Catalogo Mcset 1-17.5kv2005vacio

50
Medium voltage switchgear Withdrawable vacuum circuit-breaker 1 to 17.5 kV 2005 Catalogue MCset Web enabled Power & Control

Transcript of Catalogo Mcset 1-17.5kv2005vacio

Page 1: Catalogo Mcset 1-17.5kv2005vacio

Medium voltage switchgearWithdrawable vacuumcircuit-breaker1 to 17.5 kV

2005Catalogue

MCsetWeb enabledPower & Control

Page 2: Catalogo Mcset 1-17.5kv2005vacio

1

MCset range1 to 17.5 kV

Contents

Presentation 2

MCset range 8Presentation 8Technical characteristics 10Operating conditions 11Protection of people 12Motor protection and control 13Choice of functional units 14

Cubicle description 16AD type cubicles incomer and feeder 16CL - GL type cubicles line-up bussectioning 17TT type cubicles metering and busbar earthing 18DI type cubicles switch-fuse feeder 19Motorpact transition cubicle 20

Protection, monitoring and control 22Thermal diagnosis 22The protection system - Sepam range 23Sepam 2000 - Sepam 100 24Sepam series 20, series 40, series 80 26Instrument transformers 28

Switchgear 32Withdrawable parts 32Evolis circuit-breaker 34Vacuum type contactor 38Withdrawable part extraction 40

Installation 41Implementation examples 41Connections 42

Appendices 44Cubicle equipment 44Current transformers (Selection guide) 45

A few references 46

Personal notes 47

Page 3: Catalogo Mcset 1-17.5kv2005vacio

2

Presentation 0Field of application

MCset adapts to all electrical power distribution requirements from 1 to 17.5 kVMCset is an indoor, metal switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations.b for all your applications:

v industrial process substations,

v infrastructure supply substations.

b MCset offers you:

v pre-engineered and adaptable solutions tailored to your specific requirements,

v significantly reduced maintenance,v local support centres throughout the world.

b MCset gives you the advantages of:v continuity of service for your networks,

v enhanced safety for your staff and operations,

v optimized investment throughout the life of your installation,v the possibility of integrating your medium voltage switchboard in a monitoring and control system.

An enhanced offer with vacuum type switchgear The MCset offer is further enhanced to include a vacuum type circuit-breaker (Evolis range) and contactor.

This switchgear offers you:b high mechanical and electrical endurance;

b a comprehensive range of performance levels;

b optimal operating safety;

b environmental protection.

MT

2005

1M

T20

052

MT

2005

6

Evolis range circuit-breaker

Page 4: Catalogo Mcset 1-17.5kv2005vacio

3

Presentation Continuity of service and complete safety

MCset is solidly based on extensive experience acquired throughout the world and provides your networks with a high level of dependability and safety.

MCset integrates a host of innovative solutions designed around proven techniques: high performance switchgear, digital protection, monitoring and control systems, enclosures capable of withstanding internal arcing.From its very conception, MCset has taken account of three key user requirements:

Reliabilityb type testing was carried out for each performance level in the MCset range;b the design, manufacturing and testing of MCset was carried out according to ISO 9001 : 2000 quality standard;b three-dimensional computer modeling techniques were used to study the electrical fields.

Simplicity b a user interface which is easily understood by everybody;b interlocks and padlocks preventing operator errors;

b Sepam-type protection units enabling on-site information retrieval without any additional devices;

b maintenance limited to simple, routine operating checks and cleaning and greasing every 5 to 10 years;

b easy installation due to identical civil engineering dimensions for all cubicles and installation being possible against a wall.

Safetyb operations are all performed from the front, including access to connections and busbars;b racking in and out is only possible with the door closed;

b the power-on indicator is situated on the front of the functional unit;

b the earthing switch has making capacity;b one single "anti-reflex" handle is used for all MCset operations;

b internal arc withstand developed for all functional units.

MT

2005

8FR

MT

2005

9

Page 5: Catalogo Mcset 1-17.5kv2005vacio

4

Presentation MCset, a comprehensive solution

MCset provides the most efficient means to control and protect a wide range of applications. Due to the devices it comprises, MCset can be easily integrated into a monitoring and control system.

Sepam protection and control unitsSepam series 20, series 40 and series 80 digital protection relays take full advantage of Merlin Gerin experience in electrical network protection.

Sepam series 20, series 40 and series 80 provides all the necessary functions:

b effective protection of people and property;b accurate measurements and detailed diagnosis;

b integral equipment control;

b local or remote indication and operation.

Easy evolutionAddition of communication, digital I/O’s, analog output, or temperature acquisition are possible due to its modular design.

Power Meter and Circuit Monitor metering unitsThe PowerLogic Power Meter replaces a full complement of basic analog meters. This cost effective, high performance meter provides a full complement of accurate true-rms metering values.

The Powerlogic Series 3000/4000 Circuit Monitor is designed for critical power users and large energy consumers, to provide the information needed to confidently enter the evolving world of deregulation. It can be adapted to meter almost any time-of-use or real-time rate.

Monitoring and controlMCset can be easily:

b integrated into an existing monitoring and control system:v communication of Sepam digital relay or Power Meter/ Circuit Monitor metering device through a standard protocol (Modbus);b integrated into a SMS PowerLogic electrical installation monitoring system.

Thermal diagnosis systemSpecially designed for Schneider Electric MV equipment, this system continuously monitors the temperature rise, using optical fibres and sensors installed at the heart of the sensitive areas.

Thermal diagnosis system reduces the probability of failure and reduces maintenance time.

PE

5517

0P

E55

134

MT

2005

5P

E55

136

Page 6: Catalogo Mcset 1-17.5kv2005vacio

5

Presentation MCset, a comprehensive solution(cont’d)

MCset Transparent Ready™ optionMCset switchoards integrate Web technologies so that you can find out information about your electrical installation as easy as opening a Web page.

All you need is a standard Web browser and a PC connected to your local area network.

Simple choice A simple choice between TRe-1 and TRe-2 service levels allows you to easily order your Transparent Ready™ Motorpact switchboard.

A customized level is also available.

Your Transparent Ready™ MCset switchoard comes equipped with a web server including web pages dedicated to power equipment data.

Easy commissioningTransparent Ready™ equipment is delivered ready to connect and commission.

A Quick Start guide, packaged with your switchboard, provides three easy-to-follow steps.

Functionalities provided

PE

5513

7D

E55

465

MCset switchboard

PE

5513

8P

E55

139

PE

5514

0

Sepam

Sepam

CM/PM

TCP/IP over Ethernet

Front socketHub

EGX400

TRe-1 TRe-2Instantaneous readings Displays automatically updated meter values

b b

Circuit summaryDisplays the RMS current 3-phase average (A), the real power (kW), the power factor, the circuit-breaker status (if applicable), etc.

b b

Load current summaryDisplays the current RMS value for each phase (A), for all circuits

b b

Demand current summaryDisplays the average demand current value for each phase (A), for all circuits

b b

Power summaryDisplays the present demand (kW), the peak demand (kW) and the times and dates of the records

b b

Energy summaryDisplays the energy (kWh) the reactive energy (kvarh) and the times and dates of the records

b b

Instantaneous readings, all devicesDisplays automatically updated meter values for all the communicating devices in the equipment

b

Basic historical data logging, energy and trendingDisplays automatically updated meter values for all the communicating devices in the equipment

b

Log displaysDisplays data as time curves, or tables

b

Export of data tablesAllows data tables to be exported in a standard Windows format.

b

Page 7: Catalogo Mcset 1-17.5kv2005vacio

6

Presentation MCset, a comprehensive solution(cont’d)

Schneider Electric Services, by your side throughout the life of your installation

SpecifyingWe help you to define your solutions: selection guide, technical assistance, advice…

ImplementingWe oversee the completion and commissioning of your installation: design, cost optimization, guaranteed performances and dependability, commissioning tests, etc.

OperatingWe help run your daily operations in real time: maintenance contract, technical assistance, supply of replacement parts, corrective and preventive maintenance, operation and maintenance training, etc.

ModernizingWe can bring the performance of your installation up to date:installation audit, switchgear diagnosis, adaptation and modification, end of life recycling, etc.

Examples of services provided

Warranty extensionA warranty extension is proposed if your installation is checked by ourselves before being commissioned.

Circuit-breaker-contactor diagnosisThroughout the life of the equipment, it is possible to carry out routine measurement of its characteristics in order to optimize maintenance. This service may be part of a global installation maintenance contract.

End-of-life recyclingSchneider Electric Services has an operational subsidiary allowing you to recycle your medium voltage switchgear.

MT

2006

4 Modernizing

Operating

Specifying

Implementing

MT

2006

5FR

Page 8: Catalogo Mcset 1-17.5kv2005vacio

7

Presentation Quality assurance - environment

Certified quality: ISO 9001

A major assetIn each of its units, Schneider Electric integrates a functional organization whose main role is to check quality and monitor compliance with standards.

This procedure is:

b uniform throughout all departments;b recognized by many customers and approved organizations.

But above all, it is its strict application that has allowed us to obtain the recognition of an independent organization:

The French Quality Assurance Association (AFAQ).

The quality system for the design and manufacture of MCset is certified to be in conformity with the requirements of ISO 9001 : 2000 quality assurance standards.

Strict and systematic checksDuring manufacture, each MCset functional unit is subject to systematic routine testing with the aim of checking the quality and conformity of the following features:

v measuring of opening and closing speeds;

v measuring of operating torque;v dielectric test;

v testing of safety systems and interlocks;

v testing of low voltage components;v conformity with drawings and diagrams.

The results obtained are recorded and approved by the quality control department on each device’s test certificate.

