Safety Data Sheet

    SECTION 1. IDENTIFICATION Product identifier: HFC-227ea (Fire extinguishing agent) Trade Name/Synonym: Heptafluoropropane, FM-200 Product Use: Fire extinguishing agent Manufacturer/Supplier: Fireboy-Xintex LLC Fireboy-Xintex UK Operations Limited O-379 Lake Michigan Dr. Unit 10 Holton, Holton Ind. Estates Grand Rapids, MI 49534 Poole Dorset BH16 6LT UK 1-616-735-9380 44 (0) 845 9462 SECTION 2. HAZARDS IDENTIFICATION OSHA/HCS status: This material is considered hazardous by OSHA Hazard

    Communication Standard (29 CFR 1910.1200) Classification of substance or mixture: Gases under Pressure GHS label elements: Hazard Pictograms:

    Signal word: Warning Hazard statements: H280: Contains gas under pressure; may explode if heated P210: Keep away from heat/spark/open flame. – No smoking P233: Keep container tightly closed in a cool/well-ventilated place P260: Do not breathe dust/fumes/gas/vapors/spray P273: Avoid release to the environment

    P280: Wear protective gloves/protective clothing/eye protection/face protection

    P403: Use and store only in a well-ventilated area Other Hazards: May cause frostbite

    May displace oxygen and cause rapid suffocation Overheating and over pressurizing may cause gas release or violent cylinder bursting

    SECTION 3. COMPOSITION/INFORMATION ON INGREDIENTS

    Component CAS-No. Concentration

    1,1,1,2,3,3,3-Heptafluoropropane 431-89-0 100%

  • 27 Part Number 18014, Revision H, 09/01/2017

    SECTION 4. FIRST AID MEASURES Skin contact: In case of contact, immediately flush skin with plenty of water for at

    least 15 minutes. Take off all contaminated clothing immediately. Consult a physician. Wash contaminated clothing before re-use. Treat for frostbite if necessary by gently warming affected area.

    Eye contact: In case of contact, immediately flush eyes with plenty of water for at least 15 minutes. Consult a physician if necessary.

    Inhalation: Move to fresh air, lie down. Keep patient warm and at rest. Artificial respiration and/or oxygen may be necessary. Consult a physician.

    Ingestion: Is not considered a potential route of exposure. General advice: Never give anything by mouth to an unconscious person. When

    symptoms persist or in all cases of doubt seek medical advice. Notes to physician: Because of possible disturbances of cardiac rhythm, catecholamine

    drugs, such as epinephrine, that may be used in situations of emergency life support should be used with special caution.

    SECTION 5. FIREFIGHTING MEASURES Fire and Explosion Hazard: The product is not flammable. Hazardous decomposition

    products: Hydrogen fluoride, Carbonyl fluoride Suitable extinguishing media: This material is a fire extinguishing agent. Notes to fire-fighters: Wear full protective clothing, including helmet, self-

    contained breathing apparatus, protective clothing, and face mask. Use water to cool fire-exposed containers.

    SECTION 6. ACCIDENTAL RELEASE MEASURES NOTE: Review FIRE FIGHTING MEASURES and HANDLING

    (PERSONNEL) sections before proceeding with clean-up. Use appropriate PERSONAL PROTECTIVE EQUIPMENT during clean-up.

    Safeguards (Personnel): Evacuate personnel, thoroughly ventilate area, and use self-contained breathing apparatus. Keep upwind of leak – evacuate until gas has dispersed.

    Spill Cleanup: Ventilate area using forced ventilation, especially low or enclosed places where heavy vapors might collect.

    SECTION 7. HANDLING AND STORAGE Handling (Personnel): Do not breathe gas. Avoid contact with skin, eyes and

    clothing. Provide sufficient air exchange and/or exhaust in work rooms. For personal protection see section 8. Wash hands thoroughly after handling. Wash clothing after use. Decomposition will occur when product comes in contact with open flame or electrical heating elements. Handle in accordance with good industrial hygiene and safety practice.

  • 28 Part Number 18014, Revision H, 09/01/2017

    Safety Data Sheet Continued

    Storage: Valve protection caps and valve outlet threaded plugs

    must remain in place unless container is secured with valve outlet piped to use point. Do not drag, slide or roll cylinders. Never attempt to lift cylinder by its cap. Cylinders should be stored upright and firmly secured to prevent falling or being knocked over. Keep at temperature not exceeding 130°F (54°C). Do not store near combustible materials. Keep container tightly closed in a dry and well-ventilated place. Store in original container. Protect from contamination. Avoid area where salt or other corrosive materials are present.

