Catalogo Delixi

112
Low Voltage Electrical Appliance “Right Quality, Right Price” International Catalogue 2009

description

Catalogo Delixi

Transcript of Catalogo Delixi

Page 1: Catalogo Delixi

Low Voltage Electrical Appliance “Right Quality, Right Price”

International Catalogue 2009

Page 2: Catalogo Delixi

A global company at your serviceDelixi was founded in 1984 in Zhejiang province with salesover 1,5BM€, employing more than 15000 people.

Delixi created an international Joint Venture in November2007,named Delixi Electric LTD,in order to serve youworldwide,with core LV products having the right qualityat the right price.

Our products are designed for Residential / Building /Energy / infrastructure and Industrial markets . DelixiElectric employs 5200 people world wide.

A reliable company serving you withreliable product

Delixi Electric: Who are we

Dedicated R&D center

International quality control of suppliers

International quality control of plants

Fully automatized distribution center

Clear warranty policy

Network of recognized 600 distributorsworld wide

Page 3: Catalogo Delixi

Reliable quality

You can trust 100% our products. We offer you a 18 months warranty. During this period oftime, we will replace any defected product you may have, provided the responsibility is ours.

For more details, please contact your local Delixi Electric Company.

Page 4: Catalogo Delixi

Delixi Electric Pakistan73 / B / 3 , Race View,Jail Road,Lahore, 54000,PakistanTel 0092 - 42 - 7570412 / 7570443 , extension 100/103Fax 0092 - 42 - 7570443 , extension 108Contact : Syed Sohail IDREESMobile : 0092 [email protected]

Delixi Elecric Austral AfricaCanon Crescan Drive , RoodekopGermiston, 1400PO Box 13151 , Elspark, 1418Mobile : +27 (0) 836438898www.delixi-electric.co.zaContact : Vicky [email protected]

Delixi Electric Middle-EastRAK Free trade zonePO BOX 10559Ras El KhaimaUnited Arab EmiratesTel : +971 ( 7 ) 244 47 27Fax : + 971 ( 7 ) 244 27 [email protected] : Raja BHAUMIKMobile : +971 ( 50 ) 657 [email protected]

Delixi Electric Marocco213 Centre YousraRond-point d’EuropeCasablanca, Maroctel : +212 (0) 22 268 161Fax : +212 (0) 22 491342Contact : Hicham MOUKIMobile : +212 (0) 61 100 [email protected]

Delixi Electric South East Europe20 Tsar Samuil str . , 1rst FloorTriaditsa MunicipalitySofiaBulgariaContact : Doychin ZAHARINOVMobile : +359 885 750 [email protected]

A company to serve you where you are

We set up companies in many countries in order to deliver best in classlocal availability and support .

Delixi Elecric ChinaDelixi Liushi Industrial Park,Yueqing,Zhejiang,P.R.ChinaPost Code:325604www.delixi-electric.com

Delixi Electric IsraelIndustrial park cibleHamelaha st.22Rosh ha-aiynIsraeltel:+972546798718Contact : Hayim COHENemail:[email protected]

Delixi Electric West Africa1 Tunde Gaffar CloseOff Adeniyi JonesIkejaLagosNigeriaFax : + 234 2703941Contact : Chidiebere NWORGUMobile : +234 703 41 111 [email protected]

Delixi Electric South East AsiaP.O.Box 7567Pejabat Post Besar Shah Alam40720 Shah AlamSelangor Darul EhsanTel:03- 78809564Fax: 03-78809540Contact: Ellis LeeEmail : [email protected]

Delixi Electric ArgentinaContact : Damian CattainoMobile : +54111545658952

Delixi Electric EgyptContact : Mohamed NagyMobile 20(0) 100705454

Delixi Electric Saudi ArabiaContact : Mohkam SheikhMobile : +966050269801

Page 5: Catalogo Delixi

Power Distribution

Industry Control

Product Panorama

Page 6: Catalogo Delixi

ContentsMCB Miniature Circuit BreakersCDB6a 18mm Miniature Circuit Breakers 1

CDB6L 18mm Miniature Circuit Breakers 3

CDB6N 18mm Miniature Circuit Breakers 5

CDB6&CDB6LE Electrical Auxiliaries 7

CDB17 Miniature Circuit Breakers 8

CDB3 Phase-neutral Circuit Breakers 10

CDB2 27mm Miniature Circuit Breakers 11

CDB5 Switch Disconnectors 13

RCBO Residual Current Operated Circuit Breakers WithIntegral Overcurrent ProtectionCDB6LE Electronic Type Residual Current Operated Circuit Breakers 15

CDB3LE Electronic Type Residual Current Operated Circuit Breakers 17

CDB2LE Electronic Type Residual Current Operated Circuit Breakers 18

CDB7LSP Electronic Type Residual Current Operated Circuit Breakers 20

RCCB Residual Current Operated Circuit BreakersWithout Overcurrent ProtectionCDL7 Electromagnetic Type Residual Current Switches 21

Surge ProtectorCDY1 Surge Protective Devices 22

MCB Distribution BoardCDPZ50 Distribution Box 25

MeterDDS607 Single-phase Electronic Watt-hour Meters

MCCB Moulded Case Circuit BreakersCDM1 Moulded Case Circuit Breakers 29

ELCB Earth-leakage Circuit BreakersCDM1L Moulded Case Circuit Breakers With Electronic Type Residual Current

Operated Protection 36

27

Page 7: Catalogo Delixi

ACB Air Circuit BreakerCDW7 Air Circuit Breaker 42

ContactorsCDC17 AC Contactor 61

RelaysCDR17 Thermal overload relays 70

Current TransformerLMK Current Transformer 73

FuseRT16 Fuse 76

RT18 Fuse 78

Power Distribution BoxJXF Power Distribution Box 80

Control SignalLD11 Series of indicator light 82

LAY3 Serie of pushbuttons 86

LAY7 Serie of pushbuttons 88

LAY8 Serie of pushbuttons 93

Pannel Meter72 Series Pannel Meter 96

96 Series Pannel Meter 98

Voltage StabilizerTND Voltage Stabilizer 100

Nylon LockNylon Cable Ties Series 102

Page 8: Catalogo Delixi

Delixi Electric 1

Function CDB6a miniature circuit breakers combine the following functions:Protection of circuits against overload currentsProtection of circuits against short-circuit currentsControlIsolation

Rated current: 1, 3, 6, 10, 16, 20, 25, 32, 40, 50, 63 ARated voltage: 230/400V ACBreaking capacity

Tropicalization: treatment 2Protection degree: 2Connection:up to 25mm2 cablesTripping curves:B curve: the magnetic release operates between 3 and 5 InC curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 In35 mm standard DIN rail mounting

Description Technical data

CDB6aStandard: IEC 60898-1 IEC 60947-2Trip Curve: B, C and D curvesBreaking Capacity: 3000A

Overall dimensionsUnit:mm

Voltage(V)230400230400230400

Ratecurrent1-63A

Type

B

C

D

Poles

1P2P, 3P, 4P1P2P, 3P, 4P1P2P, 3P, 4P

Breaking capacityIcn (A)3000

Standard and certificationIEC 60898-1 IEC 60947-2KEMA, CB

Page 9: Catalogo Delixi

Delixi Electric2

CDB6aStandard: IEC 60898-1 IEC 60947-2Trip Curve: B, C and D curvesBreaking Capacity: 3000A

Type Rating(A)

Width(in mod.of 9mm)

1361016202532405063

22222222222

1P

1361016202532405063

44444444444

2P

1361016202532405063

66666666666

3P

D curveCDB6a1D1CDB6a1D3CDB6a1D6CDB6a1D10CDB6a1D16CDB6a1D20CDB6a1D25CDB6a1D32CDB6a1D40CDB6a1D50CDB6a1D63CDB6a2D1CDB6a2D3CDB6a2D6CDB6a2D10CDB6a2D16CDB6a2D20CDB6a2D25CDB6a2D32CDB6a2D40CDB6a2D50CDB6a2D63CDB6a3D1CDB6a3D3CDB6a3D6CDB6a3D10CDB6a3D16CDB6a3D20CDB6a3D25CDB6a3D32CDB6a3D40CDB6a3D50CDB6a3D63

ReferenceB curveCDB6a1B1CDB6a1B3CDB6a1B6CDB6a1B10CDB6a1B16CDB6a1B20CDB6a1B25CDB6a1B32CDB6a1B40CDB6a1B50CDB6a1B63CDB6a2B1CDB6a2B3CDB6a2B6CDB6a2B10CDB6a2B16CDB6a2B20CDB6a2B25CDB6a2B32CDB6a2B40CDB6a2B50CDB6a2B63CDB6a3B1CDB6a3B3CDB6a3B6CDB6a3B10CDB6a3B16CDB6a3B20CDB6a3B25CDB6a3B32CDB6a3B40CDB6a3B50CDB6a3B63

C curveCDB6a1C1CDB6a1C3CDB6a1C6CDB6a1C10CDB6a1C16CDB6a1C20CDB6a1C25CDB6a1C32CDB6a1C40CDB6a1C50CDB6a1C63CDB6a2C1CDB6a2C3CDB6a2C6CDB6a2C10CDB6a2C16CDB6a2C20CDB6a2C25CDB6a2C32CDB6a2C40CDB6a2C50CDB6a2C63CDB6a3C1CDB6a3C3CDB6a3C6CDB6a3C10CDB6a3C16CDB6a3C20CDB6a3C25CDB6a3C32CDB6a3C40CDB6a3C50CDB6a3C63

88888888888

4P CDB6a4D1CDB6a4D3CDB6a4D6CDB6a4D10CDB6a4D16CDB6a4D20CDB6a4D25CDB6a4D32CDB6a4D40CDB6a4D50CDB6a4D63

CDB6a4B1CDB6a4B3CDB6a4B6CDB6a4B10CDB6a4B16CDB6a4B20CDB6a4B25CDB6a4B32CDB6a4B40CDB6a4B50CDB6a4B63

CDB6a4C1CDB6a4C3CDB6a4C6CDB6a4C10CDB6a4C16CDB6a4C20CDB6a4C25CDB6a4C32CDB6a4C40CDB6a4C50CDB6a4C63

1361016202532405063

Tripping Curve

B C D

Page 10: Catalogo Delixi

Delixi Electric 3

CDB6LStandard: IEC 60947-2 IEC 60898-1Trip Curve: B, C and D curvesBreaking Capacity: 4500A

Function CDB6L miniature circuit breakers combine the following functions:Protection of circuits against overload currentsProtection of circuits against short-circuit currentsControlIsolation

Rated current: 1, 3, 6, 10, 16, 20, 25, 32, 40, 50, 63 ARated voltage: 230/400V ACBreaking capacity:

Description Technical data

Tropicalization: treatment 2Protection degree: 2Connection:up to 25mm2 cablesTripping curves:B curve: the magnetic release operates between 3 and 5 InC curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 In35 mm standard DIN rail mounting

Standard and certificationIEC 60947-2 IEC 60898-1KEMA, CB

Overall dimensionsUnit:mm

Voltage(V)

230400230400230400230400230400230400

1P

2P, 3P, 4P

1P

2P, 3P, 4P

1P

2P, 3P, 4P

Breaking capacityIcn (A)

450045004500450045004500450045004500450045004500

Ratecurrent

1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A

Type

B

C

D

Poles

Page 11: Catalogo Delixi

Delixi Electric4

CDB6LStandard: IEC 60947-2 IEC 60898-1Trip Curve: B, C and D curvesBreaking Capacity: 4500A

1P

2P

3P

1361016202532405063

22222222222

1361016202532405063

44444444444

1361016202532405063

66666666666

D curveCDB6L1D1CDB6L1D3CDB6L1D6CDB6L1D10CDB6L1D16CDB6L1D20CDB6L1D25CDB6L1D32CDB6L1D40CDB6L1D50CDB6L1D63CDB6L2D1CDB6L2D3CDB6L2D6CDB6L2D10CDB6L2D16CDB6L2D20CDB6L2D25CDB6L2D32CDB6L2D40CDB6L2D50CDB6L2D63CDB6L3D1CDB6L3D3CDB6L3D6CDB6L3D10CDB6L3D16CDB6L3D20CDB6L3D25CDB6L3D32CDB6L3D40CDB6L3D50CDB6L3D63

C curveCDB6L1C1CDB6L1C3CDB6L1C6CDB6L1C10CDB6L1C16CDB6L1C20CDB6L1C25CDB6L1C32CDB6L1C40CDB6L1C50CDB6L1C63CDB6L2C1CDB6L2C3CDB6L2C6CDB6L2C10CDB6L2C16CDB6L2C20CDB6L2C25CDB6L2C32CDB6L2C40CDB6L2C50CDB6L2C63CDB6L3C1CDB6L3C3CDB6L3C6CDB6L3C10CDB6L3C16CDB6L3C20CDB6L3C25CDB6L3C32CDB6L3C40CDB6L3C50CDB6L3C63

ReferenceB curveCDB6L1B1CDB6L1B3CDB6L1B6CDB6L1B10CDB6L1B16CDB6L1B20CDB6L1B25CDB6L1B32CDB6L1B40CDB6L1B50CDB6L1B63CDB6L2B1CDB6L2B3CDB6L2B6CDB6L2B10CDB6L2B16CDB6L2B20CDB6L2B25CDB6L2B32CDB6L2B40CDB6L2B50CDB6L2B63CDB6L3B1CDB6L3B3CDB6L3B6CDB6L3B10CDB6L3B16CDB6L3B20CDB6L3B25CDB6L3B32CDB6L3B40CDB6L3B50CDB6L3B63

Type Rating(A)

Width(in mod.of 9mm)

4P 1361016202532405063

88888888888

CDB6L4D1CDB6L4D3CDB6L4D6CDB6L4D10CDB6L4D16CDB6L4D20CDB6L4D25CDB6L4D32CDB6L4D40CDB6L4D50CDB6L4D63

CDB6L4C1CDB6L4C3CDB6L4C6CDB6L4C10CDB6L4C16CDB6L4C20CDB6L4C25CDB6L4C32CDB6L4C40CDB6L4C50CDB6L4C63

CDB6L4B1CDB6L4B3CDB6L4B6CDB6L4B10CDB6L4B16CDB6L4B20CDB6L4B25CDB6L4B32CDB6L4B40CDB6L4B50CDB6L4B63

Tripping Curve

B C D

Page 12: Catalogo Delixi

Delixi Electric 5

Standard: IEC 60947-2 IEC 60898-1Trip Curve: B, C and D curvesBreaking Capacity: 6000A

Function CDB6N miniature circuit breakers combine the following functions:Protection of circuits against overload currentsProtection of circuits against short-circuit currentsControlIsolation

Rated current: 1, 3, 6, 10, 16, 20, 25, 32, 40, 50, 63 ARated voltage: 230/400V ACBreaking capacity:

Description Technical data

CDB6N

Tropicalization: treatment 2Protection degree: 2Connection:up to 25mm2 cablesTripping curves:B curve: the magnetic release operates between 3 and 5 InC curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 In35 mm standard DIN rail mounting

Standard and certificationIEC 60947-2 IEC 60898-1KEMA, CB

Overall dimensionsUnit:mm

Voltage(V)230400230400230400230400230400230400

1P

2P, 3P, 4P

1P

2P, 3P, 4P

1P

2P, 3P, 4P

Breaking capacityIcn (A)600045006000450060004500600045006000450060004500

Ratecurrent1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A

Type

B

C

D

Poles

Page 13: Catalogo Delixi

Delixi Electric6

Standard: IEC 60947-2 IEC 60898-1Trip Curve: B, C and D curvesBreaking Capacity: 6000A

Type

1P

CDB6N

2P

3P

4P

Rating(A)

Width(in mod.of 9mm)

1361016202532405063

22222222222

1361016202532405063

44444444444

1361016202532405063

66666666666

1361016202532405063

88888888888

D curveCDB6N1D1CDB6N1D3CDB6N1D6CDB6N1D10CDB6N1D16CDB6N1D20CDB6N1D25CDB6N1D32CDB6N1D40CDB6N1D50CDB6N1D63CDB6N2D1CDB6N2D3CDB6N2D6CDB6N2D10CDB6N2D16CDB6N2D20CDB6N2D25CDB6N2D32CDB6N2D40CDB6N2D50CDB6N2D63CDB6N3D1CDB6N3D3CDB6N3D6CDB6N3D10CDB6N3D16CDB6N3D20CDB6N3D25CDB6N3D32CDB6N3D40CDB6N3D50CDB6N3D63CDB6N4D1CDB6N4D3CDB6N4D6CDB6N4D10CDB6N4D16CDB6N4D20CDB6N4D25CDB6N4D32CDB6N4D40CDB6N4D50CDB6N4D63

