CENTRIC CENTRIC AN ADVANCED MODULAR UPS FROM 25KW UP TO 1600KW

Transcript of CENTRIC - gamatronic.com · The Centric uPS from 25kw to 1.6Mw Gamatronic is proud to present the...

CENTRIC

CENTRICAN AdvANCEdModulAR uPS

fRoM 25kwuP To 1600kw

The Centric uPS from 25kw to 1.6MwGamatronic is proud to present the Centric, an innovative UPS, available in many configurations (25, 50, 75, 100, 175, 200, 400, 600, 800, 1000, 1200, 1400, 1600kW).

The Centric provides reliable, clean, regulated AC power at an attractive price. For users with greater power requirements, up to five Centric units can be operated in a parallel configuration for five times the power.

The Centric’s double conversion topology provides high quality power regulation in accordance with IEC 62040 VFI-SS-111, and AC/AC efficiency up to 96%.

The Centric battery is true online as per IEC 62040, guaranteeing instant availability of backup power in the event of mains failure, and provides high unique DC/AC efficiency of up to 98%.

The Centric’s vertical and horizontal modularity reduce the down time thus providing a fault tolerant power source to critical loads and applications.

The Centric’s reliability, flexibility, intelligent features and design make it a great choice for your data center.

features• Advanced colorful LCD touch screen

• True on-line battery

• Up to 96% efficiency

• High power output

• Small footprint

• Lightweight

• Optional manual maintenance bypass switch

• Hot swappable power modules

• Hot swappable system controller

CENTRIC

Power usage Effectiveness (PuE)

Centric is an ideal efficient UPS for Tier 3 and 4 data centers with a low load. The Centric can achieve 96% efficiency in a load between 20% to 60%.

2N+1 (Tier 4) Application

25% LOAD CENTRIC 2 x 200kW

25% LOAD CENTRIC 2 x 200kW

100% IT LOAD

Efficiency vs. load

Load 200kW(%)

Efficiency

The PC-based centric controller enhances data centre management systems with its unique abilities:

• Built-in flexible connectivity

• Intelligent interface

• Fail-safe (non-critical for UPS operation)

• Hot swappable

Additional features include:

• RS232

• Modbus RS485

• Modbus TCP/IP

• USB

• SNMP

• Configurable web interface

• Unlimited servers shutdown

• Unlimited email notifications

• Data-rich system log

• Multi-language interface

footprint Power: 49w / cm2 ׀ Power density: 0.4w / cm3

CENTRIC Power density

76 cm

120 cm

202 cm

120 cm

76 cm54 cm

Vertical modularity in a basic unit is 25kW per power module; the vertical stack is scalable to up to 8 power modules (200kW). Horizontal modularity of a basic unit is up to 200kW, the horizontal scalability is up to 8 units (1600kW).

Modularity and Scalability

front view202 cm

350 cm

Vertical and Horizontal Redundancy with Decentralized or Centralized Redundancy Battery

Solutions

Up to 175kW Vertical & Horizontal

Redundancy

Up to 200kW Horizontal

Redundancy

Up to 350kWVertical

Redundancy

Up to 75kW Vertical & Horizontal Redundancy

Up to 100kW Horizontal

Redundancy

Up to 150kW VerticalRedundancy

Up to 150kW Vertical & Horizontal

Redundancy

Up to 200kW Horizontal

Redundancy

Up to 225kWVertical

Redundancy

Up to 225kW Vertical & Horizontal

Redundancy

Up to 300kW Horizontal

Redundancy

Up to 300kW Vertical

Redundancy

Up to 350kW Vertical & Horizontal

Redundancy

Up to 400kW Horizontal

Redundancy

Up to 525kWVertical

Redundancy

Up to 525kW Vertical & Horizontal

Redundancy

Up to 600kW Horizontal

Redundancy

Up to 700kWVertical

Redundancy

Up to 700kW Vertical & Horizontal

Redundancy

Up to 800kW Horizontal

Redundancy

Up to 875kWVertical

Redundancy

* All specifications are subject to change without prior notice.

