Central Battery Systems
-
7/26/2019 Central battery system
2/12
1
Central battery system based emergency lighting is idealfor larger projects. There are many reasons for this, the
main ones being:
Simplified maintenance
Self contained emergency luminaires each incorporate
individual rechargeable batteries. The combination of
raised ambient temperature within typical luminaires and
continuous charging under mains healthy conditions
results in a normal battery life of around 4 years. At the
end of the battery life, each individual battery must be
replaced, this is a time consuming and disruptive process
often requiring the mains fittings to be dismantled to gainaccess to the battery.
With a Central battery system the battery is housed in a
secure cabinet in a suitable, easy to access location such as
a plant room. The batteries in a central battery system will
typically have a 10 year design life, and when replacement
is required they can be easily and quickly replaced.
On large systems with hundreds of emergency luminaires,
Central battery systems potentially offer massive savings in
maintenance cost and disruption.
Why central battery systems?
Integrated Emergency lighting
Static inverter type central battery systems are able to
power suitable unmodified mains luminaires at full power
during both mains healthy and mains failed conditions.
On projects with large open areas, particularly those with
high mounting heights, the use of mains fittings operating
at full output in emergency mode can greatly reduce the
number of emergency luminaires required. The use of
suitable standard unmodified mains luminaires also hasaesthetic advantages in many applications.
-
7/26/2019 Central battery system
3/12
System features
Modular inverterdesignIndividual inverter modules
can easily be removed for
maintenance or to reduce
weight during installation
(2.5KVA and above)
Integral plinthFor ease of positioning
Note: Compact units (AC500...) differ slightly from above, contact technical sales for full details (Tel: 01302 303221)
Comprehensive indicationdisplayShows current system status at
a glance
Temperature compensationwith digital displayAutomatically adjusts charger
voltage to optimise performance
and life in response to ambient
temperature.
2
-
7/26/2019 Central battery system
4/12
3
This can considerably reduce the overall installed cost ofthe system by reducing the amount of distribution wiring.
Distributed systems can also increase system integrity by
limiting the area affected by failure of an individual unit.
The compact 500VA static inverter system is ideal for use
as part of a distributed system, having a small footprint
and a lift off front cover, ideal for use in areas where access
space is limited.
Centralised or distributed systems
Cooper Lighting and Security manufactures a wide rangeof Central battery systems. Standard products include
static inverter systems with ratings from 500VA to 30KVA.
Smaller systems are ideal for providing emergency lighting
in small localised areas, e.g. Atriums where traditional
emergency lighting is not appropriate, alternatively
multiple small systems can be utilised, located at
convenient points throughout the building.
Distributed systems can save on overall wiring
-
7/26/2019 Central battery system
5/12
4
To complement the range of Central systems, a wideselection of slave luminaires and conversion modules is
also available, which have been specifically designed to
ensure compatibility with Cooper Lighting and Security
central systems. Alternatively ACM1 modules can be used
to enable suitable normal unmodified mains luminaires to
be utilised for both normal and emergency lighting
operation.
ACM1 modules can either be mounted inside the
designated luminaire, or housed in a remote enclosure.
When housed in a remote enclosure, the ACM1 can either
be used to control an individual luminaire or a series of
luminaires, that all share a common switched live under
normal mains healthy conditions.
The operation of the ACM1 module is described opposite.
Cooper Lighting and Security offer dedicated slave
luminaires, that have been purpose designed to operate
with static inverter systems, they have a light output and
distribution that has been optimised to provide typical
emergency lighting design values.
The use of these efficient low power luminaires can
significantly reduce the physical size, output rating and
cost of the static inverter system compared to the use ofadapted normal mains luminaires. ACM1 units can also be
used to control dedicated slave luminaires if either local
switching (see above) or non maintained operation is
required.
For non maintained slave operation, the ACM1 can be used
to hold off the supply to the dedicated emergency
luminaires until a mains failure occurs.
This is achieved by simply not adding a switched live
connection to the ACM1.