This therefore guarantees product traceability.

b Control of vacuum interruptersEach vacuum interrupter, sealed and airtight, is checked for the quality of the vacuum obtained. This pressure measurement is based on the proven "magnetron discharge" method. Using this sophisticated procedure, measurement is very precise and does not require access to the inside of the bulb, thus not affecting the airtight seal.

Protected environmentIn order to help you protect the environment and to relieve you of any concerns about storing or dismantling this equipment, Schneider Electric Services offers to recover your equipment at the end of its life.MCset has been designed with environmental protection in mind:the materials used, insulators and conductors are identified, easily separable and recyclable.

Production sites are certified to ISO 14000.

MT

2006

6M

T20

067

MT

2006

8M

T20

069F

R

Page 9: Catalogo Mcset 1-17.5kv2005vacio

8

MCset range Presentation 0

PE

6012

0

Busbars

Circuit-breaker

Currenttransformers

Cables connection

Low voltagecontrol cabinet

Sepam

Voltagetransformerscompartment

Page 10: Catalogo Mcset 1-17.5kv2005vacio

9

MCset range Presentation 0

(cont.)

Make up of an MCset switchboardMCset switchboards are made up of several interconnected functional units.Power connections are made between functional units within a switchboard via a single busbar.The electrical continuity of all metal frames is provided by the connection of each functional unit’s earthing busbar to the switchboard’s main earthing circuit.Low voltage wiring trays are provided in the switchboard above the low voltage control cabinets.LV cables can enter the switchboard through the top or bottom of each functional unit.

Description of a functional unitA functional unit comprises all equipment in the main and auxiliary circuits which together provide a protection function. Each functional unit combines all the components which are required to fulfil this function:b the cubicle;b the protection, monitoring and control system;b the withdrawable part.

The cubicleThe cubicle is of LSC2B (Loss of Service Continuity Category) type as defined by IEC standard 62271-200, in other words the medium voltage parts are compartmented using metal partitions (PM class) which are connected to earth and which separate:b the busbars;b the withdrawable part (circuit-breaker, fuse-contactor, disconnector truck or earthing truck);b MV connections, earthing switch, current sensors and voltage transformers as required.MCset guarantees a high level of protection of people; when a compartment containing a main circuit is open, the other compartments and/or functional units may remain energised.The low voltage auxiliaries and monitoring unit are in a control cabinet separated from the medium voltage section.Four basic cubicle layouts are offered:b incomer or feeder ADb line up bussection CL - GLb busbar metering and earthing TTb switch-fuse feeder DIAD and CL cubicles have withdrawable vacuum type circuit-breaker and contactor switchgear.

The protection, monitoring and control systemThis includes:b Sepam, protection, monitoring and control unit;b current sensors, which may be of 3 types:v conventional current transformers,v low voltage toroid type current transformers,v CSP type broad-range current transformers.b voltage transformers;b zero sequence core balance current transformers (CSH type).

The withdrawable partThis includes:b the circuit-breaker, contactor or the earthing truck with its closing and opening mechanism, or the disconnector truck;b the lever-type propulsion mechanism for racking in-out;b interlocks to fix the withdrawable part on the fixed part either in service position or disconnected.

Page 11: Catalogo Mcset 1-17.5kv2005vacio

10

MCset range Technical characteristics 0

The values below are given for normal operating conditions as defined in IEC 62271-200 and 60694.

(1) For functional units equipped with circuit-breakers or fuse-contactors, the breaking capacity is equal to the short time withstand current. In all cases, the device peak making capacity is equal to 2.5 times the short time withstand current. (2) Limited by fuses.

MT

2007

1

Rated voltage (kV)7.2 12 17.5

Rated insulation levelpower frequency withstand voltage 50 Hz - 1 mn (kV rms) 20 28 38lightning impulse withstand voltage 1.2/50 µs (kV peak) 60 75 95

Nominal current and maximum short time withstand current (1)

Functional unit with Evolis circuit-breakershort time withstand current

Ith max. (kA/3 s) 25 25 2531.5 31.5 31.540 40 40

(kA/1 s) 40 40 40rated current In max. busbar (A) 2500 2500 2500rated current In CB (A) 630 630 630

1250 1250 12502500 2500 2500

Functional unit with fuse-contactor short time withstandcurrent

Ith max. (kA) 50 (2)

rated current In max. (A) 250Functional unit with switch-fuse (DI cubicle)

short time withstandcurrent

Ith max. (kA) 50 (2) 50 (2) 31.5 (2)

rated current In max. y (A) 200 200 200

Internal arc withstand(kA) 25 to 40

Page 12: Catalogo Mcset 1-17.5kv2005vacio

11

MCset range Operating conditions 0

Operating conditionsNormal operating conditions, according to IEC 60694 for indoor switchgearb ambient air temperature: v less than or equal to 40°C,v less than or equal to 35°C on average over 24 hours,v greater than or equal to -5°C.b altitude: v less than or equal to 1000 m,v above 1000 m, a derating coefficient is applied (please consult us).b atmosphere: v no dust, smoke or corrosive or inflammable gas and vapor, or salt (clean industrial air).b humidity: v average relative humidity over a 24 hour period y 95%, v average relative humidity over a 1 month period y 90%, v average vapor pressure over a 24 hour period y 2.2 kPa, v average vapor pressure over a 1 month period y 1.8 kPa.

Specific operating conditions (please consult us)MCset has been developed to meet the following specific conditions:b temperature (possible derating);b corrosive atmospheres, vibrations, (possible adaptation).

Storage conditionsIn order to retain all of the functional unit’s qualities when stored for prolonged periods, we recommend that the equipment is stored in its original packaging, in dry conditions sheltered from the sun and rain at a temperature of between –25°C and +55°C.

StandardsThe MCset range meets the following international standards:IEC 60694: clauses common to high voltage switchgearIEC 62271-200 (60298): metal-enclosed switchgear for alternating current at rated voltages of between 1 and 52 kVIEC 62271-100 (60056): high voltage alternating current circuit-breakersIEC 60470: high voltage alternating current contactorsIEC 60265-1: high voltage alternating current switchesIEC 60282-2: high voltage fusesIEC 62271-102 (60129): alternating current disconnectors and earthing switchesIEC 60255: measurement relay and protection unit (Sepam)IEC 60044-1: current transformersIEC 60044-2: voltage transformers.

MT

2007

2M

T20

073

Page 13: Catalogo Mcset 1-17.5kv2005vacio

12

MCset range Protection of people 0

MCset internal arcInternal arc version: MCset is designed to withstand and protect operators in the case of failure due to an internal arc. MCset has been successfully tested using type tests.MCset proposes several options to install an internal arc switchboard.b 3-sided internal arc protection For an MCset switchboard fitted against a wall, access to the rear of the cubicle is impossible. Internal arc protection on 3 sides is sufficient. b 4-sided internal arc protectionIn the case of an MCset switchboard installed in the middle of a room, internal arc protection on 4 sides is necessary in order to protect an operator who goes behind the cubicle. b Installation in a room with limited ceiling heightv ceiling height over 2.8 meters, it is possible to install a tunnel in order to avoid hot gas to be reflected by the ceiling.b Internal arcing detectorMCset has a system enabling the detection of internal arcing and disconnecting of power supply in order to limit the duration of the fault to less than 140 ms. This system incorporates an electro-mechanical fail-safe trip system, located on the cubicle flaps. This unit transmits information to Sepam to give the circuit-breaker upstream of the fault the opening order.

MCsetBasic version (gas exhaust): MCset is designed to eliminate the effects of internal arcing in total safety, due to:b metal flaps positioned above the enclosure, which in the case of internal fault, limit overpressure in the compartments.b nonflammable materials used for the cubicle.

Dependable mechanical control devicesAll operations are carried out from the front face, including access to connections and busbars.The user is guided through icon-diagrams on each front panel making it easy to understand the operating sequence and device status.Interlocks and padlocks prevent operator errors.Several additional levels of security also protect operators:b racking in and out is only possible with the door closed;b the very extensive set of mechanical and electrical interlocks do not allow operator error. These can be added to by key locks or padlocks according to specific operating procedures. Each selector can be fitted with one to three padlocks;b all operations are carried out from the front face, including access to connections and busbars; b the voltage present indicator is located on the front face of the functional unit, in the immediate vicinity of the earthing switch control.

Optionsb disarming of circuit-breaker when racking out. This function enables the circuit-breaker control springs to be disarmed during the extraction operation.b disabling of racking in. This function disables the possibility of racking the withdrawable part in if the busbar is energized.

MT

2007

6

MCset switchboard with tunnel

MT

2007

7

Page 14: Catalogo Mcset 1-17.5kv2005vacio

13

MCset range Motor protection and control 0

Motorpact, an innovative range of motor starters, with vacuum contactor Motorpact is a MV motor control centre which can be used as a lined up switcboard with MCset, using a transition cubicle.b Main characteristics:v rated voltage up to 7.2 kVv rated busbar current: up to 2500 Av rated short time withstand current: 40 kA 3sv internal arc withstand: 25 kA 1 s

40 kA 0,5 s 50 kA 0,25 s

v rated operational currrent: 400 Av maximum fuse rating: 2 x 250 A.

Note: for details see Motorpact catalogue n° AMTED302059EN

Motorpact motor starters provide a wide range of applications including reduced voltage starting:b FVNR : direct on line motor starter,b RVAT : reduced voltage autotransformer motor starter,b RVSS : dreduced voltage SoftStart motor starter.

b They are suitable for all MV motor applications in markets such as: oil & gas, mining, water, pulp and paper, for starting:b pumps,b fans,b compressors,b crushers,b conveyors, etc.

