Low Voltage Electrical Appliance “Right Quality, Right Price”
International Catalogue 2009
A global company at your serviceDelixi was founded in 1984 in Zhejiang province with salesover 1,5BM€, employing more than 15000 people.
Delixi created an international Joint Venture in November2007,named Delixi Electric LTD,in order to serve youworldwide,with core LV products having the right qualityat the right price.
Our products are designed for Residential / Building /Energy / infrastructure and Industrial markets . DelixiElectric employs 5200 people world wide.
A reliable company serving you withreliable product
Delixi Electric: Who are we
Dedicated R&D center
International quality control of suppliers
International quality control of plants
Fully automatized distribution center
Clear warranty policy
Network of recognized 600 distributorsworld wide
Reliable quality
You can trust 100% our products. We offer you a 18 months warranty. During this period oftime, we will replace any defected product you may have, provided the responsibility is ours.
For more details, please contact your local Delixi Electric Company.
Delixi Electric Pakistan73 / B / 3 , Race View,Jail Road,Lahore, 54000,PakistanTel 0092 - 42 - 7570412 / 7570443 , extension 100/103Fax 0092 - 42 - 7570443 , extension 108Contact : Syed Sohail IDREESMobile : 0092 [email protected]
Delixi Elecric Austral AfricaCanon Crescan Drive , RoodekopGermiston, 1400PO Box 13151 , Elspark, 1418Mobile : +27 (0) 836438898www.delixi-electric.co.zaContact : Vicky [email protected]
Delixi Electric Middle-EastRAK Free trade zonePO BOX 10559Ras El KhaimaUnited Arab EmiratesTel : +971 ( 7 ) 244 47 27Fax : + 971 ( 7 ) 244 27 [email protected] : Raja BHAUMIKMobile : +971 ( 50 ) 657 [email protected]
Delixi Electric Marocco213 Centre YousraRond-point d’EuropeCasablanca, Maroctel : +212 (0) 22 268 161Fax : +212 (0) 22 491342Contact : Hicham MOUKIMobile : +212 (0) 61 100 [email protected]
Delixi Electric South East Europe20 Tsar Samuil str . , 1rst FloorTriaditsa MunicipalitySofiaBulgariaContact : Doychin ZAHARINOVMobile : +359 885 750 [email protected]
A company to serve you where you are
We set up companies in many countries in order to deliver best in classlocal availability and support .
Delixi Elecric ChinaDelixi Liushi Industrial Park,Yueqing,Zhejiang,P.R.ChinaPost Code:325604www.delixi-electric.com
Delixi Electric IsraelIndustrial park cibleHamelaha st.22Rosh ha-aiynIsraeltel:+972546798718Contact : Hayim COHENemail:[email protected]
Delixi Electric West Africa1 Tunde Gaffar CloseOff Adeniyi JonesIkejaLagosNigeriaFax : + 234 2703941Contact : Chidiebere NWORGUMobile : +234 703 41 111 [email protected]
Delixi Electric South East AsiaP.O.Box 7567Pejabat Post Besar Shah Alam40720 Shah AlamSelangor Darul EhsanTel:03- 78809564Fax: 03-78809540Contact: Ellis LeeEmail : [email protected]
Delixi Electric ArgentinaContact : Damian CattainoMobile : +54111545658952
Delixi Electric EgyptContact : Mohamed NagyMobile 20(0) 100705454
Delixi Electric Saudi ArabiaContact : Mohkam SheikhMobile : +966050269801
Power Distribution
Industry Control
Product Panorama
ContentsMCB Miniature Circuit BreakersCDB6a 18mm Miniature Circuit Breakers 1
CDB6L 18mm Miniature Circuit Breakers 3
CDB6N 18mm Miniature Circuit Breakers 5
CDB6&CDB6LE Electrical Auxiliaries 7
CDB17 Miniature Circuit Breakers 8
CDB3 Phase-neutral Circuit Breakers 10
CDB2 27mm Miniature Circuit Breakers 11
CDB5 Switch Disconnectors 13
RCBO Residual Current Operated Circuit Breakers WithIntegral Overcurrent ProtectionCDB6LE Electronic Type Residual Current Operated Circuit Breakers 15
CDB3LE Electronic Type Residual Current Operated Circuit Breakers 17
CDB2LE Electronic Type Residual Current Operated Circuit Breakers 18
CDB7LSP Electronic Type Residual Current Operated Circuit Breakers 20
RCCB Residual Current Operated Circuit BreakersWithout Overcurrent ProtectionCDL7 Electromagnetic Type Residual Current Switches 21
Surge ProtectorCDY1 Surge Protective Devices 22
MCB Distribution BoardCDPZ50 Distribution Box 25
MeterDDS607 Single-phase Electronic Watt-hour Meters
MCCB Moulded Case Circuit BreakersCDM1 Moulded Case Circuit Breakers 29
ELCB Earth-leakage Circuit BreakersCDM1L Moulded Case Circuit Breakers With Electronic Type Residual Current
Operated Protection 36
27
ACB Air Circuit BreakerCDW7 Air Circuit Breaker 42
ContactorsCDC17 AC Contactor 61
RelaysCDR17 Thermal overload relays 70
Current TransformerLMK Current Transformer 73
FuseRT16 Fuse 76
RT18 Fuse 78
Power Distribution BoxJXF Power Distribution Box 80
Control SignalLD11 Series of indicator light 82
LAY3 Serie of pushbuttons 86
LAY7 Serie of pushbuttons 88
LAY8 Serie of pushbuttons 93
Pannel Meter72 Series Pannel Meter 96
96 Series Pannel Meter 98
Voltage StabilizerTND Voltage Stabilizer 100
Nylon LockNylon Cable Ties Series 102
Delixi Electric 1
Function CDB6a miniature circuit breakers combine the following functions:Protection of circuits against overload currentsProtection of circuits against short-circuit currentsControlIsolation
Rated current: 1, 3, 6, 10, 16, 20, 25, 32, 40, 50, 63 ARated voltage: 230/400V ACBreaking capacity
Tropicalization: treatment 2Protection degree: 2Connection:up to 25mm2 cablesTripping curves:B curve: the magnetic release operates between 3 and 5 InC curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 In35 mm standard DIN rail mounting
Description Technical data
CDB6aStandard: IEC 60898-1 IEC 60947-2Trip Curve: B, C and D curvesBreaking Capacity: 3000A
Overall dimensionsUnit:mm
Voltage(V)230400230400230400
Ratecurrent1-63A
Type
B
C
D
Poles
1P2P, 3P, 4P1P2P, 3P, 4P1P2P, 3P, 4P
Breaking capacityIcn (A)3000
Standard and certificationIEC 60898-1 IEC 60947-2KEMA, CB
Delixi Electric2
CDB6aStandard: IEC 60898-1 IEC 60947-2Trip Curve: B, C and D curvesBreaking Capacity: 3000A
Type Rating(A)
Width(in mod.of 9mm)
1361016202532405063
22222222222
1P
1361016202532405063
44444444444
2P
1361016202532405063
66666666666
3P
D curveCDB6a1D1CDB6a1D3CDB6a1D6CDB6a1D10CDB6a1D16CDB6a1D20CDB6a1D25CDB6a1D32CDB6a1D40CDB6a1D50CDB6a1D63CDB6a2D1CDB6a2D3CDB6a2D6CDB6a2D10CDB6a2D16CDB6a2D20CDB6a2D25CDB6a2D32CDB6a2D40CDB6a2D50CDB6a2D63CDB6a3D1CDB6a3D3CDB6a3D6CDB6a3D10CDB6a3D16CDB6a3D20CDB6a3D25CDB6a3D32CDB6a3D40CDB6a3D50CDB6a3D63
ReferenceB curveCDB6a1B1CDB6a1B3CDB6a1B6CDB6a1B10CDB6a1B16CDB6a1B20CDB6a1B25CDB6a1B32CDB6a1B40CDB6a1B50CDB6a1B63CDB6a2B1CDB6a2B3CDB6a2B6CDB6a2B10CDB6a2B16CDB6a2B20CDB6a2B25CDB6a2B32CDB6a2B40CDB6a2B50CDB6a2B63CDB6a3B1CDB6a3B3CDB6a3B6CDB6a3B10CDB6a3B16CDB6a3B20CDB6a3B25CDB6a3B32CDB6a3B40CDB6a3B50CDB6a3B63
C curveCDB6a1C1CDB6a1C3CDB6a1C6CDB6a1C10CDB6a1C16CDB6a1C20CDB6a1C25CDB6a1C32CDB6a1C40CDB6a1C50CDB6a1C63CDB6a2C1CDB6a2C3CDB6a2C6CDB6a2C10CDB6a2C16CDB6a2C20CDB6a2C25CDB6a2C32CDB6a2C40CDB6a2C50CDB6a2C63CDB6a3C1CDB6a3C3CDB6a3C6CDB6a3C10CDB6a3C16CDB6a3C20CDB6a3C25CDB6a3C32CDB6a3C40CDB6a3C50CDB6a3C63
88888888888
4P CDB6a4D1CDB6a4D3CDB6a4D6CDB6a4D10CDB6a4D16CDB6a4D20CDB6a4D25CDB6a4D32CDB6a4D40CDB6a4D50CDB6a4D63
CDB6a4B1CDB6a4B3CDB6a4B6CDB6a4B10CDB6a4B16CDB6a4B20CDB6a4B25CDB6a4B32CDB6a4B40CDB6a4B50CDB6a4B63
CDB6a4C1CDB6a4C3CDB6a4C6CDB6a4C10CDB6a4C16CDB6a4C20CDB6a4C25CDB6a4C32CDB6a4C40CDB6a4C50CDB6a4C63
1361016202532405063
Tripping Curve
B C D
Delixi Electric 3
CDB6LStandard: IEC 60947-2 IEC 60898-1Trip Curve: B, C and D curvesBreaking Capacity: 4500A
Function CDB6L miniature circuit breakers combine the following functions:Protection of circuits against overload currentsProtection of circuits against short-circuit currentsControlIsolation
Rated current: 1, 3, 6, 10, 16, 20, 25, 32, 40, 50, 63 ARated voltage: 230/400V ACBreaking capacity:
Description Technical data
Tropicalization: treatment 2Protection degree: 2Connection:up to 25mm2 cablesTripping curves:B curve: the magnetic release operates between 3 and 5 InC curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 In35 mm standard DIN rail mounting
Standard and certificationIEC 60947-2 IEC 60898-1KEMA, CB
Overall dimensionsUnit:mm
Voltage(V)
230400230400230400230400230400230400
1P
2P, 3P, 4P
1P
2P, 3P, 4P
1P
2P, 3P, 4P
Breaking capacityIcn (A)
450045004500450045004500450045004500450045004500
Ratecurrent
1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A
Type
B
C
D
Poles
Delixi Electric4
CDB6LStandard: IEC 60947-2 IEC 60898-1Trip Curve: B, C and D curvesBreaking Capacity: 4500A
1P
2P
3P
1361016202532405063
22222222222
1361016202532405063
44444444444
1361016202532405063
66666666666
D curveCDB6L1D1CDB6L1D3CDB6L1D6CDB6L1D10CDB6L1D16CDB6L1D20CDB6L1D25CDB6L1D32CDB6L1D40CDB6L1D50CDB6L1D63CDB6L2D1CDB6L2D3CDB6L2D6CDB6L2D10CDB6L2D16CDB6L2D20CDB6L2D25CDB6L2D32CDB6L2D40CDB6L2D50CDB6L2D63CDB6L3D1CDB6L3D3CDB6L3D6CDB6L3D10CDB6L3D16CDB6L3D20CDB6L3D25CDB6L3D32CDB6L3D40CDB6L3D50CDB6L3D63
C curveCDB6L1C1CDB6L1C3CDB6L1C6CDB6L1C10CDB6L1C16CDB6L1C20CDB6L1C25CDB6L1C32CDB6L1C40CDB6L1C50CDB6L1C63CDB6L2C1CDB6L2C3CDB6L2C6CDB6L2C10CDB6L2C16CDB6L2C20CDB6L2C25CDB6L2C32CDB6L2C40CDB6L2C50CDB6L2C63CDB6L3C1CDB6L3C3CDB6L3C6CDB6L3C10CDB6L3C16CDB6L3C20CDB6L3C25CDB6L3C32CDB6L3C40CDB6L3C50CDB6L3C63
ReferenceB curveCDB6L1B1CDB6L1B3CDB6L1B6CDB6L1B10CDB6L1B16CDB6L1B20CDB6L1B25CDB6L1B32CDB6L1B40CDB6L1B50CDB6L1B63CDB6L2B1CDB6L2B3CDB6L2B6CDB6L2B10CDB6L2B16CDB6L2B20CDB6L2B25CDB6L2B32CDB6L2B40CDB6L2B50CDB6L2B63CDB6L3B1CDB6L3B3CDB6L3B6CDB6L3B10CDB6L3B16CDB6L3B20CDB6L3B25CDB6L3B32CDB6L3B40CDB6L3B50CDB6L3B63
Type Rating(A)
Width(in mod.of 9mm)
4P 1361016202532405063
88888888888
CDB6L4D1CDB6L4D3CDB6L4D6CDB6L4D10CDB6L4D16CDB6L4D20CDB6L4D25CDB6L4D32CDB6L4D40CDB6L4D50CDB6L4D63
CDB6L4C1CDB6L4C3CDB6L4C6CDB6L4C10CDB6L4C16CDB6L4C20CDB6L4C25CDB6L4C32CDB6L4C40CDB6L4C50CDB6L4C63
CDB6L4B1CDB6L4B3CDB6L4B6CDB6L4B10CDB6L4B16CDB6L4B20CDB6L4B25CDB6L4B32CDB6L4B40CDB6L4B50CDB6L4B63
Tripping Curve
B C D
Delixi Electric 5
Standard: IEC 60947-2 IEC 60898-1Trip Curve: B, C and D curvesBreaking Capacity: 6000A
Function CDB6N miniature circuit breakers combine the following functions:Protection of circuits against overload currentsProtection of circuits against short-circuit currentsControlIsolation
Rated current: 1, 3, 6, 10, 16, 20, 25, 32, 40, 50, 63 ARated voltage: 230/400V ACBreaking capacity:
Description Technical data
CDB6N
Tropicalization: treatment 2Protection degree: 2Connection:up to 25mm2 cablesTripping curves:B curve: the magnetic release operates between 3 and 5 InC curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 In35 mm standard DIN rail mounting
Standard and certificationIEC 60947-2 IEC 60898-1KEMA, CB
Overall dimensionsUnit:mm
Voltage(V)230400230400230400230400230400230400
1P
2P, 3P, 4P
1P
2P, 3P, 4P
1P
2P, 3P, 4P
Breaking capacityIcn (A)600045006000450060004500600045006000450060004500
Ratecurrent1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A1-40A50A, 63A
Type
B
C
D
Poles
Delixi Electric6
Standard: IEC 60947-2 IEC 60898-1Trip Curve: B, C and D curvesBreaking Capacity: 6000A
Type
1P
CDB6N
2P
3P
4P
Rating(A)
Width(in mod.of 9mm)
1361016202532405063
22222222222
1361016202532405063
44444444444
1361016202532405063
66666666666
1361016202532405063
88888888888
D curveCDB6N1D1CDB6N1D3CDB6N1D6CDB6N1D10CDB6N1D16CDB6N1D20CDB6N1D25CDB6N1D32CDB6N1D40CDB6N1D50CDB6N1D63CDB6N2D1CDB6N2D3CDB6N2D6CDB6N2D10CDB6N2D16CDB6N2D20CDB6N2D25CDB6N2D32CDB6N2D40CDB6N2D50CDB6N2D63CDB6N3D1CDB6N3D3CDB6N3D6CDB6N3D10CDB6N3D16CDB6N3D20CDB6N3D25CDB6N3D32CDB6N3D40CDB6N3D50CDB6N3D63CDB6N4D1CDB6N4D3CDB6N4D6CDB6N4D10CDB6N4D16CDB6N4D20CDB6N4D25CDB6N4D32CDB6N4D40CDB6N4D50CDB6N4D63
C curveCDB6N1C1CDB6N1C3CDB6N1C6CDB6N1C10CDB6N1C16CDB6N1C20CDB6N1C25CDB6N1C32CDB6N1C40CDB6N1C50CDB6N1C63CDB6N2C1CDB6N2C3CDB6N2C6CDB6N2C10CDB6N2C16CDB6N2C20CDB6N2C25CDB6N2C32CDB6N2C40CDB6N2C50CDB6N2C63CDB6N3C1CDB6N3C3CDB6N3C6CDB6N3C10CDB6N3C16CDB6N3C20CDB6N3C25CDB6N3C32CDB6N3C40CDB6N3C50CDB6N3C63CDB6N4C1CDB6N4C3CDB6N4C6CDB6N4C10CDB6N4C16CDB6N4C20CDB6N4C25CDB6N4C32CDB6N4C40CDB6N4C50CDB6N4C63
ReferenceB curveCDB6N1B1CDB6N1B3CDB6N1B6CDB6N1B10CDB6N1B16CDB6N1B20CDB6N1B25CDB6N1B32CDB6N1B40CDB6N1B50CDB6N1B63CDB6N2B1CDB6N2B3CDB6N2B6CDB6N2B10CDB6N2B16CDB6N2B20CDB6N2B25CDB6N2B32CDB6N2B40CDB6N2B50CDB6N2B63CDB6N3B1CDB6N3B3CDB6N3B6CDB6N3B10CDB6N3B16CDB6N3B20CDB6N3B25CDB6N3B32CDB6N3B40CDB6N3B50CDB6N3B63CDB6N4B1CDB6N4B3CDB6N4B6CDB6N4B10CDB6N4B16CDB6N4B20CDB6N4B25CDB6N4B32CDB6N4B40CDB6N4B50CDB6N4B63
Tripping Curve
B C D
Delixi Electric 7
CDB6&CDB6LE Electrical Auxiliaries
OF contact auxiliary
ReferenceCDB6OF230ACCDB6OF400ACCDB6OF24DCCDB6OF48DCCDB6OF110DCCDB6OF220DCCDB6SD230ACCDB6SD400ACCDB6SD24DCCDB6SD48DCCDB6SD110DCCDB6SD220DCCDB6MX230ACCDB6MX24AC
VoltageAC230AC400DC24DC48DC110DC220AC230AC400DC24DC48DC110DC220AC230DC24
TypeOF
SD
MX+OF*
SD fault-indicating switch
MX+OF shunt trip release
Delixi Electric8
CDB17Standard: IEC 60898-1Trip Curve: B, C and D curvesBreaking Capacity: 6000A
Function CDB17N miniature circuit breakers combine the following functions:Protection of circuits against overload currentsProtection of circuits against short-circuit currentsControlIsolation
