Catalogue - Multi C120

download Catalogue - Multi C120

of 8

Transcript of Catalogue - Multi C120

protect circuit protection

C120N circuit-breakers B, C and D curves EN 60898/EN 61009: 10000 IEC 60947-2: 10 kA# protection of cables against overloads and short-circuits in final distribution # manual control and isolation # earth leakage protection when combined with a Vigi C120 module without temperature derating: compliance with standard: EN 61009 (refer to pages 90265/2) # remote tripping, indication, by adding auxiliaries common to the entire C60/C120 range (refer to pages 90142/2).

function

description

Technical data # current rating: 63 to 125 A # voltage rating Ue max.: 440 V AC # insulation voltage Ui: 500 V # impulse withstand voltage Uimp: 6 kV # compliance with standard EN 60898: devices accessible by unexperienced persons # breaking capacity: 5 as in EN 60898type 1, 2, 3, 4P voltage (V) 230400 breaking cap. Icn (A) 10000

5 as in IEC 60947.2 (Icu)voltage breaking cap. (V) Icu (kA) 1P 130 20 230240 10 400415 3 (1) 2, 3, 4P 230240 20 400415 10 440 6 (1) breaking capacity under 1 pole with IT isolated neutral system (case of double fault) type

- degree of protection IP2 - tightening of wide cross-section cables - pull-out withstand of cables - automatic guiding of cable into the correct position # markers: 5 4 marker clips next to the upstream terminal 5 label holder on handle (2P, 3P, 4P) # degree of pollution: 3 (for use in an industrial environment) # degree of protection: 5 open or surface mounted device: IP2 5 in a Pragma or Prisma enclosure: IP4 (IPxxD)

# approval: IMQ # connection: 5 flexible cables: 1.5 to 35 mm2 5 rigid cables: 1 to 50 mm2 5 terminals ensure:

# service breaking capacity Ics =75 % Icu # positive break indication # fast closing ensures simultaneous closing of poles # electrical durability: 5 63 A: 10000 cycles (O-C) 5 80125 A: 5000 cycles (O-C) # limitation class: 3 # mechanical durability: 20000 cycles (O-C) # bistable fixing pawl: simplifies disassembly # weight (g):1P 205 2P 410 3P 615 4P 820

# magnetic trip units operate between 3 and 5 In # protection of very long cables # protection of networks supplied by generators # magnetic trip units operate between 5 and 10 In # protection of standard networks # magnetic trip units operate between 10 and 14 In # protection of circuits that supply high inrush current loads: transformers, motors, etc.

B curve

C curve

D curve

90260E.fm/2

Updated: 5/07/01

Schneider Electric

protect circuit protection

C120N circuit-breakers B curve EN 60898/EN 61009: 10000 IEC 60947-2: 10 kAtype rating (A) catalogue number width in mod. of 9 mm

catalogue numbers

B curve C120N1P 63 80 100 125 18340 18341 18342 18343 3 3 3 3

1

218340

2P

1 3

63 80 100 125

18344 18345 18346 18347

6 6 6 6

2 418344

3P 1 3 5

63 80 100 125

18348 18349 18350 18351

9 9 9 9

2 4 618349

4P 1 3 5 7

63 80 100 125

18352 18353 18354 18355

12 12 12 12

2 4 6 818355

Schneider Electric

Updated: 5/07/01

90260E.fm/3

protect circuit protection

C120N circuit-breakers C curve EN 60898/EN 61009: 10000 IEC 60947-2: 10 kAtype rating (A) catalogue number width in mod. of 9 mm

catalogue numbers

C curve C120N1P 63 80 100 125 18356 18357 18358 18359 3 3 3 3

1

218356

2P

1 3

63 80 100 125

18360 18361 18362 18363

6 6 6 6

2 418360

3P 1 3 5

63 80 100 125

18364 18365 18367 18369

9 9 9 9

2 4 618365

4P 1 3 5 7

63 80 100 125

18371 18372 18374 18376

12 12 12 12

2 4 6 818377

90260E.fm/4

Updated: 5/07/01

Schneider Electric

protect circuit protection

C120N circuit-breakers D curve EN 60898/EN 61009: 10000 IEC 60947-2: 10 kAtype rating (A) catalogue number width in mod. of 9 mm

catalogue numbers

D curve C120N1P 63 80 100 125 18378 18379 18380 18381 3 3 3 3

1

218378

2P

1 3

63 80 100 125

18382 18383 18384 18385

6 6 6 6

2 418385

3P 1 3 5

63 80 100 125

18386 18387 18388 18389

9 9 9 9

2 4 618389

4P 1 3 5 7

63 80 100 125

18390 18391 18392 18393

12 12 12 12

2 4 6 8

18393

additional informationSchneider Electric

auxiliaries: page 92142/2 accessories: page 91903/2 Vigi module: page 90265/2 discrimination table: page 92511/2

dimensions: page 90148/2 derating: page 92515/2 tripping curves: page 90180/2

Updated: 5/07/01

90260E.fm/5

protect circuit protection

C120H circuit-breakers B, C and D curves EN 60898/EN 61009: 15000 IEC 60947-2: 15 kA# protection of cables against overloads and short-circuits in final distribution # manual control and isolation # earth leakege protection when combined with a Vigi C120 module without temperature derating: compliance with standard: EN 61009 (refer to pages 90265/2) # remote tripping, indication, by adding auxiliaries common to the entire C60/C120 range (refer to pages 90142/2). # approval: IMQ # connection: 5 flexible cables: 1.5 to 352 mm2 5 rigid cables: 1 to 50 mm 5 terminal ensure:

function

description

Technical data # current rating: 10 to 125 A # max. voltage rating Ue: 440 V AC # insulation voltage Ui: 500 V # impulse withstand voltage Uimp : 6 kV # compliance with standard EN 60898: devices accessible by unexperienced persons # breaking capacity: 5 as EN 60898type 1, 2, 3, 4P voltage (V) 230400 breaking cap. Icn (A) 15000

