CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C SERIES) INSTALLATION MANUAL IM-CKBCW-0503(0)

Transcript of CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil...

Page 1: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)

CEILING CASSETTECHILLED WATER FAN COIL UNIT

(B & C SERIES)INSTALLATION MANUAL

IM-CKBCW-0503(0)

Page 2: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)
Page 3: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)

OUTLINE AND DIMENSIONS

Indoor Unit : CK15BW / 20BW / 25BW / 30BW

i

Indoor Unit : CK10CW / 15CW / 20CW

All dimensions are in mm.

All dimensions are in mm.

570

570

295

275 20

640

408

640

408

364

364

Page 4: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)

ii

Sharp edges and coil surfaces are potential locations which may cause injuryhazards. Avoid from being in contact with these places.! Caution

Les bords coupants et les surfaces du refroidisseur tubulaire présententun risque de blessure. Mieux vaut éviter le contact avec ces endroits.! Avertissement

Scharfe Kanten und Wärmetauscherflächen stellen eine Gefahrenquelle dar. JeglicherKontakt mit diesen Stellen ist zu vermeiden.! Vorsicht

Per preservarsi da eventuali ferite, evitare di toccare gli spigoli affilati e la superficiedei serpentini.! Cautela

Los Bordes afilados y la superficie del serpentín pueden producir lesiones. Evitetocarlos.! Cuidado

Острые края и поверхности змеевиков являютсяпотенциальными местами нанесения травм. Остерегайтеськонтакта с этими местами.

! Осторожно

NOTE: “Standard Marking on the cover applicable to specific models; check with label data on the unit.”

REMARQUE: “Le marquage standard qui se trouve sur la couverture s’applique à des modèles spécifiques;Vérifiez avec les données de l’étiquette placée sur l’appareil.”

HINWEIS: “Die Standardkennzeichnung auf der Abdeckhaube gilt für spezielle Modelle, daher mitEtikettdaten auf der Einheit überprüfen.”

NOTA: “ Marchio Standard in copertina riferente a modelli specifici; verificare i dati dell’etichetta checksull’unità.”

NOTA: “Marcado estándar en la tapa aplicable a modelos específicos; comprobar la información de la etiquetaen la unidad.”

ПРИМЕЧАНИЕ: “Стандартная маркировка на крышке применима к конкретным моделям;сверяйтесь с табличкой на аппарате.”

Page 5: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)

1-1

En

gli

s h

This manual provides the procedures of installation to ensure a safe and good standard of operation for the fancoil unit.Special adjustment may be necessary to suit local requirements.

Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.

INSTALLATION MANUAL

CEILING CASSETTE CHILLED WATER FAN COIL UNIT

MODEL

Reference Model Model

ACK15BW / MCK015BW / YCK15BW

ACK20BW / MCK020BW / YCK20BW

ACK25BW / MCK025BW / YCK25BW

ACK30BW / MCK030BW / YCK30BW

ACK10CW / MCK010CW / YCK10CW

ACK15CW / MCK015CW / YCK15CW

ACK20CW / MCK020CW / YCK20CW

CK15BW

CK20BW

CK25BW

CK30BW

CK10CW

CK15CW

CK20CW

Part No.: A08019018259 IM-CKBCW-0503

Page 6: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)

1-2

CONTENTS

- Outline And Dimensions page i – ii- Safety Precautions page 2- Installation Diagram page 3- Installation of Indoor Unit page 3- Electrical Wiring Connection page 6

SAFETY PRECAUTIONS

Before installing the air conditioner unit, please read the following safety precautions carefully.

! CautionPlease take note of the following important points when installing.

• Do not install the unit where leakage of flammable gas may occur.

If water leaks and accumulates around the unit, it may cause fire ignition.

• Ensure that the drainage piping is connected properly.

If the drainage piping is not connected properly, it may cause water leakage which will dampen thefurniture.

• Ensure that the units panel is closed after service or installation.

Unsecured panels will cause the unit to operate noisily.