Rated current: 1, 3, 6, 10, 16, 20, 25, 32, 40, 50, 63 ARated voltage: 230/400V ACBreaking capacity
Tropicalization: treatment 2Protection degree: 2Connection:up to 25mm2 cablesTripping curves:B curve: the magnetic release operates between 3 and 5 InC curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 In35 mm standard DIN rail mounting
Description Technical data
Standard and certification IEC 60898-1KEMA, CB, CE
Overall dimensionsUnit:mm
Voltage(V)230400230400230400
6000
Poles
1P2P,3P,4P1P2P,3P,4P1P2P,3P,4P
Type
B
C
D
Ratecurrent1-63A
Breaking capacityIcn (A)
Delixi Electric 9
1P
2P
3P
4P
1361016202532405063
22222222222
1361016202532405063
44444444444
1361016202532405063
66666666666
1361016202532405063
88888888888
D curveCDB17N1D1CDB17N1D3CDB17N1D6CDB17N1D10CDB17N1D16CDB17N1D20CDB17N1D25CDB17N1D32CDB17N1D40CDB17N1D50CDB17N1D63CDB17N2D1CDB17N2D3CDB17N2D6CDB17N2D10CDB17N2D16CDB17N2D20CDB17N2D25CDB17N2D32CDB17N2D40CDB17N2D50CDB17N2D63CDB17N3D1CDB17N3D3CDB17N3D6CDB17N3D10CDB17N3D16CDB17N3D20CDB17N3D25CDB17N3D32CDB17N3D40CDB17N3D50CDB17N3D63CDB17N4D1CDB17N4D3CDB17N4D6CDB17N4D10CDB17N4D16CDB17N4D20CDB17N4D25CDB17N4D32CDB17N4D40CDB17N4D50CDB17N4D63
C curveCDB17N1C1CDB17N1C3CDB17N1C6CDB17N1C10CDB17N1C16CDB17N1C20CDB17N1C25CDB17N1C32CDB17N1C40CDB17N1C50CDB17N1C63CDB17N2C1CDB17N2C3CDB17N2C6CDB17N2C10CDB17N2C16CDB17N2C20CDB17N2C25CDB17N2C32CDB17N2C40CDB17N2C50CDB17N2C63CDB17N3C1CDB17N3C3CDB17N3C6CDB17N3C10CDB17N3C16CDB17N3C20CDB17N3C25CDB17N3C32CDB17N3C40CDB17N3C50CDB17N3C63CDB17N4C1CDB17N4C3CDB17N4C6CDB17N4C10CDB17N4C16CDB17N4C20CDB17N4C25CDB17N4C32CDB17N4C40CDB17N4C50CDB17N4C63
ReferenceB curveCDB17N1B1CDB17N1B3CDB17N1B6CDB17N1B10CDB17N1B16CDB17N1B20CDB17N1B25CDB17N1B32CDB17N1B40CDB17N1B50CDB17N1B63CDB17N2B1CDB17N2B3CDB17N2B6CDB17N2B10CDB17N2B16CDB17N2B20CDB17N2B25CDB17N2B32CDB17N2B40CDB17N2B50CDB17N2B63CDB17N3B1CDB17N3B3CDB17N3B6CDB17N3B10CDB17N3B16CDB17N3B20CDB17N3B25CDB17N3B32CDB17N3B40CDB17N3B50CDB17N3B63CDB17N4B1CDB17N4B3CDB17N4B6CDB17N4B10CDB17N4B16CDB17N4B20CDB17N4B25CDB17N4B32CDB17N4B40CDB17N4B50CDB17N4B63
Type Rating(A)
Width(in mod.of 9mm)
CDB17Standard: IEC 60898-1Trip Curve: B, C and D curvesBreaking Capacity: 6000A
Tripping Curve
B C D
Delixi Electric10
Function CDB3 phase-neutral circuit breakers combine the following functions:Protection of circuits against overload currentsProtection of circuits against short-circuit currentsControlIsolation
Rated current: 6, 10, 16, 20, 25, 32ARated voltage: 230V ACBreaking capacity: 3 kATripping curves:C curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 InTropicalization: treatment 2Protection degree: 2ConnectionUp to 16mm2 cables35mm standard DIN rail mounting
Description Technical data
Overall dimensions
Type Rating(A)
Width(in mod.of 9mm)
ReferenceC curve D curve
61016202532
222222
CDB3a5C6CDB3a5C10CDB3a5C16CDB3a5C20CDB3a5C25CDB3a5C32
CDB3a5D6CDB3a5D10CDB3a5D16CDB3a5D20CDB3a5D25CDB3a5D32
1P+N
CDB3Standard: IEC 60898-1Trip Curve: C and D curvesBreaking Capacity: 3000A
Standard and certificationIEC 60898-1
C D
Tripping Curve
Delixi Electric 11
Function CDB2 miniature circuit breakers combine the following functions:Protection of circuits against overload currentsProtection of circuits against short-circuit currents
ControlIsolation
Description Technical dataRated current: 63, 80, 100, 125 ARated voltage : 230/400V ACBreaking capacity
CDB2Standard: IEC 60947-2Trip Curve: C and D curvesBreaking Capacity: 10000A
Standard and certification IEC 60947-2SEMKO, CE
Overall dimensions
Tripping curves:C curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 InMechanical durability: 8,500 (In 100A) / 7,000 (In=125A)Electrical durability: 1,500 (In 100A) / 1,000 (In=125A)Tropicalization: treatment 2Protection degree: 2ConnectionUp to 50 mm2 cables35mm standard DIN rail mountingClosed position indication
TypeRating(A)
Voltage(V)
Breaking capacity(kA)
63 ~125 230400
1010
1P2/3/4P
Unit:mm
Delixi Electric12
CDB2Standard: IEC 60947-2Trip Curve: C and D curvesBreaking Capacity: 10000A
Type Rating(A)
Width(in mod.of 9mm)
ReferenceC curve D curve
6380100125
3333
CDB2H1C63CDB2H1C80CDB2H1C100CDB2H1C125
CDB2H1D63CDB2H1D80CDB2H1D100CDB2H1D125
1P
6380100125
6666
2P
6380100125
9999
3P
6380100125
12121212
4P
CDB2H2C63CDB2H2C80CDB2H2C100CDB2H2C125
CDB2H2D63CDB2H2D80CDB2H2D100CDB2H2D125
CDB2H3C63CDB2H3C80CDB2H3C100CDB2H3C125
CDB2H3D63CDB2H3D80CDB2H3D100CDB2H3D125
CDB2H4C63CDB2H4C80CDB2H4C100CDB2H4C125
CDB2H4D63CDB2H4D80CDB2H4D100CDB2H4D125
C D
Tripping Curve
Delixi Electric 13
Function CDB5 switch disconnectors combine the following functions:Making and breaking normal load circuitsIsolation
Rated current: 20, 32, 63, 100 ARated voltage: 230/400V ACMechanical durability: 8500Electrical durability: 1500Short-time withstand capacity for 1 s: 12IeTropicalization: treatment 2Protection degree: 2ConnectionUp to 35 mm2 cables35 mm standard DIN rail mountingIsolation with positive break indication
Description Technical data
CDB5Standard: IEC 60947-3
Overall dimensions
Standard and certificationIEC 60947-3
Unit:mm
Delixi Electric14
CDB5Standard: IEC 60947-3
Type Rating(A)
Voltage(V AC)
Reference
1P
2P
3P
4P
Width(in mod.of 9mm)
203263100
230230230230
2222
400400400400
4444
203263100
400400400400
6666
203263100
400400400400
8888
CDB5120CDB5132CDB5163CDB51100
CDB5220CDB5232CDB5263CDB52100
CDB5320CDB5332CDB5363CDB53100
CDB5420CDB5432CDB5463CDB54100
203263100
Delixi Electric 15
Function CDB6LE electronic type residual current operated circuit breakers combine the follow-ing functions:
Overload protectionProtection against short-circuit currentProtection for users against indirect contactAdditional protection for users against direct contacts (30mA)Protection for electrical installations against insulation faults (fire hazard, etc)Isolation
Rated current: 6, 10, 16, 20, 25, 32, 40, 50, 60ARated voltage: 230V AC for 1P+N/2P, 400V AC for 3P/3P+N/4PSensitivity: 30 mATropicalization: treatment 2Protection degree: 2ConnectionUp to 16 mm2 cablesTripping curves:C curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 InMechanical indication of the earth fault on the front face by a black mechanicalindicator35 mm standard DIN rail mounting.
Description Technical data
CDB6LEStandard: IEC 61009Trip Curve: C and D curvesBreaking Capacity: 3000ASensitivity: 30mA
Standard and certificationIEC 61009
Overall dimensions
CDB6LE-32
CDB6LE-63
Delixi Electric16
CDB6LEStandard: IEC 61009Trip Curve: C and D curvesBreaking Capacity: 3000ASensitivity: 30mA
61016202532405060
4003P+N 30 111111111111141414
CDB6LEa4C6SCDB6LEa4C10SCDB6LEa4C16SCDB6LEa4C20SCDB6LEa4C25SCDB6LEa4C32SCDB6LEa4C40SCDB6LEa4C50SCDB6LEa4C60S
CDB6LEa4D6SCDB6LEa4D10SCDB6LEa4D16SCDB6LEa4D20SCDB6LEa4D25SCDB6LEa4D32SCDB6LEa4D40SCDB6LEa4D50SCDB6LEa4D60S
61016202532405060
4003P 30 101010101010121212
CDB6LEa3C6SCDB6LEa3C10SCDB6LEa3C16SCDB6LEa3C20SCDB6LEa3C25SCDB6LEa3C32SCDB6LEa3C40SCDB6LEa3C50SCDB6LEa3C60S
CDB6LEa3D6SCDB6LEa3D10SCDB6LEa3D16SCDB6LEa3D20SCDB6LEa3D25SCDB6LEa3D32SCDB6LEa3D40SCDB6LEa3D50SCDB6LEa3D60S
2P 777777888
CDB6LEa2C6SCDB6LEa2C10SCDB6LEa2C16SCDB6LEa2C20SCDB6LEa2C25SCDB6LEa2C32SCDB6LEa2C40SCDB6LEa2C50SCDB6LEa2C60S
CDB6LEa2D6SCDB6LEa2D10SCDB6LEa2D16SCDB6LEa2D20SCDB6LEa2D25SCDB6LEa2D32SCDB6LEa2D40SCDB6LEa2D50SCDB6LEa2D60S
230 30 61016202532405060
Type Width(in mod.of 9mm)
ReferenceC curve D curve
Voltage(V)
Sensitivity(mA)
2301P+N 30 555555666
CDB6LEa1C6SCDB6LLEa1C10SCDB6LEa1C16SCDB6LEa1C20SCDB6LEa1C25SCDB6LEa1C32SCDB6LEa1C40SCDB6LEa1C50SCDB6LEa1C60S
CDB6LEa1D6SCDB6LEa1D10SCDB6LEa1D16SCDB6LEa1D20SCDB6LEa1D25SCDB6LEa1D32SCDB6LEa1D40SCDB6LEa1D50SCDB6LEa1D60S
Rating(A)61016202532405060
61016202532405060
4004P 30 131313131313161616
CDB6LEa6C6SCDB6LEa6C10SCDB6LEa6C16SCDB6LEa6C20SCDB6LEa6C25SCDB6LEa6C32SCDB6LEa6C40SCDB6LEa6C50SCDB6LEa6C60S
CDB6LEa6D6SCDB6LEa6D10SCDB6LEa6D16SCDB6LEa6D20SCDB6LEa6D25SCDB6LEa6D32SCDB6LEa6D40SCDB6LEa6D50SCDB6LEa6D60S
Tripping Curve
B C D
Delixi Electric 17
Function CDB3LE electronic type residual current operated circuit breakers combine the fol-lowing functions:
Protection of circuits against overload currentsProtection of circuits against short-circuit currentsProtection of users against indirect contactAdditional protection for users against direct contacts (30mA)Protection of electrical installations against insulation faults (fire hazard, etc)Isolation
Rated current: 6, 10, 16, 20, 25, 32, 40ARated voltage: 230V ACBreaking capacity: 3kASensitivity: 30mATripping curve:C curve: the magnetic release operates between 5 and 10 InTropicalization: treatment 2Protection degree: 2ConnectionUp to 6 mm2 cablesMechanical indication of the earth fault on the front face by a red mechanical indicator35 mm standard DIN rail mounting
Description Technical data
Overall dimensions
Type Sensltivity(mA)
301P+N
Width (in mod.of 9mm)
4
Rating(A)6101620253240
CDB3LEa5C6SCDB3LEa5C10SCDB3LEa5C16SCDB3LEa5C20SCDB3LEa5C25SCDB3LEa5C32SCDB3LEa5C40S
Standard and certification IEC 61009
CDB3LEStandard: IEC 61009Trip Curve: C curvesBreaking Capacity: 3000ASensitivity: 30mA
Reference C curve
Unit:mm
Tripping Curve
C
Delixi Electric18
Function CDB2LE electronic type residual current operated circuit breakers combine the follow-ing functions:
Protection of circuits against overload currentsProtection of circuits against short-circuit currentsProtection of users against indirect contactProtection of electrical installations against insulation faults (fire hazard, etc)Isolation
Rated current: 63A, 80A,100ARated voltage: 230V for 1P+N; 400V for 2P/3P/3P+N/4PSensitivity: 100mA,300mARated ultimate short-circuit breaking capacity (Icu): 10,000ARated service short-circuit breaking capacity (Ics): 7,500ATripping curves:C curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 In2 types of residual current tripping are available:InstantaneousTime-delay with a maximum delay time of 0.2 sTropicalization: treatment 2Protection degree: 2ConnectionUp to 50 mm2 cablesMechanical indication of the earth fault on the front face by a black mechanicalindicatorClosed position indication35 mm standard DIN rail mounting
Description Technical data
Overall dimensions
Standard and certificationIEC 60947-2
CDB2LEStandard: IEC 60947-2Trip Curve: C and D curvesBreaking Capacity: 10000ASensitivity: 100mA, 300mA
Unit:mm
Delixi Electric 19
Type Width(in mod.of 9mm)
1P+N
ReferenceC curve
Rating(A)
63801006380100
Sensitivity(mA)
100100100300300300
6
D curve
CDB2LEH1D63YCDB2LEH1D80YCDB2LEH1D100YCDB2LEH1D63TCDB2LEH1D80TCDB2LEH1D100T
CDB2LEH1C63YCDB2LEH1C80YCDB2LEH1C100YCDB2LEH1C63TCDB2LEH1C80TCDB2LEH1C100T
CDB2LEStandard: IEC 60947-2Trip Curve: C and D curvesBreaking Capacity: 10000ASensitivity: 100mA, 300mA
2P 63801006380100
100100100300300300
9 CDB2LEH2D63YCDB2LEH2D80YCDB2LEH2D100YCDB2LEH2D63TCDB2LEH2D80TCDB2LEH2D100T
CDB2LEH2C63YCDB2LEH2C80YCDB2LEH2C100YCDB2LEH2C63TCDB2LEH2C80TCDB2LEH2C100T
3P 63801006380100
100100100300300300
12 CDB2LEH3D63YCDB2LEH3D80YCDB2LEH3D100YCDB2LEH3D63TCDB2LEH3D80TCDB2LEH3D100T
CDB2LEH3C63YCDB2LEH3C80YCDB2LEH3C100YCDB2LEH3C63TCDB2LEH3C80TCDB2LEH3C100T
3P+N 63801006380100
100100100300300300
12 CDB2LEH6D63YCDB2LEH6D80YCDB2LEH6D100YCDB2LEH6D63TCDB2LEH6D80TCDB2LEH6D100T
CDB2LEH6C63YCDB2LEH6C80YCDB2LEH6C100YCDB2LEH6C63TCDB2LEH6C80TCDB2LEH6C100T
4P 63801006380100
100100100300300300
15 CDB2LEH4D63YCDB2LEH4D80YCDB2LEH4D100YCDB2LEH4D63TCDB2LEH4D80TCDB2LEH4D100T
CDB2LEH4C63YCDB2LEH4C80YCDB2LEH4C100YCDB2LEH4C63TCDB2LEH4C80TCDB2LEH4C100T
C D
Tripping Curve
Delixi Electric20
Function CDB7LSP electronic type residual current operated circuit breakers combine thefollowing functions:
Protection of circuits against overload currents Protection of circuits against short-circuit currents Protection of users against indirect contact Additional protection for users against direct contacts (30mA) Protection of electrical installations against insulation faults (fire hazard, etc)
Rated current: 6, 10, 16, 20, 25, 32, 40ARated voltage: 230V ACBreaking capacity: 6kASensitivity: 30mATripping curve:B curve: the magnetic release operates between 3 and 5 InC curve: the magnetic release operates between 5 and 10 InD curve: the magnetic release operates between 10 and 14 InTropicalization: treatment 2Protection degree: 2ConnectionUp to 10 mm2 cablesMechanical indication of the earth fault on the front face by a red mechanicalindicator 35 mm standard DIN rail mounting
Description Technical data
Overall dimensions
Type Rating(A)
Width(mm)
ReferenceB curve D curve
6101620253240
18181818181818
CDB7LSPN1B6SCDB7LSPN1B10SCDB7LSPN1B16SCDB7LSPN1B20SCDB7LSPN1B25SCDB7LSPN1B32SCDB7LSPN1B40S
CDB7LSPN1D6SCDB7LSPN1D10SCDB7LSPN1D16SCDB7LSPN1D20SCDB7LSPN1D25SCDB7LSPN1D32SCDB7LSPN1D40S
1P+N
CDB7LSPStandard: IEC 61009Trip Curve: C and D curvesBreaking Capacity: 6000ASensitivity:30mA
Standard and certificationIEC 61009