Compactnessb Compact dimensions thanks to a 375 mm width.b Softarter and Autotransfo built into the switchboard.

Safetyb Full cubicle protection for internal arc withstand (AFLR 4 sides).b Electrical and mechanical interlocking, closed door operation.b Visible insulation by means of portholes

Reliabilityb Fewer components and fasteners.

Less maintenanceb Corrosive atmosphere withstand.b Maintenance free disconnector (capacity: 5000 operations).b Front access to compartments.

PE

6012

2

DE

6017

5

MCset lined up with Motorpact

Page 15: Catalogo Mcset 1-17.5kv2005vacio

14

MCset range Choice of functional units 0

The MCset range comprises 13 functional applications.The table below can be used to link requirements to functional units and gives basic information on the general composition of each unit.

Selection guide:You want to supply power to a transformer.The chosen solution is a transformer feeder/breaker.The corresponding functional unit will therefore be a TF-B, comprising a AD cubicle equipped with a withdrawable circuit-breaker, and transformser application Sepam.

(1) The direct incomer (functional unit without a circuit-breaker, equipped with a fixed busbar bridge) is produced using cubicles AD1-2-3.

Function Incomer (1) Feeder

line transformer generator line transformer transformer

Functional unit LI-B TI-B GI-B LF-B TF-B TF-S

cubicle AD (1 to 3) AD (1 to 3) AD (1 to 3) AD (1 to 3) AD (1 to 3) DI 2

device circuit-breaker circuit-breaker circuit-breaker circuit-breaker circuit-breaker fuse-switch

Sepam protection relay

application substation transformer generator substation transformer

Single line diagrams

MT

2008

0

MT

2008

1

MT

2008

2

Sepam

Page 16: Catalogo Mcset 1-17.5kv2005vacio

15

MCset range Choice of functional units(cont.)

Feeder Bussectioning Metering and busbar earthing

Motorpacttransition

motor motor capacitor capacitor switchboard substation

MF-B MF-C CB-B CB-C BS-B SS-B BB-V

AD (1 to 3) AD1 AD (1 to 3) AD1 CL (1 to 3) and GL (1 to 3)

AD (1 to 3) TT (1-2)

circuit-breaker fuse-contactor circuit-breaker fuse-contactor circuit-breaker circuit-breaker

motor motor capacitor capacitor busbar substation

MT

2008

1

MT

2008

3

MT

2008

1

MT

2008

3

MT

2008

4

DE

5507

6

MT

2007

8

DE

6016

7

Page 17: Catalogo Mcset 1-17.5kv2005vacio

16

Cubicle description AD type cubicles incomer and feeder 0

AD1, AD2, AD3

DE

5508

1

DE

5508

2

DE

6016

8

AD1 AD2

DE

5508

3

MV compartments1 busbars for cubicle interconnection2 withdrawable part3 MV connections by cables accessible from the front face4 earthing switch5 current sensors6 voltage transformers (optionally equipped with withdrawable fuses).

LV control cabinet7 low voltage auxiliaries and the protection, monitoring and control unit

are in a control cabinet which is separated from the medium voltage part.

AD3

L

H

L

H

1

7

2

54

63

P

H

L

CharacteristicsAD1

AD1 contactor

AD2

AD3

rated voltage kV 7.2 12 7.2 7.2 12 17.5 7.2 12 17.5rated insulation level kV rms 50 Hz - 1 mn 20 28 20 20 28 38 20 28 38

kV impulse 1.2/50 µs 60 75 60 60 75 95 60 75 95rated current A 250 b

630 b b b b b b b b b1250 b b b b b b b b b2500 b b b b b b b b b

breaking capacity kA 25 25 50 (3) 31.5 31.5 25 31.5 25 31.5 40 25 31.5 40 25 31.5 40short time withstand current (kA rms 1 s) 25 25 50 (3) 31.5 31.5 25 31.5 25 31.5 40 25 31.5 40 25 31.5 40short time withstand current (kA rms 3 s) 25 25 50 (3) 31.5 31.5 25 31.5 25 31.5 40 25 31.5 40 25 31.5 40weight and dimensions H (mm) 2300 2300 2300

W (mm) 570 700 900D (mm) (1) 1550 1550 1550approximate weight (kg) (2)

850 1000 1300

(1) Overall + 175 mm for 4-sided internal arcing protected switchboards, or 2 sets of CT’s.(2) Fully equipped cubicle.(3) Limited by fuses.

Page 18: Catalogo Mcset 1-17.5kv2005vacio

17

Cubicle description CL - GL type cubiclesline-up bussectioning 0

The bussectioning functional unit comprises 2 cubicles mounted side by side (one cubicle equipped with a circuit-breaker, the other with a busbar return). CL1, CL2, CL3 GL1, GL2, GL3

DE

5508

7

DE

6016

9

DE

6017

0

CL1-2-3 or GL1-2-3

MV compartments1 busbars to connect the bussectioning functional unit with other switchboard

functional units2 withdrawable part3 current sensors4 voltage transformers (optionally equipped with withdrawable fuses).

LV control cabinet5 low voltage auxiliaries and protection, monitoring and control unit

are in one control cabinet, separated from the medium voltage part.

L L

H

1

2

5

P

1

4

63

P

CharacteristicsCL1 - GL1 CL2 - GL2 CL3 - GL3

rated voltage kV 7.2 12 7.2 12 17.5 7.2 12 17.5rated insulation level kV rms 50 Hz - 1 mn 20 28 20 28 38 20 28 38

kV impulse 1.2/50 µs 60 75 60 75 95 60 75 95rated current A

630 b b b b b b b b b1250 b b b b b b b b b2500 b b b b b b b b b

breaking capacity kA 25 25 31.5 31.5 25 31.5 25 31.5 40 25 31.5 40 25 31.5 40short time withstand current (kA rms 1 s) 25 25 31.5 31.5 25 31.5 25 31.5 40 25 31.5 40 25 31.5 40short time withstand current (kA rms 3 s) 25 25 31.5 31.5 25 31.5 25 31.5 40 25 31.5 40 25 31.5 40weight and dimensions H (mm) 2300 2300 2300

W (mm) 570 (x 2) 700 (x 2) 900 (x 2)D (mm) (1) 1550 1550 1550approximate weight (kg) (2)

1300 (CL1 + GL1)

1500 (CL2 + GL2)

1700 (CL3 + GL3)

(1) Overall + 175 mm for 4-sided internal arcing protected switchboards, or 2 sets of CT’s.(2) Fully equipped cubicle.

Page 19: Catalogo Mcset 1-17.5kv2005vacio

18

Cubicle description TT type cubicles metering and busbar earthing 0

TT1, TT2

DE

5509

3

DE

5509

4

DE

6017

1

TT1 TT2

MV compartments1 busbars to connect the TT functional unit with other switchboard cubicles2 earthing switch3 voltage transformers (optionally equipped with withdrawable fuses).

LV control cabinet4 low voltage auxiliaries and the protection, monitoring and control unit

are in a control cabinet which is separate from the medium voltage part.

H

L L

H

1

4

2

3

P

CharacteristicsTT1 TT2

rated voltage kV 7.2 12 7.2 12 17.5rated insulation level kV rms 50 Hz - 1 mn 20 28 20 28 38

kV impulse 1.2/50 µs 60 75 60 75 95rated current A 630 b b b b b b

1250 b b b b b b2500 b b b b b b

short time withstand current (kA rms 1 s) 31.5 50 50 31.5 40short time withstand current (kA rms 3 s) 31.5 50 40 31.5 40weight and dimensions H (mm) 2300 2300

W (mm) 570 700D (mm) (1) 1550 1550approximate weight (kg) (2)

500 550

(1) Overall + 175 mm for 4-sided internal arcing protected switchboards.(2) Fully equipped cubicle.

Page 20: Catalogo Mcset 1-17.5kv2005vacio

19

Cubicle description DI type cubicles switch-fuse feeder 0

DI2

DE

5509

8

DE

6017

2

DI2

MV compartments1 busbars to connect the DI functional unit with other switchboard cubicles 2 switch-earthing switch3 MV fuses.

LV control cabinet4 low voltage auxiliaries and the protection, monitoring and control unit

are in a control cabinet which is separate from the medium voltage part

L

H

1

2

4

3

P

DI cubicles including a fuse switch are used to supply power and protect low power transformers.E.g.: auxiliary service transformers in primary substations.All operations are carried out from the front face, including access to connections and busbars. All functional interlocks meet recommendations in IEC 60298: b the switch is only possible to close if the earthing switch is open and the connection access panel is in place.b closing of the earthing switch is only possible if the switch is open. b opening of the access panel to medium voltage connections and fuses is only possible of the earthing switches upstream and downstream of the fuses are closed.b the switch is locked in the open position when the access panel is taken off.The voltage presence indicator is situated on the front face of the functional unit, integrated in the switch’s control panel.

CharacteristicsDI2

rated voltage kV 7.2 12 17.5rated insulation level kV rms 50 Hz - 1 mn 20 28 38

kV impulse 1.2/50 µs 60 75 95rated current A 200 b b bshort time withstand current (kA rms) (3) 50 50 31.5weight and dimensions H (mm) 2300

W (mm) 700D (mm) (1) 1550approximate weight (kg) (2)

750

(1) Overall + 175 mm for 4-sided internal arcing protected switchboards.(2) Fully equipped cubicle.(3) Limited by fuses.

MT

2009

3

SwitchThe three rotating contacts are placed in an enclosure filled with gas to a relative pressure of 0.04 MPa (0.4 bar). The system offers maximum operating reliability:b gas tightnessThe SF6 filled enclosure is of the "sealed pressure system type". Sealing tightness is always checked in the factory. b safetyv the switch may be in one of three positions: "closed", "open", or "earthed", giving a natural interlocking system that prevents operator error.Moving contact rotation is driven by a fast acting mechanism that is independent of the operator.v the device combines the breaking and disconnecting functions,v the SF6-enclosed earthing switch has a short circuit making capacity in compliance with standards.