C curveCDB6N1C1CDB6N1C3CDB6N1C6CDB6N1C10CDB6N1C16CDB6N1C20CDB6N1C25CDB6N1C32CDB6N1C40CDB6N1C50CDB6N1C63CDB6N2C1CDB6N2C3CDB6N2C6CDB6N2C10CDB6N2C16CDB6N2C20CDB6N2C25CDB6N2C32CDB6N2C40CDB6N2C50CDB6N2C63CDB6N3C1CDB6N3C3CDB6N3C6CDB6N3C10CDB6N3C16CDB6N3C20CDB6N3C25CDB6N3C32CDB6N3C40CDB6N3C50CDB6N3C63CDB6N4C1CDB6N4C3CDB6N4C6CDB6N4C10CDB6N4C16CDB6N4C20CDB6N4C25CDB6N4C32CDB6N4C40CDB6N4C50CDB6N4C63

ReferenceB curveCDB6N1B1CDB6N1B3CDB6N1B6CDB6N1B10CDB6N1B16CDB6N1B20CDB6N1B25CDB6N1B32CDB6N1B40CDB6N1B50CDB6N1B63CDB6N2B1CDB6N2B3CDB6N2B6CDB6N2B10CDB6N2B16CDB6N2B20CDB6N2B25CDB6N2B32CDB6N2B40CDB6N2B50CDB6N2B63CDB6N3B1CDB6N3B3CDB6N3B6CDB6N3B10CDB6N3B16CDB6N3B20CDB6N3B25CDB6N3B32CDB6N3B40CDB6N3B50CDB6N3B63CDB6N4B1CDB6N4B3CDB6N4B6CDB6N4B10CDB6N4B16CDB6N4B20CDB6N4B25CDB6N4B32CDB6N4B40CDB6N4B50CDB6N4B63

Tripping Curve

B C D

Page 14: Catalogo Delixi

Delixi Electric 7

CDB6&CDB6LE Electrical Auxiliaries

OF contact auxiliary

ReferenceCDB6OF230ACCDB6OF400ACCDB6OF24DCCDB6OF48DCCDB6OF110DCCDB6OF220DCCDB6SD230ACCDB6SD400ACCDB6SD24DCCDB6SD48DCCDB6SD110DCCDB6SD220DCCDB6MX230ACCDB6MX24AC

VoltageAC230AC400DC24DC48DC110DC220AC230AC400DC24DC48DC110DC220AC230DC24

TypeOF

SD

MX+OF*

SD fault-indicating switch

MX+OF shunt trip release

Page 15: Catalogo Delixi

Delixi Electric8

CDB17Standard: IEC 60898-1Trip Curve: B, C and D curvesBreaking Capacity: 6000A

Function CDB17N miniature circuit breakers combine the following functions:Protection of circuits against overload currentsProtection of circuits against short-circuit currentsControlIsolation

Rated current: 1, 3, 6, 10, 16, 20, 25, 32, 40, 50, 63 ARated voltage: 230/400V ACBreaking capacity

Tropicalization: treatment 2Protection degree: 2Connection:up to 25mm2 cablesTripping curves:B curve: the magnetic release operates between 3 and 5 InC curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 In35 mm standard DIN rail mounting

Description Technical data

Standard and certification IEC 60898-1KEMA, CB, CE

Overall dimensionsUnit:mm

Voltage(V)230400230400230400

6000

Poles

1P2P,3P,4P1P2P,3P,4P1P2P,3P,4P

Type

B

C

D

Ratecurrent1-63A

Breaking capacityIcn (A)

Page 16: Catalogo Delixi

Delixi Electric 9

1P

2P

3P

4P

1361016202532405063

22222222222

1361016202532405063

44444444444

1361016202532405063

66666666666

1361016202532405063

88888888888

D curveCDB17N1D1CDB17N1D3CDB17N1D6CDB17N1D10CDB17N1D16CDB17N1D20CDB17N1D25CDB17N1D32CDB17N1D40CDB17N1D50CDB17N1D63CDB17N2D1CDB17N2D3CDB17N2D6CDB17N2D10CDB17N2D16CDB17N2D20CDB17N2D25CDB17N2D32CDB17N2D40CDB17N2D50CDB17N2D63CDB17N3D1CDB17N3D3CDB17N3D6CDB17N3D10CDB17N3D16CDB17N3D20CDB17N3D25CDB17N3D32CDB17N3D40CDB17N3D50CDB17N3D63CDB17N4D1CDB17N4D3CDB17N4D6CDB17N4D10CDB17N4D16CDB17N4D20CDB17N4D25CDB17N4D32CDB17N4D40CDB17N4D50CDB17N4D63

C curveCDB17N1C1CDB17N1C3CDB17N1C6CDB17N1C10CDB17N1C16CDB17N1C20CDB17N1C25CDB17N1C32CDB17N1C40CDB17N1C50CDB17N1C63CDB17N2C1CDB17N2C3CDB17N2C6CDB17N2C10CDB17N2C16CDB17N2C20CDB17N2C25CDB17N2C32CDB17N2C40CDB17N2C50CDB17N2C63CDB17N3C1CDB17N3C3CDB17N3C6CDB17N3C10CDB17N3C16CDB17N3C20CDB17N3C25CDB17N3C32CDB17N3C40CDB17N3C50CDB17N3C63CDB17N4C1CDB17N4C3CDB17N4C6CDB17N4C10CDB17N4C16CDB17N4C20CDB17N4C25CDB17N4C32CDB17N4C40CDB17N4C50CDB17N4C63

ReferenceB curveCDB17N1B1CDB17N1B3CDB17N1B6CDB17N1B10CDB17N1B16CDB17N1B20CDB17N1B25CDB17N1B32CDB17N1B40CDB17N1B50CDB17N1B63CDB17N2B1CDB17N2B3CDB17N2B6CDB17N2B10CDB17N2B16CDB17N2B20CDB17N2B25CDB17N2B32CDB17N2B40CDB17N2B50CDB17N2B63CDB17N3B1CDB17N3B3CDB17N3B6CDB17N3B10CDB17N3B16CDB17N3B20CDB17N3B25CDB17N3B32CDB17N3B40CDB17N3B50CDB17N3B63CDB17N4B1CDB17N4B3CDB17N4B6CDB17N4B10CDB17N4B16CDB17N4B20CDB17N4B25CDB17N4B32CDB17N4B40CDB17N4B50CDB17N4B63

Type Rating(A)

Width(in mod.of 9mm)

CDB17Standard: IEC 60898-1Trip Curve: B, C and D curvesBreaking Capacity: 6000A

Tripping Curve

B C D

Page 17: Catalogo Delixi

Delixi Electric10

Function CDB3 phase-neutral circuit breakers combine the following functions:Protection of circuits against overload currentsProtection of circuits against short-circuit currentsControlIsolation

Rated current: 6, 10, 16, 20, 25, 32ARated voltage: 230V ACBreaking capacity: 3 kATripping curves:C curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 InTropicalization: treatment 2Protection degree: 2ConnectionUp to 16mm2 cables35mm standard DIN rail mounting

Description Technical data

Overall dimensions

Type Rating(A)

Width(in mod.of 9mm)

ReferenceC curve D curve

61016202532

222222

CDB3a5C6CDB3a5C10CDB3a5C16CDB3a5C20CDB3a5C25CDB3a5C32

CDB3a5D6CDB3a5D10CDB3a5D16CDB3a5D20CDB3a5D25CDB3a5D32

1P+N

CDB3Standard: IEC 60898-1Trip Curve: C and D curvesBreaking Capacity: 3000A

Standard and certificationIEC 60898-1

C D

Tripping Curve

Page 18: Catalogo Delixi

Delixi Electric 11

Function CDB2 miniature circuit breakers combine the following functions:Protection of circuits against overload currentsProtection of circuits against short-circuit currents

ControlIsolation

Description Technical dataRated current: 63, 80, 100, 125 ARated voltage : 230/400V ACBreaking capacity

CDB2Standard: IEC 60947-2Trip Curve: C and D curvesBreaking Capacity: 10000A

Standard and certification IEC 60947-2SEMKO, CE

Overall dimensions

Tripping curves:C curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 InMechanical durability: 8,500 (In 100A) / 7,000 (In=125A)Electrical durability: 1,500 (In 100A) / 1,000 (In=125A)Tropicalization: treatment 2Protection degree: 2ConnectionUp to 50 mm2 cables35mm standard DIN rail mountingClosed position indication

TypeRating(A)

Voltage(V)

Breaking capacity(kA)

63 ~125 230400

1010

1P2/3/4P

Unit:mm

Page 19: Catalogo Delixi

Delixi Electric12

CDB2Standard: IEC 60947-2Trip Curve: C and D curvesBreaking Capacity: 10000A

Type Rating(A)

Width(in mod.of 9mm)

ReferenceC curve D curve

6380100125

3333

CDB2H1C63CDB2H1C80CDB2H1C100CDB2H1C125

CDB2H1D63CDB2H1D80CDB2H1D100CDB2H1D125

1P

6380100125

6666

2P

6380100125

9999

3P

6380100125

12121212

4P

CDB2H2C63CDB2H2C80CDB2H2C100CDB2H2C125

CDB2H2D63CDB2H2D80CDB2H2D100CDB2H2D125

CDB2H3C63CDB2H3C80CDB2H3C100CDB2H3C125

CDB2H3D63CDB2H3D80CDB2H3D100CDB2H3D125

CDB2H4C63CDB2H4C80CDB2H4C100CDB2H4C125

CDB2H4D63CDB2H4D80CDB2H4D100CDB2H4D125

C D

Tripping Curve

Page 20: Catalogo Delixi

Delixi Electric 13

Function CDB5 switch disconnectors combine the following functions:Making and breaking normal load circuitsIsolation

Rated current: 20, 32, 63, 100 ARated voltage: 230/400V ACMechanical durability: 8500Electrical durability: 1500Short-time withstand capacity for 1 s: 12IeTropicalization: treatment 2Protection degree: 2ConnectionUp to 35 mm2 cables35 mm standard DIN rail mountingIsolation with positive break indication

Description Technical data

CDB5Standard: IEC 60947-3

Overall dimensions

Standard and certificationIEC 60947-3

Unit:mm

Page 21: Catalogo Delixi

Delixi Electric14

CDB5Standard: IEC 60947-3

Type Rating(A)

Voltage(V AC)

Reference

1P

2P

3P

4P

Width(in mod.of 9mm)

203263100

230230230230

2222

400400400400

4444

203263100

400400400400

6666

203263100

400400400400

8888

CDB5120CDB5132CDB5163CDB51100

CDB5220CDB5232CDB5263CDB52100

CDB5320CDB5332CDB5363CDB53100

CDB5420CDB5432CDB5463CDB54100

203263100

Page 22: Catalogo Delixi

Delixi Electric 15

Function CDB6LE electronic type residual current operated circuit breakers combine the follow-ing functions:

Overload protectionProtection against short-circuit currentProtection for users against indirect contactAdditional protection for users against direct contacts (30mA)Protection for electrical installations against insulation faults (fire hazard, etc)Isolation

Rated current: 6, 10, 16, 20, 25, 32, 40, 50, 60ARated voltage: 230V AC for 1P+N/2P, 400V AC for 3P/3P+N/4PSensitivity: 30 mATropicalization: treatment 2Protection degree: 2ConnectionUp to 16 mm2 cablesTripping curves:C curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 InMechanical indication of the earth fault on the front face by a black mechanicalindicator35 mm standard DIN rail mounting.

Description Technical data

CDB6LEStandard: IEC 61009Trip Curve: C and D curvesBreaking Capacity: 3000ASensitivity: 30mA

Standard and certificationIEC 61009

Overall dimensions

CDB6LE-32

CDB6LE-63

Page 23: Catalogo Delixi

Delixi Electric16

CDB6LEStandard: IEC 61009Trip Curve: C and D curvesBreaking Capacity: 3000ASensitivity: 30mA

61016202532405060

4003P+N 30 111111111111141414

CDB6LEa4C6SCDB6LEa4C10SCDB6LEa4C16SCDB6LEa4C20SCDB6LEa4C25SCDB6LEa4C32SCDB6LEa4C40SCDB6LEa4C50SCDB6LEa4C60S

CDB6LEa4D6SCDB6LEa4D10SCDB6LEa4D16SCDB6LEa4D20SCDB6LEa4D25SCDB6LEa4D32SCDB6LEa4D40SCDB6LEa4D50SCDB6LEa4D60S

61016202532405060

4003P 30 101010101010121212

CDB6LEa3C6SCDB6LEa3C10SCDB6LEa3C16SCDB6LEa3C20SCDB6LEa3C25SCDB6LEa3C32SCDB6LEa3C40SCDB6LEa3C50SCDB6LEa3C60S

CDB6LEa3D6SCDB6LEa3D10SCDB6LEa3D16SCDB6LEa3D20SCDB6LEa3D25SCDB6LEa3D32SCDB6LEa3D40SCDB6LEa3D50SCDB6LEa3D60S

2P 777777888

CDB6LEa2C6SCDB6LEa2C10SCDB6LEa2C16SCDB6LEa2C20SCDB6LEa2C25SCDB6LEa2C32SCDB6LEa2C40SCDB6LEa2C50SCDB6LEa2C60S

CDB6LEa2D6SCDB6LEa2D10SCDB6LEa2D16SCDB6LEa2D20SCDB6LEa2D25SCDB6LEa2D32SCDB6LEa2D40SCDB6LEa2D50SCDB6LEa2D60S

230 30 61016202532405060

Type Width(in mod.of 9mm)

ReferenceC curve D curve

Voltage(V)

Sensitivity(mA)

2301P+N 30 555555666

CDB6LEa1C6SCDB6LLEa1C10SCDB6LEa1C16SCDB6LEa1C20SCDB6LEa1C25SCDB6LEa1C32SCDB6LEa1C40SCDB6LEa1C50SCDB6LEa1C60S

CDB6LEa1D6SCDB6LEa1D10SCDB6LEa1D16SCDB6LEa1D20SCDB6LEa1D25SCDB6LEa1D32SCDB6LEa1D40SCDB6LEa1D50SCDB6LEa1D60S

Rating(A)61016202532405060

61016202532405060

4004P 30 131313131313161616

CDB6LEa6C6SCDB6LEa6C10SCDB6LEa6C16SCDB6LEa6C20SCDB6LEa6C25SCDB6LEa6C32SCDB6LEa6C40SCDB6LEa6C50SCDB6LEa6C60S

CDB6LEa6D6SCDB6LEa6D10SCDB6LEa6D16SCDB6LEa6D20SCDB6LEa6D25SCDB6LEa6D32SCDB6LEa6D40SCDB6LEa6D50SCDB6LEa6D60S

Tripping Curve

B C D

Page 24: Catalogo Delixi

Delixi Electric 17

Function CDB3LE electronic type residual current operated circuit breakers combine the fol-lowing functions:

Protection of circuits against overload currentsProtection of circuits against short-circuit currentsProtection of users against indirect contactAdditional protection for users against direct contacts (30mA)Protection of electrical installations against insulation faults (fire hazard, etc)Isolation

Rated current: 6, 10, 16, 20, 25, 32, 40ARated voltage: 230V ACBreaking capacity: 3kASensitivity: 30mATripping curve:C curve: the magnetic release operates between 5 and 10 InTropicalization: treatment 2Protection degree: 2ConnectionUp to 6 mm2 cablesMechanical indication of the earth fault on the front face by a red mechanical indicator35 mm standard DIN rail mounting

Description Technical data

Overall dimensions

Type Sensltivity(mA)

301P+N

Width (in mod.of 9mm)

4

Rating(A)6101620253240

CDB3LEa5C6SCDB3LEa5C10SCDB3LEa5C16SCDB3LEa5C20SCDB3LEa5C25SCDB3LEa5C32SCDB3LEa5C40S

Standard and certification IEC 61009

CDB3LEStandard: IEC 61009Trip Curve: C curvesBreaking Capacity: 3000ASensitivity: 30mA

Reference C curve

Unit:mm

Tripping Curve

C

Page 25: Catalogo Delixi

Delixi Electric18

Function CDB2LE electronic type residual current operated circuit breakers combine the follow-ing functions:

Protection of circuits against overload currentsProtection of circuits against short-circuit currentsProtection of users against indirect contactProtection of electrical installations against insulation faults (fire hazard, etc)Isolation

Rated current: 63A, 80A,100ARated voltage: 230V for 1P+N; 400V for 2P/3P/3P+N/4PSensitivity: 100mA,300mARated ultimate short-circuit breaking capacity (Icu): 10,000ARated service short-circuit breaking capacity (Ics): 7,500ATripping curves:C curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 In2 types of residual current tripping are available:InstantaneousTime-delay with a maximum delay time of 0.2 sTropicalization: treatment 2Protection degree: 2ConnectionUp to 50 mm2 cablesMechanical indication of the earth fault on the front face by a black mechanicalindicatorClosed position indication35 mm standard DIN rail mounting

Description Technical data

Overall dimensions

Standard and certificationIEC 60947-2

CDB2LEStandard: IEC 60947-2Trip Curve: C and D curvesBreaking Capacity: 10000ASensitivity: 100mA, 300mA