Voltage(V)230
Sensitivity(mA)30
C curveCDB7LSPN1C6SCDB7LSPN1C10SCDB7LSPN1C16SCDB7LSPN1C20SCDB7LSPN1C25SCDB7LSPN1C32SCDB7LSPN1C40S
Delixi Electric 21
Function CDL7 electromagnetic type residual current switch combine the following functions:Protection for users against indirect contactAdditional protection for users against direct contacts (30mA)Protection for electrical installations against insulation faults (fire hazard, etc)
Isolation
DescriptionRated current: 25, 40, 63, 80, 100ARated voltage: 230/400V ACSensitivity: 10mA, 30mA, 100mA, 300mAMechanical durability: 2000Electrical durability: 1000Tropicalization: treatment 2Protection degree: 2ConnectionTunnel terminalsUp to 16 mm2 cablesType A or type AC RCCB, without overload or short-circuit protectionDon’t need any auxiliary supply source.Instantaneous earth fault trip, unadjustableMechanical indication of the earth fault on the front face by a red mechanicalindicator35 mm standard DIN rail mounting
Technical data
CDL7Standard:IEC 61008Sensitivity: 10mA, 30mA, 100mA, 300mARCCB: Type A , Type AC
Overall dimensions
Standard and certificationIEC 61008KEMA, CB
Unit:mm
Delixi Electric22
CDL7Standard:IEC 61008Sensitivity: 10mA, 30mA, 100mA, 300mARCCB: Type A , Type AC
Type Width(in mod.of 9mm)
Sensitivity(mA)
2P 103030303030100100100100100300300300300300100100100300300300
4
Rating(A)
2525406380100254063801002540638010063801006380100
4P 103030303030100100100100100300300300300300100100100300300300
8 2525406380100254063801002540638010063801006380100
CDL7225LACDL7225SACDL7240SACDL7263SACDL7280SACDL72100SACDL7225YACDL7240YACDL7263YACDL7280YACDL72100YACDL7225TACDL7240TACDL7263TACDL7280TACDL72100TACDL7263YASCDL7280YASCDL72100YASCDL7263TASCDL7280TASCDL72100TAS
CDL7425LACDL7425SACDL7440SACDL7463SACDL7480SACDL74100SACDL7425YACDL7440YACDL7463YACDL7480YACDL74100YACDL7425TACDL7440TACDL7463TACDL7480TACDL74100TACDL7463YASCDL7480YASCDL74100YASCDL7463TASCDL7480TASCDL74100TAS
ReferenceA type AC type
CDL7225LCCDL7225SCCDL7240SCCDL7263SCCDL7280SCCDL72100SCCDL7225YCCDL7240YCCDL7263YCCDL7280YCCDL72100YCCDL7225TCCDL7240TCCDL7263TCCDL7280TCCDL72100TCCDL7263YCSCDL7280YCSCDL72100YCSCDL7263TCSCDL7280TCSCDL72100TCS
CDL7425LCCDL7425SCCDL7440SCCDL7463SCCDL7480SCCDL74100SCCDL7425YCCDL7440YCCDL7463YCCDL7480YCCDL74100YCCDL7425TCCDL7440TCCDL7463TCCDL7480TCCDL74100TCCDL7463YCSCDL7480YCSCDL74100YCSCDL7463TCSCDL7480TCSCDL74100TCS
Delixi Electric 23
CDY1 Surge Protective DevicesStandard: IEC61643-1
Function
Description
CDY1 surge protective devices provide: Applicable to household appliances and the like to offer protection When there is an over-voltage caused by either lightning strike or operation in thecircuit
Technical data
TypePoleNominal discharge currentIn(8/20us) kAMaximum dischargecurrent Imax(8/20us) kAMaximum continuousoperational voltage Uc VProtection level Up kVLeakage cur rent(75%Uc 1mA) uAResponse time ns
CDY1-80 CDY1-100 CDY1-120CDY1-60CDY1-401P+N, 2P5
10
275
1.320
25
CDY1-10 CDY1-20
1P, 1P+N, 2P, 3P, 3P+N, 4P10
20
275
1.3
385
1.5
420
1.8
20
40
Standard and certification
IEC61643-1
Overall dimensions
CDY1-10 CDY1-20 40 60
CDY1-80 100 120
30
60
40
80
50
100
60
120
320
1.3
275
1.5
385
1.8
420
2
275
2
420
2.5
385
2.2
275
2
420
2.2
385
2.2
275
2.2
420
2.5
385
2.5
275
2.2
420
2.5
385
2.5
Delixi Electric24
CDY1 Surge Protective DevicesStandard: IEC61643-1
Note:" " express Maximum continuous operational voltage (Uc) code
275V275
320V320
385V385
420V420
Imax ReferncePole10KA10KA20KA20KA20KA20KA20KA20KA40KA40KA40KA40KA40KA40KA60KA60KA60KA60KA60KA60KA80KA80KA80KA80KA80KA80KA100KA100KA100KA100KA100KA100KA120KA120KA120KA120KA120KA120KA20KA40KA60KA60KA80KA100KA120KA
1P+N2P1P2P3P4P1P+N3P+N1P2P3P4P1P+N3P+N1P2P3P4P1P+N3P+N1P2P3P4P1P+N3P+N1P2P3P4P1P+N3P+N1P2P3P4P1P+N3P+NPhase modlePhase modlePhase modleN-PEN-PEN-PEN-PE
CDY1105CDY1102CDY1201CDY1202CDY1203CDY1204CDY1205CDY1206CDY1401CDY1402CDY1403CDY1404CDY1405CDY1406CDY1601CDY1602CDY1603CDY1604CDY1605CDY1606CDY1801CDY1802CDY1803CDY1804CDY1805CDY1806CDY11001CDY11002CDY11003CDY11004CDY11005CDY11006CDY11201CDY11202CDY11203CDY11204CDY11205CDY11206CDY120PMCDY140PMCDY160PMCDY160NPCDY180NPCDY1100NPCDY1120NP
Uc
Delixi Electric 25
Function CDPZ50 distribution box provides illumination devices, sockets and electrical appli-ances with functions as follows: Protection against overload Protection against over voltage Protection against leakage
Description Technical data
TypeSurface installation
Flush installation
The amount of unit loop*68121620246812162024
CDPZ50Standard: IEC60439-1 IEC60670
ReferenceCDPZ50M6CDPZ50M8CDPZ50M12CDPZ50M16CDPZ50M20CDPZ50M24CDPZ50R6CDPZ50R8CDPZ50R12CDPZ50R16CDPZ50R20CDPZ50R24
*:18mm for one unit loop
Rated operational voltage Maximum rated current Rated insulation voltage Rated frequency Degree of protection Instantaneous withstand current
Construction feature Holistic steel-plastic construction Free assembly of components Beautiful design Flame retardant industrial plastic in panel The whole panel can move vertically
Standard and certification IEC60439-1 IEC60670
AC 400V or AC 230V100A500V50HzIP306KA
Delixi Electric26
Overall dimension
CDPZ50Standard: IEC60439-1 IEC60670
Surface installation Flush installation
Unit:mm
Loop number
6812162024*
Surface installationA171207279351423364
*:two rows product
B220220220220220303
Flush installationA163199279343413383
B220220220220220282
ThicknessC909090909090
Delixi Electric 27
Technical Data Accuracy class: 1.0, 2.0 Reference voltage:220V Current specification:1.5(6)A,3(6)A,2.5(10)A,5(20)A,5(30)A 10(40)A,15(60)A,20(80)A,30(100)A Power: 2W/10VA (voltage circuit), 4VA(Current circuit) Two-way measurement function:
Extended functions: Optional liquid crystal display, infrared communications and 485
communications
Normal work temperature:-10-~+45 Limit working temperature:-25-~+55 Normal work voltage:0.9~1.1 Reference voltage Limit work voltage:0.7~1.2 Reference voltage Relative Humidity: 85% Installation conditions:Meter should be installed in indoor drying, ventilation, fire-resistant, solid walls height of 1.8 m about the use of non-corrosive gases in the nvironment, should be moisture-proof. Lightning request:Thunderstorms in more places should be installed in the
installation of lightning equipment
Standard and Certification IEC620531-21:2003
KEMA
Overall dimensions
DDS607 single-phase electronic watt-hour meter provide: Measuring energy in household and commercial single-phase network services
Function
Description
Being able to accurately measure, antitwodirections of power andthe total electricityconsumption in one direction
Single-phase Type A,C Meter Single-phase LCD Meter
DDS607 Single-phase Electronic Watt-hour MeterStandard:IEC 620531-21:2003
Delixi Electric28
Ordering informationn
Type A (Import chip)Type A (Import chip)Type A (Import chip)Type A (Import chip)Type A (Import chip)Type A (Import chip)Type A (Import chip)Type A (Import chip)Type C (Domestic chip)Type C (Domestic chip)Type C (Domestic chip)Type C (Domestic chip)Type C (Domestic chip)Type C (Domestic chip)Type C (Domestic chip)Type C (Domestic chip)LCD without 485 communicationsLCD without 485 communicationsLCD without 485 communicationsLCD without 485 communicationsLCD without 485 communicationsLCD without 485 communicationsLCD without 485 communicationsLCD with 485 communicationsLCD with 485 communicationsLCD with 485 communicationsLCD with 485 communicationsLCD with 485 communications and infrared communicationsLCD with 485 communications and infrared communicationsLCD with 485 communications and infrared communicationsLCD with 485 communications and infrared communicationsLCD with 485 communications and infrared communicationsLCD with 485 communications and infrared communicationsLCD with 485 communications and infrared communicationsLCD with 485 communications and infrared communications
1.5(6)A2.5(10)A5(20)A5(30)A10(40)A15(60)A20(80)A30(100)A1.5(6)A2.5(10)A5(20)A5(30)A10(40)A15(60)A20(80)A30(100)A1.5(6)A2.5(10)A5(20)A5(30)A10(40)A15(60)A20(80)A1.5(6)A5(20)A10(40)A15(60)A1.5(6)A2.5(10)A5(20)A5(30)A10(40)A15(60)A20(80)A
30(100)A
DDS607N16M4ADDS607N110M4ADDS607N120M4ADDS607N130M6ADDS607N140M4ADDS607N160M4ADDS607N180M4ADDS607N1100M3ADDS607N26M4ADDS607N210M4CDDS607N220M4CDDS607N230M6CDDS607N240M4CDDS607N260M4CDDS607N280M4CDDS607N2100M3CDDS607N16M4CDDDS607N110M4CDDDS607N120M4CDDDS607N130M6CDDDS607N140M4CDDDS607N160M4CDDDS607N180M4CDDDS607N16M4CD485DDS607N120M4CD485DDS607N140M4CD485DDS607N160M4CD485DDS607N116M4CD485IDDS607N110M4CD485IDDS607N120M4CD485IDDS607N130M6CD485IDDS607N140M4CD485IDDS607N160M4CD485IDDS607N180M4CD485IDDS607N1100M3CD485I
Function Description Currentspecification Reference
Note: Users need special specifications can be customized
DDS607 Single-phase Electronic Watt-hour MeterStandard:IEC 620531-21:2003
Delixi Electric 29
Description Technical data
CDM1Standard: IEC 60947-2
Function CDM1 molded case circuit breakers can be used to provide the following functions:
Main technical parameters are shown in the table below
Constructional featuresThermamagnetic release offers instantaneous trip against short-circuit and longtime delay trip against overcurrentThe circuit breaker can be of fixed type or plug-in typeFor 4-pole circuit breakers:N-pole without overcurrent release, it switches on and off with other poles ( N-pole lead-make, lag-break)Various accessories can be attached to the circuit breaker to extend its functions,such as undervoltage release, shunt release, ON/OFF position indication contact,and tripped position indication contact, for detail see the accessories part
Standard and certificationIEC 60947-2KEMA, SEMKO, CB, CE
CDM1-6363
3P,4P5010 1620 2532 4050 63
690V
6000V
400V
5025301850120400060002530
TypeFrame size ratedcurrent ANumber of polesRated frequency HzRated current In A
Rated insulationvoltage Ui VRated impulsewithstandvoltage Uimp VRated operationalvoltage Ue VIcu kA(400V)Ics kA(400V)Arcing distance mmDurability
Power consu-mpution W
CDM1-100100
2P,3P,4P
16 2025 3032 4050 6380 100800V
8000V
400V / 690V
50353026
120300070004050
CDM1-225225
100 125160 180200 225
50353026
120150065006075
CDM1-400400
200 350250 315400
400V
70504030100601000400040110
CDM1-630630
3P,4P
400 500630
400V690V65454234
6010004000150200
CDM1-800800
400 500630 700800
400V
70504030
205002500135190
CDM1-12501250
3P
700 80010001250
85-45-
205002500240300
Type MType LType MType L
Cycles/hElectricalMechanicalFixedPlug-in
To distribute electric power and protect circuits and equipment against overload,undervoltage, and short-circuit faultsTo protect motors against overload, undervoltage and short-circuit faults (Inm²400A)To infrequently start and control AC motors
Delixi Electric30
CDM1Standard: IEC 60947-2
Type Reference
CDM1-63 3P
4P
CDM1-100 2P
3P
4P
CDM1-225 2P
In A
10162025324050631016202532405063162025324050638010016202532405063801001620253240506380100100125160180200225
Type MCDM163M103CDM163M163CDM163M203CDM163M253CDM163M323CDM163M403CDM163M503CDM163M633CDM163M104CDM163M164CDM163M204CDM163M254CDM163M324CDM163M404CDM163M504CDM163M634CDM1100M162CDM1100M202CDM1100M252CDM1100M322CDM1100M402CDM1100M502CDM1100M632CDM1100M802CDM1100M1002CDM1100M163CDM1100M203CDM1100M253CDM1100M323CDM1100M403CDM1100M503CDM1100M633CDM1100M803CDM1100M1003CDM1100M164CDM1100M204CDM1100M254CDM1100M324CDM1100M404CDM1100M504CDM1100M634CDM1100M804CDM1100M1004CDM1225M1002CDM1225M1252CDM1225M1602CDM1225M1802CDM1225M2002CDM1225M2252
Type LCDM163L103CDM163L163CDM163L203CDM163L253CDM163L323CDM163L403CDM163L503CDM163L633----------------------------------CDM1100L163CDM1100L203CDM1100L253CDM1100L323CDM1100L403CDM1100L503CDM1100L633CDM1100L803CDM1100L1003------------------------------
Delixi Electric 31
CDM1Standard: IEC 60947-2
Type ReferenceIn A
3P
4P
CDM1-400 3P
4P
CDM1-630 3P
4P
CDM1-800 3P
4P
CDM1-1250 3P
10012516018020022510012516018020022520022525031535040020021525031535040040050063040050063040050063070080040050063070080070080010001250
Type MCDM1225M1003CDM1225M1253CDM1225M1603CDM1225M1803CDM1225M2003CDM1225M2253CDM1225M1004CDM1225M1254CDM1225M1604CDM1225M1804CDM1225M2004CDM1225M2254CDM1400M2003CDM1400M2253CDM1400M2503CDM1400M3153CDM1400M3503CDM1400M4003CDM1400M2004CDM1400M2254CDM1400M2504CDM1400M3154CDM1400M3504CDM1400M4004CDM1630M4003CDM1630M5003CDM1630M6303CDM1630M4004CDM1630M5004CDM1630M6304CDM1800M4003CDM1800M5003CDM1800M6303CDM1800M7003CDM1800M8003CDM1800M4004CDM1800M5004CDM1800M6304CDM1800M7004CDM1800M8004CDM11250M7003CDM11250M8003CDM11250M10003CDM11250M12503
Type LCDM1225L1003CDM1225L1253CDM1225L1603CDM1225L1803CDM1225L2003CDM1225L2253------------CDM1400L2003CDM1400L2253CDM1400L2503CDM1400L3153CDM1400L3503CDM1400L4003------------CDM1630L4003CDM1630L5003CDM1630L6303------CDM1800L4003CDM1800L5003CDM1800L6303CDM1800L7003CDM1800L8003------------------
Note: The connection mode for CDM1 is the fixed type front connection.
