CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

138
CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL One-Way Ceiling Cassettes 7,500 to 24,200 Btu/h Two-Way Ceiling Cassettes 19,100 to 24,200 Btu/h Four-Way Ceiling Cassettes 5,500 to 48,100 Btu/h

Transcript of CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

Page 1: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

One-Way Ceiling Cassettes7,500 to 24,200 Btu/h

Two-Way Ceiling Cassettes19,100 to 24,200 Btu/h

Four-Way Ceiling Cassettes5,500 to 48,100 Btu/h

Page 2: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

For continual product development, LG Electronics U.S.A., Inc. reserves the right to change specifications without notice. © LG Electronics U.S.A., Inc.

PROPRIETARY DATA NOTICEThis document, as well as all reports, illustrations, data, information,

and other materials are the property of LG Electronics U.S.A., Inc., and are disclosed by LG Electronics U.S.A., Inc. only in confidence.

This document is for design purposes only.

A summary list of safety precautions is on page 3.

To access additional technical documentation such as submittals, outdoor unit engineering manuals, installation, service, product data performance, general best practice, and building ventilation manuals, as well as white

papers, catalogs, LATS software programs, and more, log in to www.lghvac.com.

Page 3: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

INTRODUCTION | 3

Introduction

©

TABLE OF CONTENTS

TABLE OF SYMBOLSThis symbol indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

This symbol indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

This symbol indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.

This symbol indicates situations that may result in equipment or property damage accidents only.

This symbol indicates an action should not be completed.

DANGER

CAUTION

Unit Nomenclature ................................................................................. 4

LG Air Conditioner Technical Solution (LATS) ................................... 5

Refrigerant Charge Worksheet ............................................................. 7

One-Way Ceiling Cassette .................................................................. 12 ................................................................. 12

General Data ..................................................................................... 14Electrical Data ................................................................................... 16External Dimensions .......................................................................... 17Electrical Wiring Diagram .................................................................. 19Refrigerant Flow Diagram .................................................................. 21Acoustic Data .................................................................................... 22Air Velocity / Temperature Distribution ............................................... 26Fresh Air Ventilation ........................................................................... 34Cooling Capacity Tables .................................................................... 35Heating Capacity Tables .................................................................... 38Accessories ....................................................................................... 40

Two-Way Ceiling Cassette .................................................................. 42 ................................................................. 42

General Data / Electrical Data ........................................................... 44External Dimensions .......................................................................... 45Electrical Wiring Diagram .................................................................. 46Refrigerant Flow Diagram .................................................................. 48Acoustic Data .................................................................................... 49Air Velocity / Temperature Distribution ............................................... 51Cooling Capacity Tables .................................................................... 55Heating Capacity Tables .................................................................... 56Optional Accessories ......................................................................... 57

Four-Way Ceiling Cassette ................................................................. 59 ................................................................. 59

General Data ..................................................................................... 61Electrical Data ................................................................................... 65External Dimensions .......................................................................... 66Electrical Wiring Diagram .................................................................. 70Refrigerant Flow Diagram .................................................................. 74Acoustic Data .................................................................................... 75Air Velocity / Temperature Distribution ............................................... 84Fresh Air Ventilation ......................................................................... 106Cooling Capacity Tables .................................................................. 108Heating Capacity Tables ...................................................................118Optional Accessories ....................................................................... 125

Application Guidelines ...................................................................... 127Selecting the Best Location ............................................................. 127General Mounting ............................................................................ 128General Mounting / General Drain Piping Information ..................... 129Wiring Guidelines ............................................................................ 131Wired Controller Placement ............................................................. 136

Acronyms ........................................................................................... 137

Page 4: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

4 | INTRODUCTION

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

ARN U 07 3 TN C

Generation2 = Second4 = FourthA = Second, Revision A

Electrical Ratings 3 = 208–230V/60Hz/1Ph

05 = 5,000 Btu/h 07 = 7,000 Btu/h 09 = 9,000 Btu/h 12 = 12,000 Btu/h 15 = 15,000 Btu/h

18 = 18,000 Btu/h 24 = 24,000 Btu/h 28 = 28,000 Btu/h 30 = 30,000 Btu/h 36 = 36,000 Btu/h

42 = 42,000 Btu/h 48 = 48,000 Btu/h 54 = 54,000 Btu/h 76 = 76,000 Btu/h 96 = 96,000 Btu/h

TypeU = DC Inverter Heat Pump

FamilyARN = Multi V Indoor Unit(Refrigerant R410A)

FeatureA, C, D, L, R = Standard G = Low Static

U = Uncased

HH //1P1Phh

Indoor Unit Nominal Capacity

Model

4

B8 = Ducted (high static) BH = Ducted (high static) M2 = Ducted (high static) M3 = Ducted (high static) CE = Floor Standing (small frame) CF = Floor Standing (large frame) L1 = Ducted (low static) L2 = Ducted (low static) L3 = Ducted (low static)

NJ = Vertical/Horizontal Air Handling Unit NK = Vertical/Horizontal Air Handling Unit SF = Art Cool Gallery SJ = Wall Mounted / Art Cool™ Mirror SK = Wall Mounted / Art Cool Mirror SV = Wall Mounted TT = 1-Way Ceiling Cassette TU = 1-Way Ceiling Cassette TS = 2-Way Ceiling Cassette

TM = 4-Way Ceiling Cassette TN = 4-Way Ceiling Cassette TQ = 4-Way Ceiling Cassette TR = 4-Way Ceiling Cassette

UNIT NOMENCLATURE

Page 5: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

INTRODUCTION | 5

Introduction

©

LG Air Conditioner Technical Solution (LATS) SoftwareA properly designed and installed refrigerant piping system is critical to the optimal performance of LG air-conditioning systems. To assist engineers, LG offers, free of charge, LG Air Conditioner Technical Solution (LATS) software—a total design solution for LG air conditioning systems.

To reduce the risk of designing an improper applied system or one that will not operate correctly, LG requires that LATS software be used on all projects.

FormatsLATS is available to LG customers in three user interfaces: LATS HVAC, LATS CAD2, and LATS REVIT. All three LATS formats are available through www.myLGHVAC.com, or contact an LG Sales Representative.

LATS HVAC is a Windows®-based application that aids engineers in designing LG Variable Refrigerant Flow (VRF), Multi F / Multi F MAX, Single-Zone, and Energy Recovery Ventilator (ERV) systems.*Windows® is a registered mark of Microsoft® Corporation.

LATS CAD2 combines the LG LATS program with AutoCAD® software**. It permits engineers to layout and validate LG Multi V Variable Refrigerant Flow (VRF), Multi F / Multi F MAX, Single-Zone, and Energy Recovery Ventilator (ERV) systems directly into CAD drawings.

LATS Revit integrates the LG LATS program with Revit® software**. It permits engineers to layout and validate Multi V VRF systems directly into Revit drawings.**AutoCAD® and Revit® are both registered marks of Autodesk, Inc.

FeaturesAll LG product design criteria have been loaded into the program, making LATS simple to use: double click or drag and drop the com-ponent choices. Build systems in Tree Mode where the refrigerant system can be viewed. Switch to a Schematic diagram to see the electrical and communications wiring.LATS software permits the user to input region data, indoor and outdoor design temperatures, modify humidity default values, zoning, specify type and size of outdoor units and indoor units, and input air flow and external static pressure (ESP) for ducted indoor units.

The program can also:

LG AIR CONDITIONER TECHNICAL SOLUTION (LATS)

• Import building loads from a separate Excel file.• Present options for outdoor unit auto selection.• Automatically calculate component capacity based on design

conditions for the chosen region.• Verify if the height differences between the various system

components are within system limits.• Provide the correct size of each refrigerant piping segment and LG

Y-Branches and Headers.

• Adjust overall piping system length when elbows are added.• Check for component piping limitations and flag if any parameters

are broken.• Factor operation and capacity for defrost operation.• Calculate refrigerant charge, noting any additional trim charge.• Suggest accessories for indoor units and outdoor units.• Run system simulation.

Features depend on which LATS program is being used, and the type of system being designed.

Figure 1: Example of LATS CAD2.

Page 6: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

6 | INTRODUCTION

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

LATS Generates a Complete Project ReportLATS software also generates a report containing project design parameters, cooling and heating design data, system component perfor-mance, and capacity data. The report includes system combination ratio and refrigerant charge calculations; and provides detailed bill of material, including outdoor units, indoor units, control devices, accessories, refrigerant pipe sizes segregated by building, by system, by pipe size, and by pipe segments. LATS can generate an Excel GERP report that can imported into the LG SOPS pricing and ordering system.

Proper Design to Install ProcedureLG encourages a two report design-to-install-procedure. After the design engineer determines building / zone loads and other details, the engineer opens the LATS program and inputs the project’s infor-mation. When the design is complete, the “Auto Piping” and “System Check” functions must be used to verify piping sizes, limitations, and if any design errors are present. If errors are found, engineers must adjust the design, and run Auto Piping and System Check again. When the design passes the checks, then the engineer prints out a project “Shop Drawing” (LATS Tree Diagram) and provides it to the installing contractor. The contractor must follow the LATS Tree Diagram when building the piping system, but oftentimes the design changes on the building site:

• Architect has changed location and/or purpose of room(s).• Outdoor unit cannot be placed where originally intended.• Structural elements prevent routing the piping as planned.• Air conditioning system conflicts with other building systems

(plumbing, gas lines, etc.).

The contractor must mark any deviation from the design on the Shop Drawing, including as-built straight lines and elbows. This “Mark Up” drawing must be returned to the design engineer or Rep, who must input contractor changes into the LATS file. (Copy the original LATS soft-ware file, save and rename as a separate file, and modify all piping lengths by double-clicking on each length and editing information.) Like the shop drawing, the Auto Piping and System Check must also be run on this new “As Built” drawing. The design engineer or Rep must then provide the final As Built file to the contractor. The Mark Up version must be compared to the As Built version for:

• Differences in pipe diameter(s). If incorrect diameters have been installed, the piping must be changed out. If pipe diameters have changed,check to see if Y-Branches will also need to be changed.

• Changes to outdoor unit and indoor unit capacities. Capacities changes may impact line length changes.• Additional refrigerant charge quantity (“Trim Charge”). Trim charge will change if piping lengths and diameters change. The As Built version

must reflect installed piping lengths to ensure correct trim charge.

All documents submitted by the contractor, as well as the Shop Drawing and the As Built Drawing files must be provided for commissioning purposes. Model and serial numbers for all system components must also be submitted. If the steps previously detailed are not followed, and all documents are not provided to the commissioning agent, the project runs the risk of not being commissioned and voiding any limited warranty LG offers on the equipment.

LG AIR CONDITIONER TECHNICAL SOLUTION (LATS)

Figure 2: Example of a LATS Tree Diagram.

Page 7: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

INTRODUCTION | 7

Introduction

©

REFRIGERANT CHARGE WORKSHEETMulti V 5 System R410A Refrigerant Charge Calculator (lbs.)

System Tag or ID:Job Name: __________________________________________

Project Manager: ____________________________________ Date: ______________Line # Description Chassis I.D. Size Quantity CF (Ref.)1 Total (lbs.)

1 Linear feet of 1/4" liquid line tubing2 — — 0.0152 Linear feet of 3/8" liquid line tubing2 — — 0.0413 Linear feet of 1/2" liquid line tubing2 — — 0.0794 Linear feet of 5/8" liquid line tubing2 — — 0.1165 Linear feet of 3/4" liquid line tubing2 — — 0.1796 Linear feet of 7/8" liquid line tubing2 — — 0.2387 Linear feet of 1" liquid line tubing2 — — 0.3238 Standard + Art Cool Mirror SJ, SK 5k to 15k 0.539 Standard + Art Cool Mirror SJ, SK 18k to 24k 0.62

10 Standard SV 30k to 36k 1.0111 Art Cool Gallery SF 9k to 12k 0.2212 1-Way Cassette TU 7k to 12k 0.4413 1-Way Cassette TT 18k to 24k 0.6414 2-Way Cassette TS 18k to 24k 0.7515 4-Way 2' x 2' Cassette TR 5k to 7k 0.4016 4-Way 2' x 2' Cassette TR 9k to 12k 0.5517 4-Way 2' x 2' Cassette TQ 15k to 18k 0.7118 4-Way 3' x 3' Cassette TN 7k to 24k 0.8819 4-Way 3' x 3' Cassette TM 28k to 36k 1.0820 4-Way 3’ x 3’ Cassette TM 42k to 48k 1.4121 High Static Ducted M1 7k to 24k 0.5722 High Static Ducted M2 7k to 24k 0.7723 High Static Ducted M2 28k to 42k 1.1524 High Static Ducted M3 28k to 54k 1.3525 High Static Ducted B8 36k to 96k 2.2026 Low Static Ducted, Low Static Ducted Bottom Return L1 5k to 9k 0.3127 Low Static Ducted, Low Static Ducted Bottom Return L2 12k to 18k 0.4228 Low Static Ducted, Low Static Ducted Bottom Return L3 21k to 24k 0.5529 Vertical / Horizontal Air Handling Unit NJ 12k to 30k 1.0430 Vertical / Horizontal Air Handling Unit NJ 36k 1.5731 Vertical / Horizontal Air Handling Unit NK 42k to 54k 2.0032 Floor Standing CE (U) 7k to 15k 0.3733 Floor Standing CF (U) 18k to 24k 0.8234 HRU: PRHR022A/023A, 032A/033A, 042A/043A — — 1.135 HRU: PRHR063A, 083A — — 2.236 ADDITIONAL Refrigerant Charge Required (Sum of lines 1 – 35)

37 Outdoor Unit Factory Refrigerant Charge

37A ARUM072*TE5 72k 14.337B ARUM096*TE5 96k 23.237C ARUM121*TE5 121k 23.237D ARUM144*TE5 144k 26.537E ARUM168*TE5 168k 26.537F ARUM192*TE5 192k 30.937G ARUM216*TE5 216k 37.537H ARUM241*TE5 241k 37.5

38 Total ODU FACTORY Refrigerant Charge (Sum of factory refrigerant charges for all ODUs in the system, lines 37A -37H) 39 TOTAL SYSTEM CHARGE

Sum of Additional Refrigerant Charge Required (line 36) and Total ODU Factory Refrigerant Charge (line 37)

1CF (Ref.) = Correction Factor for Refrigerant Charge. 2For refrigerant charge purposes, consider only the liquid line; ignore the vapor line(s).

Page 8: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

8 | INTRODUCTION

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

REFRIGERANT CHARGE WORKSHEETWater IV System R410A Refrigerant Charge Calculator (lbs.)

System Tag or ID:Job Name: __________________________________________

Project Manager: ____________________________________ Date: ______________Line # Description Chassis I.D. Size Quantity CF (Ref.)1 Total (lbs.)

1 Linear feet of 1/4" liquid line tubing2 — — 0.0152 Linear feet of 3/8" liquid line tubing2 — — 0.0413 Linear feet of 1/2" liquid line tubing2 — — 0.0794 Linear feet of 5/8" liquid line tubing2 — — 0.1165 Linear feet of 3/4" liquid line tubing2 — — 0.1796 Linear feet of 7/8" liquid line tubing2 — — 0.2387 Linear feet of 1" liquid line tubing2 — — 0.3238 Standard + Art Cool Mirror SJ, SK 5k to 15k 0.539 Standard + Art Cool Mirror SJ, SK 18k to 24k 0.62

10 Standard SV 30k to 36k 1.0111 Art Cool Gallery SF 9k to 12k 0.2212 1-Way Cassette TU 7k to 12k 0.4413 1-Way Cassette TT 18k to 24k 0.6414 2-Way Cassette TS 18k to 24k 0.7515 4-Way 2' x 2' Cassette TR 5k to 7k 0.4016 4-Way 2' x 2' Cassette TR 9k to 12k 0.5517 4-Way 2' x 2' Cassette TQ 15k to 18k 0.7118 4-Way 3' x 3' Cassette TN 7k to 24k 0.8819 4-Way 3' x 3' Cassette TM 28k to 36k 1.0820 4-Way 3’ x 3’ Cassette TM 42k to 48k 1.4121 High Static Ducted M1 7k to 24k 0.5722 High Static Ducted M2 7k to 24k 0.7723 High Static Ducted M2 28k to 42k 1.1524 High Static Ducted M3 28k to 54k 1.3525 High Static Ducted B8 36k to 96k 2.2026 Low Static Ducted, Low Static Ducted Bottom Return L1 5k to 9k 0.3127 Low Static Ducted, Low Static Ducted Bottom Return L2 12k to 18k 0.4228 Low Static Ducted, Low Static Ducted Bottom Return L3 21k to 24k 0.5529 Vertical / Horizontal Air Handling Unit NJ 12k to 30k 1.0430 Vertical / Horizontal Air Handling Unit NJ 36k 1.5731 Vertical / Horizontal Air Handling Unit NK 42k to 54k 2.0032 Floor Standing CE (U) 7k to 15k 0.3733 Floor Standing CF (U) 18k to 24k 0.8234 HRU: PRHR022A/023A, 032A/033A, 042A/043A — — 1.135 HRU: PRHR063A, 083A — — 2.236 ADDITIONAL Refrigerant Charge Required (Sum of lines 1 – 35)

37 Water-Source Unit Factory Refrigerant Charge

ARW*072BAS4, ARW*096BAS4, ARW*121BAS4, ARW*144BAS4 10.42ARW*072DAS4, ARW*096DAS4, ARW*121DAS4 10.42ARW*144DAS4, ARW*192DAS4 11.66

38 Total WSU FACTORY Refrigerant Charge (Sum of factory refrigerant charges for all WSUs in the system) 39 TOTAL SYSTEM CHARGE

Sum of Additional Refrigerant Charge Required (line 36) and Total WSU Factory Refrigerant Charge (line 38)

1CF (Ref.) = Correction Factor for Refrigerant Charge. 2For refrigerant charge purposes, consider only the liquid line; ignore the vapor line(s).

Page 9: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

INTRODUCTION | 9

Introduction

©

REFRIGERANT CHARGE WORKSHEETMulti V S System R410A Refrigerant Charge Calculator (lbs.)

System Tag or ID:Job Name: __________________________________________

Project Manager: ____________________________________ Date: ______________Line # Description Chassis I.D. Size Quantity CF (Ref.)1 Total (lbs.)

1 Linear feet of 1/4" liquid line tubing2 — — 0.0152 Linear feet of 3/8" liquid line tubing2 — — 0.0413 Linear feet of 1/2" liquid line tubing2 — — 0.0794 Linear feet of 5/8" liquid line tubing2 — — 0.1165 Linear feet of 3/4" liquid line tubing2 — — 0.1796 Linear feet of 7/8" liquid line tubing2 — — 0.2387 Linear feet of 1" liquid line tubing2 — — 0.3238 Standard + Art Cool Mirror SJ, SK 5k to 15k 0.539 Standard + Art Cool Mirror SJ, SK 18k to 24k 0.62

10 Standard SV 30k to 36k 1.0111 Art Cool Gallery SF 9k to 12k 0.2212 1-Way Cassette TU 7k to 12k 0.4413 1-Way Cassette TT 18k to 24k 0.6414 2-Way Cassette TS 18k to 24k 0.7515 4-Way 2' x 2' Cassette TR 5k to 7k 0.4016 4-Way 2' x 2' Cassette TR 9k to 12k 0.5517 4-Way 2' x 2' Cassette TQ 15k to 18k 0.7118 4-Way 3' x 3' Cassette TN 7k to 24k 0.8819 4-Way 3' x 3' Cassette TM 28k to 36k 1.0820 4-Way 3’ x 3’ Cassette TM 42k to 48k 1.4121 High Static Ducted M1 7k to 24k 0.5722 High Static Ducted M2 7k to 24k 0.7723 High Static Ducted M2 28k to 42k 1.1524 High Static Ducted M3 28k to 54k 1.3525 High Static Ducted B8 36k to 96k 2.2026 Low Static Ducted, Low Static Ducted Bottom Return L1 5k to 9k 0.3127 Low Static Ducted, Low Static Ducted Bottom Return L2 12k to 18k 0.4228 Low Static Ducted, Low Static Ducted Bottom Return L3 21k to 24k 0.5529 Vertical / Horizontal Air Handling Unit NJ 12k to 30k 1.0430 Vertical / Horizontal Air Handling Unit NJ 36k 1.5731 Vertical / Horizontal Air Handling Unit NK 42k to 54k 2.0032 Floor Standing CE (U) 7k to 15k 0.3733 Floor Standing CF (U) 18k to 24k 0.8234 HRU: PRHR022A/023A, 032A/033A, 042A/043A — — 1.135 HRU: PRHR063A, 083A — — 2.236 ADDITIONAL Refrigerant Charge Required (Sum of lines 1 – 35)

37 Total Outdoor Unit Factory Refrigerant Charge (Choose One)

37A ARUN024GSS4 037B ARUN038GSS4 037C ARUN048GSS4 037D ARUN053GSS4 037E ARUN060GSS4 037F ARUB060GSS4 0

38 TOTAL SYSTEM CHARGE Sum of Additional Refrigerant Charge Required (line 36) and Total ODU Factory Refrigerant Charge (from line 37A to 35F)

1CF (Ref.) = Correction Factor for Refrigerant Charge. 2For refrigerant charge purposes, consider only the liquid line; ignore the vapor line(s).

Page 10: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

10 | INTRODUCTION

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Page 11: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY CEILING CASSETTE

Mechanical Specifications on page 12General Data on page 14Electrical Data on page 16External Dimensions on page 17Electrical Wiring Diagrams on page 19Refrigerant Flow Diagrams on page 21Acoustic Data on page 22Air Velocity / Temperature Distribution on page 26Fresh Air Ventilation on page 34Capacity Tables on page 35Optional Accessories on page 40

Page 12: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

12 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

ONE-WAY CEILING CASSETTE

CasingThe case is designed to mount recessed in the ceiling and has a surface-mounted concentric grille on the bottom of the unit. The unit case is manufactured with coated metal. Cold surfaces are covered with a coated polystyrene insulating material. The case is provided with metal ears designed to support the unit weight on four corners. Ears have pre-punched holes designed to accept field-supplied all-thread rod hangers.

Ventilation AirThe case has a factory designated cutout for the connection of a field-supplied outside air duct and flange.

Architectural Filter/GrilleThe ceiling cassette assembly is provided with an off-white ABS polymeric resin architectural grille with a tapered trim edge and a hinged, spring clip (screw-less) return air filter-grille door.

Fan Assembly and ControlThe indoor unit has a single, direct-drive, cross-flow tangential Sirocco fan made of high strength ABS GP-2305 polymeric resin. The fan motor is a Brushless Digitally Controlled (BLDC) design with permanently lubricated and sealed ball bearings. The fan motor in-cludes thermal, overcurrent and low RPM protection. The fan / motor assembly is mounted on vibration attenuating rubber grommets. The fan impeller is statically and dynamically balanced. The fan speed is controlled using a microprocessor-based control algorithm that provides a high fan speed in cooling thermal ON and low fan speed in cooling thermal OFF, high fan speed in heating thermal ON and fan off in heating thermal OFF. The fan speeds can be field adjusted between low, medium, and high speeds. The fan speed algorithm provides a field-selectable fixed-speed or auto-speed setting that adjusts the fan speed to simulate natural airflow.

Air FilterReturn air is filtered with a removable, washable filter with anti-fungal treatment. Plasma filter accessories are also available separately.

Airflow Guide VanesThe architectural grille has a single directional slot diffuser with an oscillating motorized guide vane designed to change the angle airflow is discharged. The discharge range of motion is 40º in an up/down direction with the capability of locking the vanes in a field adjusted fixed position.

Microprocessor ControlsThe unit is provided with an integrated microprocessor controller capable of performing functions necessary to operate the system without the use of a wall-mounted controller. A temperature thermistor is factory-mounted in the return air stream. All unit operation parameters, excluding the operation schedule, are stored in non-volatile memory resident on the unit microprocessor.

Operating schedules are stored in select models of the optional, wall-mounted, local, or central controller. The field-supplied communication cable between the indoor unit(s) and outdoor unit is to be a minimum of 18 AWG, 2 conductor, twisted, stranded, and shielded cable (RS-485), terminated via screw terminals on the control boards. The microprocessor control provides the following functions: auto addressing, self-diagnostics, auto restart following power restoration, test run, and will operate the indoor unit using one of five operating modes:

1. Auto Changeover (Heat Recovery only)2. Heating3. Cooling4. Dry5. Fan Only

For Heat Recovery systems the Auto Changeover setting automati-cally switches control of the indoor unit between Cooling and Heating modes based on space temperature conditions.For Heat Pump systems, heated or cooled air delivery is dependent upon outdoor unit operating mode. In Heating mode, the microprocessor control will activate indoor unit operation when the indoor room temperature falls below set-point temperature. At which point, a signal is sent to the outdoor unit to begin the heating cycle. The indoor unit fan operation is delayed until coil pipe temperature reaches 76ºF. Significant airflow is generated when pipe temperature reaches 80°F. The unit is equipped with an infrared receiver designed to communicate with an LG wireless remote controller. In lieu of wireless remote or factory return air thermistor, screw terminals on the microprocessor circuit board ac-commodate various models of wall-mounted local controllers and/or a wall-mounted remote temperature sensor. The unit microprocessor is capable of accepting space temperature readings concurrently or individually from either:

1. Wall-mounted wired controller(s)2. Factory mounted return air thermistor or the optional wall- mounted wired remote temperature sensor

A single indoor unit has the capability of being controlled by up to two local wired controllers. The microprocessor controls space tem-perature using the value provided by the temperature sensor sensing a space temperature that is farthest away from the temperature set-point. The microprocessor control provides a cooling or heating

Page 13: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY | 13

One-W

ay Ceiling C

assette Product Data

©

Controls Features• Auto changeover (Heat Recovery only)• Auto operation / auto restart• External on / off control• Dual thermistor control• Dual setpoint control• Filter life display• Multiple auxiliary heater applications• Group control• High ceiling• Hot start• Self diagnostics• Timer (on / off)• Weekly schedule• Auto direction/swing (up/down)• Fan speed control• Jet cool (fast cooling)• Wi-Fi compatible• Auto fan• Leak detection

*To enable Generation 4 features, outdoor unit DIP Switch No. 3 must be set to ON. Please refer to the Multi V 5, Multi V IV, Multi V Water IV, Multi V S Engineering Manual for additional information.

mode test cycle that operates the unit for 18 minutes without regard to the space temperature. If the system is provided with an optional wall-mounted local or central controller, displayed diagnostic codes are specific, alpha-numeric, and provide the service technician with a reason for the code displayed.Indoor units are Wi-Fi compatible with the addition of an LG Wi-Fi module accessory, and can be controlled by LG’s Smart ThinQ™ app on a smart device. A field-supplied Wi-Fi network and smart device are required. The Smart ThinQ app is free, and is available for Android™ and iOS. (Android is a trademark of Google LLC.)

Condensate Lift/PumpThe indoor unit comes with a factory installed and wired condensate lift/pump capable of providing a maximum 27.5 inch lift from the bottom surface of the unit. The lift pump comes with a safety switch that shuts off the indoor unit if condensate rises too high in the drain pan.

Condensate Drain PanThe condensate drain pan is constructed of EPS (expandable poly-styrene resin).

CoilThe indoor unit coil is constructed with grooved design copper tubes with slit coil fins, two (2) rows, twenty-one (21) fins per inch.

ONE-WAY CEILING CASSETTE

Page 14: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

14 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

ONE-WAY CEILING CASSETTEGeneral Data

Model No. ARNU073TUD4 ARNU093TUD4 ARNU123TUD4Cooling Mode PerformanceCapacity (Btu/h) 7,500 9,600 12,300Max Power Input1 (W) 40 40 40L/M/H Power Input at Factory Default (W) 16 / 18 / 20 18 / 20 / 22 20 / 22 / 24

Heating Mode PerformanceCapacity (Btu/h) 8,500 10,900 13,600Max Power Input1 (W) 40 40 40L/M/H Power Input at Factory Default (W) 16 / 18 / 20 18 / 20 / 22 20 / 22 / 24

Entering Mixed AirCooling Max (°F WB) 76 76 76Heating Min (°F DB) 59 59 59

Unit DataRefrigerant Type2 R410A R410A R410ARefrigerant Control EEV EEV EEVSound Pressure3 dB(A) (H/M/L) 32 / 29 / 25 35 / 34 / 32 38 / 35 / 32Net Unit Weight (lbs.) 33 33 33Shipping Weight (lbs.) 40 40 40Grille Weight (lbs) 10 10 10Grille Shipping Weight (lbs) 16 16 16Communication Cable4 (No. x AWG) 2 x 18 2 x 18 2 x 18

FanType Cross Flow Cross Flow Cross FlowQuantity 1 1 1Motor/Drive Brushless Digitally Controlled / DirectAirflow Rate H/M/L (CFM) 290 / 258 / 226 325 / 304 / 290 353 / 325 / 290

PipingLiquid Line (in., O.D.) 1/4 Flare 1/4 Flare 1/4 FlareVapor Line (in., O.D.) 1/2 Flare 1/2 Flare 1/2 FlareCondensate Line (in., I.D.) 1 1 1

Table 1: One-Way Ceiling Cassette (TU Frames) Indoor Unit General Data.

EEV: Electronic Expansion ValvePower wiring is field supplied and must comply with the applicable local and national codes. See page 12 for detailed electrical data.This unit comes with a dry nitrogen charge.All capacities are net with a combination ratio between 95-105%. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

1Max power input is rated at maximum setting value.2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA. 3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.4Communication cable between Master ODU to IDUs / HRUs to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the communication cable shield is properly grounded to the Master ODU chassis only. Do not ground the ODU to IDUs / HRUs communication cable at any other point. Wiring must comply with all applicable local and national codes.

Page 15: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY | 15

One-W

ay Ceiling C

assette Product Data

©

ONE-WAY CEILING CASSETTEGeneral Data

Model No. ARNU183TTD4 ARNU243TTD4Cooling Mode PerformanceCapacity (Btu/h) 19,100 24,200Max Power Input1 (W) 70 70L/M/H Power Input at Factory Default (W) 24 / 28 /38 26 / 33 / 51

Heating Mode PerformanceCapacity (Btu/h) 21,500 24,200Max Power Input1 (W) 70 70L/M/H Power Input at Factory Default (W) 24 / 28 /38 26 / 33 / 51

Entering Mixed AirCooling Max (°F WB) 76 76Heating Min (°F DB) 59 59

Unit DataRefrigerant Type2 R410A R410ARefrigerant Control EEV EEVSound Pressure3 dB(A) (H/M/L) 40 / 37 / 35 43 / 40 / 36 Net Unit Weight (lbs.) 42 42Shipping Weight (lbs.) 49 49Grille Weight (lbs) 13 13Grille Shipping Weight (lbs) 20 20Communication Cable4 (No. x AWG) 2 x 18 2 x 18

FanType Cross Flow Cross FlowQuantity 1 1Motor/Drive Brushless Digitally Controlled / DirectAirflow Rate H/M/L (CFM) 470 / 427 / 385 515 / 470 / 406

PipingLiquid Line (in., O.D.) 1/4 Flare 3/8 FlareVapor Line (in., O.D.) 1/2 Flare 5/8 FlareCondensate Line (in., I.D.) 1 1

Table 2: One-Way Ceiling Cassette (TT Frames) Indoor Unit General Data.

EEV: Electronic Expansion ValvePower wiring is field supplied and must comply with the applicable local and national codes. See page 12 for detailed electrical data.This unit comes with a dry nitrogen charge.All capacities are net with a combination ratio between 95-105%. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

1Max power input is rated at maximum setting value.2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA. 3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.4Communication cable between Master ODU to IDUs / HRUs to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the communication cable shield is properly grounded to the Master ODU chassis only. Do not ground the ODU to IDUs / HRUs communication cable at any other point. Wiring must comply with all applicable local and national codes.

Page 16: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

16 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

ONE-WAY CEILING CASSETTEElectrical Data

Model Number Voltage Range MCA MOP Rated

Amps (A)

Power Supply Power Input (W)

Hz Volts Phase MaxCooling

MaxHeating L/M/H at Factory Default

TU FramesARNU073TUD4

187-2530.23

150.18

60 208-230 140 40 16 / 18 / 20

ARNU093TUD4 0.23 0.18 40 40 18 / 20 / 22ARNU123TUD4 0.23 0.18 40 40 20 / 22 / 24

TT FramesARNU183TTD4 187-253 0.38 15 0.30 60 208-230 1 70 70 24 / 28 /38ARNU243TTD4 0.38 0.30 70 70 26 / 33 / 51

Table 3: One-Way Ceiling Cassette Indoor Unit Electrical Data.