- Indicator Lights page 9- Overall Checking page 9- Auto Random Re-Start Function page 9- Service and Maintenance page 10- Troubleshooting page 10

IMPORTANTDO NOT INSTALL OR USE THE FAN COIL UNIT IN A LAUNDRY ROOM.

! Warning• Installation and maintenance should be performed by qualified persons who are familiar with local code and

regulation, and experienced with this type of appliance.

• All field wiring must be installed in accordance with the national wiring regulation.

• Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring workaccording to the wiring diagram.

• The unit must be GROUNDED to prevent possible hazard due to insulation failure.

• All electrical wiring must not touch the refrigerant piping or any moving parts of the fan motors.

• Confirm that the unit has been switched OFF before installing or servicing the unit.

Page 7: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)

1-3

En

gli

s h

INSTALLATION DIAGRAM

Drain Hose

Front Panel

Air Filter(behind the grille)

Air Discharge Louver

IR ReceiverLED Light

Water Piping

Air Intake

Air Discharge Nozzle

Air Intake

Preliminary Site Survey

• Electrical supply and installation is to conform to local authority's (e.g. National Electrical Board) codes and regulations.• Voltage supply fluctuation must not exceed +10% of rated voltage. Electricity supply lines must be independent of welding

transformers which can cause high supply fluctuation.• Ensure that the location is convenient for wiring, piping and drainage.• The indoor unit must be installed in such that is free from any obstacles in path of cool air discharge and warm air return,

and must allow spreading of air throughout the room (near the center of the room).• Must be provide clearance for the indoor unit from the wall and obstacles as shown in the figure.

• The installation place must be strong enough to support a load 4 times the indoor unit weight to avoid amplifying noise andvibration.

• The installation place (handing ceiling surface) must be assuring levelness and the height in the ceiling is 350 mm or more.• The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).

INSTALLATION OF INDOOR UNIT

Max

. 0.3

m

Min. 0.5 mMin. 0.5 m Min. 0.5 m

Min

. 1.0

m

Max

. 3.0

m

Floor

Obstacle

Bea

m

Outdoor Unit

Indoor Unit

WirelessRemote Control

orWired Remote Control

Netware - 2or

SLM - 3

Air Intake Grille

Page 8: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)

1-4

Unit Installation

• Measure and mark the position for the hanging rod. Drillthe hole for the angle nut on the ceiling and fix the hangingrod.

• The installation template is extended according totemperature & humidity. Check on dimensions in use.

• The dimensions of the installation template are the sameas those of the ceiling opening dimensions.

• Before ceiling laminating work is completed, be sure tofit the installation template to the indoor unit.

NOTEBe sure to discuss the ceiling drilling work with theinstallers concerned.

Ceiling board opening

Drain Piping Work

• Drain pipe must be in downward gradient for smoothdrainage.

• Avoid installing the drain pipe in up and down slope toprevent reversed water flow.

• During the drain pipe connection, be careful not to exertextra force on the drain connector at indoor unit.

• The outside diameter of the drain connection at the flexibledrain hose is 20 mm.

• Be sure to execute heat insulation (polyethylene foam withthickness more than 8.0 mm) on the drain piping to avoidthe condensed water dripping inside the room.

Indoor Unit

Pipe Clamp

Good Bad

Unit Hanging

• Confirm the pitch of the hanging rod.

• Hold the unit and hang it on the hanging rod with the nutand washer.

• Adjust the unit height to 35.0 mm between the indoor unitbottom surface and the ceiling surface.

• Confirm with a level gauge that the unit is installedhorizontally and tighten the nut and bolt to prevent unitfalling and vibration.

• Open the ceiling board along the outer edge of the paperinstallation template.

CeilingBoard

35.0 mm

Indoor Unit

Page 9: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)

1-5

En

gli

s h

Drain Test

NOTEThis indoor unit uses a drain pump for condensed waterdrainage. Install the unit horizontally to prevent waterleakage or condensation around the air outlet.

Main Drain Pipe

Feed Water

FlexibleDrain Hose

• Connect the main drain pipe to the flexible drain hose.• Feed water from flexible drain hose to check the piping

for leakage.• When the test is completed, connect the flexible drain hose

to the drain connector on the indoor unit.