Delixi Electric32
CDM1Standard: IEC 60947-2
Overall dimensionsUnit:mm
2P 3P 4P
Key to overall dimensions
Type
CDM1-63LCDM1-63MCDM1-63MCDM1-100MCDM1-100LCDM1-100MCDM1-100MCDM1-225MCDM1-225LCDM1-225MCDM1-225MCDM1-400L,MCDM1-400MCDM1-630L,MCDM1-630MCDM1-800L,MCDM1-800MCDM1-1250M
Poles
334233423343434343
Install dimensionsa252525--303030--35353544445858707070
b117117117129129129129126126126126215215200200243243375
d3.53.53.54.54.54.54.55.55.55.55.56.56.5777710
Overall dimensionsL135135135150150150150165165165165257257270270280280406
L12121215151515164646464105105118118102102104
W767610365929212275107107142140184182240210280210
H89.59999103.587103.5103.5124.5108124.5124.5146146160160146146190
H22128282425242424.524.52424.536.536.5414134.534.558.5
H17482828768878710487104104100100108108103103140.5
Delixi Electric 33
CDM1Standard: IEC 60947-2
A117129126215200243
B253035445870
H495454768376
Unit:mm
Unit:mm
A3535656048
B11.531151515
H4648616166
Delixi Electric34
CDM1Standard: IEC 60947-2
The accessories are fixed into the circuit breaker.
MN (Undervoltage Release)
Accessories
Technical dataRated operating voltage Us(V)Drop-out voltage(V)Pick-up voltage(V)
230V, 400V AC(0.35~0.7) Us(0.85~1.1) Us
MX (Shunt Release)
Technical dataRated control voltage US(V)Operating voltage(V)
230V, 400V AC(0.7~1.1) US
OF (Auxiliary Contact)
Rated thermal current Ith 3ARated operating voltage US(V)1NO+1NC (Change over)2NO+2NC (Change over)
SD (Alarm Switch)
Rated thermal current Ith 3ARated operating voltage US(V)
1NO+1NC
Technical data
0.4A (400V AC)
Technical data
0.26A (400V AC)0.4A (400V AC)
Delixi Electric 35
CDM1Standard: IEC 60947-2
Ordering information
Type
CDM1-63
CDM1-100
CDM1-225
CDM1-400
CDM1-630
CDM1-800
CDM1-1250
Voltage (V)
230V AC400V AC
ReferenceMN*CDM163MN230CDM163MN400CDM1100MN230CDM1100MN400CDM1225MN230CDM1225MN400CDM1400MN230CDM1400MN400CDM1630MN230CDM1630MN400CDM1800MN230CDM1800MN400CDM11250MN230CDM11250MN400
MX*CDM163MX230CDM163MX400CDM1100MX230CDM1100MX400CDM1225MX230CDM1225MX400CDM1400MX230CDM1400MX400CDM1630MX230CDM1630MX400CDM1800MX230CDM1800MX400CDM11250MX230CDM11250MX400
OFCDM163OF
CDM1100OF
CDM1225OF
CDM1400OF
CDM1630OF
CDM1800OF
CDM11250OF
SDCDM163SD
CDM1100SD
CDM1225SD
CDM1400SD
CDM1630SD
CDM1800SD
TR(Round Handle)CDM163TR
CDM1100TR
CDM1225TR
CDM1400TR
CDM1630TR
CDM1800TR
TS(Square Handle)CDM163TS
CDM1100TS
CDM1225TS
CDM1400TS
CDM1630TS
CDM1800TS
Delixi Electric36
CDM1LStandard: IEC 60947-2
Function CDM1L molded case circuit breakers with electronic type residual current operatedprotection can be used to provide the following functions:
To distribute electric power and protect circuits and equipment against overload, undervoltage, and short-circuit faults
To infrequently start and control AC motorsTo protect users against indirect contactTo protect electrical installations against insulation faults (fire hazard, etc)
Description Technical data
Main technical parameters are shown in the table below
Table for 4 pole CDM1LE (Neutral line)CodeAB
NoteN(direct connect)N(direct connect N pole lead-make, lag-break)
TypeFrame size rated current ARated current In A
Rated frequency HzRated insulation voltage Ui VRated operational voltage Ue VRated impulse withstand voltage Uimp VNumber of polesIcu kA(400V)Ics kA(400V)Rated residualoperatingcurrent I n mARated residual non-operatingcurrent I no mADurability
CDM1L-10010016 20 25 32 4050 63 80 1005080040080003P, 4P5035352230/100/500100/300/500100/300/5001/2 I n
1500850010000
CDM1L-225225100 125 140 160180 200 225
5035352230/100/500100/300/500100/300/5001/2 I n
100070008000
CDM1L-400400200 250 315350 400
70504030100/300/500
100/300/5001/2 I n
100040005000
Type MType LType MType LWithout delay
With delay
ElectricalMechanicalTotal
Maximum break time for residual operating current protectionNumber of polesMax. breaktime S
Without delayWith delay
I n0.20.5/1.15/2.15
2 I n0.10.35/1/2
5 I n0.040.25/0.9/1.9
10 I n0.040.25/0.9/1.9
Delixi Electric 37
CDM1LStandard: IEC 60947-2
Constructional featuresThermamagnetic release offers instantaneous trip against short-circuit and long time delay trip against overcurrentThe residual operating current value can be fixed or adjustableThe residual operating current protection can be with time-delay or without time-delayVarious accessories can be attached to the circuit breaker to extend its functions, such as undervoltage release, shunt release, ON/OFF positionindication contact, and tripped position indication contact, for detail see the accessories part
Standard and certificationIEC 60947-2CE
Ordering information
Delixi Electric38
CDM1LStandard: IEC 60947-2
ReferenceType MCDM1LE100M163CDM1LE100M203CDM1LE100M253CDM1LE100M323CDM1LE100M403CDM1LE100M503CDM1LE100M633CDM1LE100M803CDM1LE100M1003CDM1LE100M164 ACDM1LE100M204 ACDM1LE100M254 ACDM1LE100M324 ACDM1LE100M404 ACDM1LE100M504 ACDM1LE100M634 ACDM1LE100M804 ACDM1LE100M1004 ACDM1LE100M164 BCDM1LE100M204 BCDM1LE100M254 BCDM1LE100M324 BCDM1LE100M404 BCDM1LE100M504 BCDM1LE100M634 BCDM1LE100M804 BCDM1LE100M1004 BCDM1LE225M1003CDM1LE225M1253CDM1LE225M1403CDM1LE225M1603CDM1LE225M1803CDM1LE225M2003CDM1LE225M2253CDM1LE225M1004 ACDM1LE225M1254 ACDM1LE225M1404 ACDM1LE225M1604 ACDM1LE225M1804 ACDM1LE225M2004 ACDM1LE225M2254 ACDM1LE225M1004 BCDM1LE225M1254 BCDM1LE225M1404 BCDM1LE225M1604 BCDM1LE225M1804 BCDM1LE225M2004 BCDM1LE225M2254 BCDM1LE400M2003CDM1LE400M2503CDM1LE400M3153CDM1LE400M3503CDM1LE400M4003
Type
CDM1L-100 3P
4P A
4P B
CDM1L-225 3P
4P A
4P B
CDM1-400 3P
Rated currentIn A162025324050638010016202532405063801001620253240506380100100125140160180200225100125140160180200225100125140160180200225200250315350400
Type LCDM1LE100L163CDM1LE100L203CDM1LE100L253CDM1LE100L323CDM1LE100L403CDM1LE100L503CDM1LE100L633CDM1LE100L803CDM1LE100L1003CDM1LE100L164 ACDM1LE100L204 ACDM1LE100L254 ACDM1LE100L324 ACDM1LE100L404 ACDM1LE100L504 ACDM1LE100L634 ACDM1LE100L804 ACDM1LE100L1004 ACDM1LE100L164 BCDM1LE100L204 BCDM1LE100L254 BCDM1LE100L324 BCDM1LE100L404 BCDM1LE100L504 BCDM1LE100L634 BCDM1LE100L804 BCDM1LE100L1004 BCDM1LE225L1003CDM1LE225L1253CDM1LE225L1403CDM1LE225L1603CDM1LE225L1803CDM1LE225L2003CDM1LE225L2253CDM1LE225L1004 ACDM1LE225L1254 ACDM1LE225L1404 ACDM1LE225L1604 ACDM1LE225L1804 ACDM1LE225L2004 ACDM1LE225L2254 ACDM1LE225L1004 BCDM1LE225L1254 BCDM1LE225L1404 BCDM1LE225L1604 BCDM1LE225L1804 BCDM1LE225L2004 BCDM1LE225L2254 BCDM1LE400L2003CDM1LE400L2503CDM1LE400L3153CDM1LE400L3503CDM1LE400L4003
Delixi Electric 39
CDM1LStandard: IEC 60947-2
Overall dimensions
Type
CDM1L-100L
CDM1L-100M
CDM1L-225L
CDM1L-225M
CDM1L-400L,M
Poles
3434343434
Overall sizeL1 L2 L3 L4
150max150max150max150max165max165max165max165max257max257max
94max94max110max110max94max94max110max110max146max146max
75max75max92max92max72max72max90max90max103max103max
Installation sizea b d
30603060357035708888
129129129129126126126126194194
4 4.56 4.54 4.56 4.54 4.56 4.54 4.56 4.54 4.56 6.5
Key to overall dimensions
92max122max92max122max107max142max107max142max154max198max
Unit:mm
ReferenceType MCDM1LE400M2004 ACDM1LE400M2254 ACDM1LE400M2504 ACDM1LE400M3154 ACDM1LE400M3504 ACDM1LE400M4004 ACDM1LE400M2004 BCDM1LE400M2254 BCDM1LE400M2504 BCDM1LE400M3154 BCDM1LE400M3504 BCDM1LE400M4004 B
Type
4P A
CDM1L-400 4P B
Rated currentIn A200225250315350400200225250315350400
Type LCDM1LE400L2004 ACDM1LE400L2254 ACDM1LE400L2504 ACDM1LE400L3154 ACDM1LE400L3504 ACDM1LE400L4004 ACDM1LE400L2004 BCDM1LE400L2254 BCDM1LE400L2504 BCDM1LE400L3154 BCDM1LE400L3504 BCDM1LE400L4004 B
Delixi Electric40
CDM1LStandard: IEC 60947-2
Centrally revolvable type
FrameDimension
Dimension for handle mechanismCDM1L-10049
CDM1L-22555
CDM1L-40074
Unit:mm
Handle mechanism
Square Handle
The accessories are fixed into the circuit breaker.
MN (Undervoltage Release)
Accessories
Technical dataRated operating voltage US(V)Drop-out voltage(V)Pick-up voltage(V)
230V, 400V AC(0.35~0.7) Us(0.85~1.1) Us
Delixi Electric 41
CDM1LStandard: IEC 60947-2
MX (Shunt Release)
Technical dataRated control voltage Us(V)Operating voltage(V)
230V, 400V AC(0.7~1.1) Us
OF (Auxiliary Contact)
Rated thermal current Ith 3ARated operating voltage Us(V)1NO+1NC (Change over)2NO+2NC (Change over)
Technical data
0.4A (400V AC)
SD (Alarm Switch)
Rated thermal current Ith 3ARated operating voltage Us(V)
1NO+1NC
Technical data
0.26A (400V AC)0.4A (400V AC)
Type
CDM1L-100
CDM1L-225
CDM1L-400
Ordering information
ReferenceMN*CDM1LE100MN230CDM1LE100MN400CDM1LE225MN230CDM1LE225MN400CDM1LE400MN230CDM1LE400MN400
Voltage(V)230V AC400V AC
MX*CDM1LE100MX230CDM1LE100MX400CDM1LE225MX230CDM1LE225MX400CDM1LE400MX230CDM1LE400MX400
OFCDM1LE100OF
CDM1LE225OF
CDM1LE400OF
SDCDM1LE100SD
CDM1LE225SD
CDM1LE400SD
TS(Square Handle)CDM1LE100TS
CDM1LE225TS
CDM1LE400TS
TR(Round Handle)CDM1LE100TR
CDM1LE225TR
CDM1LE400TR
Delixi Electric42
CDW7Standard: IEC 60947-2
ApplicationApplied to power distribution of AC 50Hz, rated operational voltage 400/690V, ratedcurrent 200A~6300A and lowerFor power distribution and protecting circuit and power supply equipment aganistharm from overload, undervoltage, short circuit, earthing, and other faultsCircuit breaker which ampere frame size is under 630A can protect motor aganistoverload,undervoltage and shortcircuitCore parts use intelligent control unit which has accurate discrimination protection, itcan avoid unnecessary power failure and enhance the reliability of power supplysystem
Standard and certificationInternational standard: IEC609472Approved certification: CB, CE, KEMA
Operating condition and installation recommendation
Ambient temperature shall be controlled between+40 and -5 , the average temperature in 24 hoursshall not exceed +35Note:contacting manufacturer about circuit breakerused in place where ambient temperature is higherthan +40 or lower than -5
Delixi Electric 43
CDW7Standard: IEC 60947-2
Parameter and characteristics
Certification approved: IEC 60947-1 IEC 60947-2CDW7-10003, 4B0400690800050200/400/630/800/100042--30--88--30--90001000
CDW7-20003, 4B0400/690800800050630/800/1000/1250/1600/200080505040176105504090001000
CDW7-32003, 4B0400/6908008000502000/2500/320010065805022014365504500500
CDW7-63003, 4B04008008000504000/5000/6300120--100--264--85--1500500
In
Icu
Ics
Icm
AC 400VAC 690VAC 400VAC 690VAC 400VAC 690VAC 400VAC 690V
Delixi Electric44
Fault and alarm reset button“Fault/Alarm” LED
In normal state, this LED is off. In case of fault release, the red LED will flash quickly; in case of alarm, the red LED will be on constantly
“Normal” LED As long as the controller is on and operates normally, the green LED always flashes
Communication indicator The communication state indication is as follows: Profibus: OFF if no communication; ON if communication exists Modbus: OFF if no communication; flash if communication exists Device Net: Flash if no communication; ON if communication exists
Curve LEDs Red LEDs exist behind the curve. In case of fault release, the corresponding LED will flash indicating the fault type; During the parameter setting process, the LED is always on and indicates the current item.