MCA : Minimum Circuit Ampacity.MOP : Maximum Overcurrent Protection.Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.Select wire size based on the larger MCA value.Instead of fuse, use circuit breaker.Max. power input is rated at maximum setting value

Page 17: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY | 17

One-W

ay Ceiling C

assette Product Data

©

ONE-WAY CEILING CASSETTEExternal Dimensions

Figure 3: ARNU073TUD4, ARNU093TUD4, ARNU123TUD4 Dimensions (PT-UUC1 Grille).

TU Frame with PT-UUC1 Grille

43-5/16

19-11/161-3/8

34-11/16 (Air outlet Hole)

6-5/8

4-3/168-1/810-11/16

3-13/16

5-1/4

2-1/4

17-13/16

1-1/1612-5/8

39-13/163-7/16

33-11/16

Unit: inchesNote: All measurements have a tolerance of ±1/4 in.

2-3/4Ø

1/8Ø

2-3/4 2-5/8

Outdoor air knockout12

13-7/8

37-1/2

Page 18: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

18 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

ONE-WAY CEILING CASSETTEExternal DimensionsTT Frame with PT-UTC Grille

Figure 4: ARNU183TTD4, ARNU243TTD4 Dimensions (PT-UTC Grille).

13/16 2-9/167-1/16

9-3/42-1/43-1/23-13/16

6-7/8

5-3/16

1-1/4

17-3/4

55-15/16

19-11/161-5/16

47-1/4 (Air Outlet Hole)

2-9/1652-7/16

46-7/16

Unit: inchesNote: All measurements have a tolerance of ±1/4 in.

15-3/8

2-3/4Ø

1/8Ø2-5/8

Outdoor air knockout

13-7/8

12

50-1/4

Page 19: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY | 19

One-W

ay Ceiling C

assette Product Data

©

Electrical Wiring DiagramTU and TT Frames

ONE-WAY CEILING CASSETTE

Figure 5: TU, TT Frame Wiring Diagram.

5/18

Page 20: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

20 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Electrical Wiring Diagram

Table 4: TU, TT Frame Wiring Diagram Legend.

ONE-WAY CEILING CASSETTE

Table 5: TU, TT Frame DIP Switch Settings.

TU and TT Frames

DIP Switch Setting Off On Remarks

SW3 GROUP CONTROL Master Slave Group control setting using 7-Day Programmable Controller; selects Master/ Slave on each indoor unit

SW4 DRY CONTACT MODE Variable Auto

Sets operation mode for optional Dry Contact accessory1. Variable: Auto or Manual Mode can be set through 7-Day

Programmable Controller or Wireless Remote Controller (factory default setting is Auto if there is no setting)

2. Auto: For Dry Contact, it is always Auto mode*For Gen 4 Multi V one-way ceiling cassette indoor units, DIP switches 1, 2, 5 through 8 must be set to OFF. These DIP switch-es are used for other models. **To enable Generation 4 features, outdoor unit DIP switch no. 3 must be set to ON. Please refer to the Multi V 5, Multi V IV, Multi V Water IV, Multi V S Engineering Manual for additional information.

Terminal Purpose FunctionCN_MOTOR1 Fan motor output Motor output of BLDCCN_WF Wi-Fi module Wi-Fi module connectionCN-PTC Auxiliary heater Auxiliary heater connectionCN_DUST N/A N/ACN_FLOAT Float switch input Float switch sensingCN_EEV EEV output EEV control outputCN_DISPLAY Display Display of indoor statusCN_OPTION Option PCB (EEPROM) Option PCB connectionCN_ROOM Room sensor Room air thermistorCN_PIPE_IN Suction pipe sensor Pipe in thermistorCN_HUMID N/A N/ACN_LEAK Leak sensor Leak sensor connectionCN_PIPE_OUT Discharge pipe sensor Pipe out thermistorCN_EXT External on/off controller External on/off cotnroller connectionCN_REMO Remote controller Remote control connectionCN_CC Dry Contact Connection to Dry Contact (Optional)CN_AIRC Air cleaner Air cleaner controlCN_VANE2 Step Motor Step motor outputCN_VANE1 Step Motor Step motor outputCN_DCDRAIN Drain pump output AC output for drain pumpCN_485 Communication Connection between indoor and outdoor unitsCN_COMM Communication Connection on Sub PCB between indoor and outdoor unitsCN_POWER AC Power supply AC power line input for indoor controller

Page 21: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY | 21

One-W

ay Ceiling C

assette Product Data

©

ONE-WAY CEILING CASSETTERefrigerant Flow Diagram

Figure 6: TU, TT Frame Piping Diagram.

Model Liquid (inch) Gas (inch)

TU FramesARNU073TUD4

1/4 1/2ARNU093TUD4ARNU123TUD4

TT FramesARNU183TTD4 1/4 1/2ARNU243TTD4 3/8 5/8

Thermistor DescriptionTH1 Return air thermistorTH2 Pipe in thermistorTH3 Pipe out thermistor

Heat Exchanger

C.F.F.

lndoor unit

EEVFilter

Filter

Th3 Th2

Th1

HeatingCooling

Table 6: TU, TT Frame Refrigerant Pipe Connection Port Diameters.

TU and TT Frames

Table 7: TU, TT Frame Thermistors.

Page 22: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

22 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

ONE-WAY CEILING CASSETTE

Table 8: One-Way Ceiling Cassette Indoor Unit Sound Pressure Levels.

ModelSound Levels dB(A)

High Fan Speed Medium Fan Speed Low Fan SpeedTU Frames

ARNU073TUD4 32.0 29.0 25.0 ARNU093TUD4 35.0 34.0 32.0 ARNU123TUD4 38.0 35.0 32.0

TT FramesARNU183TTD4 40.0 37.0 35.0 ARNU243TTD4 43.0 40.0 36.0

• Measurements are taken 4.9 ft away from the front of the unit.• Sound pressure levels are measured in dB(A) with a tolerance of ±3. • Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.Operating Conditions:

• Power source: 220V/60 Hz• Sound level will vary depending on a range of factors including the construction

(acoustic absorption coefficient) of a particular room in which the unit was installed.4.9 feet

Microphone

Figure 7: Sound Pressure Measurement Location.

Figure 8: ARNU073TUD4, ARNU093TUD4, and ARNU123TUD4 Sound Pressure Level Diagrams.

Acoustic DataSound Pressure Levels

ARNU073TUD4 ARNU093TUD4 ARNU123TUD4

Page 23: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY | 23

One-W

ay Ceiling C

assette Product Data

©

Figure 9: ARNU183TTD4 and ARNU243TTD4 Sound Pressure Level Diagrams.

ONE-WAY CEILING CASSETTEAcoustic Data

Sound Pressure Levels

ARNU183TTD4 ARNU243TTD4

Page 24: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

24 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

• Data is valid under diffuse field conditions.• Data is valid under nominal operating conditions.• Sound power level is measured using rated conditions, and tested

in a reverberation room per ISO 3741 standards.• Sound level will vary depending on a range of factors such as

construction (acoustic absorption coefficient) of particular area in which the equipment is installed.

• 2.

Table 9: One-Way Ceiling Cassette Indoor Unit Sound Power Levels.

ONE-WAY CEILING CASSETTEAcoustic DataSound Power Levels

ModelSound Power Levels dB(A)

High Fan SpeedTU Frames

ARNU073TUD4 50.0 ARNU093TUD4 53.0 ARNU123TUD4 57.0

TT FramesARNU183TTD4 59.0 ARNU243TTD4 62.0

Figure 10: ARNU073TUD4, ARNU093TUD4, and ARNU123TUD4 Sound Power Level Diagrams.ARNU073TUD4 ARNU093TUD4 ARNU123TUD4

Page 25: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY | 25

One-W

ay Ceiling C

assette Product Data

©

Figure 11: ARNU183TTD4 and ARNU243TTD4 Sound Power Level Diagrams.

ONE-WAY CEILING CASSETTEAcoustic Data

Sound Power Levels

ARNU183TTD4 ARNU243TTD4

Page 26: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

26 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Air Velocity / Temperature DistributionARNU073TUD4

ONE-WAY CEILING CASSETTE

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Figure 12: ARNU073TUD4.

00

Te mperature [°C(°F)] Te mperature [°C(°F)]

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

00

22(71.

6)

24(75.2)

24(75

.2)

24(75.2)26(78.8)

26(78.8)

26(78.8)

28(82.4)

28(82.4) 28(82.4)

28(82.4)

28(82

.4)

30(86)

30(86)

30(86

)

30(86)

32(89.6)

32( 89.6)

32(89

.6)

32(89

.6)

32(89.6)32(89.6)

32(8

9.6)

33(91.4)

33(91.

4)

35(95)

36(96.8)

36(96 .8 )

36(96.8)

36(96.8)

34(93.2)

34(93.2

)

34(93.2

)

31(87.

8)

31(87.8)

31(87

.8)

31(87.8)

31(87. 8) 34(93.2)

Cooling HeatingDischarge angle: 50°

Air velocity [m/s(ft/s)]

Discharge angle: 60°

Air velocity [m/s(ft/s)]1.5

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

0.1

0.1( 0.3)

0.50

00

0.1(0.3)

0.1(0.3)

0.1( 0 .3)

0. 1(0.3)

0.1(0.3)

0.1(0.3)

1.0(3.3)

1.0( 3

. 3)

1.0(3.3)1.0(3.3)

1.0(3.3)

0.5(1.6)0.5 (1.6)

0.5(1.

6)

0.5(1.6)

0.5(1.6) 0.5(1.6)

0.5(1.6)

0.5(1.6

)

0.5(1.6)

0.5(1.6)

0.5(1.6

)

0.5(1.

6)

0.5(1.

6)

0 .5 (1.6)

0.1(0.3)

0.1(0.3)

0.5(1.6

)

0.5(1.

6)

0.5(1.6)

0.5(1.6)

1.0( 3

.3 )

1.0(3.3)

1.0(3.3)

1.5(4.

9)

2.0(6.6

)

2.5(8.2

)

1.5(4.9)

2.5(8.2)

2.0(6

.6)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

00

Temperature [°C(°F)] Temperature [°C(°F)]

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

Cooling HeatingDischarge angle: 20°

Air velocity [m/s(ft/s)]

Discharge angle: 20°

Air velocity [m/s(ft/s)]

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

2.7m(8.9ft)

2.7m(8.9ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

2.7m(8.9ft)

2.7m(8.9ft)

0.5(1.

6)

0.5(1.6)1.0(3.3)

1.5( 4 .9) 2.0(6.6)

0.5(1. 6)

0.5(1.

6)

0.5(1.6)

1.5(4.9)1.0(3.3 )

2.0(6.6)

22(71.6 )

22(71

.6 )

20(68) 18(64.4)

24(75.2)

28(82.4)28(82.4)

30(86)

24(75.2 )

26 78

.8)

26(7 8 .8 )

26(78.8)

24(75.2)

Page 27: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY | 27

One-W

ay Ceiling C

assette Product Data

©

ONE-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Figure 14: ARNU093TUD4.

ARNU073TUD4, ARNU093TUD4

Figure 13: ARNU073TUD4, continued.

00

Te mperature [°C(°F)] Te mperature [°C(°F)]

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

Cooling HeatingDischarge angle: 70°

Air velocity [m/s(ft/s)]

Discharge angle: 70°

Air velocity [m/s(ft/s)]

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

0.5(1.6)

0.5(1.

6)

0.5(1.

6)

1.0(3.

3)

1.0(3.

3)1.5

(4.9 )

2.0(6

.6)

0. 5(1.

6)

0. 5( 1.

6)

0.5(1.6)

1.0(3.

3)

1.0(3.

3)1.5

(4.9 )

2.0(6

.6)

18(64

. 4 )

20(68

)

20(68

)

22(71

. 6)

22(71.6)

22(7

1.6)

24(75.2)24(75.2)

30(86

)

30(86

)

30(86)

30 (86)

32(89

.6)

32(89.6 )

32( 8

9 .6)

34(93

.2)

00

Te mperature [°C(°F)] Te mperature [°C(°F)]

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

Cooling HeatingDischarge angle: 20°

Air velocity [m/s(ft/s)]

Discharge angle: 20°

Air velocity [m/s(ft/s)]

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

0.5(1.6)

0.5(1.6)

1.0(3.3)1.0(3.3) 1.5(4.9) 2.0(6.6) 2.5(8.2)

0.5(1.6)1.0(3.3)1 .0 (3 .3 )

1.5(4.9) 2.0(6.6)

18(64.4)20(68)22(71.6)

22(71.6)

24(75.2)

24( 75. 2)

26(78

.8)

26(78.8)

26(78. 8)

26(78

.8)

28(82.4)28(82.4)

30(86)30(86)

Page 28: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

28 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Air Velocity / Temperature DistributionONE-WAY CEILING CASSETTE

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Figure 15: ARNU093TUD4, continued.

ARNU093TUD4

00

Temperature [°C(°F)] Temperature [°C(°F)]

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

Cooling HeatingDischarge angle: 70°

Air velocity [m/s(ft/s)]

Discharge angle: 70°

Air velocity [m/s(ft/s)]

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

0.5(1.

6)

0.5(1.6)

0.5(1.

6)0.5

(1.6)

1.5(4.

9)

1 .5(4 .

9 )2.0

(6.6)

0.5(1.6

)

0.5(1.6

)

0.5(1.6)0.5(

1.6)

0.5(1.

6)

1 .0(3.

3)

1 .0(3.

3)

1.5(4.

9)

18(64

.4 )20

( 68)

20(68

)

20(68

)

22(71

.6)

22(71

.6)

22 (71.6)

22(71.6)

24(75.2)

24(75.2)

24(75.2 )

26(78.8)

26(78.8)

32(89

.6)

32(89.6)

32(8

9. 6)

34(93

.2)

30(86

)

30(86

)

30(86)

Temperature [°C(°F)] Temperature [°C(°F)]

00

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

22(71.

6)

24(75.2)24(75.2)

26(78.

8)

28( 82.4)

28(82.4 )

28(82.

4)

28(82.4)

28 (82.4)

30(86)

30(86

)

30 (86 )

30(86)

32(89.6)

32(89.6)

32(89.6)

32(89.6)

32(8 9.6 )

32(89.6)

32(89.6)

32(89.6)

33(91.4)33(91.4)

33(91.4)

33(91

.4)

34(93. 2)

34(93.2)

34(93

.2)

35(95)

35(95

)

36(96.8 )

36(96.8)

36(96. 8)36(96

.8)

37(98

.6)

37( 9

8. 6)

38 (100.4)31(87.8)

31(87.8) 31(87.8)

31(87.

8)

Air velocity [m/s(ft/s)] Air velocity [m/s(ft/s)]

1

1

2.5

3

.

01

Cooling HeatingDischarge angle: 50° Discharge angle: 60°

00

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

0. 5(1 .6)0.5(1.6)

0.5(1.6)

0.5(1.

6)

0.5(1.6

)

0.5(1.6)

0.5(1.6)

0.5(1.6)

0.5( 1

.6)

0.5(1.6)

0.5(1.

6)

0.5(1.6)

0.5(1.6)

0.5(1.6)

0.5(1.6)

0.5(1.6)

1.0(3.

3) 1. 0(3.

3)

1.0(3.3)

1.0(3.3)

2.0(6.6

)

1.5(4.9)

1.5(4.9

) 2.0(6.6)

1.5(4.9

)

1.5(4.

9)

1.5(4.9)

0.1(0.3)0.1(0.3)

0.1(0.3)

0.1(0.3)

0.1( 0.3)

0.1(0.3)

0.1(0.3)

1.0(3.3)

1.0(3.

3)

1.0( 3

. 3)

1.0( 3

.3 )

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

Page 29: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY | 29

One-W

ay Ceiling C

assette Product Data

©

Figure 16: ARNU123TUD4.

ONE-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

ARNU123TUD4

Temperature [°C(°F)] Temperature [°C(°F)]

00

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)22(

71.6)

24(75

.2)

24(75

.2)

24(75.2)26(78.8)26(78.8) 26(78.8)

26(78.8)

26(78

.8)26(

78.8)

28(82.

4)

28( 82.4)

28(8 2. 4)

28(82.4)

28(8 2. 4)

30(86)

30(86)

30(86)

30( 86)

32(89.6

)

32(89.6)

32(89.6)32(89.6)

32(89.6)

3 2 (8 9.6)

32(89.6) 32(89.6)

33(91.

4)

33(91.4)

33(91.4)

34(93.2)

34(93.2)

34(9

3.2)

35(95)

35(95

)

36(96.8)

36(96.8)

36(96

.8)

37(98.6)

37(98.6)

37(98

.6)

31(87.8)

31(87.8

)

31(87.8)

Air velocity [m/s(ft/s)] Air velocity [m/s(ft/s)]

Cooling HeatingDischarge angle: 50° Discharge angle: 60°

00 0

01m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

0.1(0.

3)

0.1(0.3)0.1(

0.3)

0.1(0.3)

0.1(0.3)

0.5( 1

.6)

0.5(1.6) 0.5(1.6)

0.5(1.6)

0.5(1.6)0.5(

1. 6)

0.5(1.6)

0.5(1.6)

0.5(1

.6)

0 .5 (1.6 )

0.5(1.6)

0.5(1.6)

0.5(1.6

)

0.5(1.6)

0.5( 1. 6)

0.5(1.6)

0.5(1.6)

1.0(3.3)

1.0(3.3)1.0(3.3 )

1.0(3.3 )

1.0(3.

3)

1.0(3.3)1.0(3.3)

1.0(3.3)

1.0(3.

3)

1.0(3

.3)

1.5(4.

9)1.5

(4.9)

1.5(4

.9)

1.5(4.9)1.5(4.

9)

1.5(4.9)

2.0(6.6

)

2.0(6.6

)

2.5(8.2)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

00

Temperature [°C(°F)] Temperature [°C(°F)]

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

Cooling HeatingDischarge angle: 20°

Air velocity [m/s(ft/s)]

Discharge angle: 20°

Air velocity [m/s(ft/s)]

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

0.5(1.6)

0.5(1.6)

0.5(1.

6)

1.0(3.3)

1.0(3.3)

1.5(4.9)2.0(6.6) 2.5(8.2)

0.5(1.6)0.5(1.6)

0.5(1.

6)

1.0(3.3)1.0(3.3) 1. 5(4.9) 2.0(6.6) 2.5(8.2)

18(64.4)20(68) 22(71.6)

22(71.6)

22(7

1.6)

24(75

.2)

24(75 .2)

24( 75.2)

24( 75. 2)

24( 75.2)

26(78

.8)

26(78.8)

26(78.8)

26(78.

8)

28(82.4)28(82.4)

28(8

2.4)

32(89.6)30(86)30(86)

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Page 30: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

30 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Air Velocity / Temperature DistributionONE-WAY CEILING CASSETTE

ARNU123TUD4, ARNU183TTD4

00

Temperature [°C(°F)] Temperature [°C(°F)]

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

Cooling HeatingDischarge angle: 70°

Air velocity [m/s(ft/s)]

Discharge angle: 70°

Air velocity [m/s(ft/s)]

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

0.5(1.6

)

0.5(1.

6 )

0.5(1.6)0.5

(1.6)

1 .0( 3

.3)

1.0(3.3)1.0

(3.3)

1.5( 4

.9)1.5

( 4.9)

2.0( 6

.6)2. 5

( 8.2)

0. 5(1.

6)

0 .5(1 .

6 )

0. 5(1.6

)

0.5(1.6)

1.0(3.

3)

1.0(3.

3)1.5

(4.9)

2.0(6.6

)

32(89.6)

32(89

.6) 32(89

.6)

34(93

.2)

30(86)

30(8

6)

30( 8

6 )

18(64

.4)

18(64

.4)

20(6

8)

20(68)

20(68)

22(71.6)

22(7

1.6)

22(71 .6)

22(71

.6)

24(75.2)24(75.2)24(75.2)

00

Temperature [°C(°F)] Temperature [°C(°F)]

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

Cooling HeatingDischarge angle: 20°

Air velocity [m/s(ft/s)]

Discharge angle: 20°

Air velocity [m/s(ft/s)]

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

18(64.4)20(68)20(68)

20(68)

22(71.

6)

22(71 .6)

22(71.6)

22(71.

6)

22(71.6)

24(75.2)

24(75.2)

24(75

.2)26

(78.8)

26(7 8.8 )

26(78

.8)

28(82.4)

28(82.4)

28(8

2.4)

32(89.6) 34(93.2)30(86)30(86)

30(86)

0.1(0.3)

0.5(1.6)

0.5(1.6)

0.5(1.6)

0.5(1

.6)

1.0(3.3)1 .0(3. 3)

1.5(4.9) 2.0(6.6)

0.5(1.6)0.5(1.6)

0.5(1.

6)

0.5(1.6)1.0(3.3)

1.0(3.3) 1.5(4.9) 2.0(6.6)

Figure 17: ARNU123TUD4, continued.

Figure 18: ARNU183TTD4.

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Page 31: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY | 31

One-W

ay Ceiling C

assette Product Data

©

Figure 19: ARNU183TTD4, continued.

ONE-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

ARNU183TTD4

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Te mperature [°C(°F)] Te mperature [°C(°F)]

00

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

22(7 1 .6

)

24(75.2)

24(75

.2)

24(75.2)

24(75

.2)

26(78.8)

26(78

. 8)

28(82.4)

28(82

.4)

28 (82.4)

28(82

.4)

28(82.4)

30(86 )

30(86)

30(86)

32(89. 6)

32(89.6)

32(89. 6)32(89.6)32(89.6)32(89.6)

32(89

.6)

33(91.4)

33(91.

4 )

33(91.4)

3 3(91

.4 )

34(93

.2)

34 (93.2) 36(96.8)

36(96

.8)36(96

.8)

36(96.8)

37(98.

6)

38(100

.4)

31(87.8)

31(87.8)

31(87.8)

31(87.8)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

Air velocity [m/s(ft/s)] Air velocity [m/s(ft/s)]

Cooling HeatingDischarge angle: 50° Discharge angle: 60°

00

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

0.5(1.6)

0.5(1.6)

0.5(1. 6)

0. 5(1 .6 )

0.5(1.

6)

0.5(1.

6)

0.5(1.6)

0.5(1.6)

0.5(1.6)

0.5(1.6)

0.5(1.6)

0.5(1.6)

0.5(1.6)

0.5(1 .6)

0.5(1.6)

0.5(1

.6)

0.5(1.6 )

1.0(3.

3)1.0(3

.3)

1.0(3.

3)

1.0(3.3)

1.0(3.

3 )

1.0(3.3)

1.0(3.3)

1.0(3 .3)

1.5(4.

9)

1.5(4.

9)

1.5(4.9)

1.5(4.

9)

1.5(4.

9)

2.0(6.6

)

2.0(6.

6)

2. 5(8.2

)

2.5(8.2)

00

Te mperature [°C(°F)] Te mperature [°C(°F)]

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

Cooling HeatingDischarge angle: 70°

Air velocity [m/s(ft/s)]

Discharge angle: 70°

Air velocity [m/s(ft/s)]

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

18(64

.4)

18(64

.4)

18(6

4 .4)

20(68

)

20(68

)

22(71.6)

22 (7 1.6 )

22(71.

6 )

24(75.2)24(75.2)

24(75.2)

26(78.8)

26(78.8)

28(82.4)

28(82

.4)

28(8 2 .4

)

28(82.4)

32(89.

6)

32(89.

6)

32( 89.6)

32(89

.6)

32(89

.6)

34(9 3

.2)

34(93.

2)

36(9 6

.8)

36(96.

8)36

(9 6. 8

)

30( 8

6)30

(86)

30(86)30(86)

30(86)

30(86)30(86)

0.5(1.

6)

0.5(1.6

)

0.5(1 .

6 )

0.5(1.6)

1.0(3.

3)

1.0 (3.3)

1.0(3.

3)1.5(4.

9)1.5

( 4.9)

2.0(6.

6)

0.5(1.6

)

0.5(1.

6)

0.5(1.

6)

0.5(1.6)

1.0(3.3

)

1.0( 3

.3)

1.5(4

.9)2.0

(6.6

)

Page 32: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

32 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

mperature [°C(°F)]Te Temperature [°C(°F)]

00

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

22(71.

6)24

(75.2)

24(75.2)

24(75.2 )

24(75.2)

26(78.8)

26(7 8

.8 )

28(82.4)

28(82.4)

28(8

2.4)

28(82.4)

28(82.4)

30(86)

30(86)

30(86)

30(86 )

32(89.6) 32(89.6)32(89.6)

32(89.6)

32(89.

6)

33(91 .4)

33(91

.4)

33(91.4)

33(91.4)

34(93.2)

34(93

.2)35

(95)

36(96.8)

36(96.8)

36(96

.8)

37( 9

8.6)

37( 9

8.6)

31(8 7.8)

31(87.8)31(87.8)

Air velocity [m/s(ft/s)] Air velocity [m/s(ft/s)]

Cooling HeatingDischarge angle: 50° Discharge angle: 60°

00

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

0.5(1.6)

0.5(1.

6)

0.5(1.6)

0.5(1

.6)

0.5(1.6)

0.5(1.6

)

0.5(1.6)

0.5(1.6 )

0.5(1.6

)

0.5(1.

6)

0 .5(1.

6 )

0.5(1.6)

0.5(1.6) 0.5(1.6)

0.5(1.6)

0.5(1.6)

1.0(3.

3)

1. 0(3 .

3 )

1.0(3.3)1.0(3.3 )1.0( 3 .3)

1.0(3.3) 1. 0 (3 .3 )

1.0( 3

. 3 )

1.0(3.

3)

1. 5(4.

9)

1. 5(4.

9)

1.5(4.9)

1.5(4.

9)

1.5(4.

9)

1.5(4.

9)

2.0(6.6

)

2.0(6.

6)

2.5(8.2)

2.5(8.2)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

00

Temperature [°C(°F)] Temperature [°C(°F)]

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

Cooling HeatingDischarge angle: 20°

Air velocity [m/s(ft/s)]

Discharge angle: 20°

Air velocity [m/s(ft/s)]

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

0.5(1.6)

0.5(1.6)

0.1(0.

3)0.5

(1.6 )

0.5(1.

6)

1.0(3.3)1.0(3. 3)1.5(4.9)

1. 5(4 .9 ) 2.0(6.6)

0.1(0.3)0.1(0.3)0.5(1.6)

0.5(1.6)

0.5(1.

6)

1.5(4.9)1.5( 4.9) 2.0(6.6) 2.5(8.2)

18(64.4)20(68)20(68)

20(68)

22(71.6)

22(71.6)

28(8

2.4)

24(75.2)

24 (75.2)

26(78.8)26(78.8 )

26(78.8)

28(82.4)

28(82.4)

28(82

.4)

28(82.4)

32(89.6) 34(93.2)30(86)30(86)

30(86

)

Air Velocity / Temperature DistributionONE-WAY CEILING CASSETTE

ARNU243TTD4

Figure 20: ARNU243TTD4.

Page 33: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY | 33

One-W

ay Ceiling C

assette Product Data

©

Figure 21: ARNU243TTD4, continued.

Air Velocity / Temperature DistributionONE-WAY CEILING CASSETTE

ARNU243TTD4

00

Temperature [°C(°F)] Temperature [°C(°F)]

1m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

Cooling HeatingDischarge angle: 70°

Air velocity [m/s(ft/s)]

Discharge angle: 70°

Air velocity [m/s(ft/s)]

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

001m(3.3ft)2m(6.6ft)3m(9.8ft)4m(13.1ft)5m(16.4ft)

1m(3.3ft)

2m(6.6ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

2.7m(8.9ft)

18(6 4.4

)

18(64

.4 )

18( 6

4 .4)

20(68

)

20(68

)

20(68

)

20(68 )

20(68

)

20( 6

8)

20(68)

20 (68)

22(71. 6)

22 (71.6)

22(71.6)

22(71.

6)

24(75.2)24(75.2)

28(82

.4)

28(82.4)

32(89.

6)

32(89.6)

34(9

3.2)

34(9

3.2)

36(9

6.8)

30(86

)

30(86)

30(86)

0.5( 1. 6)

0.5(1.6

)

0.5(1.

6)

0.5(1.

6)

1.5(4

.9)

1.5(4.

9)2.0

(6.6)

0.5(1.

6)

0.5(1.6)

0.5(1.

6)

1.5(4.

9)2.0

(6.6)

Page 34: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

34 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Fresh Air VentilationONE-WAY CEILING CASSETTE

Figure 22: TU Frame Fresh Air Ventilation.

TU, TT Frame

Figure 23: TT Frame Fresh Air Ventilation.

TU

TT

Page 35: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY | 35

One-W

ay Ceiling C

assette Product Data

©

Cooling Capacity Tables

Model No. /Capacity Index

Outdoor Air

Temp. (°F DB)

Indoor Air Temperature (°F DB / WB)68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh

ARNU073TUD4 /7.5

-9.9 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 -5 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 0 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 5 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8

10 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 14 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 20 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 23 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 25 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 30 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 35 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 40 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 45 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 50 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 55 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 60 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.6 5.8 65 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.4 5.7 70 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.3 5.6 75 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.1 5.5 80 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.7 5.8 8.8 5.5 85 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.3 5.8 8.4 5.6 8.6 5.3 90 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.2 5.7 8.3 5.5 8.4 5.2 95 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.0 5.7 8.2 5.4 8.3 5.1

100 4.9 4.2 6.0 4.8 6.8 5.2 7.5 5.5 7.9 5.6 8.0 5.4 8.2 5.1 105 4.9 4.2 5.7 4.6 6.4 4.9 7.2 5.3 7.5 5.3 7.7 5.2 7.9 5.0 110 4.8 4.1 5.4 4.4 6.0 4.6 6.8 4.9 7.1 4.9 7.3 4.9 7.7 4.8 115 4.7 4.0 5.1 4.1 5.6 4.3 6.3 4.7 6.6 4.7 7.0 4.7 7.4 4.6 118 4.6 3.8 4.9 3.9 5.4 4.1 6.1 4.5 6.3 4.5 6.7 4.5 7.1 4.4 122 4.5 3.7 4.6 3.7 5.1 3.8 5.8 4.2 6.0 4.2 6.3 4.2 6.8 4.2

ARNU093TUD4 /9.6

-9.9 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3-5 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.30 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.35 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3

10 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.314 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.320 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.323 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 25 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 30 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 35 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 40 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 45 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 50 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 55 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 60 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.3 7.3 65 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.1 7.2 70 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 11.9 7.1 75 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 11.6 6.9 80 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.1 7.3 11.3 6.9 85 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.6 7.3 10.8 7.0 11.0 6.6 90 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.5 7.2 10.6 6.9 10.8 6.5 95 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.3 7.2 10.5 6.8 10.6 6.4

100 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.1 7.1 10.3 6.7 10.5 6.4 105 6.3 5.3 7.3 5.8 8.2 6.2 9.2 6.6 9.6 6.6 9.9 6.5 10.2 6.2 110 6.2 5.1 6.9 5.5 7.7 5.8 8.6 6.2 9.0 6.2 9.4 6.2 9.8 6.0 115 6.0 5.0 6.6 5.2 7.2 5.4 8.1 5.9 8.5 5.9 8.9 5.9 9.4 5.8 118 5.9 4.8 6.2 4.9 6.9 5.1 7.8 5.6 8.1 5.6 8.5 5.6 9.0 5.6 122 5.7 4.7 5.9 4.7 6.5 4.8 7.4 5.3 7.7 5.3 8.1 5.3 8.7 5.3

Table 10: ARNU073TUD4, ARNU093TUD4, ARNU123TUD4 Cooling Capacity Table.

ARNU073TUD4, ARNU093TUD4

ONE-WAY CEILING CASSETTE

TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 36: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

36 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Cooling Capacity Tables

Model No. /Capacity Index

Outdoor Air

Temp. (°F DB)

Indoor Air Temperature (°F DB / WB)68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh

ARNU123TUD4 /12.3

-9.9 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 -5 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 0 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 5 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 10 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 14 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 20 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 23 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 25 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 30 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 35 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 40 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 45 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 50 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 55 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 60 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.7 9.4 65 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.5 9.3 70 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.3 9.1 75 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 14.9 8.9 80 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.2 9.4 14.5 8.9 85 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.6 9.5 13.8 9.0 14.0 8.5 90 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.4 9.3 13.5 8.9 13.8 8.4 95 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.2 9.3 13.4 8.8 13.6 8.3 100 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 12.9 9.1 13.2 8.7 13.4 8.3 105 8.1 6.8 9.3 7.5 10.6 8.0 11.8 8.5 12.3 8.5 12.7 8.4 13.0 8.1 110 7.9 6.6 8.9 7.1 9.8 7.5 11.1 8.0 11.6 8.0 12.0 8.0 12.6 7.8 115 7.7 6.4 8.4 6.7 9.2 7.0 10.4 7.6 10.9 7.6 11.4 7.6 12.1 7.5 118 7.5 6.2 8.0 6.4 8.8 6.6 10.0 7.2 10.4 7.2 10.9 7.2 11.6 7.2 122 7.3 6.0 7.6 6.0 8.3 6.2 9.4 6.9 9.8 6.9 10.3 6.9 11.1 6.9

Table 11: ARNU123TUD4 Cooling Capacity Table.