Unit:mm

Page 26: Catalogo Delixi

Delixi Electric 19

Type Width(in mod.of 9mm)

1P+N

ReferenceC curve

Rating(A)

63801006380100

Sensitivity(mA)

100100100300300300

6

D curve

CDB2LEH1D63YCDB2LEH1D80YCDB2LEH1D100YCDB2LEH1D63TCDB2LEH1D80TCDB2LEH1D100T

CDB2LEH1C63YCDB2LEH1C80YCDB2LEH1C100YCDB2LEH1C63TCDB2LEH1C80TCDB2LEH1C100T

CDB2LEStandard: IEC 60947-2Trip Curve: C and D curvesBreaking Capacity: 10000ASensitivity: 100mA, 300mA

2P 63801006380100

100100100300300300

9 CDB2LEH2D63YCDB2LEH2D80YCDB2LEH2D100YCDB2LEH2D63TCDB2LEH2D80TCDB2LEH2D100T

CDB2LEH2C63YCDB2LEH2C80YCDB2LEH2C100YCDB2LEH2C63TCDB2LEH2C80TCDB2LEH2C100T

3P 63801006380100

100100100300300300

12 CDB2LEH3D63YCDB2LEH3D80YCDB2LEH3D100YCDB2LEH3D63TCDB2LEH3D80TCDB2LEH3D100T

CDB2LEH3C63YCDB2LEH3C80YCDB2LEH3C100YCDB2LEH3C63TCDB2LEH3C80TCDB2LEH3C100T

3P+N 63801006380100

100100100300300300

12 CDB2LEH6D63YCDB2LEH6D80YCDB2LEH6D100YCDB2LEH6D63TCDB2LEH6D80TCDB2LEH6D100T

CDB2LEH6C63YCDB2LEH6C80YCDB2LEH6C100YCDB2LEH6C63TCDB2LEH6C80TCDB2LEH6C100T

4P 63801006380100

100100100300300300

15 CDB2LEH4D63YCDB2LEH4D80YCDB2LEH4D100YCDB2LEH4D63TCDB2LEH4D80TCDB2LEH4D100T

CDB2LEH4C63YCDB2LEH4C80YCDB2LEH4C100YCDB2LEH4C63TCDB2LEH4C80TCDB2LEH4C100T

C D

Tripping Curve

Page 27: Catalogo Delixi

Delixi Electric20

Function CDB7LSP electronic type residual current operated circuit breakers combine thefollowing functions:

Protection of circuits against overload currents Protection of circuits against short-circuit currents Protection of users against indirect contact Additional protection for users against direct contacts (30mA) Protection of electrical installations against insulation faults (fire hazard, etc)

Rated current: 6, 10, 16, 20, 25, 32, 40ARated voltage: 230V ACBreaking capacity: 6kASensitivity: 30mATripping curve:B curve: the magnetic release operates between 3 and 5 InC curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 InTropicalization: treatment 2Protection degree: 2ConnectionUp to 10 mm2 cablesMechanical indication of the earth fault on the front face by a red mechanicalindicator 35 mm standard DIN rail mounting

Description Technical data

Overall dimensions

Type Rating(A)

Width(mm)

ReferenceB curve D curve

6101620253240

18181818181818

CDB7LSPN1B6SCDB7LSPN1B10SCDB7LSPN1B16SCDB7LSPN1B20SCDB7LSPN1B25SCDB7LSPN1B32SCDB7LSPN1B40S

CDB7LSPN1D6SCDB7LSPN1D10SCDB7LSPN1D16SCDB7LSPN1D20SCDB7LSPN1D25SCDB7LSPN1D32SCDB7LSPN1D40S

1P+N

CDB7LSPStandard: IEC 61009Trip Curve: C and D curvesBreaking Capacity: 6000ASensitivity:30mA

Standard and certificationIEC 61009

Voltage(V)230

Sensitivity(mA)30

C curveCDB7LSPN1C6SCDB7LSPN1C10SCDB7LSPN1C16SCDB7LSPN1C20SCDB7LSPN1C25SCDB7LSPN1C32SCDB7LSPN1C40S

Page 28: Catalogo Delixi

Delixi Electric 21

Function CDL7 electromagnetic type residual current switch combine the following functions:Protection for users against indirect contactAdditional protection for users against direct contacts (30mA)Protection for electrical installations against insulation faults (fire hazard, etc)

Isolation

DescriptionRated current: 25, 40, 63, 80, 100ARated voltage: 230/400V ACSensitivity: 10mA, 30mA, 100mA, 300mAMechanical durability: 2000Electrical durability: 1000Tropicalization: treatment 2Protection degree: 2ConnectionTunnel terminalsUp to 16 mm2 cablesType A or type AC RCCB, without overload or short-circuit protectionDon’t need any auxiliary supply source.Instantaneous earth fault trip, unadjustableMechanical indication of the earth fault on the front face by a red mechanicalindicator35 mm standard DIN rail mounting

Technical data

CDL7Standard:IEC 61008Sensitivity: 10mA, 30mA, 100mA, 300mARCCB: Type A , Type AC

Overall dimensions

Standard and certificationIEC 61008KEMA, CB

Unit:mm

Page 29: Catalogo Delixi

Delixi Electric22

CDL7Standard:IEC 61008Sensitivity: 10mA, 30mA, 100mA, 300mARCCB: Type A , Type AC

Type Width(in mod.of 9mm)

Sensitivity(mA)

2P 103030303030100100100100100300300300300300100100100300300300

4

Rating(A)

2525406380100254063801002540638010063801006380100

4P 103030303030100100100100100300300300300300100100100300300300

8 2525406380100254063801002540638010063801006380100

CDL7225LACDL7225SACDL7240SACDL7263SACDL7280SACDL72100SACDL7225YACDL7240YACDL7263YACDL7280YACDL72100YACDL7225TACDL7240TACDL7263TACDL7280TACDL72100TACDL7263YASCDL7280YASCDL72100YASCDL7263TASCDL7280TASCDL72100TAS

CDL7425LACDL7425SACDL7440SACDL7463SACDL7480SACDL74100SACDL7425YACDL7440YACDL7463YACDL7480YACDL74100YACDL7425TACDL7440TACDL7463TACDL7480TACDL74100TACDL7463YASCDL7480YASCDL74100YASCDL7463TASCDL7480TASCDL74100TAS

ReferenceA type AC type

CDL7225LCCDL7225SCCDL7240SCCDL7263SCCDL7280SCCDL72100SCCDL7225YCCDL7240YCCDL7263YCCDL7280YCCDL72100YCCDL7225TCCDL7240TCCDL7263TCCDL7280TCCDL72100TCCDL7263YCSCDL7280YCSCDL72100YCSCDL7263TCSCDL7280TCSCDL72100TCS

CDL7425LCCDL7425SCCDL7440SCCDL7463SCCDL7480SCCDL74100SCCDL7425YCCDL7440YCCDL7463YCCDL7480YCCDL74100YCCDL7425TCCDL7440TCCDL7463TCCDL7480TCCDL74100TCCDL7463YCSCDL7480YCSCDL74100YCSCDL7463TCSCDL7480TCSCDL74100TCS

Page 30: Catalogo Delixi

Delixi Electric 23

CDY1 Surge Protective DevicesStandard: IEC61643-1

Function

Description

CDY1 surge protective devices provide: Applicable to household appliances and the like to offer protection When there is an over-voltage caused by either lightning strike or operation in thecircuit

Technical data

TypePoleNominal discharge currentIn(8/20us) kAMaximum dischargecurrent Imax(8/20us) kAMaximum continuousoperational voltage Uc VProtection level Up kVLeakage cur rent(75%Uc 1mA) uAResponse time ns

CDY1-80 CDY1-100 CDY1-120CDY1-60CDY1-401P+N, 2P5

10

275

1.320

25

CDY1-10 CDY1-20

1P, 1P+N, 2P, 3P, 3P+N, 4P10

20

275

1.3

385

1.5

420

1.8

20

40

Standard and certification

IEC61643-1

Overall dimensions

CDY1-10 CDY1-20 40 60

CDY1-80 100 120

30

60

40

80

50

100

60

120

320

1.3

275

1.5

385

1.8

420

2

275

2

420

2.5

385

2.2

275

2

420

2.2

385

2.2

275

2.2

420

2.5

385

2.5

275

2.2

420

2.5

385

2.5

Page 31: Catalogo Delixi

Delixi Electric24

CDY1 Surge Protective DevicesStandard: IEC61643-1

Note:" " express Maximum continuous operational voltage (Uc) code

275V275

320V320

385V385

420V420

Imax ReferncePole10KA10KA20KA20KA20KA20KA20KA20KA40KA40KA40KA40KA40KA40KA60KA60KA60KA60KA60KA60KA80KA80KA80KA80KA80KA80KA100KA100KA100KA100KA100KA100KA120KA120KA120KA120KA120KA120KA20KA40KA60KA60KA80KA100KA120KA

1P+N2P1P2P3P4P1P+N3P+N1P2P3P4P1P+N3P+N1P2P3P4P1P+N3P+N1P2P3P4P1P+N3P+N1P2P3P4P1P+N3P+N1P2P3P4P1P+N3P+NPhase modlePhase modlePhase modleN-PEN-PEN-PEN-PE

CDY1105CDY1102CDY1201CDY1202CDY1203CDY1204CDY1205CDY1206CDY1401CDY1402CDY1403CDY1404CDY1405CDY1406CDY1601CDY1602CDY1603CDY1604CDY1605CDY1606CDY1801CDY1802CDY1803CDY1804CDY1805CDY1806CDY11001CDY11002CDY11003CDY11004CDY11005CDY11006CDY11201CDY11202CDY11203CDY11204CDY11205CDY11206CDY120PMCDY140PMCDY160PMCDY160NPCDY180NPCDY1100NPCDY1120NP

Uc

Page 32: Catalogo Delixi

Delixi Electric 25

Function CDPZ50 distribution box provides illumination devices, sockets and electrical appli-ances with functions as follows: Protection against overload Protection against over voltage Protection against leakage

Description Technical data

TypeSurface installation

Flush installation

The amount of unit loop*68121620246812162024

CDPZ50Standard: IEC60439-1 IEC60670

ReferenceCDPZ50M6CDPZ50M8CDPZ50M12CDPZ50M16CDPZ50M20CDPZ50M24CDPZ50R6CDPZ50R8CDPZ50R12CDPZ50R16CDPZ50R20CDPZ50R24

*:18mm for one unit loop

Rated operational voltage Maximum rated current Rated insulation voltage Rated frequency Degree of protection Instantaneous withstand current

Construction feature Holistic steel-plastic construction Free assembly of components Beautiful design Flame retardant industrial plastic in panel The whole panel can move vertically

Standard and certification IEC60439-1 IEC60670

AC 400V or AC 230V100A500V50HzIP306KA

Page 33: Catalogo Delixi

Delixi Electric26

Overall dimension

CDPZ50Standard: IEC60439-1 IEC60670

Surface installation Flush installation

Unit:mm

Loop number

6812162024*

Surface installationA171207279351423364

*:two rows product

B220220220220220303

Flush installationA163199279343413383

B220220220220220282

ThicknessC909090909090

Page 34: Catalogo Delixi

Delixi Electric 27

Technical Data Accuracy class: 1.0, 2.0 Reference voltage:220V Current specification:1.5(6)A,3(6)A,2.5(10)A,5(20)A,5(30)A 10(40)A,15(60)A,20(80)A,30(100)A Power: 2W/10VA (voltage circuit), 4VA(Current circuit) Two-way measurement function:

Extended functions: Optional liquid crystal display, infrared communications and 485

communications

Normal work temperature:-10-~+45 Limit working temperature:-25-~+55 Normal work voltage:0.9~1.1 Reference voltage Limit work voltage:0.7~1.2 Reference voltage Relative Humidity: 85% Installation conditions:Meter should be installed in indoor drying, ventilation, fire-resistant, solid walls height of 1.8 m about the use of non-corrosive gases in the nvironment, should be moisture-proof. Lightning request:Thunderstorms in more places should be installed in the

installation of lightning equipment

Standard and Certification IEC620531-21:2003

KEMA

Overall dimensions

DDS607 single-phase electronic watt-hour meter provide: Measuring energy in household and commercial single-phase network services

Function

Description

Being able to accurately measure, antitwodirections of power andthe total electricityconsumption in one direction

Single-phase Type A,C Meter Single-phase LCD Meter

DDS607 Single-phase Electronic Watt-hour MeterStandard:IEC 620531-21:2003

Page 35: Catalogo Delixi

Delixi Electric28

Ordering informationn

Type A (Import chip)Type A (Import chip)Type A (Import chip)Type A (Import chip)Type A (Import chip)Type A (Import chip)Type A (Import chip)Type A (Import chip)Type C (Domestic chip)Type C (Domestic chip)Type C (Domestic chip)Type C (Domestic chip)Type C (Domestic chip)Type C (Domestic chip)Type C (Domestic chip)Type C (Domestic chip)LCD without 485 communicationsLCD without 485 communicationsLCD without 485 communicationsLCD without 485 communicationsLCD without 485 communicationsLCD without 485 communicationsLCD without 485 communicationsLCD with 485 communicationsLCD with 485 communicationsLCD with 485 communicationsLCD with 485 communicationsLCD with 485 communications and infrared communicationsLCD with 485 communications and infrared communicationsLCD with 485 communications and infrared communicationsLCD with 485 communications and infrared communicationsLCD with 485 communications and infrared communicationsLCD with 485 communications and infrared communicationsLCD with 485 communications and infrared communicationsLCD with 485 communications and infrared communications

1.5(6)A2.5(10)A5(20)A5(30)A10(40)A15(60)A20(80)A30(100)A1.5(6)A2.5(10)A5(20)A5(30)A10(40)A15(60)A20(80)A30(100)A1.5(6)A2.5(10)A5(20)A5(30)A10(40)A15(60)A20(80)A1.5(6)A5(20)A10(40)A15(60)A1.5(6)A2.5(10)A5(20)A5(30)A10(40)A15(60)A20(80)A

30(100)A

DDS607N16M4ADDS607N110M4ADDS607N120M4ADDS607N130M6ADDS607N140M4ADDS607N160M4ADDS607N180M4ADDS607N1100M3ADDS607N26M4ADDS607N210M4CDDS607N220M4CDDS607N230M6CDDS607N240M4CDDS607N260M4CDDS607N280M4CDDS607N2100M3CDDS607N16M4CDDDS607N110M4CDDDS607N120M4CDDDS607N130M6CDDDS607N140M4CDDDS607N160M4CDDDS607N180M4CDDDS607N16M4CD485DDS607N120M4CD485DDS607N140M4CD485DDS607N160M4CD485DDS607N116M4CD485IDDS607N110M4CD485IDDS607N120M4CD485IDDS607N130M6CD485IDDS607N140M4CD485IDDS607N160M4CD485IDDS607N180M4CD485IDDS607N1100M3CD485I

Function Description Currentspecification Reference

Note: Users need special specifications can be customized

DDS607 Single-phase Electronic Watt-hour MeterStandard:IEC 620531-21:2003

Page 36: Catalogo Delixi

Delixi Electric 29

Description Technical data

CDM1Standard: IEC 60947-2

Function CDM1 molded case circuit breakers can be used to provide the following functions:

Main technical parameters are shown in the table below

Constructional featuresThermamagnetic release offers instantaneous trip against short-circuit and longtime delay trip against overcurrentThe circuit breaker can be of fixed type or plug-in typeFor 4-pole circuit breakers:N-pole without overcurrent release, it switches on and off with other poles ( N-pole lead-make, lag-break)Various accessories can be attached to the circuit breaker to extend its functions,such as undervoltage release, shunt release, ON/OFF position indication contact,and tripped position indication contact, for detail see the accessories part

Standard and certificationIEC 60947-2KEMA, SEMKO, CB, CE

CDM1-6363

3P,4P5010 1620 2532 4050 63

690V

6000V

400V

5025301850120400060002530

TypeFrame size ratedcurrent ANumber of polesRated frequency HzRated current In A

Rated insulationvoltage Ui VRated impulsewithstandvoltage Uimp VRated operationalvoltage Ue VIcu kA(400V)Ics kA(400V)Arcing distance mmDurability

Power consu-mpution W

CDM1-100100

2P,3P,4P

16 2025 3032 4050 6380 100800V

8000V

400V / 690V

50353026

120300070004050

CDM1-225225

100 125160 180200 225

50353026

120150065006075

CDM1-400400

200 350250 315400

400V

70504030100601000400040110

CDM1-630630

3P,4P

400 500630

400V690V65454234

6010004000150200

CDM1-800800

400 500630 700800

400V

70504030

205002500135190

CDM1-12501250

3P

700 80010001250

85-45-

205002500240300

Type MType LType MType L

Cycles/hElectricalMechanicalFixedPlug-in

To distribute electric power and protect circuits and equipment against overload,undervoltage, and short-circuit faultsTo protect motors against overload, undervoltage and short-circuit faults (Inm²400A)To infrequently start and control AC motors