KeypadMeasure key l, used to switch to the default measurement menu.Set key 2, used to switch to the parameter setting menu.Protection Key 3, used to switch to the protection parameter setting menu.Info key 4, used to switch to the historical record and maintenance menu.Up, Move up the cursor through the menu items on the current level, or
increment the value of the selected parameter.Down, Move down the cursor through the menu items on the current
level, or decrement the value of the selected parameter.Exit, exit from the current level and return to the upper level, or cancel the
current parameter selection.Select, Select to enter into the next level from the current item, or select the
current parameter, or store the change.
CDW7Standard: IEC 60947-2
Protection characteristics
Delixi Electric 45
CDW7Standard: IEC 60947-2
Delixi Electric46
CDW7Standard: IEC 60947-2
Delixi Electric 47
ECW S- HDifferent curvesavailable for long timedelay protectionDifferent curvesavailable for inverseshort time delay protec-tionDefinite short time delayprotectionInstantaneous protectionCurrent unbalance (openphase) protectionEarth protectionEarth fault alarmNeutral phase protectionLoad monitor
ECW - M
ECW - H
DO Signal alarm functionMCR and out-of-limittripping protectionEarth fault or leakageprotection (either)
Over-voltage protectionUnder-voltage protectionVoltage unbalanceprotectionOver-currency protectionUnder-frequencyprotectionPhase protectionInverse power protectionDemand protectionZonal system interlockprotectionCommunication function
Long time delay protec-tionDefinite time delay +inverse time delay forshort time delay protec-tionInstantaneous protectionEarthing protectionLoad monitorDifferent curvesavailable for long timedelay protectionDifferent curvesavailable for inverseshort time delay protec-tionDefinite short time delayprotectionInstantaneous protectionMCR and out-of-limittripping protectionCurrent unbalance (openphase) protectionEarth protectionEarth fault alarmNeutral phase protectionLoad monitor
Max. phase currentFour phase current (I1,I2, I 3, IN) and earthcurrent
Four phase current (I1,I2, I 3, IN) and earthcurrentThermal capacity
Digital displayLED indicationKey operationDigital setting ofprotection param-eters
LCD display ofChinese GUILED indicationKey operation
Fault logSelf-diagnosisfunctionFeature testfunction
Up to 8 fault logsUp to 8 alarm logsUp to 8 position logsHistorical currentpeakContact equivalenceNumber of operatingcyclesFault clock functionSelf-diagnosis faultlogSelf-diagnosisfunctionFeature testfunction
CDW7Standard: IEC 60947-2
Four phase current (I1,I2, I 3, IN) and earthcurrentThermal capacity
Up to 8 fault logsUp to 8 alarm logsUp to 8 position logsHistorical current peakContact equivalenceNumber of operatingcyclesClock functionSelf-diagnosis function
LCD display ofChinese GUILED indicationKey operation
MCR and out-of-limittripping protectionDO Signal alarm functionCommunication function
Delixi Electric48
ECW-H intelligent controllers
Ir=(0.4~1)ln10%2h1h
15,30,60,120,240,360,480,600,720,840,960
8.4,16.9,33.8,67.5,135,202.5,270,337.5,405,472.5,540
15%
Ir2=(1.5~15)In10%
Ts=K/10(N2-1),(Ts 20ms)0.1,0.2,0.3,0.40.06,0.13,0.2,0.27
15%
Ir4=(0.2~1.0)In
0.1s~1s (Rank difference 0.1s)
CDW7-1000ECWS-H intelligent control-lersIr=(0.4~1)ln
15%2h2h
8,12.8,19.2,32,48,64,80,108,144,224,320,480,640,800,960,11203.32,5.32,8.00,13.32,20.00,26.66,33.30,45.00,60.00,93.32,133,200,266,333,400,4331.25,2.00,3.00,5.00,7.50,10.0,12.5,16.8,22.5,35.0,50.0,75.0,100,125,150,162
10%
Ir2=(1.5~15)In15%
Ts=K/10(N2-1),(Ts 20ms)0.1,0.2,0.3,0.40.06,0.13,0.2,0.27
10%
1.05 Ir h1.3 Ir h1.5Ir1
2.0Ir1
3.0Ir1
CDW7Standard: IEC 60947-2
CDW7-2000~6300ECW-M intelligent controllers
Ir=(0.4~1)ln10%2h1h
15,30,60,120,240,480
8.4,16.9,33.8,67.5,135,270
15%
Ir2=(0.4~15)In10%
I2Ts= 8Ir1)2ts0.1,0.2,0.3,0.40.06,0.16,0.25,0.34
15%
Ir4=(0.2~1.0)In10%
0.1~4s (Rank difference 0.1s)
CDW7-2000Ir3=1In~50KA+OFF
15%
ECWS-HCDW7-1000(1.0~20)ln
15%
Ir4=(0.2~1.0)In10%
0.1s~1s (Rank difference 0.1s)
15%
CDW7-3200Ir3=1In~75KA+OFF
15%
CDW7-6300IIr3=1In~100KA+OFF
15%
ECW-M ECW-H
Delixi Electric 49
AC 380V(0.35~0.7)Ue(0.85~1.1)Ue
0.35Ue36VA5VA
AC380 AC220 DC220 DC11036VA 24VA 24W 24W5VA 5VA 5W 5W(0.7~1.1)Usless than 30ms
7-2000~6300
AC380 AC220 DC220 DC11036VA 24VA 24W 24W10VA 10VA 10W 10W(0.85~1.1)Usless than 70ms
CDW7Standard: IEC 60947-2
Auxiliary functions
AC220V(0.35~0.7)Ue(0.85~1.1)Ue
0.35Ue24VA5VA
70 110
Delixi Electric50
AC-15
10110.3101.10.310
DC-13
1116Pe1.11.16Pe10
CDW7Standard: IEC 60947-2
AC380 AC220 DC220 DC11085VA 85VA 85VA 85VA110VA 110VA 110VA 110VA150VA 150VA 150VA 150VA80VA 80VA 80VA 80VA(0.85~1.1)Usless than 5s
Pe 50W T0.95e’s upper limit 300ms
U/Uecos 0.95I/IeU/Uecos T0.
CDW7-2000~6300
CDW7-1000
In 2000A2000A In 3200A3200A In 6300A
Delixi Electric 51
200, 400630800, 1000200, 400630800, 1000
CDW7-1000A fixed circuit breaker outline and horizonal/vertical connected dimension L266266266336336336
L1244244244314314314
N6121281616
L2---707070
CDW7Standard: IEC 60947-2
Overall and mounting dimension
Delixi Electric52
200, 400630800, 1000200, 400630800, 1000
CDW7-1000A drawout type circuit breaker outline and horizonal/vertical wiring Unit:mm
3P
4P
L284284284354354354
L1194194194264264264
L3557575557575
L4638383638383
L2---707070
n6121281616
H68106810
CDW7Standard: IEC 60947-2
Delixi Electric 53
CDW7-2000A fixed circuit breaker vertical connection diagram
CDW7-2000
CDW7-3200
CDW7-2000A~3200A fixed circuit breaker overall and horizonal/vertical wiring Unit:mmIn A400~8001000~160020002000~25003200
a1015202030
CDW7-2000 mounting dimension is same regardless of different current used in"horizonal-wiring" or"vertical-wiring"
3P4P
3P4P
L1362457457422537
L2318413413378493
L3292292292352352
L4340435435400515
CDW7Standard: IEC 60947-2
CDW7-2000A~3200A
Delixi Electric54
CDW7-2000
CDW7-3200
CDW7-6300(4000/5000A)CDW7-6300
CDW7-2000A~6300A drawout type circuit breaker outline and horizonal/vertical connection Unit:mmIn A400~8001000~160020002000~25003200~40003200~400040005000~63005000~6300
a101520203030203030
3P
4P3P4P4000A 3P4P3P
L1375375470435550550813928928
L2335335430395510510773888888
L3292292292352352352352352352
L4265265360325440440703818818
L5247247247307307307307307307
W1461461461471471494494494494
W2507507507517517540540540540
b179179179189189212212212212
W7-3200 can expand to 4000A,which mounting dimension is as same as 4P of CDW7-3200DW7-2000 the mounting dimension is same regardless of different current used in"horizonal-connected" or "vertical-connected"
CDW7Standard: IEC 60947-2
CDW7-2000A~6300A
CDW7-2000A drawout circuit breaker vertical connection diagram
Delixi Electric 55
CDW7-2000~6300 panel cut-out dimension and mounting dimension Unit:mm
CDW7-2000CDW7-3200CDW7-6300
a
306366366
b
346406406
c3P00189(4000/5000A)246.5(6300A)
4P47.557.5246.5(4000/5000A)--
CDW7Standard: IEC 60947-2
CDW7-1000
CDW7-2000~6300
CDW7-2000~6300A
CDW7-2000~6300A
CDW7-1000ACDW7-1000A
Delixi Electric56
41 42 when controller power choose DC,the output is DC24V,user can select DCpower module43 44 circuit breaker status detection terminal(used when MCR function included)45 overload pre-alarm signal output46 automatic diagnosis alarm signal output47 fault trip alarm signal output48 earthing but non-tripping,only alarm signal output49 four groups of contacts output common terminal50 51 externally sensor input terminal58 able to directly connect to power supply(automatic pre-energization),also ableto join up with normal open pushbutton to connect to power supply(manual pre-energization)
F X with different current ratings shall con-nect with different sources.
CDW7Standard: IEC 60947-2
Auxiliary connection diagramn
Delixi Electric 57
CDW7Standard: IEC 60947-2
Pin functions:Pin 1# and 2#: Auxiliary power input,pin 1# ispositive for DC inputPin 3#, 4#, 5#: Fault trip contact output (4# iscommon terminal); contact capacity: AC380V, 16APin 6# and 7#, 8# and 9#: Two groups of auxiliarycontacts for breaker status; contact capacity:AC380V, 16A12#,13#(Contact1)and 14#,15#(Contact2)and 16#,17#(Contact3)and 18#,19#(Contact4):Output offour groups of signal for controllers,contactcapacity:4A/240V 7A/24VDC20#: Earth protection21#~24#:input of voltage signal (Note:the order cantbe wrong)
Note: 1. If the control voltage values of Q, F, X, and M are different to eachother, these components can be connected to different power supply units; in theapplication, the shunt release and closing electromagnet shall be connectedserially with normally open and normally closed auxiliary contacts (the partenclosed by dotted lines shall be connected by the user; the part represented by atwo-dot chain line is the wiring of circuit 51); Note 2: The pin 35# can be connected to the power supply directly (automaticpre-energy storage) or connected serially to a normally open button and then tothe power supply (manual pre-energy storage); Note 3: If the user requests, pin #6~#7 can be connected to normally closedcontacts; Note 4: The ECW power supply module I is a DC power supply module, and itcan be omitted if the power supply is AC power supply; the polarity and lead-ins/lead-outs shall not be reversed (for draw-out type circuit breakers, the lead-outsof the power supply module has been connected before the circuit break isshipped from the factory); Note 5: In case of circuit 47, the auxiliary contacts are four closed and fouropen contacts; pin #25 and #26 are input terminals of an external current trans-former , used for earth fault protection as (3P+N)T type ; Note 6: In case of circuit 51, the auxiliary contacts are six closed and six opencontacts (or five closed and five open contacts); pin #25, #26, and #51 formnormally open and normally closed contacts; Note 7: If Profibus or any other protocol is used, ECW-H + DP conversion moduleand other conversion modules must be ordered; ECW power supply module lV andECW201 relay module must be ordered separately; Note 8:Pin #12~#19 input/output contacts can be user-defined programmablesignal contacts.
Components:Q - Under-voltage releaseF - Shunt releaseX – Closing electromagnetDF - Auxiliary switchM - MotorSB1—Button for closingSB2—Button for shunt
Delixi Electric58
1# 2#: 1# is the front terminal when DC is supplied by auxiliary power3# 4# 5
AC380V 16A6# 7# 8# 9#:two groups of circuit breaker status auxiliary terminal: AC380V 16A10# 11#: respectively as the communication leading-out of RS485A ,RS485B12#: overload pre-alarm signal output13#: communication remote control shunt release output14#: communication remote control closing output or instantaneous short time-delaytrip signal output15#: communication remote control energy storage or long time-delay trip signal output16#: S-earth(RS-485 transmissionn common ground wire17#: load monitor output119#: signal output common earth wire21#: neutral voltage signal N phase23#: voltage signal B phase
1
2: terminal 35# can directly connect to power supply(automatic pre-energy storage),or join up with normal openpushbutton to connect power supply(manual pre-energystorage)3: terminal 6#~7# can lead out normal close contact if usersuggested4: ECW power supply module is DC power supply module,the module doesn't exist when power supply current is AC,polarity,incoming line and leading-out line shall not con-nected reversely(leading-out terminal of power supply mod-ule in drawout type had been connected before sale)5: in 47 circuit,auxiliary contact is 4 open 4 close;25# 26# isinput terminal of external sensor6: in 51 circuit,auxiliary contact is 6open6close(5open5close);25# 26# 51# form normal open normal closecontact(earth-leakage protection excluded)7: if using profibus or other protocols, user shall orderECW-H+HP transformation module and others;ECW powersupply moduleV,ECW201 relay module and others shallorder seperately8: #12~#19 output input contacts are programmableself-defined signal contaccts
18#: load monitor signal 220#: PE line ,shield earth wire22#: voltage signal A phase24#: voltage signal C phase
CDW7Standard: IEC 60947-2
Delixi Electric 59
CDW7Standard: IEC 60947-2
Other additional parameter
Delixi Electric60
CDW7 Series Air Circuit Breakers
Order Instructions
Note:for any special requirement,please contact with the manufacturer.