ARNU123TUD4

ONE-WAY CEILING CASSETTE

TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 37: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY | 37

One-W

ay Ceiling C

assette Product Data

©

Table 12: ARNU183TTD4, ARNU243TTD4 Cooling Capacity Table.

Cooling Capacity TablesARNU183TTD4, ARNU243TTD4

Model No. /Capacity Index

Out-door Air Temp.

(°F DB)

Indoor Air Temperature (°F DB / WB)68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh

ARNU183TTD4 /19.1

-9.9 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1 -5 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1 0 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1 5 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1

10 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1 14 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1 20 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1 23 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1 25 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1 30 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1 35 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1 40 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1 45 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1 50 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1 55 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.7 14.1 60 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.4 14.0 65 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 24.0 13.8 70 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 23.7 13.6 75 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.8 14.1 23.1 13.3 80 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.4 14.3 22.1 14.0 22.5 13.2 85 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 21.2 14.1 21.4 13.4 21.8 12.7 90 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 20.9 13.9 21.0 13.2 21.4 12.5 95 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 20.5 13.8 20.9 13.1 21.2 12.4

100 12.6 10.2 15.3 11.7 17.2 12.5 19.1 13.3 20.1 13.6 20.5 13.0 20.9 12.3 105 12.6 10.2 14.5 11.1 16.4 11.9 18.3 12.7 19.0 12.7 19.7 12.5 20.2 12.0 110 12.3 9.9 13.8 10.5 15.3 11.1 17.2 11.9 18.0 11.9 18.7 11.9 19.5 11.7 115 12.0 9.6 13.1 10.0 14.4 10.5 16.2 11.4 16.9 11.4 17.8 11.4 18.7 11.2 118 11.7 9.3 12.4 9.5 13.6 9.8 15.5 10.8 16.1 10.8 17.0 10.8 18.0 10.7 122 11.3 9.0 11.8 9.0 12.9 9.3 14.7 10.2 15.3 10.2 16.0 10.2 17.2 10.2

ARNU243TTD4 /24.2

-9.9 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0 -5 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0 0 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0 5 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0

10 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0 14 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0 20 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0 23 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0 25 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0 30 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0 35 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0 40 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0 45 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0 50 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0 55 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.3 18.0 60 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 31.0 17.9 65 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 30.5 17.7 70 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 30.0 17.4 75 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.8 18.0 29.2 17.0 80 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 27.1 18.2 28.0 17.9 28.5 16.9 85 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 26.8 18.0 27.1 17.2 27.6 16.2 90 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 26.4 17.8 26.6 16.9 27.1 16.0 95 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 25.9 17.7 26.4 16.8 26.8 15.8

100 15.9 13.0 19.4 15.0 21.8 15.9 24.2 17.0 25.4 17.4 25.9 16.6 26.4 15.7 105 15.9 13.0 18.4 14.2 20.8 15.3 23.2 16.2 24.1 16.2 24.9 16.0 25.6 15.4 110 15.5 12.6 17.4 13.5 19.4 14.2 21.8 15.3 22.8 15.3 23.7 15.3 24.7 14.9 115 15.1 12.2 16.6 12.8 18.2 13.4 20.5 14.5 21.4 14.5 22.5 14.5 23.7 14.3 118 14.8 11.9 15.7 12.1 17.3 12.6 19.7 13.8 20.4 13.8 21.5 13.8 22.8 13.7 122 14.4 11.5 15.0 11.5 16.3 11.8 18.6 13.1 19.4 13.1 20.3 13.1 21.9 13.1

ONE-WAY CEILING CASSETTE

TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 38: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

38 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Table 13: ARNU073TUD4, ARNU093TUD4, ARNU123TUD4 Heating Capacity Table.

Model No. /Capacity Index

Outdoor Air Temp. Indoor Air Temperature (°F DB)59 61 64 67 70 73 76 80

°F DB °F WB TC TC TC TC TC TC TC TCMBh MBh MBh MBh MBh MBh MBh MBh

ARNU073TUD4 /7.5

-21.6 -22.0 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3-17.1 -17.5 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8-12.6 -13 5.4 5.4 5.4 5.4 5.3 5.3 5.3 5.3

-7 -7.6 5.5 5.5 5.5 5.5 5.4 5.4 5.4 5.4-4 -4.4 5.7 5.7 5.7 5.7 5.6 5.6 5.6 5.60 -0.4 5.9 5.9 5.9 5.9 5.9 5.8 5.8 5.85 4.5 6.6 6.6 6.5 6.5 6.5 6.5 6.5 6.5

10 9 6.9 6.9 6.9 6.8 6.8 6.8 6.8 6.815 14 7.3 7.3 7.3 7.3 7.3 7.3 7.2 7.120 19 7.7 7.7 7.7 7.7 7.6 7.6 7.4 7.425 23 8.1 8.1 8.1 8.1 8.1 7.9 7.8 7.430 28 8.3 8.3 8.3 8.3 8.3 8.1 7.8 7.435 32 8.5 8.5 8.5 8.5 8.4 8.3 7.8 7.440 36 8.8 8.8 8.8 8.8 8.5 8.3 7.8 7.445 41 9.2 9.2 9.2 8.9 8.5 8.3 7.8 7.447 43 9.5 9.4 9.4 8.9 8.5 8.3 7.8 7.450 46 10.2 9.8 9.4 8.9 8.5 8.3 7.8 7.455 51 10.4 9.9 9.4 8.9 8.5 8.3 7.8 7.460 56 10.4 9.9 9.4 8.9 8.5 8.3 7.8 7.4

ARNU093TUD4 /9.6

-21.6 -22.0 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5-17.1 -17.5 6.2 6.2 6.2 6.2 6.1 6.1 6.1 6.1-12.6 -13 6.9 6.9 6.9 6.9 6.8 6.8 6.8 6.8

-7 -7.6 7.1 7.1 7.1 7.1 7.0 7.0 7.0 7.0-4 -4.4 7.3 7.3 7.3 7.3 7.2 7.2 7.2 7.20 -0.4 7.5 7.5 7.5 7.5 7.5 7.4 7.4 7.45 4.5 8.5 8.4 8.3 8.3 8.3 8.3 8.3 8.3

10 9 8.8 8.8 8.8 8.7 8.7 8.7 8.7 8.715 14 9.4 9.4 9.4 9.4 9.4 9.4 9.3 9.220 19 9.9 9.9 9.9 9.9 9.7 9.7 9.5 9.425 23 10.4 10.4 10.4 10.4 10.4 10.1 10.0 9.530 28 10.6 10.6 10.6 10.6 10.6 10.4 10.0 9.535 32 10.9 10.9 10.9 10.9 10.8 10.6 10.0 9.540 36 11.3 11.3 11.3 11.3 10.9 10.6 10.0 9.545 41 11.8 11.8 11.8 11.5 10.9 10.6 10.0 9.547 43 12.2 12.1 12.0 11.5 10.9 10.6 10.0 9.550 46 13.1 12.5 12.0 11.5 10.9 10.6 10.0 9.555 51 13.4 12.6 12.0 11.5 10.9 10.6 10.0 9.560 56 13.4 12.6 12.0 11.5 10.9 10.6 10.0 9.5

ARNU123TUD4 / 12.3

-21.6 -22.0 6.9 6.9 6.9 6.9 6.8 6.8 6.8 6.8-17.1 -17.5 7.7 7.7 7.7 7.7 7.6 7.6 7.6 7.6-12.6 -13 8.6 8.6 8.6 8.6 8.5 8.5 8.5 8.5

-7 -7.6 8.8 8.8 8.8 8.8 8.7 8.7 8.7 8.7-4 -4.4 9.1 9.1 9.1 9.1 9.0 9.0 9.0 9.00 -0.4 9.4 9.4 9.4 9.4 9.4 9.3 9.3 9.35 4.5 10.6 10.5 10.3 10.3 10.3 10.3 10.3 10.3

10 9 11.0 11.0 11.0 10.9 10.9 10.9 10.9 10.915 14 11.7 11.7 11.7 11.7 11.7 11.7 11.6 11.420 19 12.4 12.4 12.4 12.4 12.1 12.1 11.9 11.825 23 12.9 12.9 12.9 12.9 12.9 12.7 12.5 11.930 28 13.2 13.2 13.2 13.2 13.2 12.9 12.5 11.935 32 13.6 13.6 13.6 13.6 13.5 13.2 12.5 11.940 36 14.1 14.1 14.1 14.1 13.6 13.2 12.5 11.945 41 14.7 14.7 14.7 14.3 13.6 13.2 12.5 11.947 43 15.2 15.1 15.0 14.3 13.6 13.2 12.5 11.950 46 16.3 15.6 15.0 14.3 13.6 13.2 12.5 11.955 51 16.7 15.8 15.0 14.3 13.6 13.2 12.5 11.9

60.0 56.0 16.7 15.8 15.0 14.3 13.6 13.2 12.5 11.9

Heating Capacity TablesARNU073TUD4, ARNU093TUD4, ARNU123TUD4

ONE-WAY CEILING CASSETTE

TC: Total Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For ODU performance data, see the respective ODU performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 39: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

ONE-WAY | 39

One-W

ay Ceiling C

assette Product Data

©

Heating Capacity TablesARNU183TTD4, ARNU243TTD4

Table 14: ARNU183TTD4, ARNU243TTD4 Heating Capacity Table.

Model No. /Capacity Index

Outdoor Air Temp. Indoor Air Temperature (°F DB)59 61 64 67 70 73 76 80

°F DB °F WB TC TC TC TC TC TC TC TCMBh MBh MBh MBh MBh MBh MBh MBh

ARNU183TTD4 /19.1

-21.6 -22.0 10.9 10.9 10.9 10.9 10.8 10.8 10.8 10.8-17.1 -17.5 12.2 12.2 12.2 12.2 12.1 12.1 12.1 12.1-12.6 -13 13.6 13.6 13.6 13.6 13.4 13.4 13.4 13.4

-7 -7.6 14.0 14.0 14.0 14.0 13.8 13.8 13.8 13.8-4 -4.4 14.4 14.4 14.4 14.4 14.2 14.2 14.2 14.20 -0.4 14.8 14.8 14.8 14.8 14.8 14.6 14.6 14.65 4.5 16.8 16.6 16.3 16.3 16.3 16.3 16.3 16.3

10 9 17.4 17.4 17.4 17.2 17.2 17.2 17.2 17.215 14 18.5 18.5 18.5 18.5 18.5 18.5 18.3 18.120 19 19.6 19.6 19.6 19.6 19.1 19.1 18.8 18.625 23 20.4 20.4 20.4 20.4 20.4 20.0 19.8 18.830 28 20.9 20.9 20.9 20.9 20.9 20.4 19.8 18.835 32 21.5 21.5 21.5 21.5 21.3 20.9 19.8 18.840 36 22.4 22.4 22.4 22.4 21.5 20.9 19.8 18.845 41 23.2 23.2 23.2 22.6 21.5 20.9 19.8 18.847 43 24.1 23.9 23.7 22.6 21.5 20.9 19.8 18.850 46 25.8 24.7 23.7 22.6 21.5 20.9 19.8 18.855 51 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.860 56 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8

ARNU243TTD4 /24.2

-21.6 -22.0 12.3 12.3 12.3 12.3 12.1 12.1 12.1 12.1-17.1 -17.5 13.8 13.8 13.8 13.8 13.6 13.6 13.6 13.6-12.6 -13 15.3 15.3 15.3 15.3 15.0 15.0 15.0 15.0

-7 -7.6 15.7 15.7 15.7 15.7 15.5 15.5 15.5 15.5-4 -4.4 16.2 16.2 16.2 16.2 16.0 16.0 16.0 16.00 -0.4 16.7 16.7 16.7 16.7 16.7 16.5 16.5 16.55 4.5 18.9 18.6 18.4 18.4 18.4 18.4 18.4 18.4

10 9 19.6 19.6 19.6 19.4 19.4 19.4 19.4 19.415 14 20.8 20.8 20.8 20.8 20.8 20.8 20.6 20.320 19 22.0 22.0 22.0 22.0 21.5 21.5 21.2 20.925 23 23.0 23.0 23.0 23.0 23.0 22.5 22.3 21.230 28 23.5 23.5 23.5 23.5 23.5 23.0 22.3 21.235 32 24.2 24.2 24.2 24.2 24.0 23.5 22.3 21.240 36 25.2 25.2 25.2 25.2 24.2 23.5 22.3 21.245 41 26.1 26.1 26.1 25.4 24.2 23.5 22.3 21.247 43 27.1 26.9 26.6 25.4 24.2 23.5 22.3 21.250 46 29.0 27.8 26.6 25.4 24.2 23.5 22.3 21.255 51 29.7 28.1 26.6 25.4 24.2 23.5 22.3 21.260 56 29.7 28.1 26.6 25.4 24.2 23.5 22.3 21.2

ONE-WAY CEILING CASSETTE

TC: Total Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 40: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

40 | ONE-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Accessories

Accessory Model Number

One-Way Ceiling Cassette Grille Kit (One Required)1 PT-UUC1 (For 7 to 12MBh One-Way Indoor Units)PT-UTC (For 18 and 24MBh One-Way Indoor Units)

Auxiliary Heater Kit1 PRARH1 (For Both TU and TT One-Way Indoor Units)

Wi-Fi Module1 PWFMDD200 (For Both TU and TT One-Way Indoor Units)

Table 15: Accessories for One-Way Ceiling-Cassette Indoor Units.

1For use with all one-way ceiling-cassette indoor units.All accessories are sold separately.

ONE-WAY CEILING CASSETTE

Page 41: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

TWO-WAY CEILING CASSETTE

Mechanical Specifications on page 42General Data on page 44Electrical Data on page 44External Dimensions on page 45Electrical Wiring Diagram on page 46Refrigerant Flow Diagram on page 48Acoustic Data on page 49Air Velocity / Temperature Distribution on page 51Capacity Tables on page 55Optional Accessories on page 57

Page 42: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

42 | TWO-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

TWO-WAY CEILING CASSETTE

CasingThe case is designed to mount recessed in the ceiling and has a surface-mounted concentric grille on the bottom of the unit. The unit case is manufactured with coated metal, and cold surfaces are covered with a coated polystyrene insulating material. The case is provided with metal ears designed to support the unit weight on four corners. Ears have pre-punched holes designed to accept field-sup-plied, all-thread rod hangers.

Ventilation AirThe case has a factory designated cutout for the connection of a field supplied outside air duct.

Architectural Filter/GrilleThe ceiling cassette assembly is provided with an off-white ABS polymeric resin architectural grille with a tapered trim edge and a hinged, spring clip (screw-less) return air filter-grille door.

Fan Assembly and ControlThe indoor unit has a single, direct-drive, turbo fan. The fan wheel is made of high strength ABS HT-700 polymeric resin. The fan motor is a Brushless Digitally-Controlled (BLDC) design with permanently lubricated and sealed ball bearings. The fan motor includes thermal, overcurrent and low RPM protection. The fan / motor assembly is mounted on vibration attenuating rubber grommets. The fan impeller is statically and dynamically balanced. The fan speed is controlled using a microprocessor-based direct digital control algorithm that provides a high fan speed in cooling thermal ON and low fan speed in cooling thermal OFF, high fan speed in heating thermal ON and fan off in heating thermal OFF. The fan speeds can be field adjusted between low, medium, and high speeds. The fan speed algorithm provides a field selectable, fixed-speed or auto-speed setting that adjusts the fan speed to simulate natural airflow.

Air FilterReturn air is filtered with a removable, washable filter with anti-fun-gal treatment.

Airflow Guide VanesThe architectural grille has two parallel directional slot diffusers each equipped with oscillating motorized guide vanes designed to change the angle airflow is discharged. Discharge range of motion is 40º in an up/down direction. The control algorithm provides the capability of locking guide vanes in a field adjusted fixed position.

Microprocessor ControlsThe unit is provided with an inte-grated microprocessor controller capable of performing functions necessary to operate the system without the use of a wall-mount-ed controller. A temperature thermistor is factory-mounted in the return air stream. All unit operation parameters, excluding the units operating schedule, are stored in non-volatile memory resident on the unit microprocessor. Operating schedules are stored in select models of the optional, wall-mounted, local, or central controller. The field-supplied communication cable between the indoor unit(s) and outdoor unit is to be a minimum of 18 AWG, 2 conductor, twisted, stranded, and shielded cable (RS 485), terminated via screw termi-nals on the control boards. The microprocessor control provides the following functions: auto addressing, self-diagnostics, auto restart following power restoration, test run, and will operate the indoor unit using one of five operating modes:

1. Auto Changeover (Heat Recovery only)2. Heating3. Cooling4. Dry5. Fan Only

For Heat Recovery systems the Auto Changeover setting automatically switches control of the indoor unit between Cooling and Heating modes based on space temperature conditions.For Heat Pump systems, heated or cooled air delivery is dependent upon outdoor unit operating mode. In Heating mode, the microprocessor control will activate indoor unit operation when the indoor room temperature falls below set-point temperature. At which point, a signal is sent to the outdoor unit to begin the heating cycle. The indoor unit fan operation is delayed until coil pipe temperature reaches 76°F. Significant airflow is generated when pipe temperature reaches 80°F. The unit is equipped with an infrared receiver designed to communicate with an LG wireless remote controller. In lieu of wireless remote or factory return air thermistor, screw terminals on the microprocessor circuit board accommodate various models of wall-mounted local controllers and or wall-mounted temperature sensors. The unit microprocessor is capable of accepting space temperature readings concurrently or individually from either:

1. Wall-mounted wired controller(s)2. Factory mounted return air thermistor or the optional wall mounted wired remote temperature sensor.

Page 43: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

TWO-WAY | 43

Two-W

ay Ceiling C

assette Product Data

©

*To enable Generation 4 features, outdoor unit DIP Switch No. 3 must be set to ON. Please refer to the Multi V 5, Multi V IV, Multi V Water IV, Multi V S Engineering Manual for additional information.

A single indoor unit has the capability of being controlled by up to two local wired controllers. The microprocessor controls space tem-perature using the value provided by the temperature sensor sens-ing a space temperature that is farthest away from the temperature set-point. The microprocessor control provides a cooling or heating mode test cycle that operates the unit for 18 minutes without regard to space temperature. If the system is provided with an optional wall-mounted or central controller, displayed diagnostic codes are specific, alpha numeric, and provide the service technician with the reason for the code displayed.

Indoor units are Wi-Fi compatible with the addition of an LG Wi-Fi module accessory, and can be controlled by LG’s Smart ThinQ™ app on a smart device. A field-supplied Wi-Fi network and smart device are required. The Smart ThinQ app is free, and is available for Android™ and iOS. (Android is a trademark of Google LLC.)

Condensate Lift/PumpThe indoor unit is provided with a factory installed and wired condensate lift/pump capable of providing a maximum 27-1/2 inch lift from the bottom surface of the unit. The lift pump comes with a safety switch that will shut off the indoor unit if condensate rises too high in the drain pan.

Condensate Drain PanThe condensate drain pan is constructed of EPS (expandable poly-styrene resin).

TWO-WAY CEILING CASSETTE

CoilThe indoor unit coil is constructed with grooved design copper tubes with slit coil fins, two (2) rows, twenty (20) fins per inch.

Controls Features• Auto changeover (Heat Recovery only)• Auto operation• Auto restart• External on/off control• Dual thermistor control• Dual set-point control• Filter life display• Multiple auxiliary heater applications• Group control• High ceiling• Hot start• Self diagnostics• Timer (on / off)• Weekly schedule• Auto direction / swing (up /down)• Fan speed control• Jet cool (fast cooling)• Auto fan• Leak detection• Wi-Fi compatible

Page 44: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

44 | TWO-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

TWO-WAY CEILING CASSETTEGeneral Data / Electrical Data

Model No. ARNU183TSA4 ARNU243TSA4Cooling Mode PerformanceCapacity (Btu/h) 19,100 24,200Max Power Input1 (W) 70 70L/M/H Power Input at Factory Default (W) 24 / 29 / 34 25 / 30 / 40

Heating Mode PerformanceCapacity (Btu/h) 21,500 27,300Max Power Input1 (W) 70 70L/M/H Power Input at Factory Default (W) 24 / 29 / 34 25 / 30 / 40

Entering Mixed AirCooling Max (°F WB) 76 76Heating Min (°F DB) 59 59

Unit DataRefrigerant Type2 R410A R410ARefrigerant Control EEV EEVSound Pressure3 dB(A) (H/M/L) 35 / 33 / 31 40 / 37 / 33Net Unit Weight (lbs.) 39.9 39.9Shipping Weight (lbs.) 49.6 49.6Grille Weight (lbs) 10.3 10.3Grille Shipping Weight (lbs) 14.3 14.3Communication Cable4 (No. x AWG) 2 x 18 2 x 18

FanType Turbo Fan Turbo FanQuantity 1 1Motor/Drive Brushless Digitally Controlled / DirectAirflow Rate H/M/L (CFM) 417 / 381 / 348 512 / 438 / 364

PipingLiquid Line (in., O.D.) 1/4 Flare 3/8 FlareVapor Line (in., O.D.) 1/2 Flare 5/8 FlareCondensate Line (in., I.D.) 1 1

Table 16: Two-Way Ceiling Cassette (TS Frames) Indoor Unit General Data.

Model Number Voltage Range MCA MOP Rated Amps (A)

Power Supply Power Input (W)

Hz Volts Phase MaxCooling

MaxHeating L/M/H at Factory Default

ARNU183TSA4 187-253 0.84 15 0.30 60 208-230 1 70 70 24 / 29 / 34ARNU243TSA4 0.30 25 / 30 / 40

Table 17: Two-Way Ceiling Cassette Indoor Unit Electrical Data.

MCA : Minimum Circuit Ampacity.MOP : Maximum Overcurrent Protection.

Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.Select wire size based on the larger MCA value.Instead of fuse, use circuit breaker.

EEV: Electronic Expansion ValvePower wiring is field supplied and must comply with the applicable local and national codes. See below for detailed electrical data.This unit comes with a dry nitrogen charge.All capacities are net with a combination ratio between 95-105%. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

1Max power Input is rated at maximum setting value.2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA. 3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.4Communication cable between Master ODU to IDUs / HRUs to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the communication cable shield is properly grounded to the Master ODU chassis only. Do not ground the ODU to IDUs / HRUs communication cable at any other point. Wiring must comply with all applicable local and national codes.

Page 45: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

TWO-WAY | 45

Two-W

ay Ceiling C

assette Product Data

©

External Dimensions

Figure 24: ARNU183TSA4, ARNU243TSA4 Dimensions.

TS Frame

TWO-WAY CEILING CASSETTE

Unit: Inch

34-13/16 (Hanging B

olt)

34-13/16

4-1/44-1/4

5-1/25-1/2 16-1/8 (Hanging Bolt)

14-1/211-13/16

6-5/81-3/4

1-3/4

5-7/84-15/16

4-15/165-1/4

7-1/2

2-9/16 (Air Outlet Hole)

3-3/16

Condensate Lift: 27-9/16

33

32-11/16

5-5/165-5/16

8-7/8

1-1/8

13/1613/16

23-5/8

9

13/16 ± 1/8

27-3/16

43-5/16

30-15/16 (Air O

utlet Hole)

Routing H

ole for Power

Wiring / C

omm

unication C

able

Liquid PipingC

onnectionVapor PipingC

onnection

Drain Piping

Connection

Routing H

ole forW

ired Rem

oteC

ontroller Wiring

Flexible D

rain H

ose

Air Intake

Ceiling C

assette Grille

Corner D

isplay Cover

(Supplied with G

rille)

Ceiling C

assette Grille K

it (PT-USC

; required, sold separately)

Air O

utlet

Knock O

ut Fresh A

ir Intake Hole

Com

munication

Line

Refrigerant / D

rain Piping D

irection

1. Unit should be installed in com

pliance with the

installation manual.

2. Unit should be grounded in accordance w

ith local, state, and federal codes and regulations.3. A

ll field-supplied electrical codes and materials

must com

ply with local, state, and federal codes

and regulations.4. R

eview the electrical inform

ation provided in the engineering and installation m

anuals for instructions on choosing the pow

er wiring, circuit

breaker; designing the electrical system; and

installation.

Refrigerant Piping

Direction

Drain Piping

Direction

Page 46: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

46 | TWO-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

TWO-WAY CEILING CASSETTEElectrical Wiring DiagramTS Frame

Figure 25: ARNU183TSA4, ARNU243TSA4 Wiring Diagram.

5/18

Page 47: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

TWO-WAY | 47

Two-W

ay Ceiling C

assette Product Data

©

Electrical Wiring DiagramTS Frame

Table 18: TS Frame Wiring Diagram Legend.

TWO-WAY CEILING CASSETTE

Table 19: TS Frame DIP Switch Settings.

DIP Switch Setting Off On Remarks

SW3 GROUP CONTROL Master Slave Group control setting using 7-Day Programmable Controller; selects Master/ Slave on each indoor unit

SW4 DRY CONTACTMODE Variable Auto

Sets operation mode for optional Dry Contact accessory1. Variable: Auto or Manual Mode can be set through 7-Day

Programmable Controller or Wireless Remote Controller (factory default setting is Auto if there is no setting)

2. Auto: For Dry Contact, it is always Auto mode*For Gen 4 Multi V two-way ceiling cassette indoor units, DIP switches 1, 2, 5 through 8 must be set to OFF. These DIP switch-es are used for other models. **To enable Generation 4 features, outdoor unit DIP switch no. 3 must be set to ON. Please refer to the Multi V 5, Multi V IV, Multi V Water IV, Multi V S Engineering Manual for additional information.

Terminal Purpose Function

CN-MOTOR1 Fan motor output Motor output of BLDC

CN-EEV EEV Output EEV Control output

CN-CC Dry Contact Dry Contact

CN-OPTION Option PCB (EEPROM) Option PCB connection

CN-ROOM Room sensor Room air thermistor

CN-PIPE_IN Suction pipe sensor Pipe in thermistor

CN-HUMID N/A N/A

CN-PIPE_OUT Discharge pipe sensor Pipe out thermistor

CN-LEAK Leak sensor Leak sensor connection

CN_EXT External on/off controller External on/off controller connection

CN-FLOAT Float switch input Float switch sensing

CN_WF Wi-Fi module Wi-Fi module connection

CN_DCDRAIN Drain pump output AC output for drain pump

CN-AIRC Air cleaner Air cleaner control

CN-PTC Auxiliary heater Auxiliary heater connection

CN-DISPLAY Display Display of indoor status

CN-VANE1 Step Motor Step motor output

CN-485 Communication Connection between indoor and outdoor units

CN-COM Communication Connection on Sub PCB between indoor and outdoor units

CN-REMO Remote controller Remote control line

CN-POWER AC Power supply AC Power line input for indoor controller

Page 48: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

48 | TWO-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

TWO-WAY CEILING CASSETTERefrigerant Flow Diagram

Figure 26: TS Piping Diagram.

TS Frame

Model Liquid (inch) Gas (inch)ARNU183TSA4 1/4 1/2ARNU243TSA4 3/8 5/8

Thermistor DescriptionTH1 Return air thermistorTH2 Pipe in thermistorTH3 Pipe out thermistor

Table 20: TS Frame Refrigerant Pipe Connection Port Diameters.

Table 21: TS Frame Thermistors.

Heat Exchanger

Turbo FanTh3

Th1

Th2

lndoor unit

EEV :Heating:Cooling

Filter

Filter

Page 49: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

TWO-WAY | 49

Two-W

ay Ceiling C

assette Product Data

©

Acoustic DataTWO-WAY CEILING CASSETTE

ModelSound Levels dB(A)

High Fan Speed Medium Fan Speed Low Fan SpeedARNU183TSA4 35.0 33.0 31.0 ARNU243TSA4 40.0 37.0 33.0

Table 22: Two-Way Ceiling Cassette Indoor Unit Sound Pressure Levels.

Figure 27: Sound Pressure Measurement Location.

Sound Pressure Levels

Figure 28: ARNU183TSA4 and ARNU243TSA4 Sound Pressure Level Diagrams.

• Measurements are taken 4.9 ft. away from the front of the unit.• Data is valid under nominal operating conditions.• Sound pressure levels are measured in dB(A) with a tolerance of ±3.• Sound pressure levels are tested in an anechoic chamber under ISO Standard

3745.•

Operating Conditions:• Power source: 220V/60 Hz• Sound level will vary depending on a range of factors including the construction

(acoustic absorption coefficient) of a particular room in which the unit was installed.

4.9 ft.

Ceiling

ARNU183TSA4

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

63 125 250 500 1000 2000 4000 8000

Oct

ave

Band

Sou

nd P

ress

ure

Leve

l (dB

= 2

0Pa

)

Octave Band Center Frequency (Hz)

NC-15

NC-20

NC-25

NC-30

NC-35

NC-40

NC-45

NC-50

NC-55

NC-60

NC-65

ApproximateHearingThreshold

HighMiddleLow

ARNU243TSA4

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

63 125 250 500 1000 2000 4000 8000

Oct

ave

Band

Sou

nd P

ress

ure

Leve

l (dB

= 2

0Pa

)

Octave Band Center Frequency (Hz)

NC-15

NC-20

NC-25

NC-30

NC-35

NC-40

NC-45

NC-50

NC-55

NC-60

NC-65

ApproximateHearingThreshold

HighMiddleLow

Page 50: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

50 | TWO-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Acoustic DataTWO-WAY CASSETTE

Sound Power Levels

• Data is valid under diffuse field conditions.• Data is valid under nominal operating conditions.• Sound power level is measured using rated conditions, and tested

in a reverberation room per ISO 3741 standards.• Sound level will vary depending on a range of factors such as

construction (acoustic absorption coefficient) of particular area in which the equipment is installed.

• 2

Table 23: Two-Way Ceiling Cassette Indoor Unit Sound Power Levels.

ModelSound Levels dB(A)

High Fan SpeedARNU183TSA4 44.0 ARNU243TSA4 48.0

Figure 29: ARNU183TSA4 and ARNU243TSA4 Sound Power Level Diagrams.ARNU183TSA4 ARNU243TSA4

10

20

30

40

50

60

70

80

90

100

125 250 500 1000 2000 4000 8000

Soun

d Po

wer

Lev

el (0

dB =

10E

-6W

/m2

)

Octave Band Center Frequency (Hz)

NR-70

NR-65

NR-60

NR-55

NR-50

NR-45

NR-40

NR-35

NR-30

NR-75

NR-25

NR-20

NR-80

NR-85

NR-90

HighMiddleLow

10

20

30

40

50

60

70

80

90

100

125 250 500 1000 2000 4000 8000

Soun

d Po

wer

Lev

el (0

dB =

10E

-6W

/m2

)

Octave Band Center Frequency (Hz)

NR-70

NR-65

NR-60

NR-55

NR-50

NR-45

NR-40

NR-35

NR-30

NR-75

NR-25

NR-20

NR-80

NR-85

NR-90

HighMiddleLow

Page 51: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

TWO-WAY | 51

Two-W

ay Ceiling C

assette Product Data

©

Air Velocity / Temperature DistributionARNU183TSA4

TWO-WAY CEILING CASSETTE

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

96.896.893.2 93.289.6 89.686 86

78.8 78.864.4 64.466.2 66.2

6868

69.8

69.8

71.6

71.6

4.9 4.91.6 1.6

0.8 0.8

3.3 3.36.6 6.6

4.9 4.93.3 3.3

6.6 6.6

1.61.6

0.8 0.8

Air velocity (ft./s)

Temperature (°F)

8.9 ft.

6.6 ft.

3.3 ft.

09.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

8.9 ft.

6.6 ft.

3.3 ft.

09.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

8.9 ft.

6.6 ft.

3.3 ft.

0

8.9 ft.

6.6 ft.

3.3 ft.