Choice of emergency luminaires
Mains onlyLuminaires
CombinedMains/EmegencyLuminaire
Local SwitchedSupply
ACM1
Mains onlyLuminaires
CombinedMains/EmegencyLuminaire
Local SwitchedSupply
ACM1
Mains onlyLuminaires
CombinedMains/EmegencyLuminaire
Local SwitchedSupply
ACM1
Mains onlyLuminaires
CombinedMains/EmegencyLuminaire
Local SwitchedSupply
ACM1
Normal mains healthy condition
Failure of normal lighting final circuit
Total mains failure
OR
KEY- LIVE- DEAD
-
7/26/2019 Central battery system
6/12
5
Legislation demands that emergency lighting systemsare regularly tested and maintained in full working order.
The Easicheck Addressable testing systems can greatly
simplify the testing and maintenance regime, by
automatically carrying out complete automatic testing of
the entire emergency lighting system and raising an alarm
when remedial work is required.
Easicheck removes the need for expensive, time consuming
manual testing of emergency lighting systems, and ensures
that a thorough, consistent test regime is implemented.
As well as carrying out regular testing of all connected
emergency luminaires, the Easicheck system continually
monitors the status of the central battery units to ensure
that key parameters such as battery voltage and charge
current are at the correct level.
The Easicheck system consists of a control panel (or series
of control panels on large projects) and an addressable
interface added to each emergency luminaire and control
device. An individual Easicheck panel can monitor and
control up to 250 addressable interfaces, each of which
could be either a luminaire, a control device or Central
battery system.
Where ACM1 modules are utilised to allow standard mainsfittings to also operate as emergency luminaires, special
addressable versions are available which have the same
functionality as normal ACM1 modules, but in addition
can be controlled by Easicheck for automatic testing
purposes. An additional interface is fitted to each central
battery unit to allow Easicheck to monitor critical
parameters and to activate discharge testing as required.
Control panels can operate on a stand alone basis or can
be networked together to form a single integrated system.
In addition, software and hardware packages are available
to allow Easicheck systems to connect to a computer to
provide either a text based or graphical user interface for
ease of monitoring on large sites.
The diagram below represents a typical wiring
arrangement for a networked Easicheck system connected
to a Central battery system. A comprehensive installation
planning guide is available on request to assist with the
detailed planning of an Easicheck installation.
Addressable testing
Data cable
Supply to emergency fitting
Network Cable
Optional PCInterface
-
7/26/2019 Central battery system
7/12
6
-
7/26/2019 Central battery system
8/12
7
Static inverter detailed technical specification
The system includes all necessary features to comply with the requirements of BS EN50171: 2001 for Central System Supplies.Inverters are able to start the full load of a previously un-powered system, within the response time of EN1838 in mains
failure mode.
Charger and Controls
Mains Supply: 230 10% VAC 1 phase 50hz
Input Control: MCB to BS3871 Pt. 1, or BS4752 Part 1
Fusegear: HRC type to BS88
Terminals: DIN rail mounted near to cable entry
Transformer: Double wound with earth screen to BS171
Rectifier: Full wave controlled thyristor/diode bridge
Display Panel: Comprehensive LED and LCD display (see below for details)
Contactor: Standard contactors comply with the requirements of EN 60947-4-1
Charger:Constant voltage, current-limited type with electronic solid-state controller. Voltage is controlled towithin 2% of setting at up to 10% mains supply variations.
TemperatureCompensation:
Fitted as standard on all units with lead acid cells. The charger voltage is automatically adjustedwith reference to ambient temperature to optimise charging and battery life.
Boost Control: Manual boost/commissioning push button is fitted to units with vented batteries.
Test Push-button: Simulates mains failure
InverterOutput voltage:
Pre-settable in the range 220-240VAC. Unless otherwise advised, the output will be set at 230VAC.The voltage tolerance is 2% on loads of 0-100% of system rating.