Customer Sets purchased Date
Mode CDW7 Fixed Draw-out 3 Poles 4Poles
AC400 AC690 Rated current In= ARated voltage
H Type Intelligent electronic trip
Mechanical interlock
Accessaries
Basic function Overload long delaytime protection
Short-circuit shortdelay time protection
Short-circuit instantaneousprotection
Earthing protection Load monitoring function(Not available for L type)
Metering function
Power supply AC 230V AC 400V DC 220V DC 110V
Under-voltage trip
Under-voltage instantaneous trip
Under-voltage time-delay trip
AC 230V AC 400V
1s 3s 5s
AC 230V AC 400V DC 220V DC 110V
AC 230V AC 400V DC 220V DC 110V
AC 230V AC 400V DC 220V DC 110V
Shunt trip
Energy releasing electromagnet
Motor Driven
Interphase barrier
N phase external connection
Escutcheon
Earth-leakage CT(Only for cable)
Auxiliary switch
Auxiliary Connection Terminal
standard(4a4b) special(6a6b)
1-lock,1-key
Steel-cable interlock
Interlocking rod with 3 switches
2-lock,1-key
Interlocking rod with 2 switches
Door interlock(Available for Draw-out type)
3-lock,1-key
Delixi Electric 61
Function
DescriptionMain circuitRated insulation voltage: 690 VRated operational voltage: up to 660 VFrequency limits: 50/60 HzRated operational current and power of controlled motors are shown in the tablebelowControl circuitControl circuit supply voltage Us:AC 36V, 110V, 127V, 220/230V, 380/400VDC 110V, 220VTechnical featuresCompact, light, low consumption, long-life durabilityFlame-resistant enclosure ensures a safe & reliable serviceFull range auxiliaries:- auxiliary contact module- time delay module- mechanical interlock moduleDirect connection with thermal overload relay to form electomagnetic starter
Technical data
Standard and certificationIEC 60947-4-1KEMA, CE
CDC17Standard: IEC 60947-4-1
Delixi Electric62
CDC17Standard: IEC 60947-4-1
CDC17-185~330CDC17-115~150
Overall dimensions
CDC17-9~32 CDC17-40~95
Note:C1max-Contactor+CDF4 C2max-Contactor+CDLA
Installation dimensions
TypeCDC17-9~12CDC17-18CDC17-25CDC17-32CDC17-40~65CDC17-80~95
Amax454556.556.57585
Cmax77829195115123
Bmax68687979127127
C1max109115124127145153
C2max133138149152170178
a35 0.21
40 0.21
40 0.21
b59 0.28
66 0.43
105 0.57
c4.5
4.5
6.5
unit:mm
TypeCDC17-185CDC17-225CDC17-265, 330
A138138171
B180199207
A1111111144
C163163201
C19595119
a1404848
a2202525
a3808096
b1158172180
b2154172180
91111
b3150150166
17711
CDC17-630~1000CDC17-400~500
Delixi Electric 63
ModelRated operationalcurrent A
Rated operational voltage VRated insulation voltage VRated conventional thermal current APower of controlled 3-phase cage motor(AC-3)kWAC-3
AC-4
Mechanical durabilities(x104 cycles)AC Coil
Accessories
Matched RelayMatched FuseCross Sectionof Cable mm2
Weight Kg
CDC17Standard: IEC 60947-4-1
Characteristics
Electric durabilities(x104 operations)Operating rate(cycles/h)Electric durabilities(x104 operations)Operating rate(cycles/h)
Coil voltage VOperational voltage VDrop-out voltage VInrush VASealed VAHeat dissipation WAuxiliary contact
Time-delay blockMechanical Interlock
Number of PieceFlexible cableInflexible cable
380V / 400V
660V
AC-3AC-4AC-3AC-4
380V/400V660V
Front mountSide mountFront mount
CDC17-121258.92
5.57.5
1 2
CDC17-18187.7123.8
327.59
RT16-321 2460.335
CDC17-25258.5184.4
401115
110113~4
CDR17-32RT16-401 2
0.513
CDC17-323212217.5
501518.580
800
RT16-501 26100.510
CDC17-993.56.61.5380 / 400 6606902045.5100120020300100036, 48, 110, 220, 38085%~110%Us20%~75%Us7081.8~2.7CDF4-CDLA2 or CDLA3CDJL17-1CDR17-18RT16-201 22.540.315
Delixi Electric64
ModelRated operationalcurrent A
Rated operational voltage VRated insulation voltage VRated conventional thermal current APower of controlled 3-phase cage motor(AC-3)kWAC-3
AC-4
Mechanical durabilities(x104 cycles)AC Coil
Accessories
Matched RelayMatched FuseCross Sectionof Cable mm2
Weight Kg
CDC17Standard: IEC 60947-4-1
CDC17-9595445521.3
45
RT16-2001 250 2550 -
Electric durabilities(x104 operations)Operating rate(cycles/h)Electric durabilities(x104 operations)Operating rate(cycles/h)
Coil voltage VOperational voltage VDrop-out voltage VInrush VASealed VAHeat dissipation WAuxiliary contact
Time-delay blockMechanical Interlock
Number of PieceFlexible cableInflexible cable
380V / 400V
660V
AC-3AC-4AC-3AC-4
380V/400V660V
Front mountSide mountFront mount
CDC17-5050243912
802233
RT16-801 21625 -
CDC17-404018.5349380 / 400 6606906018.5308012002030080036, 48, 110, 220, 38085%~110%Us20%~75%Us200206~10CDF4-CDLA2 or CDLA3CDJL17-2CDR17-95RT16-631 21016 -1.14
CDC17-6565284214
3037
RT16-1001 22525 -
CDC17-8080374917.3
125374560
600
RT16-1251 250 2550 -1.35
Delixi Electric 65
CDC17Standard: IEC 60947-4-1
ModelRated operationalcurrent A
Rated operational voltage VRated insulation voltage VRated conventional thermal current APower of controlled 3-phase cage motor(AC-3)kWAC-3
AC-4
Mechanical durabilities(x104 cycles)AC Coil
Accessories
Matched RelayMatched FuseCross Sectionof Cable mm2
Weight Kg
Electric durabilities(x104 operations)Operating rate(cycles/h)Electric durabilities(x104 operations)Operating rate(cycles/h)
Coil voltage VOperational voltage VDrop-out voltage VInrush VASealed VAHeat dissipation WAuxiliary contact
Time-delay blockMechanical Interlock
Number of PieceFlexible cableInflexible cable
380V / 400V
660V
AC-3AC-4AC-3AC-4
380V/400V660V
Front mountSide mountFront mount
CDC17-26526510517098
300132160
300
30
11988318.9
JR20-400RT16-4001 2240 -- 32x46.6
CDC17-1501506011061
75100
1 2120 -- 25x3
CDC17-1851857911869
21090110
6954513.5
RT16-2501 2150 -- 25x3
CDC17-2252258513582
225110129
600
JR20-250RT16-2501 2185 -- 32x4
CDC17-330330117225118
300160220
1 2240 -- 30x56.6
CDC17-115115528649380 / 400 66069015055806012002030060036, 48, 110, 220, 38085%~110%Us20%~75%Us559339.5-CDFC17-11,CDFC17-12-CDJL17-3CDR17-185RT16-2001 295 50- 20x32.15
Delixi Electric66
CDC17Standard: IEC 60947-4-1
CDC17-10001000-580-
1000560560
RT17-4/-1250
80x5
Electric durabilities(x104 operations)Operating rate(cycles/h)Electric durabilities(x104 operations)Operating rate(cycles/h)
Coil voltage VOperational voltage VDrop-out voltage VInrush VASealed VAHeat dissipation WAuxiliary contact
Time-delay blockMechanical Interlock
Number of PieceFlexible cableInflexible cable
380V / 400V
660V
AC-3AC-4AC-3AC-4
380V/400V660V
Front mountSide mountFront mount
CDC17-500500147355145
265335
JR20-630RT16-630
18540x5
CDC17-630630188460170
800335450
10501210
-RT16-800
24050x522.8
CDC17-800800242530215
450500
600
RT17-4/1000
-60x5
ModelRated operationalcurrent A
Rated operational voltage VRated insulation voltage VRated conventional thermal current APower of controlled 3-phase cage motor(AC-3)kWAC-3
AC-4
Mechanical durabilities(x104 cycles)AC Coil
Accessories
Matched RelayMatched FuseCross Sectionof Cable mm2
Weight Kg
CDC17-400400138305135380 / 400 660690500220280603002030600110, 220, 38085%~110%Us20%~75%Us780108--CDFC17-21-JR20-400RT16-500 215030x59.36
Delixi Electric 67
Reference
CDC17910CDC17901CDC171210CDC171201CDC171810CDC171801CDC172510CDC172501CDC173210CDC173201CDC174011CDC175011CDC176511CDC178011CDC179511CDC1711522CDC1715022CDC1718522CDC1722522CDC1726522CDC1733022CDC1740022CDC1750022CDC1763022CDC1780022CDC17100022
Rate current (A)
9
12
18
25
32
40506580951151501852252653304005006308001000
Contact blooksNO10101010101111122222222222
NC01010101011111122222222222
Ordering information
CDC17Standard: IEC 60947-4-1
coil voltage codecoil voltage (V) 36
C48E
110F
220M
380Q
frequency codefrequency 50Hz
560Hz6
Delixi Electric68
CDC17Standard: IEC 60947-4-1
DescriptionCDF4-20 Top auxiliary contactCDF4-11 Top auxiliary contactCDF4-02 Top auxiliary contactCDF4-22 Top auxiliary contactCDF4-13 Top auxiliary contactCDF4-31 Top auxiliary contactCDF4-04 Top auxiliary contactCDF4-40 Top auxiliary contactCDLA2 On delay 0.1~3SCDLA2 On delay 0.1~30SCDLA2 On delay 10~180SCDLA3 off delay 0.1~3SCDLA3 off delay 0.1~30SCDLA3 off delay 10~180SCDFC17-11 Side auxiliary contactCDFC17-12 Side auxiliary contactCDFC17-21 Side auxiliary contactCDJL17-1 Mechanical interlocking moduleCDJL17-2 Mechanical interlocking moduleCDJL17-3 Mechanical interlocking module
ReferenceCDF420CDF411CDF402CDF422CDF413CDF431CDF404CDF440CDFC1711CDFC1712CDFC1721CDLA2ON0CDLA2ON2CDLA2ON4CDLA3OFF0CDLA3OFF2CDLA3OFF4CDJL171CDJL172CDJL173
Application scope
CDC17-9~95A
CDC17-9~95A
CDC17-115~330ACDC17-115~330ACDC17-400~1000ACDC17-9~32ACDC17-40~95ACDC17-115~330A
Delixi Electric 69
CDR17Standard: IEC 60947-4-1 60947-5-1
Function CDR17 series thermal overload relays provide:Protection of circuits and motors against overloadProtection of circuits and motors against phase lossMotor starters installation in association with contactors
DescriptionMain circuit:Frequency limits: 50/60 HzRated insulation voltage: 690 VRated operational voltage: up to 690 VFrame size rated current: 18, 32, 95, 185ARated operational current and range of current setting are shown in the tablebelow
Table 1
Technical data
18
32
18
32
690
690
1801180218031804180518061807180818091810181118121813181418151816181718183201320232033204320532063207
0.150.180.250.360.50.70.91.21.82.53.64.86.3791215186.37912182532
0.1~0.13~0.150.12~0.16~0.180.18~0.2~0.250.25~0.32~0.360.35~0.4~0.50.5~0.6~0.70.63~0.72~0.90.9~1~1.21.2~1.6~1.81.8~2~2.52.5~3.2~3.63.5~4~4.84.5~5~6.35~6~76.3~7.2~99~10~1211~13~1514~16~184.5~5~6.35~6~76.3~7.2~99~10~1212~16~1818~20~2523~25~32
CDR17-18
CDR17-32
CDR1718P15CDR1718P18CDR1718P25CDR1718P36CDR1718P5CDR1718P7CDR1718P9CDR17181P2CDR17181P8CDR17182P5CDR17183P6CDR17184P8CDR17186P3CDR17187CDR17189CDR171812CDR171815CDR171818CDR17326P3CDR17327CDR17329CDR173212CDR173218CDR173225CDR173232
RatedinsulationvoltageUi V
Thermal protectionNo
RatedcurrentIe A
Framesizeratedcurrent
Ratedcurrentsetting A
Range ofcurrentsetting A
Type Reference
Delixi Electric70
CDR17Standard: IEC 60947-4-1 60947-5-1
95
185
95
185
690
690
95019502950395049505950695079508950895108501850285038504850585068507850885098510
121825324050657080955065708095115135150160185
9~10~1212~16~1818~20~2523~25~3230~36~4037~45~5048~55~6555~63~7063~70~8075~90~9537~45~5048~55~6555~63~7063~70~8075~90~9590~100~115105~115~135120~135~150130~150~160150~160~185
CDR17-95
CDR17-185
CDR179512CDR179518CDR179525CDR179532CDR179540CDR179550CDR179565CDR179570CDR179580CDR179595CDR1718550CDR1718565CDR1718570CDR1718580CDR1718595CDR17185115CDR17185135CDR17185150CDR17185160CDR17185185
Table 2 Basic data for control circuit and auxiliary circuit
Ratedinsulationvoltage V
Conventionalfree air thermalcurrent A
Ratedoperationalvoltage V
RatedcurrentA
Ratedcontrolcapacity
690 6
Utilizationcategory
RatedfrequencyHz
Circuittype
Controlcircuit
Auxiliarycircuit
AC-15
DC-13AC-15
DC-13
50
50
220(230)380(400)660(690)220(230)220(230)380(400)660(690)220(230)
1.64(1.57)0.95(0.90)0.55(0.52)0.23(0.22)6
360 VA
50 W
Table 3 Limits of operation of relays when energized on all poles
Sequence Multiples ofcurrent setting
123
4
1.051.21.5
7.2
Initial condition Ambient airtemperature
Tripping time
Non-trip within 2 hours<2hTripclass
From coldFrom hot(immediatelyfollowing sequence 1test)From cold
+20oC
10A1010A10
<2min<4min2s<TP²10s4s<TP²10s
Thermal protectionNo
RatedcurrentIe A
Framesizeratedcurrent
Ratedcurrentsetting A
Range ofcurrentsetting A
Type Reference
Delixi Electric 71
CDR17Standard: IEC 60947-4-1 60947-5-1
Table 4 Limits of operation when energized on two poles
Sequence Multiples of current setting
1
2
1.0
1.15
Initial condition Ambient airtemperature
Tripping time
Non-tripwithin 2 hours<2h
From cold state
From hot state(immediately followingsequence 1 test)
+20oCAny two poles The third-pole
0.9
0
Table 5 Temperature compensation characteristic
Sequence Multiples ofcurrent setting
12
34
56
78
1.01.2
1.051.30
0.951.2
1.051.35
Initial condition Ambient airtemperature
Tripping time
>2h<2h
>2h<2h
>2h<2h
>2h<2h
From cold stateFrom hot state(immediatelyfollowing sequence 1 test)From cold stateFrom hot state(immediatelyfollowing sequence 3 test)From cold stateFrom hot state(immediatelyfollowing sequence 5 test)From cold stateFrom hot state(immediatelyfollowing sequence 7 test)
+55oC
-10oC
+60oC
-20oC
Overall dimensions
CDR17-18
Delixi Electric72
CDR17Standard: IEC 60947-4-1 60947-5-1
CDR17-95
CDR17-185
CDR17-32
Delixi Electric 73
LMK Current TransformerStandard: BS7626, IEC44-1
LMK Current Transformer provide: Measuring current
Function
Description Technical Data Primary current: 100A-5000A Secondary approval: 5A, 1A Maximum voltage: 0.66kV Class: 0.5, 1.0, 3.0 Short time thermal current: Ith=100Ih Rated security coefficient: FS<5
Standard and Certification BS7626, IEC44-1
Overall dimensions
LMK-0.66-20LMK-0.66-30LMK-0.66-40LMK-0.66-50LMK-0.66-60LMK-0.66-80LMK-0.66-100LMK-0.66-120
87799999126118136136
68607582102125170190
4237404040404041
Model H W D
Unit: mm
Delixi Electric74
LMK Current TransformerStandard: BS7626, IEC44-1
Class: 0.5Maximum Voltage: 0.66KV
Model Current ratio(A)
Rated Load(VA)
Bar Diameter(mm) (mm)
Number of Turnsthrough the core Reference
30/550/575/5100/5100/5150/5200/5100/5200/5250/5300/5250/5300/5400/5500/5300/5400/5500/5600/5750/5800/51000/5500/5600/5750/5800/51000/51200/51500/5600/5750/5800/51000/51200/51500/52000/52500/5600/5750/5800/51000/51200/51500/52000/52500/53000/51500/52000/52500/53000/54000/55000/5