    Storage temperature: 32°F (0°C) to 130°F (< 54°C) SECTION 8. EXPOSURE CONTROLS/PERSONAL PROTECTION Engineering controls: Use only with adequate ventilation. Keep container tightly closed. Personal protective equipment Respiratory protection: Wear NIOSH approved respiratory protection as appropriate. Hand protection: Additional protection: Impervious gloves Eye protection: Safety glasses with side-shields, additionally wear a face

    shield where the possibility exists for face contact due to splashing, spraying or airborne contact with this material.

    Skin and body protection: Where there is potential for skin contact, have available and wear as appropriate, impervious gloves, apron, pants, jacket, hood and boots.

    Protective measures: Self-contained breathing apparatus (SCBA) is required if a large release occurs.

    Exposure Guidelines Exposure Limit Values Not Established. SECTION 9. PHYSICAL AND CHEMICAL PROPERTIES Form: Clear liquefied gas Odor: none Boiling point: -16.3°C (2.7°F) Vapor Pressure: 4,547hPa at 25°C (77°F) Density: 1.388g/cm3 at 25°C (77°F) (as liquid)

  • 29 Part Number 18014, Revision H, 09/01/2017

    SECTION 10. STABILITY AND REACTIVITY Stability: Stable at normal temperatures and storage conditions. Incompatibility: Alkali metals Alkaline earth metals, powdered metals,

    powdered metal salts Hazardous Decomposition Products: Hydrogen fluoride, Carbonyl fluoride, Carbon monoxide,

    Carbon dioxide Hazardous reactions: Polymerization will not occur. SECTION 11. TOXICOLOGICAL INFORMATION Inhalation 4 h LC50: > 788698ppm, rat Inhalation: dog Cardiac sensitization Dermal: not applicable Oral: not applicable Skin irritation: No skin irritation, not tested on animals

    Not expected to cause skin irritation based on expert review of the properties of the substance.

    Eye irritation: No eye irritation, not tested on animals Not expected to cause eye irritation based on expert review of the properties of the substance.

    Sensitization: Does not cause skin sensitization, not tested on animals Not expected to cause sensitization based on expert review of the properties of the substance. Did not cause sensitization on laboratory animals. There are no reports of human respiratory sensitization.

    Repeated dose toxicity: Inhalation, rat, No toxicologically significant effects were found. Carcinogenicity: Overall weight of evidence indicates that the substance is not

    carcinogenic. Mutagenicity: Did not cause genetic damage in animals.

    Did not cause genetic damage in cultured mammalian cells. Did not cause genetic damage in cultured bacterial cells.

    Reproductive toxicity: Animal testing showed no reproductive toxicity. Information given is based on data obtained from similar substances.

    Teratogenicity: Animal testing showed no developmental toxicity. Further information: Cardiac sensitization threshold limit: 730190 mg/m3

  • 30 Part Number 18014, Revision H, 09/01/2017

    Safety Data Sheet Continued

    SECTION 12. ECOLOGICAL INFORMATION Aquatic Toxicity 96 h LC50: Danio rerio (zebra fish) > 200mg/l

    Information given is based on data obtained from similar substances.

    96 h LC50: Oncorhynchus mykiss (rainbow trout) > 81.8mg/l Information given is based on data obtained from similar substances.

    72 h EC50: Pseudokirchneriella subcapitata > 114mg/l Information given is based on data obtained from similar substances.

    72 h EC50: Pseudokirchneriella subcapitata > 118mg/l Information given is based on data obtained from similar substances.

    48 h EC50: Daphnia magna (Water flea) > 200mg/l Information given is based on data obtained from similar substances.

    48 h EC50: Daphnia magna (Water flea) > 97.9mg/l Information given is based on data obtained from similar substances.

    Environmental Fate Biodegradability aerobic: 1% OECD Test Guideline 301, not readily biodegradable. Biodegradability aerobic: 5% OECD Test Guideline 301, not readily biodegradable. SECTION 13. DISPOSAL CONSIDERATIONS Waste Disposal: Can be used after re-conditioning. Recover by distillation or remove

    to a permitted waste disposal facility. Comply with applicable Federal, State/Provincial and Local Regulations.

    Environmental Hazards: Empty pressure vessels should be returned to the supplier. SECTION 14. TRANSPORT INFORMATION DOT UN number: 3296

    Proper shipping name: Heptafluoropropane Class: 2.2 (Non-Flammable Gas) Labelling No. : 2.2

    IATA_C UN number: 3296 Proper shipping name: Heptafluoropropane Class: 2.2 (Non-Flammable Gas) Labelling No. : 2.2

    IMDG UN number: 3296 Proper shipping name: Heptafluoropropane Class: 2.2 (Non-Flammable Gas) Labelling No. : 2.2

  • 31 Part Number 18014, Revision H, 09/01/2017

    Or – If packaged as a charged Fire Extinguisher…

    DOT UN number: 1044 Proper shipping name: Fire Extinguishers Class: 2.2 (Non-Flammable Gas) Labelling No. : 2.2

    IATA_C UN number: 1044 Proper shipping name: Fire Extinguishers Class: 2.2 (Non-Flammable Gas) Labelling No. : 2.2

    IMDG UN number: 1044 Proper shipping name: Fire Extinguishers Class: 2.2 (Non-Flammable Gas) Labelling No. : 2.2

    SECTION 15. REGULATORY INFORMATION SARA 313 Regulated Chemical(s): SARA 313: This material does not contain any chemical components

    with known CAS numbers that exceed the threshold (De Minimis) reporting levels established by SARA Title III, Section 313.