Page 37: Catalogo Delixi

Delixi Electric30

CDM1Standard: IEC 60947-2

Type Reference

CDM1-63 3P

4P

CDM1-100 2P

3P

4P

CDM1-225 2P

In A

10162025324050631016202532405063162025324050638010016202532405063801001620253240506380100100125160180200225

Type MCDM163M103CDM163M163CDM163M203CDM163M253CDM163M323CDM163M403CDM163M503CDM163M633CDM163M104CDM163M164CDM163M204CDM163M254CDM163M324CDM163M404CDM163M504CDM163M634CDM1100M162CDM1100M202CDM1100M252CDM1100M322CDM1100M402CDM1100M502CDM1100M632CDM1100M802CDM1100M1002CDM1100M163CDM1100M203CDM1100M253CDM1100M323CDM1100M403CDM1100M503CDM1100M633CDM1100M803CDM1100M1003CDM1100M164CDM1100M204CDM1100M254CDM1100M324CDM1100M404CDM1100M504CDM1100M634CDM1100M804CDM1100M1004CDM1225M1002CDM1225M1252CDM1225M1602CDM1225M1802CDM1225M2002CDM1225M2252

Type LCDM163L103CDM163L163CDM163L203CDM163L253CDM163L323CDM163L403CDM163L503CDM163L633----------------------------------CDM1100L163CDM1100L203CDM1100L253CDM1100L323CDM1100L403CDM1100L503CDM1100L633CDM1100L803CDM1100L1003------------------------------

Page 38: Catalogo Delixi

Delixi Electric 31

CDM1Standard: IEC 60947-2

Type ReferenceIn A

3P

4P

CDM1-400 3P

4P

CDM1-630 3P

4P

CDM1-800 3P

4P

CDM1-1250 3P

10012516018020022510012516018020022520022525031535040020021525031535040040050063040050063040050063070080040050063070080070080010001250

Type MCDM1225M1003CDM1225M1253CDM1225M1603CDM1225M1803CDM1225M2003CDM1225M2253CDM1225M1004CDM1225M1254CDM1225M1604CDM1225M1804CDM1225M2004CDM1225M2254CDM1400M2003CDM1400M2253CDM1400M2503CDM1400M3153CDM1400M3503CDM1400M4003CDM1400M2004CDM1400M2254CDM1400M2504CDM1400M3154CDM1400M3504CDM1400M4004CDM1630M4003CDM1630M5003CDM1630M6303CDM1630M4004CDM1630M5004CDM1630M6304CDM1800M4003CDM1800M5003CDM1800M6303CDM1800M7003CDM1800M8003CDM1800M4004CDM1800M5004CDM1800M6304CDM1800M7004CDM1800M8004CDM11250M7003CDM11250M8003CDM11250M10003CDM11250M12503

Type LCDM1225L1003CDM1225L1253CDM1225L1603CDM1225L1803CDM1225L2003CDM1225L2253------------CDM1400L2003CDM1400L2253CDM1400L2503CDM1400L3153CDM1400L3503CDM1400L4003------------CDM1630L4003CDM1630L5003CDM1630L6303------CDM1800L4003CDM1800L5003CDM1800L6303CDM1800L7003CDM1800L8003------------------

Note: The connection mode for CDM1 is the fixed type front connection.

Page 39: Catalogo Delixi

Delixi Electric32

CDM1Standard: IEC 60947-2

Overall dimensionsUnit:mm

2P 3P 4P

Key to overall dimensions

Type

CDM1-63LCDM1-63MCDM1-63MCDM1-100MCDM1-100LCDM1-100MCDM1-100MCDM1-225MCDM1-225LCDM1-225MCDM1-225MCDM1-400L,MCDM1-400MCDM1-630L,MCDM1-630MCDM1-800L,MCDM1-800MCDM1-1250M

Poles

334233423343434343

Install dimensionsa252525--303030--35353544445858707070

b117117117129129129129126126126126215215200200243243375

d3.53.53.54.54.54.54.55.55.55.55.56.56.5777710

Overall dimensionsL135135135150150150150165165165165257257270270280280406

L12121215151515164646464105105118118102102104

W767610365929212275107107142140184182240210280210

H89.59999103.587103.5103.5124.5108124.5124.5146146160160146146190

H22128282425242424.524.52424.536.536.5414134.534.558.5

H17482828768878710487104104100100108108103103140.5

Page 40: Catalogo Delixi

Delixi Electric 33

CDM1Standard: IEC 60947-2

A117129126215200243

B253035445870

H495454768376

Unit:mm

Unit:mm

A3535656048

B11.531151515

H4648616166

Page 41: Catalogo Delixi

Delixi Electric34

CDM1Standard: IEC 60947-2

The accessories are fixed into the circuit breaker.

MN (Undervoltage Release)

Accessories

Technical dataRated operating voltage Us(V)Drop-out voltage(V)Pick-up voltage(V)

230V, 400V AC(0.35~0.7) Us(0.85~1.1) Us

MX (Shunt Release)

Technical dataRated control voltage US(V)Operating voltage(V)

230V, 400V AC(0.7~1.1) US

OF (Auxiliary Contact)

Rated thermal current Ith 3ARated operating voltage US(V)1NO+1NC (Change over)2NO+2NC (Change over)

SD (Alarm Switch)

Rated thermal current Ith 3ARated operating voltage US(V)

1NO+1NC

Technical data

0.4A (400V AC)

Technical data

0.26A (400V AC)0.4A (400V AC)

Page 42: Catalogo Delixi

Delixi Electric 35

CDM1Standard: IEC 60947-2

Ordering information

Type

CDM1-63

CDM1-100

CDM1-225

CDM1-400

CDM1-630

CDM1-800

CDM1-1250

Voltage (V)

230V AC400V AC

ReferenceMN*CDM163MN230CDM163MN400CDM1100MN230CDM1100MN400CDM1225MN230CDM1225MN400CDM1400MN230CDM1400MN400CDM1630MN230CDM1630MN400CDM1800MN230CDM1800MN400CDM11250MN230CDM11250MN400

MX*CDM163MX230CDM163MX400CDM1100MX230CDM1100MX400CDM1225MX230CDM1225MX400CDM1400MX230CDM1400MX400CDM1630MX230CDM1630MX400CDM1800MX230CDM1800MX400CDM11250MX230CDM11250MX400

OFCDM163OF

CDM1100OF

CDM1225OF

CDM1400OF

CDM1630OF

CDM1800OF

CDM11250OF

SDCDM163SD

CDM1100SD

CDM1225SD

CDM1400SD

CDM1630SD

CDM1800SD

TR(Round Handle)CDM163TR

CDM1100TR

CDM1225TR

CDM1400TR

CDM1630TR

CDM1800TR

TS(Square Handle)CDM163TS

CDM1100TS

CDM1225TS

CDM1400TS

CDM1630TS

CDM1800TS

Page 43: Catalogo Delixi

Delixi Electric36

CDM1LStandard: IEC 60947-2

Function CDM1L molded case circuit breakers with electronic type residual current operatedprotection can be used to provide the following functions:

To distribute electric power and protect circuits and equipment against overload, undervoltage, and short-circuit faults

To infrequently start and control AC motorsTo protect users against indirect contactTo protect electrical installations against insulation faults (fire hazard, etc)

Description Technical data

Main technical parameters are shown in the table below

Table for 4 pole CDM1LE (Neutral line)CodeAB

NoteN(direct connect)N(direct connect N pole lead-make, lag-break)

TypeFrame size rated current ARated current In A

Rated frequency HzRated insulation voltage Ui VRated operational voltage Ue VRated impulse withstand voltage Uimp VNumber of polesIcu kA(400V)Ics kA(400V)Rated residualoperatingcurrent I n mARated residual non-operatingcurrent I no mADurability

CDM1L-10010016 20 25 32 4050 63 80 1005080040080003P, 4P5035352230/100/500100/300/500100/300/5001/2 I n

1500850010000

CDM1L-225225100 125 140 160180 200 225

5035352230/100/500100/300/500100/300/5001/2 I n

100070008000

CDM1L-400400200 250 315350 400

70504030100/300/500

100/300/5001/2 I n

100040005000

Type MType LType MType LWithout delay

With delay

ElectricalMechanicalTotal

Maximum break time for residual operating current protectionNumber of polesMax. breaktime S

Without delayWith delay

I n0.20.5/1.15/2.15

2 I n0.10.35/1/2

5 I n0.040.25/0.9/1.9

10 I n0.040.25/0.9/1.9

Page 44: Catalogo Delixi

Delixi Electric 37

CDM1LStandard: IEC 60947-2

Constructional featuresThermamagnetic release offers instantaneous trip against short-circuit and long time delay trip against overcurrentThe residual operating current value can be fixed or adjustableThe residual operating current protection can be with time-delay or without time-delayVarious accessories can be attached to the circuit breaker to extend its functions, such as undervoltage release, shunt release, ON/OFF positionindication contact, and tripped position indication contact, for detail see the accessories part

Standard and certificationIEC 60947-2CE

Ordering information

Page 45: Catalogo Delixi

Delixi Electric38

CDM1LStandard: IEC 60947-2

ReferenceType MCDM1LE100M163CDM1LE100M203CDM1LE100M253CDM1LE100M323CDM1LE100M403CDM1LE100M503CDM1LE100M633CDM1LE100M803CDM1LE100M1003CDM1LE100M164 ACDM1LE100M204 ACDM1LE100M254 ACDM1LE100M324 ACDM1LE100M404 ACDM1LE100M504 ACDM1LE100M634 ACDM1LE100M804 ACDM1LE100M1004 ACDM1LE100M164 BCDM1LE100M204 BCDM1LE100M254 BCDM1LE100M324 BCDM1LE100M404 BCDM1LE100M504 BCDM1LE100M634 BCDM1LE100M804 BCDM1LE100M1004 BCDM1LE225M1003CDM1LE225M1253CDM1LE225M1403CDM1LE225M1603CDM1LE225M1803CDM1LE225M2003CDM1LE225M2253CDM1LE225M1004 ACDM1LE225M1254 ACDM1LE225M1404 ACDM1LE225M1604 ACDM1LE225M1804 ACDM1LE225M2004 ACDM1LE225M2254 ACDM1LE225M1004 BCDM1LE225M1254 BCDM1LE225M1404 BCDM1LE225M1604 BCDM1LE225M1804 BCDM1LE225M2004 BCDM1LE225M2254 BCDM1LE400M2003CDM1LE400M2503CDM1LE400M3153CDM1LE400M3503CDM1LE400M4003

Type

CDM1L-100 3P

4P A

4P B

CDM1L-225 3P

4P A

4P B

CDM1-400 3P

Rated currentIn A162025324050638010016202532405063801001620253240506380100100125140160180200225100125140160180200225100125140160180200225200250315350400

Type LCDM1LE100L163CDM1LE100L203CDM1LE100L253CDM1LE100L323CDM1LE100L403CDM1LE100L503CDM1LE100L633CDM1LE100L803CDM1LE100L1003CDM1LE100L164 ACDM1LE100L204 ACDM1LE100L254 ACDM1LE100L324 ACDM1LE100L404 ACDM1LE100L504 ACDM1LE100L634 ACDM1LE100L804 ACDM1LE100L1004 ACDM1LE100L164 BCDM1LE100L204 BCDM1LE100L254 BCDM1LE100L324 BCDM1LE100L404 BCDM1LE100L504 BCDM1LE100L634 BCDM1LE100L804 BCDM1LE100L1004 BCDM1LE225L1003CDM1LE225L1253CDM1LE225L1403CDM1LE225L1603CDM1LE225L1803CDM1LE225L2003CDM1LE225L2253CDM1LE225L1004 ACDM1LE225L1254 ACDM1LE225L1404 ACDM1LE225L1604 ACDM1LE225L1804 ACDM1LE225L2004 ACDM1LE225L2254 ACDM1LE225L1004 BCDM1LE225L1254 BCDM1LE225L1404 BCDM1LE225L1604 BCDM1LE225L1804 BCDM1LE225L2004 BCDM1LE225L2254 BCDM1LE400L2003CDM1LE400L2503CDM1LE400L3153CDM1LE400L3503CDM1LE400L4003

Page 46: Catalogo Delixi

Delixi Electric 39

CDM1LStandard: IEC 60947-2

Overall dimensions

Type

CDM1L-100L

CDM1L-100M

CDM1L-225L

CDM1L-225M

CDM1L-400L,M

Poles

3434343434

Overall sizeL1 L2 L3 L4

150max150max150max150max165max165max165max165max257max257max

94max94max110max110max94max94max110max110max146max146max

75max75max92max92max72max72max90max90max103max103max

Installation sizea b d

30603060357035708888

129129129129126126126126194194

4 4.56 4.54 4.56 4.54 4.56 4.54 4.56 4.54 4.56 6.5

Key to overall dimensions

92max122max92max122max107max142max107max142max154max198max

Unit:mm

ReferenceType MCDM1LE400M2004 ACDM1LE400M2254 ACDM1LE400M2504 ACDM1LE400M3154 ACDM1LE400M3504 ACDM1LE400M4004 ACDM1LE400M2004 BCDM1LE400M2254 BCDM1LE400M2504 BCDM1LE400M3154 BCDM1LE400M3504 BCDM1LE400M4004 B

Type

4P A

CDM1L-400 4P B

Rated currentIn A200225250315350400200225250315350400

Type LCDM1LE400L2004 ACDM1LE400L2254 ACDM1LE400L2504 ACDM1LE400L3154 ACDM1LE400L3504 ACDM1LE400L4004 ACDM1LE400L2004 BCDM1LE400L2254 BCDM1LE400L2504 BCDM1LE400L3154 BCDM1LE400L3504 BCDM1LE400L4004 B

Page 47: Catalogo Delixi

Delixi Electric40

CDM1LStandard: IEC 60947-2

Centrally revolvable type

FrameDimension

Dimension for handle mechanismCDM1L-10049

CDM1L-22555

CDM1L-40074

Unit:mm

Handle mechanism

Square Handle

The accessories are fixed into the circuit breaker.

MN (Undervoltage Release)

Accessories

Technical dataRated operating voltage US(V)Drop-out voltage(V)Pick-up voltage(V)

230V, 400V AC(0.35~0.7) Us(0.85~1.1) Us

Page 48: Catalogo Delixi

Delixi Electric 41

CDM1LStandard: IEC 60947-2

MX (Shunt Release)

Technical dataRated control voltage Us(V)Operating voltage(V)

230V, 400V AC(0.7~1.1) Us

OF (Auxiliary Contact)

Rated thermal current Ith 3ARated operating voltage Us(V)1NO+1NC (Change over)2NO+2NC (Change over)

Technical data

0.4A (400V AC)

SD (Alarm Switch)

Rated thermal current Ith 3ARated operating voltage Us(V)

1NO+1NC

Technical data

0.26A (400V AC)0.4A (400V AC)

Type

CDM1L-100

CDM1L-225

CDM1L-400

Ordering information

ReferenceMN*CDM1LE100MN230CDM1LE100MN400CDM1LE225MN230CDM1LE225MN400CDM1LE400MN230CDM1LE400MN400

Voltage(V)230V AC400V AC

MX*CDM1LE100MX230CDM1LE100MX400CDM1LE225MX230CDM1LE225MX400CDM1LE400MX230CDM1LE400MX400

OFCDM1LE100OF

CDM1LE225OF

CDM1LE400OF

SDCDM1LE100SD

CDM1LE225SD

CDM1LE400SD

TS(Square Handle)CDM1LE100TS

CDM1LE225TS

CDM1LE400TS

TR(Round Handle)CDM1LE100TR

CDM1LE225TR

CDM1LE400TR

Page 49: Catalogo Delixi

Delixi Electric42

CDW7Standard: IEC 60947-2

ApplicationApplied to power distribution of AC 50Hz, rated operational voltage 400/690V, ratedcurrent 200A~6300A and lowerFor power distribution and protecting circuit and power supply equipment aganistharm from overload, undervoltage, short circuit, earthing, and other faultsCircuit breaker which ampere frame size is under 630A can protect motor aganistoverload,undervoltage and shortcircuitCore parts use intelligent control unit which has accurate discrimination protection, itcan avoid unnecessary power failure and enhance the reliability of power supplysystem

Standard and certificationInternational standard: IEC609472Approved certification: CB, CE, KEMA

Operating condition and installation recommendation

Ambient temperature shall be controlled between+40 and -5 , the average temperature in 24 hoursshall not exceed +35Note:contacting manufacturer about circuit breakerused in place where ambient temperature is higherthan +40 or lower than -5

Page 50: Catalogo Delixi

Delixi Electric 43

CDW7Standard: IEC 60947-2

Parameter and characteristics

Certification approved: IEC 60947-1 IEC 60947-2CDW7-10003, 4B0400690800050200/400/630/800/100042--30--88--30--90001000

CDW7-20003, 4B0400/690800800050630/800/1000/1250/1600/200080505040176105504090001000

CDW7-32003, 4B0400/6908008000502000/2500/320010065805022014365504500500

CDW7-63003, 4B04008008000504000/5000/6300120--100--264--85--1500500

In

Icu

Ics

Icm

AC 400VAC 690VAC 400VAC 690VAC 400VAC 690VAC 400VAC 690V

Page 51: Catalogo Delixi

Delixi Electric44

Fault and alarm reset button“Fault/Alarm” LED

In normal state, this LED is off. In case of fault release, the red LED will flash quickly; in case of alarm, the red LED will be on constantly

“Normal” LED As long as the controller is on and operates normally, the green LED always flashes

Communication indicator The communication state indication is as follows: Profibus: OFF if no communication; ON if communication exists Modbus: OFF if no communication; flash if communication exists Device Net: Flash if no communication; ON if communication exists

Curve LEDs Red LEDs exist behind the curve. In case of fault release, the corresponding LED will flash indicating the fault type; During the parameter setting process, the LED is always on and indicates the current item.