Page 21: Catalogo Mcset 1-17.5kv2005vacio

20

Cubicle description Motorpact transition cubicle 0

Compositionb Basic equipment:v 1 enclosure (standard IP3X),v 1 set of busbars in separate compartment,v 1 removable front panel.

b Optionsv internal arc withstand,v IP4X or IPX1 enclosure,v encapsulated busbars.

DE

6017

6

DE

6017

4

L P

H

CharacteristicsMotorpact transition cubicle

maximum rated voltage 7.2 kVimpulse withstand voltage (1.2/50 µs, peak value) 60 kVpower frequency withstand voltage (1 mn) 20 kVbusbars rating 630 A

1250 A2500 A3150 A

dimensions H 2300 mmL 375 mmP 1550 mm

approximate weight 1250 A 240 kg2500 A 275 kg3150 A 310 kg

Page 22: Catalogo Mcset 1-17.5kv2005vacio

21

Page 23: Catalogo Mcset 1-17.5kv2005vacio

22

Protection, monitoring and control

0Thermal diagnosis

Thermal diagnosis: Schneider Electric’s medium voltage know-how This innovative system has been specifically designed for the MCset range. It incorporates fibre optic temperature measurement systems within an environment subject to high dielectric stresses.Schneider Electric’s expertise provides you with the assurance of perfect electromagnetic compatibility between the various cubicle components.

The advantages of thermal diagnosisb permanent monitoring of temperature rise in power circuits (busbars, cable connectors, switchgear);b indication of the fault zone;b 2 trip thresholds are available, using a dry contact.

ComponentsThe thermal diagnosis system comprises the following components:b 1 or 2 modules mounted in the low voltage control cabinet;b 3 -point temperature probes (spread over the 3 phases) can be installed in various monitored zones:v 3 sensors in the busbar compartment,v 3 sensors in the cable connector compartment,v 3 sensors in the switchgear compartment;b fibre optic links to transmit the signal.

Continuity of service is of prime importance for electrical power supplies, particularly.for heavy industries.By using the new thermal diagnosis system developed for MCset, we offer you the possibility of monitoring on an on-going basis, thus reducing the probability of failure and reducing maintenance time.

MT

2011

9

PE

5516

0

Page 24: Catalogo Mcset 1-17.5kv2005vacio

23

Protection, monitoring and control

0The protection systemSepam range

Sepam: protection, monitoring and control unitsSepam, is a range of digital monitoring protection and control units.Sepam is at the centre of the protection, monitoring and control system for MCsetfunctional units: all the necessary protection, metering, control, monitoring andsignalling functions are carried out by Sepam.

Like the MCset range, the Sepam range is a range of units defined to provide an optimal solution for each application, and includes:b Sepam S, substation incomer and feeder;b Sepam B, bussectioning;b Sepam T, transformer feeder;b Sepam M, motor feeder;b Sepam G, generator feeder;b Sepam C, capacitor feeder.

The Sepam range hinges around 2 functional and hardware bases:Sepam series 20, 40 and series 80,a range of modular reays to meet your exact needs,v Sepam 2000, focused on performance, covers all MCset functional applications.

Sepam advantagesReliabilityb Over 20 years of experience in multi-function digital protection relays.b Over 150 000 Sepam units in service in more than 90 countries.Qualityb Quality design based on dependability studies and strict definition of environmental constraints: temperature, pollution, EMC, dielectric strength…b Quality manufacturing based on procurement agreements with suppliers and inspection throughout all manufacturing phases. Simplicity of useb Ergonomic and intuitive user machine interface (UMI).b User friendly and powerful PC setting software.

Each MCset functional unit is equipped with a comprehensive protection, monitoring and control system comprising:b instrument transformers to measure the necessary electrical values (phase current, residual current, voltages, etc.)b protection relays, providing functions adapted to the part of the network to be protected b metering equipment, to inform operatorsb low voltage relaying, i.e. to provide control of the breaking device (contactor or circuit-breaker) and of the withdrawable partb various auxiliaries: secondary circuit test units, etc.

MT

2009

4

protection relays metering equipment

switchgear (circuit-breaker or contactor)

instrument transformers

PE

5517

0

Page 25: Catalogo Mcset 1-17.5kv2005vacio

24

Protection, monitoring and control

0Sepam 2000Sepam 100

Sepam 2000, for all applicationsThe Sepam 2000 range of digital protection, monitoring and control unitsprovides a comprehensive solution for all applications: substation, busbar, transformer and motor, as well as generators and capacitors.Different types of Sepam 2000 dédiés à la protection are proposed for each type of equipment to be protected.For example, there are 30 different types of Sepam 2000 dedicated to protection,monitoring and control of transformers.Each Sepam 2000 is an optimized solution, designed to provide an exact responseto the actual requirements of a functional application, including all the requiredfunctions, ready to use.

Focused on performance, Sepam 2000 includes the following functions:b metering functions: measurement of current and voltage, measurement of power and active and reactive energy, etc.b protection functions: directional phase and earthing protection, differential transformer or machine protection, etc.b monitoring and control functions: in its function as a programmable logical controller, Sepam 2000 is pre-programmed to carry out standard monitoring and control functions, and can be reprogrammed to handle any specific automatic control function.

To choose the type of Sepam 2000 best suited to your application, the "Sepam range" catalogue includes selection charts for the whole Sepam 2000 range, (document AC0401).A "Sepam 2000 Selection Guide" software package is also available for computer-aided selection of Sepam 2000 for a given application.

Sepam 100 unitsSepam 100 units round off the Sepam range and can be installed either separately or combined with either Sepam series 20, 40 and series 80 or Sepam 2000.

Sepam 100 has several variants:Sepam 100 MI, local breaking device control and signalling modules (many different line diagram types are available);b Sepam 100 LD, high impedance differential protection; b Sepam 100 LA, Self-powering protection (back-up protection without auxiliary power supply).

MT

2009

7

Sepam 2000

E61

780

PE

6011

6

PE

6011

7

PE

6011

8

Sepam 100MI Sepam 100LD Sepam 100LA

Page 26: Catalogo Mcset 1-17.5kv2005vacio

25

Protection, monitoring and control

0Sepam 2000selection table

Fonctions Sepam 2000Applications Substation busbar Transformer Motor Generator Capacitor

Measurementscurrents I1/I2/I3/I0

IM1/IM2/IM3Itrip 1/2/3/0

b b b b b b

voltages and frequencies U21/U32/U13V1,V2,V3V0Vdf

b b b b b b

powers and energies P/Q, PM/QM, cos jEa/Er

b b b b b b

temperatures b b b

Protections ANSI codes phase 50/51 b b b b b b

earth 50N/51N b b b b b b

imbalance 46 b b

directional 67/67N b b 67N b

differential 87T/87M/87B 87T 87M 87Mrestricted earthing differential 64REF b b

overload 49/49T/38 b b b 49motor 37/48/51LR/66 b

voltage 59/2759N

b b b b 27/59

frequency 81H/81L b b b

uncoupling (df/dt) 81R b b

specific 32P7927R

2527D

50N/51(neutral point)50/51 (tank earth)27R

32P and32Q/4027D/47

32P, 32Q/402550V/51V

cap. bankimbalance

Network diagnosisdisturbance recording 2 recording of 86 periodsSwitchgear diagnosis

operation timetrip currents, sum of breaking currents A2 b b b b b b

trip circuit monitoring b b b b b b

watchdog 1output/4 contacts: 2 x (1NO + 1NC)Communication

protocol Modbusinterface RS485, 2 or 4 wireMonitoring and control

inputs/outputs basic 10I/6O in/outmaximum 26I/14O in/out

breaking device control b b b b b b

logical selectivity b b b b b b

customizing parameter setting b b b b b b

programming b b b b b b

b available functions

Page 27: Catalogo Mcset 1-17.5kv2005vacio

26

Protection, monitoring and control

0Sepam series 20, series 40 and series 80

The Sepam range of protection relays isdesigned for the operation of machines and electrical distribution networks of industrial installations and utility substations at all levels of voltage.It includes 3 families :b Sepam series 20, for usual applications;b Sepam series 40, for demanding applications;b Sepam series 80, for custom applications to cover all needs, from the simplest to the most complete.

Sepam protection relayA range of solutions adapted to your applicationb substation protection (incomers, feeders, busbars);b transformer protection;b motor and generator protection.

A comprehensive solution, integrating all of the necessary functions for your applicationb effective protection of people and property;b accurate measurements and detailed diagnosis;b integral equipment control;b local or remote indication and operation.

Flexibility and upgrading capabilityTo adapt to as many situations as possible, and allow for future installation upgrading, optional modules may be added to Sepam at any time for new functions.

PE

5517

0

PE

4001

3

Sepam series 20, series 40 and series 80

Sepam series 80 modular architecture1- Base unit, with integrated or remote advanced User Machine Interface.2- Parameter and protection, settings saved on removable memory cartridge.3- 42 logics inputs and 23 output relays with 3 optional modules providing 14 inputs and 6 outputs.

4- 2 independent Modbus communication portsb direct connection to 2-wire RS 485, 4-wire RS 485 and fiber optic networks,b connection to Ethernet TCP/IP network via PowerLogic System Webserver (Transparent Ready).5- Processing of data from 16 temperature sensors.

6- 1 low level analog output, 0-10 mA, 4-20 mA or, 0-20 mA.7- software tools:b Sepam parameter and protection setting and control logic customization;b local or remote installation operation;b retrieval and display of disturbance recording data.

