Certificate of Compliance Attention: Dieter Goetz€¦ · Supplement to Certificate of Compliance...
Transcript of Certificate of Compliance Attention: Dieter Goetz€¦ · Supplement to Certificate of Compliance...
Certificate of Compliance Certificate: 1153651 (LR 104225)
Project: 70039951
Issued to: Siemens AG Process Industries and Drives Process Automation DE-76181 Karlsruhe GERMANY Attention: Dieter Goetz
Master Contract: 185289
Date Issued: 2015-09-24
The products listed below are eligible to bear the CSA Mark shown
Issued by: lvf ari,w 13CU'UV Marin Banu
PRODUCTS CLASS- C225802-PROCESS CONTROL EQUIPMENT-For Hazardous Locations CLASS - C225803 - PROCESS CONTROL EQUIPMENT - Intrinsically Safe and Non-Incendive Systems -For Hazardous Locations CLASS- C225804-PROCESS CONTROL EQUIPMENT-Intrinsically Safe, Entity- For Hazardous Locations
CLASS 2258 03 - PROCESS CONTROL EQUIPMENT - For Hazardous Locations
Class I, Groups A, B, C and D; Class II, Groups E, F and G; Class III; Enclosure Type 4X
Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups F and G; Class III; Enclosure Type 4X
Type SITRANS P Pressure Transmitter Models (see Table l) with input rated 20mA, 30V de, maximum ambient temperature 85° C.
Model Type SITRANS P DS III Hart 7MF4*33 - *++** - *h+* (with suffixes)
SITRANS P DS III PA 7MF4*34 - *++** - *h+* (with suffixes)
SITRANS P DS III FF 7MF4*35 - *++** - *h+* (with suffixes)
D D 507 Rev. 2012-05-22 Pa e I
CSA Group
Certificate:
Project:
1153651
70039951
Master Contract: 185289
Date Issued: 2015-09-24
SITRANS P410 Hart 7MF4*33 - *++** - *h+* Z-C41 (with suffixes)
SITRANS P410 PA 7MF4*34 - *++** - *h+* Z-C41 (with suffixes)
SITRANS P4 l 0 FF 7MF4*35 - *++** - '*h+* Z-C41 (with suffixes)
SITRANS P310 Hart 7MF2*33 - *++** - *h+* (with suffixes)
SITRANS P310 PA 7MF2*34 - *++** - *h+* (with suffixes)
SITRANS P310 FF 7MF2*35 - *++** - *h+* (with suffixes)
h =Type of protection J, K, L, N, S (see document A5E00072719A)
Table 1
Ex nA IIC
Type SITRANS P Pressure Transmitter Models (see Table 2) 7MF4*33 (with suffixes) and 7MF2*33 (with suffixes) input rated 20rnA, 45V de, maximum ambient temperature 85° C.
Type SITRANS P Pressure Transmitter Models (see Table 2) 7MF4*34 (with suffixes) and 7MF2*34 (with suffixes) and 7MF4*35 (with suffixes) and 7MF2*35 (with suffixes) input rated 20mA, 32Vdc, maximum ambient temperature 85° C.