KeypadMeasure key l, used to switch to the default measurement menu.Set key 2, used to switch to the parameter setting menu.Protection Key 3, used to switch to the protection parameter setting menu.Info key 4, used to switch to the historical record and maintenance menu.Up, Move up the cursor through the menu items on the current level, or

increment the value of the selected parameter.Down, Move down the cursor through the menu items on the current

level, or decrement the value of the selected parameter.Exit, exit from the current level and return to the upper level, or cancel the

current parameter selection.Select, Select to enter into the next level from the current item, or select the

current parameter, or store the change.

CDW7Standard: IEC 60947-2

Protection characteristics

Page 52: Catalogo Delixi

Delixi Electric 45

CDW7Standard: IEC 60947-2

Page 53: Catalogo Delixi

Delixi Electric46

CDW7Standard: IEC 60947-2

Page 54: Catalogo Delixi

Delixi Electric 47

ECW S- HDifferent curvesavailable for long timedelay protectionDifferent curvesavailable for inverseshort time delay protec-tionDefinite short time delayprotectionInstantaneous protectionCurrent unbalance (openphase) protectionEarth protectionEarth fault alarmNeutral phase protectionLoad monitor

ECW - M

ECW - H

DO Signal alarm functionMCR and out-of-limittripping protectionEarth fault or leakageprotection (either)

Over-voltage protectionUnder-voltage protectionVoltage unbalanceprotectionOver-currency protectionUnder-frequencyprotectionPhase protectionInverse power protectionDemand protectionZonal system interlockprotectionCommunication function

Long time delay protec-tionDefinite time delay +inverse time delay forshort time delay protec-tionInstantaneous protectionEarthing protectionLoad monitorDifferent curvesavailable for long timedelay protectionDifferent curvesavailable for inverseshort time delay protec-tionDefinite short time delayprotectionInstantaneous protectionMCR and out-of-limittripping protectionCurrent unbalance (openphase) protectionEarth protectionEarth fault alarmNeutral phase protectionLoad monitor

Max. phase currentFour phase current (I1,I2, I 3, IN) and earthcurrent

Four phase current (I1,I2, I 3, IN) and earthcurrentThermal capacity

Digital displayLED indicationKey operationDigital setting ofprotection param-eters

LCD display ofChinese GUILED indicationKey operation

Fault logSelf-diagnosisfunctionFeature testfunction

Up to 8 fault logsUp to 8 alarm logsUp to 8 position logsHistorical currentpeakContact equivalenceNumber of operatingcyclesFault clock functionSelf-diagnosis faultlogSelf-diagnosisfunctionFeature testfunction

CDW7Standard: IEC 60947-2

Four phase current (I1,I2, I 3, IN) and earthcurrentThermal capacity

Up to 8 fault logsUp to 8 alarm logsUp to 8 position logsHistorical current peakContact equivalenceNumber of operatingcyclesClock functionSelf-diagnosis function

LCD display ofChinese GUILED indicationKey operation

MCR and out-of-limittripping protectionDO Signal alarm functionCommunication function

Page 55: Catalogo Delixi

Delixi Electric48

ECW-H intelligent controllers

Ir=(0.4~1)ln10%2h1h

15,30,60,120,240,360,480,600,720,840,960

8.4,16.9,33.8,67.5,135,202.5,270,337.5,405,472.5,540

15%

Ir2=(1.5~15)In10%

Ts=K/10(N2-1),(Ts 20ms)0.1,0.2,0.3,0.40.06,0.13,0.2,0.27

15%

Ir4=(0.2~1.0)In

0.1s~1s (Rank difference 0.1s)

CDW7-1000ECWS-H intelligent control-lersIr=(0.4~1)ln

15%2h2h

8,12.8,19.2,32,48,64,80,108,144,224,320,480,640,800,960,11203.32,5.32,8.00,13.32,20.00,26.66,33.30,45.00,60.00,93.32,133,200,266,333,400,4331.25,2.00,3.00,5.00,7.50,10.0,12.5,16.8,22.5,35.0,50.0,75.0,100,125,150,162

10%

Ir2=(1.5~15)In15%

Ts=K/10(N2-1),(Ts 20ms)0.1,0.2,0.3,0.40.06,0.13,0.2,0.27

10%

1.05 Ir h1.3 Ir h1.5Ir1

2.0Ir1

3.0Ir1

CDW7Standard: IEC 60947-2

CDW7-2000~6300ECW-M intelligent controllers

Ir=(0.4~1)ln10%2h1h

15,30,60,120,240,480

8.4,16.9,33.8,67.5,135,270

15%

Ir2=(0.4~15)In10%

I2Ts= 8Ir1)2ts0.1,0.2,0.3,0.40.06,0.16,0.25,0.34

15%

Ir4=(0.2~1.0)In10%

0.1~4s (Rank difference 0.1s)

CDW7-2000Ir3=1In~50KA+OFF

15%

ECWS-HCDW7-1000(1.0~20)ln

15%

Ir4=(0.2~1.0)In10%

0.1s~1s (Rank difference 0.1s)

15%

CDW7-3200Ir3=1In~75KA+OFF

15%

CDW7-6300IIr3=1In~100KA+OFF

15%

ECW-M ECW-H

Page 56: Catalogo Delixi

Delixi Electric 49

AC 380V(0.35~0.7)Ue(0.85~1.1)Ue

0.35Ue36VA5VA

AC380 AC220 DC220 DC11036VA 24VA 24W 24W5VA 5VA 5W 5W(0.7~1.1)Usless than 30ms

7-2000~6300

AC380 AC220 DC220 DC11036VA 24VA 24W 24W10VA 10VA 10W 10W(0.85~1.1)Usless than 70ms

CDW7Standard: IEC 60947-2

Auxiliary functions

AC220V(0.35~0.7)Ue(0.85~1.1)Ue

0.35Ue24VA5VA

70 110

Page 57: Catalogo Delixi

Delixi Electric50

AC-15

10110.3101.10.310

DC-13

1116Pe1.11.16Pe10

CDW7Standard: IEC 60947-2

AC380 AC220 DC220 DC11085VA 85VA 85VA 85VA110VA 110VA 110VA 110VA150VA 150VA 150VA 150VA80VA 80VA 80VA 80VA(0.85~1.1)Usless than 5s

Pe 50W T0.95e’s upper limit 300ms

U/Uecos 0.95I/IeU/Uecos T0.

CDW7-2000~6300

CDW7-1000

In 2000A2000A In 3200A3200A In 6300A

Page 58: Catalogo Delixi

Delixi Electric 51

200, 400630800, 1000200, 400630800, 1000

CDW7-1000A fixed circuit breaker outline and horizonal/vertical connected dimension L266266266336336336

L1244244244314314314

N6121281616

L2---707070

CDW7Standard: IEC 60947-2

Overall and mounting dimension

Page 59: Catalogo Delixi

Delixi Electric52

200, 400630800, 1000200, 400630800, 1000

CDW7-1000A drawout type circuit breaker outline and horizonal/vertical wiring Unit:mm

3P

4P

L284284284354354354

L1194194194264264264

L3557575557575

L4638383638383

L2---707070

n6121281616

H68106810

CDW7Standard: IEC 60947-2

Page 60: Catalogo Delixi

Delixi Electric 53

CDW7-2000A fixed circuit breaker vertical connection diagram

CDW7-2000

CDW7-3200

CDW7-2000A~3200A fixed circuit breaker overall and horizonal/vertical wiring Unit:mmIn A400~8001000~160020002000~25003200

a1015202030

CDW7-2000 mounting dimension is same regardless of different current used in"horizonal-wiring" or"vertical-wiring"

3P4P

3P4P

L1362457457422537

L2318413413378493

L3292292292352352

L4340435435400515

CDW7Standard: IEC 60947-2

CDW7-2000A~3200A

Page 61: Catalogo Delixi

Delixi Electric54

CDW7-2000

CDW7-3200

CDW7-6300(4000/5000A)CDW7-6300

CDW7-2000A~6300A drawout type circuit breaker outline and horizonal/vertical connection Unit:mmIn A400~8001000~160020002000~25003200~40003200~400040005000~63005000~6300

a101520203030203030

3P

4P3P4P4000A 3P4P3P

L1375375470435550550813928928

L2335335430395510510773888888

L3292292292352352352352352352

L4265265360325440440703818818

L5247247247307307307307307307

W1461461461471471494494494494

W2507507507517517540540540540

b179179179189189212212212212

W7-3200 can expand to 4000A,which mounting dimension is as same as 4P of CDW7-3200DW7-2000 the mounting dimension is same regardless of different current used in"horizonal-connected" or "vertical-connected"

CDW7Standard: IEC 60947-2

CDW7-2000A~6300A

CDW7-2000A drawout circuit breaker vertical connection diagram

Page 62: Catalogo Delixi

Delixi Electric 55

CDW7-2000~6300 panel cut-out dimension and mounting dimension Unit:mm

CDW7-2000CDW7-3200CDW7-6300

a

306366366

b

346406406

c3P00189(4000/5000A)246.5(6300A)

4P47.557.5246.5(4000/5000A)--

CDW7Standard: IEC 60947-2

CDW7-1000

CDW7-2000~6300

CDW7-2000~6300A

CDW7-2000~6300A

CDW7-1000ACDW7-1000A

Page 63: Catalogo Delixi

Delixi Electric56

41 42 when controller power choose DC,the output is DC24V,user can select DCpower module43 44 circuit breaker status detection terminal(used when MCR function included)45 overload pre-alarm signal output46 automatic diagnosis alarm signal output47 fault trip alarm signal output48 earthing but non-tripping,only alarm signal output49 four groups of contacts output common terminal50 51 externally sensor input terminal58 able to directly connect to power supply(automatic pre-energization),also ableto join up with normal open pushbutton to connect to power supply(manual pre-energization)

F X with different current ratings shall con-nect with different sources.

CDW7Standard: IEC 60947-2

Auxiliary connection diagramn

Page 64: Catalogo Delixi

Delixi Electric 57

CDW7Standard: IEC 60947-2

Pin functions:Pin 1# and 2#: Auxiliary power input,pin 1# ispositive for DC inputPin 3#, 4#, 5#: Fault trip contact output (4# iscommon terminal); contact capacity: AC380V, 16APin 6# and 7#, 8# and 9#: Two groups of auxiliarycontacts for breaker status; contact capacity:AC380V, 16A12#,13#(Contact1)and 14#,15#(Contact2)and 16#,17#(Contact3)and 18#,19#(Contact4):Output offour groups of signal for controllers,contactcapacity:4A/240V 7A/24VDC20#: Earth protection21#~24#:input of voltage signal (Note:the order cantbe wrong)

Note: 1. If the control voltage values of Q, F, X, and M are different to eachother, these components can be connected to different power supply units; in theapplication, the shunt release and closing electromagnet shall be connectedserially with normally open and normally closed auxiliary contacts (the partenclosed by dotted lines shall be connected by the user; the part represented by atwo-dot chain line is the wiring of circuit 51); Note 2: The pin 35# can be connected to the power supply directly (automaticpre-energy storage) or connected serially to a normally open button and then tothe power supply (manual pre-energy storage); Note 3: If the user requests, pin #6~#7 can be connected to normally closedcontacts; Note 4: The ECW power supply module I is a DC power supply module, and itcan be omitted if the power supply is AC power supply; the polarity and lead-ins/lead-outs shall not be reversed (for draw-out type circuit breakers, the lead-outsof the power supply module has been connected before the circuit break isshipped from the factory); Note 5: In case of circuit 47, the auxiliary contacts are four closed and fouropen contacts; pin #25 and #26 are input terminals of an external current trans-former , used for earth fault protection as (3P+N)T type ; Note 6: In case of circuit 51, the auxiliary contacts are six closed and six opencontacts (or five closed and five open contacts); pin #25, #26, and #51 formnormally open and normally closed contacts; Note 7: If Profibus or any other protocol is used, ECW-H + DP conversion moduleand other conversion modules must be ordered; ECW power supply module lV andECW201 relay module must be ordered separately; Note 8:Pin #12~#19 input/output contacts can be user-defined programmablesignal contacts.

Components:Q - Under-voltage releaseF - Shunt releaseX – Closing electromagnetDF - Auxiliary switchM - MotorSB1—Button for closingSB2—Button for shunt

Page 65: Catalogo Delixi

Delixi Electric58

1# 2#: 1# is the front terminal when DC is supplied by auxiliary power3# 4# 5

AC380V 16A6# 7# 8# 9#:two groups of circuit breaker status auxiliary terminal: AC380V 16A10# 11#: respectively as the communication leading-out of RS485A ,RS485B12#: overload pre-alarm signal output13#: communication remote control shunt release output14#: communication remote control closing output or instantaneous short time-delaytrip signal output15#: communication remote control energy storage or long time-delay trip signal output16#: S-earth(RS-485 transmissionn common ground wire17#: load monitor output119#: signal output common earth wire21#: neutral voltage signal N phase23#: voltage signal B phase

1

2: terminal 35# can directly connect to power supply(automatic pre-energy storage),or join up with normal openpushbutton to connect power supply(manual pre-energystorage)3: terminal 6#~7# can lead out normal close contact if usersuggested4: ECW power supply module is DC power supply module,the module doesn't exist when power supply current is AC,polarity,incoming line and leading-out line shall not con-nected reversely(leading-out terminal of power supply mod-ule in drawout type had been connected before sale)5: in 47 circuit,auxiliary contact is 4 open 4 close;25# 26# isinput terminal of external sensor6: in 51 circuit,auxiliary contact is 6open6close(5open5close);25# 26# 51# form normal open normal closecontact(earth-leakage protection excluded)7: if using profibus or other protocols, user shall orderECW-H+HP transformation module and others;ECW powersupply moduleV,ECW201 relay module and others shallorder seperately8: #12~#19 output input contacts are programmableself-defined signal contaccts

18#: load monitor signal 220#: PE line ,shield earth wire22#: voltage signal A phase24#: voltage signal C phase

CDW7Standard: IEC 60947-2

Page 66: Catalogo Delixi

Delixi Electric 59

CDW7Standard: IEC 60947-2

Other additional parameter

Page 67: Catalogo Delixi

Delixi Electric60

CDW7 Series Air Circuit Breakers

Order Instructions

Note:for any special requirement,please contact with the manufacturer.