SimplicityEasy installation b The same, easy-to-install remote modules for all Sepam units.

Commissioning assistanceb Predefined functions implemented by simple parameter setting;b user-friendly, powerful PC setting software tool.

Intuitive useb Clear graphic LCD display of all data required for local operation and installation diagnosis;b working language may be customized to be understood by all users.

31

5

6

2

7

4

Page 28: Catalogo Mcset 1-17.5kv2005vacio

27

Protection, monitoring and control

0Sepam series 20, series 40 and series 80Selection table

Sepam Protections ApplicationsBasic Specific Sub-

stationTransfo. Motor Generator Busbar

Sepam series 20b 10 logic inputsb 8 relay outputsb 8 temperature probe inputsb 1 Modbus communication port

DE

5011

3

Current protection

S20 T20 M20

DE

5011

4

Voltage andfrequency protection

B21

Loss of mains(ROCOF)

B22

Sepam series 40b 10 logic inputsb 8 relay outputsb 16 temperature probe inputsb 1 Modbus communication portb Logic equations editor

DE

5010

4

Currentvoltage and frequency protection

S40 T40 G40

Directional earth fault

S41 M41

Directional earth faultand phase overcurrent

S42 T42

Sepam series 80b 42 logic inputsb 23 relay outputsb 16 temperature probe inputsb 2 Modbus communication portb Logic equations editor

DE

5011

5

Currentvoltage and frequency protection

S80

Directional earth fault

S81 T81 M81

DE

5011

6

Directional earth fault and phase overcurrent

S82 T82 G82

Transformer or machine-transformer differential

T87 M88 G88

Machine differential

M87 G87

Page 29: Catalogo Mcset 1-17.5kv2005vacio

28

Protection, monitoring and control

Instrument transformers

Conventional current transformersConventional current transformers are used to provide power to metering, measuring or control devices. They measure the value of primary current from 10 A to 2500 A. Schneider Electric has drawn up a list of current transformers which are appropriate for use with digital protection devices in order to make it easier to determine accuracy characteristics. This list is available in the selection guide on page 45.

E28

676

For contactor cubicle AD1Transformer ARJP1/N2Jb single primary current, double secondary current for measurement or protectionb frequency 50-60 HzI1n (A) 10 20 30 50 75 100 150 200 250Ith (kA) 1.2 2.4 3.6 6 10 10 10 10 10t (s) 1 1 1 1 1 1 1 1 1measuring* protection*

cl.0.5 15 VA5P20 2.5 VA

ARJP1, 2 or 3

For cubicles AD1-CL1-GL1-AD2-CL2-GL2Transformer ARJP2/N2Jb double primary current, double secondary current for measurement or protectionb frequency 50-60 HzI1n (A) 50-100 75-150 100-200 150-300 200-400 250-500 600 750Ith (kA) 40 40 31.5-40 40 40 40 50 50t (s) 1 1 1 1 1 1 1 1measuring* protection*

cl.0.5 5-10VA 10-20 VA 7.5-15VA 10-20 VA 20VA 20VA5P20 2.5-5VA 2.5-5VA 2.5-5VA 2.5-5VA 5-10VA 5-10VA 7.5VA 7.5VA

For cubicles AD1-CL1-GL1-AD2-CL2-GL2Transformer ARJP3/N2Jb single primary current, double secondary current for measurement or protectionb frequency 50-60 HzI1n (A) 1000 1250Ith (kA) 50 50t (s) 1 1measuring* protection*

cl.0.5 30 VA 30 VA5P20 10 VA 10 VA

E74

399

For cubicles AD3-CL3-GL3Transformer ARJA1/N2Jb single primary current, double secondary current for measurement or protectionb frequency 50-60 HzI1n (A) 1500 2000 2500Ith (kA) 50 50 50t (s) 1 1 1measuring* protection*

cl.0.5 30 VA 30 VA 30 VA5P20 15 VA 15 VA 15 VA

ARJA1

* The secondary current for measuring and protection can be of 1 A or 5 A.

Page 30: Catalogo Mcset 1-17.5kv2005vacio

29

Protection, monitoring and control

Instrument transformers (cont.)

CSP type broad-range current transformers CSP type current sensors, designed for the Sepam 2000, work on the Rogowski coil principle. CSP sensors use a winding around an insulating core with no magnetic circuit, which prevents saturated and residual flux.Therefore, they are completely linear, and deliver an accurate secondary signal, a perfect image of the primary current, without distortion for both steady and transient states in the primary circuits. These sensors have much wider primary current ranges than current transformers do.The combining of CSP sensors and Sepam 2000 gives a consistent protection and measurement system. This in turn makes current sensor specification simpler (choosing from 3 sensors for a rated insulation level of 17.5 kV).

E72

965

Low voltage toroid type current transformersFor cubicles AD1-AD2 with one single-pole cableTransformer ARC2b single primary current, single secondary current for protectionb frequency 50-60 HzI1n (A) 75 100 150 200 250 300 400Ith (kA) 50 50 50 50 50 50 50t (s) 1 1 1 1 1 1 1protection 5P20 2.5 VA 2.5 VA 5 VA 5 VA 5 VA 5 VA 5 VA

b single primary current, double secondary current for measurement or protectionb frequency 50-60 HzI1n (A) 200 250 300 400 600Ith (kA) 50 50 50 50 50t (s) 1measuring protection

5 VA cl.1 10 VA cl.0.5 10 VA cl.0.5 15 VA cl.0.5 15 VA cl.0.55P20 2.5 VA 5 VA 5 VA 5 VA 5 VA

For cubicles AD1-AD2 with two single-pole cablesTransformer ARC3b single primary current, double secondary current for measurement or protectionb frequency 50-60 HzI1n (A) 750 1000 1250Ith (kA) 50 50 50t (s) 1measuring protection

cl.0.5 20 VA 30 VA 30 VA5P20 7.5 VA 10 VA 10 VA

E34

400

CSP sensor

Sensors Rated currentCSP 3110 30 to 300 ACSP 3210 160 to 640 ACSP 3310 160 to 1600 ACSP 3410 500 to 2500 A

For Sepam 2000, the primary current is chosen to be lower than the indicated range.

Cubicle type I rated Isc (kA) 1 s TypeAD1 - AD2 30 - 300 40 CSP 3110AD1 - AD2 CL1 - CL3

160 - 1250 50 CSP 3310CSP 3210

AD3 - CL3 500 - 2500 50 CSP 3410

CSP cannot be used with differential protection devices.They should be preferred in all other cases in which measurement and protection uses Sepam.

Page 31: Catalogo Mcset 1-17.5kv2005vacio

30

Protection, monitoring and control

0Instrument transformers(cont.)

Voltage transformersThese supply power to:b measuring, metering and monitoring devices;b relays or protective devices;b auxiliary LV sources for various types of switchgear; all these devices are protected and insulated from the MV section.They are installed at the bottom of the functional unit. In the withdrawable fuse version, the voltage transformers are attached to a side wall. The energized part is entirely encapsulated in an epoxy resin, which provides both electrical insulation and excellent mechanical strength.

They include the following models:b with one insulated MV terminal, for connection between neutral and phase conductors in three-phase systems with withdrawable MV fuses;b with two insulated MV terminals, for connection between phase conductors.

For cubicles AD1-CL1-GL1-TT1-AD2-CL2-GL2-AD3-CL3-GL3Transformer VRQ3n/S2b phase-earthb frequency 50-60 Hz

For cubicles AD2-CL2-GL2-TT2-AD3-CL3-GL3Transformer VRC1/S1Fb phase-phaseb frequency 50-60 Hz

E28

679

VRQ3

primary voltage (kV)

3/3 3.3/3 5.5/3 6/3 6.6/3 10/3 11/3 13.8/3 15/3

1st secondary voltage (V)

100/3 110/3 110/3 100/3 110/3 100/3 110/3 110/3 100/3

2nd secondary voltage (V)

100/3 110/3 110/3 100/3 110/3 100/3 110/3 110/3 100/3

1st secondary accuracy class (VA)

30-50 VA cl.0.5

2nd secondary accuracy class (VA)

50 VA cl.0.5

E28

680

VRC1/S1F

primary voltage (kV) 3.3 5.5 6.6 11 13.8 15secondary voltage (V) 110 110 110 110 110 100accuracy class (VA) 75 VA cl.0.5

Page 32: Catalogo Mcset 1-17.5kv2005vacio

31

Protection, monitoring and control

0Instrument transformers(cont.)

For cubicle AD1 contactor This transformer provides power to the coil in order to keep the magnetic circuit

of the contactor closed.

Transformer VRCR/S1b phase-phaseb frequency 50-60 Hz

MT

2010

4

VRCR

primary voltage (kV) 3.3 5.5 6.6secondary voltage (V) 110 110 110accuracy class (VA) 50 VA cl.0.5

E28

678

Zero sequence core balance current transformers (CSH type)CSH 120 and CSH 200 core balance CT’s, provide more sensitive protection by direct measurement of earth fault currents.Specifically designed for the Sepam range, they can be directly connected to the Sepam "residual current" input.They are only different in terms of their diameter:b CSH 120 - 120 mm internal diameter;b CSH 200 - 200 mm internal diameter.

CSH toroid CT

Page 33: Catalogo Mcset 1-17.5kv2005vacio

32

Switchgear Withdrawable parts 0

PE

5504

8

Extractiontable

Withdrawable part

Page 34: Catalogo Mcset 1-17.5kv2005vacio

33

Switchgear 0Withdrawable parts(cont.)

hese include:b the circuit-breaker or contactor, the disconnector truck or the earthing truck;b the lever-type propulsion mechanism for racking in-out;b interlocks to fix the withdrawable parts onto the fixed part.The live parts are housed in an insulating enclosure in the sealed pressure system in compliance with IEC 6271-100.