NOTEInstall the front frame panel firmly to prevent cool airleakage which will cause condensation and water dripping.

OPEN

• Be sure to remove the installation template before install-ing the front panel.

• Open the air intake grille by pulling back the catchers andremoving it together with filter from panel.

• Install the front frame panel onto the indoor unit by 4screws and tighten it completely to prevent cool air leak-age.

• Connect the LED wire and air swing wire to the indoorunit.

Panel Installation

Indoor unitcoolair

ceiling board

Panel

air leak

coolair

air leak

ceiling board

Panel

Good Installation Bad Installation

FromFrontPanel

LED Wire

Air Swing Wire

FromControlBox

Screw

Air intake grille installation

• Before installing the air intake grille, be sure to fix theionizer filter to the air filter.

• Install the air intake grille together with the air filter to thefront panel.

• The grille can be fit in any direction, when selectingdirection, the ceiling design and grille operability shouldbe considered.

• If the unit comes with ionizer filter (optional item), makesure to fix the ionizer filter to the air filter before installingthe air intake grille.

• Fix the ionizer filter to the air filter with the black side ontop and white side at bottom.

• Carefully clip on the ionizer filter frame.

Frame

Ionizer

Filter

Page 10: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)

1-6

ELECTRICAL WIRING CONNECTION

This is a proposed wiring connection. It may change subject to the chiller unit and must comply with the local and nationalcode and regulations.

MODEL : CK15BW - CK30BW

3WV3WV

X1 X2 X3

3WV

R

COMPCOMPL/L1 N/L2 N/L2COMP

S

TN

CHILLER

FCU 1 FCU 2 FCU 3

200-240V/1 /50Hz208-230V/1 /60Hz

3WV Solenoid Valve for 3 way valve

Relay (220-240V, 10A)X1, X2, X3

L/L1 N/L2 N/L2 L/L1 N/L2 N/L2

MODEL : CK10CW - CK20CW

X1 X2 X3

3WV 3WV 3WV

R

L/L1 N/L2 N/L2COMP

S

T

N

CHILLER

FCU 1

L/L1 N/L2 N/L2COMP

FCU 3

L/L1 N/L2 N/L2COMP

FCU 2

200-240V/1 /50Hz 208-230V/1 /60Hz

3WV Solenoid Valve for 3 way valve

Relay (220-240V, 10A)X1, X2, X3

Page 11: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)

1-7

En

gli

s h

L/L

1N

/L2

N/L

2C

OM

P

SO

LE

NO

ID V

ALV

E

PAR

T N

O :

08

02 4

063

847

TO C

HIL

LE

R

L

1PH

AS

E

N

200

/ 240

VAC

50H

z

E

208

/ 230

VAC

60H

z O

R

GR

EE

N/Y

EL

LO

W

GR

EE

N/Y

EL

LO

WB

LU

E

WH

ITE

RE

D

RE

D

BL

UE

BL

AC

K

PO

WE

RB

OA

RD

BR

OW

N (

FM

)

OR

AN

GE

(F

L)

YE

LL

OW

(F

H)

BL

UE

TR

AN

SF

OR

ME

R

LIV

E

LO M

ED HI

WTP

A

G VALV

E

SW

ING

MO

TOR

WA

TE

RP

UM

P

LE

VE

LS

WIT

CH

GR

EE

N/Y

EL

LO

W

TO W

IRE

D O

R W

IRE

LE

SS

CO

NT

RO

LL

ER

GR

EE

N/Y

EL

LO

W

JVLV

T.F

UL

L

MA

IN B

OA

RD

I/D C

OIL

SE

NS

OR

TH

ER

MIS

TOR

WIRED CONTROLLER

WIRELESS CONTROLLER

VALV

E

HE

AT

BLAC

BLACK

GREEN/YELLOW

FAN

MO

TOR

AC

LC

ML

C

WHITE

RED

N2

N1

MODEL : CK15BW / 20BW / 25BW / 30BW

Page 12: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)