5-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.7510-3.7510-3.7510-3.7510-3.755-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7515-3.7515-3.7520-3.7510-3.7510-3.7510-3.7510-3.7510-3.7515-3.7515-3.7520-3.7520-3.7515-3.7515-3.7520-3.7520-3.7525-3.7525-3.75
20202020202020202020203030303035353535353535454545454545455050505050505050606060606060606060606060606060
5322111211111111111111111111111111111111111111111111
LMKP63020LMKP65020LMKP67520LMKP610020LMKP610020LMKP615020LMKP620020LMKP610030LMKP620030LMKP625030LMKP630030LMKP625040LMKP630040LMKP640040LMKP650040LMKP630050LMKP640050LMKP650050LMKP660050LMKP675050LMKP680050LMKP6100050LMKP650060LMKP660060LMKP675060LMKP680060LMKP6100060LMKP6120060LMKP6150060LMKP660080LMKP675080LMKP680080LMKP6100080LMKP6120080LMKP6150080LMKP6200080LMKP6250080LMKP6600100LMKP6750100LMKP6800100LMKP61000100LMKP61200100LMKP61500100LMKP62000100LMKP62500100LMKP63000100LMKP61500120LMKP62000120LMKP62500120LMKP63000120LMKP64000120LMKP65000120
LMK-0.66-20
LMK-0.66-30
LMK-0.66-40
LMK-0.66-50
LMK-0.66-60
LMK-0.66-80
LMK-0.66-100
LMK-0.66-120
30 1030 1030 1040 1040 1040 1040 1050 1050 1050 1050 1050 1050 1050 1060 2060 2060 2060 2060 2060 2060 2080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30
Rated Load(VA)
Delixi Electric 75
LMK Current TransformerStandard: BS7626, IEC44-1
Class: 1Maximum Voltage: 0.66KV
532211211111111111111111111111111111111111111111111111
LMK-0.66-20
LMK-0.66-30
LMK-0.66-40
LMK-0.66-50
LMK-0.66-60
LMK-0.66-80
LMK-0.66-100
LMK-0.66-120
30/550/575/5100/5150/5200/5100/5200/5250/5300/5250/5300/5400/5500/5600/5300/5400/5500/5600/5750/5800/51000/51200/5500/5600/5750/5800/51000/51200/51500/52000/5600/5750/5800/51000/51200/51500/52000/52500/5600/5750/5800/51000/51200/51500/52000/52500/53000/51500/52000/52500/53000/54000/55000/5
5-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.755-3.7510-3.755-3.755-3.755-3.7510-3.7510-3.7510-3.7510-3.7510-3.755-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7510-3.7515-3.7515-3.7520-3.7510-3.7510-3.7510-3.7510-3.7510-3.7515-3.7515-3.7520-3.7520-3.7515-3.7515-3.7520-3.7520-3.7525-3.7525-3.75
202020202020202020203030303030353535353535353545454545454545455050505050505050606060606060606060606060606060
LMKP6P13020LMKP6P15020LMKP6P17520LMKP6P110020LMKP6P115020LMKP6P120020LMKP6P110030LMKP6P120030LMKP6P125030LMKP6P130030LMKP6P125040LMKP6P130040LMKP6P140040LMKP6P150040LMKP6P160040LMKP6P130050LMKP6P140050LMKP6P150050LMKP6P160050LMKP6P175050LMKP6P180050LMKP6P1100050LMKP6P1120050LMKP6P150060LMKP6P160060LMKP6P175060LMKP6P180060LMKP6P1100060LMKP6P1120060LMKP6P1150060LMKP6P1200060LMKP6P160080LMKP6P175080LMKP6P180080LMKP6P1100080LMKP6P1120080LMKP6P1150080LMKP6P1200080LMKP6P1250080LMKP6P1600100LMKP6P1750100LMKP6P1800100LMKP6P11000100LMKP6P11200100LMKP6P11500100LMKP6P12000100LMKP6P12500100LMKP6P13000100LMKP6P11500120LMKP6P12000120LMKP6P12500120LMKP6P13000120LMKP6P14000120LMKP6P15000120
Model Current ratio(A)
Rated Load(VA)
Bar Diameter(mm) (mm)
Number of Turnsthrough the core Reference
30 1030 1030 1040 1040 1040 1040 1040 1050 1050 1050 1050 1050 1050 1050 1060 2060 2060 2060 2060 2060 2060 2060 2060 2080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 3080 10 or 60 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30100 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30120 10 or 80 30
Delixi Electric76
RT16 FuseStandard: IEC 60269
Function
Description
RT16 fuse provide: Protection of circuits against overload current Protection of circuits against short-circuit current
Technical Data Rate current range:2-630A Rate voltage:500/660V Rate breaking capacity:120KA(500V),50KA(660V)
Standard and certification IEC60269 CE
Overall dimensions
abcdeABC1C2DEFG
78.52957496301206185100257.5
13548626765820083961752510.530
150587267664250991122002510.530
1506785676642501051202102510.530
Type RT16-00 RT16-1 RT16-2 RT16-3
Delixi Electric 77
RT16 FuseStandard: IEC 60269
24681012162025324050638010012516080100125160200250125160200250300315355400315355400450500630
Ordering information
RT16002RT16004RT16006RT16008RT160010RT160012RT160016RT160020RT160025RT160032RT160040RT160050RT160063RT160080RT1600100RT1600125RT1600160RT16180RT161100RT161125RT161160RT161200RT161250RT162125RT162160RT162200RT162250RT162300RT162315RT162355RT162400RT163315RT163355RT163400RT163450RT163500RT163630
ReferenceFuse-link Rate current In(A) Suitable fuse bases Weight(g)
RT16-00
RT16-1
RT16-2
RT16-3
170
450
660
850
ReferenceFuse Base Rate current In(A) Material Weight(g)
RT16-00
RT16-1
RT16-2
RT16-3
CeramicResinCeramicResinCeramicResinCeramicResin
RT1600ZTRT1600ZSRT161ZTRT161ZSRT162ZTRT162ZSRT163ZTRT163ZS
RT16-00
RT16-1
RT16-2
RT16-3
160
250
400
630
200
700
1150
1280
Delixi Electric78
RT18 FuseStandard: IEC 60269
RT18 fuse provide: Protection of circuits against overload current Protection of circuits against short-circuit current
Function
Description Technical Data Rate current range:2-63A Rate voltage:380V Rate breaking capacity:100KA
Standard and certification IEC60269 CE
Overall dimensions
RT18-32RT18-63
10 3814 51
10.513.8
38 0.651 +0.6
-1.0
10.3 0.114.3 0.1
Type Size L C Hmax
RT18-32RT18-63
Type A B C D E F G6378
6076
79103
3535
80110
1825
5475
Cylindrical Fuse
Holder of fuse
Delixi Electric 79
RT18 FuseStandard: IEC 60269
ReferenceCylindrical Fuse Rate current In(A) Weight(g)
ReferenceHolder of fuse Rate current In(A) Weight(g)Pole Note
24681012162025322468101216202532405063
1P2P3P1P2P3P1P2P3P1P2P3P1P2P3P1P2P3P
RT10382RT10384RT10386RT10388RT103810RT103812RT103816RT103820RT103825RT103832RT14512RT14514RT14516RT14518RT145110RT145112RT145116RT145120RT145125RT145132RT145140RT145150RT145163
RT18-32
RT18-63
8
20
Material:ResinPilotlamp
Material:ResinNot Pilotlamp
Material:NylonPilotlamp
Material:NylonNot Pilotlamp
Material:ResinNot Pilotlamp
Material:ResinPilotlamp
RT1832ZXBRT1832Z2XBRT1832Z3XBRT1832ZBRT1832Z2BRT1832Z3BRT1832ZXRT1832Z2XRT1832Z3XRT1832ZRT1832Z2RT1832Z3RT1863ZXBRT1863Z2XBRT1863Z3XBRT1863ZBRT1863Z2BRT1863Z3B
RT18-32X
RT18-32
RT18-32X
RT18-32
RT18-63X
RT18-63
32
32
32
32
63
63
82
82
82
82
206
206
Delixi Electric80
JXF Power Distribution BoxStandard: IEC 670.1989, IEC 60439-1
Function
Description
JXF power distribution box provide: Control,monitoring,measurement and protectionfor the electric power lines and the main power control equipment
Technical Data Rated operating voltage:220V,380V Rated insulated voltage:400V,660V Rated operating current:400A Protection rating:IP30 for complete set,IP43 for box Instantaneous withstand current:6KA,15KA
Standard and certification IE670.1989,IEC60439-1
Overall dimensions
cover plate
sealing strip
sealing strip
handle lock
hingedoor
boxpeg board
Delixi Electric 81
JXF252014JXF302514JXF302518JXF303014JXF303018JXF403014JXF403020JXF504014JXF504020JXF504025JXF604014JXF604020JXF604025JXF605014JXF605020JXF605025JXF705016JXF705020JXF705025JXF806020JXF806025JXF1008020JXF1008025JXF1008030
JXF Power Distribution BoxStandard: IEC 670.1989, IEC 60439-1
Reference
JXF-2520/14JXF-3025/14JXF-3025/18JXF-3030/14JXF-3030/18JXF-4030/14JXF-4030/20JXF-5040/14JXF-5040/20JXF-5040/25JXF-6040/14JXF-6040/20JXF-6040/25JXF-6050/14JXF-6050/20JXF-6050/25JXF-7050/16JXF-7050/20JXF-7050/25JXF-8060/20JXF-8060/25JXF-10080/20JXF-10080/25JXF-10080/30
1.01.01.01.01.01.01.01.01.01.01.21.21.21.21.21.21.21.21.21.51.51.51.51.5
250300300300300400400500500500600600600600600600700700700800800100010001000
200250250300300300300400400400400400400500500500500500500600600800800800
140140180140180140200140200250140200250140200250160200250200250200250300
290340340340340440440540540540640640640640640640740740740840840104010401040
150200200250250250250350350350350350350450450450450450450550550750750750
170220220220220320320420420420520520520520520520620620620720720920920920
158208208258258258258358358358358358358458458458458458458558558758758758
111111112222222222222222
Type
Thicknessof ironcharge
Figuredimension
Istallationdimension
Botoomboard Number
of lock
Dimension
H W D H1 B1 H6 B6
Delixi Electric82
Function LD11 Series of indicator light provide:Pilot signal, anticipating signalsEmergency signals and other instructions incidents signal use
Description Technical dataRated voltage(V)
Rated current(mA)Working life(H)Brightness of light(cd/m2)Power frequency withstand voltageDegree of protection
LD11 Series of indicator lightStandard: IEC 60947-5-1
AC/DC6 12 24 36 48 110 220
5030000
402500V AC 1minIP65
Standard and certificationIEC 60947-5-1CE
AC220 380
20
Delixi Electric 83
LD11 Series of indicator lightStandard: IEC 60947-5-1
Button colour Rated voltageAC.DC 6V
AC.DC 12V
AC.DC 24V
AC.DC 110V
AC.DC 220V
AC 220V
AC 380V
AC.DC 6V
AC.DC 12V
AC.DC 24V
ReferenceLD1122A21T7LD1122A21T3LD1122A21T4LD1122A21T5LD1122A21T8LD1122A21J7LD1122A21J3LD1122A21J4LD1122A21J5LD1122A21J8LD1122A21B7LD1122A21B3LD1122A21B4LD1122A21B5LD1122A21B8LD1122A21F7LD1122A21F3LD1122A21F4LD1122A21F5LD1122A21F8LD1122A21M7LD1122A21M3LD1122A21M4LD1122A21M5LD1122A21M8LD1122A41M7LD1122A41M3LD1122A41M4LD1122A41M5LD1122A41M8LD1122A41Q7LD1122A41Q3LD1122A41Q4LD1122A41Q5LD1122A41Q8LD1122B21T7LD1122B21T3LD1122B21T4LD1122B21T5LD1122B21T8LD1122B21J7LD1122B21J3LD1122B21J4LD1122B21J5LD1122B21J8LD1122B21B7LD1122B21B3LD1122B21B4
Overall dimensions Unit:mm
Delixi Electric84
Button colour Rated voltageAC.DC 24V
AC.DC 110V
AC.DC 220V
AC 220V
AC 380V
AC.DC 6V
AC.DC 12V
AC.DC 24V
AC 220V
AC 380V
ReferenceLD1122B21B5LD1122B21B8LD1122B21F7LD1122B21F3LD1122B21F4LD1122B21F5LD1122B21F8LD1122B21M7LD1122B21M3LD1122B21M4LD1122B21M5LD1122B21M8LD1122B41M7LD1122B41M3LD1122B41M4LD1122B41M5LD1122B41M8LD1122B41Q7LD1122B41Q3LD1122B41Q4LD1122B41Q5LD1122B41Q8LD1122C21T7LD1122C21T3LD1122C21T4LD1122C21T5LD1122C21T8LD1122C21J7LD1122C21J3LD1122C21J4LD1122C21J5LD1122C21J8LD1122C21B7LD1122C21B3LD1122C21B4LD1122C21B5LD1122C21B8LD1122C41M7LD1122C41M3LD1122C41M4LD1122C41M5LD1122C41M8LD1122C41Q7LD1122C41Q3LD1122C41Q4LD1122C41Q5LD1122C41Q8
Overall dimensions Unit:mm
LD11 Series of indicator lightStandard: IEC 60947-5-1
Delixi Electric 85
LD11 Series of indicator lightStandard: IEC 60947-5-1
Button colour Rated voltageAC.DC 6V
AC.DC 12V
AC.DC 24V
AC 220V
AC 380V
ReferenceLD1122D21T7LD1122D21T3LD1122D21T4LD1122D21T5LD1122D21T8LD1122D21J7LD1122D21J3LD1122D21J4LD1122D21J5LD1122D21J8LD1122D21B7LD1122D21B3LD1122D21B4LD1122D21B5LD1122D21B8LD1122D41M7LD1122D41M3LD1122D41M4LD1122D41M5LD1122D41M8LD1122D41Q7LD1122D41Q3LD1122D41Q4LD1122D41Q5LD1122D41Q8
Overall dimensions Unit:mm
Delixi Electric86
Function LAY3 Serie of Pushbuttons: Control and signal chain
Description Technical dataConventional thermal current(A)AC-15 Rated operational voltage(V)
Rated operational current(A)DC-13 Rated operational voltage(V)
Rated operational current(A)Degree of protectionDegree of pollutionType of installationAltitudeAmbient air temperature
LAY3 Serie of pushbuttons
10660 380 2201.5 2.5 4.5440 220 1100.1 0.3 0.6IP553
2000m-5 ~+40
Standard and certificationIEC 60947-5-1
Standard: IEC 60947-5-1
Delixi Electric 87
LAY3 Serie of pushbuttons
Button colour Contact blooks1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC
1NO+1NC1NO+1NC1NO+1NC
1NO+1NC1NO+1NC1NO+1NC
1NO+1NC1NO+1NC1NC
1NO+1NC1NO+1NC1NO+1NC
1NO+1NC1NO+1NC1NO+1NC
1NO+1NC1NO+1NC1NO+1NC
1NO+1NC1NO+1NC1NO+1NC
NoteMomentary(Non-illuminated)
Two-positionMaintained
Three-positionMaintained
Maintained
Incandescent lampAC DC 6V
LED AC DC 6V
NEON AC 220V
NEON AC 380V
Overall dimensions Unit:mm
Standard: IEC 60947-5-1
Flush ButtonReferenceLAY311BN4LAY311BN3LAY311BN2LAY311BN5LAY311BN6LAY311BN1
LAY311X204LAY311X203LAY311X202
LAY311X304LAY311X303LAY311X302
LAY311ZS14LAY311ZS13LAY301ZS14
LAY311D4TLAY311D3TLAY311D4T
LAY311D4TLLAY311D3TLLAY311D5TL
LAY311D4MNLAY311D3MNLAY311D5MN
LAY311D4QNLAY311D3QNLAY311D5QN
Selector Switche-Short Handle
Emergency Stop Pushbutton
Flush Buttons Illuminated
LAY3 general
LAY3-X/2 Selector Swiches
LAY3-X/3 Selector Swiches
LAY3-ZS/1 Maintained
LAY3-D Illuminated
Delixi Electric88
Function LAY7 Serie of Pushbuttons: Control and signal chain
Description Technical dataConventional thermal current(A)AC-15 Rated operational voltage(V)
Rated operational current(A)DC-13 Rated operational voltage(V)
Rated operational current(A)Degree of protectionDegree of pollutionType of installationAltitudeAmbient air temperature
LAY7 Serie of pushbuttons
10660 380 2201.1 2.0 3.3440 220 1100.25 0.5 1IP553
2000m-5 ~+40
Standard and certificationIEC 60947-5-1
CE
Standard: IEC 60947-5-1
Overall dimensions Unit:mm
Type
Flush Button MomentaryExtended Button MomentaryWhole protection cover buttonFlush Buttons IlluminatedMushroom Pushbutton IlluminatedMushroom Pushbutton Non-illuminatedFlush Button MaintainedExtended Button MaintainedMushroom Pushbutton MaintainedFlush Button Maintained IlluminatedEmergency Stop PushbuttonSelector Swiches-Short HandleSelector Swiches-Long HandleKey-operated Selector Swiches
22, 25, 30A
1420202224.524.5142024.52224.5262640
B1-2 block50
66
48
6648
3-4 block70
86
68
8648
Note: long 37mm, wide A 30mm B 42mm, in the table values is max.