The devices used to equip the MCset range of functional units have outstanding features:b long service life;b maintenance-free live parts;b high electrical endurance;b operating safety;b insensitivity to the environment.

Withdrawable partsCircuit-breaker

Earthing truck

Disconnector truck

MT

2010

1

A circuit-breaker is a safety device enabling switching and protection of electrical distribution networks. Installed in the MCset cubicle, it protects all components situated downstream during a short-circuit.

MT

2010

2

The earthing truck is a safety feature which allows the cubicle busbar to be earthed. It is installed instead of the circuit-breaker and has the same interlock possibilities.

MT

2010

3

The disconnector truck enables the upper and lower part of the cubicle to be short-circuited. It is installed instead of the circuit-breaker and has the same interlock possibilities.

Page 35: Catalogo Mcset 1-17.5kv2005vacio

34

Switchgear 0Withdrawable partsEvolis circuit-breaker

PresentationThe Evolis circuit-breaker equips cubicles AD1-2-3 and CL1-2-3 at ratings of 7.2 kV to 17.5 kV.

High electrical enduranceA magnetic field is applied in the axis of the vacuum interrupter contacts. This process maintains the arc in diffused mode even at high current values. It ensures optimal dispersion of the energy over the contact surface and avoids localised temperature rise.

The advantages of this technique are:b a very compact vacuum interrupter;b low energy dissipation of the arc in the vacuum interrupters.

Evolis is in conformity with the highest electrical endurance class (IEC 60056: class E2).

High mechanical enduranceThe magnetic field is generated by a patented outside coil which surrounds the contact area. This solution has many advantages:b a simplified and therefore reliable vacuum interrupter unit;b heavy duty contacts which do not distort under repeated switching operations.

This is the first time that a low voltage device control mechanism has been used on a medium voltage circuit-breaker. The Masterpact control unit used on Evolis has the advantages of a system which has been proven for over 10 years in hundreds of thousands of installations.

Evolis is in conformity with the most demanding mechanical endurance class(IEC 60056: class M2).

Characterisitics of Evolis circuit-breakers in MCset cubiclesThe electrical characteristics are given on the circuit-breaker designation (rating plate).

E.g. (in grey in the table): 7 P1 630 (7.2 kV; 25 kA; 630 A)

MT

2010

5M

T20

106

xx Px xxxxRated current:

Breaking capacity:

Rated voltage:

630 (630 A)1250 (1250 A)2500 (2500 A)

1 (P1 = 25 kA)2 (P2 = 31.5 kA)3 (P3 = 40 kA)

7 (7.2 kV)12 (12 kV)17 (17.5 kV)

Evolis/ MCset 1

Evolis/MCset 2

Evolis/MCset 3

rated voltage kV 7.2 12 7.2 12 17.5 7.2 12 17.5insulation level kV rms 50 Hz - 1 mn 20 28 20 28 38 20 28 38

kV impulse 1.2/50 µs 60 75 60 75 95 60 75 95rated current A

630 b b b b b b b b

1250 b b b b b b b b

2500 b b b b b b b b b

breaking capacity kA 25 25 31.5 31.5 25 31.5 25 31.5 40 25 31.5 40 25 31.5 40short time withstand current kA rms 1 s 25 25 31.5 31.5 25 31.5 25 31.5 40 25 31.5 40 25 31.5 40short time withstand current kA rms 3 s 25 25 31,5 31.5 25 31.5 25 31.5 40 25 31.5 40 25 31.5 40capacitor breaking capacity A 400 400 400

rated operating sequence O - 0.3 s - FO - 15 s - FO

Page 36: Catalogo Mcset 1-17.5kv2005vacio

35

Switchgear 0Withdrawable partsEvolis circuit-breaker (cont.)

Operating mechanism descriptionEvolis range circuit-breakers are actuated by an Masterpact operating mechanism, that ensures a switching device closing and opening rate that is independent of the operator.This operating mechanism, which is always motorised, can perform remote control functions and enables fast reclosing cycles.This Masterpact operating mechanism includes:

mechanical devices: b an energy storage mechanism stores the energy required in the springs, to close and then to open the device;b a manual lever-controlled arming device; b an electric motor-controlled (MCH) arming device which automatically rearms the control unit as soon as the device is closed;. Re-arming time less than 4 s;b a mechanical opening and closing device using two push buttons situated on the front circuit-breaker panel which are accessible with the cubicle door open (circuit-breaker in the test position).For the door closed control unit (circuit-breaker racked in): the circuit-breaker can be opened by controlling the propulsor unit.

release units: b an electrical closing device (XF), comprising a closing release for remote control with an anti-pumping device;b an electrical opening device comprising one or several opening releases. The basic circuit-breaker equipment comprises a shunt trip unit (MX). This can be supplemented with the following options:v either a second shunt release unit (MX),v or an undervoltage release unit (MN),v or an undervoltage release unit with time delay (MN + delay unit).b a switching operation counter (CDM);b an indication contact for when the circuit-breaker is "Ready to close" (PF) - option;b an indication contact for when the circuit-breaker is "Ready to Function" (PAF) - option;b a position indicator for "open" "closed" through a mechanical "black-white" indicator;b a multipin connector to disconnect the auxiliary circuits in the "racked-out" position.

auxiliary contacts:b 4 changeover contacts are available;b 1 or 2 blocks of 4 changeover contacts can be added as an option.

Antipumping functionIn the case of latched opening and closing orders, the device is blocked in the open position.This function involves on one hand giving absolute priority to the opening order, but also and above all to stopping closing, in order to avoid the device being locked in an indefinite opening/closing cycle:b the opening and closing coils can be supplied power on a permanent basis in order to provide electrical interlocking: there is no internal self-breaking contact in the device.b interlocking between the opening and closing orders, for whatever reason, is achieved in a standard manner within the device’s control mechanism.

General diagram

MT

2010

9

MT

2010

8

OFPF

XFMX

CH

MCHOF OF

openingorder

closingorder

readyto close closed

Page 37: Catalogo Mcset 1-17.5kv2005vacio

36

Switchgear 0Withdrawable partsEvolis circuit-breaker (cont.)

Charging motor and associated mechanism (MCH)The MCH unit arms and rearms the energy storage springs as soon as the circuit-breaker is closed. This enables instant reclosing of the device after opening. The arming lever is only used as back up control in the absence of an auxiliary voltage.The MCH is equipped as standard with a CH limit switch. This contact indicates the "armed" position of the mechanism (spring armed).

Opening release on energising (MX)This causes the instantaneous opening of the circuit-breaker as soon as it is energised. Permanent power supply to the MX locks the circuit-breaker in the "open" position.The possibility of installing a second release as an option. This causes the instantaneous opening of the circuit-breaker as soon as the power is supplied, and can be supplied power on a permanent basis or on an impulse basis.

Closing release on energising (XF)This causes the circuit-breaker to close when the control unit is armed.

Switching operation counter (CDM)The switching operation counter is visible from the front panel. It gives a total number of switching cycles that the device has been through.

"Ready to close" contact (PF) - optionb the "ready to close" position of the circuit-breaker is indicated by a mechanical indicator and a PF changeover contact. b this information indicates simultaneously that:v the circuit-breaker is open,v the energy storage springs are armed.

The "ready to function" contact (PAF) - optionThis contact indicates that the circuit-breaker is locked in the "racked in" position.

MT

5516

5

Characteristics supply V AC 50/60 Hz 48/60 100/130 200/240

V DC 24/30 48/60 100/125 200/250threshold 0.85 to 1.1 Unconsumption (VA or W) 180motor overcurrent 2 to 3 In during 0.1 sarming time 4 s max.switching rate 3 cycles per minute max.mechanical endurance 10000 remote controlled opening operations

for 25 and 31.5 kA circuit-breaker5000 remote controlled opening operations for 40 kA circuit-breaker

CH contact 10 A to 240 V

MT

5516

4

Characteristics of MX - XF release unitspower supply V AC 50/60 Hz 24/30 48/60 100/130 200/250

V DC 24/30 48/60 100/130 200/250operating threshold (MX) 0.7 to 1.1 Unoperating threshold (XF) 0.85 to 1.1 Unconsumption (VA or W) pick-up: 200

latched: 4.5response time of the circuit-breaker at Un (MX)

50 ms ± 10

response time of the circuit-breaker at Un (XF)

70 ms ± 10 for 25 and 31.5 kA performance levels80 ms ± 10 for 40 kA performance level

MT

5516

9

00399

MT

5516

8

PF contact

MT

5518

0

PAF contact

Characteristicsbreaking capacity V AC 240/380 5 Acos j: 0.3 V DC 24/48 3 AAC12/DC12 125 0.3 A

250 0.15 Aminimum load: 10 mA/24 V

Characteristicsrated current 16 Abreaking capacity V AC 220 16 A (cos j: 0.4)

V DC 220 0.8 A (L/R y 40 ms)

Page 38: Catalogo Mcset 1-17.5kv2005vacio

37

Switchgear 0Withdrawable partsEvolis circuit-breaker (cont.)

Undervoltage release (MN) - optionThis release unit causes the instantaneous opening of the circuit-breaker when its supply voltage drops below a value of between 35 and 70% of its rated voltage. If the release unit is not supplied power, it is impossible to close (manually or electrically) the circuit-breaker. Any attempt to close the circuit-breaker causes no movement of the main contacts. Closing of the main circuit-breaker is authorised when the supply voltage of the release unit reaches 85% of its rated voltage.