1-8

L1P

HA

SE

N22

0 / 2

40VA

C 5

0Hz

OR

E20

8 / 2

30VA

C 6

0Hz

L/L

1N

/L2

N/L

2C

OM

P

BL

UE

RE

TU

RN

AIR

SE

NS

OR

IND

OO

R C

OIL

SE

NS

OR

RO

OM

IDOD

HEAT

JH

CN3

JVLV

CN

6

LO

W

N2

ME

D

HIGH

AS

VALVE

WTP

N1

L1

TR

AN

SF

OR

ME

RC

N4

FL

OA

T S

WIT

CH

WIR

ED

OR

W

IRE

LE

SS

R

EM

OT

EC

ON

TR

OL

LE

R

YE

LL

OW

FH

BR

OW

NF

M

OR

AN

GE

FL

BLACK

WHITE

RED AC

IC

MC

FAN

MO

TOR

PURPLE

RED

BLACK

(TO

OU

TD

OO

R U

NIT

)BLUE

BLUE

DP

AS

G/Y

G/Y

BL

AC

K

RE

D

(PO

WE

R S

UP

PLY

FR

OM

IND

OO

R U

NIT

)PA

RT

NO

: 08

02

4 06

6429

MODEL : CK10CW / 15CW / 20CW

Page 13: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)

1-9

En

gli

s h

OVERALL CHECKING

• Ensure the following, in particular:-1) The unit is mounted solidly and rigid in position.2) Piping and connections are leak proof after charging.3) Proper wiring has been installed.

• Drainage check – pour some water into left side of drain pipe (drainage is at the right side of the unit).• Test run:

1) Conduct a test run after water drainage test and gas leakage test.2) Check the following items:-

a. Is the electric plug firmly inserted into the socket?b. Is there any abnormal sound from the unit?c. Is there any abnormal vibration on the unit itself or piping?

d. Is the drainage of water smooth?

NOTE• The installation guide above covers only the fan coil unit. For installation of outdoor (mini chiller etc) please refer to the

installation guide for such unit.• The installation of fan coil unit may vary according to the type of outdoor unit.• Installation must be done by qualified personnel who are familiar with this type of product.

INDICATOR LIGHTS

Remote ControlWhen there is infrared remote control operating signal, the signal receiver on indoor unit will made a <beep> for signalacceptance confirmation.

Other LED

Fan blinks

Sleep blinks

Cool & Fan blinks

Cool & Dry blinks

Cool blinks

Seven Segments

E1 blinking

E2 blinking

E6 blinking

E4 blinking

E5 blinking

Operation LED

blinks 4 times

blinks 4 times

blinks 2 times

blinks 3 times

blinks 1 time

Faulty Indication

Room Sensormissing

Indoor Coil Sensormissing

Pump fault

Pipe WaterTemperature poor

Pipe WaterTemperature fault

If there is a power cut when the unit is operating, it will automatically resume the same operating mode when the power isrestored. (Applicable only to units with this feature)

AUTO RANDOM RE-START FUNCTION

Wire termination to the controller board is as shown in the wiring diagrams.The standard controller board (W1V3) comes with a VALVE (JVLV) jumper and a HEAT (OD) jumper. The system mustbe configured as the jumper selection listed below:

√ Jumper Remained × Jumper Removed

Example: If the unit is running “Heatpump Mode & Valveless Application”, remain the HEAT jumper while removing theVALVE jumper.

HEAT Jumper VALVE JumperCooling Mode & Valve Application × √Cooling Mode & Valveless Application × ×Heatpump Mode & Valve Application √ √Heatpump Mode & Valveless Application √ ×

! CautionDisconnect the live power supply to the unit before attempting to connect the wiring.

Page 14: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)

1-10

Causes / Action

- Protection against frequent starting. Wait for 3 to 4minutes for the compressor to start operating.

- Power failure, or the fuse need to be replaced.- The power plug is disconnected.- It is possible that your delay timer has been set incorrectly.- If the fault persist after all these verifications, please

contact the unit installer.

- The air filter is dirty.- The doors or windows are open.- The air suction and discharge are clogged.- The regulated temperature is not high enough.