0

Air velocity (ft./s)

Temperature (°F)

CoolingDischarge angle: 35°

HeatingDischarge angle: 35°

9.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft. 9.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

ARNU183TSA4

1.6 1.66.66.6

4.9 4.9 3.33.3

68 68

69.8 69.8

71.2 71.266.2 66.2

64.4 64.4

1.6 1.63.33.3

6.6 6.6

4.94.90.8 0.8

0.80.8

82.4 82.4

86 8689.689.693.2 93.2

96.896.8

Air velocity (ft./s)

Temperature (°F)

8.9 ft.

6.6 ft.

3.3 ft.

09.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

8.9 ft.

6.6 ft.

3.3 ft.

09.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6. ft.3.3 ft.06.6 ft.9.8 ft.

8.9 ft.

6.6 ft.

3.3 ft.

0

8.9 ft.

6.6 ft.

3.3 ft.

0

Air velocity (ft./s)

Temperature (°F)

Discharge angle: 40° Discharge angle: 50°

Cooling Heating

9.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft. 9.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

Page 52: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

52 | TWO-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

TWO-WAY CEILING CASSETTE

ARNU183TSA4Air Velocity / Temperature Distribution

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

93.2 93.2

96.896.8

89.689.6

868682.482.4

0.80.8

0.81.6

3.3

4.9

71.671.6

66.266.264.4

69.869.8 6868

1.61.6 3.3

6.66.6

4.9 0.80.8

Air velocity (ft./s)

Temperature (°F)

8.9 ft.

6.6 ft.

3.3 ft.

09.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

8.9 ft.

6.6 ft.

3.3 ft.

09.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

8.9 ft.

6.6 ft.

3.3 ft.

09.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

8.9 ft.

6.6 ft.

3.3 ft.

09.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

Air velocity (ft./s)

Temperature (°F)

Discharge angle: 80° Discharge angle: 80°

Cooling Heating

Page 53: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

TWO-WAY | 53

Two-W

ay Ceiling C

assette Product Data

©

Air Velocity / Temperature DistributionARNU243TSA4

TWO-WAY CEILING CASSETTE

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

0.8 0.8

1.6 1.6

4.9 4.93.33.3

6.6 6.6

66.2 66.2

64.4 64.471.6 71.6

69.8 69.8

68 68

6.6 6.6

4.9 4.91.61.6 1.60.8 0.8

3.3 3.3

93.2 93.289.6 89.686 86

96.8 96.8

82.4 82.4

8686

Air velocity (ft./s)

Temperature (°F)

Air velocity (ft./s)

Temperature (°F)

Discharge angle: 40° Discharge angle: 50°Cooling Heating

8.9 ft.

6.6 ft.

3.3 ft.

0

8.9 ft.

6.6 ft.

3.3 ft.

0

8.9 ft.

6.6 ft.

3.3 ft.

0

8.9 ft.

6.6 ft.

3.3 ft.

0

9.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

9.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

9.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

9.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

3.3

3.33.3

3.3

4.9 4.9

1.6

1.61.6

1.60.8 0.8

6.6 6.6

64.4 64.466.2 66.2

68 68

6869.869.8 71.6 71.6

69.8 69.8

71.6 71.6

4.94.96.6 6.6

0.80.8

3.33.31.61.6

96.8 96.893.4 93.489.6 89.6

86 8682.4 82.4

Air velocity (ft./s)

Temperature (°F)

8.9 ft.

6.6 ft.

3.3 ft.

09.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

8.9 ft.

6.6 ft.

3.3 ft.

09.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

8.9 ft.

6.6 ft.

3.3 ft.

09.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

8.9 ft.

6.6 ft.

3.3 ft.

09.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

Air velocity (ft./s)

Temperature (°F)

Discharge angle: 35° Discharge angle: 35°Cooling Heating

ARNU243TSA4

Page 54: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

54 | TWO-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Air Velocity / Temperature DistributionARNU243TSA4

TWO-WAY CEILING CASSETTE

0.80.8

6.6

4.91.61.6 3.33.3

71.671.6

69.869.86866.266.2 64.468

0.8

0.80.8

0.8

1.6

6.6

1.6

3.3

4.91.6

96.896.893.293.2

89.6 89.6

868682.4 82.4

Air velocity (ft./s)

Temperature (°F)

Air velocity (ft./s)

Temperature (°F)

Discharge angle: 80° Discharge angle: 80°Cooling Heating

8.9 ft.

6.6 ft.

3.3 ft.

09.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft. 9.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

8.9 ft.

6.6 ft.

3.3 ft.

0

8.9 ft.

6.6 ft.

3.3 ft.

0

8.9 ft.

6.6 ft.

3.3 ft.

09.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft. 9.8 ft.3.3 ft. 13.1 ft.13.1 ft. 6.6 ft.3.3 ft.06.6 ft.9.8 ft.

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Page 55: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

TWO-WAY | 55

Two-W

ay Ceiling C

assette Product Data

©

Cooling Capacity Tables

Model No. /Capacity Index

Outdoor Air

Temp. (°F DB)

Indoor Air Temperature (°F DB / WB)68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh

ARNU183TSA4 /19.1

-9.9 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.5-5 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.50 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.55 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.510 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.514 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.520 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.523 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.525 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.530 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.535 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.540 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.545 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.550 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.555 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.7 14.2 14.560 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.4 14.2 14.465 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 24.0 13.9 14.270 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 23.7 13.7 13.975 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.8 14.2 23.1 13.4 13.680 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.4 14.4 22.1 14.2 22.5 13.3 13.685 10.2 15.3 11.8 17.2 12.6 19.1 13.4 21.2 14.2 21.4 13.6 21.8 12.8 13.090 10.2 15.3 11.8 17.2 12.6 19.1 13.4 20.9 14.0 21.0 13.3 21.4 12.7 12.995 10.2 15.3 11.8 17.2 12.6 19.1 13.4 20.5 13.9 20.9 13.3 21.2 12.5 12.7100 10.2 15.3 11.8 17.2 12.6 19.1 13.4 20.1 13.7 20.5 13.1 20.9 12.4 12.6105 10.2 14.5 11.2 16.4 12.1 18.3 12.8 19.0 12.8 19.7 12.7 20.2 12.1 12.3110 9.9 13.8 10.6 15.3 11.2 17.2 12.1 18.0 12.1 18.7 12.1 19.5 11.8 12.0115 9.7 13.1 10.1 14.4 10.6 16.2 11.5 16.9 11.5 17.8 11.5 18.7 11.3 11.5118 9.4 12.4 9.6 13.6 9.9 15.5 10.9 16.1 10.9 17.0 10.9 18.0 10.8 11.0122 9.1 11.8 9.1 12.9 9.3 14.7 10.3 15.3 10.3 16.0 10.3 17.2 10.3 10.5

ARNU243TSA4 /24.2

-9.9 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.1-5 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.10 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.15 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.110 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.114 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.120 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.123 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.125 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.130 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.135 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.140 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.145 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.150 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.155 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.3 17.9 18.160 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 31.0 17.8 18.065 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 30.5 17.6 17.770 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 30.0 17.3 17.475 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.8 17.9 29.2 16.9 17.080 12.9 19.4 14.9 21.8 15.8 24.2 16.9 27.1 18.1 28.0 17.8 28.5 16.8 16.985 12.9 19.4 14.9 21.8 15.8 24.2 16.9 26.8 17.9 27.1 17.1 27.6 16.1 16.390 12.9 19.4 14.9 21.8 15.8 24.2 16.9 26.4 17.7 26.6 16.8 27.1 15.9 16.195 12.9 19.4 14.9 21.8 15.8 24.2 16.9 25.9 17.6 26.4 16.7 26.8 15.8 15.9100 12.9 19.4 14.9 21.8 15.8 24.2 16.9 25.4 17.3 25.9 16.5 26.4 15.7 15.8105 12.9 18.4 14.1 20.8 15.2 23.2 16.1 24.1 16.1 24.9 15.9 25.6 15.3 15.4110 12.5 17.4 13.4 19.4 14.1 21.8 15.2 22.8 15.2 23.7 15.2 24.7 14.8 14.9115 12.2 16.6 12.7 18.2 13.3 20.5 14.4 21.4 14.4 22.5 14.4 23.7 14.2 14.3118 11.8 15.7 12.1 17.3 12.5 19.7 13.7 20.4 13.7 21.5 13.7 22.8 13.6 13.7122 11.4 15.0 11.5 16.3 11.8 18.6 13.0 19.4 13.0 20.3 13.0 21.9 13.0 13.1

Table 24: ARNU183TSA4, ARNU243TSA4 Cooling Capacity Table.

ARNU183TSA4, ARNU243TSA4

TWO-WAY CEILING CASSETTE

TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).Cooling range with the Low Ambient Baffle Kit (sold separately) installed on the outdoor unit(s) is -9.9°F to +122°F, and is achieved only when all indoor units are operating in cooling mode. Does not impact heat recovery system synchronous operating range.The System Combination Ratio must be between 50–130%.

Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 56: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

56 | TWO-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Table 25: ARNU183TSA4, ARNU243TSA4 Heating Capacity Table.

Heating Capacity TablesARNU183TSA4, ARNU243TSA4

Model No. /Capacity Index

Outdoor Air Temp. Indoor Air Temperature (°F DB)59 61 64 67 70 73 76 80

°F DB °F WB TC TC TC TC TC TC TC TCMBh MBh MBh MBh MBh MBh MBh MBh

ARNU183TSA4 /19.1

-21.6 -22.0 10.9 10.9 10.9 10.9 10.8 10.8 10.8 10.8-17.1 -17.5 12.2 12.2 12.2 12.2 12.1 12.1 12.1 12.1-12.6 -13 13.6 13.6 13.6 13.6 13.4 13.4 13.4 13.4

-7 -7.6 14.0 14.0 14.0 14.0 13.8 13.8 13.8 13.8-4 -4.4 14.4 14.4 14.4 14.4 14.2 14.2 14.2 14.20 -0.4 14.8 14.8 14.8 14.8 14.8 14.6 14.6 14.65 4.5 16.8 16.6 16.3 16.3 16.3 16.3 16.3 16.3

10 9 17.4 17.4 17.4 17.2 17.2 17.2 17.2 17.215 14 18.5 18.5 18.5 18.5 18.5 18.5 18.3 18.120 19 19.6 19.6 19.6 19.6 19.1 19.1 18.8 18.625 23 20.4 20.4 20.4 20.4 20.4 20.0 19.8 18.830 28 20.9 20.9 20.9 20.9 20.9 20.4 19.8 18.835 32 21.5 21.5 21.5 21.5 21.3 20.9 19.8 18.840 36 22.4 22.4 22.4 22.4 21.5 20.9 19.8 18.845 41 23.2 23.2 23.2 22.6 21.5 20.9 19.8 18.847 43 24.1 23.9 23.7 22.6 21.5 20.9 19.8 18.850 46 25.8 24.7 23.7 22.6 21.5 20.9 19.8 18.855 51 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.860 56 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8

ARNU243TSA4 /24.2

-21.6 -22.0 13.9 13.9 13.9 13.9 13.7 13.7 13.7 13.7-17.1 -17.5 15.5 15.5 15.5 15.5 15.3 15.3 15.3 15.3-12.6 -13 17.2 17.2 17.2 17.2 17.0 17.0 17.0 17.0

-7 -7.6 17.8 17.8 17.8 17.8 17.5 17.5 17.5 17.5-4 -4.4 18.3 18.3 18.3 18.3 18.0 18.0 18.0 18.00 -0.4 18.8 18.8 18.8 18.8 18.8 18.6 18.6 18.65 4.5 21.3 21.0 20.8 20.8 20.8 20.8 20.8 20.8

10 9 22.1 22.1 22.1 21.8 21.8 21.8 21.8 21.815 14 23.5 23.5 23.5 23.5 23.5 23.5 23.2 22.920 19 24.8 24.8 24.8 24.8 24.3 24.3 23.9 23.625 23 25.9 25.9 25.9 25.9 25.9 25.4 25.1 23.930 28 26.5 26.5 26.5 26.5 26.5 25.9 25.1 23.935 32 27.3 27.3 27.3 27.3 27.0 26.5 25.1 23.940 36 28.4 28.4 28.4 28.4 27.3 26.5 25.1 23.945 41 29.5 29.5 29.5 28.7 27.3 26.5 25.1 23.947 43 30.6 30.3 30.0 28.7 27.3 26.5 25.1 23.950 46 32.8 31.4 30.0 28.7 27.3 26.5 25.1 23.955 51 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.960 56 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.9

TWO-WAY CEILING CASSETTE

TC: Total Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 57: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

TWO-WAY | 57

Two-W

ay Ceiling C

assette Product Data

©

Optional Accessories

Accessory Model Number

Two-Way Ceiling Cassette Grille Kit (One Required) PT-USC

Auxiliary Heater Kit PRARH1

Wi-Fi Module PWFMDD200

Table 26: Optional Accessories for Two-Way Ceiling Cassette Indoor Units.

TWO-WAY CEILING CASSETTE

All accessories are sold separately.

Page 58: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAYCEILING CASSETTE

Mechanical Specifications on page 59General Data on page 61Electrical Data on page 65External Dimensions on page 66Electrical Wiring Diagrams on page 70Refrigerant Flow Diagrams on page 74Acoustic Data on page 75Air Velocity / Temperature Distribution on page 84Fresh Air Ventilation on page 106Capacity Tables on page 108Optional Accessories on page 125

2' x 2' Frame 3' x 3' Frame

Page 59: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 59

Four-Way C

eiling Cassette Product D

ata

©

CasingThe case is designed to mount recessed in the ceiling and has a surface-mounted concentric grille on the bottom of the unit. The unit case is manufactured with coated metal. Cold surfaces are covered with a coated polystyrene insulating material. The case is provided with metal ears designed to support the unit weight on four corners. Ears have pre-punched holes designed to accept field-supplied all-thread rod hangers.

Ventilation AirTQ, TR FrameThe case has a factory designated cutout for the connection of a field-supplied outside air duct. An optional flange kit is available from LG.

TM, TN FrameThe case has a factory designated cutout for the connection of a field-supplied outside air duct. LG offers two flange kits.

Supply Air Branch Duct ConnectionsFactory designated cutouts are marked on the unit case. Branch ducts provide the designer with the ability to duct up to 1/2 the unit airflow capacity to adjacent spaces. The adjacent space must be in the room where the ceiling cassette is installed. It cannot be branched to another room.

Architectural Filter/GrilleThe ceiling cassette assembly is provided with an off-white ABS polymeric resin architectural grille equipped with a tapered trim edge and a hinged, spring clip (screwless) return air filter-grille door.

TM, TN FrameThe unit case allows access to hanger rods and the inspection of piping through corner access panels on the architectural grille. The optional auto-elevating grille kit is designed to provide motorized ascent/descent of the return air grille/pre-filter assembly a distance of up to 14-3/4 feet allowing easy access to remove and clean the filter.The kit consists of two lifting mechanisms comprised of an electric motor driven winch with braided steel lifting cables. The winch kit is mounted behind the grille and is not visible during normal unit operation. The auto-elevating return air grille appearance and finish matches that of the architectural grille on similar indoor unit models equipped with the standard hinged filter grilles. The auto-elevating grille control algorithm accepts up, down, and stop control com-mands from either a wall-mounted or the lift remote controller. The algorithm does not permit the lowering of the grille while the indoor unit fan is operating. The pair of winch controllers work in unison to keep the return air grille level during lift and descent operations and will automatically stop the descent of the return air grille/filter if contact is made with any obstacle.

Fan Assembly and ControlThe indoor unit has a single, direct-drive, turbo fan. The fan wheel is made of high strength ABS HT-700 polymeric resin. The fan motor is a Brushless Digitally-Controlled (BLDC) design with permanently lubricated and sealed ball bearings. The fan motor includes thermal, overcurrent and low RPM protection. The fan/motor assembly is mounted on vibration attenuating rubber grommets. The fan impeller is statically and dynamically balanced. The fan speed is controlled using a microprocessor-based, direct digital control algorithm that provides a high fan speed in cooling thermal ON and low fan speed in cooling thermal OFF, high fan speed in heating thermal ON and fan off in heating thermal OFF. The fan speeds can be field adjusted between low, medium, and high speeds. The fan speed algorithm provides a field selectable, fixed-speed or auto-speed setting that adjusts the fan speed to simulate natural airflow.

Air FilterReturn air is filtered with a removable, washable filter with anti-fungal treatment. Plasma filter accessories are also available separately.

Airflow Guide VanesThe architectural grille has four-directional slot diffusers each equipped with independent oscillating motorized guide vanes de-signed to change the angle airflow is discharged. Discharge range of motion is 40° in an up/down direction. The unit has a guide vane control algorithm designed to sequentially change the predomi-nant discharge airflow direction in a counterclockwise pattern. The control algorithm also provides the capability of locking each guide vane independently in a field adjusted fixed position. Guide vanes provide airflow in all directions. The ends of each vane are tapered to provide airflow to the space in the direction of the four corners of the architectural grille.

Microprocessor ControlsThe unit is provided with an integrated microprocessor controller capable of performing functions necessary to operate the system without the use of a wall-mounted controller. A temperature therm-istor is factory-mounted in the return air stream. All unit operation parameters, excluding the unit operating schedule, are stored in non-volatile memory resident on the unit microprocessor. Operating schedules are stored in select models of the optional, wall-mounted, local, or central controller. The field-supplied communication cable between the indoor unit(s) and outdoor unit is to be a minimum of 18

FOUR-WAY CEILING CASSETTE

Page 60: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

60 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

AWG, 2 conductor, twisted, stranded, and shielded cable (RS-485), terminated via screw terminals on the control boards. The micro-processor control algorithms provide the following functions: auto addressing, self-diagnostics, auto restart following power restoration, test run, and will operate the indoor unit using one of five operating modes:

1. Auto Changeover (Heat Recovery only)2. Heating3. Cooling4. Dry5. Fan Only

For Heat Recovery systems the Auto Changeover setting automati-cally switches control of the indoor unit between cooling and heating modes based on space temperature conditions.For Heat Pump systems, heated or cooled air delivery is dependent upon outdoor unit operating mode.In Heating mode, the microprocessor control will activate indoor unit operation when the indoor room temperature falls below setpoint temperature. At which point, a signal is sent to the outdoor unit to begin the heating cycle. The indoor unit fan operation is delayed until coil pipe temperature reaches 76°F. Significant airflow is generated when pipe temperature reaches 80°F. The unit is equipped with an infrared receiver designed to communicate with an LG wireless remote controller. In lieu of wireless remote or factory return air thermistor, screw terminals on the microprocessor circuit board ac-commodate various models of wall-mounted local controllers and/or a wall-mounted remote temperature sensor. The unit microprocessor is capable of accepting space temperature readings concurrently or individually from either:

1. Wall-mounted wired controller(s)2. Factory mounted return air thermistor or the optional wall- mounted wired remote temperature sensor.

A single indoor unit has the capability of being controlled by up to two local wired controllers. The microprocessor controls space tem-perature using the value provided by the temperature sensor sensing a space temperature that is farthest away from the temperature set-point. The microprocessor control provides a cooling or heating mode test cycle that operates the unit for 18 minutes without regard to the space temperature. If the system is provided with an optional wall-mounted, local, or central controller, displayed diagnostic codes are specific, alpha numeric, and provide the service technician with the reason for the code displayed.

The indoor units are Wi-Fi compatible with the addition of an LG Wi-Fi module accessory, and can be controlled by LG’s Smart ThinQ™ app on a smart device. A field-supplied Wi-Fi network and smart device are required. The Smart ThinQ app is free, and is available for Android™ and iOS. (Android is a trademark of Google LLC.)

Condensate Lift/PumpThe indoor unit is provided with a factory installed and wired conden-sate lift/pump capable of providing a maximum 27-1/2 inch lift from the bottom surface of the unit. The lift pump comes with a safety switch that shuts off the indoor unit if condensate rises too high in the drain pan.

Condensate Drain PanThe condensate drain pan is constructed of EPS (expandable poly-styrene resin).

CoilThe indoor unit coil is constructed with grooved design copper tubes with slit coil fins, one (1) to two (2) rows, eighteen (18) to nineteen (19) fins per inch.

Controls Features• Auto changeover (Heat Recovery only)• Auto operation• Auto restart• External on/off control• Dual thermistor control• Dual set-point control• Filter life display• Multiple auxiliary heater applications• Group control• High ceiling• Hot start• Self diagnostics• Timer (on / off)• Weekly schedule• Auto direction / swing (up / down)• Fan speed control• Swirl wind (alternating vanes)• Jet cool (fast cooling)• Wi-Fi compatible• Auto fan• Leak detection

FOUR-WAY CEILING CASSETTE

*To enable Generation 4 features, outdoor unit DIP Switch No. 3 must be set to ON. Please refer to the Multi V 5, Multi V IV, Multi V Water IV, Multi V S Engineering Manual for additional information.

Page 61: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 61

Four-Way C

eiling Cassette Product D

ata

©

FOUR-WAY CEILING CASSETTEGeneral Data

Model No. ARNU053TRD4 ARNU073TRD4 ARNU093TRD4 ARNU123TRD4 ARNU153TQD4 ARNU183TQD4Cooling Mode PerformanceCapacity (Btu/h) 5,500 7,500 9,600 12,300 15,400 19,100Max Power Input1 (W) 30 30 30 30 30 30L/M/H Power at Factory Default (W) 11 / 12 / 13 11 / 12 / 13 12 / 13 / 14 13 / 15 / 17 18 / 21 / 24 19 / 22 /25

Heating Mode PerformanceCapacity (Btu/h) 6,100 8,500 10,900 13,600 17,100 21,500Max Power Input1 (W) 30 30 30 30 30 30L/M/H Power at Factory Default (W) 11 / 12 / 13 11 / 12 / 13 12 / 13 / 14 13 / 15 / 17 18 / 21 / 24 19 / 22 / 25

Entering Mixed AirCooling Max. (°F WB) 76 76 76 76 76 76Heating Min. (°F DB) 59 59 59 59 59 59

Unit DataRefrigerant Type2 R410A R410A R410A R410A R410A R410ARefrigerant Control EEV EEV EEV EEV EEV EEVSound Pressure3 dB(A) (H/M/L) 29 / 27 / 26 29 / 27 / 26 30 / 29 / 27 32 / 30 / 27 36 / 34 / 32 37 / 35 / 34Net Unit Weight (lbs.) 29 29 32 32 35 35Shipping Weight (lbs.) 34 34 38 38 40 40Grille Weight (lbs) 7 7 7 7 7 7Grille Shipping Weight (lbs) 11 11 11 11 11 11Communication Cable4 (No. x AWG) 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18

FanType Turbo Turbo Turbo Turbo Turbo TurboQuantity 1 1 1 1 1 1Motor/Drive Brushless Digitally Controlled / DirectAirflow Rate H/M/L (CFM) 265 / 247 / 212 265 / 247 / 212 283 / 265 / 251 307 / 283 / 247 388 / 353 / 328 396 / 388 / 353

PipingLiquid Line (in., O.D.) 1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare 1/4 FlareVapor Line (in., O.D.) 1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare 1/2 FlareCondensate Line (in., I.D.) 1 1 1 1 1 1

Table 27: Four-Way Ceiling Cassette (2' x 2' TR and TQ Frames) Indoor Unit General Data.

EEV: Electronic Expansion ValvePower wiring is field supplied and must comply with the applicable local and national codes. See page 61 for detailed electrical data.This unit comes with a dry nitrogen charge.All capacities are net with a combination ratio between 95-105%. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

1Max power Input is rated at maximum setting value.2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA. 3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.4Communication cable between Master ODU to IDUs / HRUs to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the communication cable shield is properly grounded to the Master ODU chassis only. Do not ground the ODU to IDUs / HRUs communication cable at any other point. Wiring must comply with all applicable local and national codes.

Page 62: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

62 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Model No. ARNU073TNA4 ARNU093TNA4 ARNU123TNA4 ARNU153TNA4Cooling Mode PerformanceCapacity (Btu/h) 7,500 9,600 12,300 15,400Max Power Input1 (W) 144 144 144 144L/M/H Power Input at Factory Default (W) 12 / 15 / 18 12 / 15 / 19 14 / 17 / 22 14 / 17 / 25

Heating Mode PerformanceCapacity (Btu/h) 8,500 10,900 13,600 17,100Max Power Input1 (W) 144 144 144 144L/M/H Power Input at Factory Default (W) 12 / 15 / 18 12 / 15 / 19 14 / 17 / 22 14 / 17 / 25

Entering Mixed AirCooling Max (°F WB) 76 76 76 76Heating Min (°F DB) 59 59 59 59

Unit DataRefrigerant Type2 R410A R410A R410A R410ARefrigerant Control EEV EEV EEV EEVSound Pressure3 dB(A) (H/M/L) 29 / 26 / 24 29 / 26 / 24 31 / 29 / 26 32 / 29 / 26Net Unit Weight (lbs.) 53.6 53.6 53.6 53.6Shipping Weight (lbs.) 66.1 66.1 66.1 66.1Grill Weight (lbs) 13 13 13 13Grill Shipping Weight (lbs) 20 20 20 20Communication Cable4 (No. x AWG) 2 x 18 2 x 18 2 x 18 2 x 18

FanType Turbo Turbo Turbo TurboQuantity 1 1 1 1Motor/Drive Brushless Digitally Controlled / DirectAirflow Rate H/M/L (CFM) 459 / 424 / 388 477 / 424 / 388 494 / 459 / 424 530 / 459 / 424

PipingLiquid Line (in., O.D.) 3/8 Flare 3/8 Flare 3/8 Flare 3/8 FlareVapor Line (in., O.D.) 5/8 Flare 5/8 Flare 5/8 Flare 5/8 FlareCondensate Line (in., I.D.) 1 1 1 1

Table 28: Four-Way Ceiling Cassette (3' x 3' TN Frames) Indoor Unit General Data.

FOUR-WAY CEILING CASSETTEGeneral Data

EEV: Electronic Expansion ValvePower wiring is field supplied and must comply with the applicable local and national codes. See page 61 for detailed electrical data.This unit comes with a dry nitrogen charge.All capacities are net with a combination ratio between 95-105%. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

1Max power Input is rated at maximum setting value.2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA. 3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.4Communication cable between Master ODU to IDUs / HRUs to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the communication cable shield is properly grounded to the Master ODU chassis only. Do not ground the ODU to IDUs / HRUs communication cable at any other point. Wiring must comply with all applicable local and national codes.

Page 63: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 63

Four-Way C

eiling Cassette Product D

ata

©

Model No. ARNU183TNA4 ARNU243TNA4Cooling Mode PerformanceCapacity (Btu/h) 19,100 24,200Max Power Input1 (W) 144 144L/M/H Power Input at Factory Default (W) 14 / 18 / 27 30 / 38 / 51

Heating Mode PerformanceCapacity (Btu/h) 21,500 27,300Max Power Input1 (W) 144 144L/M/H Power Input at Factory Default (W) 14 / 18 / 27 30 / 38 / 51

Entering Mixed AirCooling Max (°F WB) 76 76Heating Min (°F DB) 59 59

Unit DataRefrigerant Type2 R410A R410ARefrigerant Control EEV EEVSound Pressure3 dB(A) (H/M/L) 34 / 30 / 26 40 / 38 / 35Net Unit Weight (lbs.) 53.6 53.6Shipping Weight (lbs.) 66.1 66.1Grill Weight (lbs) 13 13Grill Shipping Weight (lbs) 20 20Communication Cable4 (No. x AWG) 2 x 18 2 x 18

FanType Turbo TurboQuantity 1 1Motor/Drive Brushless Digitally Controlled / DirectAirflow Rate H/M/L (CFM) 565 / 530 / 424 742 / 671 / 600

PipingLiquid Line (in., O.D.) 3/8 Flare 3/8 FlareVapor Line (in., O.D.) 5/8 Flare 5/8 FlareCondensate Line (in., I.D.) 1 1

Table 29: Four-Way Ceiling Cassette (3' x 3' TN Frames) Indoor Unit General Data, continued.

FOUR-WAY CEILING CASSETTEGeneral Data

EEV: Electronic Expansion ValvePower wiring is field supplied and must comply with the applicable local and national codes. See page 61 for detailed electrical data.This unit comes with a dry nitrogen charge.All capacities are net with a combination ratio between 95-105%. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

1Max power Input is rated at maximum setting value..2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA. 3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.4Communication cable between Master ODU to IDUs / HRUs to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the communication cable shield is properly grounded to the Master ODU chassis only. Do not ground the ODU to IDUs / HRUs communication cable at any other point. Wiring must comply with all applicable local and national codes.

Page 64: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

64 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Model No. ARNU283TMA4 ARNU363TMA4 ARNU423TMC4 ARNU483TMC4Cooling Mode PerformanceCapacity (Btu/h) 28,000 36,200 42,000 48,100Max Power Input1 (W) 144 144 144 144L/M/H Power Input at Factory Default (W) 31 / 43 / 52 34 / 47 / 64 53 / 75 / 104 66 / 80 / 120

Heating Mode PerformanceCapacity (Btu/h) 31,500 40,600 43,800 51,200Max Power Input1 (W) 144 144 144 144L/M/H Power Input at Factory Default (W) 31 / 43 / 52 34 / 47 / 64 53 / 75 / 104 66 / 80 / 120

Entering Mixed AirCooling Max (°F WB) 76 76 76 76Heating Min (°F DB) 59 59 59 59

Unit DataRefrigerant Type2 R410A R410A R410A R410ARefrigerant Control EEV EEV EEV EEVSound Pressure3 dB(A) (H/M/L) 41 / 39 / 35 44 / 41 / 37 45 / 41 / 38 46 / 42 / 40 Net Unit Weight (lbs.) 58.4 58.4 59 59Shipping Weight (lbs.) 70.5 70.5 69 69Grill Weight (lbs) 13 13 13 13Grill Shipping Weight (lbs) 20 20 20 20Communication Cable4 (No. x AWG) 2 x 18 2 x 18 2 x 18 2 x 18

FanType Turbo Turbo Turbo TurboQuantity 1 1 1 1Motor/Drive Brushless Digitally Controlled DirectAirflow Rate H/M/L (CFM) 812 / 741 / 635 918 / 812 / 706 1,059 / 918 / 812 1,130 / 953 / 883

PipingLiquid Line (in., O.D.) 3/8 Flare 3/8 Flare 3/8 Flare 3/8 FlareVapor Line (in., O.D.) 5/8 Flare 5/8 Flare 5/8 Flare 5/8 FlareCondensate Line (in., I.D.) 1 1 1 1

Table 30: Four-Way Ceiling Cassette (3' x 3' TM Frames) Indoor Unit General Data.

FOUR-WAY CEILING CASSETTEGeneral Data

EEV: Electronic Expansion ValvePower wiring is field supplied and must comply with the applicable local and national codes. See page 61 for detailed electrical data.This unit comes with a dry nitrogen charge.All capacities are net with a combination ratio between 95-105%. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

1Max power Input is rated at maximum setting value.2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA. 3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.4Communication cable between Master ODU to IDUs / HRUs to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the communication cable shield is properly grounded to the Master ODU chassis only. Do not ground the ODU to IDUs / HRUs communication cable at any other point. Wiring must comply with all applicable local and national codes.

Page 65: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 65

Four-Way C

eiling Cassette Product D

ata

©

FOUR-WAY CEILING CASSETTEElectrical Data

Table 31: Four-Way Ceiling Cassette (2' x 2' and 3' x 3' Frames) Indoor Unit Electrical Data.

Model Voltage Range MCA MOP Rated

Amps (A)

Power Supply Power Input (W)

Hz Volts Phase Max Cooling

MaxHeating L / M / H at Factory Default

2' x 2' FramesARNU053TRD4

187-253

0.25

15

0.2

60 208-230 1

30 30 11 / 12 / 13ARNU073TRD4 0.25 0.2 30 30 11 / 12 / 13ARNU093TRD4 0.25 0.2 30 30 12 / 13 / 14ARNU123TRD4 0.25 0.2 30 30 13 / 15 / 17ARNU153TQD4 0.25 0.2 30 30 18 / 21 / 24ARNU183TQD4 0.25 0.2 30 30 19 / 22 / 25

ARNU073TNA4

187-253

0.71

15

0.56

60 208-230 1

144 144 12 / 15 / 18ARNU093TNA4 0.71 0.56 144 144 12 / 15 / 19ARNU123TNA4 0.71 0.56 144 144 14 / 17 / 22ARNU153TNA4 0.71 0.56 144 144 14 / 17 / 25ARNU183TNA4 0.71 0.56 144 144 14 / 18 / 27ARNU243TNA4 0.71 0.56 144 144 30 / 38 / 51

ARNU283TMA4

187-253

1.6

15

1.3

60 208-230 1

144 144 31 / 43 / 52ARNU363TMA4 1.6 1.3 144 144 34 / 47 / 64ARNU423TMC4 1.6 1.3 144 144 53 / 75 / 104ARNU483TMC4 1.6 1.3 144 144 66 / 80 / 120

MCA : Minimum Circuit Ampacity.MOP : Maximum Overcurrent Protection.

Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.Select wire size based on the larger MCA value.Instead of a fuse, use the circuit breaker.

Page 66: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

66 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

FOUR-WAY CEILING CASSETTEExternal Dimensions

Figure 30: ARNU053TRD4, ARNU073TRD4, ARNU093TRD4, ARNU123TRD4 Dimensions.

TR Frame

Page 67: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 67

Four-Way C

eiling Cassette Product D

ata

©

FOUR-WAY CEILING CASSETTEExternal Dimensions

TQ Frame

Figure 31: ARNU153TQD4, ARNU183TQD4 Dimensions.U

nit: Inch (mm

)

2-13/16 (71)

5-15/16 (150)

1/8 (3)2-3/4 (70)

6-3/16 (157)

7-9/16 (192)

23-5/8 (600) (Ceiling O

pening)

23-5/8 (600) (Ceiling Opening)

20-3/8 (517) (Hanging Bolt)

20-3/8 (517) (Hanging Bolt)

10-3/16 (259)

10-3/16 (259)

10-3/16 (259)

10-3/16 (259)

20-9/16 (523) (Hanging Bolt)

18-1/8 (461) (Hanging Bolt)

22-7/16 (570)

22-7/16 (570)5-9/16(142)

2(50)1-3/16(30)

1(25)1(25)

7-3/16(183)

1-5/16 (34)

3-1/2(89)

6-1/16 (154)

24-7/16 (620)

14-15/16 (379) (Air Outlet H

ole)

24-7/16 (620)

14-15/16 (379) (Air Outlet Hole)

Max. Condensate Lift: 27-9/16 (700) or less

7-15/16(202)

7-15/16(202)

11(279)

1113224-7/16 (620)

24-7/16 (620)

PT-QC

HW

0

Page 68: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

68 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

FOUR-WAY CEILING CASSETTEExternal DimensionsTN Frame

Figure 32: ARNU073TNA4, ARNU093TNA4, ARNU123TNA4, ARNU153TNA4, ARNU183TNA4, and ARNU243TNA4 Dimensions.

Page 69: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 69

Four-Way C

eiling Cassette Product D

ata

©

FOUR-WAY CEILING CASSETTEExternal Dimensions

TM Frame

Figure 33: ARNU283TMA4, ARNU363TMA4, ARNU423TMC4, and ARNU483TMC4 Dimensions.

Page 70: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

70 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

FOUR-WAY CEILING CASSETTEElectrical Wiring DiagramTR and TQ Frames

Figure 34: ARNU053TRD4, ARNU073TRD4, ARNU093TRD4, ARNU123TRD4, ARNU153TQD4, ARNU183TQD4 Wiring Diagram.

5/18

Page 71: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 71

Four-Way C

eiling Cassette Product D

ata

©

Table 32: TR / TQ Frame Wiring Diagram Legend.

FOUR-WAY CEILING CASSETTEElectrical Wiring Diagram

TR and TQ Frames

Table 33: TR / TQ Frame DIP Switch Settings.

*For Gen 4 Multi V four-way ceiling cassette indoor units, DIP switches 1, 2, 5, 6, and 8 must be set to OFF. These DIP switch-es are used for other models. **To enable Generation 4 features, outdoor unit DIP switch no. 3 must be set to ON. Please refer to the Multi V 5, Multi V IV, Multi V Water IV, Multi V S Engineering Manual for additional information.

DIP Switch Setting Off On Remarks

SW3 GROUP CONTROL Master Slave Group control setting using 7-Day Programmable Controller; selects Master / Slave on each indoor unit

SW4 DRY CONTACT MODE Variable Auto

Sets operation mode for optional Dry Contact accessory1. Variable: Auto or Manual Mode can be set through 7-Day

Programmable Controller or Wireless Remote Controller (factory default setting is Auto if there is no setting)

2. Auto: For Dry Contact, it is always Auto mode

SW7 VENTILATORINTERLOCK Off On

Selects ventilator interlock function for four-way ceiling cassette indoor units.1. On: Automatic (vent relay will be turned on after ten [10] seconds

of indoor unit operation2. Off: Manual (ventilator needs to be set through the controller)

Terminal Purpose FunctionCN_MOTOR1 Fan motor output Motor output of BLDCCN_WF Wi-Fi module Wi-Fi module connectionCN-PTC Auxiliary heater Auxiliary heater connectionCN_DUST N/A N/ACN_FLOAT Float switch input Float switch sensingCN_EEV EEV output EEV control outputCN_DISPLAY Display Display of indoor statusCN_OPTION Option PCB (EEPROM) Option PCB connectionCN_ROOM Room sensor Room air thermistorCN_PIPE_IN Suction pipe sensor Pipe in thermistorCN_HUMID N/A N/ACN_LEAK Leak sensor Leak sensor connectionCN_PIPE_OUT Discharge pipe sensor Pipe out thermistorCN_EXT External on/off controller External on/off controller connectionCN_CC Dry Contact Connection to Dry Contact (Optional)CN_AIRC Air cleaner Air cleaner controlCN_VANE2 Step Motor Step motor outputCN_VANE1 Step Motor Step motor outputCN_DCDRAIN Drain pump output AC output for drain pumpCN_485 Communication Connection between indoor and outdoor unitsCN_COMM Communication Connection on Sub PCB between indoor and outdoor unitsCN_REMO Remote controller Remote control connectionCN_POWER AC Power supply AC power line input for indoor controller

Page 72: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

72 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

FOUR-WAY CEILING CASSETTEElectrical Wiring DiagramTN and TM Frames

Figure 35: ARNU073TNA4, ARNU093TNA4, ARNU123TNA4, ARNU153TNA4, ARNU183TNA4, ARNU243TNA4, ARNU283TMA4, ARNU363TMA4, ARNU423TMC4, ARNU483TMC4 Wiring Diagram.

5/18

Page 73: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 73

Four-Way C

eiling Cassette Product D

ata

©

FOUR-WAY CEILING CASSETTEElectrical Wiring Diagram

TN, and TM Frames

Table 34: TN, and TM Frame Wiring Diagram Legend.

Table 35: TN, and TM Frame DIP Switch Settings.

*For Gen 4 Multi V four-way ceiling cassette indoor units, DIP switches 1, 2, 5, 6, and 8 must be set to OFF. These DIP switch-es are used for other models. **To enable Generation 4 features, outdoor unit DIP switch no. 3 must be set to ON. Please refer to the Multi V 5, Multi V IV, Multi V Water IV, Multi V S Engineering Manual for additional information.

DIP Switch Setting Off On Remarks

SW3 GROUP CONTROL Master Slave Group control setting using 7-Day Programmable Controller; selects Master / Slave on each indoor unit

SW4 DRY CONTACT MODE Variable Auto

Sets operation mode for optional Dry Contact accessory1. Variable: Auto or Manual Mode can be set through 7-Day

Programmable Controller or Wireless Remote Controller (factory default setting is Auto if there is no setting)

2. Auto: For Dry Contact, it is always Auto mode

SW7 VENTILATORINTERLOCK Off On

Selects ventilator interlock function for four-way ceiling cassette indoor units.1. On: Automatic (vent relay will be turned on after ten [10] seconds

of indoor unit operation2. Off: Manual (ventilator needs to be set through the controller)

Terminal Purpose FunctionCN-MOTOR1 Fan motor output Motor output of BLDCCN-D_PUMP Drain pump output AC output for drain pumpCN-GRILL Elevation grille Elevation grille connectionCN-PTC Auxiliary heater Auxiliary heater connectionCN-FLOAT Float switch input Float switch sensingCN-EEV EEV Output EEV control outputCN-DUST N/A N/ACN-DISPLAY Display Display of indoor statusCN-OPTION Optional PCB EEPROM Option PCB connectionCN-WF Wi-Fi module Wi-Fi module connectionCN-ROOM Room sensor Room air thermistorCN-PIPE_IN Suction pipe sensor Pipe in thermistorCN_LEAK Leak sensor Leak sensor connectionCN-PIPE_OUT Discharge pipe sensor Pipe out thermistorCN-EXT External on/off controller External on/off controller connectionCN-HUMID N/A N/ACN-CC Dry contact Dry Contact connectionCN-AIRC Air cleaner Air cleaner controlCN-VANE2 Step motor Step motor outputCN-VANE1 Step motor Step motor outputCN-485 Communication Connection between indoor and outdoor unitsCN-COM Communication Connection on Sub PCB between indoor and outdoor unitsCN-REMO Wired remote controller Wired remote control connectionCN-POWER AC Power supply AC Power line

Page 74: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

74 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

FOUR-WAY CEILING CASSETTERefrigerant Flow DiagramTR, TQ, TN, TM Frames

Figure 36: TR, TQ, TN, TM Frame Piping Diagram.

Heat Exchanger

Turbo FanTH3

TH1

TH2

lndoor unit

EEV HeatingCooling

Filter

Filter

Model Liquid (inch) Vapor (inch)2' x 2' Frames

ARNU053TRD4

1/4 Flare 1/2 Flare

ARNU073TRD4ARNU093TRD4ARNU123TRD4ARNU153TQD4ARNU183TQD4

ARNU073TNA4

3/8 Flare 5/8 Flare

ARNU093TNA4ARNU123TNA4ARNU153TNA4ARNU183TNA4ARNU243TNA4

ARNU283TMA4

3/8 Flare 5/8 FlareARNU363TMA4ARNU423TMC4ARNU483TMC4

Thermistor DescriptionTH1 Return air thermistorTH2 Pipe in thermistorTH3 Pipe out thermistor

Table 36: TR, TQ, TN, TM Frame Refrigerant Pipe Connection Port Diameters.

Table 37: TR, TQ, TN, TM Frame Thermistors.

Page 75: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 75

Four-Way C

eiling Cassette Product D

ata

©

FOUR-WAY CEILING CASSETTEAcoustic Data

Sound Pressure Levels

• Measurements are taken 4.9 ft away from the front of the unit.• Sound pressure levels are measured in dB(A) with a tolerance of ±3.• Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.Operating Conditions:

• Power source: 220V/60 Hz• Sound level will vary depending on a range of factors including the construction (acous-

tic absorption coefficient) of a particular room in which the unit was installed.

Figure 37: Sound Pressure Measurement Location.

4.9 ft.

Ceiling

Microphone

Table 38: Four-Way Ceiling Cassette Indoor Unit Sound Pressure Levels.

ModelSound Pressure Levels dB(A)

High Fan Speed Medium Fan Speed Low Fan Speed2' x 2' Frames

ARNU053TRD4 29.0 27.0 26.0 ARNU073TRD4 29.0 27.0 26.0 ARNU093TRD4 30.0 29.0 27.0 ARNU123TRD4 32.0 30.0 27.0 ARNU153TQD4 36.0 34.0 32.0 ARNU183TQD4 37.0 35.0 34.0

3' x 3' ARNU073TNA4 29.0 26.0 24.0 ARNU093TNA4 29.0 26.0 24.0 ARNU123TNA4 31.0 29.0 26.0 ARNU153TNA4 32.0 29.0 26.0 ARNU183TNA4 34.0 30.0 26.0 ARNU243TNA4 40.0 38.0 35.0

ARNU283TMA4 41.0 39.0 35.0 ARNU363TMA4 44.0 41.0 37.0 ARNU423TMC4 45.0 41.0 38.0 ARNU483TMC4 46.0 42.0 40.0

Page 76: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

76 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Figure 39: ARNU123TRD4, ARNU153TQD4, and ARNU183TQD4 Sound Pressure Level Diagrams.

FOUR-WAY CEILING CASSETTEAcoustic DataSound Pressure Levels

ARNU123TRD4 ARNU153TQD4 ARNU183TQD4

ARNU053TRD4 ARNU073TRD4 ARNU093TRD4Figure 38: ARNU053TRD4, ARNU073TRD4, and ARNU093TRD4 Sound Pressure Level Diagrams.

Page 77: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 77

Four-Way C

eiling Cassette Product D

ata

©

FOUR-WAY CEILING CASSETTEAcoustic Data

Sound Pressure Levels

Figure 40: ARNU073TNA4, ARNU093TNA4, and ARNU123TNA4 Sound Pressure Level Diagrams.

ARNU073TNA4 ARNU093TNA4 ARNU123TNA4

Page 78: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

78 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

ARNU283TMA4

Figure 42: ARNU283TMA4 Sound Pressure Level Diagram.

Figure 41: ARNU153TNA4, ARNU183TNA4, and ARNU243TNA4 Sound Pressure Level Diagrams.ARNU153TNA4 ARNU183TNA4 ARNU243TNA4

FOUR-WAY CEILING CASSETTEAcoustic DataSound Pressure Levels

Page 79: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 79

Four-Way C

eiling Cassette Product D

ata

©

ARNU423TMC4 ARNU483TMC4Figure 43: ARNU363TMA4, ARNU423TMCA, and ARNU483TMCA Sound Pressure Level Diagrams.

FOUR-WAY CEILING CASSETTEAcoustic Data

Sound Pressure Levels

ARNU363TMA4

Page 80: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

80 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

• Data is valid under diffuse field conditions.• Data is valid under nominal operating conditions.• Sound power level is measured using rated conditions, and tested

in a reverberation room per ISO 3741 standards.• Sound level will vary depending on a range of factors such as

construction (acoustic absorption coefficient) of particular area in which the equipment is installed.

• 2

FOUR-WAY CEILING CASSETTEAcoustic DataSound Power Levels

Table 39: Four-Way Ceiling Cassette Indoor Unit Sound Power Levels.

Figure 44: ARNU053TRD4, ARNU073TRD4, and ARNU093TRD4 Sound Power Level Diagrams.ARNU053TRD4 ARNU073TRD4 ARNU093TRD4

Model Sound Power Levels dB(A)High Fan Speed

2' x 2' FramesARNU053TRD4 46.0 ARNU073TRD4 46.0 ARNU093TRD4 47.0 ARNU123TRD4 48.0 ARNU153TQD4 51.0 ARNU183TQD4 52.0

3' x 3' ARNU073TNA4 44.0 ARNU093TNA4 44.0 ARNU123TNA4 46.0 ARNU153TNA4 47.0 ARNU183TNA4 48.0 ARNU243TNA4 58.0

ARNU283TMA4 56.0 ARNU363TMA4 63.0 ARNU423TMC4 63.0 ARNU483TMC4 65.0

Page 81: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 81

Four-Way C

eiling Cassette Product D

ata

©

Figure 45: ARNU123TRD4, ARNU153TQD4, and ARNU183TQD4 Sound Power Level Diagrams.

ARNU123TRD4 ARNU153TQD4 ARNU183TQD4

FOUR-WAY CEILING CASSETTEAcoustic Data

Sound Power Levels

Page 82: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

82 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

FOUR-WAY CEILING CASSETTEAcoustic DataSound Power Levels

Figure 46: ARNU073TNA4, ARNU093TNA4, and ARNU123TNA4 Sound Power Level Diagrams.ARNU073TNA4 ARNU093TNA4 ARNU123TNA4

Figure 47: ARNU153TNA4, ARNU183TNA4, and ARNU243TNA4 Sound Power Level Diagrams.ARNU153TNA4 ARNU183TNA4 ARNU243TNA4

Page 83: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 83

Four-Way C

eiling Cassette Product D

ata

©

ARNU423TMC4 ARNU483TMC4

Figure 48: ARNU283TMA4 Sound Power Level Diagram.

Figure 49: ARNU363TMA4 Sound Power Level Diagram.

ARNU283TMA4

ARNU363TMA4

Figure 50: ARNU423TMC4 and ARNU483TMC4 Sound Power Level Diagrams.

FOUR-WAY CEILING CASSETTEAcoustic Data

Sound Power Levels

Page 84: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

84 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature DistributionARNU053TRD4

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Discharge angle: 20°

Air velocity ft/s

Temperature (°F)

0

0

Discharge angle: 20°

Air velocity ft/s

Temperature (°F)

0

0

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

3.3

6.6

4.9

1.6

3.3

6.6

4.9

1.6

3.31.6

75.2

71.6

69.8

68

75.2

75.2

71.6

69.8

68

75.2

1.63.3

4.9

6.6

1.6

3.3

4.9

6.6

3.3

75.2

75.2

78.8

82.4

86 75.2

75.2

78.8

82.4

86

Discharge angle: 40°

Air velocity ft/s

Temperature (°F)

0

6.66.6

4.94.93.33.3

1.61.6

0

64.4

68

71.6

75.2

64.468

71.6

75.2

Discharge angle: 50°

Air velocity ft/s

Temperature (°F)

0

0

91.491.4

80.680.6

75.2 75.2

69.8

64.4

69.8

64.4

6.6

4.9

3.3

1.6

6.6

4.9

3.3

1.6

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

gnitaeHgnilooC

gnitaeHgnilooC

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft 8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

Figure 51: ARNU053TRD4.

Page 85: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 85

Four-Way C

eiling Cassette Product D

ata

©

ARNU053TRD4, ARNU073TRD4

Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

0

0

Discharge angle: 70°

Air velocity ft/s

Temperature(°F)

0

0

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

0.7

0.7

0.7

2.3

3.9

0.7

0.7

0.7

2.3

3.9

73.4

73.4

68

71.666.2

73.4

73.4

68

71.6 66.2

1.6

1.6

1.63.3

3.3

4.9

1.6

1.6

3.3

4.9

78.8

82.4

86

89.6

78.8

82.4

86

89.6

gnitaeHgnilooC

Discharge angle: 20°

Air velocity ft/s

Temperature (°F)

0

0

Discharge angle: 20°

Air velocity ft/s

Temperature (°F)

0

0

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

3.3

6.6

4.9

1.6

3.3

6.6

4.9

1.6

3.31.6

75.2

71.6

69.8

68

75.2

75.2

71.6

69.8

68

75.2

1.63.3

4.9

6.6

1.6

3.3

4.9

6.6

3.3

75.2

75.2

78.8

82.4

86 75.2

75.2

78.8

82.4

86

gnitaeHgnilooC

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft 8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Figure 52: ARNU053TRD4, continued.

Figure 53: ARNU073TRD4.

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

Page 86: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

86 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

0

0

Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

0

0

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

0.7

0.7

0.7

2.3

3.9

0.7

0.7

0.7

2.3

3.9

73.4

73.4

68

71.666.2

73.4

73.4

68

71.6 66.2

1.6

1.6

1.63.3

3.3

4.9

1.6

1.6

3.3

4.9

78.8

82.4

86

89.6

78.8

82.4

86

89.6

gnitaeHgnilooC

Discharge angle: 40°

Air velocity ft/s

Temperature (°F)

0

6.66.6

4.94.93.33.3

1.61.6

0

64.4

68

71.6

75.2

64.468

71.6

75.2

Discharge angle: 50°

Air velocity ft/s

Temperature (°F)

0

0

91.491.4

80.680.6

75.2 75.2

69.8

64.4

69.8

64.4

6.6

4.9

3.3

1.6

6.6

4.9

3.3

1.6

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

gnitaeHgnilooC

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft 8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Figure 54: ARNU073TRD4, continued.

ARNU073TRD4

Page 87: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 87

Four-Way C

eiling Cassette Product D

ata

©

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Discharge angle: 20°

Air velocity ft/s

Temperature (°F)

0

0

Discharge angle: 20°

Air velocity ft/s

Temperature (°F)

0

0

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

3.3

6.6

4.9

1.6

3.3

6.6

4.9

1.6

3.31.6

75.2

71.6

69.8

68

75.2

75.2

71.6

69.8

68

75.2

1.63.3

4.9

6.6

1.6

3.3

4.9

6.6

3.3

75.2

75.2

78.8

82.4

86 75.2

75.2

78.8

82.4

86

gnitaeHgnilooC

Discharge angle: 40°

Air velocity ft/s

Temperature (°F)

0

6.66.6

4.94.93.33.3

1.61.6

0

64.4

68

71.6

75.2

64.468

71.6

75.2

Discharge angle: 50°

Air velocity ft/s

Temperature (°F)

0

0

91.491.4

80.680.6

75.2 75.2

69.8

64.4

69.8

64.4

6.6

4.9

3.3

1.6

6.6

4.9

3.3

1.6

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

gnitaeHgnilooC

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft 8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

Figure 55: ARNU093TRD4.

ARNU093TRD4

Page 88: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

88 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

ARNU093TRD4, ARNU123TRD4

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Discharge angle: 20°

Air velocity ft/s

Temperature (°F)

0

0

Discharge angle: 20°

Air velocity ft/s

Temperature (°F)

0

0

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

3.3

3.3

6.6

4.9

1.6

3.3

6.6

4.9

1.6

75.2

69.8

71.6

68

75.2

69.8

71.6

68

1.6

3.3

4.96.6

8.21.6

1.6

3.3

4.96.6

8.21.6

71.6

78.8

82.486

89.6

71.6

78.8

82.486

89.6

gnitaeHgnilooC

Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

0

0

Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

0

0

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

0.7

0.7

0.7

2.3

3.9

0.7

0.7

0.7

2.3

3.9

73.4

73.4

68

71.666.2

73.4

73.4

68

71.6 66.2

1.6

1.6

1.63.3

3.3

4.9

1.6

1.6

3.3

4.9

78.8

82.4

86

89.6

78.8

82.4

86

89.6

gnitaeHgnilooC

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft 8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

8.2 ft 4.9 ft 0 ft 8.2 ft4.9 ft

Figure 56: ARNU093TRD4, continued.

Figure 57: ARNU123TRD4.

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

Page 89: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 89

Four-Way C

eiling Cassette Product D

ata

©

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

ARNU123TRD4

Discharge angle: 40°

Air velocity ft/s

Temperature (°F)

8.9 ft

6.6 ft

3.3 ft

08.2 ft 0 ft

8.9 ft

6.6 ft

3.3 ft

0

(.0

1 .5 ( )1 .5 ( )

1 .0 3)1 .0 ( )

0 .5 (0 .5 (

18(6 )18(6 )

20(20(6 )

22(722(7 )

24(7 )24(75 )

6.66.6

4.94.9

3.33.3

1.61.6

64.464.4

6868

71.671.6

75.275.2

Discharge angle: 50°

Air velocity ft/s

Temperature (°F)

.01.5(4.5 (

1 .1 .0 )

0 .5 6)0 .5 (

33(933(9

30(0(27(80 . )27(8 )

24(7 )24(7 )21(621(6 )

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

6.66.64.94.9

3.33.3

1.61.6

91.491.4

868680.680.6

75.275.269.869.8

gnitaeHgnilooC

Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

0

0

Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

0

0

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

1.6

1.64.9

3.3

1.6

4.9

3.3

71.6 71.668

64.4

60.8

68

64.4

60.8

4.9

4.9

3.3

4.9

4.9

3.3

4.9

75.2

78.882.4

86

89.6

75.2

78.882.4

86

89.6

gnitaeHgnilooC

4.9 ft 4.9 ft 8.2 ft

8.2 ft 0 ft4.9 ft 4.9 ft 8.2 ft

8.2 ft 0 ft4.9 ft 4.9 ft 8.2 ft

8.2 ft 0 ft4.9 ft 4.9 ft 8.2 ft 8.2 ft 0 ft4.9 ft 4.9 ft 8.2 ft

8.2 ft 0 ft4.9 ft 4.9 ft 8.2 ft

8.2 ft 0 ft4.9 ft 4.9 ft 8.2 ft

8.2 ft 0 ft4.9 ft 4.9 ft 8.2 ft

Figure 58: ARNU123TRD4, continued.

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

Page 90: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

90 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature DistributionARNU153TQD4

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Discharge angle: 40°

0

0

6.66.64.94.9

3.33.3

1.61.6

Discharge angle: 50°

0

0

91.491.4

80.680.6

75.275.269.869.8

75.2

6.66.6

4.94.9

3.33.3

1.61.6

64.464.468

71.671.6

68

75.2

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

gnitaeHgnilooC

Discharge angle: 20°

0

0

Discharge angle: 20°

0

0

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

69.8

68

66.2

75.2

69.8

68

66.2

75.2

3.3

4.9

4.9

6.6 8.2

3.34.9

6.68.2

78.8

82.486

89.6 78.8

82.486

89.6

3.3

4.9 6.6

8.2

3.3

4.96.6

8.24.9

gnitaeHgnilooC

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

Figure 59: ARNU153TQD4.

Page 91: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 91

Four-Way C

eiling Cassette Product D

ata

©

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

ARNU153TQD4, ARNU183TQD4

Discharge angle: 70°

0

0

Discharge angle: 70°

0

0

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

1.6

1.6

3.3

4.9

1.6

3.3

4.9

68

73.4

66.2

64.4

68

73.4

66.2

64.4

1.63.3

4.9

6.6

1.63.3

4.9

6.6

86

89.6

93.2

78.886

89.6

93.2

78.8

gnitaeHgnilooC

Discharge angle: 20°

0

0

Discharge angle: 20°

0

0

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

6.6

8.23.3

4.93.3 3.36.6

8.2

4.9

73.468

73.468

3.3

3.3

4.9

6.68.2

3.34.9

6.68.2

86

91.4

75.2

75.2

86

91.4

75.2

75.2

69.8

75.2 75.2

69.8 80.6 80.6

gnitaeHgnilooC

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft 13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

Figure 60: ARNU153TQD4, continued.

Figure 61: ARNU183TQD4.

Page 92: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

92 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

ARNU183TQD4

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Discharge angle: 70°

0

0

Discharge angle: 70°

0

0

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

3.3 1.6

1.6

4.9

3.31.6

1.6

4.94.9

69.8

6866.2

64.469.8

68 66.2

64.4

1.61.6

3.3

3.3

4.9

6.6

1.61.6

3.3

4.9

6.6

71.6

75.286 78.8

82.4 75.2

71.6

75.28678.8

82.475.2

gnitaeHgnilooC

Discharge angle: 40°

Air velocity ft/s

Temperature (°F)

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

18(64 )18(6 )20( 8)

22(722(7 )

24(7 )24(7 )

.0 . )2 .0 ( 6 )

1 .5 ( )1 .5 ( )

1 .0 ( )1 .0 ( )5 (10 .5 ( )

64.464.46868

71.671.6

75.275.2

6.66.6

4.94.9

3.33.31.61.6

Discharge angle: 50°

Air velocity ft/s

Temperature (°F)

.2.0(

1 .5 ( )1 .5 ( )

1 .0 )1 .0

.5 (0 .5 (

33(933(9 )

0(30

27(80 )27(8 )24(7 )24(7 )

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

6.66.6

4.94.9

3.33.3

1.61.6

91.491.4

8686

80.680.6 75.275.221(6 )21(69.8)21(69 .8 ) 69.869.8

gnitaeHgnilooC

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft3.3 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft3.3 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft3.3 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft3.3 ft 13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft3.3 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft3.3 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft3.3 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft3.3 ft

Figure 62: ARNU183TQD4, continued.

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

Page 93: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 93

Four-Way C

eiling Cassette Product D

ata

©

Figure 63: ARNU073TNA4 and ARNU093TNA4.Discharge angle: 20°

Air velocity ft/s

Temperature (°F)

Discharge angle: 20°

Air velocity ft/s

Temperature (°F)

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

1.5(4.9)1.5(4.9)4.91.5(4.9 )4.9 1.0(3.31.0(3.3)1.0(3.3)3.30.5(1.6)0.5(1.6)1.60.50.51.6

18(64.4)18(64.4)64.418(64.4)18(64.4)64.420(68)20(68)6820(68)20(68)68

22(71.6)22(71.6)71.622(71.6)22(71.6)71.6

1.5(4. )4.91.5(4.91.5(4.9)4.9 2.6.62.0(6.6)2.0(6.6)6.63.3 )1.0(3.3)1.0(3.3)3.3

0.5(1.6)0.5(1.6)1.60.5(1.6 )0.5(1.6 )1.6

28(82 )82.428(82.4)28(82.4)82.4

)8630(86)30(86)8632(89.6 )89.632(8 )89.6 34(93.2)34(93.2)93.234(93.2)34(93.2)93.2 36(96.8)36(96.8)96.836(96.8 )96.8

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft 9.8 ft13.1 ft16.4 ft 6.6 ft2m(6.6ft) 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

0m16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

Discharge angle: 40°

Air velocity ft/s

Temperature (°F)

Discharge angle: 50°

Air velocity ft/s

Temperature (°F)

1.5(4.9)1.5(4.9)4.91.5(4.9)1.5(4.9)4.9

3.31.0(3.3 )3.3

0.5(1.61.60.5(1.6)0.5(1.6)1.6

18(64 )64.464.4

20(68)20(68)6820 6822(71.6)22(71.6)71.622(71.6)22(71.6)71.6

1.5(4.9)1.5(4.9)4.91.5(4.9)1.5(4.9)4.9

2.0(6.6)2.0(6.6)6.62.0(6.6)2.0(6.6)6.6

1.0(33.31.0(3.3 )1.0(3.3 )3.3

)1.61.6 )1

28(82.4 )82.428(82.4)28(82.4)82.4

30(86)30(86)8630(86)30(86)86 89.6 )32(89.6)32(89.6)89.6

34(93.2)34(93.2)93.293.236(96.8)36(96.8)96.836(996.8

38(100.4)38(100.4)100.438(100.4)38(100.4)100.4

Cooling Heating

1.5(4.9

1.0(3.3 )1.0(3.3)0.5(1.6))

16(60.8)16(60.8)

20(68)20(68)22(71.6)22(71.6)

24(75.2)24(75.2)

)

1.0(3.3 )

26(78.8))30(86)

32(89.6))

36(96.8)

38(100.4)

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

ARNU073TNA4, ARNU093TNA4

Page 94: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

94 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Figure 64: ARNU073TNA4 and ARNU093TNA4, continued.

1.5(4.9)1.5(4.9)

1.0(3.3 )

0.5(1.60.5(1.6)

18(64 )

20(68)2022(71.6)22(71.6)

1.5(4.9)1.5(4.9)

2.0(6.6)2.0(6.6)

1.0(31.0(3.3 )

))

28(82.4 )28(82.4)

30(86)30(86) )32(89.6)

34(93.2)36(96.8)36(9

38(100.4)38(100.4)

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft9.8 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

1.5(4.94.94.9

1.0(3.3 )3.31.0(3.3)1.0(3.3)3.30.5(1.60.5(1.6)1.6)1.6

64.464.4

16(60.8)16(60.8)60.816(60.8)16(60.8)60.8

20(68)20(68)6820(68)20(68)6822(71.6)22(71.6)71.622(71.6)22(71.6)71.6

24(75.2)24(75.2)75.224(75.2)24(75.2)75.2

4.9

)6.68.28.2

3.31.0(3.3 )1.0(3.3 )3.31.61.6

82.482.4 26(78.8)26(78.8)78.8)78.830(86)30(86)8686

89.632(89.6)32(89.6)89.693.2)93.2

96.836(96.8)36(96.8)96.8

100.438(100.4)38(100.4)100.4

Cooling Heating

6.6

4.9

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

Figure 65: ARNU123TNA4 and ARNU153TNA4.

0.5(1.6)

)20(68) 22(71.6 )

)

)

))

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

Discharge angle: 20° Discharge angle: 20°

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

4.93.31.6

18(64.4)18(64.4)64.418(64.4)18(64.4)64.4 20(68)20(68)6820(68)20(68)68

22(771.622(71.6)22(71.6)71.6

4.96.6 8.2

3.3

28(82.4 )

28(82.4)28(82.4)82.48632(89.6)32(89.6))89.6 93.2 96.8 100.4

Cooling Heating

1.6

3.34.9

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0 16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

4.98.28.2 6.6

3.3

1.61.6

89.686

82.4

93.293.2 96.8100.4

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

ARNU073TNA4, ARNU093TNA4, ARNU123TNA4, ARNU153TNA4

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

Page 95: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 95

Four-Way C

eiling Cassette Product D

ata

©

Figure 66: ARNU123TNA4 and ARNU153TNA4, continued.