Model Type SITRANS P DS III Hart 7MF4*33 - *++** - *h+* (with suffixes)
SITRANS P DS III PA 7MF4*34 - *++** - *h+* (with suffixes)
SITRANS P DS III FF 7MF4*35 - *++** - *h+* (with suffixes)
SITRANS P410 Hart 7MF4*33 - *++** - *h+* Z-C4 l (with suffixes)
SITRANS P410 PA 7MF4*34 - *++** - *h+* Z-C41 (with suffixes)
SITRANS P410 FF 7MF4*35 - *++** - *h+* Z-C4 I (with suffixes)
SITRANS P310 Hart 7MF2*33 - *++** - *h+* (with suffixes)
SITRANS P310 PA 7MF2*34 - *++** - *h+* (with suffixes)
SITRANS P310 FF 7MF2*35 - *++** - *h+* (with suffixes)
h =Type of protection J, K, L, N, S (see document A5E000727 l 9A)
Table 2
CLASS 2258 03 - PROCESS CONTROL EQUIPMENT - Intrinsically Safe and Non-Incendive Systems - For Hazardous Locations
Ex nL IIC
Type SITRANS P Pressure Transmitter Models (see Table 3) 7MF4*33 (with suffixes) and 7MF2*33 (with suffixes) with entity parameters Ui=24V, Ii=250mA, Pi=l.2W, Li=7µH, Ci=2.2nF as non-incendive. Type SITRANS P Pressure Transmitter Models (see Table 3) 7MF4*34 (with suffixes) and 7MF2*34 (with suffixes) and 7MF4*35 (with suffixes) and 7MF2*35 (with suffixes) with entity parameters Ui=24V, Ii=250mA,
D 507 Rev. 2012-05-22 p
Certificate: 1153651
Project: 70039951
Master Contract: 185289
Date Issued: 2015-09-24
Pi=l.2W, Li=7µH, Ci=2.2nF as non-incendive when installed per drawing No. A5E00118127A page 6 and with entity parameters Ui=l7.5V, Li=7µH, Ci=2.2nF as non-incendive (FNICO) when installed per drawing No. A5E00118127A pages 4 and 5.
Model Type SITRANS P DS III Hart 7MF4*33 - *++** - *h+* (with suffixes)
SITRANS P DS III PA 7MF4*34 - *++** - *h+* (with suffixes)
SITRANS P DS III FF 7MF4*35 - *++** - *h+* (with suffixes)
SITRANS P410 Hart 7MF4*33 - *++** - *h+* Z-C41 (with suffixes)
SITRANS P410 PA 7MF4*34 - *++** - *h+* Z-C41 (with suffixes)
SITRANS P410 FF 7MF4*35 - *++** - *h+* Z-C41 (with suffixes)
SITRANS P310 Hart 7MF2*33 - *++** - *h+* (with suffixes)
SITRANS P3 l 0 PA 7MF2*34 - *++** - *h+* (with suffixes)
SITRANS P310 FF 7MF2*35 - *++** - *h+* (with suffixes)
h =Type of protection J, K, L, N, S (see document A5E00072719A)
Table 3
CLASS 2258 04 - PROCESS CONTROL EQUIPMENT - Intrinsically Safe Entity - For Hazardous Locations
Ex ia IIC; Class II, Groups E, F and G; Class III; Enclosure Type 4X:
Type SITRANS P Pressure Transmitter Models (see Table 4) per drawing A5E00072865A, maximum ambient temperature +80°C; rated 4 - 20rnA, with entity parameters Ui=30V, Ii=lOOrnA, Pi=0.75W, Li=0.4mH, Ci=6nF, Intrinsically safe per drawing No. A5E00072770A; with entity parameters Ui=24V, Ii=250rnA, Pi=l.2W, Li=7µH, Ci=2.2nF, Intrinsically safe per drawing No. A5EOOI 18127A page 3 and with entity parameters Ui=17.5V, Ii=380rnA, Pi=5.32W, Li=7µH, Ci=2.2nF, Intrinsically safe (FISCO) per drawing No.A5E00118127A pages 1 and 2. For all models (see Table 4) the Temperature Code is T4 (for maximum ambient temperature of 85°C) or T5 (for maximum ambient temperature of 70°C) or T6 (for maximum ambient temperature of 60°C). All models have Dual Seal markings.
