Catalogue No: IMAX20 MON RLY 1PH O/ I 2-20A AC 2WIRE SELF ...
Transcript of Catalogue No: IMAX20 MON RLY 1PH O/ I 2-20A AC 2WIRE SELF ...
Timers and Control Relays > Monitoring Relays > Voltage, Current, Phase and Power Factor Monitoring Relays > CarloGavazzi Voltage / Current / Phase and Power Monitoring > Current Monitoring Relays > Self-Powered Through-hole
MON RLY 1PH O/ I 2-20A AC 2WIRE SELF POWER NPN/PNP NO OUT
IMAX20Catalogue No:
· Comprehensive range of relays for monitoring of phase loss, incorrect phase sequence, phase unbalance, over / under current, over / under load, over / under frequency, and over / under voltage for various application requirements
· Range available in a variety of package sizes and mounting (DIN or Plug-in) to suit various preferences
· International certifications including ISO 9001 with wide install base ensuring delivery of a quality tested product
Representative Photo Only(actual product may vary based on configuration selections)
Current monitoring relay, overcurrent 2 - 20A AC
SPECIFICATIONS
Product Series
Component Type Timers and Control relays
Signal Type(s)
Measurement Range(s)
Voltage Drop, Output(s)
Output Voltage, DC, Max
Rated Frequency
Configuration Method
Operational Frequency, Min
Operational Frequency, Max
Details, Output(s)
Digital Output Type
IΔn, Leakage Current, Max
Current, Overload Capacity, Continuous
Current, Overload Capacity, 30s (rms)
Output Current, Max (rms)
Terminal Type
Mounting
Material, Body / Housing
IP Rating
Indicator Type
Tightening Torque, Max
Pollution Degree
Operating Temperature, Min
Operating Temperature, Max
Height
Width
Depth
DIA
Monitoring Relay
AC: 1-Phase
2 ... 20A
2.5 V
40 V DC max
50 Hz
DIP-Switch
45 Hz min
400 Hz max
NPN-PNP open collector
NO Relay type
0.1 mA
0.04 kA
0.2 kA
0.1 A max, rms
Screw Terminal(s)
DIN-35 Rail Mount
Noryl material
IP20
LED
0.5 Nm
3
-20 °C min
60 °C max
81 mm
17.5 mm
67.2 mm
Page 1 of 316 September 2021,1300 NHP NHP | nhp.com.au | 0800 NHP NHP | nhp-nz.com
IMAX20 DatasheetNHP Electrical Engineering Products
Timers and Control Relays > Monitoring Relays > Voltage, Current, Phase and Power Factor Monitoring Relays > CarloGavazzi Voltage / Current / Phase and Power Monitoring > Current Monitoring Relays > Self-Powered Through-hole
MON RLY 1PH O/ I 2-20A AC 2WIRE SELF POWER NPN/PNP NO OUT
IMAX20Catalogue No:
Weight
Standards Compliance
Certifications
0.08 kg
EN 60255-1EN 61000-6-2EN 61000-6-3EN 50022DIN 43880
CECSAUL
REFERENCES
Installation Guide: IMAX20_Installation Instructions
User Manual: -
Manufacturer Datasheet: IMAX20_Manufacturer Datasheet
Manufacturer Catalogue& Product Selection:
-
Supplier Declaration ofConformity:
-
IECEx Certificate -
Dimension Diagram
Page 2 of 316 September 2021,1300 NHP NHP | nhp.com.au | 0800 NHP NHP | nhp-nz.com
IMAX20 DatasheetNHP Electrical Engineering Products
Timers and Control Relays > Monitoring Relays > Voltage, Current, Phase and Power Factor Monitoring Relays > CarloGavazzi Voltage / Current / Phase and Power Monitoring > Current Monitoring Relays > Self-Powered Through-hole
MON RLY 1PH O/ I 2-20A AC 2WIRE SELF POWER NPN/PNP NO OUT
IMAX20Catalogue No:
Connection / Wiring Diagram
Technical Diagram
Page 3 of 316 September 2021,1300 NHP NHP | nhp.com.au | 0800 NHP NHP | nhp-nz.com
IMAX20 DatasheetNHP Electrical Engineering Products