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

Discharge angle: 40° Discharge angle: 50°

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

4.9

3.3

0.5(1.6)0.5(1.6)1.6

64.4

)20(68)20(68)68 22(71.6 )71.6

4.9

)6.68.2

)3.3

1.6

)82.4

86

89.693.2

96.8)100.4

Cooling Heating

18(64.4)18(64.4) 20(68)20(68)

22(722(71.6)28(82.4 )

28(82.4)

32(89.6))

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

4.9

3.33.3

1.6

64.4

6871.6

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.26.6

4.9

3.3

1.6

82.4100.4

96.893.2

89.6

86

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

ARNU123TNA4, ARNU153TNA4

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

Discharge angle: 70° Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

64.4

68

71.6

24(75.2)24(75.2) 26(78.8)26(78.8)78.826(78.8)26(78.8)78.882.4

8689.6

)93.2)96.8

75.2

1.6

)6.6

3.3

1.6 1.0(3.3)1.0(3.3)3.33.3

4.9

4.9

Cooling Heating

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0 16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

4.9

3.3

1.6

64.4

6875.2

71.6

6.6

4.9

1.6

96.893.2

89.686

82.4

Page 96: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

96 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

Discharge angle: 70° Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

64.4

68

71.6

24(75.2)24(75.2) 26(78.8)26(78.8)78.826(78.8)26(78.8)78.882.4

8689.6

)93.2)96.8

75.2

1.6

)6.6

3.3

1.6 1.0(3.3)1.0(3.3)3.33.3

4.9

4.9

Cooling Heating

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0 16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

4.9

3.3

1.6

64.4

6875.2

71.6

6.6

4.9

1.6

96.893.2

89.686

82.4

Figure 67: ARNU183TNA4.

Discharge angle: 40°

00

0

6.66.6

4.9 4.9

3.33.3

Discharge angle: 50°

0

0

91.491.486 86

80.680.675.275.2

71.671.6

75.275.2

6.6 6.6

3.33.3

1.61.6

6864.464.4

6871.671.6

75.575.5

8.9 ft

6.6 ft

3.3 ft

13.1 ft9.8 ft9.8 ft13.1 ft 6.6 ft6.6 ft 3.3 ft3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Cooling Heating

0 13.1 ft9.8 ft9.8 ft13.1 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0 13.1 ft9.8 ft9.8 ft13.1 ft 6.6 ft6.6 ft 3.3 ft3.3 ft

0 13.1 ft9.8 ft9.8 ft13.1 ft 6.6 ft6.6 ft 3.3 ft3.3 ft

Temperature (°F)

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

ARNU183TNA4

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

Page 97: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 97

Four-Way C

eiling Cassette Product D

ata

©

Figure 68: ARNU183TNA4, continued.

Figure 69: ARNU243TNA4.

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Discharge angle: 70°

0

0

Discharge angle: 70°

0

0

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

8.9 ft

6.6 ft

3.3 ft

Air velocity ft/s Air velocity ft/s

1.6

3.3

4.9

6.68.2

1.6

3.3

4.9

6.68.2

73.471.6

69.8

6866.2

64.4

73.471.6

69.8

6866.2

64.4

3.3

4.9

6.6

8.2

3.3

4.9

6.6

8.2

75.2 78.8

82.4 86

89.6

75.278.8

82.486

89.6

Cooling Heating

0 13.1 ft9.8 ft9.8 ft13.1 ft 6.6 ft6.6 ft 3.3 ft3.3 ft

0 13.1 ft9.8 ft9.8 ft13.1 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0 13.1 ft9.8 ft9.8 ft13.1 ft 6.6 ft6.6 ft 3.3 ft3.3 ft

0 13.1 ft9.8 ft9.8 ft13.1 ft 6.6 ft6.6 ft 3.3 ft3.3 ft

Temperature (°F) Temperature (°F)

Discharge angle: 20° Discharge angle: 20°

Air velocity ft/s

Temperature °F

Air velocity ft/s

Temperature °F

0 13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 16.4 ft6.6 ft6.6 ft 3.3 ft3.3 ft0

6.6 ft

3.3 ft

8.9 ft6.6 8.2 9.8

4.93.3

6.68.29.84.9

3.3

0

6.6 ft

3.3 ft

8.9 ft68 66.2

62.662.6

6866.262.6

62.6

0

6.6 ft

3.3 ft

8.9 ft11.5

6.6 8.2 9.8

4.9 11.56.68.29.8

4.9

0

6.6 ft

3.3 ft

8.9 ft91.4

98.6

88

95102 91.4

98.6

88

95102

Cooling Heating

0 13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 16.4 ft6.6 ft6.6 ft 3.3 ft3.3 ft 0 13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 16.4 ft6.6 ft6.6 ft 3.3 ft3.3 ft

0 13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 16.4 ft6.6 ft6.6 ft 3.3 ft3.3 ft

ARNU183TNA4, ARNU243TNA4

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

Page 98: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

98 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Figure 70: ARNU243TNA4, continued.

Discharge angle: 40° Discharge angle: 50°

Air velocity ft/s

Temperature °F

Air velocity ft/s

Temperature °F

0

6.6 ft

3.3 ft

8.9 ft

8.2

9.8

6.6

4.93.3

8.2

9.8

6.6

4.9 3.3

0

6.6 ft

3.3 ft

8.9 ft

70

66.2

71.6

62.6

70

66.2

71.6

62.6

0

6.6 ft

3.3 ft

8.9 ft

8.2

9.8

6.64.93.3

8.2

9.8

6.64.9 3.3

0

6.6 ft

3.3 ft

8.9 ft

89.6 9397

100.4

89.69397

100.4

Cooling Heating

0 13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 16.4 ft6.6 ft6.6 ft 3.3 ft3.3 ft

0 13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 16.4 ft6.6 ft6.6 ft 3.3 ft3.3 ft 0 13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 16.4 ft6.6 ft6.6 ft 3.3 ft3.3 ft

0 13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 16.4 ft6.6 ft6.6 ft 3.3 ft3.3 ft

Discharge angle: 70° Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

0 13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 16.4 ft6.6 ft6.6 ft 3.3 ft3.3 ft0

6.6 ft

3.3 ft

8.9 ft

8.2

6.6

4.9

3.31.6

8.2

6.6

4.9

3.3 1.6

0

6.6 ft

3.3 ft

8.9 ft

71.670

66.2

62.6

71.670

66.2

62.6

0

6.6 ft

3.3 ft

8.9 ft

8.2

9.8

6.6

4.93.3

8.2

9.8

6.6

4.9 3.3

0

6.6 ft

3.3 ft

8.9 ft

89.686 93

100.4

104

89.6 8693

100.4

104

Cooling Heating

0 13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 16.4 ft6.6 ft6.6 ft 3.3 ft3.3 ft 0 13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 16.4 ft6.6 ft6.6 ft 3.3 ft3.3 ft

0 13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 16.4 ft6.6 ft6.6 ft 3.3 ft3.3 ft

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

ARNU243TNA4

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

Page 99: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 99

Four-Way C

eiling Cassette Product D

ata

©

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Figure 71: ARNU283TMA4.

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

Discharge angle: 20° Discharge angle: 20°

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

)4.91.5(4.9)1.5(4.9)4.91.5(4.9)1.5(4.9)4.9

4.96.6 2.0(6.6)2.0(6.6)6.66.66.6

6.6 8.2 2.5(8.2)2.5(8.2)8.28.28.2 9.89.8

9.811.5 13.19.8

29(84.2)29(84.2)84.229(8484.2

87.8

91.491.4 95 98.6

102.2105.862.662.6 19(66.2)19(66.2)66.219(66.2)19(66.2)66.2

69.869.8

23(73.4)23(73.4)73.423(73.4)23(73.4)73.4

Cooling Heating

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0 16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

105.8102.2

98.6 95

87.8

11.513.1

ARNU283TMA4

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

Page 100: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

100 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

ARNU283TMA4

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

Figure 72: ARNU283TMA4, continued.

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

Discharge angle: 70° Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

1.0(3.3)1.0(3.3)3.3

5917(62.6)17(62.6)62.6

66.2

69.8

1.0(3.3)1.0(3.3)3.3

4.9

2.0(6.6)2.0(6.6)6.6 )

3.3

30(86)30(86)8630(86)30(86)86

32(89.6 ))89.6

93.2

)96.8)100.4

)104)107.6

4.9

6.6

8.29.8

)3.5( .511.52.5(8.2)2.5(8.2)8.2

9.8

Cooling Heating

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

Discharge angle: 40° Discharge angle: 50°

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

4.9

3.3

62.6

)66.2

)69.8

6.6

8.2

9.8

3.3

89.632(89.6)32(89.6)89.6 93.296.8

)100.4

104107.6

4.96.6

8.2)9.8

)11.5)13.1

Cooling Heating

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0 16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

9.8

8.2

6.64.9

3.3

62.6

66.2

69.8

9.8

8.2

6.6

4.9

69.8

66.2

62.659 107.6

104100.4

96.8

93.2

89.6

11.59.8

8.2

6.6

4.93.3

107.6104

100.496.8

93.2

13.111.5

9.88.2

6.64.9

3.3

Page 101: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 101

Four-Way C

eiling Cassette Product D

ata

©

ARNU363TMA4

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

Discharge angle: 20° Discharge angle: 20°

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

2.0(6.6)2.0(6.6)6.62.0(6.6)2.0(6.6)6.6

55.8 )66.2

21(69.8)21(69.8)

)

31(87.8)31(87.8)87.8

91.491.4 9595 98.6102.2 105.8105.8

4.9)6.6

2.5(8.2)2.5(8.2)8.2 )9.8 11.513.1 14.814.8

21(69.8)21(69.8)69.8

23(73.4)23(73.4)73.4

23(73.4)23(73.4)73.4

2.5(8.2)2.5(8.2)8.22.5(8.2)2.5(8.2)8.29.8 11 .5

Cooling Heating

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

Discharge angle: 40° Discharge angle: 50°

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

3.3 4.9

89.6 93.234(93.2)34(93.2)93.2

)96.8)100.4

104107.6

6.68.2

9.83.5(11.5

)13.1)14.8

3.3

55.8

66.2

21(69.8)21(69.8)69.821(69.8)21(69.8)69.8

1.5(4.9)1.5(4.9)4.96.6

8.29.8

)11.53.5(3.5(13.1 14.8

Cooling Heating

11 .5 9.8

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0 16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

107.6104

100.4

96.889.6

55.8

66.2

14.8 13.111.5

9.88.2

6.64.9

3.3

55.8 66.2

69.8

14.813.1

11.59.8

8.26.6

4.93.3

87.8

98.6 102.2

4.96.6

8.29.811.513.1

Figure 73: ARNU363TMA4.

Page 102: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

102 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Discharge angle: 20° Discharge angle: 20°

Temperature (°F)

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

0

6.6 ft

3.3 ft

10.5 ft

0

6.6 ft

3.3 ft

10.5 ft

0

6.6 ft

3.3 ft

10.5 ft

0

6.6 ft

3.3 ft

10.5 ft 93.2

4.9

11.5

8.2

6.6

3.3

9.8

4.9

11.5

8.2

6.6

3.3

9.8

73.471.6

69.8 68 64.466.2

73.471.6

69.86864.4 66.2

6.68.2 9.8

13.111.56.6

8.29.8

13.1 11.5

89.6

75.2 8682.4

78.8

93.2 89.6

75.28682.4

78.8

gnitaeHgnilooC

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft

Figure 74: ARNU423TMC4.

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

ARNU363TMA4, ARNU423TMC4

Figure 75: ARNU363TMA4, continued.

8.9 ft

6.6 ft

3.3 ft

016.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

8.9 ft

6.6 ft

3.3 ft

0

Discharge angle: 70° Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

1.0(3.3)1.0(3.3)3.3 3.33.3

32(89.6)32(89.6)89.632(89.6)32(89.6)89.6 93.296.8

)100.4

104)107.6

.2 ).2 )111.2.2.2

4.96.6

8.2 )9.8 1111

11.5)13.1

1.0(3.3)1.0(3.3)3.3

5955.8

)66.2

69.821(69.8)21(69.8)69.8

4.9

4.9 2.0(6.6)2.0(6.6)6.6

2.0(6.6)2.0(6.6)6.62.5(8.2)2.5(8.2)8.2

3.0(9.8)3.0(9.8)9.8

Cooling Heating

9.8

8.2

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

59

55.8

66.2

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

16.4 ft13.1 ft9.8 ft9.8 ft13.1 ft16.4 ft 6.6 ft6.6 ft 3.3 ft3.3 ft 0

13.1

11.5

9.88.2

6.64.9

111.2107.6

104100.4

96.893.2

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

Page 103: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 103

Four-Way C

eiling Cassette Product D

ata

©

Discharge angle: 40

13.113.1

9.89.8

6.66.63.33.3

Discharge angle: 50°°

10.5 ft

0

10.5 ft

0

10.5 ft

0

0

75.2

91.4 91.4

75.2

80.6 80.6

86 86

71.671.6

13.113.1

9.8 9.8

6.66.6

3.33.3

64.464.4

6868

71.671.675.275.2

6.6 ft

3.3 ft

6.6 ft

3.3 ft

6.6 ft

10.5 ft

3.3 ft

6.6 ft

3.3 ft

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

gnitaeHgnilooC

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft

Figure 76: ARNU423TMC4, continued.

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

ARNU423TMC4

Discharge angle: 70° Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

0

6.6 ft

3.3 ft

10.5 ft

0

6.6 ft

3.3 ft

10.5 ft

0

6.6 ft

3.3 ft

10.5 ft

0

6.6 ft

3.3 ft

10.5 ft

8.2

11.5

6.6

4.9

3.3

8.2

11.5

6.6

4.9

3.3

3.3

75.2

69.8

68

66.264.4

75.2

69.8

68

66.264.4

6.6

13.1

8.2

3.36.6

13.1

8.2

3.3

78.8 78.8

89.6

86

82.4

93.2

78.8

89.6

86

82.4

93.2

78.8

gnitaeHgnilooC

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft3.3 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft3.3 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft3.3 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft3.3 ft

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Page 104: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

104 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Figure 77: ARNU483TMC4.

Discharge angle: 20° Discharge angle: 20°

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

0

6.6 ft

3.3 ft

10.5 ft

0

6.6 ft

3.3 ft

10.5 ft

0

6.6 ft

3.3 ft

10.5 ft

0

6.6 ft

3.3 ft

10.5 ft

6.6

8.29.8

13.111.5

6.6

8.29.8

13.1 11.5

75.273.471.6

69.868 64.4

75.273.4 71.6

69.86864.4

8.21.6 13.1

11.59.8

1.6

8.21.613.1

11.59.8

1.6

78.889.6

93.282.4

8678.8

89.6

93.2 82.4

86

gnitaeHgnilooC

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft3.3 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft3.3 ft 13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft3.3 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 6.6 ft 8.9 ft 13.1 ft3.3 ft

ARNU483TMC4

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

Discharge angle: 40°

13.113.1

9.89.8

6.66.63.33.3

Discharge angle: 50°

0

00

0

75.2

91.4 91.4

75.2

80.6 80.686 86

71.671.6

13.113.1

9.8 9.8

6.66.63.33.3

64.464.4

6868

71.671.675.275.2

6.6 ft

3.3 ft

6.6 ft

3.3 ft

6.6 ft

3.3 ft

6.6 ft

3.3 ft

10.5 ft 10.5 ft

10.5 ft10.5 ft

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

gnitaeHgnilooC

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft 13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Page 105: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 105

Four-Way C

eiling Cassette Product D

ata

©

Figure 78: ARNU483TMC4, continued.

FOUR-WAY CEILING CASSETTEAir Velocity / Temperature Distribution

ARNU483TMC4

Discharge angle: 70° Discharge angle: 70°

Air velocity ft/s

Temperature (°F)

Air velocity ft/s

Temperature (°F)

0

6.6 ft

3.3 ft

10.5 ft

0

6.6 ft

3.3 ft

10.5 ft

0

6.6 ft

3.3 ft

10.5 ft

0

6.6 ft

3.3 ft

10.5 ft

4.9

4.9

6.6

8.29.8

13.1 4.9

4.9

6.6

8.29.8

13.1

71.6

69.8

68

71.6

69.8

68

4.96.6

8.29.8

11.513.1

4.96.6

8.29.8

11.513.1

4.9

78.8

82.4 86

89.6

93.2

78.8

82.486

89.6

93.2

gnitaeHgnilooC

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft 13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft

13.1 ft 9.8 ft 6.6 ft 3.3 ft 0 ft 3.3 ft 6.6 ft 8.9 ft 13.1 ft16.4 ft 16.4 ft

The standard setup height is 8.9 ft. The charts above show the measurement distribution at the ceiling height of 8.9 ft with a high fan operating mode.

Page 106: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

106 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

TR, TQ Frame

Figure 79: TR Frame Fresh Air Ventilation.Fresh Air Ventilation (with PTVK430)

-1.0

-0.9

-0.8

-0.7

-0.6

-0.5

-0.4

-0.3

-0.2

-0.1

0.0

0 20 40 60 80 100 120 140 160

Q (CFM)

P (in

Aq)

TR

Fresh Air Ventilation (with PTVK430)

-1.0

-0.9

-0.8

-0.7

-0.6

-0.5

-0.4

-0.3

-0.2

-0.1

0.0

0 20 40 60 80 100 120 140 160

Q (CFM)

P (in

Aq)

TQ

Figure 80: TQ Frame Fresh Air Ventilation.

Fresh Air VentilationFOUR-WAY CEILING CASSETTE

Page 107: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 107

Four-Way C

eiling Cassette Product D

ata

©

Fresh Air Ventilation (with PTVK430)

-1.0

-0.9

-0.8

-0.7

-0.6

-0.5

-0.4

-0.3

-0.2

-0.1

0.0

0 20 40 60 80 100 120 140 160

Q (CFM)

P (in

Aq)

TN/TM

Fresh Air Ventilation (with PTVK410 + PTVK420)

-1.0

-0.9

-0.8

-0.7

-0.6

-0.5

-0.4

-0.3

-0.2

-0.1

0.0

0 20 40 60 80 100 120 140 160

Q (CFM)

P (in

Aq)

TN/TM

Figure 81: TN and TM Frame Fresh Air Ventilation with PTVK430 Accessory.

Figure 82: TN and TM Frame Fresh Air Ventilation with PTVK410 + PTVK420 Accessories.

TN, TM FrameFresh Air Ventilation

FOUR-WAY CEILING CASSETTE

Page 108: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

108 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

FOUR-WAY CEILING CASSETTECooling Capacity Tables

Model No. / Capacity Index

Outdoor Air

Temp. (°F DB)

Indoor Air Temperature (°F DB / WB)68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh

ARNU053TRD4 / 5.5

-9.9 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 -5 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 0 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 5 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 10 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 14 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 20 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 23 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 25 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 30 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 35 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 40 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 45 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 50 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 55 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.1 4.1 60 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 7.0 4.1 65 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 6.9 4.1 70 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 6.8 4.0 75 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.6 4.1 6.6 3.9 80 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.2 4.2 6.4 4.1 6.5 3.9 85 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.1 4.1 6.2 3.9 6.3 3.7 90 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 6.0 4.1 6.1 3.9 6.2 3.7 95 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 5.9 4.1 6.0 3.9 6.1 3.6 100 3.6 3.0 4.4 3.4 5.0 3.7 5.5 3.9 5.8 4.0 5.9 3.8 6.0 3.6 105 3.6 3.0 4.2 3.3 4.7 3.5 5.3 3.7 5.5 3.7 5.7 3.7 5.8 3.5 110 3.5 2.9 4.0 3.1 4.4 3.3 5.0 3.5 5.2 3.5 5.4 3.5 5.6 3.4 115 3.4 2.8 3.8 2.9 4.1 3.1 4.7 3.3 4.9 3.3 5.1 3.3 5.4 3.3 118 3.4 2.7 3.6 2.8 3.9 2.9 4.5 3.2 4.6 3.2 4.9 3.2 5.2 3.1 122 3.3 2.6 3.4 2.6 3.7 2.7 4.2 3.0 4.4 3.0 4.6 3.0 5.0 3.0

ARNU073TRD4 / 7.5

-9.9 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 -5 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 0 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 5 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 10 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 14 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 20 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 23 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 25 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 30 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 35 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 40 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 45 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 50 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 55 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.7 5.7 60 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.6 5.7 65 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.4 5.6 70 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.3 5.5 75 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.7 9.1 5.4 80 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.7 5.7 8.8 5.4 85 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.3 5.7 8.4 5.5 8.6 5.2 90 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.2 5.6 8.3 5.4 8.4 5.1 95 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.0 5.6 8.2 5.3 8.3 5.0 100 4.9 4.1 6.0 4.8 6.8 5.1 7.5 5.4 7.9 5.5 8.0 5.3 8.2 5.0 105 4.9 4.1 5.7 4.5 6.4 4.9 7.2 5.2 7.5 5.2 7.7 5.1 7.9 4.9 110 4.8 4.0 5.4 4.3 6.0 4.5 6.8 4.9 7.1 4.9 7.3 4.9 7.7 4.7 115 4.7 3.9 5.1 4.1 5.6 4.2 6.3 4.6 6.6 4.6 7.0 4.6 7.4 4.5 118 4.6 3.8 4.9 3.9 5.4 4.0 6.1 4.4 6.3 4.4 6.7 4.4 7.1 4.4 122 4.5 3.7 4.6 3.7 5.1 3.8 5.8 4.2 6.0 4.2 6.3 4.2 6.8 4.2

Table 40: ARNU053TRD4, ARNU073TRD4 Cooling Capacity Table.

ARNU053TRD4, ARNU073TRD4

TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 109: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 109

Four-Way C

eiling Cassette Product D

ata

©

FOUR-WAY CEILING CASSETTECooling Capacity Tables

Model No. / Capacity Index

Outdoor Air

Temp. (°F DB)

Indoor Air Temperature (°F DB / WB)68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh

ARNU093TRD4 /9.6

-9.9 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 -5 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 0 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 5 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 10 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 14 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 20 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 23 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 25 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 30 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 35 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 40 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 45 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 50 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 55 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.4 7.3 60 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.3 7.3 65 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 12.1 7.2 70 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 11.9 7.1 75 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.3 11.6 6.9 80 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.1 7.3 11.3 6.9 85 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.6 7.3 10.8 7.0 11.0 6.6 90 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.5 7.2 10.6 6.9 10.8 6.5 95 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.3 7.2 10.5 6.8 10.6 6.4 100 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.1 7.1 10.3 6.7 10.5 6.4 105 6.3 5.3 7.3 5.8 8.2 6.2 9.2 6.6 9.6 6.6 9.9 6.5 10.2 6.2 110 6.2 5.1 6.9 5.5 7.7 5.8 8.6 6.2 9.0 6.2 9.4 6.2 9.8 6.0 115 6.0 5.0 6.6 5.2 7.2 5.4 8.1 5.9 8.5 5.9 8.9 5.9 9.4 5.8 118 5.9 4.8 6.2 4.9 6.9 5.1 7.8 5.6 8.1 5.6 8.5 5.6 9.0 5.6 122 5.7 4.7 5.9 4.7 6.5 4.8 7.4 5.3 7.7 5.3 8.1 5.3 8.7 5.3

Table 41: ARNU093TRD4 Cooling Capacity Table.

ARNU093TRD4

TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 110: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

110 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Table 42: ARNU123TRD4, ARNU153TQD4 Cooling Capacity Table.

Model No. /Capacity Index

Outdoor Air

Temp. (°F DB)

Indoor Air Temperature (°F DB / WB)68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh

ARNU123TRD4 / 12.3

-9.9 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 -5 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 0 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 5 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5

10 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 14 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 20 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 23 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 25 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 30 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 35 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 40 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 45 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 50 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 55 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.9 9.5 60 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.7 9.4 65 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.5 9.3 70 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 15.3 9.1 75 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.7 9.5 14.9 8.9 80 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.8 9.6 14.2 9.4 14.5 8.9 85 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.6 9.5 13.8 9.0 14.0 8.5 90 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.4 9.3 13.5 8.9 13.8 8.4 95 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 13.2 9.3 13.4 8.8 13.6 8.3

100 8.1 6.8 9.8 7.9 11.1 8.4 12.3 8.9 12.9 9.1 13.2 8.7 13.4 8.3 105 8.1 6.8 9.3 7.5 10.6 8.0 11.8 8.5 12.3 8.5 12.7 8.4 13.0 8.1 110 7.9 6.6 8.9 7.1 9.8 7.5 11.1 8.0 11.6 8.0 12.0 8.0 12.6 7.8 115 7.7 6.4 8.4 6.7 9.2 7.0 10.4 7.6 10.9 7.6 11.4 7.6 12.1 7.5 118 7.5 6.2 8.0 6.4 8.8 6.6 10.0 7.2 10.4 7.2 10.9 7.2 11.6 7.2 122 7.3 6.0 7.6 6.0 8.3 6.2 9.4 6.9 9.8 6.9 10.3 6.9 11.1 6.9

ARNU153TQD4 / 15.4

-9.9 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8 -5 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8 0 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8 5 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8

10 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8 14 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8 20 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8 23 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8 25 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8 30 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8 35 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8 40 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8 45 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8 50 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8 55 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.9 11.8 60 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.7 11.7 65 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.4 11.5 70 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 19.1 11.4 75 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 18.4 11.8 18.6 11.1 80 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.3 11.9 17.8 11.7 18.2 11.0 85 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.1 11.8 17.3 11.2 17.6 10.6 90 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 16.8 11.6 16.9 11.0 17.3 10.5 95 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 16.5 11.5 16.8 11.0 17.1 10.4

100 10.1 8.5 12.3 9.8 13.9 10.4 15.4 11.1 16.2 11.4 16.5 10.9 16.8 10.3 105 10.1 8.5 11.7 9.3 13.2 10.0 14.8 10.6 15.4 10.6 15.8 10.5 16.3 10.0 110 9.9 8.2 11.1 8.8 12.3 9.3 13.9 10.0 14.5 10.0 15.1 10.0 15.7 9.7 115 9.6 8.0 10.5 8.3 11.6 8.7 13.0 9.5 13.6 9.5 14.3 9.5 15.1 9.3 118 9.4 7.8 10.0 7.9 11.0 8.2 12.5 9.0 13.0 9.0 13.7 9.0 14.5 9.0 122 9.1 7.5 9.5 7.5 10.4 7.7 11.8 8.5 12.3 8.5 12.9 8.5 13.9 8.5

FOUR-WAY CEILING CASSETTECooling Capacity TablesARNU123TRD4, ARNU153TQD4

TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 111: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 111

Four-Way C

eiling Cassette Product D

ata

©

Table 43: ARNU183TQD4 Cooling Capacity Table.

Model No. /Capacity Index

Outdoor Air

Temp. (°F DB)

Indoor Air Temperature (°F DB / WB)68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh

ARNU183TQD4 / 19.1

-9.9 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7 -5 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7 0 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7 5 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7

10 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7 14 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7 20 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7 23 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7 25 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7 30 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7 35 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7 40 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7 45 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7 50 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7 55 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.7 14.7 60 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.4 14.6 65 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 24.0 14.4 70 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 23.7 14.1 75 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.8 14.7 23.1 13.8 80 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.4 14.8 22.1 14.6 22.5 13.7 85 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 21.2 14.7 21.4 14.0 21.8 13.2 90 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 20.9 14.4 21.0 13.7 21.4 13.0 95 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 20.5 14.4 20.9 13.7 21.2 12.9

100 12.6 10.6 15.3 12.2 17.2 13.0 19.1 13.8 20.1 14.1 20.5 13.5 20.9 12.8 105 12.6 10.6 14.5 11.6 16.4 12.4 18.3 13.2 19.0 13.2 19.7 13.0 20.2 12.5 110 12.3 10.2 13.8 10.9 15.3 11.6 17.2 12.4 18.0 12.4 18.7 12.4 19.5 12.1 115 12.0 9.9 13.1 10.4 14.4 10.9 16.2 11.8 16.9 11.8 17.8 11.8 18.7 11.6 118 11.7 9.6 12.4 9.9 13.6 10.2 15.5 11.2 16.1 11.2 17.0 11.2 18.0 11.1 122 11.3 9.3 11.8 9.4 12.9 9.6 14.7 10.6 15.3 10.6 16.0 10.6 17.2 10.6

FOUR-WAY CEILING CASSETTECooling Capacity Tables

ARNU183TQD4

TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 112: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

112 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Table 44: ARNU073TNA4, ARNU093TNA4 Cooling Capacity Table.

FOUR-WAY CEILING CASSETTECooling Capacity TablesARNU073TNA4, ARNU093TNA4

Model No. /Capacity Index

Outdoor Air Temp. (°F DB)

Indoor Air Temperature (°F DB / WB)68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh

ARNU073TNA4 /7.5

-9.9 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9 -5 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9 0 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9 5 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9

10 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9 14 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9 20 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9 23 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9 25 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9 30 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9 35 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9 40 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9 45 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9 50 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9 55 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.7 5.9 60 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.6 5.9 65 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.4 5.8 70 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.3 5.7 75 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.9 5.9 9.1 5.6 80 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.4 6.0 8.7 5.9 8.8 5.6 85 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.3 5.9 8.4 5.7 8.6 5.4 90 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.2 5.9 8.3 5.6 8.4 5.3 95 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 8.0 5.8 8.2 5.5 8.3 5.2

100 4.9 4.3 6.0 4.9 6.8 5.3 7.5 5.6 7.9 5.7 8.0 5.5 8.2 5.2 105 4.9 4.3 5.7 4.7 6.4 5.0 7.2 5.4 7.5 5.4 7.7 5.3 7.9 5.1 110 4.8 4.2 5.4 4.4 6.0 4.7 6.8 5.0 7.1 5.0 7.3 5.0 7.7 4.9 115 4.7 4.0 5.1 4.2 5.6 4.4 6.3 4.8 6.6 4.8 7.0 4.8 7.4 4.7 118 4.6 3.9 4.9 4.0 5.4 4.1 6.1 4.5 6.3 4.5 6.7 4.5 7.1 4.5 122 4.5 3.8 4.6 3.8 5.1 3.9 5.8 4.3 6.0 4.3 6.3 4.3 6.8 4.3

ARNU093TNA4 /9.6

-9.9 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5 -5 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5 0 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5 5 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5

10 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5 14 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5 20 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5 23 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5 25 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5 30 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5 35 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5 40 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5 45 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5 50 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5 55 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.4 7.5 60 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.3 7.5 65 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 12.1 7.4 70 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 11.9 7.3 75 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.4 7.5 11.6 7.1 80 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.8 7.6 11.1 7.5 11.3 7.1 85 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.6 7.5 10.8 7.2 11.0 6.8 90 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.5 7.4 10.6 7.1 10.8 6.7 95 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.3 7.4 10.5 7.0 10.6 6.6 100 6.3 5.4 7.7 6.3 8.6 6.7 9.6 7.1 10.1 7.3 10.3 6.9 10.5 6.6 105 6.3 5.4 7.3 5.9 8.2 6.4 9.2 6.8 9.6 6.8 9.9 6.7 10.2 6.4 110 6.2 5.3 6.9 5.6 7.7 5.9 8.6 6.4 9.0 6.4 9.4 6.4 9.8 6.2 115 6.0 5.1 6.6 5.3 7.2 5.6 8.1 6.1 8.5 6.1 8.9 6.1 9.4 6.0 118 5.9 5.0 6.2 5.1 6.9 5.3 7.8 5.8 8.1 5.8 8.5 5.8 9.0 5.7 122 5.7 4.8 5.9 4.8 6.5 4.9 7.4 5.5 7.7 5.5 8.1 5.5 8.7 5.5

TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 113: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 113

Four-Way C

eiling Cassette Product D

ata

©

Table 45: ARNU123TNA4 Cooling Capacity Table.

FOUR-WAY CEILING CASSETTECooling Capacity Tables

ARNU123TNA4

Model No. /Capacity Index

Outdoor Air Temp. (°F DB)

Indoor Air Temperature (°F DB / WB)68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh

ARNU123TNA4 / 12.3

-9.9 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 -5 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 0 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 5 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 10 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 14 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 20 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 23 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 25 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 30 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 35 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 40 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 45 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 50 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 55 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.9 9.7 60 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.7 9.6 65 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.5 9.5 70 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 15.3 9.3 75 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.7 9.7 14.9 9.1 80 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.8 9.8 14.2 9.6 14.5 9.1 85 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.6 9.7 13.8 9.2 14.0 8.7 90 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.4 9.5 13.5 9.1 13.8 8.6 95 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 13.2 9.5 13.4 9.0 13.6 8.5 100 8.1 7.0 9.8 8.0 11.1 8.5 12.3 9.1 12.9 9.3 13.2 8.9 13.4 8.4 105 8.1 7.0 9.3 7.6 10.6 8.2 11.8 8.7 12.3 8.7 12.7 8.6 13.0 8.2 110 7.9 6.7 8.9 7.2 9.8 7.6 11.1 8.2 11.6 8.2 12.0 8.2 12.6 8.0 115 7.7 6.6 8.4 6.8 9.2 7.2 10.4 7.8 10.9 7.8 11.4 7.8 12.1 7.7 118 7.5 6.4 8.0 6.5 8.8 6.7 10.0 7.4 10.4 7.4 10.9 7.4 11.6 7.3 122 7.3 6.2 7.6 6.2 8.3 6.3 9.4 7.0 9.8 7.0 10.3 7.0 11.1 7.0

TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 114: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

114 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Table 46: ARNU153TNA4, ARNU183TNA4, ARNU243TNA4 Cooling Capacity Table.