Frequency: 50 or 60hz. 0.01%. Standard setting 50hz
Waveform: Sinusoidal
Voltage Regulation: Static 2%, dynamic 6%
Isolation: 1.5kv rms between input and output terminals
Total HarmonicDistortion:
Less than 3% into a linear load
Power Factor: Will supply loads in the 0.3 lag - 0.3 lead range (0.7 lag - 0.7 lead for AC500 units)
Overload: 200% for 10 seconds, 125% for 20 minutes without reduction in output voltage
Start-up Time: Standard 30mS
Noise Level: Less than 55dBA at 1 metre
Efficiency: 85-89%
Protection:
DC input and AC output MCBsDC input reverse polarity protectionShort circuit protectionReverse-fed mains proof
Low voltage shutdown:
The inverter automatically shuts down when the battery discharges to a pre-set level. Re-set isfollowing a combination of the restoration of the mains supply and an increase in battery voltageabove the disconnect threshold level. Residual current drain when the disconnect circuit hasoperated is less than 1mA per module
Technology: Pulse width modulation with high frequency switching
-
7/26/2019 Central battery system
9/12
8
Display Indication
Power OnIndicates that mains power is supplied to the charger, and to all connected sub-circuit monitors(LK1), and that no brown-out has occurred.
Maintained lightsIndicating that mains power is supplied to the Maintained circuit, and that any switchingconnected to LK2 is closed
Float mode*Indicating that the charger is working in the constant voltage mode (and hence the charge currentis low or falling). Unless the Boost Mode indicator is also lit (see below) this indicates that thebattery voltage is at the preset float voltage
Current limit* Indicating that the charger is in constant current mode (and hence the battery voltage is rising).
Full charge*Indicating that the charger is in constant voltage mode (at float voltage unless the boost indicatoris also illuminated), and that the current has dropped to a low level (generally below 10-20% ofcurrent limit)
Boost mode*
(Not applicable to Valve Regulated Lead Acid types of batteries) - Indicating that the unit ischarging towards a target voltage about 20% higher than the preset float voltage. Depending onoptions selected at the design stage, this can be initiated automatically or manually. If automatic,it shall start and finish on preset voltage thresholds. If initiated manually, it shall be terminatedeither manually or by a timer. Manual operation shall be by means of two push buttons on theinternal PCB.
Mains fail*Indicating that mains power has failed (or dropped below the brown-out threshold) either tothe unit or to one of the sub-circuit monitors connected to it. The charger will then not beoperating, and the output will be supplied from the battery
Charge fail Indicates that battery voltage and charge current are both low.
Battery high voltsIndicating that the battery voltage has risen above a preset threshold, normally 5% above floatvoltage
Battery low voltsIndicates that the battery voltage has dropped below a preset threshold, normally 5% below floatvoltage
Earth fault*Indicating some leakage to earth (resistance approximately 5kohms or less) on any circuitconnected to the battery positive or negative.
Deep discharge
protection
Indicating that the deep discharge protection circuit has operated, cutting off the output to avoiddamage to the battery. It shall remain illuminated until mains power has been restored AND the
condition has been acknowledged by pressing the Deep Discharge Protection Reset button
Inverter running Indicates that the inverter is providing an output of nominally 230VAC
Display current Changes the digital meter display from battery voltage to battery current
Display Temp* Changes the digital meter display from battery voltage to battery temperature
Mute buzzer An internal buzzer sounds when any alarm condition occurs, which can be silenced with this button
LCD DisplayDisplays Battery voltage by default, will display charge/discharge current or ambient temperatureif above buttons are operated
* Not fitted on compact static inverter units (AC500...) See page 10 for details.
-
7/26/2019 Central battery system
10/12
9
Use the following procedure to select a correctly sizedstatic inverter:
1) Make a list of all the luminaires to be connected to the
static inverter.
2) Note the quantity of fittings of each type.
3) Establish the electrical supply details for each luminaire
type (the circuit watts and the circuit VA).
4) Multiply each of these by the quantity of luminaires
5) Add together the total Circuit wattage requirement
and the total circuit VA requirement.
6) Add an allowance (recommend a minimum of 20%)
for future expansion.
7) Select an inverter unit from the list opposite which is
capable of supplying both the required VA rating and
the required wattage rating.