5 as IEC 60947-2 (Icu)voltage breaking cap. (V) Icu (kA) 1P 130 30 230240 15 400415 4.5 (1) 2, 3, 4P 230240 30 400415 15 440 10 (1) breaking capacity under 1 pole with IT isolated neutral system (case of double fault) type

- degree of protection IP2 - tightening of wide cross-section cables - pull-out withstand of cables - automatic guiding of cable into the correct position # markers: 5 4 marker clips next to the upstream terminal 5 label holder on handle (2P, 3P, 4P) # degree of pollution: 3 (for use in an industrial environment) # degree of protection: 5 open or surface mounted device: IP2 5 in a Pragma or Prisma enclosure: IP4 (IPxxD)

# service breaking capacity Ics =50 % Icu # positive break indication # fast closing ensures simultaneous closing of poles # electrical durability: 5 63 A: 10000 cycles (O-C) 5 80125 A: 5000 cycles (O-C) # limitation class: 3 # mechanical durability: 20000 cycles (O-C) # bistable fixing pawl: simplifies diasassembly # weight (g):1P 205 2P 410 3P 615 4P 820

# magnetic trip units operate between 3 and 5 In # protection of very long cables # protection of networks supplied by generators

B curve

# magnetic trip units operate between 5 and 10 In # protection of standard networks # magnetic trip units operate between 10 and 14 In # protection of circuits that supply high inrush current loads: transformers, motors, etc...

C curve

D curve

90261E.fm/2

Updated: 5/07/01

Schneider Electric

protect circuit protection

C120H circuit-breakers B,C and D curves EN 60898/EN 61009: 15000 IEC 60947-2 : 15 kAtype rating (A) catalogue number width in mod. of 9 mm

catalogue numbers

B curve C120H1P 10 16 20 25 32 40 50 63 80 100 125 18394 18395 18396 18397 18398 18399 18400 18401 18402 18403 18404 3 3 3 3 3 3 3 3 3 3 3

1

218394

2P

1 3

2 418412

10 16 20 25 32 40 50 63 80 100 125

18405 18406 18407 18408 18409 18410 18411 18412 18413 18414 18415

6 6 6 6 6 6 6 6 6 6 6

3P

1 3 5

2 4 618424

10 16 20 25 32 40 50 63 80 100 125

18416 18417 18418 18419 18420 18421 18422 18423 18424 18425 18426

9 9 9 9 9 9 9 9 9 9 9

4P

1 3 5 7

2 4 6 818437

10 16 20 25 32 40 50 63 80 100 125

18427 18428 18429 18430 18431 18432 18433 18434 18435 18436 18437

12 12 12 12 12 12 12 12 12 12 12

Schneider Electric

Updated: 5/07/01

90261E.fm/3

protect circuit protection

C120H circuit-breakers B,C and D curves EN 60898/EN 61009: 15000 IEC 60947-2 : 15 kAtype rating (A) catalogue number width in mod. of 9 mm

catalogue numbers

C curve C120H1P 10 16 20 25 32 40 50 63 80 100 125 18438 18439 18440 18441 18442 18443 18444 18445 18446 18447 18448 3 3 3 3 3 3 3 3 3 3 3

1

218445

2P

1 3

2 418456

10 16 20 25 32 40 50 63 80 100 125

18449 18450 18451 18452 18453 18454 18455 18456 18457 18458 18459

6 6 6 6 6 6 6 6 6 6 6

3P

1 3 5

2 4 618468

10 16 20 25 32 40 50 63 80 100 125

18460 18461 18462 18463 18464 18465 18466 18467 18468 18469 18470

9 9 9 9 9 9 9 9 9 9 9

4P

1 3 5 7

2 4 6 818481

10 16 20 25 32 40 50 63 80 100 125

18471 18472 18473 18474 18475 18476 18477 18478 18479 18480 18481

12 12 12 12 12 12 12 12 12 12 12

90261E.fm/4

Updated: 5/07/01

Schneider Electric

protect circuit protection

C120H circuit-breakers B,C and D curves EN 60898/EN 61009: 15000 IEC 60947-2 : 15 kAtype rating (A) catalogue number width in mod. of 9 mm

catalogue numbers

D curve C120H1P 10 16 20 25 32 40 50 63 80 100 125 18482 18483 18484 18485 18486 18487 18488 18489 18490 18491 18492 3 3 3 3 3 3 3 3 3 3 3

1

218482

2P

1 3

2 418500

10 16 20 25 32 40 50 63 80 100 125

18493 18494 18495 18496 18497 18498 18499 18500 18501 18502 18503

6 6 6 6 6 6 6 6 6 6 6

3P

1 3 5

2 4 618514

10 16 20 25 32 40 50 63 80 100 125

18504 18505 18506 18507 18508 18509 18510 18511 18512 18513 18514

9 9 9 9 9 9 9 9 9 9 9

4P

1 3 5 7

2 4 6 818525

10 16 20 25 32 40 50 63 80 100 125

18515 18516 18517 18518 18519 18520 18521 18522 18523 18524 18525

12 12 12 12 12 12 12 12 12 12 12

additional informationSchneider Electric

auxiliaries: page 92142/2 accessories: page 91903/2 Vigi module: page 90265/2 discrimination table: page 92511/2

dimensions: page 90148/2 derating: page 92515/2 tripping curves: page 90180/2

Updated: 5/07/01

90261E.fm/5