Time delay for undervoltage release unit (MN) - optionIn order to eliminate spurious tripping of the circuit-breaker during short voltage sags (micro-outage), the action of the MN is time-delayed. This function is achieved by adding an external time delay unit on the MN voltage release unit (adjustable).The time delay unit placed outside of the circuit-breaker can be disabled by an emergency stop button in order to obtain instantaneous opening.

Auxiliary circuit-breaker position contacts - optionThese contacts indicate the "open" or "closed" position of the circuit-breaker. 1 or 2 blocks of 4 changeover contacts can be installed. 2 applications are available:b standard for a relayed application;b low level for the control of plc’s or electronic circuits. This version is compatible with Sepam 1000+.

Control unit spring disarming - optionThis option guarantees operator safety when the circuit-breaker’s front panel is removed from the MCset.

MT

5516

4

Characteristics power supply V AC 50/60 Hz 24/30 48/60 100/130 200/250

V DC 24/30 48/60 100/130 200/250operating threshold

opening 0.35 to 0.7 Unclosing 0.85 Un

consumption (VA or W) 20response time of the circuit-breaker at Un

90 ms ± 5

MT

5517

0

Characteristicspower supply V AC 50/60 Hz 48/60 100/130 200/250

V DC 48/60 100/130 200/250operating threshold

opening 0.35 to 0.7 Unclosing 0.85 Un

consumption (VA or W) 200response time of the circuit-breaker at Un

0.5 s - 0.9 s - 1.5 s - 3 s

MT

5516

7

Characteristicsbreaking capacity standard V AC 240/380 6 A 10/6cos j: 0.3 V DC 24/48 2.5 A 10/6AC12/DC12 125 0.5 A 10/6

250 0.3 A 3minimum load: 10 mA/24 V

low level V AC 24/48240 5 A 10/6380 5 A 3

V DC 24/48 5/2.5 A 10/6125 0.5 A 10/6250 0.3 A 3

minimum load: 1 mA/4 V

Page 39: Catalogo Mcset 1-17.5kv2005vacio

38

Switchgear 0Withdrawable partsVacuum type contactor

DescriptionThe vacuum type contactor comprises:b 3 vacuum interrupters (breaking);b an electromagnetic control unit which can be of:v magnetic latching type,v mechanical latching type.b upstream and downstream connection terminals for the power circuit;b mechanical contactor locking in the open position in order to avoid racking out or racking in with the contacts closed;b 3 HPC fuses with a striker and auxiliary contacts to trip the contactor;b the possibility of installing a transformer to provide an independent power supply for the contactor control unit (option);b an indicator on the front panel to show the contactor position (2);b a switching operation counter;b auxiliary contacts;b interchangeable with other contactors in the range (Rollarc).

Control unitSupply voltage (3)

ConsumptionClosing is achieved via the inrush coils. The latching coils are inserted in the circuit at the end of travel.

Auxiliary contacts The auxiliary contacts are of changeover type with a common point. The following are available :v 3 NO + 3 NC for the magnetic latching version,v 2 NO + 2 NC for the mechanical latching version.

Contact characteristics

MT

2010

7

Electrical characteristicsrated voltage kV (50/60 Hz) 7.2insulation level kV, rms 50 Hz - 1 mn 20

kV, impulse 1.2/50 µs 60operating current A 250 (1)

rated current A 400short time withstand current (kA rms 2 s) 8short time withstand current (kA rms 12 s) 4short time withstand current (kA rms 30 s) 2.4mechanical endurance (number of operations) 2 500 000 250 000 (2)

electrical endurance (number of operations) 250 000 250 000 (2)

(1) For greater values: please consult us.(2) Version with mechanical latching.

V DC: 110, 120 and 220 VV AC: 100, 110, 120 and 220 Vpossible variations: +10% -15%(3) Possibility of supplying power through an auxiliary transformer, optional (see page 31).

under 100-110 V inrush latchedwith magnetic latching 5 A 0.6 Awith mechanical latching 5.5 A —

operating voltage max. 480 V, min. 48 Vrated current 10 Abreaking capacity: V DC: 60 W (L/R 150 ms)

V AC: 700 VA (cos j 0.35)

Page 40: Catalogo Mcset 1-17.5kv2005vacio

39

Switchgear 0Withdrawable partsVacuum type contactor(cont.)

Maximum switchable powerCalculation assumptions (motor)b ratio between starting current Id and maximum current In: Id/In = 5 ± 20%;b power factor x efficiency0.88 x 0.9 = 0.792 for 300 < P < 600 kW0.9 x 0.92 = 0.828 for 600 < P < 1100 kW0.92 x 0.94 = 0.865 for 1100 < P < 5000 kW;b starting time < 10 s;b starts per hour y 3 according to IEC 60644.

FusesThe fuses used are of the Fusarc CF or Ferraz type (Standard IEC 60282.1 and DIN 43625) with high breaking capacity. Substantial fault current limitation reduces the electrodynamic stresses on the load-side components (contactor, cables, CT, etc).A "blown fuse" device is used to open the three poles of the contactor.

Schematic diagrams

E32

130

Figure 1

E32

151

Figure 2

Trip curvesThe trip curves for Fusarc CF (figure 1) and Ferraz (figure 2) fuses are shown above. These are the average curves with an rms current value tolerance I ± 10%.

E32

131 Figure 3

E32

152 Figure 4

Limitation curvesFusarc CF (figure 3) and Ferraz (figure 4) fuses have current limiting capacity. These curves give the maximum value of the limited breaking current Ic (in kA peak), as a function of the value Ip (in kA rms) of the presumed current that would be created if there were no protection. For further details, ask for the fuse catalogues.

Operating voltage (kV) Direct starting motor (kW)with 315 A fuses

Transformer (kVA)with 315 A fuses

Capacitor(kvar)with 315 A fuses

3.3 1170 1130 10004.16 1480 1420 12605 1780 1710 15205.5 1960 1880 16706 2130 2050 18206.6 2350 2250 2000

rated voltage (kV) 7.2max. fuse rating (A) 315*breaking capacity (kA) 50

* Higher values, please consult us.

Magnetic latching contactor

MT

2011

0

Contacteur à maintien magnétique

MT

2011

1

S4: release push buttonYD: release coilDU: control componentP61: switching operation counterYF: closing coil

K1: MV contactorS61: latching contactFU1: MV fusesXE: auxiliary control relayXU: auxiliary relay

DU

YF

X61

X20 32

21

33 4 1 3

6

5

4 1

2

2

3

10 21

YDXU

M2- C- C

M1+ C

Sepam

XE

XU

XEXE

verrouillage enclenchementclosinginterlock

S4

+ C

S61

P61 000O

FU1K1

K1

FU1

FU1

S61 K1

K1

K1

40 9 2036

7

- CM2- C

M1+ C + C

Sepam

XU XE

XE

XUXE

K1

P61

FU1

X61

X20 32

22

2122

21

33 4 1 3

4

5

6

1

2

2

3

K1

000ODU

YF

verrouillage enclenchementclosinginterlock

Page 41: Catalogo Mcset 1-17.5kv2005vacio

40

Switchgear Withdrawable part extraction 0

Extraction tableAdaptable to 3 cubicle widths, this extraction table enables:b the withdrawable part to be removed from the cubicle;b the withdrawable part to be fitted into the cubicle.

Extraction and lowering tool - optionAdaptable to 3 cubicle widths, this extraction tool enables:b the withdrawable part to be removed from the cubicle;b the withdrawable part to be introduced into the cubicle;b the withdrawable part to be lowered to the ground;b the withdrawable part to be lifted from the ground.

Racking handleThis handle enables:b the withdrawable part to be racked in/out;b the earthing switch to be open/closed.

MT

2011

2M

T20

113

MT

2011

4

Page 42: Catalogo Mcset 1-17.5kv2005vacio

41

Installation Implementation examples 0

MCset 1-2-3(7.2 to 17.5 kV)

Line up switchboard (2 supplies cubicles and 1 bussection)

DE

5507

5

Civil engineering with utility space (MCset 7.2 to 17.5 kV)

DE

5507

4

(1) Minimum dimensions to be complied with when installing the MCset switchboard.(2) Minimum dimensions to be defined according to the cable bending radius.(3) Operating distance.(4) Distance needed to extract a functional unit from the switchboard without moving the other units.(5) Provide an exhaust tunnel above the switchboard when the room height is less than 4 metres (see page 14).A anchor pointB adjustment pointNote: for further information, refer to the civil engineering, user and instruction manual.

500 570 570 900 900 900 900 570 570 570 500

2 feeders cubicle AD1

incomer cubicle AD3

bussection cubicles CL3/GL3

incomer cubicle AD3

3 feeders cubicle AD1

1520(3)

- 1720(4)

2500 2800(1) (1)(5)

1100

810 A420

200 1550

(2)

(1)B

room entrance

Page 43: Catalogo Mcset 1-17.5kv2005vacio

42

Installation Connections 0

Dry, single pole cableShort end piece, cold connectable

Dry, three-pole cableShort end piece, cold connectable

Connection possibilities using dry cables

E72

901R

Switchgear resistance to ageing in a substation depends on 3 key factorsb the need for correctly made connectionsNew cold connecting technologies offer easy installation and favour durability in time. Their design means they can be used in polluted environments with harsh atmospheres.b the impact of relative humidityThe installing of a heating element is essential in climates with high relative humidities and significant temperature differentials.b ventilation controlThe dimensions of air vents must be appropriate for the dissipated energy in the substation. They must only sweep across the transformer environment.