Notes
1) Make sure you use the circuit watts of the fitting not
the lamp watts (with a switch start fitting, there can be
as much as 40% difference between the lamp wattage
and the actual circuit wattage of the fitting)
2) The circuit wattage of a HF fitting will be normally be
substantially lower than that of an equivalent switch
start fitting. If HF fittings are used instead of switch
start fittings, the resulting inverter is likely to besignificantly cheaper and smaller.
3) Fittings with a low Power factor have a much highercircuit VA than fittings with a high power factor.
Using low power factor fittings on a static inverter will
increase the size and cost of the static inverter unit.
4) Ensure any fitting selected for use as an emergency
fitting complies with the product standard for
emergency fittings (EN60598-2-22) note, that to
comply with this standard glow starters, or lamps
with built in starters must not be used, (use electronic
starters instead).
Worked examples
In the following examples the same fitting types have beenused in both cases, however in the first example, switch
start gear has been used as the basis for calculation, the
second example, is based on HF gear. These examples
illustrate how the use of HF gear results in a smaller and
cheaper static inverter unit.
Calculate the correct sized static inverter to support the
following load:
55 x 58W battens
21 x Twin 58W Weatherproof fittings
20 x 8W Exit signs
Selecting the correct sized unit
Qty Type Circuit VA (ea) Circuit VA (Tot) Circuit Watts (Ea) Circuit Watts (Tot)
55 1 x 58W Switch start batten 79.3 4361.5 69 3795
21 2 x 58W Switch start weatherproof 158.6 3330.6 138 2898
20 8W Exit sign (HF) 11 220 9 180
Total connected load 7912.10 6873
Plus 20% spare 9494.52 8247.60
Qty Type Circuit VA (ea) Circuit VA (Tot) Circuit Watts (Ea) Circuit Watts (Tot)
55 58W High frequency batten 56.1 3085.5 55 3025
21 2 x 58W High frequency weatherproof 112.2 2356.2 110 2310
20 8W Exit sign (HF) 11 220 9 180
Total connected load 5661.7 5515
Plus 20% spare 6794.04 6618
Example 1 (Switch start gear)
Example 2 (HF gear)
-
7/26/2019 Central battery system
11/12
10
Having calculated the required system size, select a unit from the list below which has sufficient capacity to support therequired load (including the spare capacity), note bolts and VA wattage must be checked.
Cooper Lighting and Security offers a wide range of static inverter systems, with ratings from 500VA to 30KVA. The list below
shows a number of popular sized units are available on short delivery lead times. For requirements outside this range, please
contact out central battery systems technical sales department, who will be pleased to provide further details.
Head Office
Cooper Lighting and Security Ltd, Wheatley Hall Road, Doncaster, South Yorkshire, DN2 4NB
Sales General Major Projects London Export
T: +44 (0)1302 303303 +44 (0)1302 321541 +44 (0)1992 787999 +44 (0)1302 303250F: +44 (0)1302 367155 +44 (0)1302 303220 +44 (0)1992 787222 +44 (0)1302 303251E: [email protected] [email protected] [email protected] [email protected] CC1285/03_07/10Kwww.cooper-ls.com
* contains Easicheck interface
Part Number Easicheck compatible Max output VA Max output Watts Standby hrs
1AC500VAM3 No 500 400 3
1AC500VAM3EC Yes 500 400 3
1ACSLX12503AP No 1250 1065 3
1ACSLX25003AP No 2500 2000 3
1ACSLX37503AP No 3750 3200 3
SK-AC4KVA-SLR3 No 4000 3400 3
SK-JAC4KVA-SLR3* Yes 4000 3400 3
SK-AC5KVA-SLR3 No 5000 4250 3
SK-JAC5KVA-SLR3* Yes 5000 4250 3
SK-AC7-5KVA-SLR3 No 7500 6375 3
SK-JAC7-5KVA-SLR3* Yes 7500 6375 3
SK-AC8KVA-SLR3 No 8000 6800 3
SK-JAC8KVA-SLR3* Yes 8000 6800 3
SK-AC10KVA-SLR3 No 10000 8500 3
SK-JAC10KVA-SLR3* Yes 10000 8500 3
Contact technical sales for details of cubicle dimensions (Tel: 01302 303221)
-