    California Prop. 65: Chemicals known to the State of California to cause cancer, birth defects or any other harm: none known

    SECTION 16. OTHER INFORMATION HMIS Health: 1 Flammability: 0 Reactivity/Physical hazard: 0 PPE: Personal Protection rating to be supplied by user depending on use

    conditions. The information provided in this Safety Data Sheet is correct to the best of our knowledge, information and belief at the date of its publication. The information given is designed only as a guidance for safe handling, use, processing, storage, transportation, disposal and release and is not to be considered a warranty or quality specification. The information relates only to the specific material designated and may not be valid for such material used in combination with any other materials or in any process, unless specified in the text. Revision: December 21, 2015 May 9, 2016 January 27, 2017

  • 32 Part Number 18014, Revision H, 09/01/2017

    Returning Fireboy-Xintex Equipment

    No product may be returned for credit or repair without a written “Returned Material Authorization” (RMA) form. Purchaser must call or email Fireboy-Xintex 616-735-9380 or [email protected] for a RMA. If due to extenuating circumstances a product is to be returned, after approval it must be received in 100% new/resalable condition. Products stored by the buyer for more than 26 weeks may not be returned for any reason. Maintaining fresh and current inventory is the responsibility of the buyer.

    Recharging Fireboy Extinguishers

    Fireboy-Xintex cylinders comply with DOT specification 4B/240, 4B/360, and 4BW/360 which allows for recharging as long as the extinguisher was not discharged due to a fire and passes visual inspection in accordance with CGA C-6, or a hydrostatic test. Extinguisher cannot be recharged or refilled in the field. Contact manufacturer for details on the recharging process.

  • 33 Part Number 18014, Revision H, 09/01/2017

    3 Year Limited Warranty

    This Warranty is in lieu of all other expressed or implied Warranties Seller warrants title, materials, and workmanship on equipment, except components manufactured by others for which the Seller assigns, as permitted, the original manufacturer’s warranty. Seller’s warranty shall be for a period of (3) three years from the date of sale to the ORIGINAL CONSUMER PURCHASER, during which non-conforming equipment returned to the Seller at Buyer’s expense and risk, be repaired or replaced at the Seller’s option. Fireboy-Xintex LLC will repair or replace products found to be defective in materials or workmanship within the period set forth above, provided that: (a) the product has not been subjected to abuse, contamination, neglect, accident, incorrect wiring not our own, improper installation or servicing, or used in violation of instructions furnished by Fireboy-Xintex LLC and (b) as to any prior defects in materials or workmanship covered by this warranty, the product has not been repaired or altered by anyone except Fireboy-Xintex LLC and (c) the serial number has not been removed, defaced or otherwise changed, and (d) examination discloses, in the judgment of Fireboy-Xintex LLC, does not assume the costs of removal and/or installation of the product or any other incidental costs of removal and/or installation of the product or any other incidental costs which may arise as a result of any defect in material or workmanship, and (e) upon discovery of defect, Buyer shall immediately cease use of and notify Fireboy-Xintex LLC. Any warranty implied by law, including warranties of merchantability or fitness, is in effect only for the duration of the expressed warranties set forth above, no person is authorized to give any other warranty, or to assume for Fireboy-Xintex LLC any other liability in connection with the sale of its products; Fireboy-Xintex LLC shall not be liable for the loss of use, revenue, or profit or for any injury, or for any other consequential or incidental damages, buyer is not relying on seller’s judgment regarding his or her particular requirements, and has had an opportunity to inspect the product to his or her satisfaction. This warranty gives you specific legal rights, and you may also have other rights, which vary, from state to state.

    www.fireboy-xintex.com

    Fireboy-Xintex LLC O-379 Lake Michigan Dr. NW

    Grand Rapids, MI 49534 [email protected]

    Phone (616) 735 9380

    Fireboy-Xintex UK Operations Limited 10 Holton Road, Holton Heath Trading Park

    Poole Dorset BH16 6LT UK [email protected]

    Phone 44 (0) 845 9462

    http://www.fireboy-xintex.com/mailto:[email protected]:[email protected]