Customer Sets purchased Date

Mode CDW7 Fixed Draw-out 3 Poles 4Poles

AC400 AC690 Rated current In= ARated voltage

H Type Intelligent electronic trip

Mechanical interlock

Accessaries

Basic function Overload long delaytime protection

Short-circuit shortdelay time protection

Short-circuit instantaneousprotection

Earthing protection Load monitoring function(Not available for L type)

Metering function

Power supply AC 230V AC 400V DC 220V DC 110V

Under-voltage trip

Under-voltage instantaneous trip

Under-voltage time-delay trip

AC 230V AC 400V

1s 3s 5s

AC 230V AC 400V DC 220V DC 110V

AC 230V AC 400V DC 220V DC 110V

AC 230V AC 400V DC 220V DC 110V

Shunt trip

Energy releasing electromagnet

Motor Driven

Interphase barrier

N phase external connection

Escutcheon

Earth-leakage CT(Only for cable)

Auxiliary switch

Auxiliary Connection Terminal

standard(4a4b) special(6a6b)

1-lock,1-key

Steel-cable interlock

Interlocking rod with 3 switches

2-lock,1-key

Interlocking rod with 2 switches

Door interlock(Available for Draw-out type)

3-lock,1-key

Page 68: Catalogo Delixi

Delixi Electric 61

Function

DescriptionMain circuitRated insulation voltage: 690 VRated operational voltage: up to 660 VFrequency limits: 50/60 HzRated operational current and power of controlled motors are shown in the tablebelowControl circuitControl circuit supply voltage Us:AC 36V, 110V, 127V, 220/230V, 380/400VDC 110V, 220VTechnical featuresCompact, light, low consumption, long-life durabilityFlame-resistant enclosure ensures a safe & reliable serviceFull range auxiliaries:- auxiliary contact module- time delay module- mechanical interlock moduleDirect connection with thermal overload relay to form electomagnetic starter

Technical data

Standard and certificationIEC 60947-4-1KEMA, CE

CDC17Standard: IEC 60947-4-1

Page 69: Catalogo Delixi

Delixi Electric62

CDC17Standard: IEC 60947-4-1

CDC17-185~330CDC17-115~150

Overall dimensions

CDC17-9~32 CDC17-40~95

Note:C1max-Contactor+CDF4 C2max-Contactor+CDLA

Installation dimensions

TypeCDC17-9~12CDC17-18CDC17-25CDC17-32CDC17-40~65CDC17-80~95

Amax454556.556.57585

Cmax77829195115123

Bmax68687979127127

C1max109115124127145153

C2max133138149152170178

a35 0.21

40 0.21

40 0.21

b59 0.28

66 0.43

105 0.57

c4.5

4.5

6.5

unit:mm

TypeCDC17-185CDC17-225CDC17-265, 330

A138138171

B180199207

A1111111144

C163163201

C19595119

a1404848

a2202525

a3808096

b1158172180

b2154172180

91111

b3150150166

17711

CDC17-630~1000CDC17-400~500

Page 70: Catalogo Delixi

Delixi Electric 63

ModelRated operationalcurrent A

Rated operational voltage VRated insulation voltage VRated conventional thermal current APower of controlled 3-phase cage motor(AC-3)kWAC-3

AC-4

Mechanical durabilities(x104 cycles)AC Coil

Accessories

Matched RelayMatched FuseCross Sectionof Cable mm2

Weight Kg

CDC17Standard: IEC 60947-4-1

Characteristics

Electric durabilities(x104 operations)Operating rate(cycles/h)Electric durabilities(x104 operations)Operating rate(cycles/h)

Coil voltage VOperational voltage VDrop-out voltage VInrush VASealed VAHeat dissipation WAuxiliary contact

Time-delay blockMechanical Interlock

Number of PieceFlexible cableInflexible cable

380V / 400V

660V

AC-3AC-4AC-3AC-4

380V/400V660V

Front mountSide mountFront mount

CDC17-121258.92

5.57.5

1 2

CDC17-18187.7123.8

327.59

RT16-321 2460.335

CDC17-25258.5184.4

401115

110113~4

CDR17-32RT16-401 2

0.513

CDC17-323212217.5

501518.580

800

RT16-501 26100.510

CDC17-993.56.61.5380 / 400 6606902045.5100120020300100036, 48, 110, 220, 38085%~110%Us20%~75%Us7081.8~2.7CDF4-CDLA2 or CDLA3CDJL17-1CDR17-18RT16-201 22.540.315

Page 71: Catalogo Delixi

Delixi Electric64

ModelRated operationalcurrent A

Rated operational voltage VRated insulation voltage VRated conventional thermal current APower of controlled 3-phase cage motor(AC-3)kWAC-3

AC-4

Mechanical durabilities(x104 cycles)AC Coil

Accessories

Matched RelayMatched FuseCross Sectionof Cable mm2

Weight Kg

CDC17Standard: IEC 60947-4-1

CDC17-9595445521.3

45

RT16-2001 250 2550 -

Electric durabilities(x104 operations)Operating rate(cycles/h)Electric durabilities(x104 operations)Operating rate(cycles/h)

Coil voltage VOperational voltage VDrop-out voltage VInrush VASealed VAHeat dissipation WAuxiliary contact

Time-delay blockMechanical Interlock

Number of PieceFlexible cableInflexible cable

380V / 400V

660V

AC-3AC-4AC-3AC-4

380V/400V660V

Front mountSide mountFront mount

CDC17-5050243912

802233

RT16-801 21625 -

CDC17-404018.5349380 / 400 6606906018.5308012002030080036, 48, 110, 220, 38085%~110%Us20%~75%Us200206~10CDF4-CDLA2 or CDLA3CDJL17-2CDR17-95RT16-631 21016 -1.14

CDC17-6565284214

3037

RT16-1001 22525 -

CDC17-8080374917.3

125374560

600

RT16-1251 250 2550 -1.35

Page 72: Catalogo Delixi

Delixi Electric 65

CDC17Standard: IEC 60947-4-1

ModelRated operationalcurrent A

Rated operational voltage VRated insulation voltage VRated conventional thermal current APower of controlled 3-phase cage motor(AC-3)kWAC-3

AC-4

Mechanical durabilities(x104 cycles)AC Coil

Accessories

Matched RelayMatched FuseCross Sectionof Cable mm2

Weight Kg

Electric durabilities(x104 operations)Operating rate(cycles/h)Electric durabilities(x104 operations)Operating rate(cycles/h)

Coil voltage VOperational voltage VDrop-out voltage VInrush VASealed VAHeat dissipation WAuxiliary contact

Time-delay blockMechanical Interlock

Number of PieceFlexible cableInflexible cable

380V / 400V

660V

AC-3AC-4AC-3AC-4

380V/400V660V

Front mountSide mountFront mount

CDC17-26526510517098

300132160

300

30

11988318.9

JR20-400RT16-4001 2240 -- 32x46.6

CDC17-1501506011061

75100

1 2120 -- 25x3

CDC17-1851857911869

21090110

6954513.5

RT16-2501 2150 -- 25x3

CDC17-2252258513582

225110129

600

JR20-250RT16-2501 2185 -- 32x4

CDC17-330330117225118

300160220

1 2240 -- 30x56.6

CDC17-115115528649380 / 400 66069015055806012002030060036, 48, 110, 220, 38085%~110%Us20%~75%Us559339.5-CDFC17-11,CDFC17-12-CDJL17-3CDR17-185RT16-2001 295 50- 20x32.15

Page 73: Catalogo Delixi

Delixi Electric66

CDC17Standard: IEC 60947-4-1

CDC17-10001000-580-

1000560560

RT17-4/-1250

80x5

Electric durabilities(x104 operations)Operating rate(cycles/h)Electric durabilities(x104 operations)Operating rate(cycles/h)

Coil voltage VOperational voltage VDrop-out voltage VInrush VASealed VAHeat dissipation WAuxiliary contact

Time-delay blockMechanical Interlock

Number of PieceFlexible cableInflexible cable

380V / 400V

660V

AC-3AC-4AC-3AC-4

380V/400V660V

Front mountSide mountFront mount

CDC17-500500147355145

265335

JR20-630RT16-630

18540x5

CDC17-630630188460170

800335450

10501210

-RT16-800

24050x522.8

CDC17-800800242530215

450500

600

RT17-4/1000

-60x5

ModelRated operationalcurrent A

Rated operational voltage VRated insulation voltage VRated conventional thermal current APower of controlled 3-phase cage motor(AC-3)kWAC-3

AC-4

Mechanical durabilities(x104 cycles)AC Coil

Accessories

Matched RelayMatched FuseCross Sectionof Cable mm2

Weight Kg

CDC17-400400138305135380 / 400 660690500220280603002030600110, 220, 38085%~110%Us20%~75%Us780108--CDFC17-21-JR20-400RT16-500 215030x59.36

Page 74: Catalogo Delixi

Delixi Electric 67

Reference

CDC17910CDC17901CDC171210CDC171201CDC171810CDC171801CDC172510CDC172501CDC173210CDC173201CDC174011CDC175011CDC176511CDC178011CDC179511CDC1711522CDC1715022CDC1718522CDC1722522CDC1726522CDC1733022CDC1740022CDC1750022CDC1763022CDC1780022CDC17100022

Rate current (A)

9

12

18

25

32

40506580951151501852252653304005006308001000

Contact blooksNO10101010101111122222222222

NC01010101011111122222222222

Ordering information

CDC17Standard: IEC 60947-4-1

coil voltage codecoil voltage (V) 36

C48E

110F

220M

380Q

frequency codefrequency 50Hz

560Hz6

Page 75: Catalogo Delixi

Delixi Electric68

CDC17Standard: IEC 60947-4-1

DescriptionCDF4-20 Top auxiliary contactCDF4-11 Top auxiliary contactCDF4-02 Top auxiliary contactCDF4-22 Top auxiliary contactCDF4-13 Top auxiliary contactCDF4-31 Top auxiliary contactCDF4-04 Top auxiliary contactCDF4-40 Top auxiliary contactCDLA2 On delay 0.1~3SCDLA2 On delay 0.1~30SCDLA2 On delay 10~180SCDLA3 off delay 0.1~3SCDLA3 off delay 0.1~30SCDLA3 off delay 10~180SCDFC17-11 Side auxiliary contactCDFC17-12 Side auxiliary contactCDFC17-21 Side auxiliary contactCDJL17-1 Mechanical interlocking moduleCDJL17-2 Mechanical interlocking moduleCDJL17-3 Mechanical interlocking module

ReferenceCDF420CDF411CDF402CDF422CDF413CDF431CDF404CDF440CDFC1711CDFC1712CDFC1721CDLA2ON0CDLA2ON2CDLA2ON4CDLA3OFF0CDLA3OFF2CDLA3OFF4CDJL171CDJL172CDJL173

Application scope

CDC17-9~95A

CDC17-9~95A

CDC17-115~330ACDC17-115~330ACDC17-400~1000ACDC17-9~32ACDC17-40~95ACDC17-115~330A

Page 76: Catalogo Delixi

Delixi Electric 69

CDR17Standard: IEC 60947-4-1 60947-5-1

Function CDR17 series thermal overload relays provide:Protection of circuits and motors against overloadProtection of circuits and motors against phase lossMotor starters installation in association with contactors

DescriptionMain circuit:Frequency limits: 50/60 HzRated insulation voltage: 690 VRated operational voltage: up to 690 VFrame size rated current: 18, 32, 95, 185ARated operational current and range of current setting are shown in the tablebelow

Table 1

Technical data

18

32

18

32

690

690

1801180218031804180518061807180818091810181118121813181418151816181718183201320232033204320532063207

0.150.180.250.360.50.70.91.21.82.53.64.86.3791215186.37912182532

0.1~0.13~0.150.12~0.16~0.180.18~0.2~0.250.25~0.32~0.360.35~0.4~0.50.5~0.6~0.70.63~0.72~0.90.9~1~1.21.2~1.6~1.81.8~2~2.52.5~3.2~3.63.5~4~4.84.5~5~6.35~6~76.3~7.2~99~10~1211~13~1514~16~184.5~5~6.35~6~76.3~7.2~99~10~1212~16~1818~20~2523~25~32

CDR17-18

CDR17-32

CDR1718P15CDR1718P18CDR1718P25CDR1718P36CDR1718P5CDR1718P7CDR1718P9CDR17181P2CDR17181P8CDR17182P5CDR17183P6CDR17184P8CDR17186P3CDR17187CDR17189CDR171812CDR171815CDR171818CDR17326P3CDR17327CDR17329CDR173212CDR173218CDR173225CDR173232

RatedinsulationvoltageUi V

Thermal protectionNo

RatedcurrentIe A

Framesizeratedcurrent

Ratedcurrentsetting A

Range ofcurrentsetting A

Type Reference

Page 77: Catalogo Delixi

Delixi Electric70

CDR17Standard: IEC 60947-4-1 60947-5-1

95

185

95

185

690

690

95019502950395049505950695079508950895108501850285038504850585068507850885098510

121825324050657080955065708095115135150160185

9~10~1212~16~1818~20~2523~25~3230~36~4037~45~5048~55~6555~63~7063~70~8075~90~9537~45~5048~55~6555~63~7063~70~8075~90~9590~100~115105~115~135120~135~150130~150~160150~160~185

CDR17-95

CDR17-185

CDR179512CDR179518CDR179525CDR179532CDR179540CDR179550CDR179565CDR179570CDR179580CDR179595CDR1718550CDR1718565CDR1718570CDR1718580CDR1718595CDR17185115CDR17185135CDR17185150CDR17185160CDR17185185

Table 2 Basic data for control circuit and auxiliary circuit

Ratedinsulationvoltage V

Conventionalfree air thermalcurrent A

Ratedoperationalvoltage V

RatedcurrentA

Ratedcontrolcapacity

690 6

Utilizationcategory

RatedfrequencyHz

Circuittype

Controlcircuit

Auxiliarycircuit

AC-15

DC-13AC-15

DC-13

50

50

220(230)380(400)660(690)220(230)220(230)380(400)660(690)220(230)

1.64(1.57)0.95(0.90)0.55(0.52)0.23(0.22)6

360 VA

50 W

Table 3 Limits of operation of relays when energized on all poles

Sequence Multiples ofcurrent setting

123

4

1.051.21.5

7.2

Initial condition Ambient airtemperature

Tripping time

Non-trip within 2 hours<2hTripclass

From coldFrom hot(immediatelyfollowing sequence 1test)From cold

+20oC

10A1010A10

<2min<4min2s<TP²10s4s<TP²10s

Thermal protectionNo

RatedcurrentIe A

Framesizeratedcurrent

Ratedcurrentsetting A

Range ofcurrentsetting A

Type Reference

Page 78: Catalogo Delixi

Delixi Electric 71

CDR17Standard: IEC 60947-4-1 60947-5-1

Table 4 Limits of operation when energized on two poles

Sequence Multiples of current setting

1

2

1.0

1.15

Initial condition Ambient airtemperature

Tripping time

Non-tripwithin 2 hours<2h

From cold state

From hot state(immediately followingsequence 1 test)

+20oCAny two poles The third-pole

0.9

0

Table 5 Temperature compensation characteristic

Sequence Multiples ofcurrent setting

12

34

56

78

1.01.2

1.051.30

0.951.2

1.051.35

Initial condition Ambient airtemperature

Tripping time

>2h<2h

>2h<2h

>2h<2h

>2h<2h

From cold stateFrom hot state(immediatelyfollowing sequence 1 test)From cold stateFrom hot state(immediatelyfollowing sequence 3 test)From cold stateFrom hot state(immediatelyfollowing sequence 5 test)From cold stateFrom hot state(immediatelyfollowing sequence 7 test)

+55oC

-10oC

+60oC

-20oC

Overall dimensions

CDR17-18

Page 79: Catalogo Delixi

Delixi Electric72

CDR17Standard: IEC 60947-4-1 60947-5-1

CDR17-95

CDR17-185

CDR17-32

Page 80: Catalogo Delixi

Delixi Electric 73

LMK Current TransformerStandard: BS7626, IEC44-1

LMK Current Transformer provide: Measuring current

Function

Description Technical Data Primary current: 100A-5000A Secondary approval: 5A, 1A Maximum voltage: 0.66kV Class: 0.5, 1.0, 3.0 Short time thermal current: Ith=100Ih Rated security coefficient: FS<5

Standard and Certification BS7626, IEC44-1

Overall dimensions

LMK-0.66-20LMK-0.66-30LMK-0.66-40LMK-0.66-50LMK-0.66-60LMK-0.66-80LMK-0.66-100LMK-0.66-120

87799999126118136136

68607582102125170190

4237404040404041

Model H W D

Unit: mm

Page 81: Catalogo Delixi

Delixi Electric74

LMK Current TransformerStandard: BS7626, IEC44-1

Class: 0.5Maximum Voltage: 0.66KV

Model Current ratio(A)

Rated Load(VA)

Bar Diameter(mm) (mm)

Number of Turnsthrough the core Reference

30/550/575/5100/5100/5150/5200/5100/5200/5250/5300/5250/5300/5400/5500/5300/5400/5500/5600/5750/5800/51000/5500/5600/5750/5800/51000/51200/51500/5600/5750/5800/51000/51200/51500/52000/52500/5600/5750/5800/51000/51200/51500/52000/52500/53000/51500/52000/52500/53000/54000/55000/5

5-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.7510-3.7510-3.7510-3.7510-3.755-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7515-3.7515-3.7520-3.7510-3.7510-3.7510-3.7510-3.7510-3.7515-3.7515-3.7520-3.7520-3.7515-3.7515-3.7520-3.7520-3.7525-3.7525-3.75

20202020202020202020203030303035353535353535454545454545455050505050505050606060606060606060606060606060

5322111211111111111111111111111111111111111111111111

LMKP63020LMKP65020LMKP67520LMKP610020LMKP610020LMKP615020LMKP620020LMKP610030LMKP620030LMKP625030LMKP630030LMKP625040LMKP630040LMKP640040LMKP650040LMKP630050LMKP640050LMKP650050LMKP660050LMKP675050LMKP680050LMKP6100050LMKP650060LMKP660060LMKP675060LMKP680060LMKP6100060LMKP6120060LMKP6150060LMKP660080LMKP675080LMKP680080LMKP6100080LMKP6120080LMKP6150080LMKP6200080LMKP6250080LMKP6600100LMKP6750100LMKP6800100LMKP61000100LMKP61200100LMKP61500100LMKP62000100LMKP62500100LMKP63000100LMKP61500120LMKP62000120LMKP62500120LMKP63000120LMKP64000120LMKP65000120