- Odors may be caused by cigarettes, smoke particles,perfume etc. which might have adhered onto the coil.

- This is caused by air humidity after an extended longperiod of operation.

- The set temperature is too low, increase the temperaturesetting and operate the unit at high fan speed.

- Switch off unit and call dealer.

Fault

1. The compressor does not start operate after 3 minutesfrom starting the air conditioner unit.

2. The fan coil unit does not operate.

3. The airflow is too low.

4. Discharge airflow has bad odor.

5. Condensation on the front air grille of the indoor unit.

6. Water flowing out from the fan coil unit.

When any malfunction of the air conditioner unit is noted, immediately switch off the power supply to theunit. Check the following fault conditions and causes for some simple troubleshooting tips.

TROUBLESHOOTING

If the fault persists, please call your local dealer / serviceman.

SERVICE AND MAINTENANCE

Indoor Air Filter 1. Remove any dust adhere on the filter by using a vacuum cleaner orwash in lukewarm water (below 40oC) with neutral cleaning detergent.

2. Rinse the filter well and dry before placing it back onto the unit.3. Do not use gasoline, volatile substances or chemical to clean the filter.

Indoor Unit 1. Clean any dirt or dust on the grille or panel by wiping it off with softcloth soaked in lukewarm water (below 40oC) with neutral detergentsolution.

2. Do not use gasoline, volatile substances or chemical to clean the in-door unit.

At least onceevery 2 weeks.

More frequentlyif necessary.

At least onceevery 2 weeks.

More frequentlyif necessary.

Service Parts Maintenance Procedures Period

! Warning• Disconnect from the main power supply before servicing the air conditioner unit.• DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result

in fire hazards.

! CautionDo not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic panel to melt ordeform as a result of the excessive heat.

! CautionBefore turning off the power supply, set the remote controller's ON/OFF switch to the “OFF” position to prevent thenuisance tripping of the unit.

If this is not done, the unit's fans will start turning automatically when power resumes, posing a hazard to servicepersonnel or the user.

Page 15: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)
Page 16: CEILING CASSETTE CHILLED WATER FAN COIL UNIT (B & C … · ceiling cassette chilled water fan coil unit (b & c series) installation manual im-ckbcw-0503(0)

OYL MANUFACTURING COMPANY SDN. BHD.

JALAN PENGAPIT 15/19, P.O. BOX 7072, 40702 SHAH ALAM, SELANGOR DARUL EHSAN, MALAYSIA.

• In the event that there is any conflict in the interpretation of this manual and any translation of the same in any language,the English version of this manual shall prevail.

• The manufacturer reserves the right to revise any of the specification and design contain herein at any time without priornotification.

• En cas de désaccord sur l’interprétation de ce manuel ou une de ses traductions, la version anglaise fera autorité.

• Le fabriquant se réserve le droit de modifier à tout moment et sans préavis la conception et les caractéristiques techniquesdes appareils présentés dans ce manuel.

• Im Falle einer widersprüchlichen Auslegung der vorliegenden Anleitung bzw. einer ihrer Übersetzungen gilt die Ausführungin Englisch.

• Änderungen von Design und technischen Merkmalen der in dieser Anleitung beschriebenen Geräte bleiben dem Herstellerjederzeit vorbehalten.

• Nel caso ci fossero conflitti nell’interpretazione di questo manuale o delle sue stesse traduzioni in altre lingue, la versionein lingua inglese prevale.

• Il fabbricante mantiene il diritto di cambiare qualsiasi specificazione e disegno contenuti qui senza precedente notifica.

• En caso de conflicto en la interpretación de este manual, y en su traducción a cualquier idioma, prevalecerá la versióninglesa.

• El fabricante se reserva el derecho a modificar cualquiera de las especificaciones y diseños contenidos en el presentemanual en cualquier momento y sin notificación previa.

• В случае противоречия перевода данного руководства с другими переводами одного и того же текста,английский вариант рассматривается как приоритетный.

• Завод-изготовитель оставляет за собой право изменять характеристики и конструкцию в любое времябез предварительного уведомления.