Model No. /Capacity Index

Outdoor Air Temp. (°F DB)

Indoor Air Temperature (°F DB / WB)68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh

ARNU153TNA4 /15.4

-9.9 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1 -5 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1 0 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1 5 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1

10 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1 14 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1 20 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1 23 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1 25 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1 30 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1 35 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1 40 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1 45 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1 50 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1 55 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.9 12.1 60 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.7 12.0 65 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.4 11.8 70 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 19.1 11.7 75 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 18.4 12.1 18.6 11.4 80 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.3 12.2 17.8 12.0 18.2 11.3 85 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 17.1 12.1 17.3 11.5 17.6 10.9 90 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 16.8 11.9 16.9 11.3 17.3 10.8 95 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 16.5 11.8 16.8 11.3 17.1 10.6

100 10.1 8.7 12.3 10.1 13.9 10.7 15.4 11.4 16.2 11.7 16.5 11.1 16.8 10.6 105 10.1 8.7 11.7 9.5 13.2 10.2 14.8 10.9 15.4 10.9 15.8 10.8 16.3 10.3 110 9.9 8.5 11.1 9.0 12.3 9.5 13.9 10.2 14.5 10.2 15.1 10.2 15.7 10.0 115 9.6 8.2 10.5 8.6 11.6 9.0 13.0 9.7 13.6 9.7 14.3 9.7 15.1 9.6 118 9.4 8.0 10.0 8.1 11.0 8.4 12.5 9.2 13.0 9.2 13.7 9.2 14.5 9.2 122 9.1 7.7 9.5 7.7 10.4 7.9 11.8 8.8 12.3 8.8 12.9 8.8 13.9 8.8

ARNU183TNA4 /19.1

-9.9 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2 -5 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2 0 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2 5 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2

10 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2 14 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2 20 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2 23 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2 25 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2 30 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2 35 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2 40 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2 45 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2 50 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2 55 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.7 16.2 60 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.4 16.2 65 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 24.0 15.9 70 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 23.7 15.6 75 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.8 16.2 23.1 15.3 80 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.4 16.4 22.1 16.2 22.5 15.2 85 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 21.2 16.2 21.4 15.5 21.8 14.6 90 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 20.9 16.0 21.0 15.2 21.4 14.4 95 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 20.5 15.9 20.9 15.1 21.2 14.3

100 12.6 11.7 15.3 13.5 17.2 14.4 19.1 15.3 20.1 15.6 20.5 15.0 20.9 14.2 105 12.6 11.7 14.5 12.8 16.4 13.8 18.3 14.6 19.0 14.6 19.7 14.4 20.2 13.8 110 12.3 11.3 13.8 12.1 15.3 12.8 17.2 13.8 18.0 13.8 18.7 13.8 19.5 13.4 115 12.0 11.0 13.1 11.5 14.4 12.0 16.2 13.1 16.9 13.1 17.8 13.1 18.7 12.9 118 11.7 10.7 12.4 10.9 13.6 11.3 15.5 12.4 16.1 12.4 17.0 12.4 18.0 12.3 122 11.3 10.3 11.8 10.4 12.9 10.6 14.7 11.8 15.3 11.8 16.0 11.8 17.2 11.8

FOUR-WAY CEILING CASSETTECooling Capacity TablesARNU153TNA4, ARNU183TNA4

TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 115: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 115

Four-Way C

eiling Cassette Product D

ata

©

Table 47: ARNU243TNA4 Cooling Capacity Table.

Model No. /Capacity Index

Outdoor Air Temp. (°F DB)

Indoor Air Temperature (°F DB / WB)68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh

ARNU243TNA4 / 24.2

-9.9 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8 -5 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8 0 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8 5 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8

10 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8 14 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8 20 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8 23 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8 25 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8 30 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8 35 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8 40 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8 45 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8 50 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8 55 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.3 20.8 60 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 31.0 20.7 65 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 30.5 20.4 70 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 30.0 20.0 75 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.8 20.8 29.2 19.6 80 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 27.1 21.0 28.0 20.7 28.5 19.5 85 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 26.8 20.8 27.1 19.8 27.6 18.7 90 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 26.4 20.5 26.6 19.5 27.1 18.5 95 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 25.9 20.4 26.4 19.4 26.8 18.3

100 15.9 15.0 19.4 17.3 21.8 18.4 24.2 19.6 25.4 20.0 25.9 19.2 26.4 18.2 105 15.9 15.0 18.4 16.4 20.8 17.6 23.2 18.7 24.1 18.7 24.9 18.5 25.6 17.7 110 15.5 14.5 17.4 15.5 19.4 16.4 21.8 17.6 22.8 17.6 23.7 17.6 24.7 17.2 115 15.1 14.1 16.6 14.7 18.2 15.4 20.5 16.7 21.4 16.7 22.5 16.7 23.7 16.5 118 14.8 13.7 15.7 14.0 17.3 14.5 19.7 15.9 20.4 15.9 21.5 15.9 22.8 15.8 122 14.4 13.3 15.0 13.3 16.3 13.6 18.6 15.1 19.4 15.1 20.3 15.1 21.9 15.1

FOUR-WAY CEILING CASSETTECooling Capacity Tables

ARNU243TNA4

TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 116: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

116 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

FOUR-WAY CEILING CASSETTECooling Capacity TablesARNU283TMA4, ARNU363TMA4

Table 48: ARNU283TMA4, ARNU363TMA4 Cooling Capacity Table.

Model No. /Capacity Index

Out-door Air Temp.

(°F DB)

Indoor Air Temperature (°F DB / WB)68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh

ARNU283TMA4 /28.0

-9.9 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6 -5 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6 0 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6 5 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6

10 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6 14 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6 20 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6 23 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6 25 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6 30 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6 35 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6 40 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6 45 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6 50 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6 55 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 36.2 22.6 60 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 35.8 22.5 65 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 35.2 22.1 70 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 34.8 21.8 75 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 33.4 22.6 33.8 21.3 80 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.4 22.9 32.4 22.5 33.0 21.2 85 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 31.0 22.6 31.4 21.5 32.0 20.4 90 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 30.6 22.3 30.8 21.2 31.4 20.1 95 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 30.0 22.1 30.6 21.1 31.0 19.9

100 18.4 16.3 22.4 18.8 25.2 20.0 28.0 21.3 29.4 21.8 30.0 20.8 30.6 19.8 105 18.4 16.3 21.2 17.8 24.0 19.2 26.8 20.4 27.9 20.4 28.8 20.1 29.6 19.3 110 18.0 15.8 20.2 16.9 22.4 17.8 25.2 19.2 26.4 19.2 27.4 19.2 28.6 18.7 115 17.5 15.3 19.2 16.0 21.1 16.8 23.7 18.2 24.8 18.2 26.0 18.2 27.4 17.9 118 17.1 14.9 18.2 15.2 20.0 15.8 22.7 17.3 23.7 17.3 24.9 17.3 26.3 17.2 122 16.6 14.4 17.3 14.4 18.9 14.8 21.5 16.4 22.4 16.4 23.5 16.4 25.3 16.4

ARNU363TMA4 /36.2

-9.9 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4 -5 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4 0 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4 5 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4

10 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4 14 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4 20 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4 23 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4 25 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4 30 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4 35 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4 40 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4 45 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4 50 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4 55 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.8 28.4 60 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 46.3 28.3 65 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 45.6 27.8 70 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 44.9 27.4 75 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 43.1 28.4 43.7 26.8 80 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.6 28.7 41.9 28.3 42.7 26.6 85 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 40.1 28.4 40.6 27.1 41.3 25.6 90 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 39.5 28.0 39.8 26.6 40.6 25.3 95 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 38.8 27.8 39.5 26.5 40.1 25.0

100 23.8 20.5 29.0 23.6 32.6 25.1 36.2 26.8 38.0 27.4 38.8 26.2 39.5 24.8 105 23.8 20.5 27.5 22.4 31.1 24.1 34.7 25.6 36.1 25.6 37.3 25.3 38.3 24.2 110 23.2 19.9 26.1 21.2 29.0 22.4 32.6 24.1 34.1 24.1 35.4 24.1 37.0 23.5 115 22.7 19.3 24.8 20.1 27.2 21.1 30.6 22.9 32.0 22.9 33.7 22.9 35.5 22.5 118 22.1 18.7 23.5 19.1 25.8 19.8 29.4 21.7 30.6 21.7 32.1 21.7 34.1 21.6 122 21.5 18.1 22.4 18.2 24.4 18.6 27.8 20.6 29.0 20.6 30.4 20.6 32.7 20.6

TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 117: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 117

Four-Way C

eiling Cassette Product D

ata

©

Model No. /Capacity Index

Outdoor Air Temp. (°F DB)

Indoor Air Temperature (°F DB / WB)68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh

ARNU423TMC4 / 42.0

-9.9 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1 -5 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1 0 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1 5 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1

10 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1 14 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1 20 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1 23 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1 25 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1 30 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1 35 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1 40 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1 45 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1 50 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1 55 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 54.3 32.1 60 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 53.7 31.9 65 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 52.9 31.4 70 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 52.2 30.9 75 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 50.1 32.1 50.8 30.2 80 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 47.1 32.4 48.7 31.9 49.5 30.0 85 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 46.6 32.1 47.1 30.5 48.0 28.8 90 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 45.9 31.6 46.2 30.0 47.1 28.5 95 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 45.0 31.4 45.9 29.9 46.6 28.2

100 27.7 23.1 33.6 26.6 37.8 28.3 42.0 30.2 44.1 30.9 45.0 29.5 45.9 28.0 105 27.7 23.1 31.9 25.3 36.1 27.1 40.3 28.8 41.9 28.8 43.2 28.5 44.5 27.3 110 27.0 22.4 30.3 23.9 33.6 25.3 37.8 27.1 39.6 27.1 41.1 27.1 42.9 26.5 115 26.3 21.7 28.8 22.7 31.6 23.8 35.5 25.8 37.2 25.8 39.1 25.8 41.2 25.4 118 25.6 21.1 27.3 21.6 30.0 22.3 34.1 24.5 35.5 24.5 37.3 24.5 39.5 24.4 122 24.9 20.4 26.0 20.5 28.4 21.0 32.3 23.3 33.6 23.3 35.3 23.3 37.9 23.3

ARNU483TMC4 /48.1

-9.9 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7 -5 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7 0 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7 5 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7

10 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7 14 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7 20 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7 23 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7 25 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7 30 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7 35 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7 40 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7 45 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7 50 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7 55 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 62.1 36.7 60 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 61.5 36.5 65 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 60.5 35.9 70 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 59.7 35.4 75 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 57.3 36.7 58.1 34.6 80 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.9 37.1 55.7 36.5 56.7 34.4 85 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 53.3 36.7 53.9 35.0 54.9 33.0 90 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 52.5 36.1 52.9 34.4 53.9 32.6 95 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 51.5 35.9 52.5 34.2 53.3 32.3

100 31.7 26.4 38.5 30.5 43.3 32.4 48.1 34.6 50.5 35.4 51.5 33.8 52.5 32.1 105 31.7 26.4 36.5 28.9 41.3 31.1 46.1 33.0 48.0 33.0 49.5 32.6 50.9 31.3 110 30.9 25.6 34.7 27.4 38.5 28.9 43.3 31.1 45.3 31.1 47.1 31.1 49.1 30.3 115 30.1 24.9 32.9 26.0 36.2 27.2 40.7 29.5 42.6 29.5 44.7 29.5 47.1 29.1 118 29.3 24.1 31.3 24.7 34.3 25.6 39.1 28.0 40.6 28.0 42.7 28.0 45.3 27.9 122 28.6 23.4 29.7 23.4 32.5 24.1 36.9 26.6 38.5 26.6 40.4 26.6 43.4 26.6

Table 49: ARNU423TMC4, ARNU483TMC4 Cooling Capacity Table.

FOUR-WAY CEILING CASSETTECooling Capacity Tables

ARNU423TMC4, ARNU483TMC4

TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 118: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

118 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Table 50: ARNU053TRD4, ARNU073TRD4, ARNU093TRD4, ARNU123TRD4 Heating Capacity Table.

Model No. /Capacity Index

Outdoor Air Temp. Indoor Air Temperature (°F DB)59 61 64 67 70 73 76 80

°F DB °F WB TC TC TC TC TC TC TC TCMBh MBh MBh MBh MBh MBh MBh MBh

ARNU053TRD4 / 5.5

-21.6 -22.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1-17.1 -17.5 3.5 3.5 3.5 3.5 3.4 3.4 3.4 3.4-12.6 -13 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

-7 -7.6 4.0 4.0 4.0 4.0 3.9 3.9 3.9 3.9-4 -4.4 4.1 4.1 4.1 4.1 4.0 4.0 4.0 4.00 -0.4 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.25 4.5 4.8 4.7 4.6 4.6 4.6 4.6 4.6 4.6

10 9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.915 14 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.120 19 5.6 5.6 5.6 5.6 5.4 5.4 5.3 5.325 23 5.8 5.8 5.8 5.8 5.8 5.7 5.6 5.330 28 5.9 5.9 5.9 5.9 5.9 5.8 5.6 5.335 32 6.1 6.1 6.1 6.1 6.0 5.9 5.6 5.340 36 6.3 6.3 6.3 6.3 6.1 5.9 5.6 5.345 41 6.6 6.6 6.6 6.4 6.1 5.9 5.6 5.347 43 6.8 6.8 6.7 6.4 6.1 5.9 5.6 5.350 46 7.3 7.0 6.7 6.4 6.1 5.9 5.6 5.355 51 7.5 7.1 6.7 6.4 6.1 5.9 5.6 5.360 56 7.5 7.1 6.7 6.4 6.1 5.9 5.6 5.3

ARNU073TRD4 /7.5

-21.6 -22.0 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3-17.1 -17.5 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8-12.6 -13 5.4 5.4 5.4 5.4 5.3 5.3 5.3 5.3

-7 -7.6 5.5 5.5 5.5 5.5 5.4 5.4 5.4 5.4-4 -4.4 5.7 5.7 5.7 5.7 5.6 5.6 5.6 5.60 -0.4 5.9 5.9 5.9 5.9 5.9 5.8 5.8 5.85 4.5 6.6 6.6 6.5 6.5 6.5 6.5 6.5 6.5

10 9 6.9 6.9 6.9 6.8 6.8 6.8 6.8 6.815 14 7.3 7.3 7.3 7.3 7.3 7.3 7.2 7.120 19 7.7 7.7 7.7 7.7 7.6 7.6 7.4 7.425 23 8.1 8.1 8.1 8.1 8.1 7.9 7.8 7.430 28 8.3 8.3 8.3 8.3 8.3 8.1 7.8 7.435 32 8.5 8.5 8.5 8.5 8.4 8.3 7.8 7.440 36 8.8 8.8 8.8 8.8 8.5 8.3 7.8 7.445 41 9.2 9.2 9.2 8.9 8.5 8.3 7.8 7.447 43 9.5 9.4 9.4 8.9 8.5 8.3 7.8 7.450 46 10.2 9.8 9.4 8.9 8.5 8.3 7.8 7.455 51 10.4 9.9 9.4 8.9 8.5 8.3 7.8 7.460 56 10.4 9.9 9.4 8.9 8.5 8.3 7.8 7.4

ARNU093TRD4 /9.6

-21.6 -22.0 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5-17.1 -17.5 6.2 6.2 6.2 6.2 6.1 6.1 6.1 6.1-12.6 -13 6.9 6.9 6.9 6.9 6.8 6.8 6.8 6.8

-7 -7.6 7.1 7.1 7.1 7.1 7.0 7.0 7.0 7.0-4 -4.4 7.3 7.3 7.3 7.3 7.2 7.2 7.2 7.20 -0.4 7.5 7.5 7.5 7.5 7.5 7.4 7.4 7.45 4.5 8.5 8.4 8.3 8.3 8.3 8.3 8.3 8.3

10 9 8.8 8.8 8.8 8.7 8.7 8.7 8.7 8.715 14 9.4 9.4 9.4 9.4 9.4 9.4 9.3 9.220 19 9.9 9.9 9.9 9.9 9.7 9.7 9.5 9.425 23 10.4 10.4 10.4 10.4 10.4 10.1 10.0 9.530 28 10.6 10.6 10.6 10.6 10.6 10.4 10.0 9.535 32 10.9 10.9 10.9 10.9 10.8 10.6 10.0 9.540 36 11.3 11.3 11.3 11.3 10.9 10.6 10.0 9.545 41 11.8 11.8 11.8 11.5 10.9 10.6 10.0 9.547 43 12.2 12.1 12.0 11.5 10.9 10.6 10.0 9.550 46 13.1 12.5 12.0 11.5 10.9 10.6 10.0 9.555 51 13.4 12.6 12.0 11.5 10.9 10.6 10.0 9.560 56 13.4 12.6 12.0 11.5 10.9 10.6 10.0 9.5

FOUR-WAY CEILING CASSETTEHeating Capacity TablesARNU053TRD4, ARNU073TRD4, ARNU093TRD4, ARNU123TRF4

TC: Total Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 119: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 119

Four-Way C

eiling Cassette Product D

ata

©

Table 51: ARNU153TQD4, ARNU183TQD4 Heating Capacity Table.

Model No. /Capacity Index

Outdoor Air Temp. Indoor Air Temperature (°F DB)59 61 64 67 70 73 76 80

°F DB °F WB TC TC TC TC TC TC TC TCMBh MBh MBh MBh MBh MBh MBh MBh

ARNU123TRD4 / 12.3

-21.6 -22.0 6.9 6.9 6.9 6.9 6.8 6.8 6.8 6.8-17.1 -17.5 7.7 7.7 7.7 7.7 7.6 7.6 7.6 7.6-12.6 -13 8.6 8.6 8.6 8.6 8.5 8.5 8.5 8.5

-7 -7.6 8.8 8.8 8.8 8.8 8.7 8.7 8.7 8.7-4 -4.4 9.1 9.1 9.1 9.1 9.0 9.0 9.0 9.00 -0.4 9.4 9.4 9.4 9.4 9.4 9.3 9.3 9.35 4.5 10.6 10.5 10.3 10.3 10.3 10.3 10.3 10.3

10 9 11.0 11.0 11.0 10.9 10.9 10.9 10.9 10.915 14 11.7 11.7 11.7 11.7 11.7 11.7 11.6 11.420 19 12.4 12.4 12.4 12.4 12.1 12.1 11.9 11.825 23 12.9 12.9 12.9 12.9 12.9 12.7 12.5 11.930 28 13.2 13.2 13.2 13.2 13.2 12.9 12.5 11.935 32 13.6 13.6 13.6 13.6 13.5 13.2 12.5 11.940 36 14.1 14.1 14.1 14.1 13.6 13.2 12.5 11.945 41 14.7 14.7 14.7 14.3 13.6 13.2 12.5 11.947 43 15.2 15.1 15.0 14.3 13.6 13.2 12.5 11.950 46 16.3 15.6 15.0 14.3 13.6 13.2 12.5 11.955 51 16.7 15.8 15.0 14.3 13.6 13.2 12.5 11.960 56 16.7 15.8 15.0 14.3 13.6 13.2 12.5 11.9

ARNU153TQD4 /15.4

-21.6 -22.0 8.7 8.7 8.7 8.7 8.6 8.6 8.6 8.6-17.1 -17.5 9.7 9.7 9.7 9.7 9.6 9.6 9.6 9.6-12.6 -13 10.8 10.8 10.8 10.8 10.6 10.6 10.6 10.6

-7 -7.6 11.1 11.1 11.1 11.1 10.9 10.9 10.9 10.9-4 -4.4 11.5 11.5 11.5 11.5 11.3 11.3 11.3 11.30 -0.4 11.8 11.8 11.8 11.8 11.8 11.6 11.6 11.65 4.5 13.3 13.2 13.0 13.0 13.0 13.0 13.0 13.0

10 9 13.9 13.9 13.9 13.7 13.7 13.7 13.7 13.715 14 14.7 14.7 14.7 14.7 14.7 14.7 14.5 14.420 19 15.6 15.6 15.6 15.6 15.2 15.2 15.0 14.825 23 16.3 16.3 16.3 16.3 16.3 15.9 15.7 15.030 28 16.6 16.6 16.6 16.6 16.6 16.3 15.7 15.035 32 17.1 17.1 17.1 17.1 16.9 16.6 15.7 15.040 36 17.8 17.8 17.8 17.8 17.1 16.6 15.7 15.045 41 18.5 18.5 18.5 18.0 17.1 16.6 15.7 15.047 43 19.2 19.0 18.8 18.0 17.1 16.6 15.7 15.050 46 20.5 19.7 18.8 18.0 17.1 16.6 15.7 15.055 51 21.0 19.8 18.8 18.0 17.1 16.6 15.7 15.060 56 21.0 19.8 18.8 18.0 17.1 16.6 15.7 15.0

ARNU183TQD4 /19.1

-21.6 -22.0 10.9 10.9 10.9 10.9 10.8 10.8 10.8 10.8-17.1 -17.5 12.2 12.2 12.2 12.2 12.1 12.1 12.1 12.1-12.6 -13 13.6 13.6 13.6 13.6 13.4 13.4 13.4 13.4

-7 -7.6 14.0 14.0 14.0 14.0 13.8 13.8 13.8 13.8-4 -4.4 14.4 14.4 14.4 14.4 14.2 14.2 14.2 14.20 -0.4 14.8 14.8 14.8 14.8 14.8 14.6 14.6 14.65 4.5 16.8 16.6 16.3 16.3 16.3 16.3 16.3 16.3

10 9 17.4 17.4 17.4 17.2 17.2 17.2 17.2 17.215 14 18.5 18.5 18.5 18.5 18.5 18.5 18.3 18.120 19 19.6 19.6 19.6 19.6 19.1 19.1 18.8 18.625 23 20.4 20.4 20.4 20.4 20.4 20.0 19.8 18.830 28 20.9 20.9 20.9 20.9 20.9 20.4 19.8 18.835 32 21.5 21.5 21.5 21.5 21.3 20.9 19.8 18.840 36 22.4 22.4 22.4 22.4 21.5 20.9 19.8 18.845 41 23.2 23.2 23.2 22.6 21.5 20.9 19.8 18.847 43 24.1 23.9 23.7 22.6 21.5 20.9 19.8 18.850 46 25.8 24.7 23.7 22.6 21.5 20.9 19.8 18.855 51 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.860 56 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8

FOUR-WAY CEILING CASSETTEHeating Capacity Tables

ARNU153TQD4, ARNU183TQD4

TC: Total Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 120: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

120 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Table 52: ARNU073TNA4, ARNU093TNA4, ARNU123TNA4, ARNU153TNA4 Heating Capacity Table.

Model No. /Capacity Index

Outdoor Air Temp. Indoor Air Temperature (°F DB)59 61 64 67 70 73 76 80

°F DB °F WB TC TC TC TC TC TC TC TCMBh MBh MBh MBh MBh MBh MBh MBh

ARNU073TNA4 /7.5

-21.6 -22.0 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3-17.1 -17.5 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8-12.6 -13 5.4 5.4 5.4 5.4 5.3 5.3 5.3 5.3

-7 -7.6 5.5 5.5 5.5 5.5 5.4 5.4 5.4 5.4-4 -4.4 5.7 5.7 5.7 5.7 5.6 5.6 5.6 5.60 -0.4 5.9 5.9 5.9 5.9 5.9 5.8 5.8 5.85 4.5 6.6 6.6 6.5 6.5 6.5 6.5 6.5 6.5

10 9 6.9 6.9 6.9 6.8 6.8 6.8 6.8 6.815 14 7.3 7.3 7.3 7.3 7.3 7.3 7.2 7.120 19 7.7 7.7 7.7 7.7 7.6 7.6 7.4 7.425 23 8.1 8.1 8.1 8.1 8.1 7.9 7.8 7.430 28 8.3 8.3 8.3 8.3 8.3 8.1 7.8 7.435 32 8.5 8.5 8.5 8.5 8.4 8.3 7.8 7.440 36 8.8 8.8 8.8 8.8 8.5 8.3 7.8 7.445 41 9.2 9.2 9.2 8.9 8.5 8.3 7.8 7.447 43 9.5 9.4 9.4 8.9 8.5 8.3 7.8 7.450 46 10.2 9.8 9.4 8.9 8.5 8.3 7.8 7.455 51 10.4 9.9 9.4 8.9 8.5 8.3 7.8 7.460 56 10.4 9.9 9.4 8.9 8.5 8.3 7.8 7.4

ARNU093TNA4 /9.6

-21.6 -22.0 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5-17.1 -17.5 6.2 6.2 6.2 6.2 6.1 6.1 6.1 6.1-12.6 -13 6.9 6.9 6.9 6.9 6.8 6.8 6.8 6.8

-7 -7.6 7.1 7.1 7.1 7.1 7.0 7.0 7.0 7.0-4 -4.4 7.3 7.3 7.3 7.3 7.2 7.2 7.2 7.20 -0.4 7.5 7.5 7.5 7.5 7.5 7.4 7.4 7.45 4.5 8.5 8.4 8.3 8.3 8.3 8.3 8.3 8.3

10 9 8.8 8.8 8.8 8.7 8.7 8.7 8.7 8.715 14 9.4 9.4 9.4 9.4 9.4 9.4 9.3 9.220 19 9.9 9.9 9.9 9.9 9.7 9.7 9.5 9.425 23 10.4 10.4 10.4 10.4 10.4 10.1 10.0 9.530 28 10.6 10.6 10.6 10.6 10.6 10.4 10.0 9.535 32 10.9 10.9 10.9 10.9 10.8 10.6 10.0 9.540 36 11.3 11.3 11.3 11.3 10.9 10.6 10.0 9.545 41 11.8 11.8 11.8 11.5 10.9 10.6 10.0 9.547 43 12.2 12.1 12.0 11.5 10.9 10.6 10.0 9.550 46 13.1 12.5 12.0 11.5 10.9 10.6 10.0 9.555 51 13.4 12.6 12.0 11.5 10.9 10.6 10.0 9.560 56 13.4 12.6 12.0 11.5 10.9 10.6 10.0 9.5

FOUR-WAY CEILING CASSETTEHeating Capacity TablesARNU073TNA4, ARNU093TNA4

TC: Total Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 121: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 121

Four-Way C

eiling Cassette Product D

ata

©

Table 53: ARNU073TNA4, ARNU093TNA4, ARNU123TNA4, ARNU153TNA4 Heating Capacity Table.

Model No. /Capacity Index

Outdoor Air Temp. Indoor Air Temperature (°F DB)59 61 64 67 70 73 76 80

°F DB °F WB TC TC TC TC TC TC TC TCMBh MBh MBh MBh MBh MBh MBh MBh

ARNU123TNA4 /12.3

-21.6 -22.0 6.9 6.9 6.9 6.9 6.8 6.8 6.8 6.8-17.1 -17.5 7.7 7.7 7.7 7.7 7.6 7.6 7.6 7.6-12.6 -13 8.6 8.6 8.6 8.6 8.5 8.5 8.5 8.5

-7 -7.6 8.8 8.8 8.8 8.8 8.7 8.7 8.7 8.7-4 -4.4 9.1 9.1 9.1 9.1 9.0 9.0 9.0 9.00 -0.4 9.4 9.4 9.4 9.4 9.4 9.3 9.3 9.35 4.5 10.6 10.5 10.3 10.3 10.3 10.3 10.3 10.3

10 9 11.0 11.0 11.0 10.9 10.9 10.9 10.9 10.915 14 11.7 11.7 11.7 11.7 11.7 11.7 11.6 11.420 19 12.4 12.4 12.4 12.4 12.1 12.1 11.9 11.825 23 12.9 12.9 12.9 12.9 12.9 12.7 12.5 11.930 28 13.2 13.2 13.2 13.2 13.2 12.9 12.5 11.935 32 13.6 13.6 13.6 13.6 13.5 13.2 12.5 11.940 36 14.1 14.1 14.1 14.1 13.6 13.2 12.5 11.945 41 14.7 14.7 14.7 14.3 13.6 13.2 12.5 11.947 43 15.2 15.1 15.0 14.3 13.6 13.2 12.5 11.950 46 16.3 15.6 15.0 14.3 13.6 13.2 12.5 11.955 51 16.7 15.8 15.0 14.3 13.6 13.2 12.5 11.960 56 16.7 15.8 15.0 14.3 13.6 13.2 12.5 11.9

ARNU153TNA4 / 15.4

-21.6 -22.0 8.7 8.7 8.7 8.7 8.6 8.6 8.6 8.6-17.1 -17.5 9.7 9.7 9.7 9.7 9.6 9.6 9.6 9.6-12.6 -13 10.8 10.8 10.8 10.8 10.6 10.6 10.6 10.6

-7 -7.6 11.1 11.1 11.1 11.1 10.9 10.9 10.9 10.9-4 -4.4 11.5 11.5 11.5 11.5 11.3 11.3 11.3 11.30 -0.4 11.8 11.8 11.8 11.8 11.8 11.6 11.6 11.65 4.5 13.3 13.2 13.0 13.0 13.0 13.0 13.0 13.0

10 9 13.9 13.9 13.9 13.7 13.7 13.7 13.7 13.715 14 14.7 14.7 14.7 14.7 14.7 14.7 14.5 14.420 19 15.6 15.6 15.6 15.6 15.2 15.2 15.0 14.825 23 16.3 16.3 16.3 16.3 16.3 15.9 15.7 15.030 28 16.6 16.6 16.6 16.6 16.6 16.3 15.7 15.035 32 17.1 17.1 17.1 17.1 16.9 16.6 15.7 15.040 36 17.8 17.8 17.8 17.8 17.1 16.6 15.7 15.045 41 18.5 18.5 18.5 18.0 17.1 16.6 15.7 15.047 43 19.2 19.0 18.8 18.0 17.1 16.6 15.7 15.050 46 20.5 19.7 18.8 18.0 17.1 16.6 15.7 15.055 51 21.0 19.8 18.8 18.0 17.1 16.6 15.7 15.060 56 21.0 19.8 18.8 18.0 17.1 16.6 15.7 15.0

FOUR-WAY CEILING CASSETTEHeating Capacity Tables

ARNU123TNA4, ARNU153TNA4

TC: Total Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 122: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

122 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Table 54: ARNU183TNA4, ARNU243TNA4 Heating Capacity Table.

Model No. /Capacity Index

Outdoor Air Temp. Indoor Air Temperature (°F DB)59 61 64 67 70 73 76 80

°F DB °F WB TC TC TC TC TC TC TC TCMBh MBh MBh MBh MBh MBh MBh MBh

ARNU183TNA4 /19.1

-21.6 -22.0 10.9 10.9 10.9 10.9 10.8 10.8 10.8 10.8-17.1 -17.5 12.2 12.2 12.2 12.2 12.1 12.1 12.1 12.1-12.6 -13 13.6 13.6 13.6 13.6 13.4 13.4 13.4 13.4

-7 -7.6 14.0 14.0 14.0 14.0 13.8 13.8 13.8 13.8-4 -4.4 14.4 14.4 14.4 14.4 14.2 14.2 14.2 14.20 -0.4 14.8 14.8 14.8 14.8 14.8 14.6 14.6 14.65 4.5 16.8 16.6 16.3 16.3 16.3 16.3 16.3 16.3

10 9 17.4 17.4 17.4 17.2 17.2 17.2 17.2 17.215 14 18.5 18.5 18.5 18.5 18.5 18.5 18.3 18.120 19 19.6 19.6 19.6 19.6 19.1 19.1 18.8 18.625 23 20.4 20.4 20.4 20.4 20.4 20.0 19.8 18.830 28 20.9 20.9 20.9 20.9 20.9 20.4 19.8 18.835 32 21.5 21.5 21.5 21.5 21.3 20.9 19.8 18.840 36 22.4 22.4 22.4 22.4 21.5 20.9 19.8 18.845 41 23.2 23.2 23.2 22.6 21.5 20.9 19.8 18.847 43 24.1 23.9 23.7 22.6 21.5 20.9 19.8 18.850 46 25.8 24.7 23.7 22.6 21.5 20.9 19.8 18.855 51 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.860 56 26.3 24.9 23.7 22.6 21.5 20.9 19.8 18.8

ARNU243TNA4 /24.2

-21.6 -22.0 13.9 13.9 13.9 13.9 13.7 13.7 13.7 13.7-17.1 -17.5 15.5 15.5 15.5 15.5 15.3 15.3 15.3 15.3-12.6 -13 17.2 17.2 17.2 17.2 17.0 17.0 17.0 17.0

-7 -7.6 17.8 17.8 17.8 17.8 17.5 17.5 17.5 17.5-4 -4.4 18.3 18.3 18.3 18.3 18.0 18.0 18.0 18.00 -0.4 18.8 18.8 18.8 18.8 18.8 18.6 18.6 18.65 4.5 21.3 21.0 20.8 20.8 20.8 20.8 20.8 20.8

10 9 22.1 22.1 22.1 21.8 21.8 21.8 21.8 21.815 14 23.5 23.5 23.5 23.5 23.5 23.5 23.2 22.920 19 24.8 24.8 24.8 24.8 24.3 24.3 23.9 23.625 23 25.9 25.9 25.9 25.9 25.9 25.4 25.1 23.930 28 26.5 26.5 26.5 26.5 26.5 25.9 25.1 23.935 32 27.3 27.3 27.3 27.3 27.0 26.5 25.1 23.940 36 28.4 28.4 28.4 28.4 27.3 26.5 25.1 23.945 41 29.5 29.5 29.5 28.7 27.3 26.5 25.1 23.947 43 30.6 30.3 30.0 28.7 27.3 26.5 25.1 23.950 46 32.8 31.4 30.0 28.7 27.3 26.5 25.1 23.955 51 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.960 56 33.4 31.7 30.0 28.7 27.3 26.5 25.1 23.9

ARNU183TNA4, ARNU243TNA4

FOUR-WAY CEILING CASSETTEHeating Capacity Tables

TC: Total Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 123: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 123

Four-Way C

eiling Cassette Product D

ata

©

Table 55: ARNU283TMA4, ARNU363TMA4, ARNU423TMC4 Heating Capacity Table.