CENTRIC uPS System SpecificationsTopology Modular, hot swappable, double-conversion, VFI, online battery

Operation Continuous

INPUT

Voltage (V) 3x400 (4 wires + Gnd)

Voltage range (%)-20 / +15 (360 ~ 460 Vac: full power; 320 ~ 360 Vac: derated 20 %)

Current (A) 3 × 42 per module – no inrush current at startup

Rectifier frequency (Hz) 40 ~ 70

Power walk-in (sec) >60

Power factor correction >0.99

THDI (%) <3

Inrush current None

OUTPUT

Rated Power kW) 25 ~ 1600

Nominal frequency (Hz) 50/60

Frequency tracking range (Hz) ±(0.5, 1, 2, 3, 4), selectable

Frequency tracking slew rate (Hz/sec) 1

Frequency (in free-running mode) (Hz) 50/60 ±0.1 %

Nominal voltage (Vac) 3x380, 3x400, 3x415 (4 wires + Gnd)

Static voltage regulation (%) ±1

Regulation for 100 % unbalanced load (%) ±1

Dynamic response to 100 % load step (%) ±2

Overload withstandInverter mode 110 % : 10 min, 125 % : 60 s, 150 % : 30 s

Bypass mode 125 % : 10 min, 1000 % : 1 cycle

Waveform Sinusoidal

THD (%) Linear load: <2; non-linear load: <6

Load CF (max) 6:1

Power factor Any

AC/AC efficiency (nominal) (%) Up to 96

BATTERIES

DC-link voltage (Vdc) +/-405V (405 floating, accuracy to ±1 %)

Quantity 60 × 12 Vdc

Type Sealed, lead-acid. Lithium-ion batteries also supported

GENERAL

Maximum power dissipation (Po=25 kW) N*1041 W (N*3552 BTU/h), where N = # modules

Ambient temperature (°C) -10 to +40 (operating), -20 to +60 (storage)

Relative humidity (%) 95 maximum, non-condensing

Altitude (m) 1500 without derating

Enclosure IP20

Cooling system Multi-fan with speed control (forced)

DESIGN & MANUFACTURING STANDARDS

Safety IEC 62040-1

EMC IEC 62040-2

Design classification IEC 62040-3

Low magnetic field radiation EMF as per ICNIRP

DIMENSIONS

UPS MODEL 50 kW 100 kW 200 kW

# OF POWER MODULES 1 2 3 4 4 5 6 7 8

POWER OUTPUT (kW/kVA) 25 50 75 100 100 125 150 175 200

Height (mm) 932 1200

Width (mm) 540

Depth (mm) 757

Weight (kg) w/o batt. box 82.6 102.4 122.2 142 149.3 169.1 188.9 208.7 228.5

CENTRIC

Technical Specifications for the System Controller

Display LCD flat panel, touch-sensitive

Other indicators Audible alarm

Analog input channels 4 input dry contacts (N.O. / N.C.)

Real-time clock (RTC) Yes, with backup

Power meter kVA, kW, PF

Volt-free outputs (dry contacts) 6 outputs, rated 48 V / 1 A

Output dry contacts

AC failureDC failureUPS module(s) failureLoad on bypassBattery test failureOver/under temperatureOverload(Each system alarm type can be routed to the dry contact of your choice)

Communication ports Serial, Ethernet, USB

Communication protocols RS232, RS485, TCP/IP, SNMP, Modbus

Communications with system modules Serial, isolated

Events log 500 events

System operation without controller Unchanged

On-screen parameters

Load bar-graph3-phase voltages3-phase currentsBattery voltageStatus of each UPS moduleStatic-switch parameters and statusBattery sensor temperature

RTC operation without power Indefinitely

Power requirements 3 × 400 Vac and 405 Vdc

Remote indication panel capability Yes

* All specifications are subject to change without prior notice.

Technical Specifications for the System Controller

Choose the Centric and enjoy a reliable, clean, regulated AC power UPS.

This is the kind of feedback we continually receive from our customers:

“We are very satisfied with the Centric’s performance and back up of the critical load in the data center.”

With Regards,

Jacob Shaaltiel

Business Manager, Data Center Consulting

Technology Consulting

Hewlett-Packard (Israel) Ltd.

February 2017

GAMATRoNIC ElECTRoNIC INduSTRIES lTd.

ISRAEl (HEAdquARTERS)17 Hartum St. P.O. Box 45029, Jerusalem 9777517, Israel Tel: +972 2 588 8222 | Fax: +972 2 582 8875 [email protected] | www.gamatronic.com

GAMATRoNIC uk ltd. 15 Chester Road, Colmworth Business Park, Eaton Socon, Cambridgeshire, PE19 8YT, United Kingdom Tel: +44 (0)1480 479889/ 472665 | Fax: +44(0)1480 407865 [email protected] | www.gamatronic.co.uk

GAMATRoNIC SouTH AfRICA 377 Rivonia Boulevard, Rivonia 2128, Gauteng, South Africa Office: +27 11 593 2403 | Fax: +27 86 682 2468 [email protected] | www.gamatronic.co.za

GAMATRoNIC CHINA RM2001, No 1, Alley 100. East Tiyuhui Rd, Shanghai 200081, China Tel: +86 21 6587 2583 | [email protected] | www.gamatronic.cn