Model Type SITRANS P DS III Hart 7MF4*33 - *++** - *h+* (with suffixes)
SITRANS P DS III PA 7MF4*34 - *++** - *h+* (with suffixes)
SITRANS P DS III FF 7MF4*35 - *++** - *h+* (with suffixes)
SITRANS P410 Hart 7MF4*33 - *++** - *h+* Z-C41 (with suffixes)
SITRANS P410 PA 7MF4*34 - *++** - *h+* Z-C41 (with suffixes)
SITRANS P410 FF 7MF4*35 - *++** - *h+* Z-C41 (with suffixes)
SITRANS P310 Hart 7MF2*33 - *++** - *h+* (with suffixes)
SITRANS P310 PA 7MF2*34 - *++** - *h+* (with suffixes)
D D 507 Rev. 2012-05-22 Pa
CSA Group
Certificate: Project:
1153651
70039951
Master Contract: 185289
Date Issued: 2015-09-24
I SITRANS P310 FF I 7MF2*35 - *++** - *h+* (with suffixes)
h =Type of protection J, K, L, N, S (see document A5E000727 l 9A)
Table 4
APPLICABLE REQUIREMENTS
CSA Std C22.2 No. 0-19991 (R 2006) CSA Std C22.2 No. 142-M1987 (R 2004) CSA Std C22.2 No. 30-Ml986 (R 2003)
CSA Std C22.2 No. 94-1976 (R 2006) CSA Std C22.2 No. 213-Ml987 (R 2004)
CSA Std C22.2 No. 25: 1996 (R 2004)
CAN/CSA E60079-1 l :02
CAN/CSA E60079-15:02
ANSI/ISA 12.27.01-2003
MARKINGS
General Requirements - Canadian Electrical Code, Part II Process Control Equipment Explosion-Proof Enclosures for Use in Class I Hazardous Locations Special Purpose Enclosures Non-incendive Electrical Equipment for Use in Class I, Division 2 Hazardous Locations Enclosures for Use in Class II, Groups E, F and G Hazardous Locations Electrical Apparatus for Explosive Gas Atmospheres--Part 11: Intrinsic Safety "i" Electrical Apparatus for Explosive Gas Atmospheres--Part 15: Type of Protection "n" Process Sealing Electrical Systems and flammable or Combustible Process Fluids.
Product markings shall be in accordance with the related standards. In addition, it shall be the responsibility of the manufacturer to provide additional markings on the product to comply with the requirements of the local regulatory authorities. For example, in Canada, any caution and warning markings must be provided in French and English.
Markings appear on metallic nameplate as shown in drawings A5E00072854A and A5E00130551A.
Note - Jurisdictions in Canada may require these markings to also be provided in French language. It is the responsibility of the manufacturer to provide bilingual marking, where applicable, in accordance with the requirements of the Provincial Regulatory Authorities. It is the responsibility of the manufacturer to determine this requirement and have bilingual wording added to the "Markings".
D D 507 Rev. 2012-05-22 Pa e4
Certificate:
Project
70039951
2456918
2227588
1697166
1603685
1486466
1153651
D 507 Rev. 2012-05-22
Supplement to Certificate of Compliance
1153651 (LR 104225) Master Contract: 185289
The products listed, including the latest revision described below, are eligible to be marked in accordance with the referenced Certificate.
Date
2015-09-24
2011-09-24
2010-05-12
2005-07-27
2004-10-12
2003-12-05
2000-12-15
Product Certification History
Description
Update to Report 1153651 to delist models SITRANS P MK.II and SITRANS P MS and include the new pressure transmitter models SITRANS P410 and SITRANS P3 l 0 and drawing revisions.
IFE for the addition of new factory location Siemens ltd., I IA CE WSGR QM, Thane - Belapur Road, Thane -400601, India
Update to cover requested construction revisions and update documentation.
Update to cover minor modifications of enclosure construction
Update to cover addition of DSIIIFF models and drawings revision
Update to cover drawing revisions.
Original certification
Pae I
SITRANS P DS III / P410 / P310
Communication HART
Control Drawing for DIV 1, Zone 1
SITRANS P DS III / P410 / P310
Communication HART
Control Drawing for DIV 2, Zone 2
SITRANS P DS III / P410 / P310
Communication PA and FF
Control Drawing (FISCO)
SITRANS P DS III / P410 / P310
Communication PA and FF
Control Drawing (FISCO)
SITRANS P DS III / P410 / P310
Communication PA and FF
Control Drawing (FISCO)
SITRANS P DS III / P410 / P310
Communication PA and FF
Control Drawing (FNICO)
SITRANS P DS III / P410 / P310
Communication PA and FF
Control Drawing (FNICO)
SITRANS P DS III / P410 / P310
Communication PA and FF
Control Drawing (FNICO)