FOUR-WAY CEILING CASSETTEHeating Capacity Tables

ARNU283TMA4, ARNU363TMA4, ARNU423TMC4

Model No. /Capacity Index

Outdoor Air Temp. Indoor Air Temperature (°F DB)59 61 64 67 70 73 76 80

°F DB °F WB TC TC TC TC TC TC TC TCMBh MBh MBh MBh MBh MBh MBh MBh

ARNU283TMA4 /28.0

-21.6 -22.0 16.0 16.0 16.0 16.0 15.8 15.8 15.8 15.8-17.1 -17.5 17.9 17.9 17.9 17.9 17.7 17.7 17.7 17.7-12.6 -13 19.9 19.9 19.9 19.9 19.6 19.6 19.6 19.6

-7 -7.6 20.5 20.5 20.5 20.5 20.2 20.2 20.2 20.2-4 -4.4 21.1 21.1 21.1 21.1 20.8 20.8 20.8 20.80 -0.4 21.7 21.7 21.7 21.7 21.7 21.4 21.4 21.45 4.5 24.6 24.3 23.9 23.9 23.9 23.9 23.9 23.9

10 9 25.5 25.5 25.5 25.2 25.2 25.2 25.2 25.215 14 27.1 27.1 27.1 27.1 27.1 27.1 26.8 26.520 19 28.7 28.7 28.7 28.7 28.0 28.0 27.6 27.325 23 29.9 29.9 29.9 29.9 29.9 29.3 29.0 27.630 28 30.6 30.6 30.6 30.6 30.6 29.9 29.0 27.635 32 31.5 31.5 31.5 31.5 31.2 30.6 29.0 27.640 36 32.8 32.8 32.8 32.8 31.5 30.6 29.0 27.645 41 34.0 34.0 34.0 33.1 31.5 30.6 29.0 27.647 43 35.3 35.0 34.7 33.1 31.5 30.6 29.0 27.650 46 37.8 36.2 34.7 33.1 31.5 30.6 29.0 27.655 51 38.6 36.5 34.7 33.1 31.5 30.6 29.0 27.660 56 38.6 36.5 34.7 33.1 31.5 30.6 29.0 27.6

ARNU363TMA4 /36.2

-21.6 -22.0 20.6 20.6 20.6 20.6 20.3 20.3 20.3 20.3-17.1 -17.5 23.1 23.1 23.1 23.1 22.8 22.8 22.8 22.8-12.6 -13 25.6 25.6 25.6 25.6 25.2 25.2 25.2 25.2

-7 -7.6 26.4 26.4 26.4 26.4 26.0 26.0 26.0 26.0-4 -4.4 27.2 27.2 27.2 27.2 26.8 26.8 26.8 26.80 -0.4 28.0 28.0 28.0 28.0 28.0 27.6 27.6 27.65 4.5 31.7 31.3 30.9 30.9 30.9 30.9 30.9 30.9

10 9 32.9 32.9 32.9 32.5 32.5 32.5 32.5 32.515 14 34.9 34.9 34.9 34.9 34.9 34.9 34.5 34.120 19 37.0 37.0 37.0 37.0 36.1 36.1 35.5 35.125 23 38.6 38.6 38.6 38.6 38.6 37.8 37.4 35.530 28 39.4 39.4 39.4 39.4 39.4 38.6 37.4 35.535 32 40.6 40.6 40.6 40.6 40.2 39.4 37.4 35.540 36 42.2 42.2 42.2 42.2 40.6 39.4 37.4 35.545 41 43.9 43.9 43.9 42.6 40.6 39.4 37.4 35.547 43 45.5 45.1 44.7 42.6 40.6 39.4 37.4 35.550 46 48.7 46.7 44.7 42.6 40.6 39.4 37.4 35.555 51 49.7 47.1 44.7 42.6 40.6 39.4 37.4 35.560 56 49.7 47.1 44.7 42.6 40.6 39.4 37.4 35.5

TC: Total Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 124: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

124 | FOUR-WAY

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

FOUR-WAY CEILING CASSETTEHeating Capacity TablesARNU483TMC4

Model No. /Capacity Index

Outdoor Air Temp. Indoor Air Temperature (°F DB)59 61 64 67 70 73 76 80

°F DB °F WB TC TC TC TC TC TC TC TCMBh MBh MBh MBh MBh MBh MBh MBh

ARNU423TMC4 /42.0

-21.6 -22.0 22.2 22.2 22.2 22.2 21.9 21.9 21.9 21.9-17.1 -17.5 24.9 24.9 24.9 24.9 24.6 24.6 24.6 24.6-12.6 -13 27.6 27.6 27.6 27.6 27.2 27.2 27.2 27.2

-7 -7.6 28.5 28.5 28.5 28.5 28.0 28.0 28.0 28.0-4 -4.4 29.4 29.4 29.4 29.4 28.9 28.9 28.9 28.90 -0.4 30.2 30.2 30.2 30.2 30.2 29.8 29.8 29.85 4.5 34.2 33.7 33.3 33.3 33.3 33.3 33.3 33.3

10 9 35.5 35.5 35.5 35.0 35.0 35.0 35.0 35.015 14 37.7 37.7 37.7 37.7 37.7 37.7 37.2 36.820 19 39.9 39.9 39.9 39.9 39.0 39.0 38.3 37.925 23 41.6 41.6 41.6 41.6 41.6 40.7 40.3 38.330 28 42.5 42.5 42.5 42.5 42.5 41.6 40.3 38.335 32 43.8 43.8 43.8 43.8 43.4 42.5 40.3 38.340 36 45.6 45.6 45.6 45.6 43.8 42.5 40.3 38.345 41 47.3 47.3 47.3 46.0 43.8 42.5 40.3 38.347 43 49.1 48.6 48.2 46.0 43.8 42.5 40.3 38.350 46 52.6 50.4 48.2 46.0 43.8 42.5 40.3 38.355 51 53.7 50.8 48.2 46.0 43.8 42.5 40.3 38.360 56 53.7 50.8 48.2 46.0 43.8 42.5 40.3 38.3

ARNU483TMC4 /48.1

-21.6 -22.0 26.0 26.0 26.0 26.0 25.6 25.6 25.6 25.6-17.1 -17.5 29.1 29.1 29.1 29.1 28.7 28.7 28.7 28.7-12.6 -13 32.3 32.3 32.3 32.3 31.8 31.8 31.8 31.8

-7 -7.6 33.3 33.3 33.3 33.3 32.8 32.8 32.8 32.8-4 -4.4 34.3 34.3 34.3 34.3 33.8 33.8 33.8 33.80 -0.4 35.3 35.3 35.3 35.3 35.3 34.8 34.8 34.85 4.5 39.9 39.4 38.9 38.9 38.9 38.9 38.9 38.9

10 9 41.5 41.5 41.5 41.0 41.0 41.0 41.0 41.015 14 44.0 44.0 44.0 44.0 44.0 44.0 43.5 43.020 19 46.6 46.6 46.6 46.6 45.6 45.6 44.8 44.325 23 48.6 48.6 48.6 48.6 48.6 47.6 47.1 44.830 28 49.7 49.7 49.7 49.7 49.7 48.6 47.1 44.835 32 51.2 51.2 51.2 51.2 50.7 49.7 47.1 44.840 36 53.3 53.3 53.3 53.3 51.2 49.7 47.1 44.845 41 55.3 55.3 55.3 53.8 51.2 49.7 47.1 44.847 43 57.3 56.8 56.3 53.8 51.2 49.7 47.1 44.850 46 61.4 58.9 56.3 53.8 51.2 49.7 47.1 44.855 51 62.7 59.4 56.3 53.8 51.2 49.7 47.1 44.860 56 62.7 59.4 56.3 53.8 51.2 49.7 47.1 44.8

Table 56: ARNU483TMC4 Heating Capacity Table.

TC: Total Capacity (MBh).The System Combination Ratio must be between 50–130%.Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

For outdoor unit performance data, see the respective outdoor unit performance data manuals on www.lghvac.com.Low ambient performance with LGRED° heat techlology is included in Multi V 5 air source units produced after February 2019.

Page 125: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

FOUR-WAY | 125

Four-Way C

eiling Cassette Product D

ata

©

Optional AccessoriesFOUR-WAY CEILING CASSETTE

Accessory Model Number

' x 2') Four-Way CeilingCassette Grille Kit — White (One Required)

PT-QCHW0 (For 5~19MBh TR and TQ FrameIndoor Units)

27-9/16" x 27-9/16" (2’ x 2’) Four-Way CeilingCassette Grille Kit — White (One Required)

PT-UQC (For 5~19MBh TR and TQ FrameIndoor Units)

3' x 3' Four-Way Ceiling Cassette Grille Kit — White(One Required)

PT-UMC1 (For 7~48MBh TN, TM Frame Indoor Units)

Ventilation Kit1 PTVK410 + PTVK420

Ventilation Kit2 PTVK430

Auto Elevation Kit1 PTEGM0

Cassette Decorative Cover2

PTDCQ (For 5~19MBh TR and TQ FrameIndoor Units)

PTDCM (For 7~48MBh TN, TM Frame Indoor Units)

Auxiliary Heater Kit2 PRARH1

Wi-Fi Module2 PWFMDD200

1For use with TN and TM frame four-way ceiling-cassette indoor units.2For use with all four-way ceiling-cassette indoor units.All accessories are sold separately.

Table 57: Optional Accessories for Four-Way Ceiling Cassette Indoor Units.

Page 126: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

APPLICATION GUIDELINES

Selecting the Best Location on page 127General Mounting on page 128General Drain Piping Information on page 129Wiring Guidelines on page 131Wired Controller Location on page 136Acronyms on page 137

Page 127: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

GUIDELINES | 127

Application G

uidelines

©

APPLICATION GUIDELINESSelecting the Best Location

Selecting the Best LocationDo’s• Place the unit where air circulation will not be blocked.• Place the unit where drainage can be obtained easily and to mini-

mize the length of the condensate drain piping.• Place the unit where noise prevention is taken into consideration.• Ensure there is sufficient space from the ceiling and floor.• Ensure there is sufficient maintenance space.• Locate the indoor unit in a location where it can be easily connect-

ed to the outdoor unit / heat recovery unit.

Installing in an Area Exposed to Unconditioned AirIn some installation applications, areas (floors, walls) in some rooms may be exposed to unconditioned air (room may be above or next to an unheated garage or storeroom). To countermeasure: • Verify that carpet is or will be installed (carpet may increase the temperature by three [3] degrees).• Add insulation between the floor joists. • Install radiant heat or another type of heating system to the floor.

Figure 83: Selecting the Best Location / Minimum Clearance Require-ments — One-, Two-, and Four-Way Ceiling-Cassette Indoor Units.

Install a ventilation fanwith sufficient capacity

Heat or steam source

Indoor Unit

Include enough distance

Figure 84: Installing Near a Heat or Steam Source.

Do Not’s• Avoid installing the unit near high-frequency generators.• Do not install the unit near a doorway.• The unit must not be installed near a heat or steam source, or

where considerable amounts of oil, iron powder, or flour are used. (These materials may generate condensate, cause a reduction in heat exchanger efficiency, or the drain pump to malfunction. If this is a potential problem, install a ventilation fan large enough to vent

The unit may be damaged, may malfunction, and / or will not operate as designed if installed in any of the conditions listed.

corrosive gases are generated, vented into, or stored. There is risk of

• or in environments where there is improper air make up or supply or inadequate ventilation. If there are concerns about VOCs in the environ-ment where the IDUs are installed, proper air make up or supply and/or adequate ventilation should be provided. Additionally, in buildings where IDUs will be exposed to VOCs, consider a third party factory-applied epoxy coating to the fan coils for each IDU where the entire coil is dipped, not sprayed.

• If the unit is installed near a body of water, the installation parts are at risk of corroding. Appropriate anti-corrosion methods must be taken for the unit and all installation parts.

Ceiling

Ceiling TileCeiling Tile

Floor

Unit: Inch

39-3/8or more

13/32or more

19-11/16or more

19-11/16or more 11-13/16

or less19/32 ±1/8

1-3/16 ± 1/8

* Four-Way TQ/TR Frames

* Four-Way TN/TM Frames

“A”

“A”Four-Way <36,000 Btu/h: 70-7/8 to 141-23/32 inches Four-Way >36,000 Btu/h: 70-7/8 to 165-11/32 inches

One-Way Only: 7-7/8 or more

One-Way: 70-7/8 to 129-15/16 inches Two-Way: 70-7/8 to 129-15/16 inches

* Two-Way TS Frames

13/16 ±1/8

Page 128: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

128 | GUIDELINES

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

General MountingThe ceiling must be strong and solid enough to protect the unit from vibration. All ceiling-cassette indoor units include a pattern to help deter-mine the size necessary for the opening in the false ceiling (paper pattern dimensions match those for the ceiling opening dimensions), and where the hanging bolts and refrigerant / drain piping are placed.

Figure 85: Ceiling Opening / Hanging Bolt Locations for One-Way Ceil-ing Cassette Indoor Units.

Figure 86: Ceiling Opening / Hanging Bolt Locations for Two-Way Ceil-ing Cassette Indoor Units.

General MountingAPPLICATION GUIDELINES

Figure 87: Ceiling Opening / Hanging Bolt Locations for Four-Way Ceiling Cassette Indoor Units.

(Unit: Inch)

TU Frames: 38, TT Frames: 50-5/8

TU Frames: 41-15/16, TT Frames: 54-9/16

2

TU Frames: 33-7/8, TT Frames: 46-1/2 17-5/8

12-1/16

2

9-7/8

23-5/8

15-3/4

1-9/16

1-9/16

18-3/8

13-15/

16

16-1/

8 Han

ging B

olt23

-5/8

25-1

/4 C

eilin

g O

peni

ng

(Unit: Inch)

40-11/16 Ceiling Opening33-11/16 Hanging Bolt

32-11/162-3/8

116(4-9

/16)4-9/

16

Unit: Inch (mm)

31 (788) (Hanging Bolt)26

-15/

16 (6

84) (

Hang

ing

Bolt)

26-7

16 (6

71)

34-7

/16

(875

) (Ce

iling

Ope

ning

)

33-1/16 (840)Unit Size

33-1/

16 (8

40) U

nit si

ze

34-7/16 (875) (Ceiling Opening)TM-TN Frame

Unit: Inch (mm)

20-23/64 (517)

18-5/32 (461)

20-1

9/32

(523

)

22-7

/16

(570

) 12

-9/1

6 (3

19)

23~2

6 (5

85~6

60) (

Ceilin

g O

peni

ng)

23~26 (585~660) (Ceiling Opening)

20-2

3/64

(517

)

22-7/16(570)

TR-TQ Frame

Page 129: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

GUIDELINES | 129

Application G

uidelines

©

General Drain Piping InformationAll ceiling-cassette indoor units generate water during cooling operation, therefore, properly handling this condensation must be considered. Ceiling-cassette indoor units include factory-installed drain pumps. Depending on the location of the indoor unit, condensation can be drained directly to the outside of the building, or a common indoor unit drainage piping system can be installed.

Indoor Unit Drain Type Drain Pipe Dia. (OD / ID, in.)

One-Way Ceiling Cassette 27-9/16 in. (700 mm) Max. Lift

Drain Pump,Factory Installed

Ø1-1/4 / Ø1Two-Way Ceiling CassetteFour-Way Ceiling Cassette

Table 58:

1/50~1/100 slope

Hanger distance

3.3~49.2ftHanger Bracket

MAX

27

-1/2

inch

Flexible drain hose

Insulation

Metalclamp

Max 11-13/16 inch

Do not damage power wiring during installation. There is risk of electric shock, which may result in physical injury or death.

Ceiling

Figure 88: Using the Paper Pattern / Drilling Holes for the Bolts, Refrigerant and Condensate Piping.

Set screw ofpaper pattern (4 pieces)Paper pattern

for installation

Ceiling boardCeiling board

Ceiling

Flat washer for M10(accessory)

Keep the length of the bolt from the bracket to 1-1/2 inches (1-9/16 inchesOne-Way only)

Open the ceiling boardalong the outer edge of the paper pattern

Flat washer for M10(accessory)

Hanging bolt(W3/8 or M10)

Nut(W3/8 or M10)

Nut(W3/8 or M10)Spring washer

(M10)

Air Conditioner body

One-Way TT/TU Frames: 2-3/4 inchesTwo-Way TS Frames: 3-9/16 inchesFour-Way TQ/TR Frames: 4-1/8 inchesFour-Way TM/TN Frames: 4-1/4 inches

Leave about 19/32 inches (TM/TN), 1-7/32~1-11/32 inches (TQ/TR), 25/32 ±1/8 (TT/TU), or 13/16 ±1/8 (TS) between the bottom surface of the indoor unit and the ceiling surface.

Bottom align

General Mounting / General Drain Piping Information

APPLICATION GUIDELINES

General Mounting Procedure1. Using the included paper pattern, select and mark the area where the hanging

bolts, refrigerant and condensate piping will be placed. The hanging bolts must be slightly tilted to the direction of the drain hose.

2. Drill the holes.3. Install the unit horizontally using a level gauge.

Figure 89: Hanging Bolt Installation.

The following parts are field supplied:• Hanging bolt - W-3/8” or 1/2”• Nut - W-3/8” or M10• Spring washer - M10

Included with the indoor unit:• Flat washer - M10

tightened to prevent the unit from falling from its installation loca-tion. There is a risk of personal injury from falling equipment.Figure 90: Ceiling-Cassette Indoor Unit Drain Pump to Drain Piping System.

Flexible Drain HoseCeiling-cassette indoor units in-clude a factory-provided flexible drain hose (with two clamps) to connect the indoor unit to the drain piping / drain piping system. If necessary, the drain hose can be extended. When the bottom surface of the indoor unit is at an elevation below the receiving building drain line connection, install an inverted trap at the top of the condensate pump dis-charge riser before connection to the building drain pipe.

Figure 91: Flexible Drain Hose Connection.

Do not damage power wiring during installation. There is a risk of equipment malfunction, which may result in property damage.

Page 130: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

130 | GUIDELINES

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

APPLICATION GUIDELINESGeneral Drain Piping Information

Ensure the indoor unit, refrigerant piping, drain piping, and power wiring / communication cables are properly supported with anchor bolts and clamp hangers positioned at 3.3 to 4.9 foot intervals.

Figure 93: Example of a Common Indoor Unit Drainage System.

Drain Piping• Drain piping must have down slope (1/50 to 1/100). • Any holes through the ceilings, walls, etc., must be large enough to accom-

modate the drain piping and insulation.• The outside diameter of the drain connection on the indoor unit is 1-1/4

inches.• Drain piping material is polyvinyl chloride pipe (1 inch).

Drain Leak TestA leak test must be performed 24 hours after the drainage system has been installed.

Drain Pipe InsulationInstall field supplied polyethylene foam insulation 5/16 inch thick or greater on the flexible drain pipe and position snugly again indoor unit.

Common Indoor Unit Drainage SystemIt is usual work practice to connect individual indoor unit drain pipes to one common indoor unit drainage system.

The diameter of the common vertical drain pipe must be as large as necessary. The diameter of the horizontal pipe must be the same or larger than the vertical drain pipe. To avoid property damage in the event of the primary drain becom-ing clogged, and to optimize drain system perfor-mance, it may be prudent to install a secondary drain line.

Design the drain system to plan for winter opera-tion (condensate line may freeze up if condensate does not properly drain away). Drain all gener-ated condensate from the external condensate pan to an appropriate area. Install a trap in the condensate lines as near to the indoor unit coil as possible. To prevent overflow, the outlet of each trap must be positioned below its connection to the condensate pan. All traps must be primed, insulated, and leak tested.

Common horizontal drain pipe 1/50 to 1/100 Slope

27-1/2 in. (Maximum pumplift distance [depends on indoorunit type]).

Include trapat the end.

45° to 60° Angle

Position the vent down to preventdebris from enteringthe system

45° to 60° Angle

45° to 60° Angle

45° to 60° angle for protection against overflow

Common verticaldrain pipe

Maintenancedrain port

Upwardroutingnot allowed

Pipe clamp

Indoor unit

Figure 92: Drain Piping Slope.

• It is recommended that a dedicated drain pipe be installed for the air conditioning sys-tem. If the indoor unit drainage system is shared with a rainwater drain, waste water, or any other type of building drain system, back flow, leaks, ice may form, or noxious odors may infiltrate the air conditioning system.

• Install a trap if the drain access to the outside faces an undesirable location (i.e.,

Flexible Drain Hose, continued.When the receiving drain line is mounted horizontal, connect the inverted trap to the top half of the pipe. The connection point of the inverted trap to the building drain pipe must always be to the top half of the pipe and must never be over 45° either side of the upper most point of the horizontal building drain line.

Page 131: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

GUIDELINES | 131

Application G

uidelines

©

APPLICATION GUIDELINESWiring Guidelines

Connecting the Power Wiring / Communication CableDANGE

High voltage electricity is required to operate this system. Adhere to the National Electrical Codes and these instructions when wiring. Always ground the unit following local, state, and National Electrical Codes. Read the safety summary at the begin-ning of this manual.• Secure all field wiring connections with appropriate wire strain relief. Improperly securing wires will create undue stress on equipment power

lugs. Inadequate connections will generate heat, cause a fire and physical injury or death.• Properly tighten all power connections. Loose wiring will overheat at connection points, causing a fire, physical injury or death.

• Connect the indoor unit input power cable but do not apply power to the indoor unit until authorized to do so by the system commission-ing agent. Inappropriate power connection can result in equipment damage and will void the LG limited liability warranty.

• -cal path or route the wire takes. The installer can use discretion when choosing the order the components are connected to the communica-tions bus, but must maintain the daisy chain and polarity configuration.

• Failure to follow any of these power and communications wiring guidelines or instructions will cause communications errors and unit mal-function.

Do Not’s• Never use wire caps and never splice communications cables.• Never connect zone controllers or other central controllers or LG building management system gateways to the indoor unit / outdoor unit

communications cable.

Connection ProcedureIndoor unit installation best practices are to connect control wiring (low voltage) and then connect power wiring (high voltage). Do not apply power to the indoor unit or any Multi V system component until authorized to do so by the system commissioning agent.

1. Ensure the input power is disconnected and there is no power on the power input cable.

2. Remove the knock-out plugs from the control box. Remember the communications cable and the power cable must enter the control box through different knockouts.

3. Field-install a plastic or rubber grommet in the knockout holes to prevent wire chaffing.

4. If using conduit, connect the conduit to the control box using field-provided fittings and industry best-practice procedures.

5. Separately route the power wiring and communications cables to the unit’s terminal block (see figures on the following pages). Do not route the communications cable near the power cable. Two-way and four-way cassettes feature wiring and cable paths on opposites side of the indoor unit. Provide at least three (3) to four (4) inches of slack cable at each indoor unit.

6. Connect the power wiring to the terminal block connections. Ensure the screws securely connect the wire to the terminals and are not loose.• For One-Way Cassettes: Terminal Block 1(L1) and 2(L2) connections.• For Two-Way and Four-Way Cassettes: Terminal Block L(L1) and N(L2) connections.

Page 132: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

132 | GUIDELINES

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

7. Connect the field-provided communications cable to the 3(A) and 4(B) terminal block connections. Polarity matters on the outdoor unit to indoor unit / heat recovery unit communications bus, and must be maintained throughout the entire system. Be sure to connect 3(A) terminals to A terminals and 4(B) terminals to B terminals. Refer to the next pages for indoor unit wiring connections, the Outdoor Unit Installation Manual for information regarding the outdoor unit and heat recovery unit wiring connections, or review the wiring diagrams on the applicable units.

• • Field-provided communication cable between Master ODU to IDUs / HRUs to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure

the communication cable shield is properly grounded to the Master ODU chassis only. Do not ground the ODU to IDUs / HRUs commu-nication cable at any other point. Wiring must comply with all applicable local and national codes.

8. If a remote controller is to be installed, connect the remote controller’s cable to the indoor unit’s remote controller connection. Controller connections depend on type of indoor unit being installed. Some indoor units use terminal block connections; other indoor units use Molex connections. See the wiring diagram for each specific indoor unit.

9. Connect any additional cables required for the installation such as those for the decoration panels.

APPLICATION GUIDELINESWiring Guidelines

Page 133: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

GUIDELINES | 133

Application G

uidelines

©

APPLICATION GUIDELINESWiring Guidelines

1(L1) 2(L2)3(A) 4(B)

Power SupplyHigh Voltage(208/230V)

Communications

Lock nut

Conduitmountingplate

Conduit

Indoor Unit Terminal Block

1(L1)

Power Input208-230V /

60 Hz / 1 Phase

A - - - - - -AB B

GND 12VDRY2DRY1INTERNETIDUSODU3 42(L2)

Outdoor Unit Terminal Block

Ground

Communication Line (IDU to ODU)

Figure 94: TT, TU Frame Wiring / Cable Connections.

Figure 95: Typical TT, TU Frame Wiring / Cable Routing.One-Way Cassette TT, TU Frames

Page 134: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

134 | GUIDELINES

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

APPLICATION GUIDELINESWiring Guidelines

Lock nut

Communication Cable / Remote Controller Wiring

Conduit

Power Wiring

Figure 96: Typical TS Frame Wiring / Cable Routing.

Figure 97: TS Frame Wiring / Cable Connections.

Communication Line (IDU to ODU)

Indoor Unit Terminal Block

RDYL A BBKN(L2)L(L1)

Wired RemoteController

----AB AB AB

GND 12VDRY2DRY1INTERNET

Outdoor Unit Terminal Block

IDUODU

GroundPower Input208-230V /

60 Hz / 1 Phase

Two-Way Cassette TS Frame

Page 135: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

GUIDELINES | 135

Application G

uidelines

©

Wiring GuidelinesAPPLICATION GUIDELINES

Figure 98: Typical Four-Way Cassette Wiring / Cable Routing.

Figure 99: Typical Four-Way Cassette Wiring / Cable Routing, Side View.

Figure 100: Four-Way Ceiling-Cassette Wiring / Cable Connections.

Indoor Unit Terminal Block

L(L1) N(L2) A - - AB B

GND 12VDRY2DRY1INTERNETIDUSODU

TR/TQ Frame

TM/TN Frame

L(L1) N(L2) A BRD A - - AB B

GND 12VDRY2DRY1INTERNETIDUSODU

Ground

YL BKIndoor Unit Terminal Block

Outdoor Unit Terminal Block

Outdoor Unit Terminal Block

-- - -

Ground

L(L3) N(L4)

Wired ControllerFresh Air Kit

- - - -

Power Input208-230V /

60 Hz / 1 Phase

Power Input208-230V /

60 Hz / 1 Phase

RDYL A BBK

Wired Remote Controller

Lock nut

Conduitmountingplate

Conduit

Power Supply High Voltage(208/230 V)

Power Wiring

Communication CableRemote Controller Wiring

Four-Way Cassette TR, TQ, TM, TN Frames

Page 136: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

136 | GUIDELINES

MUL

TI V

Cei

ling

Cass

ette

Indo

or U

nit E

ngin

eerin

g M

anua

l

©

Wired Controller PlacementWired controllers include a sensor to detect room temperature. To maintain comfort levels in the conditioned space, the wired controller must be installed in a location away from direct sunlight, high humid-ity, and where it could be directly exposed to cold air. Controller must be installed four (4) to five (5) feet above the floor where its display can be read easily, in an area with good air circulation, and where it can detect an average room temperature.

Do not install the wired controller near or in:• Drafts or dead spots behind doors and in corners

• Hot or cold air from ducts

• Radiant heat from the sun or appliances

• Concealed pipes and chimneys

• An area where temperatures are uncontrolled, such as an outside wall

Figure 101: Proper Location for the Wired Controller.

4 to 5 feetabove the floor

NO

NO

NO

YES

Remote Controlle r

TEMP

Remote Controlle r

TEMP

Rem ot e Cont roller

TEMP

Wired Controller PlacementAPPLICATION GUIDELINES

Optional WiFi ControlWifi control is an option for ceiling cassette IDUs. Wifi control requires the optional wifi module PWFMDD200 and the Smart ThinQ app on a compatible device such as a smartphone. Install the wifi module by connecting it to the CN_WF connector on the IDU moth-erboard. Refer to the Smart ThinQ manual for operation details.

Page 137: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

GUIDELINES | 137

Application G

uidelines

©

ABS Acrylonitrile Butadiene Styrene IDU Indoor UnitAC Air Conditioner/Alternate Current kW Kilowatts

ACP Advanced Control Platform in Aq inches waterAHU Air Handling Unit ISO International Standards Organization

ASHRAE American Society of Heating, Refrigeration, and Air Conditioning LATS LG Air Conditioning Technical Solution softwareASTM American Society for Testing and Materials LED Light Emitting DiodeAWG American Wire Gauge LEED Leadership in Energy and Environmental Design

AWHP Air-to-Air Water Heat Pump MBh Thousands BTUs per hourBLDC Brushless Digitally-Controlled MCA Minimum Circuit AmpacityBTL BACnet® Testing Laboratories mm MillimeterBtu/h British Thermal Unit per Hour MOP Maximum Overcurrent ProtectionCAA Clean Air Act OD Outside DiameterCFM Cubic Feet per Minute ODU Outdoor UnitCFR Code of Federal Regulations PI Power InputDB Dry Bulb PTAC Packaged Terminal Air Conditioner

dB(A) Decibels with “A” frequency weighting SHC Sensible Heat CapacityDPST Double-Pole Single Throw SMACNA Sheet Metal & Air Conditioning Contractors’ National Association

DX Direct expansion RPM Revolutions per MinuteEEV Electric Expansion valve TC Total Capacity

EPDM Ethylene Propylene Diene M-Class Rubber USD United States DollarEMF Electromagnetic Field UL Underwriters LaboratoriesESP External Static Pressure V VoltageETL Electric Testing Laboratories VAV Variable Air VolumeGND Ground VRF Variable Refrigerant FlowH/M/L High/Medium/Low W WattsHVAC Heating, Ventilating and Air Conditioning WB Wet Bulb

Hz Hertz wg Water GaugeID Inside Diameter

ACRONYMS

Table 59: Acronym Table.

Page 138: CEILING CASSETTE INDOOR UNIT ENGINEERING MANUAL

EM_MultiV_CeilingCassette_IndoorUnits_6_20Supersedes: EM_MultiV_CeilingCassette_IndoorUnits_12_19

EM_MultiV_CeilingCassette_IndoorUnits_6_18EM_MultiV_CeilingCassette_IndoorUnits_8_17EM_MultiV_CeilingCassette_IndoorUnits_8_16EM_MultiV_CeilingCassette_IndoorUnits_4_16

LG Electronics, U.S.A., Inc.Air Conditioning Technologies4300 North Point ParkwayAlpharetta, Georgia 30022www.lghvac.com