Application The CB780/CB784 Burner Control is a microprocessor

based integrated control for gas, oil or combination fuel single burner applications. The CB780/CB784 consists of a Relay Module, Subbase, Amplifier, Keyboard Display Mod- ule (CB780) and Purge Card. Options include Keyboard Display Module (CB784), Personal Computer Communi- cation Interface, ControlBus Module, Remote Display Mounting, First Out Expanded Annunciator, and Combus- tion System Management Software.

The CB780/CB784 is programmed to provide safety, functional capability and features beyond the capacity of conventional controls. The CB780/CB784 is Underwriters Laboratories Inc. listed, Canadian Standards Association certified, Factory Mutual approved, Federal Communica- tions System and Canadian Department of Communication approved.

Functions provided by the CB780/CB784 include auto- matic burner sequencing, flame supervision, system status indication, historical files (total cycles, total hours, last six lockouts), system or self-diagnostics and troubleshooting aids.

TheCB780/CB784CommunicationInterfaceoptionpro- vides local and remote monitoring and diagnostics of the CB780KB784 by using an DM@ equivalent personal com- puter and MicrosoftB WindowsTM 3.0 (or higher) software.

The First Out Expanded Annunciator provides system status indication for up to 21 points for system and self- diagnostics beyond standard CB780/CB784 functions.

The CB780KB784 Remote Keyboard Display Module mounting provides system status monitoring from mul- tiple locations.

FEATURES Dynamic self-check logic. Dynamic safety relay test. Tamper resistant timing and logic. Dynamic input check. First out annunciation and system diagnostics are pro- vided by a 40 character vacuum fluorescent display (VFD) located on the Keyboard Display Module (stan- dard with CB780, optional with CB784). Five LEDs for system sequence status. Five function Ruf les t switches. Nonvolatile memory (CB780KB784 retains history files and sequencing status after loss of power). Interchangeable plug-in flame amplifiers. Dependable, long term operating microcomputer technology. Communication interface capability. Local or remote annunciation of CB780/CB784 shut- downs. First out expanded annunciation with 24 LEDs for limit or interlock status with optional CB783. Application flexibility. Burner controller data. - Sequence status. - Sequence time. - Hold status. - Lockout/alarm status.

CB-7836

- Flame signal strength. - Expanded annunciator status. - Total hours of operation. - Total cycles of operation. - Fault history of the six most recent faults.

- Fault message and code. - Sequence status at the time of fault. - Sequence time of the fault. - Expanded annunciator data at the time of fault. - Cycles of operation at the time of fault. - Hours of operation at the time of fault.

- Diagnostic information. - Relay module type. - Software revision and version. - Odoff status of all digital inputs/outputs. - Status of configuration jumpers. - Selected prepurge time. - Flame failure response time. - Flame amplifier type. - Manufacturing code.

Off cycle flame signal check. Preignition interlock check. Airflow switch check. Configuration jumpers for sequence timings and tests. Interchangeable purge timers.

Specifications ELECTRICAL RATINGS:

Voltage and Frequency: Relay Module:

120 Vac (+lo/-15%). 50 or 60 Hz (+/-lo%).

Display Module:

Expanded Annunciator: 120 Vac (+lo/-15%). 50 or 60 Hz

Power Dissipation:

13 Vdc (+lo/-15%).

Relay Module: 10 watts maximum. Expanded Annunciator: 5 watts maximum. Keyboard Display Module: 3 watts maximum. Communication Interface: 5 watts maximum. Maximum Total Connected Load: 2000 VA.

CB780KB784:

Total System:

Fusing:

15A maximum, type FRN or equivalent.

20A maximum, type FRN or equivalent.

DIMENSIONS: 5 x 5 x 5-1/4 in. (Relay Module, Ampli- fier, Keyboard Display Module, Purge Timer and panel type mounting subbase).

ENVIRONMENTAL RATINGS: Ambient Temperature:

Operating -40°F to 140°F. Storage -40°F to 150°F.

Humidity: 85% RH continuous, noncondensing.

2

APPROVALS: Underwriters Laboratories Inc. listed. Canadian Standards certified.

Factory Mutual approved. Federal Communications Commission. Canadian Department of Communication.

Fig. 1-Single CB-HAWK or CB780 local and remote communications.

CB-HAWK CHASSIS AND PROGRAM MODULE

CB-HAWK KEYBOARD

I ,

1 1000 FT. MAXIMUM CONTROL BUS

COMMUNICATIONS 50' MAXIMUM INTERFACE

COMMUNICATIONS

RJll CONNECTOR

PHONE LINES

300 OR 1200 BAUD

M7645

3 CB-7836

Fig. 2-Multiple CB-HAWK or CB780 communications.

L

L

L

CB-HAWK CHASSIS AND

CB-HAWK KEYBOARD P R O G R ~ M . M ~ D U L E

M7646

Cleave rooks" Performance Proven Worldwide