LMK-0.66-20

LMK-0.66-30

LMK-0.66-40

LMK-0.66-50

LMK-0.66-60

LMK-0.66-80

LMK-0.66-100

LMK-0.66-120

30 1030 1030 1040 1040 1040 1040 1050 1050 1050 1050 1050 1050 1050 1060 2060 2060 2060 2060 2060 2060 2080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30

Rated Load(VA)

Page 82: Catalogo Delixi

Delixi Electric 75

LMK Current TransformerStandard: BS7626, IEC44-1

Class: 1Maximum Voltage: 0.66KV

532211211111111111111111111111111111111111111111111111

LMK-0.66-20

LMK-0.66-30

LMK-0.66-40

LMK-0.66-50

LMK-0.66-60

LMK-0.66-80

LMK-0.66-100

LMK-0.66-120

30/550/575/5100/5150/5200/5100/5200/5250/5300/5250/5300/5400/5500/5600/5300/5400/5500/5600/5750/5800/51000/51200/5500/5600/5750/5800/51000/51200/51500/52000/5600/5750/5800/51000/51200/51500/52000/52500/5600/5750/5800/51000/51200/51500/52000/52500/53000/51500/52000/52500/53000/54000/55000/5

5-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.7510-3.755-3.755-3.755-3.7510-3.7510-3.7510-3.7510-3.7510-3.755-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7515-3.7515-3.7520-3.7510-3.7510-3.7510-3.7510-3.7510-3.7515-3.7515-3.7520-3.7520-3.7515-3.7515-3.7520-3.7520-3.7525-3.7525-3.75

202020202020202020203030303030353535353535353545454545454545455050505050505050606060606060606060606060606060

LMKP6P13020LMKP6P15020LMKP6P17520LMKP6P110020LMKP6P115020LMKP6P120020LMKP6P110030LMKP6P120030LMKP6P125030LMKP6P130030LMKP6P125040LMKP6P130040LMKP6P140040LMKP6P150040LMKP6P160040LMKP6P130050LMKP6P140050LMKP6P150050LMKP6P160050LMKP6P175050LMKP6P180050LMKP6P1100050LMKP6P1120050LMKP6P150060LMKP6P160060LMKP6P175060LMKP6P180060LMKP6P1100060LMKP6P1120060LMKP6P1150060LMKP6P1200060LMKP6P160080LMKP6P175080LMKP6P180080LMKP6P1100080LMKP6P1120080LMKP6P1150080LMKP6P1200080LMKP6P1250080LMKP6P1600100LMKP6P1750100LMKP6P1800100LMKP6P11000100LMKP6P11200100LMKP6P11500100LMKP6P12000100LMKP6P12500100LMKP6P13000100LMKP6P11500120LMKP6P12000120LMKP6P12500120LMKP6P13000120LMKP6P14000120LMKP6P15000120

Model Current ratio(A)

Rated Load(VA)

Bar Diameter(mm) (mm)

Number of Turnsthrough the core Reference

30 1030 1030 1040 1040 1040 1040 1040 1050 1050 1050 1050 1050 1050 1050 1060 2060 2060 2060 2060 2060 2060 2060 2060 2080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30

Page 83: Catalogo Delixi

Delixi Electric76

RT16 FuseStandard: IEC 60269

Function

Description

RT16 fuse provide: Protection of circuits against overload current Protection of circuits against short-circuit current

Technical Data Rate current range:2-630A Rate voltage:500/660V Rate breaking capacity:120KA(500V),50KA(660V)

Standard and certification IEC60269 CE

Overall dimensions

abcdeABC1C2DEFG

78.52957496301206185100257.5

13548626765820083961752510.530

150587267664250991122002510.530

1506785676642501051202102510.530

Type RT16-00 RT16-1 RT16-2 RT16-3

Page 84: Catalogo Delixi

Delixi Electric 77

RT16 FuseStandard: IEC 60269

24681012162025324050638010012516080100125160200250125160200250300315355400315355400450500630

Ordering information

RT16002RT16004RT16006RT16008RT160010RT160012RT160016RT160020RT160025RT160032RT160040RT160050RT160063RT160080RT1600100RT1600125RT1600160RT16180RT161100RT161125RT161160RT161200RT161250RT162125RT162160RT162200RT162250RT162300RT162315RT162355RT162400RT163315RT163355RT163400RT163450RT163500RT163630

ReferenceFuse-link Rate current In(A) Suitable fuse bases Weight(g)

RT16-00

RT16-1

RT16-2

RT16-3

170

450

660

850

ReferenceFuse Base Rate current In(A) Material Weight(g)

RT16-00

RT16-1

RT16-2

RT16-3

CeramicResinCeramicResinCeramicResinCeramicResin

RT1600ZTRT1600ZSRT161ZTRT161ZSRT162ZTRT162ZSRT163ZTRT163ZS

RT16-00

RT16-1

RT16-2

RT16-3

160

250

400

630

200

700

1150

1280

Page 85: Catalogo Delixi

Delixi Electric78

RT18 FuseStandard: IEC 60269

RT18 fuse provide: Protection of circuits against overload current Protection of circuits against short-circuit current

Function

Description Technical Data Rate current range:2-63A Rate voltage:380V Rate breaking capacity:100KA

Standard and certification IEC60269 CE

Overall dimensions

RT18-32RT18-63

10 3814 51

10.513.8

38 0.651 +0.6

-1.0

10.3 0.114.3 0.1

Type Size L C Hmax

RT18-32RT18-63

Type A B C D E F G6378

6076

79103

3535

80110

1825

5475

Cylindrical Fuse

Holder of fuse

Page 86: Catalogo Delixi

Delixi Electric 79

RT18 FuseStandard: IEC 60269

ReferenceCylindrical Fuse Rate current In(A) Weight(g)

ReferenceHolder of fuse Rate current In(A) Weight(g)Pole Note

24681012162025322468101216202532405063

1P2P3P1P2P3P1P2P3P1P2P3P1P2P3P1P2P3P

RT10382RT10384RT10386RT10388RT103810RT103812RT103816RT103820RT103825RT103832RT14512RT14514RT14516RT14518RT145110RT145112RT145116RT145120RT145125RT145132RT145140RT145150RT145163

RT18-32

RT18-63

8

20

Material:ResinPilotlamp

Material:ResinNot Pilotlamp

Material:NylonPilotlamp

Material:NylonNot Pilotlamp

Material:ResinNot Pilotlamp

Material:ResinPilotlamp

RT1832ZXBRT1832Z2XBRT1832Z3XBRT1832ZBRT1832Z2BRT1832Z3BRT1832ZXRT1832Z2XRT1832Z3XRT1832ZRT1832Z2RT1832Z3RT1863ZXBRT1863Z2XBRT1863Z3XBRT1863ZBRT1863Z2BRT1863Z3B

RT18-32X

RT18-32

RT18-32X

RT18-32

RT18-63X

RT18-63

32

32

32

32

63

63

82

82

82

82

206

206

Page 87: Catalogo Delixi

Delixi Electric80

JXF Power Distribution BoxStandard: IEC 670.1989, IEC 60439-1

Function

Description

JXF power distribution box provide: Control,monitoring,measurement and protectionfor the electric power lines and the main power control equipment

Technical Data Rated operating voltage:220V,380V Rated insulated voltage:400V,660V Rated operating current:400A Protection rating:IP30 for complete set,IP43 for box Instantaneous withstand current:6KA,15KA

Standard and certification IE670.1989,IEC60439-1

Overall dimensions

cover plate

sealing strip

sealing strip

handle lock

hingedoor

boxpeg board

Page 88: Catalogo Delixi

Delixi Electric 81

JXF252014JXF302514JXF302518JXF303014JXF303018JXF403014JXF403020JXF504014JXF504020JXF504025JXF604014JXF604020JXF604025JXF605014JXF605020JXF605025JXF705016JXF705020JXF705025JXF806020JXF806025JXF1008020JXF1008025JXF1008030

JXF Power Distribution BoxStandard: IEC 670.1989, IEC 60439-1

Reference

JXF-2520/14JXF-3025/14JXF-3025/18JXF-3030/14JXF-3030/18JXF-4030/14JXF-4030/20JXF-5040/14JXF-5040/20JXF-5040/25JXF-6040/14JXF-6040/20JXF-6040/25JXF-6050/14JXF-6050/20JXF-6050/25JXF-7050/16JXF-7050/20JXF-7050/25JXF-8060/20JXF-8060/25JXF-10080/20JXF-10080/25JXF-10080/30

1.01.01.01.01.01.01.01.01.01.01.21.21.21.21.21.21.21.21.21.51.51.51.51.5

250300300300300400400500500500600600600600600600700700700800800100010001000

200250250300300300300400400400400400400500500500500500500600600800800800

140140180140180140200140200250140200250140200250160200250200250200250300

290340340340340440440540540540640640640640640640740740740840840104010401040

150200200250250250250350350350350350350450450450450450450550550750750750

170220220220220320320420420420520520520520520520620620620720720920920920

158208208258258258258358358358358358358458458458458458458558558758758758

111111112222222222222222

Type

Thicknessof ironcharge

Figuredimension

Istallationdimension

Botoomboard Number

of lock

Dimension

H W D H1 B1 H6 B6

Page 89: Catalogo Delixi

Delixi Electric82

Function LD11 Series of indicator light provide:Pilot signal, anticipating signalsEmergency signals and other instructions incidents signal use

Description Technical dataRated voltage(V)

Rated current(mA)Working life(H)Brightness of light(cd/m2)Power frequency withstand voltageDegree of protection

LD11 Series of indicator lightStandard: IEC 60947-5-1

AC/DC6 12 24 36 48 110 220

5030000

402500V AC 1minIP65

Standard and certificationIEC 60947-5-1CE

AC220 380

20

Page 90: Catalogo Delixi

Delixi Electric 83

LD11 Series of indicator lightStandard: IEC 60947-5-1

Button colour Rated voltageAC.DC 6V

AC.DC 12V

AC.DC 24V

AC.DC 110V

AC.DC 220V

AC 220V

AC 380V

AC.DC 6V

AC.DC 12V

AC.DC 24V

ReferenceLD1122A21T7LD1122A21T3LD1122A21T4LD1122A21T5LD1122A21T8LD1122A21J7LD1122A21J3LD1122A21J4LD1122A21J5LD1122A21J8LD1122A21B7LD1122A21B3LD1122A21B4LD1122A21B5LD1122A21B8LD1122A21F7LD1122A21F3LD1122A21F4LD1122A21F5LD1122A21F8LD1122A21M7LD1122A21M3LD1122A21M4LD1122A21M5LD1122A21M8LD1122A41M7LD1122A41M3LD1122A41M4LD1122A41M5LD1122A41M8LD1122A41Q7LD1122A41Q3LD1122A41Q4LD1122A41Q5LD1122A41Q8LD1122B21T7LD1122B21T3LD1122B21T4LD1122B21T5LD1122B21T8LD1122B21J7LD1122B21J3LD1122B21J4LD1122B21J5LD1122B21J8LD1122B21B7LD1122B21B3LD1122B21B4

Overall dimensions Unit:mm

Page 91: Catalogo Delixi

Delixi Electric84

Button colour Rated voltageAC.DC 24V

AC.DC 110V

AC.DC 220V

AC 220V

AC 380V

AC.DC 6V

AC.DC 12V

AC.DC 24V

AC 220V

AC 380V

ReferenceLD1122B21B5LD1122B21B8LD1122B21F7LD1122B21F3LD1122B21F4LD1122B21F5LD1122B21F8LD1122B21M7LD1122B21M3LD1122B21M4LD1122B21M5LD1122B21M8LD1122B41M7LD1122B41M3LD1122B41M4LD1122B41M5LD1122B41M8LD1122B41Q7LD1122B41Q3LD1122B41Q4LD1122B41Q5LD1122B41Q8LD1122C21T7LD1122C21T3LD1122C21T4LD1122C21T5LD1122C21T8LD1122C21J7LD1122C21J3LD1122C21J4LD1122C21J5LD1122C21J8LD1122C21B7LD1122C21B3LD1122C21B4LD1122C21B5LD1122C21B8LD1122C41M7LD1122C41M3LD1122C41M4LD1122C41M5LD1122C41M8LD1122C41Q7LD1122C41Q3LD1122C41Q4LD1122C41Q5LD1122C41Q8

Overall dimensions Unit:mm

LD11 Series of indicator lightStandard: IEC 60947-5-1

Page 92: Catalogo Delixi

Delixi Electric 85

LD11 Series of indicator lightStandard: IEC 60947-5-1

Button colour Rated voltageAC.DC 6V

AC.DC 12V

AC.DC 24V

AC 220V

AC 380V

ReferenceLD1122D21T7LD1122D21T3LD1122D21T4LD1122D21T5LD1122D21T8LD1122D21J7LD1122D21J3LD1122D21J4LD1122D21J5LD1122D21J8LD1122D21B7LD1122D21B3LD1122D21B4LD1122D21B5LD1122D21B8LD1122D41M7LD1122D41M3LD1122D41M4LD1122D41M5LD1122D41M8LD1122D41Q7LD1122D41Q3LD1122D41Q4LD1122D41Q5LD1122D41Q8

Overall dimensions Unit:mm

Page 93: Catalogo Delixi

Delixi Electric86

Function LAY3 Serie of Pushbuttons: Control and signal chain

Description Technical dataConventional thermal current(A)AC-15 Rated operational voltage(V)

Rated operational current(A)DC-13 Rated operational voltage(V)

Rated operational current(A)Degree of protectionDegree of pollutionType of installationAltitudeAmbient air temperature

LAY3 Serie of pushbuttons

10660 380 2201.5 2.5 4.5440 220 1100.1 0.3 0.6IP553

2000m-5 ~+40

Standard and certificationIEC 60947-5-1

Standard: IEC 60947-5-1

Page 94: Catalogo Delixi

Delixi Electric 87

LAY3 Serie of pushbuttons

Button colour Contact blooks1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC

1NO+1NC1NO+1NC1NO+1NC

1NO+1NC1NO+1NC1NO+1NC

1NO+1NC1NO+1NC1NC

1NO+1NC1NO+1NC1NO+1NC

1NO+1NC1NO+1NC1NO+1NC

1NO+1NC1NO+1NC1NO+1NC

1NO+1NC1NO+1NC1NO+1NC

NoteMomentary(Non-illuminated)

Two-positionMaintained

Three-positionMaintained

Maintained

Incandescent lampAC DC 6V

LED AC DC 6V

NEON AC 220V

NEON AC 380V

Overall dimensions Unit:mm

Standard: IEC 60947-5-1

Flush ButtonReferenceLAY311BN4LAY311BN3LAY311BN2LAY311BN5LAY311BN6LAY311BN1

LAY311X204LAY311X203LAY311X202

LAY311X304LAY311X303LAY311X302

LAY311ZS14LAY311ZS13LAY301ZS14

LAY311D4TLAY311D3TLAY311D4T

LAY311D4TLLAY311D3TLLAY311D5TL

LAY311D4MNLAY311D3MNLAY311D5MN

LAY311D4QNLAY311D3QNLAY311D5QN

Selector Switche-Short Handle

Emergency Stop Pushbutton

Flush Buttons Illuminated

LAY3 general

LAY3-X/2 Selector Swiches

LAY3-X/3 Selector Swiches

LAY3-ZS/1 Maintained

LAY3-D Illuminated

Page 95: Catalogo Delixi

Delixi Electric88

Function LAY7 Serie of Pushbuttons: Control and signal chain

Description Technical dataConventional thermal current(A)AC-15 Rated operational voltage(V)

Rated operational current(A)DC-13 Rated operational voltage(V)

Rated operational current(A)Degree of protectionDegree of pollutionType of installationAltitudeAmbient air temperature

LAY7 Serie of pushbuttons

10660 380 2201.1 2.0 3.3440 220 1100.25 0.5 1IP553

2000m-5 ~+40

Standard and certificationIEC 60947-5-1

CE

Standard: IEC 60947-5-1

Overall dimensions Unit:mm

Type

Flush Button MomentaryExtended Button MomentaryWhole protection cover buttonFlush Buttons IlluminatedMushroom Pushbutton IlluminatedMushroom Pushbutton Non-illuminatedFlush Button MaintainedExtended Button MaintainedMushroom Pushbutton MaintainedFlush Button Maintained IlluminatedEmergency Stop PushbuttonSelector Swiches-Short HandleSelector Swiches-Long HandleKey-operated Selector Swiches

22, 25, 30A

1420202224.524.5142024.52224.5262640

B1-2 block50

66

48

6648

3-4 block70

86

68

8648

Note: long 37mm, wide A 30mm B 42mm, in the table values is max.