Cold connected terminalsSchneider Electric’s experience has led it to favour this technology wherever possible for optimum durability. The maximum acceptable cable cross-section for standard assemblies are: b 630 mm2 for incomer or feeder cubicles with single-pole cables;b 400 mm2 for incomer or feeder cubicles with three-pole cables;b 95 mm2 for transformer protection cubicles with fuses.Access to the compartment is only possible when the earthing switch is closed.Tightening torques for cables will be attained using a dynamo wrench set to 50 mN.

performance 3 to 17.5 kV - 400 A - 2500 Across section mm2 50 to 630 mm2

supplier all suppliers of cold connectable terminals: Silec, 3M, Pirelli, Raychem...

number of cables 1 to 8 per phasecomments for greater cross-section and number of cables, please consult us

performance 3 to 17.5 kV - 400 A - 2500 Across section mm2 50 to 400 mm2

supplier all suppliers of cold connectable terminals: Silec, 3M, Pirelli, Raychem...

number of cables 1 to 4 per phasecomments for greater cross-section and number of cables, please consult us

Number of cables AD1 AD1 cont. AD2 AD3 DI21 single per phase b (1) b (1) b (1) b2 single per phase b (1) b (1) b (1) b3 single per phase b b b b4 single per phase b1 three per cubicle b b b2 three per cubicle b b b b3 three per cubicle b b b b4 three per cubicle b

(1) Possibility of installing LV toroid transformers.

Page 44: Catalogo Mcset 1-17.5kv2005vacio

43

Installation Connections 0

(cont.)

MT

2011

7

Bottom cable connectionCable connection heightType of cubicle Configuration H (mm)

AD1 - AD2 630 A LV toroid CT 650 (1)

1 set of 3 CT’s 5002 sets of 3 CT’s 465

1250 A LV toroid CT 650 (1)

1 set of 3 CT’s 4802 sets of 3 CT’s 465

AD3 2500 A 1 set of 3 CT’s 4352 sets of 3 CT’s 435

DI2 450

(1) When installing with a LV core balance CT, use a LV core balance CT of type ARC3 when connecting with 2 cables (see page 31).

Figure 1

MT

2011

8

b The cubicles and cables requiring the maximum depth should be taken into consideration when determining the depth P of a switchboard cable duct (figure 1).b When using cables of length greater than 460 mm, install an additional compartment as marked (A) under the cubicle (figure 2).

Top cable connection (optional)

2 depths are available, function of the number of cables and the internal arc withstand of the cubicle: 2000 mm and 2275 mm.

Figure 2

DE

6017

3

Top busbar connection (optional, figure 3)

The cubicle depth is equal to 2000 mm, it can be equipped with 1 or 2 CT’s.

Figure 3

Page 45: Catalogo Mcset 1-17.5kv2005vacio

44

Appendices Cubicle equipment 0

Equipment Type of cubicleAD1 AD1

cont.AD2 AD3 CL1 CL2 CL3 GL1 GL2 GL3 TT1 TT2 DI2

Switchgearcircuit-breaker b b b b b bcontactor bfuse switch bdisconnector truck v v v v v vearthing truck v v v v v v vfixed busbars b b bracking position indication contact for the withdrawable part

3 NO + 3 NC b b b b b b b6 NO + 6 NC v v v v v v

padlocking of isolating shutters for withdrawable parts v v v v v v vlocking of withdrawable part/cable compartment v v v v v v vdisabling of circuit-breaker operating mechanism v v v v v vvoltage present indicator b b b b v v v b (1) b (1) blocking of mechanical racking of the withdrawable part (padlock) b b b b b b blocking of mechanical racking of the withdrawable part (keylock) v v v v v v vlocking of the electromagnetic racking of the withdrawable part v v v v v v v

Earthing switch (SMALT)earthing switch v v v v v v v v v bearthing switch position indication contacts 3 NO + 3 NF v (1) v (1) v (1) v (1) v (1) v (1) v (1) v (1) v (1) v (4)

earthing switch position key locking (2) v (1) v (1) v (1) v (1) v (1) v (1) v (1) v (1) v (1) velectromagnetic earthing switch position locking v v v v v v v v v

Transformersvoltage transformers(1 per phase)

without fuse phase-phase v v v v v v vphase-earth v v v v v v v v v v v

with plug-in fuses phase-phase v v v v v v vphase-earth v v v v v v v v v v v

fuse melting indication contact 1 NO v v v v v v v v v v vcurrent transformer single set 3 CT’s v v v v v v v v v v

double set 6 CT’s v v v vLV toroid transformer CT (3) v v v

Connectionsconnection with cable terminal height > 460 mm v v v v vconnection from top bar v v v vconnection by cable from the top v v v vconnection by cable from the bottom b b b b b

Cubicleprotection index enclosure IP3X b b b b b b b b b b b b b

IP4X b b b v b b v b b v b b bIPX1 v v v v v v v v v v v v v

compartments (5) IP2XC b b b b b b b b b b b b banti-arcing protection (2) 25 kA - 1 s v v v v v v v v v v v v v

40 kA - 1 s v v v v v v v vlightning arrester v v v v v v v v v

Busbars1250 A/2500 A exposed b b b b b b b b b b b b b

insulated v v v v v v v v v v v v vLV control cabinet key locking v v v v v v v v v v v v vLV control cabinet lighting v v v v v v v v v v v v vanti-condensation heating element v v v v v v v v v v

key:b: basic equipmentv: option(1) basic equipment with earthing switch option.(2) according to the room in which the MCset switchboard is installed, you can choose option 3 or 4 sides, and possibly an exhaust tunnel for hot gases (see page 14).(3) Connection 1 or 2 cables per phase.(4) 1 NO + 1 NC available.(5) Compartment protection.

Page 46: Catalogo Mcset 1-17.5kv2005vacio

45

Appendices Current transformers (Selection guide) 0

Preferred current transformers: 7.2 to 17.5 kV secondary 1 A or 5 A

Type of cubicle Accuracy classand ratio

AD1 AD1 fuse- contactor

AD2 AD2 AD3CL3

CL1 CL2

Isc kA 1 s 31,5 NA (1) 40 50 50 31,5 50ratio number 1accuracy classand ratio

40-80/1 or 52.5-5 VA - 5P20

v 10/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v

50-100/1-52.5-5 VA - 5P20

v 20/1-12.5 VA - 5P2015 VA - cl 0.5

v v

75-150/1 or 52.5-5 VA - 5P20

v 30/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v v

100-200/1-1 or 5-52.5-5 VA - 5P20

v 40/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v v

150-300/1-1 or 5-52.5-5 VA - 5P2010-20 VA - cl 0.5

v 50/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v v

200-400/1-1 or 5-55-10 VA - 5P207.5-15 VA - cl 0.5

v 75/1-1 or 5/52.5 VA - 5P2015 VA - cl 0.5

v v

250-500/1-1 or 5-55-10 VA - 5P2010-20 VA - cl 0.5

v 100/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v v

600/1-1 or 5-57.5 VA - 5P2020 VA - cl 0.5

v 150/1-1 or 5-57.5 VA - 5P1015 VA - cl 0.5

v v v v v

750/1-1 or 5-57.5 VA - 5P2020 VA - cl 0.5

v 200/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v v v v v

1000/1-1 or 5-510 VA - 5P2030 VA - cl 0.5

v 250/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v v v v v

1250/1-1 or 5-510 VA - 5P2030 VA - cl 0.5

v 300/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v v v v v

1500/1-1 or 5-515 VA - 5P2030 VA - cl 0.5

400/1-1 or 5-52.5 VA - 5P2015 VA - cl 0.5

v

2000/1-1 or 5-515 VA - 5P2030 VA - cl 0.5

v

2500/1-1 or 5-515 VA - 5P20 30 VA - cl 0.5

v

(1) Short-circuit current withstand is co-ordinated with the current limited through the fuses.Other characteristics are available, including the possibility of having 3 secondary windings. Please consult us detailing the type of protection or measuring required as well as the impedance of the outside loads and the cabling.

Page 47: Catalogo Mcset 1-17.5kv2005vacio

46

A few references MCset, a product for all your electrical distribution applications

MA

PP

Energyb EPM, Colombiab CHE-POIANA-TEIULUI, Roumania

Infrastructureb Heathrow airport, United Kingdomb commercial building, ATIRAU, Azerbaijan

Industryb steel, SIDMAR, Belgiumb steel, SMS DEMAG, Chileb paper, SOPORCEL, Portugalb water, LATTAKIA-WATER, Syriab water, KHARAMA, Algeriab water, GAZIANTEP DSI, Turkeyb oil, SHELL, Netherlandsb oil, SHELL, Bruneib oil, SHELL, Nigeriab automotive, FORD KOLN, Germanyb chemistry, AMMONIA UREA, Turkmenistanb petrochemistry, TEKFEN AIOC, Azerbaijanb petrochemistry, TURKMENBASHI, Azerbaïdjanb wood, ÇAMSAN, Turkey

E74

223

E74

226

Page 48: Catalogo Mcset 1-17.5kv2005vacio

47

Appendices Personal notes 0

Page 49: Catalogo Mcset 1-17.5kv2005vacio

48

Appendices Personal notes 0

Page 50: Catalogo Mcset 1-17.5kv2005vacio

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

Publishing: Schneider Electric SAProduction: SEDOC-HeadLinesPrinting: Imprimerie du Pont de Claix

Schneider Electric Industries SAS

ART 25091 11-04

AM

TE

D30

1014

EN

© 2

004

Sch

neid

er E

lect

ric -

All

right

s re

serv

ed

89 boulevard F. RooseveltF-92500 Rueil MalmaisonFranceTel: +33 (0)1 41 29 85 00Fax : +33 (0)1 41 29 89 01http://www.schneider-electric.com

RSC Nanterre B 954 503 439