Delixi Electric 89
LAY7 Serie of pushbuttonsStandard: IEC 60947-5-1
Button colour Contact blooks1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC
1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC
1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC
NoteMomentary(Non-illuminated)
Maintained(Non-illuminated)
Momentary(Non-illuminated)
Maintained(Non-illuminated)
Flush ButtonReferenceLAY711BN12LAY711BN22LAY711BN32LAY711BN42LAY711BN52LAY711BN62LAY711BNZS12LAY711BNZS22LAY711BNZS32LAY711BNZS42LAY711BNZS52LAY711BNZS62
LAY711GN12LAY711GN22LAY711GN32LAY711GN42LAY711GN52LAY711GN62LAY711GNZS12LAY711GNZS22LAY711GNZS32LAY711GNZS42LAY711GNZS52LAY711GNZS62
LAY711JN12LAY711JN22LAY711JN32LAY711JN42LAY711JN52LAY711JN62
Extended Button
Whole protection cover button
Delixi Electric90
LAY7 Serie of pushbuttonsStandard: IEC 60947-5-1
Button colour Contact blooks1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC2NO2NO2NO1NO+1NC1NO+1NC1NO+1NC2NO
1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC2NO2NO2NO1NO+1NC1NO+1NC1NO+1NC2NO
1NO+1NC1NO+1NC2NO1NO+1NC1NO+1NC1NO+1NC2NO
1NO+1NC1NO+1NC1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NC
NoteTwo-position Maintained
Three-position Maintained
Two-position Right MomentaryThree-position Right MomentaryThree-position Right and left MomentaryThree-position Right and left Momentary
Two-position Maintained
Three-position Maintained
Two-position Right MomentaryThree-position Right MomentaryThree-position Right and left MomentaryThree-position Right and left Momentary
Two-position MaintainedThree-position MaintainedThree-position MaintainedTwo-position Right MomentaryThree-position Right MomentaryThree-position Right and left MomentaryThree-position Right and left Momentary
Momentary(Non-illuminated)
Momentary(illuminated LED 6V)
Maintained(Non-illuminated)
Selector Switche-Short HandleReferenceLAY711X2022LAY711X2032LAY711X2042LAY711X3022LAY711X3032LAY711X3042LAY720X3022LAY720X3032LAY720X3042LAY711X2122LAY711X3122LAY711X3322LAY720X3322
LAY711XB2022LAY711XB2032LAY711XB2042LAY711XB3022LAY711XB3032LAY711XB3042LAY720XB3022LAY720XB3032LAY720XB3042LAY711XB2122LAY711XB3122LAY711XB3322LAY720XB3322
LAY711Y2002LAY711Y3002LAY720Y3002LAY711Y2102LAY711Y3102LAY711Y3302LAY720Y3302
LAY711M32LAY711M42LAY701M42LAY711DM3T2LLAY711DM4T2LLAY711DM5T2LLAY711MZS32LAY711MZS42LAY701MZS42
Selector Switche-Long Handle
Key-operated Selector Swiche
Mushroom Pushbutton
Delixi Electric 91
LAY7 Serie of pushbuttonsStandard: IEC 60947-5-1
Button colour Contact blooks1NO+1NC1NO+1NC1NO
1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC
Note
Momentary LED 6V
Momentary LED 24V
Momentary LED 220V
Momentary NEON 220V
Momentary NEON 380V
Maintained LED 6V
Maintained LED 24V
Emergency Stop PushbuttonReferenceLAY711ZS32LAY711ZS42LAY710ZS42
LAY711D7T2LLAY711D3T2LLAY711D4T2LLAY711D5T2LLAY711D8T2LLAY711D7B2LLAY711D3B2LLAY711D4B2LLAY711D5B2LLAY711D8B2LLAY711D7M2LLAY711D3M2LLAY711D4M2LLAY711D5M2LLAY711D8M2LLAY711D1M2NLAY711D3M2NLAY711D4M2NLAY711D5M2NLAY711D6M2NLAY711D1Q2NLAY711D3Q2NLAY711D4Q2NLAY711D5Q2NLAY711D6Q2NLAY711DZS7T2LLAY711DZS3T2LLAY711DZS4T2LLAY711DZS5T2LLAY711DZS8T2LLAY711DZS7B2LLAY711DZS3B2LLAY711DZS4B2LLAY711DZS5B2LLAY711DZS8B2L
Flush Buttons Illuminated
Delixi Electric92
LAY7 Serie of pushbuttonsStandard: IEC 60947-5-1
Button colour Contact blooks1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC
NoteMaintained LED 220V
Maintained NEON 220V
Maintained NEON 380V
Flush Buttons IlluminatedReferenceLAY711DZS7M2LLAY711DZS3M2LLAY711DZS4M2LLAY711DZS5M2LLAY711DZS8M2LLAY711DZS1M2NLAY711DZS3M2NLAY711DZS4M2NLAY711DZS5M2NLAY711DZS6M2NLAY711DZS1Q2NLAY711DZS3Q2NLAY711DZS4Q2NLAY711DZS5Q2NLAY711DZS6Q2N
Delixi Electric 93
Function LAY8 Serie of Pushbuttons: Control and signal chain
Description
LAY8 Serie of pushbuttonsStandard: IEC 60947-5-1
Standard and certificationIEC 60947-5-1CE
Technical dataConventional thermal current(A)AC-15 Rated operational voltage(V)
Rated operational current(A)DC-13 Rated operational voltage(V)
Rated operational current(A)Degree of protectionDegree of pollutionType of installationAltitudeAmbient air temperature
10660 380 2201.5 2.5 4.5440 220 1100.2 0.4 0.8IP553
2000m-5 ~+40
Delixi Electric94
Button colour Contact blooks1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC
1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC
1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC
1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC2NO1NO+1NC1NO+1NC2NO
1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC2NO1NO+1NC1NO+1NC2NO
NoteMomentary(Non-illuminated)
Maintained(Non-illuminated)
Waterproof(Non-illuminated)
Two-position Maintained
Three-position Maintained
Two-position Right MomentaryThree-position Right MomentaryThree-position Right and left Momentary
Two-position Maintained
Three-position Maintained
Momentary(Non-illuminated)Three-position Right MomentaryThree-position Right and left Momentary
Overall dimensions Unit:mm
Flush ButtonReferenceLAY811BN1LAY811BN2LAY811BN3LAY811BN4LAY811BN5LAY811BN6
LAY811ZS1LAY811ZS2LAY811ZS3LAY811ZS4LAY811ZS5LAY811ZS6
LAY811S1LAY811S2LAY811S3LAY811S4LAY811S5LAY811S6
LAY811X202LAY811X203LAY811X204LAY811X302LAY811X303LAY811X304LAY820X302LAY811X312LAY811X212LAY820X312
LAY811XB202LAY811XB203LAY811XB204LAY811XB302LAY811XB303LAY811XB304LAY820XB302LAY811XB212LAY811XB312LAY820XB332
Selector Switche-Short Handle
Selector Switche-Long Handle
LAY8 Serie of pushbuttonsStandard: IEC 60947-5-1
Delixi Electric 95
Button colour Contact blooks1NO+1NC1NO+1NC
1NO+1NC1NO+1NC1NO
1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC1NO+1NC
Note
LED AC.DC 6V
LED AC.DC 24V
LED AC.DC 220V
LED AC 220V
LED AC 380V
Overall dimensions Unit:mm
Mushroom PushbuttonReferenceLAY811M3LAY811M4
LAY811ZS3LAY811ZS4LAY810ZS4
LAY811D7T2LLAY811D3T2LLAY811D4T2LLAY811D5T2LLAY811D8T2LLAY811D7B2LLAY811D3B2LLAY811D4B2LLAY811D5B2LLAY811D8B2LLAY811D7M2LLAY811D3M2LLAY811D4M2LLAY811D5M2LLAY811D8M2LLAY811D7M4LLAY811D3M4LLAY811D4M4LLAY811D5M4LLAY811D8M4LLAY811D7Q4LLAY811D3Q4LLAY811D4Q4LLAY811D5Q4LLAY811D8Q4L
Flush Buttons Illuminated
LAY8 Serie of pushbuttonsStandard: IEC 60947-5-1
Emergency Stop Pushbutton
Delixi Electric96
Overall dimensions
Standard and certificationIEC 51-1~9
CE
72 Series Pannel Meter
Function
DescriptionPressure testVoltage:2000VFrequency:50Hz
Duration:1min
Tolerance mechanical impact:max 147m/s2
Response time: 4sPointer deflection angle:90
72 series pannel meter provide:
Standard: IEC 51-1~9
Unit:mm
Measuring current,voltageMeasuring frequency,power,power factor
Delixi Electric 97
30/5A40/5A50/5A60/5A75/5A80/5A100/5A150/5A160/5A200/5A250/5A300/5A400/5A600/5A800/5A1000/5A1600/5A5000/5A10000/5A 5A
15A20A25A30A40A50A60A80A100A5A300V500V600V500V45-55HZ (200V)
Standard: IEC 51-1~9
72 Series Pannel Meter
Ordering information
72 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.5
72 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.572 72 67.5
72TA3072TA4072TA5072TA6072TA7572TA8072TA10072TA15072TA16072TA20072TA25072TA30072TA40072TA60072TA80072TA100072TA160072TA500072TA1000072TA5A
72TA15A72TA20A72TA25A72TA30A72TA40A72TA50A72TA60A72TA80A72TA100A72C1A5A72TV30072TV50072TV60072C1V50072TZ200
AC TypeExternal connectiontransformer2 times of currentoverload
AC TypeDirect connectionAC TypeDirect connection2 times of currentoverload
DC TypeAC Type
DC TypeAC Type
Ammeter
Voltmerer
Frequency meter
Type Accuracy Specification Note Shape(mm) Reference rating
9
1.5
2.5
1.51.5
1.0
Delixi Electric98
Overall dimensions
96 Series Pannel Meter
Function
DescriptionPressure testVoltage:2000VFrequency:50Hz
Duration:1min
Tolerance mechanical impact:max 147m/s2
Response time: 4sPointer deflection angle:90
96 series pannel meter provide:
Standard: IEC 51-1~9
Standard and certification IEC 51-1~9
CE
Unit:mm
Measuring current,voltageMeasuring frequency,power,power factor
Delixi Electric 99
96 Series Pannel MeterStandard: IEC 51-1~9
96 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.5
96 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.596 96 67.5
96TA3096TA4096TA5096TA6096TA7596TA8096TA10096TA15096TA16096TA20096TA25096TA30096TA40096TA60096TA80096TA100096TA160096TA500096TA1000096TA5A
96TA15A96TA20A96TA25A96TA30A96TA40A96TA50A96TA60A96TA80A96TA100A96C1A5A96TV30096TV50096TV60096C1V50096TZ200
30/5A40/5A50/5A60/5A75/5A80/5A100/5A150/5A160/5A200/5A250/5A300/5A400/5A600/5A800/5A1000/5A1600/5A5000/5A10000/5A 5A
15A20A25A30A40A50A60A80A100A5A300V500V600V500V45-55HZ (200V)
Ordering information
AC TypeExternal connectiontransformer
AC TypeDirect connectionAC TypeDirect connection
DC TypeAC Type
DC TypeAC Type
Ammeter
Voltmerer
Frequency meter
Type Accuracy Specification Note Shape(mm) Reference rating
1.5
2.5
1.51.5
1.0
Delixi Electric100
TND Voltage Stabilizer
Function
Description Technical Data
TND voltage stabilizer provide: Control system consist of linear integrated circuit automaticly control voltage regulation Timelag, overvoltage and undervoltage protection
Overall dimensions
Type
Output voltage
PhaseInput voltage rangeEfficiencyVoltage regulation speedTemperature riseFrequencyEnviroment temperature,relative temperatureWaveform distortionRated maximum output current(A)
TND0.5kVA~5kVA TND7kVA~30kVA220 4%,110 4% 220 4%184V 4V(set up according to the customers request)246V 4Vsingle-phase160V~240V>90%<1s(when input voltage change 10%)<60 (full range)50Hz/60Hz -50 ~40 below 90%no additional distortion2(500VA),4(1000VA),6(1500VA),8(2000VA),12(3000VA),20(5000VA),25(7000VA),40(10KVA),85(15KVA),73(20KVA),109(30KVA)
Voltage regulation accuracyUndervoltage protectionOvervoltage protection
TND-0.5TND-1TND-1.5TND-2TND-3TND-5TND-7TND-10TND-10TND-15TND-20TND30
Desktop
Cabinet type
Product shape Model Wide Length Hight
190 160 135205 190 155205 190 155240 270 200225 305 235225 310 290240 387 360240 387 360310 340 535340 360 640340 380 780425 390 845
unit: mm
Withstand voltage 1500V/1min
Delixi Electric 101
TND Voltage Stabilizer
Ordering information
Desktop
Cabinet type
Product shape Power rating Referencce
0.5K1K1.5K2K3K5K7K10K
10K15K20K30K
TNDP5TND1TND1P5TND2TND3TND5TND7TND10
TND10GTND15GTND20GTND30G
Delixi Electric102
2.4"3.2"4"4.7"6"12"4.7"6"7.1"8"10"12"14.6"7.1"8"10"12"14"15"16"17.7"19.7"8"10"12"14"16"20"30"18"20"21.6"27.5"32"2.4"3.2"4"4.7"6"8"4.7"6"
60801001201502001201501802002503003701802002503003503804004505002002503003504005007504505005507008006080100120150200120150
2.52.52.52.52.52.53.63.63.63.63.63.63.64.84.84.84.84.84.84.84.84.87.27.27.27.27.27.27.2999992.22.22.22.22.22.23.23.2
2-112-162-222-302-353-802-302-353-423-503-653-803-803-423-503-653-803-903-1023-1053-1303-1503-503-654-804-904-1054-15010-2208-1188-1508-16010-20510-2302-112-162-222-302-353-503-303-35
181818181818404040404040405050505050505050501201201201201201201201751751751751751818181818184040
888888181818181818182222222222222222225555555555555580808080808888881818
100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100100
DAR205060**DAR205080**DAR205100**DAR205120**DAR205150**DAR205200**DAR306120**DAR306150**DAR306180**DAR306200**DAR306250**DAR306300**DAR306370**DAR408180**DAR408200**DAR408250**DAR408300**DAR408350**DAR408380**DAR408400**DAR408450**DAR408500**DAR702200**DAR702250**DAR702300**DAR702350**DAR702400**DAR702500**DAR702750**DAR900450**DAR900500**DAR900550**DAR900700**DAR900800**DAR202060**DAR202080**DAR202100**DAR202120**DAR202150**DAR202200**DAR302120**DAR302150**
Nylon Cable Ties Series
Description Technical Data
Overall dimensions
Material: Using nylon 66 material that recognized by ULFire-protection rating:94V-2Acid and erosion control,insulate well and difficult to aging
Color: White, black and other colors
LBS KGSLong
INCH MMWidth MAX.Bundle
DIA(mm)Tensile Strength Packing
(root)Reference
Delixi Electric 103
Nylon Cable Ties Series
LBS KGSLong
INCH MMWidth MAX.Bundle
DIA(mm)Tensile Strength Packing
(root) Reference
7"8"10"12"14"4.7"6"7.1"8"10"12"14"16"8"10"12"14"16"17.7"19.7"21.6"24"
180200250300350120150180200250300350400200250300350400450500550600
3.23.23.23.23.24.24.24.24.24.24.24.24.26.56.56.56.56.56.56.56.56.5
3-423-503-653-803-903-303-353-423-503-653-803-903-1053-503-654-804-904-1053-1304-1504-1654-170
40404040405050505050505050120120120120120120120120120
18181818182222222222222222555555555555555555
100100100100100100100100100100100100100100100100100100100100100100
DAR302180DAR302200DAR302250DAR302300DAR302350DAR402120DAR402150DAR402180DAR402200DAR402250DAR402300DAR402350DAR402400DAR605200DAR605250DAR605300DAR605350DAR605400DAR605450DAR605500DAR605550DAR605600
Note:" " express color and packing code
Normal PackingHang tag Packing
BBBL
WBWL
UBUL
RBRL
YBYL
GBGL
Normal Packing
Hang tag Packing
Color Black White Blue Red Yellow Green
Building Industry Energy
CDW7
CDM1
CDM1
CDC17
CDR17CDM1L
CDB6a CDB6LECDPZ50 CDY1 DDS607
Power Distribution and Industry Control Product
JXF
LMK LAY3 72
Residential