Page 96: Catalogo Delixi

Delixi Electric 89

LAY7 Serie of pushbuttonsStandard: IEC 60947-5-1

Button colour Contact blooks1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC

1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC

1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC

NoteMomentary(Non-illuminated)

Maintained(Non-illuminated)

Momentary(Non-illuminated)

Maintained(Non-illuminated)

Flush ButtonReferenceLAY711BN12LAY711BN22LAY711BN32LAY711BN42LAY711BN52LAY711BN62LAY711BNZS12LAY711BNZS22LAY711BNZS32LAY711BNZS42LAY711BNZS52LAY711BNZS62

LAY711GN12LAY711GN22LAY711GN32LAY711GN42LAY711GN52LAY711GN62LAY711GNZS12LAY711GNZS22LAY711GNZS32LAY711GNZS42LAY711GNZS52LAY711GNZS62

LAY711JN12LAY711JN22LAY711JN32LAY711JN42LAY711JN52LAY711JN62

Extended Button

Whole protection cover button

Page 97: Catalogo Delixi

Delixi Electric90

LAY7 Serie of pushbuttonsStandard: IEC 60947-5-1

Button colour Contact blooks1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC2NO2NO2NO1NO+1NC1NO+1NC1NO+1NC2NO

1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC2NO2NO2NO1NO+1NC1NO+1NC1NO+1NC2NO

1NO+1NC1NO+1NC2NO1NO+1NC1NO+1NC1NO+1NC2NO

1NO+1NC1NO+1NC1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NC

NoteTwo-position Maintained

Three-position Maintained

Two-position Right MomentaryThree-position Right MomentaryThree-position Right and left MomentaryThree-position Right and left Momentary

Two-position Maintained

Three-position Maintained

Two-position Right MomentaryThree-position Right MomentaryThree-position Right and left MomentaryThree-position Right and left Momentary

Two-position MaintainedThree-position MaintainedThree-position MaintainedTwo-position Right MomentaryThree-position Right MomentaryThree-position Right and left MomentaryThree-position Right and left Momentary

Momentary(Non-illuminated)

Momentary(illuminated LED 6V)

Maintained(Non-illuminated)

Selector Switche-Short HandleReferenceLAY711X2022LAY711X2032LAY711X2042LAY711X3022LAY711X3032LAY711X3042LAY720X3022LAY720X3032LAY720X3042LAY711X2122LAY711X3122LAY711X3322LAY720X3322

LAY711XB2022LAY711XB2032LAY711XB2042LAY711XB3022LAY711XB3032LAY711XB3042LAY720XB3022LAY720XB3032LAY720XB3042LAY711XB2122LAY711XB3122LAY711XB3322LAY720XB3322

LAY711Y2002LAY711Y3002LAY720Y3002LAY711Y2102LAY711Y3102LAY711Y3302LAY720Y3302

LAY711M32LAY711M42LAY701M42LAY711DM3T2LLAY711DM4T2LLAY711DM5T2LLAY711MZS32LAY711MZS42LAY701MZS42

Selector Switche-Long Handle

Key-operated Selector Swiche

Mushroom Pushbutton

Page 98: Catalogo Delixi

Delixi Electric 91

LAY7 Serie of pushbuttonsStandard: IEC 60947-5-1

Button colour Contact blooks1NO+1NC1NO+1NC1NO

1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC

Note

Momentary LED 6V

Momentary LED 24V

Momentary LED 220V

Momentary NEON 220V

Momentary NEON 380V

Maintained LED 6V

Maintained LED 24V

Emergency Stop PushbuttonReferenceLAY711ZS32LAY711ZS42LAY710ZS42

LAY711D7T2LLAY711D3T2LLAY711D4T2LLAY711D5T2LLAY711D8T2LLAY711D7B2LLAY711D3B2LLAY711D4B2LLAY711D5B2LLAY711D8B2LLAY711D7M2LLAY711D3M2LLAY711D4M2LLAY711D5M2LLAY711D8M2LLAY711D1M2NLAY711D3M2NLAY711D4M2NLAY711D5M2NLAY711D6M2NLAY711D1Q2NLAY711D3Q2NLAY711D4Q2NLAY711D5Q2NLAY711D6Q2NLAY711DZS7T2LLAY711DZS3T2LLAY711DZS4T2LLAY711DZS5T2LLAY711DZS8T2LLAY711DZS7B2LLAY711DZS3B2LLAY711DZS4B2LLAY711DZS5B2LLAY711DZS8B2L

Flush Buttons Illuminated

Page 99: Catalogo Delixi

Delixi Electric92

LAY7 Serie of pushbuttonsStandard: IEC 60947-5-1

Button colour Contact blooks1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC

NoteMaintained LED 220V

Maintained NEON 220V

Maintained NEON 380V

Flush Buttons IlluminatedReferenceLAY711DZS7M2LLAY711DZS3M2LLAY711DZS4M2LLAY711DZS5M2LLAY711DZS8M2LLAY711DZS1M2NLAY711DZS3M2NLAY711DZS4M2NLAY711DZS5M2NLAY711DZS6M2NLAY711DZS1Q2NLAY711DZS3Q2NLAY711DZS4Q2NLAY711DZS5Q2NLAY711DZS6Q2N

Page 100: Catalogo Delixi

Delixi Electric 93

Function LAY8 Serie of Pushbuttons: Control and signal chain

Description

LAY8 Serie of pushbuttonsStandard: IEC 60947-5-1

Standard and certificationIEC 60947-5-1CE

Technical dataConventional thermal current(A)AC-15 Rated operational voltage(V)

Rated operational current(A)DC-13 Rated operational voltage(V)

Rated operational current(A)Degree of protectionDegree of pollutionType of installationAltitudeAmbient air temperature

10660 380 2201.5 2.5 4.5440 220 1100.2 0.4 0.8IP553

2000m-5 ~+40

Page 101: Catalogo Delixi

Delixi Electric94

Button colour Contact blooks1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC

1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC

1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC

1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC2NO1NO+1NC1NO+1NC2NO

1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC2NO1NO+1NC1NO+1NC2NO

NoteMomentary(Non-illuminated)

Maintained(Non-illuminated)

Waterproof(Non-illuminated)

Two-position Maintained

Three-position Maintained

Two-position Right MomentaryThree-position Right MomentaryThree-position Right and left Momentary

Two-position Maintained

Three-position Maintained

Momentary(Non-illuminated)Three-position Right MomentaryThree-position Right and left Momentary

Overall dimensions Unit:mm

Flush ButtonReferenceLAY811BN1LAY811BN2LAY811BN3LAY811BN4LAY811BN5LAY811BN6

LAY811ZS1LAY811ZS2LAY811ZS3LAY811ZS4LAY811ZS5LAY811ZS6

LAY811S1LAY811S2LAY811S3LAY811S4LAY811S5LAY811S6

LAY811X202LAY811X203LAY811X204LAY811X302LAY811X303LAY811X304LAY820X302LAY811X312LAY811X212LAY820X312

LAY811XB202LAY811XB203LAY811XB204LAY811XB302LAY811XB303LAY811XB304LAY820XB302LAY811XB212LAY811XB312LAY820XB332

Selector Switche-Short Handle

Selector Switche-Long Handle

LAY8 Serie of pushbuttonsStandard: IEC 60947-5-1

Page 102: Catalogo Delixi

Delixi Electric 95

Button colour Contact blooks1NO+1NC1NO+1NC

1NO+1NC1NO+1NC1NO

1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC

Note

LED AC.DC 6V

LED AC.DC 24V

LED AC.DC 220V

LED AC 220V

LED AC 380V

Overall dimensions Unit:mm

Mushroom PushbuttonReferenceLAY811M3LAY811M4

LAY811ZS3LAY811ZS4LAY810ZS4

LAY811D7T2LLAY811D3T2LLAY811D4T2LLAY811D5T2LLAY811D8T2LLAY811D7B2LLAY811D3B2LLAY811D4B2LLAY811D5B2LLAY811D8B2LLAY811D7M2LLAY811D3M2LLAY811D4M2LLAY811D5M2LLAY811D8M2LLAY811D7M4LLAY811D3M4LLAY811D4M4LLAY811D5M4LLAY811D8M4LLAY811D7Q4LLAY811D3Q4LLAY811D4Q4LLAY811D5Q4LLAY811D8Q4L

Flush Buttons Illuminated

LAY8 Serie of pushbuttonsStandard: IEC 60947-5-1

Emergency Stop Pushbutton

Page 103: Catalogo Delixi

Delixi Electric96

Overall dimensions

Standard and certificationIEC 51-1~9

CE

72 Series Pannel Meter

Function

DescriptionPressure testVoltage:2000VFrequency:50Hz

Duration:1min

Tolerance mechanical impact:max 147m/s2

Response time: 4sPointer deflection angle:90

72 series pannel meter provide:

Standard: IEC 51-1~9

Unit:mm

Measuring current,voltageMeasuring frequency,power,power factor

Page 104: Catalogo Delixi

Delixi Electric 97

30/5A40/5A50/5A60/5A75/5A80/5A100/5A150/5A160/5A200/5A250/5A300/5A400/5A600/5A800/5A1000/5A1600/5A5000/5A10000/5A 5A

15A20A25A30A40A50A60A80A100A5A300V500V600V500V45-55HZ (200V)

Standard: IEC 51-1~9

72 Series Pannel Meter

Ordering information

72 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.5

72 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.5

72TA3072TA4072TA5072TA6072TA7572TA8072TA10072TA15072TA16072TA20072TA25072TA30072TA40072TA60072TA80072TA100072TA160072TA500072TA1000072TA5A

72TA15A72TA20A72TA25A72TA30A72TA40A72TA50A72TA60A72TA80A72TA100A72C1A5A72TV30072TV50072TV60072C1V50072TZ200

AC TypeExternal connectiontransformer2 times of currentoverload

AC TypeDirect connectionAC TypeDirect connection2 times of currentoverload

DC TypeAC Type

DC TypeAC Type

Ammeter

Voltmerer

Frequency meter

Type Accuracy Specification Note Shape(mm) Reference rating

9

1.5

2.5

1.51.5

1.0

Page 105: Catalogo Delixi

Delixi Electric98

Overall dimensions

96 Series Pannel Meter

Function

DescriptionPressure testVoltage:2000VFrequency:50Hz

Duration:1min

Tolerance mechanical impact:max 147m/s2

Response time: 4sPointer deflection angle:90

96 series pannel meter provide:

Standard: IEC 51-1~9

Standard and certification IEC 51-1~9

CE

Unit:mm

Measuring current,voltageMeasuring frequency,power,power factor

Page 106: Catalogo Delixi

Delixi Electric 99

96 Series Pannel MeterStandard: IEC 51-1~9

96 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.5

96 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.5

96TA3096TA4096TA5096TA6096TA7596TA8096TA10096TA15096TA16096TA20096TA25096TA30096TA40096TA60096TA80096TA100096TA160096TA500096TA1000096TA5A

96TA15A96TA20A96TA25A96TA30A96TA40A96TA50A96TA60A96TA80A96TA100A96C1A5A96TV30096TV50096TV60096C1V50096TZ200

30/5A40/5A50/5A60/5A75/5A80/5A100/5A150/5A160/5A200/5A250/5A300/5A400/5A600/5A800/5A1000/5A1600/5A5000/5A10000/5A 5A

15A20A25A30A40A50A60A80A100A5A300V500V600V500V45-55HZ (200V)

Ordering information

AC TypeExternal connectiontransformer

AC TypeDirect connectionAC TypeDirect connection

DC TypeAC Type

DC TypeAC Type

Ammeter

Voltmerer

Frequency meter

Type Accuracy Specification Note Shape(mm) Reference rating

1.5

2.5

1.51.5

1.0

Page 107: Catalogo Delixi

Delixi Electric100

TND Voltage Stabilizer

Function

Description Technical Data

TND voltage stabilizer provide: Control system consist of linear integrated circuit automaticly control voltage regulation Timelag, overvoltage and undervoltage protection

Overall dimensions

Type

Output voltage

PhaseInput voltage rangeEfficiencyVoltage regulation speedTemperature riseFrequencyEnviroment temperature,relative temperatureWaveform distortionRated maximum output current(A)

TND0.5kVA~5kVA TND7kVA~30kVA220 4%,110 4% 220 4%184V 4V(set up according to the customers request)246V 4Vsingle-phase160V~240V>90%<1s(when input voltage change 10%)<60 (full range)50Hz/60Hz -50 ~40 below 90%no additional distortion2(500VA),4(1000VA),6(1500VA),8(2000VA),12(3000VA),20(5000VA),25(7000VA),40(10KVA),85(15KVA),73(20KVA),109(30KVA)

Voltage regulation accuracyUndervoltage protectionOvervoltage protection

TND-0.5TND-1TND-1.5TND-2TND-3TND-5TND-7TND-10TND-10TND-15TND-20TND30

Desktop

Cabinet type

Product shape Model Wide Length Hight

190 160 135205 190 155205 190 155240 270 200225 305 235225 310 290240 387 360240 387 360310 340 535340 360 640340 380 780425 390 845

unit: mm

Withstand voltage 1500V/1min

Page 108: Catalogo Delixi

Delixi Electric 101

TND Voltage Stabilizer

Ordering information

Desktop

Cabinet type

Product shape Power rating Referencce

0.5K1K1.5K2K3K5K7K10K

10K15K20K30K

TNDP5TND1TND1P5TND2TND3TND5TND7TND10

TND10GTND15GTND20GTND30G

Page 109: Catalogo Delixi

Delixi Electric102

2.4"3.2"4"4.7"6"12"4.7"6"7.1"8"10"12"14.6"7.1"8"10"12"14"15"16"17.7"19.7"8"10"12"14"16"20"30"18"20"21.6"27.5"32"2.4"3.2"4"4.7"6"8"4.7"6"

60801001201502001201501802002503003701802002503003503804004505002002503003504005007504505005507008006080100120150200120150

2.52.52.52.52.52.53.63.63.63.63.63.63.64.84.84.84.84.84.84.84.84.87.27.27.27.27.27.27.2999992.22.22.22.22.22.23.23.2

2-112-162-222-302-353-802-302-353-423-503-653-803-803-423-503-653-803-903-1023-1053-1303-1503-503-654-804-904-1054-15010-2208-1188-1508-16010-20510-2302-112-162-222-302-353-503-303-35

181818181818404040404040405050505050505050501201201201201201201201751751751751751818181818184040

888888181818181818182222222222222222225555555555555580808080808888881818

100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100

DAR205060**DAR205080**DAR205100**DAR205120**DAR205150**DAR205200**DAR306120**DAR306150**DAR306180**DAR306200**DAR306250**DAR306300**DAR306370**DAR408180**DAR408200**DAR408250**DAR408300**DAR408350**DAR408380**DAR408400**DAR408450**DAR408500**DAR702200**DAR702250**DAR702300**DAR702350**DAR702400**DAR702500**DAR702750**DAR900450**DAR900500**DAR900550**DAR900700**DAR900800**DAR202060**DAR202080**DAR202100**DAR202120**DAR202150**DAR202200**DAR302120**DAR302150**

Nylon Cable Ties Series

Description Technical Data

Overall dimensions

Material: Using nylon 66 material that recognized by ULFire-protection rating:94V-2Acid and erosion control,insulate well and difficult to aging

Color: White, black and other colors

LBS KGSLong

INCH MMWidth MAX.Bundle

DIA(mm)Tensile Strength Packing

(root)Reference

Page 110: Catalogo Delixi

Delixi Electric 103

Nylon Cable Ties Series

LBS KGSLong

INCH MMWidth MAX.Bundle

DIA(mm)Tensile Strength Packing

(root) Reference

7"8"10"12"14"4.7"6"7.1"8"10"12"14"16"8"10"12"14"16"17.7"19.7"21.6"24"

180200250300350120150180200250300350400200250300350400450500550600

3.23.23.23.23.24.24.24.24.24.24.24.24.26.56.56.56.56.56.56.56.56.5

3-423-503-653-803-903-303-353-423-503-653-803-903-1053-503-654-804-904-1053-1304-1504-1654-170

40404040405050505050505050120120120120120120120120120

18181818182222222222222222555555555555555555

100100100100100100100100100100100100100100100100100100100100100100

DAR302180DAR302200DAR302250DAR302300DAR302350DAR402120DAR402150DAR402180DAR402200DAR402250DAR402300DAR402350DAR402400DAR605200DAR605250DAR605300DAR605350DAR605400DAR605450DAR605500DAR605550DAR605600

Note:" " express color and packing code

Normal PackingHang tag Packing

BBBL

WBWL

UBUL

RBRL

YBYL

GBGL

Normal Packing

Hang tag Packing

Color Black White Blue Red Yellow Green

Page 111: Catalogo Delixi

Building Industry Energy

CDW7

CDM1

CDM1

CDC17

CDR17CDM1L

CDB6a CDB6LECDPZ50 CDY1 DDS607

Power Distribution and Industry Control Product

JXF

LMK LAY3 72

Residential

Page 112: Catalogo Delixi